Island bus expansion module

Size: px
Start display at page:

Download "Island bus expansion module"

Transcription

1 s P01 TX-I/O Island bus expansion TXA1.IBE Expand island bus to a distance of up to 2 x 200 meters Compact design per DIN , requires little space Easy installation and setup Mounted on standard rails Self-connecting bus (island bus) for the easiest possible installation Plug-in screw terminals for island bus expansion No programming / parameterization tool required CM2N8184en_03 15 Jul 2010 Building Technologies

2 Function The island bus expansion s allow for decentralized sub-islands with TX-I/O-s, that may be located up to 2 x 200 m from the "local" sub-island. A programming / parameterization tool is not required. The DIP switches for the bus master and bus terminator must be set correctly on the island bus expansion s. The island bus expansion is based on differential RS-485 transmission technology. "Decentralized" sub-island can be supplied using a separate power supply. Loss of this power does not impact the island bus of local sub-islands. For details on wiring and topology, refer to TX-I/O engineering and installation manual, CM Type summary Island bus expansion TXA1.IBE Ordering When ordering, please specify the quantity, product name, and type code. Example: 10 Island bus expansion s TXA1.IBE Equipment combinations Compatibility Full functionality is only possible using TX-I/O s from series C and higher P-bus interface s series B and higher PXC-NRUD Series C and higher only (Migration INTEGRAL AS1000) All models of PROFINET BIM Functionality is reduced when using s for series B and BIM series A: refer to CM System restrictions Number of decentralized sub-islands per I/O island Max. 8 Number of island bus expansion s per Exactly 1 decentralized sub-island Number of I/O s per I/O island Maximum of 64 Number of I/O s per sub-island No limit, as long as the total of the entire island (64) is maintained. See TX-I/O engineering and installation manual, CM for more details. 2 / 10

3 Design and technology Overview COM Attachment slider for standard rails DIP switch *) for bus master (island bus) LED "COM", displays island bus communication Bus connector right Bus connector left TXA1.IBE DIP switch *) for bus terminal (island bus expansion) + 1 _ Z01 Plug-in screw terminals + Signal island bus expansion Signal island bus expansion equipotential bonding *) DIP switch: Both "" switches must have the same position. The same applies to "" switches. For details on wiring and topology, refer to TX-I/O engineering and installation manual, CM Mechanical properties The housing complies with DIN and is 32mm wide. The island bus expansion is plugged on the right side of the power / bus connection on the standard rail. The electrical connection is on the 4 side island bus contacts. The bus establishes its own connection, when TX-I/O devices are plugged into one another on the rails. Electrical properties Interfaces Island bus expansion: Plug-in screw terminals Island bus: Bus connector on the right and left side of the. System ground Protection against incorrect wiring Island bus and island bus expansion are galvanically connected All terminals are protected against short circuit and incorrect wiring using AC/DC 24 V. This applies as well to reverse phase voltage AC 24 V Side bus connector: No protection Signaling LED COM (yellow) The LED indicates bus traffic on the island bus: Both directions OK: irregular blinking Bus short circuit: bright 3 / 10

4 Schematic Island bus CD 24V~ CD 24V~ 1 Island Bus 2 RS PTC _ + Island bus expansion 8184Z02 Engineering, topology Please consult the following document: TX-I/O engineering and installation manual, CM Mounting Fixings Order Exchange Permissible mounting positions The device is mounted on a standard rail 35 x 7.5 mm (tophat rails TH per EN60715) In an I/O row, an island bus expansion is placed immediately to the right of the power supply, bus connection or bus interface. Dee also the connection examples on pages 7 and 8. An island bus expansion may be removed from the row. The electronic component from the neighboring right must, however, be removed. Its terminal block may remain. TX-I/O devices can be mounted in any position: horizontally, vertically, on a horizontal surface. You must ensure, however, that sufficient ventilation is available to maintain the permissible ambient temperature (max. 50 C). Disposal The device is classified as waste electronic equipment in terms of the European Directive 2002/96/EC (WEEE) and should not be disposed of as unsorted municipal waste. The relevant national legal rules are to be adhered to. Regarding disposal, use the systems setup for collecting electronic waste. Observe all local and applicable laws. 4 / 10

5 Technical data Supply (bus connector on side) Operating voltage range SELV / PELV DC V Max. power consumption 1.2W (for the sizing of power supplies, see CM110562) Maximum distances (only with TX-I/O s series C and higher; only with BIM Series B and higher) Number of supported s Island bus expansion Island bus inside of a sub-island (depending on cross section and current load for details, refer to TX-I/O engineering and installation manual, CM110562) Bus expansion s per I/O island I/O s per I/O island Max. 2 x 200 m Max. 50 m with round cable Max. 100 m with RG-62 Max. 9 s Max. 64 s Island bus communication Island bus traffic display LED "COM" Bus master function 2 DIP switches = Bus terminator function (terminator) 2 DIP switches = Galvanic isolation Island bus and island bus expansion are galvanically connected via PTC (Conductors and ). Short-circuit protection Side bus connector No protection! and incorrect wiring Terminal See below Cabling For details on cabling for RS485 and wiring rules, refer to TX-I/O engineering and installation manual, CM Connection terminals, plug-in, for island bus expansion Mechanical design Copper wire Copper stranded wires with ferrules Copper stranded wires without ferrules Screwdriver Maximum stud torque Plug-in screw terminal 1 x 0.6 mm to 2.5mm 2 or 2 x 0.6 mm to 1.0 mm 2 1 x 0.6 mm to 2.5mm 2 or 2 x 0.6 mm to 1.0 mm 2 1 x 0.6 mm to 2.5 mm 2 or 2 x 0.6 mm to 1.5 mm 2 Flat screwdriver size 1 with shaft ø 4.5 mm 0.6 Nm Classification per EN Function of automatic control devices Degree of pollution Mechanical design Housing type IP class per EN Front parts in DIN excerpt terminal part Type 1 2 Protection class III IP30 IP20 5 / 10

