1 s P01 TX-I/O ; DESIGO OPEN TX OPEN RS/485 module for integrating third-party systems and devices to DESIGO (V4 or higher) TXI1.OPEN Platform to integrate third-party systems and devices to the DESIGO building automation and control system (Version 4 or higher) Suitable for operation using pre-defined applications from Siemens or using in-house developed applications USB interface for connecting the TX OPEN Tool Compact design per DIN Easy installation and setup Plug-in screw terminals Power from Island bus (DC 4 V) Simple, fast diagnostics CMN8185en_0 5 Nov 009 Building Technologies
2 Function The TX OPEN RS/485 module integrates third-party systems via RS or RS485 interface to the DESIGO building automation and control system. The required applications are loaded onto the module via the USB interface. Siemens offers finished applications for the following systems: Modbus (Engineering guide CM110571) M-bus (Engineering guide CM11057) SED (Engineering guide CM11057) Additional applications are currently being prepared You may also develop your own applications using Microsoft embedded Visual C++ 4.0, see Developer's guideline for the TXI1.OPEN, CM The TX OPEN RS/485 module is powered directly with DC 4 V from the island bus. A webpage that may be viewed in the web browser via the USB interface, displays the interface configuration and values from the third-party system / device. The TX OPEN Tool supports the download of firmware and applications as well as the configuration data. Type summary Product No. Stock number Designation TXI1.OPEN S55661-J100 TX OPEN RS/485 module Accessories Configuration software TX OPEN Tool (Please contact your regional company for orders) Ordering When ordering, please specify the quantity, designation, product number and stock number. Example: 10 TX OPEN RS/485 Module TXI1.OPEN, S55661-J100 Equipment combinations Note: Version.7 The TX OPEN RS/485 module is suitable for using an island-bus capable automation station, i.e. in plants with version 4 or higher. For plants with versions up to.7, only I/O OPEN modules from the PT-I/O range are suitable.. / 8
3 Design and technology Overview F 1 TX RX GND _ + RUN B A G RS RS485 D E C G x10 x1 Address COM 1 4 F Key A Plug-in screw terminal for RS and RS485 (Changeover via software) Terminal RS RS485 1 TX + RX GND (Potential equalization) B LED "RUN" Power OK C LED COM Communication (RS) D USB connection for TX OPEN Tool E Rotary switches to set module address G 8185Z01_01 F G Bus connector Attachment slider for standard rails Mechanical properties Housing The housing complies with DIN 4880 and is 96 mm wide. During mounting, ensure sufficient convection (max. ambient temperature 50 C). Electrical properties Power Interfaces Island bus System ground Protection against incorrect wiring The TX OPEN RS/485 module is powered directly with DC 4 V from the island bus. No separate power required. Plug-in screw terminal for serial interfaces RS and RS485 USB plug type B for connecting the TX OPEN Tool The TX OPEN RS/485 module has contacts on the left and right side of the housing for the island bus. The module is plugged in between existing modules or attached at the end of a I/O row. The serial interfaces RS / RS485 are electrically isolated from the island bus side. The connected third-party system may be earthed. All terminals are protected against short circuit and incorrect wiring using AC/DC 4 V. Side bus connector: No protection Voltage higher than AC / DC 4 V: No protection / 8
4 Interfaces General RS RS485 Bus terminator Serial interfaces are electrically isolated The serial interfaces use the same connection terminals. You can use either RS or RS485 (Changeover via software). The interface supports baud rates from 00 to Baud. The signals RXD and TXD are available, but without handshake signals. The interface supports baud rates of 9600 and 1900 Baud. You can switch up a bus termination via software in the I/O OPEN module (1nF, 10 Ohm in series). Signaling RUN (green) COM (green) LED displays power is available and sufficient. This LED displays communications on the RS side. Address switch The module address is switched using the two rotary switches. The factory setting is 00 (the TX OPEN RS/485 module is inactive). Corresponds to a open address key in an I/O module. Related documents Document Number [1] TX OPEN developer's guideline CM [] TX-OPEN Modbus engineering CM [] TX OPEN M-bus engineering CM11057 [4] TX OPEN SED engineering CM11057 [5] TX OPEN Tool online help -- [6] TX-I/O module, data sheets CM1N [7] TX-I/O Planning and installation manual CM11056 Disposal The device is classified as waste electronic equipment in terms of the European Directive 00/96/EC (WEEE) and should not be disposed of as unsorted municipal waste. The relevant national legal rules are to be adhered to. Regarding disposal, use the systems setup for collecting electronic waste. Observe all local and applicable laws. 4 / 8
