Heating Load Calculation

Size: px
Start display at page:

Download "Heating Load Calculation"

Transcription

1 Heating Load Calculation ME 425 Air Conditioning System Design Keith E. Elder, P.E. Heating Load Calculation The heating load calculation begins with the determination of heat loss through a variety of building envelope components and situations. Walls Windows Exposed Floors Basement Walls Infiltration Duct Loss Roofs Doors Slab-on-Grade Floors Basement Floors Ventilation Building Pickup 1

2 The Heat Loss Equation q = U o x A ( T i - T o ) Where: U o =the overall heat transfer coefficient, Btu/hr/ft 2 / F A = the surface area, ft 2 T i = the indoor design temperature, F T o = the outdoor design temperature, F Heat Loss Equation Assumptions Steady State Conditions No Thermal Storage Heat Transfer is Instantaneous One-Dimensional Parallel "Heat Flow" Thermally Homogeneous Construction Construction Anomalies can be Accounted for by Transmission Weighting Corrections Heat flow path ignores temperature variations due to construction anomalies 2

3 Solving the Heat Loss Equation Area Takeoffs (from plans with est. zoning) Design Temperatures ( 05F28 CD & Std. 55) Assembly U-factors, U o : U o = 1/ R Total R Total = R 1 + R 2 + R n +... R 1, R 2 and R n represent the thermal resistance of each of the elements in the path of the "heat flow. Properties of typical construction materials can be found in Table 3 of 05F25. Construction Material Properties 3

4 Air Film Properties From 05F25.2 Air Gap Properties From 05F25.4 4

5 Wall with no Framing Elements What is the U-factor of a 3-1/2 inch wall composed of 4 inch brick, R-11 insulation and 5/8 inch gypboard? Outside Air Film 4" Brick R-11 Batt Insulation 5/8" Gypboard Inside Air Film Total R = Ri Uo = 1/R = 1/12.81 = Btu Hr-SF-deg F Correcting for Cavity Depth The R-value of batt insulation is rated by manufacturers for predetermined depths. Corrections must be made to calculations for installation in non-standard cavities. TABLE 20-A R-Value of Fiberglass Batts Compressed within Various Depth Cavities Insulation R-Value at Standard Thickness R-Value Standard Thickness 12" 9-½ " 6-¾ " 5-½ " 6-¼ " 3-½ " 3-5/8" 3-½ " 2-½ " 1-½ " ¾ " Nominal Lumber Sizes, Inches Actual Depth of Cavity, Inches Insulation R-Values when Installed in a Confined Cavity 2 x / x / x 8 7-1/ x 6 5-1/ x 4 3-1/ x 3 2-1/ x 2 1-1/2" x 1 3/4"

6 Correcting for Wood Framing What is the U-factor of the previous example if the wall is framed with Douglas Fir studs spaced 16" on-center. Through Insulation Through 16" OC Stud Outside Air Film 4" Brick R-11 Batt Insulation 3-1/2" Fir Stud 5/8" Gypboard Inside Air Film Total R = Uo = Uavg = 0.20 x x = Btu/(hr-S.F.-F) What About Metal Studs? Transmission weighting is not appropriate if the conductivity of the penetration exceeds that of the layer being penetrated by more than an order of magnitude. Isotherms 6

7 Correcting for Metal Studs ASHRAE Standard 90.1 Correction Factors Size of Insulation Correction Members Framing R-Value Factor, F c 2 x 4 16 in. O.C. R x 4 24 in. O.C. R x 6 16 in. O.C. R x 6 24 in. O.C R Using Metal Stud Factors What is the heat loss of the wall in the first example if the wall is framed with 3-1/2" metal studs spaced 16" on-center? Ri Outside Air Film " Brick 0.40 R-11 + Mtl. Stud (11.0 x 0.50) = /8" Gypboard 0.56 Inside Air Film 0.68 Total R = Uo = 1/7.31 = Btu Hr-SF-deg F 7

8 ASHRAE Window Performance Because of conductive spacers, frames & new coatings available, window U- factors cannot be calculated accurately. ASHRAE Window Performance Reasonable estimates can be found in Table 4, 05F

