A STUDY OF NATURAL VENTILATION OF PUBLIC HOUSING IN SINGAPORE USING COMPUTATIONAL FLUID DYNAMICS (CFD) SIMULATIONS

Size: px
Start display at page:

Download "A STUDY OF NATURAL VENTILATION OF PUBLIC HOUSING IN SINGAPORE USING COMPUTATIONAL FLUID DYNAMICS (CFD) SIMULATIONS"

Transcription

1 , Volume 2, Number 2, p.35-45, 2001 A STUDY OF NATURAL VENTILATION OF PUBLIC HOUSING IN SINGAPORE USING COMPUTATIONAL FLUID DYNAMICS (CFD) SIMULATIONS N.H. Wong and A. Loke Department of Building, School of Design and Environment, National University of Singapore, Singapore (Received 22 March 2001; Accepted 19 June 2001) ABSTRACT The aim of this paper is to discuss the application of CFD for the study of natural ventilation of public housing flats in Singapore. The flat types chosen for this study include the 3-room and 4-room flats. Two cases are simulated based on these flat types, one having the internal doors closed and the other opened. The results show that naturally ventilated flats are able to achieve reasonable ventilation performance especially when the internal doors within the flats are opened for cross-ventilation. When the internal doors are closed, the ventilation performance drops drastically especially in the bedrooms which are side-sided ventilated. The results have also demonstrated that a reasonable degree of accuracy can be attained in the CFD simulations when the results obtained are compared with the field measurements. 1. INTRODUCTION Singapore is an island city-state where a multiracial population of 3.9 million live and work on a landmass of less than 648 km 2 to create a nation that enjoys one of the highest living standards in the world. On an island that is devoid of natural resources, the country has only one valuable resource to tap on, its human resources. Singapore is presently reviewing its land uses based on an estimated population of five million. In order to accommodate the rising demographic population under the huge constraint of limited land, the only option is to move upwards. With the move in this vertical fashion, the issue of ventilation comes into discussion. The ventilation of a building can be either natural or artificial. Natural ventilation, put simply is the air movement, which is caused by pressure or temperature differences across building apertures. Mechanical ventilation, on the other hand is the energy-driven alternatives to natural ventilation, it uses fans and ducts to supply and extract air in localized areas. Air conditioning, another form of mechanical ventilation treats and supplies air. This method is particularly useful to cool air below ambient temperatures. The decision that designers make in regard to the natural ventilation is often one made with little information since natural ventilation is an area where many uncertainties exist. At present, the government is also studying the viability of having a central air-conditioning unit for the public residential dwellings. Somehow, recent development in mechanical ventilation have encouraged researchers to focus more on the use of mechanical ventilation as the solution for thermal comfort and health. However, the problem with mechanical ventilation is that it is energy intensive. Singapore, being an island endowed with no natural resources has to get supply from overseas markets. On the other hand, the use of natural ventilation as a solution for ventilation requires no such resources and is a much cheaper alternative. CFD simulation has been used very extensively for the studies of velocity and temperature distribution in an enclosure that is mechanically ventilated [1-6]. However, the use of CFD for the studies of natural ventilation is still limited [7-9]. This is partially due to the dynamic fluctuation of the wind speeds and directions. Furthermore, these parameters are also governed by many other factors such as the surrounding obstructions, terrain factors, geometrical configuration of the building etc [10]. This study therefore attempts to explore the potential of using CFD for the study of natural ventilation in public housing in Singapore. The study will involve two different flat types, i.e. 3- room and 4-room flats. In order to validate the CFD simulation results, site measurements are also conducted. The CFD software employed for the purpose of this study is Phoenics [11]. 2. METHODOLOGY 2.1 Buildings and Sites Selection Two different flat types were used in this study: 3- room and 4-room flat types that serve as the classic examples of residential high-rise HDB buildings in Singapore. The site plans of the 3-room and 4-35

2 room blocks are shown in Figs. 1 and 2. The 3- room flat block of 15 storeys high is surrounded by a number of high-rise blocks of equal height on the south-west, with a low-rise school located to its north-east. For the 4-room flat block, it is surrounded by a number of high-rise blocks on three sides except the eastern part, which is unobstructed. N omni-directional hot wire anemometers (Fig. 4) and their automatic logging meet the ASNI/ASHRAE [12] and ISO 7726 [13] specifications for accuracy and response time. The range of measurement of the hot wire anemometers used was 0.1 to 5 ms -1 with accuracy of 5 %. Sampling of the wind speed is taken at half an hour interval with an integration time of 180 seconds and the monitored results are then printed out every half hourly. In this case, 3-minute average wind speed data at half hourly intervals was obtained. The anemometers were also placed on the outside of the windows that are used for the establishment of the boundary conditions of the inlets in the CFD modeling. Another hot wire anemometer was also placed at the rooftop to track the wind speeds and directions that were assumed to be unobstructed. Housing blocks Location of site measurement Fig. 1: Site plan of the 3-room flat block N Fig. 3: DANTEC multi-channel flow analyzer Housing blocks Location of site measurement Fig. 2: Site plan of the 4-room flat block 2.2 Field Studies DANTEC multi-channel flow analyzer type 54N10 (see Fig. 3) with 12 hot wire anemometers were used to measure the wind velocities within each room of the investigated units as well as the outdoor wind condition. The transducers were Fig. 4: Omni-directional hot-wire anemometer The plan of each dwelling unit and the positioning of the indoor sensors are shown in Figs. 5 and 6, with measuring points placed near the windows and at the center of each room. The measurements were taken at a height of 1.5 m above the floor level, which is almost half the height of the ceiling of the room and represents the approximate height 36

3 of occupants at standing level. The windows of each unit investigated are widely opened to investigate the effect of cross ventilation. Measurements were done for two conditions: internal door fully opened to determine the effect of cross ventilation; and internal door fully closed. The measurements were carried out over two days from 9 a.m. to 10 p.m. The characteristics of the investigated units and the measuring periods are summarized in Table 1. Table 1: Data for investigated dwellings Flat type Housing estate Measuring period Floor of the building Measuring time 3-room ST George s Lane June 22 nd 23 rd 7 th 9 a.m. 10 p.m. 4-room Ang Mo Kio June 2 nd 3 rd 11 th 48 hrs for 2 days W1 Door-BAT1 8 N W2 Door-BAT m Door-MB Door-SR 3 Door-BR W3 6 m W4 Fig. 5: Plan of 3-room flat and locations of indoor sensors 37

4 W1 N Door-BAT1 9 W3 W2 Door-BAT Door-BR2 6 Door-MB Door-BR m 1 7 W5 4.5 m W4 Fig. 6: Plan of 4-room flat and locations of indoor sensors 2.3 CFD Simulations Grid Structure and Boundary Conditions A simulation domain size of 6.00 m in the X- direction, m in the Z-direction and 2.45 m in the Y-direction was used for the modeling of the 3- room flat. For the 4-room flat, the simulation domain size of 9 m along the X-axis, m along the Z-axis and 2.45 m along the Y-axis was adopted. The grid structures used in the four simulations are shown in Table 2. All floors and walls are defined as BLOCKAGE and made of concrete block with medium weight and adiabatic in nature. All inlets and outlets are defined as OPENING. The degree of opening of the internal doors as well as the crack width at the top and bottom of the doors were measured on site and modeled accordingly. Since measurement of the temperatures in the vertical profile shows that the difference is very minimal, the buoyancy effect is ignored. Table 3 shows the boundary conditions used in the four cases Assumptions 3-Dimensional steady state flow. 38