6 Environmental conditions Standards, directives and approvals Operation Climatic conditions Temperature Humidity Mechanical conditions Transport Climatic conditions Temperature Humidity Mechanical conditions Product standard Automatic electrical controls devices for household and similar use As per IEC Class 3K C 5 95 % r.h. Class 3M2 As per IEC Class 2K C 5 95 % r.h. Class 2M2 EN Electromagnetic compatibility Immunity Residential & industrial EN Emissions Residential & industrial EN CE conformity Electromagnetic compatibility 2004/108/EG c-tick conformity Emissions AS/NZS UL approval UL 916 Environmental compatibility The product environmental declaration CM1E8184 contains data on environmentally compatible product design and assessments (RoHS compliance, materials composition, packaging, environmental benefit, disposal) ISO (Environment) ISO 9001 (Quality) SN (Environmentally compatible products) 2002/95/EC (RoHS directive) Color Housing Light gray, RAL 7035 Dimensions Housing as per DIN 43880, see dimensions Weight Without / with packaging 64 / 84 g 6 / 10

7 Connection examples for automation station with island bus or PROFINET BIM See TX-I/O engineering and installation manual, CM for more details. A) Maximum 2 segments of max. 200 meters each are possible using the island bus expansion s A) Max. 200 m = = Key N1 Automation station with island bus or PROFINET BIM Power supply Island bus expansion TX-I/O s X1 Bus connection N1 = OFF = Bus master function (island bus, both switches in the same position!) Bus terminator function (island bus expansion, both switches in the same position!) Max. 200 m = = OFF = = B) Decentralized subisland without power supply (maximum distance depends on current on conductors and ) B) N1 T = OFF = T X1 = = 8184A01e 7 / 10

8 Connection examples for automation station with P-bus See TX-I/O engineering and installation manual, CM for more details. C) Maximum 2 segments of max. 200 meters each are possible using the island bus expansion s C) Max. 200 m = = Key N2 Automation station with P-bus Power supply Island bus expansion TX-I/O s U4 P-bus interface X1 Bus connection N2 P-Bus U4 = OFF = Bus master function (island bus, both switches in the same position!) Bus terminator function (island bus expansion, both switches in the same position!) Max. 200 m = = OFF = = D) Decentralized subisland without power supply (maximum distance depends on current on conductors and ) D) N2 P-Bus T U4 = OFF = T X1 = = 8184A11b 8 / 10

9 Dimensions Dimensions in mm M01 9 / 10

10 10 / Siemens Switzerland Ltd Subject to change

TX OPEN RS232/485 module

TX OPEN RS232/485 module s 8 185 8185P01 TX-I/O ; DESIGO OPEN TX OPEN RS/485 module for integrating third-party systems and devices to DESIGO (V4 or higher) TXI1.OPEN Platform to integrate third-party systems and devices to the

More information

Digital input modules

Digital input modules 8 172 TX-I/O Digital input modules TXM1.8D TXM1.16D Two fully compatible versions: TXM1.8D: 8 inputs, each with a three-color LED (green, yellow or red) TXM1.16D: As TXM1.8X, but 16 inputs, each with a

More information

BACnet router for BACnet/IP BACnet/LonTalk BACnet MS/TP

BACnet router for BACnet/IP BACnet/LonTalk BACnet MS/TP s 9 270 Desigo PX BACnet router for BACnet/IP BACnet/LonTalk BACnet MS/TP PXG3.L PXG3.M Routing between BACnet/IP, BACnet/LonTalk (PXG3.L only), and BACnet MS/TP Supports BACnet/IPv4 and BACnet/IPv6 ANSI/ASHRAE

More information

SEZ220. Signal Converter. Synco 200. With preprogrammed standard applications Freely programmable Menu-driven operation. Use

SEZ220. Signal Converter. Synco 200. With preprogrammed standard applications Freely programmable Menu-driven operation. Use s 5 146 Synco 200 Signal Converter SEZ220 With preprogrammed standard applications Freely programmable enu-driven operation Use The signal converter is for use in HVAC plant to provide minimum / maximum

More information

For UK only RXL39.1 and the applications package SP-03 are sold in the United Kingdom only.

For UK only RXL39.1 and the applications package SP-03 are sold in the United Kingdom only. s For UK only RX39.1 and the applications package SP-03 are sold in the United Kingdom only. 3 876 3876P01 RX Room controller Communicating controllers for fan-coil applications SP-03 RX39.1 The RX39.1

More information

STEP-PS/1AC/12DC/1.5. Extract from the online catalog. Order No.: 2868567. DIN rail power supply unit 12 V DC/1.5 A, primary switched-mode, 1- phase

STEP-PS/1AC/12DC/1.5. Extract from the online catalog. Order No.: 2868567. DIN rail power supply unit 12 V DC/1.5 A, primary switched-mode, 1- phase Extract from the online catalog STEP-PS/1AC/12DC/1.5 Order No.: 2868567 DIN rail power supply unit 12 V DC/1.5 A, primary switched-mode, 1- phase Commercial data EAN 4046356292924 Pack 1 pcs. Customs tariff

More information

HCR3.2/.. Chipcard reader HOTEL SOLUTION

HCR3.2/.. Chipcard reader HOTEL SOLUTION s 6 332 HOTEL SOLUTION Chipcard reader HCR3.2/.. Chipcard reader for hotel room access control Reads access code on chipcard Transfers access code to room controller Built-in optical display of messages

More information

PCS0100en 02.2008. Persy Control Services B.V. Netherlands

PCS0100en 02.2008. Persy Control Services B.V. Netherlands P-Bus Gateway PBGW2.128 Universal gateway between the P-bus protocol and open standard protocols. The variety of available electrical interfaces on the gateway offers a wide range of possibilities for

More information

QFP910. Water detector. Building Technologies. CE1N2732en. Synco living

QFP910. Water detector. Building Technologies. CE1N2732en. Synco living 2 732 Synco living Water detector QFP910 Wireless radio sensor to record water puddles RF communication based on KNX standard (868 MHz unidirectional) Battery operation with standard 1.5 V batteries Use

More information

RRV934. Multi-controller. Synco living

RRV934. Multi-controller. Synco living s 2 709 Synco living Multi-controller RRV934 RF-based multi-controller For precontrol of up to 2 room groups For control of ventilation plant with up to 3 stages RF communication based on KNX standard

More information

Product and Applications Description. Application Programs. Example of Operation. GAMMA instabus Technical Product-Information.