9 ASHRAE Window U-factors ASHRAE Window U-factors 9

10 Door U-Factors Door U-factors can be found in Table 4, 05F Floors on Grade q slab = F 2 x Perimeter x T 10

11 Floors on Grade - F 2 Factors Infiltration The uncontrolled inward air leakage through cracks and interstices in any building element and around windows and doors of a building, caused by the pressure effects of wind and/or the effect of differences in the outdoor/indoor air density. q infiltration = 0.018Q T Q = air flow due to infiltration, ft 3 /hr 11

12 Infiltration Estimates From the 1972 Fundamentals Manual: Number of Air Changes Taking Kind of Room or Building Place per Hour Rooms with no windows or exterior doors 1/2 Rooms with windows/exterior doors on one side 1 Rooms with windows/exterior doors on two sides 1-1/2 Rooms with windows/exterior doors on three sides 2 Entrance Halls 2 Note: Values may be reduced by 1/3 if windows & doors weatherstripped In-Class Heating Load Exercise What is the heat loss for a Seattle office space 12 feet deep by 50 feet long, with 10 foot ceilings and floor-to-floor spacing of 12 feet? The office zone is located on the third floor of a five story building. The wall is constructed of 6 inch concrete, with R-11 batt insulation installed between metal studs 16 inch on-center, and 5/8 inch gypsum board. The window is insulated 1/4 inch glass with 1/2 inch air space and composes 40 percent of the gross wall area. The window framing is metal and has no thermal break. 12

13 Building & Space Sketch Section Sketch Outside Air Film 6 Inch Concrete R-11 Batt Insulation between mtl studs 16 O.C. 5/8 Inch Sheet Rock Inside Air Film Total R = U wall = 13

1/9/2013. Terminology Calculating Heat Transfer Code Requirements Design Examples and Sustainability

1/9/2013. Terminology Calculating Heat Transfer Code Requirements Design Examples and Sustainability 1/9/13 By Brett T. Fagan, P.E. Presented by Marie Horan, P.E. Building Diagnostics, Inc. Building Diagnostics Terminology Calculating Heat Transfer Code Requirements Design Examples and Sustainability

More information

2009 IECC Update. Scope. Content. International Energy Conservation Code

2009 IECC Update. Scope. Content. International Energy Conservation Code 2009 IECC Update International Energy Conservation Code Scope The code applies to both residential and commercial buildings. In the code, the United States is divided into eight climate zones which are

More information

Building Energy Codes 101 October 23, 2013. Matthew Giudice Building Policy Associate Midwest Energy Efficiency Alliance

Building Energy Codes 101 October 23, 2013. Matthew Giudice Building Policy Associate Midwest Energy Efficiency Alliance Building Energy Codes 101 October 23, 2013 Matthew Giudice Building Policy Associate Midwest Energy Efficiency Alliance OVERVIEW 1. Introduction 2. Energy Code Development 3. Adoption Process 4. Elements

More information

Roof insulations must perform the basic function of helping to control fluctuations in building interior temperature

Roof insulations must perform the basic function of helping to control fluctuations in building interior temperature Thermal Values Roof insulations must perform the basic function of helping to control fluctuations in building interior temperature relative to changing exterior temperatures. By reducing interior temperature

More information

HVAC Calculations and Duct Sizing

HVAC Calculations and Duct Sizing PDH Course M199 HVAC Calculations and Duct Sizing Gary D. Beckfeld, M.S.E., P.E. 2007 PDH Center 2410 Dakota Lakes Drive Herndon, VA 20171-2995 Phone: 703-478-6833 Fax: 703-481-9535 www.pdhcenter.com An

More information

THERMAL LOSSES Thermal Losses Calculations

THERMAL LOSSES Thermal Losses Calculations Calculations -1- THERMAL LOSSES Thermal Losses Calculations Employer : 4M SA Project Location : ASHRAE Office Room : Example from ASHRAE 2013 Handbook - Fundamentals : Chapter 18, Single Room Example Peak

More information

2014 British Columbia Building Code Changes

2014 British Columbia Building Code Changes District of Houston 250-845-2238 2014 British Columbia Building Code Changes A District of Houston interpretation of the 2014 Building Code Changes for 9.36 & 9.32 The following changes reflect the most

More information

Introduction to Energy Performance of Brick Masonry

Introduction to Energy Performance of Brick Masonry TECHNICAL NOTES on Brick Construction 1850 Centennial Park Drive, Reston, Virginia 20191 www.gobrick.com 703-620-0010 Introduction to Energy Performance of Brick Masonry 4 January 2016 Abstract: Thermal