5 Table 2: Grid distribution for the simulations Cases Grid distribution X-direction Y-direction Z-direction C C C C Table 3: Boundary conditions for the 3-room and 4-room flat Cases Case 1 Case 2 Case 3 Case 4 Inlet velocity (ms -1 ) W2 (Z-direction) W5 (Z-direction) W1 (Z-direction) W4 (Z-direction) Angle of openings of internal doors (degree) Door-MB Door-BR Door-BR Door-BR Door-BAT Door-BAT Door-SR Crack Width when internal doors are closed (mm) All structural elements like floors, walls etc are assumed to be adiabatic in nature. The effects of gravity were disregarded in order to achieve a more speedy convergence since such forces would have minimum impact on the simulations. k-e turbulence model. Other than the inlets and outlets, all other external leakage paths are ignored. The global convergence criterion is taken as 0.001%. 3. DATA ANALYSIS 3.1 Overview The analysis will be covered in 3 aspects: Analysis of the individual cases Comparison between the two cases Comparison between simulation results and site measurements. Since the results obtained from the CFD simulations are in terms of absolute air velocities, this would render the comparisons between different cases difficult as the boundary conditions used in each case are different. A common approach is to use the concept of velocity coefficient (C v ) by normalizing the velocity at each point with a reference velocity. The formula is shown below: C v = V 1 /V 2 where V 1 is the velocity at the point of interest, and V 2 is the reference velocity. In this case, the reference velocity is obtained from site measurement at the rooftop, in which the average 3-minute wind speed data was recorded concurrently with that obtained for the indoor points. 39

6 3.2 3-Room Cases Fig. 7 and Table 4 show the velocity distribution and C v of the 3-room flat with the internal doors closed (Case 1). It can be seen that cross ventilation occurs effectively between the Living Room and Kitchen since their windows are directly facing each other. This has contributed to the high C v of 0.9 for both the Living Room and Kitchen. For the Master Bedroom, even though the window is facing the prevailing wind, the airflow within the room is minimal. This has contributed to a low C v of 0.2. The closing of the internal doors has prevented cross ventilation from taking place. Bedroom 1 has the lowest C v of 0.1. Being situated in the leeward side of prevailing wind and the door being closed, there is adequate reason for the dire state that this room is experiencing. The only airflow experienced in this room is due to the infiltration through the internal door of the bedroom. Fig. 8 and Table 4 show the velocity profile and C v of the 3-room flat with the internal doors opened (Case 2). For the Living Room and Kitchen, cross ventilation is further enhanced with the opening of internal doors resulting in the high C v of 1.0 and 1.5 respectively. The higher C v of Kitchen indicates that some of the airflow from the Kitchen are being diverted to Bedroom 1. With the opening of the internal door of Master Bedroom, the C v has increased to 0.5. However, the C v is the lowest among the rooms. For Bedroom 1, there is a drastic improvement of C v from 0.1 to 1.4 when the internal door is opened. The velocity profile shows that air from both Kitchen and Master Bedroom is channeled into Bedroom 1. A close examination of the two cases in Table 4 shows that Case 2 performed much better than Case 1 in terms of C v values. The C v values of all the rooms show an increase, with the greatest increase in Bedroom 1 of almost 93%. In the Living Room, the increase in C v is little, from 0.9 to 1.0 (10% improvement). Case 2 shows a 40% increase in the C v value for the Kitchen. In the Master Bedroom, the room enjoys better ventilation when the internal door is opened, evidenced by the 60% rise in the C v. However, even with the opening of the internal door, the ventilation condition in Master Bedroom is still fared badly with respect to the other rooms. This could be explained by the orientation of the window opening in relation to the door opening. It is apparent that when the internal door is opened, the room is able to have more significant airflow. However, the effect of cross-ventilation does not have much of an impact, given the fact that the fresh air coming from the inlet does not cover some areas of the room before leaving the room through the door opening. With regard to Bedroom 1, this room definitely benefits from the opening of the internal door. Having a 93% rise in C v value is clear instance of how cross-ventilation is helping to improve the ventilation condition of this room. The vectors diagram (Fig. 8) shows that the bedroom not only enjoys the airflow coming from the Master Bedroom, but also from the Living Room due to the proximity of the door opening to the path of the main airflow from the Kitchen. Under such favorable condition, there is no doubt that this room is well ventilated Room Cases Fig. 9 and Table 5 show the velocity distribution and C v of the 4-room flat with the internal doors closed (Case 3). For the Living Room, the vector diagram shows that the main path of airflow is from the Living Room s window to the Kitchen s window. Since the two windows are not directly opposite each other, there is a turning of the air currents at the side of the Master Bedroom. This has resulted in the reduction of the effectiveness of the cross ventilation with the Living Room having a low C v of 0.5. The Kitchen, on the other hand, is better ventilated having a higher C v of 0.9. The Master Bedroom has a C v of only 0.05 indicating that there is barely any airflow inside the room. This can be explained by the fact that the bedroom door is orientated towards the Storeroom instead of the Living Room. Thus, the room is not able to experience the infiltration from the Living Room. For Bedroom 2, this room is again under-ventilated having a low C v of only 0.1. However, it is better ventilated than the Master Bedroom since infiltration can occur from both the Living Room and Bedroom 3 due to the orientation of the bedroom door. The ventilation in Bedroom 3 is reasonable, considering that it shares the same C v of 0.5 for the Living Room. Table 4: Comparison of C v in 3-room flat with internal doors opened and closed Room types Case 1 Case 2 % Improvement C v C v [(Case 2 Case 1)/Case 1] x 100% Living Room % Kitchen % Master Bedroom % Bedroom % 40

7 Average % Fig. 7: Velocity distribution in 3-room flat with internal doors closed (Case 1) Fig. 8: Velocity distribution of the 3-room flat with internal doors opened (Case 2) 41

8 Fig. 10 and Table 5 show the velocity profile and C v of the 4-room flat with the internal doors opened (Case 4). For the Living Room, it is surprised to see that the opening of the internal doors has resulted in a slight reduction of C v from 0.5 to 0.4. A close examination of the velocity profile reveals that the opening of the internal doors has minimal effect on the cross ventilation that occurs between the Living Room and Kitchen. As for the Kitchen, the C v has reduced from 0.9 to 0.4. The Master Bedroom is the worst ventilated, having the lowest C v of 0.1. The obvious reason is again due to the location of the door that does not allow much air to enter the room. Instead, the projecting edge of the Master Bedroom deflects the air away to the direction of the Storeroom. The airflow in the room is induced in this case by the suction effect of the airflow passing through the door of the bedroom. The ventilation in Bedroom 2 is slightly better than the Master Bedroom having a C v of 0.2. The velocity vectors in this room indicate that the airflow comes mainly from Bedroom 3 with some airflow channeled from the Living Room. For Bedroom 3, being situated opposite Bedroom 2, this room has a higher C v of 0.3. This can be due to the fact that the windows here are windward and that the door of the Bedroom is facing that of Bedroom 2. This allows cross ventilation to occur effectively. A close examination of the two cases as shown in Table 5 shows that by opening the internal doors, C v values especially in the Living Room, Kitchen and Bedroom 3 have reduced. On the other hand, there is improvement for both Master Bedroom and Bedroom 2. The Kitchen shows the largest reduction in C v of 125%, followed by Bedroom 3 of 67% and Living Room of 25%. Both Master Bedroom and Bedroom 2 show improvement of 50%. Table 5: Comparison of C v in 4-room flat with internal doors opened and closed Room types Case 3 Case 4 % Improvement C v C v [(Case 2 Case 1)/Case 1] x 100% Living Room % Kitchen % Master Bedroom % Bedroom % Bedroom % Average % Fig. 9: Velocity distribution of the 4-room flat with internal doors closed (Case 3) 42

