1 s P01 TX-I/O Island bus expansion TXA1.IBE Expand island bus to a distance of up to 2 x 200 meters Compact design per DIN , requires little space Easy installation and setup Mounted on standard rails Self-connecting bus (island bus) for the easiest possible installation Plug-in screw terminals for island bus expansion No programming / parameterization tool required CM2N8184en_03 15 Jul 2010 Building Technologies
2 Function The island bus expansion s allow for decentralized sub-islands with TX-I/O-s, that may be located up to 2 x 200 m from the "local" sub-island. A programming / parameterization tool is not required. The DIP switches for the bus master and bus terminator must be set correctly on the island bus expansion s. The island bus expansion is based on differential RS-485 transmission technology. "Decentralized" sub-island can be supplied using a separate power supply. Loss of this power does not impact the island bus of local sub-islands. For details on wiring and topology, refer to TX-I/O engineering and installation manual, CM Type summary Island bus expansion TXA1.IBE Ordering When ordering, please specify the quantity, product name, and type code. Example: 10 Island bus expansion s TXA1.IBE Equipment combinations Compatibility Full functionality is only possible using TX-I/O s from series C and higher P-bus interface s series B and higher PXC-NRUD Series C and higher only (Migration INTEGRAL AS1000) All models of PROFINET BIM Functionality is reduced when using s for series B and BIM series A: refer to CM System restrictions Number of decentralized sub-islands per I/O island Max. 8 Number of island bus expansion s per Exactly 1 decentralized sub-island Number of I/O s per I/O island Maximum of 64 Number of I/O s per sub-island No limit, as long as the total of the entire island (64) is maintained. See TX-I/O engineering and installation manual, CM for more details. 2 / 10
3 Design and technology Overview COM Attachment slider for standard rails DIP switch *) for bus master (island bus) LED "COM", displays island bus communication Bus connector right Bus connector left TXA1.IBE DIP switch *) for bus terminal (island bus expansion) + 1 _ Z01 Plug-in screw terminals + Signal island bus expansion Signal island bus expansion equipotential bonding *) DIP switch: Both "" switches must have the same position. The same applies to "" switches. For details on wiring and topology, refer to TX-I/O engineering and installation manual, CM Mechanical properties The housing complies with DIN and is 32mm wide. The island bus expansion is plugged on the right side of the power / bus connection on the standard rail. The electrical connection is on the 4 side island bus contacts. The bus establishes its own connection, when TX-I/O devices are plugged into one another on the rails. Electrical properties Interfaces Island bus expansion: Plug-in screw terminals Island bus: Bus connector on the right and left side of the. System ground Protection against incorrect wiring Island bus and island bus expansion are galvanically connected All terminals are protected against short circuit and incorrect wiring using AC/DC 24 V. This applies as well to reverse phase voltage AC 24 V Side bus connector: No protection Signaling LED COM (yellow) The LED indicates bus traffic on the island bus: Both directions OK: irregular blinking Bus short circuit: bright 3 / 10
4 Schematic Island bus CD 24V~ CD 24V~ 1 Island Bus 2 RS PTC _ + Island bus expansion 8184Z02 Engineering, topology Please consult the following document: TX-I/O engineering and installation manual, CM Mounting Fixings Order Exchange Permissible mounting positions The device is mounted on a standard rail 35 x 7.5 mm (tophat rails TH per EN60715) In an I/O row, an island bus expansion is placed immediately to the right of the power supply, bus connection or bus interface. Dee also the connection examples on pages 7 and 8. An island bus expansion may be removed from the row. The electronic component from the neighboring right must, however, be removed. Its terminal block may remain. TX-I/O devices can be mounted in any position: horizontally, vertically, on a horizontal surface. You must ensure, however, that sufficient ventilation is available to maintain the permissible ambient temperature (max. 50 C). Disposal The device is classified as waste electronic equipment in terms of the European Directive 2002/96/EC (WEEE) and should not be disposed of as unsorted municipal waste. The relevant national legal rules are to be adhered to. Regarding disposal, use the systems setup for collecting electronic waste. Observe all local and applicable laws. 4 / 10