Product and Applications Description. Application Programs. Example of Operation. GAMMA instabus Technical Product-Information. Product and Applications Description The power supply units N 125/x2 can supply DC 24 V power from an additional pair of terminals (yellowwhite). This DC 24 V output voltage can be used to power e.g. an

More information

PXM20-E. Operator unit DESIGO PX

PXM20-E. Operator unit DESIGO PX 9 234 DESIGO PX Operator unit PXM20-E Network-compatible operator unit for viewing and operating one or more DESIGO PX automation stations. High-grade display with adjustable contrast Simple key operation

More information

Air damper actuators

Air damper actuators 4 634 OpenAir TM Air damper actuators GDB...1 GLB...1 Rotary version, / AC 230 V Electronic motor driven actuators for three-position and modulating control Nominal torque 5 Nm (GDB), 10 Nm (GLB) Mechanically

More information

Differential Pressure Sensors for air and non-corrosive gases, with calibration certificate

Differential Pressure Sensors for air and non-corrosive gases, with calibration certificate 1 919 1919P01 1919P03 QBM65/C, QBM75-1U/C Differential Pressure Sensors for air and non-corrosive gases, with calibration certificate QBM751-1/C QBM65/C QBM75/C Highly accurate measurements with calibration

More information

RDJ10RF/SET. Wireless room temperature controller with 24-hour time switch and LCD. Programmable, for heating systems

RDJ10RF/SET. Wireless room temperature controller with 24-hour time switch and LCD. Programmable, for heating systems 3 072 RDJ10RF RCR10/433 Wireless room temperature controller with 24-hour time switch and LCD Programmable, for heating systems RDJ10RF/SET Operating modes: Automatic, Comfort, Energy Saving, and Frost

More information

AXIS T81B22 DC 30W Midspan

AXIS T81B22 DC 30W Midspan INSTALLATION GUIDE AXIS T81B22 DC 30W Midspan ENGLISH About this Document This document includes instructions for installing AXIS T81B22 on your network. Previous experience of networking will be beneficial

More information

QFP910. Water detector. Building Technologies. CE1N2732en 2016-03-01. Synco living

QFP910. Water detector. Building Technologies. CE1N2732en 2016-03-01. Synco living 2 732 Synco living Water detector QFP910 Wireless radio sensor to record water puddles RF communication based on KNX standard (868 MHz unidirectional) Battery operation with standard 1.5 V batteries Use

More information

RM17TE 183...528 V AC. Main. Product or component type. Product specific application. Relay monitored parameters 250 V DC 5 A DC

RM17TE 183...528 V AC. Main. Product or component type. Product specific application. Relay monitored parameters 250 V DC 5 A DC Characteristics multifunction control relay RM17-TE - range 183..528 V AC Complementary Reset time Maximum switching voltage Minimum switching current Maximum switching current [Us] rated supply voltage

More information

Power Supply Unit, Primary Switched, Narrow Design MINI-PS-12-24DC/24DC/1

Power Supply Unit, Primary Switched, Narrow Design MINI-PS-12-24DC/24DC/1 Power Supply Unit, Primary Switched, Narrow Design MINI POWER provides: Extra narrow design with widths of 22.5 mm, 45 mm, and 67.5 mm (0.886, 1.772, and 2.657 in.) Global use due to a wide-range input

More information

OZS164... Web server. For LPB/BSB plants

OZS164... Web server. For LPB/BSB plants s 5 711 Web server For LPB/BSB plants OZS164... Remotely operate and monitor a LPB or BSB device Web browser operation via PC/laptop or Smartphone SMS operation via mobile phone (OZS164.23) 2 digital inputs

More information

Electronic timer CT-AHD.12 OFF-delayed with 1 c/o (SPDT) contact

Electronic timer CT-AHD.12 OFF-delayed with 1 c/o (SPDT) contact Data sheet Electronic timer CT-AHD.12 OFF-delayed with 1 c/o (SPDT) contact The CT-AHD.12 is an electronic time relay with OFF-delay. It is from the CT-D range. With their MDRC profile and a width of only

More information

VAV compact controller KNX / PL-Link

VAV compact controller KNX / PL-Link s 3 547 OpenAir VAV compact controller KNX / PL-Link Series E GDB181.1E/KN GLB181.1E/KN Networked compact controller featuring KNX (S-mode / LTE-mode) and PL- Link capability for plants with variable air

More information

Duct Humidity Transmitter

Duct Humidity Transmitter SDC-H Duct Humidity Transmitter Features Replaceable sensor element Humidity measurement for air ducts Minimum and maximum value memory 0 0V, 0 0mA or 0V, 4 0mA measuring signals selectable with jumpers

More information

TM7BDM8B expansion block - TM7 - IP67-8 DI/DO - 24V DC - 0.5 A - M8 connector

TM7BDM8B expansion block - TM7 - IP67-8 DI/DO - 24V DC - 0.5 A - M8 connector Product datasheet Characteristics TM7BDM8B expansion block - TM7 - IP67-8 DI/DO - 24V DC - 0.5 A - M8 connector Main Range of product Product or component type Range compatibility Enclosure material Bus