9 Fig. 10: Velocity distribution of the 4-room flat with internal doors opened (Case 4) 3.4 Comparative Analysis between the 3- Room Cases and the 4-Room Cases Comparing the C v values for 3-room and 4-room flats (Tables 4 and 5) under the close door condition, it can be seen that 3-room flat has better ventilation in most locations than the 4-room flat. For the Kitchen and Living Room of the 3-room flat, the vertical alignment of the windows of Kitchen and Living Room enhances cross ventilation resulting in high C v of 0.9 in both locations. However, this is not the case for the 4- room flat. This accounts for the low C v of 0.5 for the Living Room in 4-room flat. The Master Bedroom of 3-room flat also shows higher C v than that of the 4-room flat. This is due to the orientation of the door that faces Bedroom 1 and Living Room, thus promoting infiltration/ exfiltration to occur from/to both Living Room and Bedroom 1. However, in the case of 4-room flat, the door of the Master Bedroom is orientated towards the Store. As a result, it is unable to capture effectively the airflow from the Living Room. On the other hand, comparing Bedroom 1 of 3-room flat with Bedroom 3 of 4-room flat, Bedroom 3 shows a higher C v of 0.5 as compared to 0.1 in Bedroom 1. Comparing the C v values under the open door condition, it is obvious that the 3-room flat performs much better than the 4-room flat in all locations. By comparing the velocity profile between the two cases (Figs. 8 and 10), it can be seen that for 3-room flat, the opening of the door of Bedroom 1 has enhanced the cross ventilation between the Living Room, Kitchen as well as Bedroom 1. However, in the case of 4- room flat, this is not the case by opening the door of the Master Bedroom. The cross ventilation between Kitchen and Living Room is not enhanced. In this case, suction effect due to the airflow parallel to the door causes minor wind effect in the Master Bedroom. 3.5 Comparison of CFD Simulations with Field Measurements Figs. 11 and 12 show the comparison of the velocities at various locations between CFD simulations and field measurements for both 3- room and 4-room flats. The results show that in general, CFD simulations produce lower velocities than site measurements. For 3-room flat, the main deviations occur in points 4 and 5, which are located in Bedroom 1. For all the other points, the simulation results are comparable to that of the field measurements. With respect to the 4-room flat, the velocities obtained from CFD simulations are much closer to that obtained from field measurements except for point 5. The results show that the discrepancy tends to occur at the window locations at the leeward side of the flats. During the measurement, it was observed that the wind speed fluctuated quite significantly in these areas. This has added to the uncertainty in the comparison. 43

10 Wind Velocity (m/s) Location CFD-Case 1 Site Measurements - Case 1 CFD-Case 2 Site Measurements - Case 2 Fig. 11: Comparison of velocity between CFD simulations and site measurements for 3-room flat Velocity (m/s) Location CFD-Case 3 Site Measurements-Case 3 CFD-Case 4 Site measurements-case 4 Fig. 12: Comparison of velocity between CFD simulations and site measurements for 4-room flat 1. CONCLUSION The aim of this study is to provide an insight into the application of CFD techniques in the modelling of 3-room and 4-room public housing flats. Two cases are simulated for each flat type, in order to compare the difference in the overall ventilation performance of the unit, given that the internal doors are opened or closed. The results show that the CFD techniques could provide the designers very useful information in terms of the impact of flat layout on the velocity distribution so that optimum designs can be achieved to reap the full potential of the natural ventilation. The case studies on the two flat types demonstrated that the 3-room flat is better ventilated than the 4-room flat in both situations when the internal doors are opened and closed. The simulation results also show that when the bedroom doors are closed, the ventilation performance of bedrooms is drastically affected in most cases. This is primarily due to the fact that the rooms become single-sided ventilated. The studies also show that by strategically 44

11 orientating the bedroom door to face the direction where cross ventilation could occur, it can improve the airflow inside the room through better infiltration/ exfiltration. The finding has demonstrated that CFD techniques have the potential to predict airflow to a reasonable degree of accuracy. However, the accuracy achieved was attainable only with a certain level of familiarization of the CFD program employed and elementary knowledge of fluids dynamics principles. Judgment on the part of the user is required both in the CFD modelling process and in the interpretation of the CFD results. In the CFD modelling process, users need to establish the correct boundary conditions such as the wind direction and magnitude. This could prove to be difficult at times and such error made in the CFD simulations will manifest in the CFD results. 10. M. Grosso, Wind pressure distribution around buildings: a parametrical model, Energy and Buildings, Vol. 18 (1992). 11. PHOENICS on-line information system, CHAM LTD. 12. ASHRAE standard , Thermal environmental conditions for human occupancy, ASHRAE, GA, USA (1992). 13. ISO 7726:1985, Thermal environments instruments and methods for measuring physical quantities, International Standard Organisation (ISO), Geneva, Switzerland (1985). REFERENCES 1. W.K. Chow and W.Y. Fung, Numerical studies on the indoor air flow in the occupied zone of ventilated and air-conditioned space, Building and Environment, Vol. 31, No. 4, pp (1996). 2. P.J. Jones and P.E. O Sullivan, Development of a model to predict air flow and heat distribution in factories, SERC final report (1994). 3. H.B. Awbi and G.H. Gan, Predicting air flow and thermal comfort in offices, ASHRAE Journal, Vol. 36, No. 2, pp (1994). 4. K.W.D. Cheong, S.C. Sekhar, K.W. Tham and E. Djunaedy, Airflow pattern in air-conditioned seminar room, Indoor Air 99, Proc. 8th Int. Conf. on Indoor Air Quality and Climate, Vol. 2, pp (1999). 5. P.T. Williams, A.J. Baker and R.M. Kelso, Numerical calculation of room air motion - Part 3: Three dimensional CFD simulation of a full scale room air experiment, ASHRAE Transactions, Vol. 100, No. 1, pp (1994). 6. P.T. Williams, A.J. Baker and R.M. Kelso, Development of a robust finite element CFD procedure for predicting indoor room air motion, Building and Environment Vol. 29, No. 3, pp (1994). 7. G.H. Gan, Effective depth of fresh air distribution in rooms with single-sided natural ventilation, Energy and Buildings, Vol. 31, Issue 1, pp (2000). 8. K.A. Papakonstantinou, C.T. Kiranoudis and N.C. Markatos, Numerical Simulation of air flow field in single-sided ventilated buildings, Energy and Buildings, Vol. 33, Issue 1, pp (2000). 9. R. Southall and M. McEvoy, Validation of a computational fluid dynamics simulation of supply air ventilated windows, Durlin Conference, CIBSE. 45

Mechanical and Natural Ventilation

Mechanical and Natural Ventilation BBSE3006: Air Conditioning and Refrigeration II http://www.hku.hk/bse/bbse3006/ Mechanical and Natural Ventilation Dr. Sam C. M. Hui Department of Mechanical Engineering The University of Hong Kong E-mail:

More information

Eco Pelmet Modelling and Assessment. CFD Based Study. Report Number 610.14351-R1D1. 13 January 2015

Eco Pelmet Modelling and Assessment. CFD Based Study. Report Number 610.14351-R1D1. 13 January 2015 EcoPelmet Pty Ltd c/- Geoff Hesford Engineering 45 Market Street FREMANTLE WA 6160 Version: Page 2 PREPARED BY: ABN 29 001 584 612 2 Lincoln Street Lane Cove NSW 2066 Australia (PO Box 176 Lane Cove NSW

More information

CAN DEMAND CONTROLLED VENTILATION REPLACE SPACE HEATING IN OFFICE BUILDINGS WITH LOW HEATING DEMAND?

CAN DEMAND CONTROLLED VENTILATION REPLACE SPACE HEATING IN OFFICE BUILDINGS WITH LOW HEATING DEMAND? Topic B3: Control of indoor environment CAN DEMAND CONTROLLED VENTILATION REPLACE SPACE HEATING IN OFFICE BUILDINGS WITH LOW HEATING DEMAND? Axel CABLE 1,*, Mads MYSEN 1,2, Kari THUNSHELLE 1 1 SINTEF,

More information

5.14 COMPUTATIONAL MODELLING OF AIRFLOW IN URBAN STREET CANYON AND COMPARISON WITH MEASUREMENTS

5.14 COMPUTATIONAL MODELLING OF AIRFLOW IN URBAN STREET CANYON AND COMPARISON WITH MEASUREMENTS 5.14 COMPUTATIONAL MODELLING OF AIRFLOW IN URBAN STREET CANYON AND COMPARISON WITH MEASUREMENTS J. Pospisil 1,M. Jicha 1, A. Niachou 2 and M. Santamouris 2 1 Brno University of Technology, Faculty of Mechanical

More information

Essam E. Khalil khalile1@asme.org

Essam E. Khalil khalile1@asme.org AIR-CONDITIONING SYSTEMS DEVELOPMENTS IN HOSPITALS: COMFORT, AIR QUALITY, AND ENERGY UTILIZATION Essam E. Khalil khalile1@asme.org PROFESSOR OF MECHANICAL ENGINEERING, CAIRO UNIVERSITY, EGYPT Abstract

More information

Experimental Evaluation of the Discharge Coefficient of a Centre-Pivot Roof Window

Experimental Evaluation of the Discharge Coefficient of a Centre-Pivot Roof Window Experimental Evaluation of the Discharge Coefficient of a Centre-Pivot Roof Window Ahsan Iqbal #1, Alireza Afshari #2, Per Heiselberg *3, Anders Høj **4 # Energy and Environment, Danish Building Research

More information

Problem Statement In order to satisfy production and storage requirements, small and medium-scale industrial

Problem Statement In order to satisfy production and storage requirements, small and medium-scale industrial Problem Statement In order to satisfy production and storage requirements, small and medium-scale industrial facilities commonly occupy spaces with ceilings ranging between twenty and thirty feet in height.