More information

Envelope INSULATION BATT (2) Avoid Using Batt Insulation With Metal Framing. Pressure or Friction Fit

Envelope INSULATION BATT (2) Avoid Using Batt Insulation With Metal Framing. Pressure or Friction Fit R-H-DI1 INSULATION BATT NR-E-IB1 Avoid Using Batt Insulation With Metal Framing Batt insulation should not be used with metal framing systems. Although it is common to see fiberglass batt insulation installed

More information

Is Your Envelope Effective? Mark Lawton P.Eng Morrison Hershfield Limited Vancouver

Is Your Envelope Effective? Mark Lawton P.Eng Morrison Hershfield Limited Vancouver Is Your Envelope Effective? Mark Lawton P.Eng Morrison Hershfield Limited Vancouver Designing an Effective Envelope Roofs Below Grade Walls and slabs Glazing & Windows Opaque portions of walls 2 3 Energy

More information

Figure 1. Skylight U-factor Zone 4.60 Glazed fenestration SHGC

Figure 1. Skylight U-factor Zone 4.60 Glazed fenestration SHGC Figure 1 City of Prescott Complying with the Residential IECC 2006 Prescriptively ZONE 4 See policies and ordinances for additional information. All details are for EXAMPLE ONLY. Plans shall have details

More information

DEFAULT HEAT LOSS COEFFICIENTS

DEFAULT HEAT LOSS COEFFICIENTS DEFAULT HEAT LOSS COEFFICIENTS SECTION A101 GENERAL REQUIREMENTS A101.1 Scope. The following defaults shall apply to Chapter 4 of both the (RE) and (CE) sections of the IECC. This chapter includes tables

More information

) and air spaces (R a

) and air spaces (R a 5.3.3 Thermal Resistance (R-value) Common thermal properties of materials and air spaces are based on steady state tests, which measure the heat that passes from the warm side to the cool side of the test

More information

WASHINGTON STATE ENERGY CODE, APPENDIX CHAPTERS

WASHINGTON STATE ENERGY CODE, APPENDIX CHAPTERS Chapter 51-11C WAC WASHINGTON STATE ENERGY CODE, APPENDIX CHAPTERS TABLE OF CONTENTS Appendix A Default Heat Loss Coefficients... AE-3 A101 General... AE-3 A101.1 Scope... AE-3 A101.2 Description... AE-3

More information

24.301.161 INCORPORATION BY REFERENCE OF INTERNATIONAL. (1) The Department of Labor and Industry adopts and incorporates by

24.301.161 INCORPORATION BY REFERENCE OF INTERNATIONAL. (1) The Department of Labor and Industry adopts and incorporates by 24.301.161 INCORPORATION BY REFERENCE OF INTERNATIONAL ENERGY CONSERVATION CODE (1) The Department of Labor and Industry adopts and incorporates by reference the International Code Council's International

More information

Energy Use in Residential Housing: A Comparison of Insulating Concrete Form and Wood Frame Walls

Energy Use in Residential Housing: A Comparison of Insulating Concrete Form and Wood Frame Walls PCA R&D Serial No. 415 Energy Use in Residential Housing: A Comparison of Insulating Concrete Form and Wood Frame Walls by John Gajda and Martha VanGeem 000 Portland Cement Association KEYWORDS Concrete,

More information

2014 British Columbia Building Code Changes

2014 British Columbia Building Code Changes 2014 British Columbia Building Code Changes A City of Kelowna interpretation of the 2014 Building Code Changes for 9.36 & 9.32 The following changes reflect the most notable revisions and staff interpretations.

More information

2012 ENERGY STAR. Tables for Calculating Effective Thermal Resistance of Opaque Assemblies

2012 ENERGY STAR. Tables for Calculating Effective Thermal Resistance of Opaque Assemblies 2012 ENERGY STAR for New for Homes New Standard Homes Tables for Calculating of Opaque Assemblies TABLE OF CONTENTS 1.0 Purpose... 1 2.0 Methodology... 1 3.0 Instructions... 3 4.0 List of Tables... 5 5.0

More information

AIR INFILTRATION AND ENERGY EFFICIENCY IN YOUR HOME

AIR INFILTRATION AND ENERGY EFFICIENCY IN YOUR HOME AIR INFILTRATION AND ENERGY EFFICIENCY IN YOUR HOME When you think about the energy efficiency of a home, things like the heating and cooling system and insulation readily come to mind. These are certainly

More information

Chapter 2: Foundations

Chapter 2: Foundations Chapter 2: Foundations Crawlspace [V502.1.2] Vents. Vents in the crawlspace help keep floor insulation and floor framing dry. Crawlspace vents also reduce the potential for radon buildup under the floor.