More information

RM35UA13MW. range 15..600 V. Main. Product or component type. Relay monitored parameters

RM35UA13MW. range 15..600 V. Main. Product or component type. Relay monitored parameters Characteristics multifunction voltage control relay RM35-U - range 15..600 V Complementary Reset time Maximum switching voltage [Us] rated supply voltage Supply voltage limits Power consumption in W Main

More information

Product and functional description

Product and functional description Product and functional description The KNX / DALI gateway N 141/02 is a 4 MU wide, DINrail mounted KNX device with one DALI interface to which up to 64 DALI actuators (e.g. DALI ballasts) can be connected

More information

CompactLogix Power Supplies Specifications

CompactLogix Power Supplies Specifications Technical Data CompactLogix Power Supplies Specifications 1768 CompactLogix Power Supplies Catalog Numbers 1768-PA3, 1768-PB3 1769 Compact I/O Power Supplies Catalog Numbers 1769-PA2, 1769-PB2, 1769-PA4,

More information

RISH CON - Hz. Salient Features : Application : Product Features: FREQUENCY TRANSDUCER

RISH CON - Hz. Salient Features : Application : Product Features: FREQUENCY TRANSDUCER Application : The RISH CON - Hz transducer is used for frequency measurement. The output signal is proportional to measured frequency and is either load independent DC Current or load independent DC Voltage.

More information

VAV compact controller KNX / PL-Link

VAV compact controller KNX / PL-Link s 3 547 OpenAir VAV compact controller KNX / PL-Link Series E GDB181.1E/KN GLB181.1E/KN Networked compact controller featuring KNX (S-mode / LTE-mode) and PL- Link capability for plants with variable air

More information

ConneXium Ethernet Switches TCSESU0 F N0 Quick Reference Guide

ConneXium Ethernet Switches TCSESU0 F N0 Quick Reference Guide 31007950 7/2009 ConneXium Ethernet Switches TCSESU0 F N0 Quick Reference Guide 7/2009 31007950.02 www.schneider-electric.com NOTICE Read these instructions carefully, and look at the equipment to become

More information

Current valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw

Current valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw 4 937 DESIO Current valve for AC 24 V pulse/pause control of electrical loads up to 30 kw SEA45.1 Use The current valve is used for the control of electric heating elements in heating, ventilation and

More information

IntesisBox Modbus Server Fidelio IP

IntesisBox Modbus Server Fidelio IP IntesisBox Server Fidelio IP Gateway for integration of Micros Fidelio Ho management system into (RTU and TCP) enabled control systems. Integrate your Micros Fidelio Ho management system into your master

More information

MILLENIUM INSTALLATION MANUAL NTR 735 A. Simple Automation Control Module (MAS)

MILLENIUM INSTALLATION MANUAL NTR 735 A. Simple Automation Control Module (MAS) MILLENIUM Table of contents 1. INTRODUCTION 1 2. HARDWARE DESCRIPTION 2 3. INSTALLATION 5 4. CONNECTION 6 5. USER SAFETY AND PROTECTION OF EQUIPMENT 8 1. Introduction The MILLENIUM series has been designed

More information

HARTING econ 3000 Introduction and features

HARTING econ 3000 Introduction and features HARTING Introduction and features HARTING es, unmanaged, for installation in control cabinets General Description Features The Fast es of the product family HARTING are suitable for industrial applications

More information

OZW772... V2.0. Web server. Synco TM, Synco TM living

OZW772... V2.0. Web server. Synco TM, Synco TM living s 5 701 Web server Synco TM, Synco TM living OZW772... V2.0 The OZW772 web server allows for remote operation and monitoring of plants via the web and send faults and system reports to e-mail recipients.

More information

Redundancy Module QUINT-DIODE/40

Redundancy Module QUINT-DIODE/40 Redundancy Module QUT DIODE provides: 00% decoupling of power supplies connected in parallel Can be installed in potentially explosive areas Load currents up to 60 A supported Easy assembly by snapping

More information

XUSL4E4BB091NS2 XUSL type 4 - Slave2 - For body protection - 4 Beams, Hp = 910 mm

XUSL4E4BB091NS2 XUSL type 4 - Slave2 - For body protection - 4 Beams, Hp = 910 mm Characteristics XUSL type 4 - Slave2 - For body protection - 4 Beams, Hp = 910 mm Complementary Detection system Kit composition [EAA] effective aperture angle Emission Main Range of product Product or

More information

Your Advantages For safety application up to PL e / Cat. 4 e.g. SIL 3 Manual or automatic start 0225592. * see variants. Applications.

Your Advantages For safety application up to PL e / Cat. 4 e.g. SIL 3 Manual or automatic start 0225592. * see variants. Applications. Safety Technique SAFEMASTER Emergency Stop Module BG 5924, IP 5924 Your Advantages For safety application up to PL e / Cat. 4 e.g. SIL 3 Manual or automatic start 0225592 BG 5924 IP 5924 Product Description

More information

NI 9423. NI C Series Overview DATASHEET. 8-Channel Sinking Digital Input Module

NI 9423. NI C Series Overview DATASHEET. 8-Channel Sinking Digital Input Module DATASHEET NI 9423 8-Channel Sinking Digital Input Module 8-channel, 100 µs digital input 24 V logic, sinking digital input Compatible with NI CompactDAQ counters 250 Vrms, CAT II isolation 10-position

More information

Features. Display. Measurements. Intelligent. Accuracy. Models. Installation DEIF A/S. Multi-instrument 4921210109D

Features. Display. Measurements. Intelligent. Accuracy. Models. Installation DEIF A/S. Multi-instrument 4921210109D 7000/7000C/7020 Multi-instrument 4921210109D Features Measurements All 3-phase AC measurements True RMS Replaces analogue meters Demand on each phase current Accuracy U, I and F class 0.5 Other values

More information

Waveguide Access Point WGA631. Product Guide

Waveguide Access Point WGA631. Product Guide Waveguide Access Point Product Guide Waveguide Access Point Contents 1. Description............................ 3 2. Application............................ 3 3. Technical data... 4 4. Physical interfaces......................