5 Mounting Fixings Order Exchange Permissible mounting positions The device is mounted on a standard rail 5 x 7.5 mm (tophat rails TH5-7.5 per EN60715) The device can be plugged into any position on the I/O row. One TX OPEN RS/485 module may be removed from the row of modules. Please note, however, that the island bus and power is interrupted for all subsequent modules. TX-I/O devices can be mounted in any position: You must ensure, however, that sufficient ventilation is available to maintain the permissible ambient temperature (max. 50 C). Technical data Operating voltage Power consumption Power from the island bus. No separate power required. DC 4 V 55 ma / 1. W Protection against shortcircuit Side bus connector No protection! and incorrect wiring Serial interfaces Protection against surges to AC/DC 4 V and short circuits Electronic isolation from island bus GND RS4/485 interface You can switch up a bus termination via software in the I/O OPEN module (1nF, 10 Ohm in series) USB interface Plug Type B (USB device) Data rate (USB 1.0 full speed) 1 MBit/s Electronic isolation from island bus GND No Protective switch against surges and over current Yes Connection terminals, plug-in Mechanical design Copper wire or copper stranded wires with ferrules Copper stranded wires without ferrules Screwdriver Maximum stud torque Plug-in screw terminal 1 x 0.6 mm to.5mm or x 0.6 mm to 1,0 mm 1 x 0.6 mm to.5 mm or x 0.6 mm to 1,5 mm Flat screwdriver size 1 with shaft ø 4.5 mm 0.6 Nm 5 / 8
6 Classification per EN 6070 Function of automatic control devices Degree of pollution Mechanical design Housing type IP class per EN 6059 Front parts in DIN excerpt terminal part Type 1 Protection class III IP0 IP0 Environmental conditions Standards, directives and approvals Operation Climatic conditions Temperature Humidity Mechanical conditions Transport Climatic conditions Temperature Humidity Mechanical conditions Product safety Automatic electrical controls devices for household and similar use Electromagnetic compatibility Immunity Industrial sector Emissions Residential, Light industry CE conformity Electromagnetic compatibility Low-voltage directive c-tick conformity as per Australian EMC Framework Radio Emission Standard UL approval (UL 916) As per IEC Class K C 5 95 % r.f Class M As per IEC Class K C 5 95 % r.f Class M EN EN EN /108/EC 006/95/EC Radio Communication Act 199 AS/NZS M5 Color Housing Light gray, RAL 705 Dimensions Housing as per DIN 4 880, see dimensions Weight With / without packaging 10g / 168g 6 / 8
7 Dimensions Dimensions in mm M01 7 / 8
8 8 / Siemens Switzerland Ltd Subject to change
Digital input modules
8 172 TX-I/O Digital input modules TXM1.8D TXM1.16D Two fully compatible versions: TXM1.8D: 8 inputs, each with a three-color LED (green, yellow or red) TXM1.16D: As TXM1.8X, but 16 inputs, each with a
More informationFor UK only RXL39.1 and the applications package SP-03 are sold in the United Kingdom only.
s For UK only RX39.1 and the applications package SP-03 are sold in the United Kingdom only. 3 876 3876P01 RX Room controller Communicating controllers for fan-coil applications SP-03 RX39.1 The RX39.1
More informationBACnet router for BACnet/IP BACnet/LonTalk BACnet MS/TP
s 9 270 Desigo PX BACnet router for BACnet/IP BACnet/LonTalk BACnet MS/TP PXG3.L PXG3.M Routing between BACnet/IP, BACnet/LonTalk (PXG3.L only), and BACnet MS/TP Supports BACnet/IPv4 and BACnet/IPv6 ANSI/ASHRAE
More informationPCS0100en 02.2008. Persy Control Services B.V. Netherlands
P-Bus Gateway PBGW2.128 Universal gateway between the P-bus protocol and open standard protocols. The variety of available electrical interfaces on the gateway offers a wide range of possibilities for
More informationSEZ220. Signal Converter. Synco 200. With preprogrammed standard applications Freely programmable Menu-driven operation. Use
s 5 146 Synco 200 Signal Converter SEZ220 With preprogrammed standard applications Freely programmable enu-driven operation Use The signal converter is for use in HVAC plant to provide minimum / maximum
More informationProduct and Applications Description. Application Programs. Example of Operation. GAMMA instabus Technical Product-Information.
Product and Applications Description The power supply units N 125/x2 can supply DC 24 V power from an additional pair of terminals (yellowwhite). This DC 24 V output voltage can be used to power e.g. an
More informationIntesisBox Modbus Server Fidelio IP
IntesisBox Server Fidelio IP Gateway for integration of Micros Fidelio Ho management system into (RTU and TCP) enabled control systems. Integrate your Micros Fidelio Ho management system into your master
More informationis then retained absolutely without interruption.