More information

2014 Amendments to: 2012 British Columbia Building Code. An interpretation of the 2014 Building Code Changes for 9.36 & 9.32.

2014 Amendments to: 2012 British Columbia Building Code. An interpretation of the 2014 Building Code Changes for 9.36 & 9.32. 2014 Amendments to: 2012 British Columbia Building Code An interpretation of the 2014 Building Code Changes for 9.36 & 9.32. Prepared by the Building Inspection Services Department The following changes

More information

Study of Poured-In-Place Concrete Wall Performance in Coastal British Columbia

Study of Poured-In-Place Concrete Wall Performance in Coastal British Columbia AGENDA l Study of Poured-In-Place Concrete Wall Performance in Coastal British Columbia l Types of Concrete Walls l Water Penetration Control Strategies l Focus on Poured In Place Concrete Walls CONTEXT

More information

Fiberglas, Exterior Wall Thermal Insulation

Fiberglas, Exterior Wall Thermal Insulation PROJECT ENGINEER RESPONSIBILITY: This is a general specification guide, intended to be used by experienced construction professionals, in conjunction with good construction practice and professional judgment.

More information

CITY PLAN REVIEW AND INSPECTION. Lisa Fleming Brown, CPM

CITY PLAN REVIEW AND INSPECTION. Lisa Fleming Brown, CPM CITY PLAN REVIEW AND INSPECTION Lisa Fleming Brown, CPM Houston Commercial Energy Conservation Code (2011) A choice of 2009 IECC or ASHRAE 90.1-2007 with amendments. Effective September 2, 2011. Complete

More information

North Carolina State Buildings

North Carolina State Buildings North Carolina State Buildings Efficiency Conference Building Envelope Sponsored by: State Energy Office and State Construction Office NC Department of Administration Conducted by: Jeff Tiller, PE Appalachian

More information

This handout is a guide only and does not contain all of the requirements of the Minnesota State Building Code or city ordinances.

This handout is a guide only and does not contain all of the requirements of the Minnesota State Building Code or city ordinances. Basement Finishing Guide Community Development Department Building Inspections Division 5200 85 th Avenue North / Brooklyn Park, MN 55443 Phone: (763) 488-6379 / Fax: (763) 493-8171 6/15 www.brooklynpark.org

More information

Insulation Requirements vs. Fire Protection Requirements for Basements per IRC-2012

Insulation Requirements vs. Fire Protection Requirements for Basements per IRC-2012 Mark Bartel, P.E., Technical Director International Beams Page 1 of 8 Fire protection requirement of R503.1, IRC-2012 Here are some solutions to meeting the fire protection requirements of IRC-2012 that

More information

Including excerpts from the Energy Efficiency Guide (HPO) and the BC Building Code 2012

Including excerpts from the Energy Efficiency Guide (HPO) and the BC Building Code 2012 Including excerpts from the Energy Efficiency Guide (HPO) and the BC Building Code 2012 The Energy Efficiency Provisions that have been circulating will become part of the BC Building Code effective December

More information

R-Matte Plus-3. Insulation for the Building Envelope ROOF WALL SPECIALTY

R-Matte Plus-3. Insulation for the Building Envelope ROOF WALL SPECIALTY Insulation for the Building Envelope ROOF WALL SPECIALTY PRODUCT DESCRIPTION Rmax R-Matte Plus-3 is an energy-efficient thermal insulation board composed of a closed-cell polyisocyanurate (polyiso) foam

More information

CHAPTER 3. BUILDING THERMAL LOAD ESTIMATION

CHAPTER 3. BUILDING THERMAL LOAD ESTIMATION CHAPTER 3. BUILDING THERMAL LOAD ESTIMATION 3.1 Purpose of Thermal Load Estimation 3.2 Heating Load versus Cooling Load 3.3 Critical Conditions for Design 3.4 Manual versus Computer Calculations 3.5 Heating

More information

Some Thermal Resistance Values

Some Thermal Resistance Values Some Thermal Resistance Values Substance Assuming constant thickness of given material R (1 inch) (imperial units) Air (non-convecting) 6 0.42 R (1cm) (metric units) Copper 3.7x10-4 2.6x10-5 Plywood 1.25

More information

R-Value and Densities Chart

R-Value and Densities Chart R-Value and Densities Chart Material R-Value Per Inch R-Value Per Unit Inside Air Film 0.68 Air Space between Studs 0.95 Building Pa 0.06 ½ in. Fiberboard Sheathing 1.52 Gypsum Wallboard or Drywall 0.90

More information

*Trademark of The Dow Chemical Company A business unit of The Dow Chemical Company and its subsidiaries Copyright 2003 The Dow Chemical Company.