More information

Energy Efficient Data Center Design. Can Ozcan Ozen Engineering Emre Türköz Ozen Engineering

Energy Efficient Data Center Design. Can Ozcan Ozen Engineering Emre Türköz Ozen Engineering Energy Efficient Data Center Design Can Ozcan Ozen Engineering Emre Türköz Ozen Engineering 1 Bio Can Ozcan received his Master of Science in Mechanical Engineering from Bogazici University of Turkey in

More information

CFD SIMULATION OF SDHW STORAGE TANK WITH AND WITHOUT HEATER

CFD SIMULATION OF SDHW STORAGE TANK WITH AND WITHOUT HEATER International Journal of Advancements in Research & Technology, Volume 1, Issue2, July-2012 1 CFD SIMULATION OF SDHW STORAGE TANK WITH AND WITHOUT HEATER ABSTRACT (1) Mr. Mainak Bhaumik M.E. (Thermal Engg.)

More information

Accurate Air Flow Measurement in Electronics Cooling

Accurate Air Flow Measurement in Electronics Cooling Accurate Air Flow Measurement in Electronics Cooling Joachim Preiss, Raouf Ismail Cambridge AccuSense, Inc. E-mail: info@degreec.com Air is the most commonly used medium to remove heat from electronics

More information

Development of Ventilation Strategy in Diesel Engine Power Plant by Using CFD Modelling

Development of Ventilation Strategy in Diesel Engine Power Plant by Using CFD Modelling Development of Ventilation Strategy in Diesel Engine Power Plant by Using CFD Modelling Panu Mustakallio and Risto Kosonen Halton Oy, Haltonintie 1-3, 47400 Kausala, Finland E-mail: panu.mustakallio@halton.com

More information

CFD Grows Up! Martin W. Liddament Ventilation, Energy and Environmental Technology (VEETECH Ltd) What is Computational Fluid Dynamics?

CFD Grows Up! Martin W. Liddament Ventilation, Energy and Environmental Technology (VEETECH Ltd) What is Computational Fluid Dynamics? CIBSE/ASHRAE Meeting CFD Grows Up! Martin W. Liddament Ventilation, Energy and Environmental Technology (VEETECH Ltd) 10 th December 2003 What is Computational Fluid Dynamics? CFD is a numerical means

More information

DESIGN OF NATURAL VENTILATION WITH CFD CHAPTER SEVEN. Qingyan Chen. difficult to understand and model, even for simple

DESIGN OF NATURAL VENTILATION WITH CFD CHAPTER SEVEN. Qingyan Chen. difficult to understand and model, even for simple CHAPTER SEVEN L. Glicksman and J. Lin (eds), Sustainable Urban Housing in China, 116-123 2006 Springer. Printed in the Netherlands. DESIGN OF NATURAL VENTILATION WITH CFD Qingyan Chen INTRODUCTION As the

More information

Effect of design parameters on temperature rise of windings of dry type electrical transformer

Effect of design parameters on temperature rise of windings of dry type electrical transformer Effect of design parameters on temperature rise of windings of dry type electrical transformer Vikas Kumar a, *, T. Vijay Kumar b, K.B. Dora c a Centre for Development of Advanced Computing, Pune University

More information

INTERNATIONAL JOURNAL OF MECHANICAL ENGINEERING AND TECHNOLOGY (IJMET)

INTERNATIONAL JOURNAL OF MECHANICAL ENGINEERING AND TECHNOLOGY (IJMET) INTERNATIONAL JOURNAL OF MECHANICAL ENGINEERING AND TECHNOLOGY (IJMET) Proceedings of the 2 nd International Conference on Current Trends in Engineering and Management ICCTEM -2014 ISSN 0976 6340 (Print)

More information

Thermal Mass Availability for Cooling Data Centers during Power Shutdown

Thermal Mass Availability for Cooling Data Centers during Power Shutdown 2010 American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). Published in ASHRAE Transactions (2010, vol 116, part 2). For personal use only. Additional reproduction,

More information

Validation of CFD Simulations for Natural Ventilation

Validation of CFD Simulations for Natural Ventilation Jiang, Y., Allocca, C., and Chen, Q. 4. Validation of CFD simulations for natural ventilation, International Journal of Ventilation, (4), 359-37. Validation of CFD Simulations for Natural Ventilation Yi

More information

CALCULATION AND ASSESSING NATURAL VENTILATION IN A SINGLE OPENING OFFICE ROOM WITH DIFFERENT WINDOWS IN THE REGIME OF HOT SUMMER AND COLD WINTER

CALCULATION AND ASSESSING NATURAL VENTILATION IN A SINGLE OPENING OFFICE ROOM WITH DIFFERENT WINDOWS IN THE REGIME OF HOT SUMMER AND COLD WINTER CALCULATION AND ASSESSING NATURAL VENTILATION IN A SINGLE OPENING OFFICE ROOM WITH DIFFERENT WINDOWS IN THE REGIME OF HOT SUMMER AND COLD WINTER Fang Ruan 1,2, Nianping Li 1,*, Jibo Long 1,2 1 College

More information

Supporting document to NORSOK Standard C-004, Edition 2, May 2013, Section 5.4 Hot air flow

Supporting document to NORSOK Standard C-004, Edition 2, May 2013, Section 5.4 Hot air flow 1 of 9 Supporting document to NORSOK Standard C-004, Edition 2, May 2013, Section 5.4 Hot air flow A method utilizing Computational Fluid Dynamics (CFD) codes for determination of acceptable risk level

More information

Effect of Rack Server Population on Temperatures in Data Centers

Effect of Rack Server Population on Temperatures in Data Centers Effect of Rack Server Population on Temperatures in Data Centers Rajat Ghosh, Vikneshan Sundaralingam, Yogendra Joshi G.W. Woodruff School of Mechanical Engineering Georgia Institute of Technology, Atlanta,

More information

EFA PSBP. Natural Ventilation Strategy. Introduction. 1.1 Relevant legislation. 1.1.1 The Building Regulations 2010

EFA PSBP. Natural Ventilation Strategy. Introduction. 1.1 Relevant legislation. 1.1.1 The Building Regulations 2010 EFA PSBP Natural Ventilation Strategy Introduction The Baseline Designs Project will provide scheme design details for a number of Primary and Secondary School Exemplars. For the purposes of setting a

More information

MODELLING COUPLED HEAT AND AIR FLOW: PING-PONG VS ONIONS

MODELLING COUPLED HEAT AND AIR FLOW: PING-PONG VS ONIONS MODELLING COUPLED HEAT AND AIR FLOW: PING-PONG VS ONIONS Jan Hensen University of Strathclyde Energy Systems Research Unit 75 Montrose Street, GLASGOW G1 1XJ, Scotland Email: jan@esru.strath.ac.uk SYNOPSIS

More information

TWO-DIMENSIONAL FINITE ELEMENT ANALYSIS OF FORCED CONVECTION FLOW AND HEAT TRANSFER IN A LAMINAR CHANNEL FLOW

TWO-DIMENSIONAL FINITE ELEMENT ANALYSIS OF FORCED CONVECTION FLOW AND HEAT TRANSFER IN A LAMINAR CHANNEL FLOW TWO-DIMENSIONAL FINITE ELEMENT ANALYSIS OF FORCED CONVECTION FLOW AND HEAT TRANSFER IN A LAMINAR CHANNEL FLOW Rajesh Khatri 1, 1 M.Tech Scholar, Department of Mechanical Engineering, S.A.T.I., vidisha

More information

Energy Efficient HVAC-system and Building Design

Energy Efficient HVAC-system and Building Design Energy Efficient HVAC-system and Building Design Maija Virta 1, Harri Itkonen 1, Panu Mustakallio 1, Risto Kosonen 1 1 Halton Oy, Finland Corresponding email: maija.virta@halton.com SUMMARY This paper