5 Technical data Supply (bus connector on side) Operating voltage range SELV / PELV DC V Max. power consumption 1.2W (for the sizing of power supplies, see CM110562) Maximum distances (only with TX-I/O s series C and higher; only with BIM Series B and higher) Number of supported s Island bus expansion Island bus inside of a sub-island (depending on cross section and current load for details, refer to TX-I/O engineering and installation manual, CM110562) Bus expansion s per I/O island I/O s per I/O island Max. 2 x 200 m Max. 50 m with round cable Max. 100 m with RG-62 Max. 9 s Max. 64 s Island bus communication Island bus traffic display LED "COM" Bus master function 2 DIP switches = Bus terminator function (terminator) 2 DIP switches = Galvanic isolation Island bus and island bus expansion are galvanically connected via PTC (Conductors and ). Short-circuit protection Side bus connector No protection! and incorrect wiring Terminal See below Cabling For details on cabling for RS485 and wiring rules, refer to TX-I/O engineering and installation manual, CM Connection terminals, plug-in, for island bus expansion Mechanical design Copper wire Copper stranded wires with ferrules Copper stranded wires without ferrules Screwdriver Maximum stud torque Plug-in screw terminal 1 x 0.6 mm to 2.5mm 2 or 2 x 0.6 mm to 1.0 mm 2 1 x 0.6 mm to 2.5mm 2 or 2 x 0.6 mm to 1.0 mm 2 1 x 0.6 mm to 2.5 mm 2 or 2 x 0.6 mm to 1.5 mm 2 Flat screwdriver size 1 with shaft ø 4.5 mm 0.6 Nm Classification per EN Function of automatic control devices Degree of pollution Mechanical design Housing type IP class per EN Front parts in DIN excerpt terminal part Type 1 2 Protection class III IP30 IP20 5 / 10
6 Environmental conditions Standards, directives and approvals Operation Climatic conditions Temperature Humidity Mechanical conditions Transport Climatic conditions Temperature Humidity Mechanical conditions Product standard Automatic electrical controls devices for household and similar use As per IEC Class 3K C 5 95 % r.h. Class 3M2 As per IEC Class 2K C 5 95 % r.h. Class 2M2 EN Electromagnetic compatibility Immunity Residential & industrial EN Emissions Residential & industrial EN CE conformity Electromagnetic compatibility 2004/108/EG c-tick conformity Emissions AS/NZS UL approval UL 916 Environmental compatibility The product environmental declaration CM1E8184 contains data on environmentally compatible product design and assessments (RoHS compliance, materials composition, packaging, environmental benefit, disposal) ISO (Environment) ISO 9001 (Quality) SN (Environmentally compatible products) 2002/95/EC (RoHS directive) Color Housing Light gray, RAL 7035 Dimensions Housing as per DIN 43880, see dimensions Weight Without / with packaging 64 / 84 g 6 / 10
7 Connection examples for automation station with island bus or PROFINET BIM See TX-I/O engineering and installation manual, CM for more details. A) Maximum 2 segments of max. 200 meters each are possible using the island bus expansion s A) Max. 200 m = = Key N1 Automation station with island bus or PROFINET BIM Power supply Island bus expansion TX-I/O s X1 Bus connection N1 = OFF = Bus master function (island bus, both switches in the same position!) Bus terminator function (island bus expansion, both switches in the same position!) Max. 200 m = = OFF = = B) Decentralized subisland without power supply (maximum distance depends on current on conductors and ) B) N1 T = OFF = T X1 = = 8184A01e 7 / 10
8 Connection examples for automation station with P-bus See TX-I/O engineering and installation manual, CM for more details. C) Maximum 2 segments of max. 200 meters each are possible using the island bus expansion s C) Max. 200 m = = Key N2 Automation station with P-bus Power supply Island bus expansion TX-I/O s U4 P-bus interface X1 Bus connection N2 P-Bus U4 = OFF = Bus master function (island bus, both switches in the same position!) Bus terminator function (island bus expansion, both switches in the same position!) Max. 200 m = = OFF = = D) Decentralized subisland without power supply (maximum distance depends on current on conductors and ) D) N2 P-Bus T U4 = OFF = T X1 = = 8184A11b 8 / 10
9 Dimensions Dimensions in mm M01 9 / 10
10 10 / Siemens Switzerland Ltd Subject to change
TX OPEN RS232/485 module
s 8 185 8185P01 TX-I/O ; DESIGO OPEN TX OPEN RS/485 module for integrating third-party systems and devices to DESIGO (V4 or higher) TXI1.OPEN Platform to integrate third-party systems and devices to the
More informationDigital input modules
8 172 TX-I/O Digital input modules TXM1.8D TXM1.16D Two fully compatible versions: TXM1.8D: 8 inputs, each with a three-color LED (green, yellow or red) TXM1.16D: As TXM1.8X, but 16 inputs, each with a
More informationBACnet router for BACnet/IP BACnet/LonTalk BACnet MS/TP
s 9 270 Desigo PX BACnet router for BACnet/IP BACnet/LonTalk BACnet MS/TP PXG3.L PXG3.M Routing between BACnet/IP, BACnet/LonTalk (PXG3.L only), and BACnet MS/TP Supports BACnet/IPv4 and BACnet/IPv6 ANSI/ASHRAE
More informationSEZ220. Signal Converter. Synco 200. With preprogrammed standard applications Freely programmable Menu-driven operation. Use
s 5 146 Synco 200 Signal Converter SEZ220 With preprogrammed standard applications Freely programmable enu-driven operation Use The signal converter is for use in HVAC plant to provide minimum / maximum
More informationFor UK only RXL39.1 and the applications package SP-03 are sold in the United Kingdom only.