*Trademark of The Dow Chemical Company A business unit of The Dow Chemical Company and its subsidiaries Copyright 2003 The Dow Chemical Company. Dow Chemical is a Registered Provider with The American Institute of Architects Continuing Education Systems. Credit earned on completion of this program will be reported to CES Records for AIA members.

More information

RULING OF THE MINISTER OF MUNICIPAL AFFAIRS AND HOUSING

RULING OF THE MINISTER OF MUNICIPAL AFFAIRS AND HOUSING BUILDING CODEACT, 1992 RULING OF THE MINISTER OF MUNICIPAL AFFAIRS AND HOUSING Pursuant to clause 29(l)(b) of the Building Code Act, 1992. as amended, the Director of the Building and Development Branch

More information

SOUND INSULATION REQUIREMENTS FOR NOISE SENSITIVE STRUCTURES NEAR LOS ANGELES INTERNATIONAL AIRPORT

SOUND INSULATION REQUIREMENTS FOR NOISE SENSITIVE STRUCTURES NEAR LOS ANGELES INTERNATIONAL AIRPORT INFORMATION BULLETIN / PUBLIC - BUILDING CODE REFERENCE NO.: LAMC 91.1207 Effective: 01-01-2014 DOCUMENT NO.: P/BC 2014-074 Revised: Previously Issued As: P/BC 2011-074 PURPOSE SOUND INSULATION REQUIREMENTS

More information

ENERGY STAR Qualified Homes, Version 3 (Rev. 03) National Program Requirements

ENERGY STAR Qualified Homes, Version 3 (Rev. 03) National Program Requirements Qualifying Homes ENERGY STAR Qualified Homes, Version 3 (Rev. 03) The following homes are eligible to earn the ENERGY STAR: Single-family homes; Units in multi-family buildings that are three stories or

More information

State of Connecticut Department of Public Health RADON PROGRAM

State of Connecticut Department of Public Health RADON PROGRAM State of Connecticut Department of Public Health RADON PROGRAM Scope The Connecticut Department of Public Health (DPH) Radon Program is providing this information for contractors who decide to build radon

More information

CONDENSATION IN REFRIDGERATED BUILDINGS

CONDENSATION IN REFRIDGERATED BUILDINGS CONDENSATION IN REFRIDGERATED BUILDINGS By: Steve Salisbury Nov. 10, 2010 (revised Nov. 14, 2013) Introduction The following discussion reviews the basic causes of condensation in refrigerated buildings

More information

SEE JAMB 3/4" 1 1/2" 14 NOTES: 1. SEE DETAIL 1 FOR KEYNOTE MATERIAL DESCRIPTIONS

SEE JAMB 3/4 1 1/2 14 NOTES: 1. SEE DETAIL 1 FOR KEYNOTE MATERIAL DESCRIPTIONS . FACE OF WALL.. STUD CONSTRUCTION WITH FIBERGLASS BATT INSULATION AND FIBERGLASS FACED EXTERIOR GYPSUM SHEATHING WITH JOINTS SEALED USING -PART POLYURETHANE PRIOR TO INSTALLING FLUID APPLIED WEATHER RESISTANT

More information

R-VALUES AND U-FACTORS OF SINGLE WYTHE CONCRETE MASONRY WALLS. TEK 6-2C Energy & IAQ (2013) Related TEK: 2-5B, 6-1C, 6-4B, 6-11A, 6-12C, 6-12D, 6-12E

R-VALUES AND U-FACTORS OF SINGLE WYTHE CONCRETE MASONRY WALLS. TEK 6-2C Energy & IAQ (2013) Related TEK: 2-5B, 6-1C, 6-4B, 6-11A, 6-12C, 6-12D, 6-12E An information series from the national authority on concrete masonry technology R-VALUES AND U-FACTORS OF SINGLE WYTHE CONCRETE MASONRY WALLS TEK 6-2C Energy & IAQ (201) INTRODUCTION Single wythe concrete