More information

Using Computational Fluid Dynamics (CFD) for improving cooling system efficiency for Data centers

Using Computational Fluid Dynamics (CFD) for improving cooling system efficiency for Data centers Data Centre Best Practises Workshop Using Computational Fluid Dynamics (CFD) for improving cooling system efficiency for Data centers Shishir Gupta 17 th March 2009 You are Here Introduction to CFD Data

More information

AIR STREAMS IN BUILDING FOR BROILERS

AIR STREAMS IN BUILDING FOR BROILERS AIR STREAMS IN BUILDING FOR BROILERS PAVEL KIC - MILAN ZAJÍČEK ABSTRACT The Fluent CFD software is used to do numerical analysis of existing poultry house during the summer and winter periods. Principal

More information

NEBB STANDARDS SECTION-8 AIR SYSTEM TAB PROCEDURES

NEBB STANDARDS SECTION-8 AIR SYSTEM TAB PROCEDURES NEBB STANDARDS SECTION-8 AIR SYSTEM TAB PROCEDURES 8.1 INTRODUCTION Testing, adjusting, and balancing of HVAC systems can best be accomplished by following a series of systematic procedures. The NEBB TAB

More information

HPPR Data Center Improvements Projects Towards Energy Efficiency (CFD Analysis, Monitoring, etc.)

HPPR Data Center Improvements Projects Towards Energy Efficiency (CFD Analysis, Monitoring, etc.) HPPR Data Center Improvements Projects Towards Energy Efficiency (CFD Analysis, Monitoring, etc.) Felipe Visbal / March 27, 2013 HPPR Data Center Technologies Team Services Data Centers: Thermal Assessments

More information

Opening the Bonnet. Prof Darren Woolf WYSINWYG 1

Opening the Bonnet. Prof Darren Woolf WYSINWYG 1 Opening the Bonnet Prof Darren Woolf WYSINWYG 1 WYSINWYG What You See Is NOT What You Get: Looking inside the Pandora s Box Prof Darren Woolf WYSINWYG 2 WYSIWYG implies a user interface that allows the

More information

Methods for Effective Room Air Distribution. Dan Int-Hout Chief Engineer, Krueger Richardson, Texas

Methods for Effective Room Air Distribution. Dan Int-Hout Chief Engineer, Krueger Richardson, Texas Methods for Effective Room Air Distribution Dan Int-Hout Chief Engineer, Krueger Richardson, Texas Agenda Overview LEED issues and Update Perimeter Acoustics Thermal Comfort IAQ / Standard 62.1 Update

More information

Analysis of the UNH Data Center Using CFD Modeling

Analysis of the UNH Data Center Using CFD Modeling Applied Math Modeling White Paper Analysis of the UNH Data Center Using CFD Modeling By Jamie Bemis, Dana Etherington, and Mike Osienski, Department of Mechanical Engineering, University of New Hampshire,

More information

OPTIMISE TANK DESIGN USING CFD. Lisa Brown. Parsons Brinckerhoff

OPTIMISE TANK DESIGN USING CFD. Lisa Brown. Parsons Brinckerhoff OPTIMISE TANK DESIGN USING CFD Paper Presented by: Lisa Brown Authors: Lisa Brown, General Manager, Franz Jacobsen, Senior Water Engineer, Parsons Brinckerhoff 72 nd Annual Water Industry Engineers and

More information

CFD STUDY OF TEMPERATURE AND SMOKE DISTRIBUTION IN A RAILWAY TUNNEL WITH NATURAL VENTILATION SYSTEM

CFD STUDY OF TEMPERATURE AND SMOKE DISTRIBUTION IN A RAILWAY TUNNEL WITH NATURAL VENTILATION SYSTEM CFD STUDY OF TEMPERATURE AND SMOKE DISTRIBUTION IN A RAILWAY TUNNEL WITH NATURAL VENTILATION SYSTEM J. Schabacker, M. Bettelini, Ch. Rudin HBI Haerter AG Thunstrasse 9, P.O. Box, 3000 Bern, Switzerland

More information

MacroFlo Opening Types User Guide <Virtual Environment> 6.0

MacroFlo Opening Types User Guide <Virtual Environment> 6.0 MacroFlo Opening Types User Guide 6.0 Page 1 of 18 Contents 1. Introduction...4 2. What Are Opening Types?...5 3. MacroFlo Opening Types Manager Interface...5 3.1. Add... 5 3.2. Reference

More information

Air distribution effectiveness with stratified air distribution systems

Air distribution effectiveness with stratified air distribution systems Lee, K.S., Jiang, Z., and Chen, Q. 2009 Air distribution effectiveness with stratified air distribution systems, ASHRAE Transactions, 115(2). Air distribution effectiveness with stratified air distribution

More information

CFD AND MULTI-ZONE MODELLING OF FOG FORMATION RISK IN A NATURALLY VENTILATED INDUSTRIAL BUILDING

CFD AND MULTI-ZONE MODELLING OF FOG FORMATION RISK IN A NATURALLY VENTILATED INDUSTRIAL BUILDING 2000 Elsevier Science Ltd. All rights reserved., Air Distribution in Rooms, (ROOMVENT 2000) Editor: H.B. Awbi 767 CFD AND MULTI-ZONE MODELLING OF FOG FORMATION RISK IN A NATURALLY VENTILATED INDUSTRIAL

More information

Fundamentals of CFD and Data Center Cooling Amir Radmehr, Ph.D. Innovative Research, Inc. radmehr@inres.com

Fundamentals of CFD and Data Center Cooling Amir Radmehr, Ph.D. Innovative Research, Inc. radmehr@inres.com Minneapolis Symposium September 30 th, 2015 Fundamentals of CFD and Data Center Cooling Amir Radmehr, Ph.D. Innovative Research, Inc. radmehr@inres.com Learning Objectives 1. Gain familiarity with Computational

More information

Software Development for Cooling Load Estimation by CLTD Method

Software Development for Cooling Load Estimation by CLTD Method IOSR Journal of Mechanical and Civil Engineering (IOSR-JMCE) ISSN: 2278-1684Volume 3, Issue 6 (Nov. - Dec. 2012), PP 01-06 Software Development for Cooling Load Estimation by CLTD Method Tousif Ahmed Department

More information

Unique Airflow Visualization Techniques for the Design and Validation of Above-Plenum Data Center CFD Models

Unique Airflow Visualization Techniques for the Design and Validation of Above-Plenum Data Center CFD Models Unique Airflow Visualization Techniques for the Design and Validation of Above-Plenum Data Center CFD Models The MIT Faculty has made this article openly available. Please share how this access benefits

More information

THERMAL LOSSES Thermal Losses Calculations

THERMAL LOSSES Thermal Losses Calculations Calculations -1- THERMAL LOSSES Thermal Losses Calculations Employer : 4M SA Project Location : ASHRAE Office Room : Example from ASHRAE 2013 Handbook - Fundamentals : Chapter 18, Single Room Example Peak

More information

ASTACEA4 Inspect complex/central air conditioning systems

ASTACEA4 Inspect complex/central air conditioning systems Overview This Unit covers the competences required to inspect complex/central air conditioning systems as defined by the CIBSE TM 44 Figure 1.1: Summary of system types and their component parts. The air

More information

SPECIAL ISSUE: NATIONAL SCIENCE FOUNDATION WORKSHOP

SPECIAL ISSUE: NATIONAL SCIENCE FOUNDATION WORKSHOP research journal 2013 / VOL 05.01 www.perkinswill.com SPECIAL ISSUE: NATIONAL SCIENCE FOUNDATION WORKSHOP ARCHITECTURE AND ENGINEERING OF SUSTAINABLE BUILDINGS Current Trends in Low-Energy HVAC Design

More information

Flow in data racks. 1 Aim/Motivation. 3 Data rack modification. 2 Current state. EPJ Web of Conferences 67, 02070 (2014)

Flow in data racks. 1 Aim/Motivation. 3 Data rack modification. 2 Current state. EPJ Web of Conferences 67, 02070 (2014) EPJ Web of Conferences 67, 02070 (2014) DOI: 10.1051/ epjconf/20146702070 C Owned by the authors, published by EDP Sciences, 2014 Flow in data racks Lukáš Manoch 1,a, Jan Matěcha 1,b, Jan Novotný 1,c,JiříNožička

More information

Energy Efficient Hospital Patient Room Design: Effect of Room Shape on Windowto-Wall Ratio in a Desert Climate

Energy Efficient Hospital Patient Room Design: Effect of Room Shape on Windowto-Wall Ratio in a Desert Climate Energy Efficient Hospital Patient Room Design: Effect of Room Shape on Windowto-Wall Ratio in a Desert Climate Ahmed Sherif Hanan Sabry Rasha Arafa Ayman Wagdy [Department of Construction and Architectural

More information

Adaptive strategies for office spaces in the UK climate

Adaptive strategies for office spaces in the UK climate International Conference Passive and Low Energy Cooling 631 Adaptive strategies for office spaces in the UK climate I. Gallou Environment & Energy Studies Programme, Architectural Association Graduate

More information

THE USE OF CFD APPLIED TO STUDIES OF VENTILATION IN URBAN AREAS IN CAMPINAS, BRAZIL OLIVEIRA, M.C.A 1 ; LABAKI, L.C. 2 ;VATAVUK,P.