Page 1 of 11 DC UPS uninterruptible power supplies - DC UPS module 15 A Compact design, only 50 mm wide Absolutely interruption-free buffering of power failures through immediate electronic connection
More informationRDJ10RF/SET. Wireless room temperature controller with 24-hour time switch and LCD. Programmable, for heating systems
3 072 RDJ10RF RCR10/433 Wireless room temperature controller with 24-hour time switch and LCD Programmable, for heating systems RDJ10RF/SET Operating modes: Automatic, Comfort, Energy Saving, and Frost
More informationIntesisBox Modbus Server SAMSUNG Air Conditioners
IntesisBox Modbus Server SAMSUNG Air Conditioners Gateway for monitoring and control of Samsung NASA compatible Air Conditioning Systems from any Modbus master device TCP or RTU (BMS, PLC, SCADA, HMI,
More informationRRV934. Multi-controller. Synco living
s 2 709 Synco living Multi-controller RRV934 RF-based multi-controller For precontrol of up to 2 room groups For control of ventilation plant with up to 3 stages RF communication based on KNX standard
More informationOZS164... Web server. For LPB/BSB plants
s 5 711 Web server For LPB/BSB plants OZS164... Remotely operate and monitor a LPB or BSB device Web browser operation via PC/laptop or Smartphone SMS operation via mobile phone (OZS164.23) 2 digital inputs
More informationWaveguide Access Point WGA631. Product Guide
Waveguide Access Point Product Guide Waveguide Access Point Contents 1. Description............................ 3 2. Application............................ 3 3. Technical data... 4 4. Physical interfaces......................
More informationAutomation stations modular series
s 9 222 9222P01 DESIGO PX Automation stations modular series PXC...D PXC...-E.D PXA40- Freely programmable modular automation stations for HVAC and building services plants. Native BACnet automation station
More informationHCR3.2/.. Chipcard reader HOTEL SOLUTION
s 6 332 HOTEL SOLUTION Chipcard reader HCR3.2/.. Chipcard reader for hotel room access control Reads access code on chipcard Transfers access code to room controller Built-in optical display of messages
More informationPower Supply Unit, Primary Switched, Narrow Design MINI-PS-12-24DC/24DC/1
Power Supply Unit, Primary Switched, Narrow Design MINI POWER provides: Extra narrow design with widths of 22.5 mm, 45 mm, and 67.5 mm (0.886, 1.772, and 2.657 in.) Global use due to a wide-range input
More informationModular I/O System Analog and Digital Interface Modules
OPERATING INSTRUCTIONS Modular I/O System Analog and Digital Interface Modules Installation Operation Maintenance Document Information Document ID Title: Operating Instructions Modular I/O System Part
More informationIntesisBox KNX Modbus RTU master
IntesisBox KNX RTU master Gateway for integration of RTU devices into KNX control systems. Integrate RTU devices (Chillers, Roof Tops, electricity meters, heating floors, heat pumps, PLCs ) into KNX control
More informationProgrammable set for Ethernet Modbus/TCP in IP67 TI-BL67-PG-EN-2
Type code Ident no. 1545065 Number of channels 2 Dimensions (W x L x H) 108 x 145 x 77.5 mm CoDeSys-programmable acc. to IEC 61131-3 Cable max. 50 m between interface and read/write head 10/100 Mbps Male
More informationEZmoto V2. Product description Rev. 6 10/01/2014. EZmoto V2 Product description Rev.6 10/01/2014
EZmoto V2 Product description Rev. 6 10/01/2014 1 Contents 1. Overview... 3 2. Hardware Interface Description... 3 2.1 Main features of the EZmoto... 3 2.2 Hardware block diagram... 4 2.3 Internal Hardware
More informationIntesisBox KNX Mitsubishi Heavy Industries AC
IntesisBox KNX Mitsubishi Heavy Industries AC Gateway for integration of Mitsubishi Heavy Indsutries (MHI) Air Conditioners with KNX control systems. 1. Main Features Direct connection to KNX TP-1 (EIB)
More informationRedundancy Module QUINT-DIODE/40
Redundancy Module QUT DIODE provides: 00% decoupling of power supplies connected in parallel Can be installed in potentially explosive areas Load currents up to 60 A supported Easy assembly by snapping
More informationAccessories SUNNY REMOTE CONTROL
Accessories SUNNY REMOTE CONTROL Mounting Instructions SRC20-MO-IEN121010 IMEN-SRC20 Version 1.0 EN SMA Solar Technology AG 1 Information on this Document 1 Information on this Document Validity This