More information

REScheck Software User's Guide. Building Energy Codes Program

REScheck Software User's Guide. Building Energy Codes Program REScheck Software User's Guide Building Energy Codes Program Table Of Contents Software User's Guide...1 Table Columns and Rows...3 Rows...3 Columns...4 Project Folder...7 Project Folder Required Inputs...7

More information

Envelope INSULATION BATT (1) (2) Pressure or Friction Fit

Envelope INSULATION BATT (1) (2) Pressure or Friction Fit R-H-DI1 INSULATION BATT Pressure or Friction Fit Insulation should be cut to fit snugly against studs on all sides, and should completely fill the cavity with no air gaps. Cut lengths of insulation should

More information

research highlight Highly Energy Efficient Building Envelope Retrofits for Houses

research highlight Highly Energy Efficient Building Envelope Retrofits for Houses research highlight June 2012 Technical Series 12-103 Highly Energy Efficient Building Envelope Retrofits for Houses introduction In Canada approximately 30% of all energy is consumed in buildings, with

More information

Fire Resistance Bulletin

Fire Resistance Bulletin New 1-hr Rated Exterior Wall Assembly Includes Allowances for Various Insulation Options and Much Wider Maximum Girt Spacing Under the auspices of the MBMA Committee on Fire Protection and Related Insurance

More information

Atlantic Post and Beam Construction 1245 Hanwell Rd. Fredericton, NB. E3C 1A6 Tel: (506) 450-5445

Atlantic Post and Beam Construction 1245 Hanwell Rd. Fredericton, NB. E3C 1A6  Tel: (506) 450-5445 Atlantic Post and Beam Construction 1245 Hanwell Rd. Fredericton, NB. E3C 1A6 www.atlanticpostandbeam.ca Tel: (506) 450-5445 Prefabricated/Modular Timber frame Home / Cottage: At Atlantic Post and Beam,

More information

Heat Transfer. Conduction. Introduction. How does heat flow through solids? Factors that affect heat conduction. Q/ t = ka( T /L)

Heat Transfer. Conduction. Introduction. How does heat flow through solids? Factors that affect heat conduction. Q/ t = ka( T /L) Introduction Conduction is the transfer of heat through solid materials. Thermal conductivity is the measure of how fast a material conducts heat. The opposite of conductivity is resistivity, or insulating

More information

Energy Code Compliance With SIPs. Frank Baker, PFB Corporation Don Ferrier, Ferrier Custom Homes

Energy Code Compliance With SIPs. Frank Baker, PFB Corporation Don Ferrier, Ferrier Custom Homes Energy Code Compliance With SIPs Frank Baker, PFB Corporation Don Ferrier, Ferrier Custom Homes Outline Overview of 2009 and 2012 energy codes Code compliance with SIPs Reducing air infiltration with SIP

More information

Prescriptive Checklist for the 2012 Washington State Energy Code

Prescriptive Checklist for the 2012 Washington State Energy Code Prescriptive Checklist for the 2012 Washington State Energy Code Prepared by Washington State University Energy Program Building Sciences Updated October 2013 2013 Washington State University Energy Program

More information

BUILDING IN ALASKA HCM-00952

BUILDING IN ALASKA HCM-00952 BUILDING IN ALASKA HCM-00952 Building Challenges in Alaska INTRODUCTION Special considerations for building in Alaska are recommended that are normally not included in structures designed for milder climates

More information

IECC Compliance Guide for Homes in Virginia

IECC Compliance Guide for Homes in Virginia IECC Compliance Guide for Homes in Virginia Amended Version of 2012 International Energy Conservation Code July 14, 2014 Climate Zone Since the entire state of Virginia falls in the IECC Climate Zone 4,

More information

ECHO System for Basements

ECHO System for Basements ECHO System for Basements Homeowners looking for more space are all too familiar with the cold, damp and dingy basement. Now, the Enclosure Conditioned Housing (ECHO) System TM, winner of the Ottawa-Carleton

More information

Vestibule Case Study. Vestibule Requirement Intent [2003 IECC, 2006 IECC, 2003 IBC, 2006 IBC, 90.1-2001, 90.1-2004]