s For UK only RX39.1 and the applications package SP-03 are sold in the United Kingdom only. 3 876 3876P01 RX Room controller Communicating controllers for fan-coil applications SP-03 RX39.1 The RX39.1
More informationSTEP-PS/1AC/12DC/1.5. Extract from the online catalog. Order No.: 2868567. DIN rail power supply unit 12 V DC/1.5 A, primary switched-mode, 1- phase
Extract from the online catalog STEP-PS/1AC/12DC/1.5 Order No.: 2868567 DIN rail power supply unit 12 V DC/1.5 A, primary switched-mode, 1- phase Commercial data EAN 4046356292924 Pack 1 pcs. Customs tariff
More informationHCR3.2/.. Chipcard reader HOTEL SOLUTION
s 6 332 HOTEL SOLUTION Chipcard reader HCR3.2/.. Chipcard reader for hotel room access control Reads access code on chipcard Transfers access code to room controller Built-in optical display of messages
More informationPCS0100en 02.2008. Persy Control Services B.V. Netherlands
P-Bus Gateway PBGW2.128 Universal gateway between the P-bus protocol and open standard protocols. The variety of available electrical interfaces on the gateway offers a wide range of possibilities for
More informationQFP910. Water detector. Building Technologies. CE1N2732en. Synco living
2 732 Synco living Water detector QFP910 Wireless radio sensor to record water puddles RF communication based on KNX standard (868 MHz unidirectional) Battery operation with standard 1.5 V batteries Use
More informationRRV934. Multi-controller. Synco living
s 2 709 Synco living Multi-controller RRV934 RF-based multi-controller For precontrol of up to 2 room groups For control of ventilation plant with up to 3 stages RF communication based on KNX standard
More informationProduct and Applications Description. Application Programs. Example of Operation. GAMMA instabus Technical Product-Information.
Product and Applications Description The power supply units N 125/x2 can supply DC 24 V power from an additional pair of terminals (yellowwhite). This DC 24 V output voltage can be used to power e.g. an
More informationPXM20-E. Operator unit DESIGO PX
9 234 DESIGO PX Operator unit PXM20-E Network-compatible operator unit for viewing and operating one or more DESIGO PX automation stations. High-grade display with adjustable contrast Simple key operation
More informationAir damper actuators
4 634 OpenAir TM Air damper actuators GDB...1 GLB...1 Rotary version, / AC 230 V Electronic motor driven actuators for three-position and modulating control Nominal torque 5 Nm (GDB), 10 Nm (GLB) Mechanically
More informationDifferential Pressure Sensors for air and non-corrosive gases, with calibration certificate
1 919 1919P01 1919P03 QBM65/C, QBM75-1U/C Differential Pressure Sensors for air and non-corrosive gases, with calibration certificate QBM751-1/C QBM65/C QBM75/C Highly accurate measurements with calibration
More informationRDJ10RF/SET. Wireless room temperature controller with 24-hour time switch and LCD. Programmable, for heating systems
3 072 RDJ10RF RCR10/433 Wireless room temperature controller with 24-hour time switch and LCD Programmable, for heating systems RDJ10RF/SET Operating modes: Automatic, Comfort, Energy Saving, and Frost
More informationAXIS T81B22 DC 30W Midspan
INSTALLATION GUIDE AXIS T81B22 DC 30W Midspan ENGLISH About this Document This document includes instructions for installing AXIS T81B22 on your network. Previous experience of networking will be beneficial
More informationQFP910. Water detector. Building Technologies. CE1N2732en 2016-03-01. Synco living
2 732 Synco living Water detector QFP910 Wireless radio sensor to record water puddles RF communication based on KNX standard (868 MHz unidirectional) Battery operation with standard 1.5 V batteries Use
More informationRM17TE 183...528 V AC. Main. Product or component type. Product specific application. Relay monitored parameters 250 V DC 5 A DC
Characteristics multifunction control relay RM17-TE - range 183..528 V AC Complementary Reset time Maximum switching voltage Minimum switching current Maximum switching current [Us] rated supply voltage
More informationPower Supply Unit, Primary Switched, Narrow Design MINI-PS-12-24DC/24DC/1
Power Supply Unit, Primary Switched, Narrow Design MINI POWER provides: Extra narrow design with widths of 22.5 mm, 45 mm, and 67.5 mm (0.886, 1.772, and 2.657 in.) Global use due to a wide-range input
More informationOZS164... Web server. For LPB/BSB plants
s 5 711 Web server For LPB/BSB plants OZS164... Remotely operate and monitor a LPB or BSB device Web browser operation via PC/laptop or Smartphone SMS operation via mobile phone (OZS164.23) 2 digital inputs
More informationElectronic timer CT-AHD.12 OFF-delayed with 1 c/o (SPDT) contact