THE USE OF CFD APPLIED TO STUDIES OF VENTILATION IN URBAN AREAS IN CAMPINAS, BRAZIL OLIVEIRA, M.C.A 1 ; LABAKI, L.C. 2 ;VATAVUK,P. Eleventh International IBPSA Conference Glasgow, Scotland July 27-30, 2009 THE USE OF CFD APPLIED TO STUDIES OF VENTILATION IN URBAN AREAS IN CAMPINAS, BRAZIL OLIVEIRA, M.C.A 1 ; LABAKI, L.C. 2 ;VATAVUK,P.

More information

Displacement ventilation

Displacement ventilation General The displacement ventilation principle is the oldest form of ventilation and can be achieved without the use of fans. Air movement occurs by means of the density differences between supply air

More information

HEAT TRANSFER ANALYSIS IN A 3D SQUARE CHANNEL LAMINAR FLOW WITH USING BAFFLES 1 Vikram Bishnoi

HEAT TRANSFER ANALYSIS IN A 3D SQUARE CHANNEL LAMINAR FLOW WITH USING BAFFLES 1 Vikram Bishnoi HEAT TRANSFER ANALYSIS IN A 3D SQUARE CHANNEL LAMINAR FLOW WITH USING BAFFLES 1 Vikram Bishnoi 2 Rajesh Dudi 1 Scholar and 2 Assistant Professor,Department of Mechanical Engineering, OITM, Hisar (Haryana)

More information

Natural Convection. Buoyancy force

Natural Convection. Buoyancy force Natural Convection In natural convection, the fluid motion occurs by natural means such as buoyancy. Since the fluid velocity associated with natural convection is relatively low, the heat transfer coefficient

More information

NUMERICAL INVESTIGATION OF HEAT AND MASS TRANSFER IN A REFRIGERATED TRUCK COMPARTMENT

NUMERICAL INVESTIGATION OF HEAT AND MASS TRANSFER IN A REFRIGERATED TRUCK COMPARTMENT NUMERICAL INVESTIGATION OF HEAT AND MASS TRANSFER IN A REFRIGERATED TRUCK COMPARTMENT T. LAFAYE DE MICHEAUX (a), V. SARTRE (a)*, A. STUMPF (b), J. BONJOUR (a) (a) Université de Lyon, CNRS INSA-Lyon, CETHIL,

More information

THERMAL STRATIFICATION IN A HOT WATER TANK ESTABLISHED BY HEAT LOSS FROM THE TANK

THERMAL STRATIFICATION IN A HOT WATER TANK ESTABLISHED BY HEAT LOSS FROM THE TANK THERMAL STRATIFICATION IN A HOT WATER TANK ESTABLISHED BY HEAT LOSS FROM THE TANK J. Fan and S. Furbo Abstract Department of Civil Engineering, Technical University of Denmark, Brovej, Building 118, DK-28

More information

Paul Linden & Guilherme Carrilho da Graça. NaturalWorks Inc

Paul Linden & Guilherme Carrilho da Graça. NaturalWorks Inc Building simulation Case Studies Paul Linden & Guilherme Carrilho da Graça NaturalWorks Inc www.natural-works.com Natural Ventilation Design San Francisco Federal Office Building MORPHOSIS San Francisco

More information

International Telecommunication Union SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES IN PUBLIC NETWORKS

International Telecommunication Union SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES IN PUBLIC NETWORKS International Telecommunication Union ITU-T TELECOMMUNICATION STANDARDIZATION SECTOR OF ITU Technical Paper (13 December 2013) SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES

More information

Air, Fluid Flow, and Thermal Simulation of Data Centers with Autodesk Revit 2013 and Autodesk BIM 360

Air, Fluid Flow, and Thermal Simulation of Data Centers with Autodesk Revit 2013 and Autodesk BIM 360 Autodesk Revit 2013 Autodesk BIM 360 Air, Fluid Flow, and Thermal Simulation of Data Centers with Autodesk Revit 2013 and Autodesk BIM 360 Data centers consume approximately 200 terawatt hours of energy

More information

AIR DISTRIBUTION FOR COMFORT AND IAQ

AIR DISTRIBUTION FOR COMFORT AND IAQ AIR DISTRIBUTION FOR COMFORT AND IAQ Heating Piping and Air Conditioning March 1998 Dan Int-Hout Chief Engineer KRUEGER EXCELLENCE IN AIR DISTRIBUTION Modern environmentally controlled spaces consume significant

More information

Ravi Kumar Singh*, K. B. Sahu**, Thakur Debasis Mishra***

Ravi Kumar Singh*, K. B. Sahu**, Thakur Debasis Mishra*** Ravi Kumar Singh, K. B. Sahu, Thakur Debasis Mishra / International Journal of Engineering Research and Applications (IJERA) ISSN: 48-96 www.ijera.com Vol. 3, Issue 3, May-Jun 3, pp.766-77 Analysis of

More information

NUMERICAL ANALYSIS OF THE EFFECTS OF WIND ON BUILDING STRUCTURES

NUMERICAL ANALYSIS OF THE EFFECTS OF WIND ON BUILDING STRUCTURES Vol. XX 2012 No. 4 28 34 J. ŠIMIČEK O. HUBOVÁ NUMERICAL ANALYSIS OF THE EFFECTS OF WIND ON BUILDING STRUCTURES Jozef ŠIMIČEK email: jozef.simicek@stuba.sk Research field: Statics and Dynamics Fluids mechanics

More information

CHAPTER 4 VENTILATION

CHAPTER 4 VENTILATION CHAPTER 4 VENTILATION SECTION 401 GENERAL 401.1 Scope. This chapter, in conjunction with the building code, shall govern the ventilation of spaces within a building intended to be occupied. Mechanical

More information

Express Introductory Training in ANSYS Fluent Lecture 1 Introduction to the CFD Methodology

Express Introductory Training in ANSYS Fluent Lecture 1 Introduction to the CFD Methodology Express Introductory Training in ANSYS Fluent Lecture 1 Introduction to the CFD Methodology Dimitrios Sofialidis Technical Manager, SimTec Ltd. Mechanical Engineer, PhD PRACE Autumn School 2013 - Industry

More information

MEASUREMENT AND CFD ANALYSIS OF UNSTEADY THERMAL ENVIRONMENT IN GYMNASIUM ADOPTED DISPLACEMENT AIR CONDITION SYSTEM

MEASUREMENT AND CFD ANALYSIS OF UNSTEADY THERMAL ENVIRONMENT IN GYMNASIUM ADOPTED DISPLACEMENT AIR CONDITION SYSTEM MEASUREMENT AND CFD ANALYSIS OF UNSTEADY THERMAL ENVIRONMENT IN GYMNASIUM ADOPTED DISPLACEMENT AIR CONDITION SYSTEM Koji Sakai 1, Yasutaka Murata 2, Ryutaro Kubo 3 Ryoichi Kajiya 1, and Osamu Ishihara