Vestibule Case Study. Vestibule Requirement Intent [2003 IECC, 2006 IECC, 2003 IBC, 2006 IBC, 90.1-2001, 90.1-2004] Vestibule Case Study [2003 IECC, 2006 IECC, 2003 IBC, 2006 IBC, 90.1-2001, 90.1-2004] Vestibule Requirement Intent Page 1 of 14 The primary intent behind the requirement for a vestibule is to reduce infiltration

More information

Design Guide Solutions to Prevent Thermal Bridging

Design Guide Solutions to Prevent Thermal Bridging Design Guide Solutions to Prevent Thermal Bridging June 2014 Foreword This publication presents information on the nature and significance of structural thermal bridges in buildings constructed of concrete

More information

ATTENTION CONTRACTORS AND HOMEOWNERS JANUARY 1, 2010

ATTENTION CONTRACTORS AND HOMEOWNERS JANUARY 1, 2010 2010 CALIFORNIA BUILDING CODE CALIFORNIA RESIDENTIAL CODE 2008 BUILDING ENERGY EFFICIENCY STANDARDS STANDARDS REVIEW WITH REPLACEMENT WINDOW PERMIT APPLICATION ATTENTION CONTRACTORS AND HOMEOWNERS NEW

More information

CITY OF MERCER ISLAND, WASHINGTON

CITY OF MERCER ISLAND, WASHINGTON www.mercergov.org CITY OF MERCER ISLAND, WASHINGTON 9611 S.E. 36th St. Mercer Island, WA 98040-3732 p: (206) 275-7605 f: (206) 275-7725 TDD: (425) 803-1751 Inspection Requests: Online: www.mybuildingpermit.com

More information

Underwriters Laboratories Testing Information

Underwriters Laboratories Testing Information Underwriters Laboratories Testing Information R-8078 Underwriters Laboratories Inc. R-13173 Classified Spray Fiber Surface burning characteristics applied to inorganic reinforced cement board with a maximum

More information

Low-cost Construction for High-energy Savings. Brian J. Wimmer Construction Manager Rochester Area Habitat for Humanity

Low-cost Construction for High-energy Savings. Brian J. Wimmer Construction Manager Rochester Area Habitat for Humanity Low-cost Construction for High-energy Savings Brian J. Wimmer Construction Manager Rochester Area Habitat for Humanity construction@rahh.org Objectives: 1. Control air & moisture in high-performance, low-cost

More information

City of Houston, Texas, Ordinance No. 2008-

City of Houston, Texas, Ordinance No. 2008- City of Houston, Texas, Ordinance No. 2008- AN ORDINANCE AMENDING THE CITY OF HOUSTON BUILDING CODE AND ADOPTING ADDITIONAL LOCAL AMENDMENTS TO THE INTERNATIONAL RESIDENTIAL CODE FOR ONE- AND TWO- FAMILY

More information

Minnesota State Residential Energy Code Requirements

Minnesota State Residential Energy Code Requirements Minnesota State Residential Energy Code Requirements The Energy Code provides minimum standards for permitting energy efficient operation, assuring building durability and furnishing quality indoor air.

More information

Module 3.7. Thermal bridging

Module 3.7. Thermal bridging Module 3.7 Thermal bridging Learning Outcomes On successful completion of this module learners will be able to - Describe construction details which influence thermal bridging. 2 Introduction to thermal

More information

COMMONLY USED RESIDENTIAL BUILDING CODES

COMMONLY USED RESIDENTIAL BUILDING CODES COMMONLY USED RESIDENTIAL BUILDING CODES INTERNATIONAL RESIDENTIAL CODE (2009) form revised 5/10 WALL FRAMING 23. DESIGN AND CONSTRUCTION. Section R602.3 IRC 2009 Exterior walls of wood-frame construction

More information

COMcheck Software User's Guide for 90.1-2004 and 90.1-2007. Building Energy Codes Program

COMcheck Software User's Guide for 90.1-2004 and 90.1-2007. Building Energy Codes Program COMcheck Software User's Guide for 90.1-2004 and 90.1-2007 Building Energy Codes Program Table Of Contents Overview...1 Table Columns and Rows...3 Columns...3 Rows...3 File Menu...5 Edit Menu...5 Cut...6

More information

Special Applications and Building Type. Special precautions are required for buildings with high indoor humidities or spaces with sensitive

Special Applications and Building Type. Special precautions are required for buildings with high indoor humidities or spaces with sensitive Special Applications and Building Type. Special precautions are required for buildings with high indoor humidities or spaces with sensitive electronic equipment or artifacts. These include swimming pools,