Data sheet Electronic timer CT-AHD.12 OFF-delayed with 1 c/o (SPDT) contact The CT-AHD.12 is an electronic time relay with OFF-delay. It is from the CT-D range. With their MDRC profile and a width of only
More informationVAV compact controller KNX / PL-Link
s 3 547 OpenAir VAV compact controller KNX / PL-Link Series E GDB181.1E/KN GLB181.1E/KN Networked compact controller featuring KNX (S-mode / LTE-mode) and PL- Link capability for plants with variable air
More informationDuct Humidity Transmitter
SDC-H Duct Humidity Transmitter Features Replaceable sensor element Humidity measurement for air ducts Minimum and maximum value memory 0 0V, 0 0mA or 0V, 4 0mA measuring signals selectable with jumpers
More informationTM7BDM8B expansion block - TM7 - IP67-8 DI/DO - 24V DC - 0.5 A - M8 connector
Product datasheet Characteristics TM7BDM8B expansion block - TM7 - IP67-8 DI/DO - 24V DC - 0.5 A - M8 connector Main Range of product Product or component type Range compatibility Enclosure material Bus
More informationRM35UA13MW. range 15..600 V. Main. Product or component type. Relay monitored parameters
Characteristics multifunction voltage control relay RM35-U - range 15..600 V Complementary Reset time Maximum switching voltage [Us] rated supply voltage Supply voltage limits Power consumption in W Main
More informationProduct and functional description
Product and functional description The KNX / DALI gateway N 141/02 is a 4 MU wide, DINrail mounted KNX device with one DALI interface to which up to 64 DALI actuators (e.g. DALI ballasts) can be connected
More informationCompactLogix Power Supplies Specifications
Technical Data CompactLogix Power Supplies Specifications 1768 CompactLogix Power Supplies Catalog Numbers 1768-PA3, 1768-PB3 1769 Compact I/O Power Supplies Catalog Numbers 1769-PA2, 1769-PB2, 1769-PA4,
More informationRISH CON - Hz. Salient Features : Application : Product Features: FREQUENCY TRANSDUCER
Application : The RISH CON - Hz transducer is used for frequency measurement. The output signal is proportional to measured frequency and is either load independent DC Current or load independent DC Voltage.
More informationVAV compact controller KNX / PL-Link
s 3 547 OpenAir VAV compact controller KNX / PL-Link Series E GDB181.1E/KN GLB181.1E/KN Networked compact controller featuring KNX (S-mode / LTE-mode) and PL- Link capability for plants with variable air
More informationConneXium Ethernet Switches TCSESU0 F N0 Quick Reference Guide
31007950 7/2009 ConneXium Ethernet Switches TCSESU0 F N0 Quick Reference Guide 7/2009 31007950.02 www.schneider-electric.com NOTICE Read these instructions carefully, and look at the equipment to become
More informationCurrent valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw
4 937 DESIO Current valve for AC 24 V pulse/pause control of electrical loads up to 30 kw SEA45.1 Use The current valve is used for the control of electric heating elements in heating, ventilation and
More informationIntesisBox Modbus Server Fidelio IP
IntesisBox Server Fidelio IP Gateway for integration of Micros Fidelio Ho management system into (RTU and TCP) enabled control systems. Integrate your Micros Fidelio Ho management system into your master
More informationMILLENIUM INSTALLATION MANUAL NTR 735 A. Simple Automation Control Module (MAS)
MILLENIUM Table of contents 1. INTRODUCTION 1 2. HARDWARE DESCRIPTION 2 3. INSTALLATION 5 4. CONNECTION 6 5. USER SAFETY AND PROTECTION OF EQUIPMENT 8 1. Introduction The MILLENIUM series has been designed
More informationHARTING econ 3000 Introduction and features
HARTING Introduction and features HARTING es, unmanaged, for installation in control cabinets General Description Features The Fast es of the product family HARTING are suitable for industrial applications
More informationOZW772... V2.0. Web server. Synco TM, Synco TM living
s 5 701 Web server Synco TM, Synco TM living OZW772... V2.0 The OZW772 web server allows for remote operation and monitoring of plants via the web and send faults and system reports to e-mail recipients.
More informationRedundancy Module QUINT-DIODE/40
Redundancy Module QUT DIODE provides: 00% decoupling of power supplies connected in parallel Can be installed in potentially explosive areas Load currents up to 60 A supported Easy assembly by snapping
More informationXUSL4E4BB091NS2 XUSL type 4 - Slave2 - For body protection - 4 Beams, Hp = 910 mm
Characteristics XUSL type 4 - Slave2 - For body protection - 4 Beams, Hp = 910 mm Complementary Detection system Kit composition [EAA] effective aperture angle Emission Main Range of product Product or
More informationYour Advantages For safety application up to PL e / Cat. 4 e.g. SIL 3 Manual or automatic start 0225592. * see variants. Applications.