More informationPXM20-E. Operator unit DESIGO PX
9 234 DESIGO PX Operator unit PXM20-E Network-compatible operator unit for viewing and operating one or more DESIGO PX automation stations. High-grade display with adjustable contrast Simple key operation
More informationIntesisBox KNX LG Air Conditioning
IntesisBox KNX LG Air Conditioning Gateway for integration of LG Air Conditioners with KNX control systems. 1. Main Features Direct connection to KNX TP-1 (EIB) bus. Direct connection to LG outdoor unit
More informationAir damper actuators
4 634 OpenAir TM Air damper actuators GDB...1 GLB...1 Rotary version, / AC 230 V Electronic motor driven actuators for three-position and modulating control Nominal torque 5 Nm (GDB), 10 Nm (GLB) Mechanically
More informationVAV compact controller KNX / PL-Link
s 3 547 OpenAir VAV compact controller KNX / PL-Link Series E GDB181.1E/KN GLB181.1E/KN Networked compact controller featuring KNX (S-mode / LTE-mode) and PL- Link capability for plants with variable air
More informationKNX Panasonic Air Conditioners
IntesisBox KNX Panasonic Air Conditioners Gateway for Panasonic ECOi and PACi system integration into KNX networks Up to 30 Outdoor units Up to 64 Indoor units PA-AC-KNX-64/128 EIA485 U1U2 line U1U2 line
More informationElectronic timer CT-AHD.12 OFF-delayed with 1 c/o (SPDT) contact
Data sheet Electronic timer CT-AHD.12 OFF-delayed with 1 c/o (SPDT) contact The CT-AHD.12 is an electronic time relay with OFF-delay. It is from the CT-D range. With their MDRC profile and a width of only
More informationZC-24DO CANopen I/O Module: 24 Digital Outputs
Z-PC Line EN ZC-24DO CANopen I/O Module: 24 Digital Outputs Installation Manual Contents: - General Specifications - Technical Specifications - Installation Rules - Electrical connections - DIP-switches
More informationVoltage monitoring relays CM-ESS.2 For single-phase AC/DC voltages
Data sheet Voltage monitoring relays CM-ESS.2 For single-phase AC/DC voltages The CM-ESS.2 is an electronic voltage monitoring relay that provides reliable monitoring of voltages as well as detection of
More informationSTEP-PS/1AC/12DC/1.5. Extract from the online catalog. Order No.: 2868567. DIN rail power supply unit 12 V DC/1.5 A, primary switched-mode, 1- phase
Extract from the online catalog STEP-PS/1AC/12DC/1.5 Order No.: 2868567 DIN rail power supply unit 12 V DC/1.5 A, primary switched-mode, 1- phase Commercial data EAN 4046356292924 Pack 1 pcs. Customs tariff
More informationTM7BDM8B expansion block - TM7 - IP67-8 DI/DO - 24V DC - 0.5 A - M8 connector
Product datasheet Characteristics TM7BDM8B expansion block - TM7 - IP67-8 DI/DO - 24V DC - 0.5 A - M8 connector Main Range of product Product or component type Range compatibility Enclosure material Bus
More informationQFP910. Water detector. Building Technologies. CE1N2732en 2016-03-01. Synco living
2 732 Synco living Water detector QFP910 Wireless radio sensor to record water puddles RF communication based on KNX standard (868 MHz unidirectional) Battery operation with standard 1.5 V batteries Use
More informationOZW30. Central Unit SYNERGYR
2 841 SYNERGYR Central Unit OZW30 Collects billing data from the apartments. Generates an image of each apartment's heat consumption and makes it available for readout. Acts on room temperature control
More informationIntesisBox KNX - LON
IntesisBox KNX - Gateway for integration of devices into KNX systems. Integrate Air Conditioning from the main manufacturers (DAIKIN, Mitsubishi Electric, Mitsubishi Heavy Industries, Toshiba, Fujitsu,
More informationThree-phase monitoring relay CM-PFE
Data sheet Three-phase monitoring relay CM-PFE The CM-PFE is a three-phase monitoring relay that monitors the phase parameter phase sequence and phase failure in three-phase mains. 2CDC 251 005 S0012 Characteristics
More informationTX2123 RS485 TO ETHERNET ADAPTOR
TX2123 RS485 TO ETHERNET ADAPTOR Converts Datacomms between fibre optic Modbus TCP over Ethernet and hard-wired copper Modbus RTU over RS485 Fibre Optic MODBUS TCP/ IP Ethernet Copper MODBUS RTU RS485
More informationIntesisBox KNX Modbus TCP master
IntesisBox KNX TCP master Gateway for integration of TCP slave devices into KNX control systems. Integrate any TCP slave device into KNX. KNX TCP slave EIB Bus IntesisBox Ethernet slave LinkBoxEIB Configuration