More information

Quick Connect. quick - simple - efficient. www.g-mw.de

Quick Connect. quick - simple - efficient. www.g-mw.de Quick Connect quick - simple - efficient www.g-mw.de Phone: +49 9103 7129-0 Fax: +49 9103 7129-207 Innovative connection technology to plug three single-phase current transformers to multifunctional power

More information

Type: EASY719 DC RC Article No.: 274119. Ordering information Relay outputs Quantity 6 Power supply V DC 24 V DC. Description

Type: EASY719 DC RC Article No.: 274119. Ordering information Relay outputs Quantity 6 Power supply V DC 24 V DC. Description Type: EASY719 DC RC Article.: 274119 Ordering information Relay outputs Quantity 6 Power supply V DC 24 V DC Description 12 digital inputs (4 inputs available as analog inputs) 6 relay outputs LCD display

More information

HARTING mcon 3000 Introduction and features

HARTING mcon 3000 Introduction and features Introduction and features HARTING mcon 3000 es, managed, for mounting onto top-hat mounting rail in control cabinets General Description Features The fully managed es of the product family HARTING mcon

More information

OZW30. Central Unit SYNERGYR

OZW30. Central Unit SYNERGYR 2 841 SYNERGYR Central Unit OZW30 Collects billing data from the apartments. Generates an image of each apartment's heat consumption and makes it available for readout. Acts on room temperature control

More information

ABB i-bus KNX Switch Actuator, x-fold, 16 A, MDRC SA/S x.16.2.1, 2CDG1101xxR0011

ABB i-bus KNX Switch Actuator, x-fold, 16 A, MDRC SA/S x.16.2.1, 2CDG1101xxR0011 Technical Data 2CDC505051D0205 ABB i-bus KNX Product description Switch Actuators SA/S x.16.2.1, 16 A are modular installation devices in ProM design for installation in the distribution board. They are

More information

aseries A13B Mini Bullet Camera User Manual

aseries A13B Mini Bullet Camera User Manual aseries A13B Mini Bullet Camera User Manual Thank you for purchasing our product. If there are any questions, or requests, please do not hesitate to contact the dealer. This manual applies to the MicroView

More information

Technical Data. General specifications Switching element function Rated operating distance s n 15 mm

Technical Data. General specifications Switching element function Rated operating distance s n 15 mm 0102 Model Number Features Comfort series 15 mm flush Accessories MHW 01 Modular mounting bracket MH 04-2057B Mounting aid for VariKont and +U1+ Technical Data General specifications Switching element

More information

Automation stations modular series

Automation stations modular series s 9 222 9222P01 DESIGO PX Automation stations modular series PXC...D PXC...-E.D PXA40- Freely programmable modular automation stations for HVAC and building services plants. Native BACnet automation station

More information

IFS SP-PoE Splitter User Manual

IFS SP-PoE Splitter User Manual IFS SP-PoE Splitter User Manual P/N 1069176-EN REV 1.01 ISS 01JUL10 2011 UTC Fire & Security. All rights reserved. Content Overview 2 Package contents 2 Introduction 3 Product Specifications 3 Hardware

More information

IntesisBox KNX - LON

IntesisBox KNX - LON IntesisBox KNX - Gateway for integration of devices into KNX systems. Integrate Air Conditioning from the main manufacturers (DAIKIN, Mitsubishi Electric, Mitsubishi Heavy Industries, Toshiba, Fujitsu,

More information

ISIO 200. Binary Input/Output (I/O) Terminal with IEC 61850 Interface

ISIO 200. Binary Input/Output (I/O) Terminal with IEC 61850 Interface ISIO 200 Binary Input/Output (I/O) Terminal with IEC 61850 Interface Compact and Easy ISIO 200 Put your Binary I/Os where you need them ISIO 200 is a simple and versatile binary I/O terminal with IEC 61850

More information

40.3. Control Relays and Timers

40.3. Control Relays and Timers .3 Contents EASY500/700/800 Intelligent Relays........ EASY/MFD Expansion Modules............ MFD Intelligent Relays................... EASY/MFD Communication Modules....... EASY/MFD Power Supplies, Accessories

More information

How To Write A Librao Low Voltage Differential (Lvds) Module On An Nio 6585 Fuserio (Flexrio) Power Supply (Femaleseo) And Power Supply On An Iphone Or Ip

How To Write A Librao Low Voltage Differential (Lvds) Module On An Nio 6585 Fuserio (Flexrio) Power Supply (Femaleseo) And Power Supply On An Iphone Or Ip NI 6585 Specifications This document lists the specifications of the National Instruments 6585 FlexRIO low-voltage differential (LVDS) adapter module. Pair these specifications with your FPGA module specifications.