Safety Technique SAFEMASTER Emergency Stop Module BG 5924, IP 5924 Your Advantages For safety application up to PL e / Cat. 4 e.g. SIL 3 Manual or automatic start 0225592 BG 5924 IP 5924 Product Description
More informationNI 9423. NI C Series Overview DATASHEET. 8-Channel Sinking Digital Input Module
DATASHEET NI 9423 8-Channel Sinking Digital Input Module 8-channel, 100 µs digital input 24 V logic, sinking digital input Compatible with NI CompactDAQ counters 250 Vrms, CAT II isolation 10-position
More informationFeatures. Display. Measurements. Intelligent. Accuracy. Models. Installation DEIF A/S. Multi-instrument 4921210109D
7000/7000C/7020 Multi-instrument 4921210109D Features Measurements All 3-phase AC measurements True RMS Replaces analogue meters Demand on each phase current Accuracy U, I and F class 0.5 Other values
More informationWaveguide Access Point WGA631. Product Guide
Waveguide Access Point Product Guide Waveguide Access Point Contents 1. Description............................ 3 2. Application............................ 3 3. Technical data... 4 4. Physical interfaces......................
More informationQuick Connect. quick - simple - efficient. www.g-mw.de
Quick Connect quick - simple - efficient www.g-mw.de Phone: +49 9103 7129-0 Fax: +49 9103 7129-207 Innovative connection technology to plug three single-phase current transformers to multifunctional power
More informationType: EASY719 DC RC Article No.: 274119. Ordering information Relay outputs Quantity 6 Power supply V DC 24 V DC. Description
Type: EASY719 DC RC Article.: 274119 Ordering information Relay outputs Quantity 6 Power supply V DC 24 V DC Description 12 digital inputs (4 inputs available as analog inputs) 6 relay outputs LCD display
More informationHARTING mcon 3000 Introduction and features
Introduction and features HARTING mcon 3000 es, managed, for mounting onto top-hat mounting rail in control cabinets General Description Features The fully managed es of the product family HARTING mcon
More informationOZW30. Central Unit SYNERGYR
2 841 SYNERGYR Central Unit OZW30 Collects billing data from the apartments. Generates an image of each apartment's heat consumption and makes it available for readout. Acts on room temperature control
More informationABB i-bus KNX Switch Actuator, x-fold, 16 A, MDRC SA/S x.16.2.1, 2CDG1101xxR0011
Technical Data 2CDC505051D0205 ABB i-bus KNX Product description Switch Actuators SA/S x.16.2.1, 16 A are modular installation devices in ProM design for installation in the distribution board. They are
More informationaseries A13B Mini Bullet Camera User Manual
aseries A13B Mini Bullet Camera User Manual Thank you for purchasing our product. If there are any questions, or requests, please do not hesitate to contact the dealer. This manual applies to the MicroView
More informationTechnical Data. General specifications Switching element function Rated operating distance s n 15 mm
0102 Model Number Features Comfort series 15 mm flush Accessories MHW 01 Modular mounting bracket MH 04-2057B Mounting aid for VariKont and +U1+ Technical Data General specifications Switching element
More informationAutomation stations modular series
s 9 222 9222P01 DESIGO PX Automation stations modular series PXC...D PXC...-E.D PXA40- Freely programmable modular automation stations for HVAC and building services plants. Native BACnet automation station
More informationIFS SP-PoE Splitter User Manual
IFS SP-PoE Splitter User Manual P/N 1069176-EN REV 1.01 ISS 01JUL10 2011 UTC Fire & Security. All rights reserved. Content Overview 2 Package contents 2 Introduction 3 Product Specifications 3 Hardware
More informationIntesisBox KNX - LON
IntesisBox KNX - Gateway for integration of devices into KNX systems. Integrate Air Conditioning from the main manufacturers (DAIKIN, Mitsubishi Electric, Mitsubishi Heavy Industries, Toshiba, Fujitsu,
More informationISIO 200. Binary Input/Output (I/O) Terminal with IEC 61850 Interface
ISIO 200 Binary Input/Output (I/O) Terminal with IEC 61850 Interface Compact and Easy ISIO 200 Put your Binary I/Os where you need them ISIO 200 is a simple and versatile binary I/O terminal with IEC 61850
More information40.3. Control Relays and Timers
.3 Contents EASY500/700/800 Intelligent Relays........ EASY/MFD Expansion Modules............ MFD Intelligent Relays................... EASY/MFD Communication Modules....... EASY/MFD Power Supplies, Accessories
More informationHow To Write A Librao Low Voltage Differential (Lvds) Module On An Nio 6585 Fuserio (Flexrio) Power Supply (Femaleseo) And Power Supply On An Iphone Or Ip
NI 6585 Specifications This document lists the specifications of the National Instruments 6585 FlexRIO low-voltage differential (LVDS) adapter module. Pair these specifications with your FPGA module specifications.