More information

How To Improve Energy Efficiency Through Raising Inlet Temperatures

How To Improve Energy Efficiency Through Raising Inlet Temperatures Data Center Operating Cost Savings Realized by Air Flow Management and Increased Rack Inlet Temperatures William Seeber Stephen Seeber Mid Atlantic Infrared Services, Inc. 5309 Mohican Road Bethesda, MD

More information

Effect of Aspect Ratio on Laminar Natural Convection in Partially Heated Enclosure

Effect of Aspect Ratio on Laminar Natural Convection in Partially Heated Enclosure Universal Journal of Mechanical Engineering (1): 8-33, 014 DOI: 10.13189/ujme.014.00104 http://www.hrpub.org Effect of Aspect Ratio on Laminar Natural Convection in Partially Heated Enclosure Alireza Falahat

More information

CFD MODELLING FOR SWIRL DIFFUSER AND ITS IMPLICATIONS ON AIR CHANGE EFFECTIVENESS ASSESSMENT TO GREEN STAR'S IEQ-2

CFD MODELLING FOR SWIRL DIFFUSER AND ITS IMPLICATIONS ON AIR CHANGE EFFECTIVENESS ASSESSMENT TO GREEN STAR'S IEQ-2 CFD MODELLING FOR SWIRL DIFFUSER AND ITS IMPLICATIONS ON AIR CHANGE EFFECTIVENESS ASSESSMENT TO GREEN STAR'S IEQ-2 Eddy Rusly 1 and Mirek Piechowski 2 1,2 Meinhardt (VIC), Melbourne, Australia ABSTRACT

More information

A NODAL MODEL FOR DISPLACEMENT VENTILATION AND CHILLED CEILING SYSTEMS IN OFFICE SPACES

A NODAL MODEL FOR DISPLACEMENT VENTILATION AND CHILLED CEILING SYSTEMS IN OFFICE SPACES A NODAL MODEL FOR DISPLACEMENT VENTILATION AND CHILLED CEILING SYSTEMS IN OFFICE SPACES Simon J. Rees and Philip Haves School of Mechanical & Aerospace Engineering, Oklahoma State University, Stillwater,

More information

Thermal environment in indoor spaces with under-floor air distribution systems: 1. Impact of design parameters (1522-RP)

Thermal environment in indoor spaces with under-floor air distribution systems: 1. Impact of design parameters (1522-RP) Lee, K.S., Xue, G., Jiang, Z., and Chen, Q. 0. Thermal environment in indoor spaces with under-floor air distribution systems:. Impact of design parameters (5-RP), HVAC&R Research, 8(6), 8 9. Thermal environment

More information

Virtual Data Centre Design A blueprint for success

Virtual Data Centre Design A blueprint for success Virtual Data Centre Design A blueprint for success IT has become the back bone of every business. Advances in computing have resulted in economies of scale, allowing large companies to integrate business

More information

EVALUATION OF PHOENICS CFD FIRE MODEL AGAINST ROOM CORNER FIRE EXPERIMENTS

EVALUATION OF PHOENICS CFD FIRE MODEL AGAINST ROOM CORNER FIRE EXPERIMENTS EVALUATION OF PHOENICS CFD FIRE MODEL AGAINST ROOM CORNER FIRE EXPERIMENTS Yunlong Liu and Vivek Apte CSIRO Fire Science and Technology Laboratory PO Box 31 North Ryde, NSW 167, Australia TEL:+61 2 949

More information

Supporting Cisco Switches In Hot Aisle/Cold Aisle Data Centers

Supporting Cisco Switches In Hot Aisle/Cold Aisle Data Centers CABINETS: ENCLOSED THERMAL MOUNTING MANAGEMENT SYSTEMS WHITE PAPER Supporting Cisco Switches In Hot Aisle/Cold Aisle Data Centers 800-834-4969 techsupport@chatsworth.com www.chatsworth.com All products

More information

Protocol for the Certification of Energy Simulation Software: First edition, December 2009

Protocol for the Certification of Energy Simulation Software: First edition, December 2009 Copyright Agrément South Africa, December 2009 The master copy of this document appears on the website: http://www.agrement.co.za Protocol for the Certification of Energy Simulation Software: First edition,

More information

Rate of Heating Analysis of Data Centers during Power Shutdown

Rate of Heating Analysis of Data Centers during Power Shutdown 2011. American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). Published in ASHRAE Transactions, Volume 117, Part 1. For personal use only. Additional reproduction,

More information

Information paper 20. Prepared by: David Clark. book:

Information paper 20. Prepared by: David Clark. book: Information paper 20 Ventilation rates in offices and natural mechanical Prepared by: David Clark A paper referenced in the book: Cundall Johnston & Partners LLP. 2013 Issue 1.0: 29 July 2013 This information

More information

Residential HVAC Load Sizing Training October 14, 2015. David Kaiser Green Code Plan Reviewer

Residential HVAC Load Sizing Training October 14, 2015. David Kaiser Green Code Plan Reviewer Residential HVAC Load Sizing Training October 14, 2015 David Kaiser Green Code Plan Reviewer DCRA - Green Building Division Regulations of green codes including: Green Building Act Green Construction Code

More information

How To Model With Cfd Using Phoenics

How To Model With Cfd Using Phoenics The Use and Application of CFD in the Air Conditioning and Fire Protection Industry AIRAH NSW February 2008 The Use and Application of CFD in the Air Conditioning and Fire Protection Industry An Introduction

More information

OPTIMIZATION OF VENTILATION SYSTEMS IN OFFICE ENVIRONMENT, PART II: RESULTS AND DISCUSSIONS

OPTIMIZATION OF VENTILATION SYSTEMS IN OFFICE ENVIRONMENT, PART II: RESULTS AND DISCUSSIONS OPTIMIZATION OF VENTILATION SYSTEMS IN OFFICE ENVIRONMENT, PART II: RESULTS AND DISCUSSIONS Liang Zhou, and Fariborz Haghighat Department of Building, Civil and Environmental Engineering Concordia University,

More information

Dealing with Thermal Issues in Data Center Universal Aisle Containment

Dealing with Thermal Issues in Data Center Universal Aisle Containment Dealing with Thermal Issues in Data Center Universal Aisle Containment Daniele Tordin BICSI RCDD Technical System Engineer - Panduit Europe Daniele.Tordin@Panduit.com AGENDA Business Drivers Challenges

More information

Window Thermal Performance Optimization in Governmental Emirati Housing Prototype in Abu Dhabi, UAE

Window Thermal Performance Optimization in Governmental Emirati Housing Prototype in Abu Dhabi, UAE Window Thermal Performance Optimization in Governmental Emirati Housing Prototype in Abu Dhabi, UAE Abuimara, Tareq A 1 ; Tabet Aoul, Kheira A. 1 1 Department of Architectural Engineering, United Arab

More information

ENERGY SAVING STUDY IN A HOTEL HVAC SYSTEM

ENERGY SAVING STUDY IN A HOTEL HVAC SYSTEM ENERGY SAVING STUDY IN A HOTEL HVAC SYSTEM J.S. Hu, Philip C.W. Kwong, and Christopher Y.H. Chao Department of Mechanical Engineering, The Hong Kong University of Science and Technology Clear Water Bay,

More information

2013 Code_Saturne User Group Meeting. EDF R&D Chatou, France. 9 th April 2013

2013 Code_Saturne User Group Meeting. EDF R&D Chatou, France. 9 th April 2013 2013 Code_Saturne User Group Meeting EDF R&D Chatou, France 9 th April 2013 Thermal Comfort in Train Passenger Cars Contact For further information please contact: Brian ANGEL Director RENUDA France brian.angel@renuda.com

More information

Heating Load Calculation

Heating Load Calculation Heating Load Calculation ME 425 Air Conditioning System Design Keith E. Elder, P.E. Heating Load Calculation The heating load calculation begins with the determination of heat loss through a variety of

More information

EXPERIMENTAL ANALYSIS OF PARTIAL AND FULLY CHARGED THERMAL STRATIFIED HOT WATER STORAGE TANKS

EXPERIMENTAL ANALYSIS OF PARTIAL AND FULLY CHARGED THERMAL STRATIFIED HOT WATER STORAGE TANKS INTERNATIONAL JOURNAL OF MECHANICAL ENGINEERING AND TECHNOLOGY (IJMET) International Journal of Mechanical Engineering and Technology (IJMET), ISSN 0976 6340(Print), ISSN 0976 6340 (Print) ISSN 0976 6359

More information

Great Lakes Data Room Case Study

Great Lakes Data Room Case Study Great Lakes Data Room Case Study WeRackYourWorld.com Problem: During a warm summer period in 2008, Great Lakes experienced a network outage due to a switch failure in the network enclosure. After an equipment

More information

Verizon SMARTS Data Center Design Phase 1 Conceptual Study Report Ms. Leah Zabarenko Verizon Business 2606A Carsins Run Road Aberdeen, MD 21001

Verizon SMARTS Data Center Design Phase 1 Conceptual Study Report Ms. Leah Zabarenko Verizon Business 2606A Carsins Run Road Aberdeen, MD 21001 Verizon SMARTS Data Center Design Phase 1 Conceptual Study Report Ms. Leah Zabarenko Verizon Business 2606A Carsins Run Road Aberdeen, MD 21001 Presented by: Liberty Engineering, LLP 1609 Connecticut Avenue

More information

Prediction Is Better Than Cure CFD Simulation For Data Center Operation.