More information

IntesisBox KNX Mitsubishi Heavy Industries AC

IntesisBox KNX Mitsubishi Heavy Industries AC IntesisBox KNX Mitsubishi Heavy Industries AC Gateway for integration of Mitsubishi Heavy Indsutries (MHI) Air Conditioners with KNX control systems. 1. Main Features Direct connection to KNX TP-1 (EIB)

More information

Type: DILM115(RAC240) Article No.: 239548 Sales text Contactor,55kW/400V,AC operated. Ordering information

Type: DILM115(RAC240) Article No.: 239548 Sales text Contactor,55kW/400V,AC operated. Ordering information Type: DILM115(RAC240) Article No.: 239548 Sales text Contactor,55kW/400V,AC operated Ordering information Connection technique Description Description Rated operational current Screw terminals 3 pole AC

More information

Three-phase monitoring relay CM-PFE

Three-phase monitoring relay CM-PFE Data sheet Three-phase monitoring relay CM-PFE The CM-PFE is a three-phase monitoring relay that monitors the phase parameter phase sequence and phase failure in three-phase mains. 2CDC 251 005 S0012 Characteristics

More information

Electronic overload relay EF19 and EF45

Electronic overload relay EF19 and EF45 Data sheet Electronic overload relay EF19 and EF45 Electronic overload relays offer reliable protection in case of overload and phase-failure. They are the alternative to thermal overload relays. Motor

More information

ABB i-bus KNX Fan Coil Actuator, MDRC FCA/S 1.1M, 2CDG 110 084 R0011

ABB i-bus KNX Fan Coil Actuator, MDRC FCA/S 1.1M, 2CDG 110 084 R0011 , 2CDG 110 084 R0011 2CDC 071 112 F0008 The Fan Coil Actuator is a modular installation device (MDRC) in pro M design. It is intended for installation in the distribution board on 35 mm mounting rails.

More information

Modular I/O System Analog and Digital Interface Modules

Modular I/O System Analog and Digital Interface Modules OPERATING INSTRUCTIONS Modular I/O System Analog and Digital Interface Modules Installation Operation Maintenance Document Information Document ID Title: Operating Instructions Modular I/O System Part

More information

IntesisBox Modbus Server SAMSUNG Air Conditioners

IntesisBox Modbus Server SAMSUNG Air Conditioners IntesisBox Modbus Server SAMSUNG Air Conditioners Gateway for monitoring and control of Samsung NASA compatible Air Conditioning Systems from any Modbus master device TCP or RTU (BMS, PLC, SCADA, HMI,

More information

FOSTCDR. Industrial Serial to Multimode Fiber Optic Converter PRODUCT INFORMATION B&B ELECTRONICS. Specifications Serial Technology

FOSTCDR. Industrial Serial to Multimode Fiber Optic Converter PRODUCT INFORMATION B&B ELECTRONICS. Specifications Serial Technology FOSTCDR pn 8684R1 FOSTCDR-0812ds page 1/5 Industrial Serial to Multimode Fiber Optic Converter Data Rates up to 115.2 kbps 2.5 Mile (4 km) Range 10 to 30 VDC Input Voltage Wide Operating Temperature 2000V

More information

J TB/TW Temperature limiter, temperature monitor

J TB/TW Temperature limiter, temperature monitor JUMO GmbH & Co. KG Delivery address:mackenrodtstraße 14, 36039 Fulda, Germany Postal address: 36035 Fulda, Germany Phone: +49 661 6003-0 Fax: +49 661 6003-607 e-mail: mail@jumo.net Internet: www.jumo.net

More information

ABB 1. Three-phase monitoring relay CM-PFS. Data sheet. Features. Approvals. Marks. Order data. Order data - Accessories. Application.

ABB 1. Three-phase monitoring relay CM-PFS. Data sheet. Features. Approvals. Marks. Order data. Order data - Accessories. Application. 1SR 430 824 F9300 Features Monitoring of three-phase mains for phase sequence and failure Powered by the measuring circuit 2 c/o (SPDT) contacts 1 LED for status indication Approvals R: yellow LED - relay

More information

Type: DILM50(230V50HZ,240V60HZ) Article No.: 277830

Type: DILM50(230V50HZ,240V60HZ) Article No.: 277830 Type: DILM50(230V50HZ,240V60HZ) Article No.: 277830 Ordering information Rated operational current AC 3 400 V I e A 50 Max. rating for three phase motors, 50 60 Hz AC 3 230 V Max. rating for three phase

More information

Voltage monitoring relays CM-ESS.2 For single-phase AC/DC voltages

Voltage monitoring relays CM-ESS.2 For single-phase AC/DC voltages Data sheet Voltage monitoring relays CM-ESS.2 For single-phase AC/DC voltages The CM-ESS.2 is an electronic voltage monitoring relay that provides reliable monitoring of voltages as well as detection of

More information

33.6W Power over Ethernet Waterproof Adapter PoE Plus Single Port Injector for Outdoor Application

33.6W Power over Ethernet Waterproof Adapter PoE Plus Single Port Injector for Outdoor Application 33.6W Power over Ethernet Waterproof Adapter PoE Plus Single Port Injector for Outdoor Application Features Compliant with the IEEE802.3at Standard -40 to +60 C Temperature Range Diagnostic LEDs Full Protection

More information

Temperature monitoring relays CM-TCS Monitoring relays for monitoring temperatures with a PT100 sensor (2- or 3-wire connection)

Temperature monitoring relays CM-TCS Monitoring relays for monitoring temperatures with a PT100 sensor (2- or 3-wire connection) Data sheet Temperature monitoring relays CM-TCS Monitoring relays for monitoring temperatures with a PT100 sensor (2- or 3-wire connection) The temperature monitoring relays CM-TCS monitor overtemperature,

More information

Outdoor 33.6W Dual Port Passive Power-over-Ethernet Midspan For External Security Cameras and Wireless Access Points

Outdoor 33.6W Dual Port Passive Power-over-Ethernet Midspan For External Security Cameras and Wireless Access Points Outdoor 33.6W Dual Port Passive Power-over-Ethernet Midspan For External Security Cameras and Wireless Access Points Features SELV Compliant No Detection Passive Injector Gigabit Compatible Full Protection

More information

HMI display Installation Guide

HMI display Installation Guide HMI display Installation Guide Product Description Specifications Important Information o Package Contents o Related Documents o Accessories Cautions and Warnings Mounting and Dimensions o BAC-DIS-ENC

More information

Technical Data. Dimensions

Technical Data. Dimensions 0102 Model Number Features 15 mm quasi flush Usable up to SIL2 acc. to IEC 61508 Accessories BF 30 Mounting flange, 30 mm V1-G-N-2M-PUR Female cordset, M12, 2-pin, NAMUR, PUR cable V1-W-N-2M-PUR Female

More information

PD30ETB20xxIS. Photoelectrics, Background Suppression reflective with IR light. Main features. Description

PD30ETB20xxIS. Photoelectrics, Background Suppression reflective with IR light. Main features. Description Photoelectrics, Background Suppression reflective with IR light Main features Description The PD30ET... stainless steel sensors are built with high-quality materials and designed for harsh environments.