More informationIntesisBox KNX Mitsubishi Heavy Industries AC
IntesisBox KNX Mitsubishi Heavy Industries AC Gateway for integration of Mitsubishi Heavy Indsutries (MHI) Air Conditioners with KNX control systems. 1. Main Features Direct connection to KNX TP-1 (EIB)
More informationType: DILM115(RAC240) Article No.: 239548 Sales text Contactor,55kW/400V,AC operated. Ordering information
Type: DILM115(RAC240) Article No.: 239548 Sales text Contactor,55kW/400V,AC operated Ordering information Connection technique Description Description Rated operational current Screw terminals 3 pole AC
More informationThree-phase monitoring relay CM-PFE
Data sheet Three-phase monitoring relay CM-PFE The CM-PFE is a three-phase monitoring relay that monitors the phase parameter phase sequence and phase failure in three-phase mains. 2CDC 251 005 S0012 Characteristics
More informationElectronic overload relay EF19 and EF45
Data sheet Electronic overload relay EF19 and EF45 Electronic overload relays offer reliable protection in case of overload and phase-failure. They are the alternative to thermal overload relays. Motor
More informationABB i-bus KNX Fan Coil Actuator, MDRC FCA/S 1.1M, 2CDG 110 084 R0011
, 2CDG 110 084 R0011 2CDC 071 112 F0008 The Fan Coil Actuator is a modular installation device (MDRC) in pro M design. It is intended for installation in the distribution board on 35 mm mounting rails.
More informationModular I/O System Analog and Digital Interface Modules
OPERATING INSTRUCTIONS Modular I/O System Analog and Digital Interface Modules Installation Operation Maintenance Document Information Document ID Title: Operating Instructions Modular I/O System Part
More informationIntesisBox Modbus Server SAMSUNG Air Conditioners
IntesisBox Modbus Server SAMSUNG Air Conditioners Gateway for monitoring and control of Samsung NASA compatible Air Conditioning Systems from any Modbus master device TCP or RTU (BMS, PLC, SCADA, HMI,
More informationFOSTCDR. Industrial Serial to Multimode Fiber Optic Converter PRODUCT INFORMATION B&B ELECTRONICS. Specifications Serial Technology
FOSTCDR pn 8684R1 FOSTCDR-0812ds page 1/5 Industrial Serial to Multimode Fiber Optic Converter Data Rates up to 115.2 kbps 2.5 Mile (4 km) Range 10 to 30 VDC Input Voltage Wide Operating Temperature 2000V
More informationJ TB/TW Temperature limiter, temperature monitor
JUMO GmbH & Co. KG Delivery address:mackenrodtstraße 14, 36039 Fulda, Germany Postal address: 36035 Fulda, Germany Phone: +49 661 6003-0 Fax: +49 661 6003-607 e-mail: mail@jumo.net Internet: www.jumo.net
More informationABB 1. Three-phase monitoring relay CM-PFS. Data sheet. Features. Approvals. Marks. Order data. Order data - Accessories. Application.
1SR 430 824 F9300 Features Monitoring of three-phase mains for phase sequence and failure Powered by the measuring circuit 2 c/o (SPDT) contacts 1 LED for status indication Approvals R: yellow LED - relay
More informationType: DILM50(230V50HZ,240V60HZ) Article No.: 277830
Type: DILM50(230V50HZ,240V60HZ) Article No.: 277830 Ordering information Rated operational current AC 3 400 V I e A 50 Max. rating for three phase motors, 50 60 Hz AC 3 230 V Max. rating for three phase
More informationVoltage monitoring relays CM-ESS.2 For single-phase AC/DC voltages
Data sheet Voltage monitoring relays CM-ESS.2 For single-phase AC/DC voltages The CM-ESS.2 is an electronic voltage monitoring relay that provides reliable monitoring of voltages as well as detection of
More information33.6W Power over Ethernet Waterproof Adapter PoE Plus Single Port Injector for Outdoor Application
33.6W Power over Ethernet Waterproof Adapter PoE Plus Single Port Injector for Outdoor Application Features Compliant with the IEEE802.3at Standard -40 to +60 C Temperature Range Diagnostic LEDs Full Protection
More informationTemperature monitoring relays CM-TCS Monitoring relays for monitoring temperatures with a PT100 sensor (2- or 3-wire connection)
Data sheet Temperature monitoring relays CM-TCS Monitoring relays for monitoring temperatures with a PT100 sensor (2- or 3-wire connection) The temperature monitoring relays CM-TCS monitor overtemperature,
More informationOutdoor 33.6W Dual Port Passive Power-over-Ethernet Midspan For External Security Cameras and Wireless Access Points
Outdoor 33.6W Dual Port Passive Power-over-Ethernet Midspan For External Security Cameras and Wireless Access Points Features SELV Compliant No Detection Passive Injector Gigabit Compatible Full Protection
More informationHMI display Installation Guide
HMI display Installation Guide Product Description Specifications Important Information o Package Contents o Related Documents o Accessories Cautions and Warnings Mounting and Dimensions o BAC-DIS-ENC
More informationTechnical Data. Dimensions
0102 Model Number Features 15 mm quasi flush Usable up to SIL2 acc. to IEC 61508 Accessories BF 30 Mounting flange, 30 mm V1-G-N-2M-PUR Female cordset, M12, 2-pin, NAMUR, PUR cable V1-W-N-2M-PUR Female
More informationPD30ETB20xxIS. Photoelectrics, Background Suppression reflective with IR light. Main features. Description
Photoelectrics, Background Suppression reflective with IR light Main features Description The PD30ET... stainless steel sensors are built with high-quality materials and designed for harsh environments.