More informationQFP910. Water detector. Building Technologies. CE1N2732en. Synco living
2 732 Synco living Water detector QFP910 Wireless radio sensor to record water puddles RF communication based on KNX standard (868 MHz unidirectional) Battery operation with standard 1.5 V batteries Use
More informationPHOENIX CONTACT - 2012-12-14. Features
Electronic monitoring relay for phase sequence, phase failure, and asymmetry monitoring Data sheet 101748_en_03 1 Description PHOEIX COTACT - 2012-12-14 Features Increasingly higher demands are being placed
More informationDifferential Pressure Sensors for air and non-corrosive gases, with calibration certificate
1 919 1919P01 1919P03 QBM65/C, QBM75-1U/C Differential Pressure Sensors for air and non-corrosive gases, with calibration certificate QBM751-1/C QBM65/C QBM75/C Highly accurate measurements with calibration
More information16-Port RS232 to USB2.0 High Speed Multi Serial Adapter (w/ Metal Case) Installation Guide
16-Port RS232 to USB2.0 High Speed Multi Serial Adapter (w/ Metal Case) Installation Guide 1. Introduction Thank you for purchasing this 16-Port RS232 to USB2.0 High Speed Multi Serial Adapter. It is an
More informationMILLENIUM INSTALLATION MANUAL NTR 735 A. Simple Automation Control Module (MAS)
MILLENIUM Table of contents 1. INTRODUCTION 1 2. HARDWARE DESCRIPTION 2 3. INSTALLATION 5 4. CONNECTION 6 5. USER SAFETY AND PROTECTION OF EQUIPMENT 8 1. Introduction The MILLENIUM series has been designed
More informationNI 9423. NI C Series Overview DATASHEET. 8-Channel Sinking Digital Input Module
DATASHEET NI 9423 8-Channel Sinking Digital Input Module 8-channel, 100 µs digital input 24 V logic, sinking digital input Compatible with NI CompactDAQ counters 250 Vrms, CAT II isolation 10-position
More informationHARTING econ 3000 Introduction and features
HARTING Introduction and features HARTING es, unmanaged, for installation in control cabinets General Description Features The Fast es of the product family HARTING are suitable for industrial applications
More informationCompactLogix Power Supplies Specifications
Technical Data CompactLogix Power Supplies Specifications 1768 CompactLogix Power Supplies Catalog Numbers 1768-PA3, 1768-PB3 1769 Compact I/O Power Supplies Catalog Numbers 1769-PA2, 1769-PB2, 1769-PA4,
More informationRM17TE 183...528 V AC. Main. Product or component type. Product specific application. Relay monitored parameters 250 V DC 5 A DC
Characteristics multifunction control relay RM17-TE - range 183..528 V AC Complementary Reset time Maximum switching voltage Minimum switching current Maximum switching current [Us] rated supply voltage
More informationSeries AMEPR30-AZ up to 2.5A AC-DC / DC-DC LED Driver / Converter
FEATURES: Click on Series name for product info on aimtec.com Models Single output Model Max Output Power (W) 1 AC-DC Constant Current or Constant Over temperature protection Voltage LED Driver Over current
More informationHARTING mcon 1000 Introduction and features
Introduction and features HARTING mcon 1000 es, managed, for mounting onto top-hat mounting rail in control cabinets General Description Features Supporting Ethernet (10 Mbit/s), Fast Ethernet (100 Mbit/s)
More informationSquare D Clipsal DIN-Rail Four-Channel Auxiliary Input Unit
Square D Clipsal DIN-Rail Four-Channel Auxiliary Input Unit SLCLE5504AUX for Use with Wired C-Bus Networks Instruction Bulletin Retain for future use. Square D Clipsal DIN-Rail Four-Channel Auxiliary Input
More informationABB i-bus KNX Switch Actuator, x-fold, 16 A, MDRC SA/S x.16.2.1, 2CDG1101xxR0011
Technical Data 2CDC505051D0205 ABB i-bus KNX Product description Switch Actuators SA/S x.16.2.1, 16 A are modular installation devices in ProM design for installation in the distribution board. They are
More informationOZW772... V2.0. Web server. Synco TM, Synco TM living
s 5 701 Web server Synco TM, Synco TM living OZW772... V2.0 The OZW772 web server allows for remote operation and monitoring of plants via the web and send faults and system reports to e-mail recipients.
More informationRISH CON - Hz. Salient Features : Application : Product Features: FREQUENCY TRANSDUCER
Application : The RISH CON - Hz transducer is used for frequency measurement. The output signal is proportional to measured frequency and is either load independent DC Current or load independent DC Voltage.