Prediction Is Better Than Cure CFD Simulation For Data Center Operation. Prediction Is Better Than Cure CFD Simulation For Data Center Operation. This paper was written to support/reflect a seminar presented at ASHRAE Winter meeting 2014, January 21 st, by, Future Facilities.

More information

HVAC Code Requirements

HVAC Code Requirements one and two family dwellings? Answer: SECTION 2001: GENERAL 2001.1 Air supply. Fuel-burning equipment shall be provided with a supply of air for fuel combustion, draft hood dilution and ventilation of

More information

AMCA International. Investigation of the Impact of Building Entrance Air Curtain on Whole Building Energy Use AIR MOVEMENT AND CONTROL

AMCA International. Investigation of the Impact of Building Entrance Air Curtain on Whole Building Energy Use AIR MOVEMENT AND CONTROL AMCA International Investigation of the Impact of Building Entrance Air Curtain on Whole Building Energy Use AIR MOVEMENT AND CONTROL ASSOCIATION INTERNATIONAL, INC. The International Authority on Air

More information

Case Studies: Infrared Heating in Industrial Applications

Case Studies: Infrared Heating in Industrial Applications Case Studies: Infrared Heating in Industrial Applications Chao Chen, Puget Sound Energy ABSTRACT Puget Sound Energy (PSE) is a utility which serves more than one million electric customers and over 700,000

More information

New Deluxe Wall Mounted Heat Pump Series EXTERIOS

New Deluxe Wall Mounted Heat Pump Series EXTERIOS New Deluxe Wall Mounted Heat Pump Series EXTERIOS May 2013 New Deluxe Wall Mounted Heat Pump Series Panasonic Adding New Air Conditioner Lineup Setting Another Mile Stone in the US Ductless Split History

More information

Data Bulletin. Mounting Variable Frequency Drives in Electrical Enclosures Thermal Concerns OVERVIEW WHY VARIABLE FREQUENCY DRIVES THERMAL MANAGEMENT?

Data Bulletin. Mounting Variable Frequency Drives in Electrical Enclosures Thermal Concerns OVERVIEW WHY VARIABLE FREQUENCY DRIVES THERMAL MANAGEMENT? Data Bulletin April 2001 Raleigh, NC, USA Mounting Variable Frequency Drives in Electrical Enclosures Thermal Concerns OVERVIEW Variable frequency drives are available from manufacturers as enclosed engineered

More information

FAN PROTECTION AGAINST STALLING PHENOMENON

FAN PROTECTION AGAINST STALLING PHENOMENON FAN PROTECTION AGAINST STALLING PHENOMENON Roberto Arias Álvarez 1 Javier Fernández López 2 2 1 ZITRON Technical Director roberto@zitron.com ZITRON Technical Pre Sales Management jfernandez@zitron.com

More information

SEPARATING DUST PARTICLES USING AN AERODYNAMIC DEDUSTER

SEPARATING DUST PARTICLES USING AN AERODYNAMIC DEDUSTER SEPARATING DUST PARTICLES USING AN AERODYNAMIC DEDUSTER DEVELOPMENT OF AN AERODYNAMIC DEDUSTER FOR LIVESTOCK BUILDINGS G.A. Zhao, Y. Zhang Summary Dust is among the major pollutants that have a detrimental

More information

Averaging Pitot Tubes; Fact and Fiction

Averaging Pitot Tubes; Fact and Fiction Averaging Pitot Tubes; Fact and Fiction Abstract An experimental investigation has been undertaken to elucidate effects of averaging stagnation pressures on estimated velocities for pressure averaging

More information

Basic Selection & Proper Application of Overhead Air Distribution Devices

Basic Selection & Proper Application of Overhead Air Distribution Devices Basic Selection & Proper Application of Overhead Air Distribution Devices GRD Selection & Application Terms Selection Throw Sound Installation Variations affect Performance Inlet Effects Basics Return

More information

Mechanical Systems Proposal revised

Mechanical Systems Proposal revised Mechanical Systems Proposal revised Prepared for: Dr. William Bahnfleth, Professor The Pennsylvania State University, Department of Architectural Engineering Prepared by: Chris Nicolais Mechanical Option

More information

HVAC Systems in Schools & Commercial Buildings and Radon

HVAC Systems in Schools & Commercial Buildings and Radon HVAC Systems in Schools & Commercial Buildings and Radon References US EPA Radon Prevention in the Design and Construction of Schools and Other Large Buildings http://www.epa.gov/ordntrnt/ord/nrmrl/pubs/1993/air/

More information

Simplified Procedure For Estimating Air- Conditioning Cooling Load In Ghana

Simplified Procedure For Estimating Air- Conditioning Cooling Load In Ghana Simplified Procedure For Estimating Air- Conditioning Cooling Load In Ghana Felix A. Uba, YesuenyeagbeA. K. Fiagbeand Emmanuel A. Sarsah Abstract: Undersized or oversized air conditioning equipment leads

More information

ON MOST schemes, the architectural design of. Flexible strategy. Case study. The Forum

ON MOST schemes, the architectural design of. Flexible strategy. Case study. The Forum Flexible strategy ON MOST schemes, the architectural design of a building is influenced by fire engineering strategy. This could be in the form of visual, physical elements such as fire doors, fire curtains,

More information

CHAPTER 3. BUILDING THERMAL LOAD ESTIMATION

CHAPTER 3. BUILDING THERMAL LOAD ESTIMATION CHAPTER 3. BUILDING THERMAL LOAD ESTIMATION 3.1 Purpose of Thermal Load Estimation 3.2 Heating Load versus Cooling Load 3.3 Critical Conditions for Design 3.4 Manual versus Computer Calculations 3.5 Heating

More information

3-D Modeller Rendered Visualisations

3-D Modeller Rendered Visualisations Recognised energy Dynamic Simulation Modelling (DSM) software DesignBuilder is a user interface to the EnergyPlus DSM. EnergyPlus builds on the most popular features and capabilities of BLAST and DOE-2

More information

THERMAL DESIGN AND TEST REQUIREMENTS FOR OUTSIDE PLANT CABLE TELECOMMUNICATIONS EQUIPMENT Al Marshall, P.E. Philips Broadband Networks

THERMAL DESIGN AND TEST REQUIREMENTS FOR OUTSIDE PLANT CABLE TELECOMMUNICATIONS EQUIPMENT Al Marshall, P.E. Philips Broadband Networks THERMAL DESIGN AND TEST REQUIREMENTS FOR OUTSIDE PLANT CABLE TELECOMMUNICATIONS EQUIPMENT Al Marshall, P.E. Philips Broadband Networks Abstract Shrinking thermal margins, driven by sophisticated but thermally

More information

CFD Application on Food Industry; Energy Saving on the Bread Oven

CFD Application on Food Industry; Energy Saving on the Bread Oven Middle-East Journal of Scientific Research 13 (8): 1095-1100, 2013 ISSN 1990-9233 IDOSI Publications, 2013 DOI: 10.5829/idosi.mejsr.2013.13.8.548 CFD Application on Food Industry; Energy Saving on the

More information