More information

Flush-mount room temperature sensor AQR2531ANW.

Flush-mount room temperature sensor AQR2531ANW. 1 408 Flush-mount room temperature sensor AQR2531... Passive sensor to acquire room temperature. Field of use 0 +50 C Use In heating, ventilation and air conditioning plants, primarily in the comfort range

More information

Alarm over IP. IRIS Touch Home Installation Manual. Version 1.0 ENGLISH. Now certified and compliant with EN50131, EN50136 Security Grade 4 ATS6

Alarm over IP. IRIS Touch Home Installation Manual. Version 1.0 ENGLISH. Now certified and compliant with EN50131, EN50136 Security Grade 4 ATS6 Alarm over IP IRIS Touch Home Installation Manual Version 1.0 ENGLISH Now certified and compliant with EN50131, EN50136 Security Grade 4 ATS6 1. Introduction No more bulky batteries, just one sleek unit

More information

INPUT/OUTPUT MODULE CONVERT INPUTS AND OUTPUTS TO WIRELESS

INPUT/OUTPUT MODULE CONVERT INPUTS AND OUTPUTS TO WIRELESS VMC A4 INPUT/OUTPUT MODULE CONVERT INPUTS AND OUTPUTS TO WIRELESS PRODUCT DATA SHEET FEATURES RF to 0-10 VDC out, analogue or PWM Maximal 3 digital inputs to RF RF communication with other equipment Wireless

More information

Programmable set for Ethernet Modbus/TCP in IP67 TI-BL67-PG-EN-2

Programmable set for Ethernet Modbus/TCP in IP67 TI-BL67-PG-EN-2 Type code Ident no. 1545065 Number of channels 2 Dimensions (W x L x H) 108 x 145 x 77.5 mm CoDeSys-programmable acc. to IEC 61131-3 Cable max. 50 m between interface and read/write head 10/100 Mbps Male

More information

Emergency stop As an emergency switching off/emergency stop device. Standards According to IEC/EN 60204-1, VDE 0113 Part 1

Emergency stop As an emergency switching off/emergency stop device. Standards According to IEC/EN 60204-1, VDE 0113 Part 1 MainswitchSurfacemounting Partno. P3-63/I4/SVB Articleno. 207343 CatalogNo. SP3-063-I4CRQ IP65 Deliveryprogramme Product range Switch-disconnectors Basic function Main switches Maintenance switches Manual

More information

Semi flush-mount room thermostat with KNX communications For VAV heating and cooling systems

Semi flush-mount room thermostat with KNX communications For VAV heating and cooling systems s 3 72 Semi flush-mount room thermostat with KNX communications For VAV heating and cooling systems RDU34 KNX bus communications (S-mode and LTE mode) Backlit display PI / P control Outputs for DC 0 0

More information

USB-to-Data Highway Plus Cable

USB-to-Data Highway Plus Cable Installation Instructions USB-to-Data Highway Plus Cable Catalog Number 1784-U2DHP Topic Page Important User Information 2 Environment and Enclosure 3 Install the Cable 5 Configure the DH+ Node Address

More information

KNX Panasonic Air Conditioners

KNX Panasonic Air Conditioners IntesisBox KNX Panasonic Air Conditioners Gateway for Panasonic ECOi and PACi system integration into KNX networks Up to 30 Outdoor units Up to 64 Indoor units PA-AC-KNX-64/128 EIA485 U1U2 line U1U2 line

More information

ZC-24DO CANopen I/O Module: 24 Digital Outputs

ZC-24DO CANopen I/O Module: 24 Digital Outputs Z-PC Line EN ZC-24DO CANopen I/O Module: 24 Digital Outputs Installation Manual Contents: - General Specifications - Technical Specifications - Installation Rules - Electrical connections - DIP-switches

More information

PSU-U-24V/AC-6A/10/FTA-TR-MC PSAC 0624

PSU-U-24V/AC-6A/10/FTA-TR-MC PSAC 0624 PSU-U-24V/AC-6A/10/FTA-TR-MC PSAC 0624 v.1.0 AC/AC power supply unit Edition: 1 from 24 th October 2008 Supercedes edition: ---------- 10062009 CONTENTS: 1. Technical description. 1.1. General description

More information

5-port / 8-port 10/100BaseTX Industrial Ethernet Switch User Manual

5-port / 8-port 10/100BaseTX Industrial Ethernet Switch User Manual 5-port / 8-port 10/100BaseTX Industrial Ethernet Switch User Manual Content Overview... 1 Introduction... 1 Features... 3 Packing List... 4 Safety Precaution... 4 Hardware Description... 5 Front Panel...

More information

Electronic overload relay EF65, EF96 and EF146

Electronic overload relay EF65, EF96 and EF146 Data sheet Electronic overload relay EF65, EF96 and EF146 Electronic overload relays offer reliable protection in case of overload and phase-failure. They are the alternative to thermal overload relays.