More informationVoltage monitoring relays CM-ESS.M For single-phase AC/DC voltages
Data sheet Voltage monitoring relays CM-ESS.M For single-phase AC/DC voltages The CM-ESS.M is an electronic voltage monitoring relay that provides reliable monitoring of voltages as well as detection of
More informationInstallation instructions CAN/RS232-USB interface CANfox EC2112 7390837 / 00 09 / 2010
Installation instructions CAN/RS232-USB interface CANfox UK EC2112 7390837 / 00 09 / 2010 Contents 1 Preliminary note 3 1.1 Symbols used 3 1.2 Warning signs used 3 2 Safety instructions 4 2.1 General 4
More informationFOSTCDR. Industrial Serial to Multimode Fiber Optic Converter PRODUCT INFORMATION B&B ELECTRONICS. Specifications Serial Technology
FOSTCDR pn 8684R1 FOSTCDR-0812ds page 1/5 Industrial Serial to Multimode Fiber Optic Converter Data Rates up to 115.2 kbps 2.5 Mile (4 km) Range 10 to 30 VDC Input Voltage Wide Operating Temperature 2000V
More informationOptions for ABB drives, converters and inverters. User s manual FDPI-02 diagnostics and panel interface
Options for ABB drives, converters and inverters User s manual FDPI-02 diagnostics and panel interface Table of contents Table of contents 3 1. FDPI-02 diagnostics and panel interface Safety..............................................
More informationCurrent valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw
4 937 DESIO Current valve for AC 24 V pulse/pause control of electrical loads up to 30 kw SEA45.1 Use The current valve is used for the control of electric heating elements in heating, ventilation and
More informationHow To Write A Librao Low Voltage Differential (Lvds) Module On An Nio 6585 Fuserio (Flexrio) Power Supply (Femaleseo) And Power Supply On An Iphone Or Ip
NI 6585 Specifications This document lists the specifications of the National Instruments 6585 FlexRIO low-voltage differential (LVDS) adapter module. Pair these specifications with your FPGA module specifications.
More informationApplication. Characteristics RTU560. Data Sheet Communication Unit 560CMD11. Communication Unit 560CMD11
Communication Unit 560CMD11 The SLC works as master for the RTU560 serial peripheral bus (I/O-Interface/ Wired-OR-Bus ). The MPU is responsible for the other tasks. The MPU handles the absolute time and
More informationIntesisBox. KNX SAMSUNG Air Conditioning. Gateway for integration of Samsung air conditioners into KNX control systems. RS485.
IntesisBox KNX SAMSUNG Air Conditioning Gateway for integration of Samsung air conditioners into KNX control systems. Integrate Samsung Air Conditioners into KNX. KNX EIB Bus IntesisBox RS485 MIM-B13x/B04A
More informationAutomation System TROVIS 6400 TROVIS 6493 Compact Controller
Automation System TROVIS 6400 TROVIS 6493 Compact Controller For panel mounting (front frame 48 x 96 mm/1.89 x 3.78 inch) Application Digital controller to automate industrial and process plants for general
More informationAXIS T81B22 DC 30W Midspan
INSTALLATION GUIDE AXIS T81B22 DC 30W Midspan ENGLISH About this Document This document includes instructions for installing AXIS T81B22 on your network. Previous experience of networking will be beneficial
More informationIntroduction. Features. Industrial 2 ports RS-422/485 with Surge PCI-Express Low Profile Serial Card
IPC-E2202SL Industrial 2 ports RS-422/485 with Surge PCI-Express Low Profile Serial Card Introduction SUNIX IPC-E2202SL, Industrial 2 ports RS-422/485 with Surge PCI-Express Low Profile Serial Card, allows
More informationRM35UA13MW. range 15..600 V. Main. Product or component type. Relay monitored parameters
Characteristics multifunction voltage control relay RM35-U - range 15..600 V Complementary Reset time Maximum switching voltage [Us] rated supply voltage Supply voltage limits Power consumption in W Main
More informationType: EASY719 DC RC Article No.: 274119. Ordering information Relay outputs Quantity 6 Power supply V DC 24 V DC. Description
Type: EASY719 DC RC Article.: 274119 Ordering information Relay outputs Quantity 6 Power supply V DC 24 V DC Description 12 digital inputs (4 inputs available as analog inputs) 6 relay outputs LCD display
More informationINPUT/OUTPUT MODULE CONVERT INPUTS AND OUTPUTS TO WIRELESS
VMC A4 INPUT/OUTPUT MODULE CONVERT INPUTS AND OUTPUTS TO WIRELESS PRODUCT DATA SHEET FEATURES RF to 0-10 VDC out, analogue or PWM Maximal 3 digital inputs to RF RF communication with other equipment Wireless
More informationRack mounted telephone- and leased line modem for industrial applications
Rack mounted telephone- and leased line modem for industrial applications TR-6 Rack modem for industrial PSTNand /-wire leased line applications The TR-6 is an analogue V. 9 -rack PSTN modem as well as
More informationHSP GmbH Zum Handwerkerhof 2 90530 Wendelstein Tel. 09129 / 2852-0 Fax: 09129 / 2852-11 Web: www.hsshsp.de EMAIL: HSP@hsshsp.de NTG-3000.