More informationFlush-mount room temperature sensor AQR2531ANW.
1 408 Flush-mount room temperature sensor AQR2531... Passive sensor to acquire room temperature. Field of use 0 +50 C Use In heating, ventilation and air conditioning plants, primarily in the comfort range
More informationAlarm over IP. IRIS Touch Home Installation Manual. Version 1.0 ENGLISH. Now certified and compliant with EN50131, EN50136 Security Grade 4 ATS6
Alarm over IP IRIS Touch Home Installation Manual Version 1.0 ENGLISH Now certified and compliant with EN50131, EN50136 Security Grade 4 ATS6 1. Introduction No more bulky batteries, just one sleek unit
More informationINPUT/OUTPUT MODULE CONVERT INPUTS AND OUTPUTS TO WIRELESS
VMC A4 INPUT/OUTPUT MODULE CONVERT INPUTS AND OUTPUTS TO WIRELESS PRODUCT DATA SHEET FEATURES RF to 0-10 VDC out, analogue or PWM Maximal 3 digital inputs to RF RF communication with other equipment Wireless
More informationProgrammable set for Ethernet Modbus/TCP in IP67 TI-BL67-PG-EN-2
Type code Ident no. 1545065 Number of channels 2 Dimensions (W x L x H) 108 x 145 x 77.5 mm CoDeSys-programmable acc. to IEC 61131-3 Cable max. 50 m between interface and read/write head 10/100 Mbps Male
More informationEmergency stop As an emergency switching off/emergency stop device. Standards According to IEC/EN 60204-1, VDE 0113 Part 1
MainswitchSurfacemounting Partno. P3-63/I4/SVB Articleno. 207343 CatalogNo. SP3-063-I4CRQ IP65 Deliveryprogramme Product range Switch-disconnectors Basic function Main switches Maintenance switches Manual
More informationSemi flush-mount room thermostat with KNX communications For VAV heating and cooling systems
s 3 72 Semi flush-mount room thermostat with KNX communications For VAV heating and cooling systems RDU34 KNX bus communications (S-mode and LTE mode) Backlit display PI / P control Outputs for DC 0 0
More informationUSB-to-Data Highway Plus Cable
Installation Instructions USB-to-Data Highway Plus Cable Catalog Number 1784-U2DHP Topic Page Important User Information 2 Environment and Enclosure 3 Install the Cable 5 Configure the DH+ Node Address
More informationKNX Panasonic Air Conditioners
IntesisBox KNX Panasonic Air Conditioners Gateway for Panasonic ECOi and PACi system integration into KNX networks Up to 30 Outdoor units Up to 64 Indoor units PA-AC-KNX-64/128 EIA485 U1U2 line U1U2 line
More informationZC-24DO CANopen I/O Module: 24 Digital Outputs
Z-PC Line EN ZC-24DO CANopen I/O Module: 24 Digital Outputs Installation Manual Contents: - General Specifications - Technical Specifications - Installation Rules - Electrical connections - DIP-switches
More informationPSU-U-24V/AC-6A/10/FTA-TR-MC PSAC 0624
PSU-U-24V/AC-6A/10/FTA-TR-MC PSAC 0624 v.1.0 AC/AC power supply unit Edition: 1 from 24 th October 2008 Supercedes edition: ---------- 10062009 CONTENTS: 1. Technical description. 1.1. General description
More information5-port / 8-port 10/100BaseTX Industrial Ethernet Switch User Manual
5-port / 8-port 10/100BaseTX Industrial Ethernet Switch User Manual Content Overview... 1 Introduction... 1 Features... 3 Packing List... 4 Safety Precaution... 4 Hardware Description... 5 Front Panel...
More informationElectronic overload relay EF65, EF96 and EF146
Data sheet Electronic overload relay EF65, EF96 and EF146 Electronic overload relays offer reliable protection in case of overload and phase-failure. They are the alternative to thermal overload relays.