More information

3RT1015-1BB41 CONTACTOR, AC-3 3 KW/400 V,

3RT1015-1BB41 CONTACTOR, AC-3 3 KW/400 V, Automation Technology > Industrial Controls > Switching Devices > Contactors and Contactor Assemblies > Power Contactors for Switching Motors > Contactors SIRIUS 3RT10, 3-pole, 3... 250 kw 3RT1015-1BB41

More information

IntesisBox KNX Modbus RTU master

IntesisBox KNX Modbus RTU master IntesisBox KNX RTU master Gateway for integration of RTU devices into KNX control systems. Integrate RTU devices (Chillers, Roof Tops, electricity meters, heating floors, heat pumps, PLCs ) into KNX control

More information

is then retained absolutely without interruption.

is then retained absolutely without interruption. Page 1 of 11 DC UPS uninterruptible power supplies - DC UPS module 15 A Compact design, only 50 mm wide Absolutely interruption-free buffering of power failures through immediate electronic connection

More information

Positive-guided relay outputs: 3 safety contacts (N/O), instantaneous. 1 auxiliary contact (N/C), instantaneous

Positive-guided relay outputs: 3 safety contacts (N/O), instantaneous. 1 auxiliary contact (N/C), instantaneous Safety relay for monitoring E-STOP pushbuttons. Approvals Unit features Positive-guided relay outputs: 3 safety contacts (N/O), instantaneous 1 auxiliary contact (N/C), instantaneous Safe separation of

More information

4 non-safe digital I/O channels 2 IO-Link Master V1.1 slots. Figure 1. Figure 2. Type code. TBPN-L1-FDIO1-2IOL Ident no. 6814053.

4 non-safe digital I/O channels 2 IO-Link Master V1.1 slots. Figure 1. Figure 2. Type code. TBPN-L1-FDIO1-2IOL Ident no. 6814053. PROFINET slave Integrated Ethernet switch 100 Mbps supported 2 x M12, 4-pin, D-coded, Ethernet fieldbus connection Glass-fiber reinforced housing Shock and vibration tested Potted module electronics Protection

More information

Cable Plug acc. to DIN EN 175301-803, Form A

Cable Plug acc. to DIN EN 175301-803, Form A Cable Plug acc. to DIN EN 175301-803, Form A Complete program Contact form 18 mm Also available with LED indicator Optional 4-pin version for pressure switch or impulse valves respectively Versions with

More information

Installation Manual (English) Adjustable Active DP Terminator T1-Pepper Active RS485 segment termination for non-compliant cable

Installation Manual (English) Adjustable Active DP Terminator T1-Pepper Active RS485 segment termination for non-compliant cable Installation Manual (English) Adjustable Active DP Terminator T1-Pepper Active RS485 segment termination for non-compliant cable Designed for use with the COMbricks SALT repeater All baudrates Redundant

More information

Voltage monitoring relays CM-ESS.M For single-phase AC/DC voltages

Voltage monitoring relays CM-ESS.M For single-phase AC/DC voltages Data sheet Voltage monitoring relays CM-ESS.M For single-phase AC/DC voltages The CM-ESS.M is an electronic voltage monitoring relay that provides reliable monitoring of voltages as well as detection of

More information

ACS-30-EU-EMDR-10-MOD

ACS-30-EU-EMDR-10-MOD Multi-application heat tracing Control and Monitoring in commercial and residential buildings Roof & Gutter de-icing sensor module Technical Information Approvals Module IP rating Ambient operating temperature

More information

Características. Starligh SA 9 de julio 1595 Córdoba Argentina - 0351-4809210 / 4119600

Características. Starligh SA 9 de julio 1595 Córdoba Argentina - 0351-4809210 / 4119600 Balun Activo - BALUN_ACT Características Single Channel Active Video Transmitter Full-motion color video signal up to 3900ft(1200m) via UTP cat5e/6 NTSC, PAL & SECAM video format compatible Real-time transmission

More information

Zlinx Wireless I/O. Peer-to-Peer and Modbus I/O B&B ELECTRONICS PRODUCT INFORMATION

Zlinx Wireless I/O. Peer-to-Peer and Modbus I/O B&B ELECTRONICS PRODUCT INFORMATION Modular, Customizable Wire Replacement 128 / 256 Bit AES Encryption Software Selectable RF Transmit Power Software Selectable Over-the-air Data Rate Modbus ASCII /RTU Compatible Wide Operating Temperature

More information

IntesisBox KNX LG Air Conditioning

IntesisBox KNX LG Air Conditioning IntesisBox KNX LG Air Conditioning Gateway for integration of LG Air Conditioners with KNX control systems. 1. Main Features Direct connection to KNX TP-1 (EIB) bus. Direct connection to LG outdoor unit

More information

5-port 10/100Base-TX Industrial Switch (314500) User s Guide

5-port 10/100Base-TX Industrial Switch (314500) User s Guide 5-port 10/100Base-TX Industrial Switch (314500) User s Guide COPYRIGHT All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, or transmitted in any form or by

More information

IntesisBox KNX Modbus TCP master

IntesisBox KNX Modbus TCP master IntesisBox KNX TCP master Gateway for integration of TCP slave devices into KNX control systems. Integrate any TCP slave device into KNX. KNX TCP slave EIB Bus IntesisBox Ethernet slave LinkBoxEIB Configuration

More information

EMOSAFE EN-100. Network Isolators for PCB assembly 1 GENERAL DESCRIPTION. Product Data Sheet ENGLISH

EMOSAFE EN-100. Network Isolators for PCB assembly 1 GENERAL DESCRIPTION. Product Data Sheet ENGLISH ENGLISH EMOSAFE EN-100 Product Data Sheet Network Isolators for PCB assembly November 2013 1 GENERAL DESCRIPTION The EMOSAFE EN-100 Network Isolator interrupts all galvanically conducting connections (conductors

More information

Dear Customer! Thank you for choosing our product.

Dear Customer! Thank you for choosing our product. Dear Customer! Edition 1.4 Thank you for choosing our product. MIDI AMP CONTROLLER MAC-4.4 is an adaptor that enables to control (switch the channels, switch on/off other functions) the amps equipped with

More information