NTG-3000 Transducer Data Sheet Document Version 2.8 Page 1 of 10 Versions / Revisions: Document Creation Author Description version date 2.0 2012-07-25 P. Compensis First official version 2.1 2012-08-24
More informationHARTING mcon 3000 Introduction and features
Introduction and features HARTING mcon 3000 es, managed, for mounting onto top-hat mounting rail in control cabinets General Description Features The fully managed es of the product family HARTING mcon
More informationTelephone- and leased line modem for industrial applications TD-36
Telephone- and leased line modem for industrial applications TD-36 Modem for industrial PSTN- and leased line applications The TD-36 is an analogue V.34 PSTN modem as well as an industrial 2-wire leased
More informationDuct Humidity Transmitter
SDC-H Duct Humidity Transmitter Features Replaceable sensor element Humidity measurement for air ducts Minimum and maximum value memory 0 0V, 0 0mA or 0V, 4 0mA measuring signals selectable with jumpers
More informationInstallation Manual (English) Adjustable Active DP Terminator T1-Pepper Active RS485 segment termination for non-compliant cable
Installation Manual (English) Adjustable Active DP Terminator T1-Pepper Active RS485 segment termination for non-compliant cable Designed for use with the COMbricks SALT repeater All baudrates Redundant
More informationIFS SP-PoE Splitter User Manual
IFS SP-PoE Splitter User Manual P/N 1069176-EN REV 1.01 ISS 01JUL10 2011 UTC Fire & Security. All rights reserved. Content Overview 2 Package contents 2 Introduction 3 Product Specifications 3 Hardware
More informationProduct and functional description
Product and functional description The KNX / DALI gateway N 141/02 is a 4 MU wide, DINrail mounted KNX device with one DALI interface to which up to 64 DALI actuators (e.g. DALI ballasts) can be connected
More information48.12. 2 pole, 8 A Safety relay. Screw terminal. 35 mm rail (EN 60715) mounting. 2 CO (DPDT) 8/15 250/400 2,000 500 0.37 8/0.65/0.
48 Series - Relay interface modules 8 A Features 48.12 2 Pole Safety relay interface modules, 15.8 mm wide 48.12-2 Pole 8 A (screw terminal) DC sensitive coils Relay with forcibly guided contacts according
More informationCompactRIO crio-9052
OPERATING INSTRUCTIONS CompactRIO crio-9052 CompactRIO StarFabric Interface 1 POWER BACKUP STATUS FPGA V1 C V2 2 C Rx INPUT 9 35 V 17 W MAX 3 Tx NI crio-9052 CompactRIO StarFabric Interface 1 LEDs 2 Power
More informationConneXium Ethernet Switches TCSESU0 F N0 Quick Reference Guide
31007950 7/2009 ConneXium Ethernet Switches TCSESU0 F N0 Quick Reference Guide 7/2009 31007950.02 www.schneider-electric.com NOTICE Read these instructions carefully, and look at the equipment to become
More informationSemi flush-mount room thermostat with KNX communications For VAV heating and cooling systems
s 3 72 Semi flush-mount room thermostat with KNX communications For VAV heating and cooling systems RDU34 KNX bus communications (S-mode and LTE mode) Backlit display PI / P control Outputs for DC 0 0
More informationModbus Server SAMSUNG Air Conditioners
IntesisBox Server SAMSUNG Air Conditioners Gateway for monitoring and control of Samsung Air Conditioning Systems from any master device TCP or RTU (BMS, PLC, SCADA, HMI, TouchPanel ) Master TCP Master
More informationYour Advantages For safety application up to PL e / Cat. 4 e.g. SIL 3 Manual or automatic start 0225592. * see variants. Applications.
Safety Technique SAFEMASTER Emergency Stop Module BG 5924, IP 5924 Your Advantages For safety application up to PL e / Cat. 4 e.g. SIL 3 Manual or automatic start 0225592 BG 5924 IP 5924 Product Description
More informationStrato Pi Hardware Guide
Strato Pi Hardware Guide October 2015 Revision 001 a professional expansion board for Raspberry Pi 2 Introduction 3 Features 4 Usage and connections 5 Hardware Installation 5 Strato Pi boards 5 Strato
More informationQuick Connect. quick - simple - efficient. www.g-mw.de
Quick Connect quick - simple - efficient www.g-mw.de Phone: +49 9103 7129-0 Fax: +49 9103 7129-207 Innovative connection technology to plug three single-phase current transformers to multifunctional power
More informationABB i-bus KNX Fan Coil Actuator, MDRC FCA/S 1.1M, 2CDG 110 084 R0011
, 2CDG 110 084 R0011 2CDC 071 112 F0008 The Fan Coil Actuator is a modular installation device (MDRC) in pro M design. It is intended for installation in the distribution board on 35 mm mounting rails.