More information3RT1015-1BB41 CONTACTOR, AC-3 3 KW/400 V,
Automation Technology > Industrial Controls > Switching Devices > Contactors and Contactor Assemblies > Power Contactors for Switching Motors > Contactors SIRIUS 3RT10, 3-pole, 3... 250 kw 3RT1015-1BB41
More informationIntesisBox KNX Modbus RTU master
IntesisBox KNX RTU master Gateway for integration of RTU devices into KNX control systems. Integrate RTU devices (Chillers, Roof Tops, electricity meters, heating floors, heat pumps, PLCs ) into KNX control
More informationis then retained absolutely without interruption.
Page 1 of 11 DC UPS uninterruptible power supplies - DC UPS module 15 A Compact design, only 50 mm wide Absolutely interruption-free buffering of power failures through immediate electronic connection
More informationPositive-guided relay outputs: 3 safety contacts (N/O), instantaneous. 1 auxiliary contact (N/C), instantaneous
Safety relay for monitoring E-STOP pushbuttons. Approvals Unit features Positive-guided relay outputs: 3 safety contacts (N/O), instantaneous 1 auxiliary contact (N/C), instantaneous Safe separation of
More information4 non-safe digital I/O channels 2 IO-Link Master V1.1 slots. Figure 1. Figure 2. Type code. TBPN-L1-FDIO1-2IOL Ident no. 6814053.
PROFINET slave Integrated Ethernet switch 100 Mbps supported 2 x M12, 4-pin, D-coded, Ethernet fieldbus connection Glass-fiber reinforced housing Shock and vibration tested Potted module electronics Protection
More informationCable Plug acc. to DIN EN 175301-803, Form A
Cable Plug acc. to DIN EN 175301-803, Form A Complete program Contact form 18 mm Also available with LED indicator Optional 4-pin version for pressure switch or impulse valves respectively Versions with
More informationInstallation Manual (English) Adjustable Active DP Terminator T1-Pepper Active RS485 segment termination for non-compliant cable
Installation Manual (English) Adjustable Active DP Terminator T1-Pepper Active RS485 segment termination for non-compliant cable Designed for use with the COMbricks SALT repeater All baudrates Redundant
More informationVoltage monitoring relays CM-ESS.M For single-phase AC/DC voltages
Data sheet Voltage monitoring relays CM-ESS.M For single-phase AC/DC voltages The CM-ESS.M is an electronic voltage monitoring relay that provides reliable monitoring of voltages as well as detection of
More informationACS-30-EU-EMDR-10-MOD
Multi-application heat tracing Control and Monitoring in commercial and residential buildings Roof & Gutter de-icing sensor module Technical Information Approvals Module IP rating Ambient operating temperature
More informationCaracterísticas. Starligh SA 9 de julio 1595 Córdoba Argentina - 0351-4809210 / 4119600
Balun Activo - BALUN_ACT Características Single Channel Active Video Transmitter Full-motion color video signal up to 3900ft(1200m) via UTP cat5e/6 NTSC, PAL & SECAM video format compatible Real-time transmission
More informationZlinx Wireless I/O. Peer-to-Peer and Modbus I/O B&B ELECTRONICS PRODUCT INFORMATION
Modular, Customizable Wire Replacement 128 / 256 Bit AES Encryption Software Selectable RF Transmit Power Software Selectable Over-the-air Data Rate Modbus ASCII /RTU Compatible Wide Operating Temperature
More informationIntesisBox KNX LG Air Conditioning
IntesisBox KNX LG Air Conditioning Gateway for integration of LG Air Conditioners with KNX control systems. 1. Main Features Direct connection to KNX TP-1 (EIB) bus. Direct connection to LG outdoor unit
More information5-port 10/100Base-TX Industrial Switch (314500) User s Guide
5-port 10/100Base-TX Industrial Switch (314500) User s Guide COPYRIGHT All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, or transmitted in any form or by
More informationIntesisBox KNX Modbus TCP master
IntesisBox KNX TCP master Gateway for integration of TCP slave devices into KNX control systems. Integrate any TCP slave device into KNX. KNX TCP slave EIB Bus IntesisBox Ethernet slave LinkBoxEIB Configuration
More informationEMOSAFE EN-100. Network Isolators for PCB assembly 1 GENERAL DESCRIPTION. Product Data Sheet ENGLISH
ENGLISH EMOSAFE EN-100 Product Data Sheet Network Isolators for PCB assembly November 2013 1 GENERAL DESCRIPTION The EMOSAFE EN-100 Network Isolator interrupts all galvanically conducting connections (conductors
More informationDear Customer! Thank you for choosing our product.
Dear Customer! Edition 1.4 Thank you for choosing our product. MIDI AMP CONTROLLER MAC-4.4 is an adaptor that enables to control (switch the channels, switch on/off other functions) the amps equipped with
More information