More informationconnecdim Gateway G1 Ethernet TCP/IP to DALI
Gateway G1 Ethernet TCP/IP to LI Independent lighting control for up to 256 LI gears on 4 LI lines Can be expanded by connecting multiple gateways on the same network Cloud based web interface for configuration
More informationR.C.C.B. s two-pole LEXIC
87045 LIMOGES Cedex Telephone : (+33) 05 55 06 87 87 Fax : (+ 33) 05 55 06 88 88 R.C.C.B. s two-pole LEXIC 089 06/09/10/11/12/15/16/17/18/ 27/28/29/30/35, CONTENTS PAGES 1. Electrical and mechanical characteristics...
More informationMINI MCR-SL-R-UI(-SP)
Resistance/potiposition transducer INTERFACE Data Sheet 0807_en_05 Description PHOENIX CONTACT - 0/008 Features The slim MINI MCR-SL-R-UI... potiposition transducer has a width of only 6. mm and converts
More information48 SERIES Relay interface modules 10 A
48 Relay interface modules 10 A 1 CO relay interface modules, mm wide Ideal interface for PLC and electronic systems Type 48.P3 1 CO 10 A s Type 48.31 1 CO 10 A s AC coils or DC sensitive coils Supply
More informationElectronic timer CT-VBS.17+18 OFF-delayed without auxiliary voltage, for DC contactors Data sheet
Characteristics Single-function OFF-delay timer for DC contactors, without auxiliary voltage Width.5 mm CDC 5 6 F3 Approvals A culus E CCC CT-VBS a Circuit diagram b Marker label Marks a CE b C-Tick Order
More informationVAV compact controller KNX / PL-Link
s 3 547 OpenAir VAV compact controller KNX / PL-Link Series E GDB181.1E/KN GLB181.1E/KN Networked compact controller featuring KNX (S-mode / LTE-mode) and PL- Link capability for plants with variable air
More informationTemperature monitoring relays CM-TCS Monitoring relays for monitoring temperatures with a PT100 sensor (2- or 3-wire connection)
Data sheet Temperature monitoring relays CM-TCS Monitoring relays for monitoring temperatures with a PT100 sensor (2- or 3-wire connection) The temperature monitoring relays CM-TCS monitor overtemperature,
More informationDVPPF02-H2. PROFIBUS DP Slave Communication Module Application Manual
DVPPF02-H2 PROFIBUS DP Slave Communication Module Application Manual Warning Please read this instruction carefully before use and follow this instruction to operate the device in order to prevent damages
More informationABB 1. Three-phase monitoring relay CM-PFS. Data sheet. Features. Approvals. Marks. Order data. Order data - Accessories. Application.
1SR 430 824 F9300 Features Monitoring of three-phase mains for phase sequence and failure Powered by the measuring circuit 2 c/o (SPDT) contacts 1 LED for status indication Approvals R: yellow LED - relay
More informationAXIS 291 1U Video Server Rack Installation Guide
AXIS 291 1U Video Server Rack Installation Guide About This Document This document describes how to install Axis blade video servers in the AXIS 291 1U Video Server Rack. Updated versions of this document
More informationPD30ETB20xxIS. Photoelectrics, Background Suppression reflective with IR light. Main features. Description
Photoelectrics, Background Suppression reflective with IR light Main features Description The PD30ET... stainless steel sensors are built with high-quality materials and designed for harsh environments.
More informationSafety technique. Emergency stop module BO 5988 safemaster
Safety technique Emergency stop module BO 5988 safemaster 0221562 Function diagram Pushbutton on Mains or emergencystop () K1 According to EC Directive for machines 98/37/EG According to IEC/E 60204-1
More information0.8 U N /0.5 U N 0.8 U N /0.5 U N 0.8 U N /0.5 U N 0.2 U N /0.1 U N 0.2 U N /0.1 U N 0.2 U N /0.1 U N
55 Series - General purpose relays 7-10 A Features 55.12 55.13 55.14 Printed circuit mount, general purpose 2, 3 & 4 Pole relays 55.12-2 Pole 10 A 55.13-3 Pole 10 A 55.14-4 Pole 7 A AC coils & DC coils
More informationPositive-guided relay outputs: 3 safety contacts (N/O), instantaneous. 1 auxiliary contact (N/C), instantaneous
Safety relay for monitoring E-STOP pushbuttons. Approvals Unit features Positive-guided relay outputs: 3 safety contacts (N/O), instantaneous 1 auxiliary contact (N/C), instantaneous Safe separation of
More informationPCAN-B10011S Bus Converter High-speed CAN to Truck Trailer CAN. User Manual. Document version 2.1.0 (2013-11-15)
PCAN-B10011S Bus Converter High-speed CAN to Truck Trailer CAN User Manual Document version 2.1.0 (2013-11-15) Products taken into account Product Name Model Part number PCAN-B10011S IPEH-002041 CANopen
More information