More information

THERMAL DESIGN AND CODE COMPLIANCE FOR COLD-FORMED STEEL WALLS. Steel Framing Alliance 1201 15th Street, NW, Suite 320 Washington, DC 20005

THERMAL DESIGN AND CODE COMPLIANCE FOR COLD-FORMED STEEL WALLS. Steel Framing Alliance 1201 15th Street, NW, Suite 320 Washington, DC 20005 THERMAL DESIGN AND CODE COMPLIANCE FOR COLD-FORMED STEEL WALLS Steel Framing Alliance 1201 15th Street, NW, Suite 320 Washington, DC 20005 August 2008 Acknowledgements This report updates the Thermal Design

More information

STAYFLEX CORROSION CONTROL AND THERMAL INSULATION SYSTEM

STAYFLEX CORROSION CONTROL AND THERMAL INSULATION SYSTEM STAYFLEX CORROSION CONTROL AND THERMAL INSULATION SYSTEM Installed in Pre-engineered Steel Buildings Provides Lowest Cost Construction Method for CORROSIVE AND WET Environments PREFERRED SOLUTIONS, INC.

More information

Use of the Blower Door with IR/Thermal Imaging for Residential Building Diagnostics

Use of the Blower Door with IR/Thermal Imaging for Residential Building Diagnostics Use of the Blower Door with IR/Thermal Imaging for Residential Building Diagnostics Howard Vics Building Performance Consulting of NY ABSTRACT The infrared thermal imaging camera has become an invaluable

More information

Building Department John Fiedler Construction Official Ext. 211. SAMPLE GUIDE FOR 1&2 FAMILY DWELLING BASEMENTS Rev 4-3-2014

Building Department John Fiedler Construction Official Ext. 211. SAMPLE GUIDE FOR 1&2 FAMILY DWELLING BASEMENTS Rev 4-3-2014 TOWNSHIP OF HILLSBOROUGH COUNTY OF SOMERSET Hillsborough Township Municipal Complex The Peter J. Biondi Building 379 South Branch Road Hillsborough, NJ 08844 P: (908) 369-4313 F: (908) 369-3954 Building

More information

Building Permit Application Packet. BUILDING CODES Adopted by La Plata County For Enforcement In The Unincorporated Areas Of La Plata County

Building Permit Application Packet. BUILDING CODES Adopted by La Plata County For Enforcement In The Unincorporated Areas Of La Plata County Building Permit Application Packet The purpose of Building Codes is to establish the minimum requirements to safe guard the public health, safety and general welfare through structural strength, means

More information

2015 1322) SIGNIFICANT CHANGES INCLUDING CODE COMMENTARY

2015 1322) SIGNIFICANT CHANGES INCLUDING CODE COMMENTARY MINNESOTA ENERGY CODE COMPLIANCE COLLABORATIVE 2015 Minnesota Residential Energy Code (MR 1322) SIGNIFICANT CHANGES INCLUDING CODE COMMENTARY (July 15, 2015 Update) Note: The following information contains

More information

R-VALUES AND U-FACTORS OF SINGLE WYTHE CONCRETE MASONRY WALLS. TEK 6-2B Energy & IAQ (2009) Related TEK: 6-1B, 6-11, 6-12C INTRODUCTION

R-VALUES AND U-FACTORS OF SINGLE WYTHE CONCRETE MASONRY WALLS. TEK 6-2B Energy & IAQ (2009) Related TEK: 6-1B, 6-11, 6-12C INTRODUCTION An information series from the national authority on concrete masonry technology R-VALUES AND U-FACTORS OF SINGLE WYTHE CONCRETE MASONRY WALLS TEK 6-2B Energy & IAQ (2009) INTRODUCTION Single wythe concrete

More information

ROOFS, SNOW AND ICE DAMS

ROOFS, SNOW AND ICE DAMS ROOFS, SNOW AND ICE DAMS The Problem Ice dams are a common roof performance problem in cold climate buildings. Simply put, they are ridges of ice and icicles caused by melt water from further up the roof

More information

How to Use this Guide

How to Use this Guide How to Use this Guide Provide two sets of plans, drawn to scale and complete the following (hint: use graph paper with 1/4" squares. Example: 1/4" =1'): Check with your jurisdiction for additional requirements.

More information

2/10/2011. Toxic Mold Hilton Hotel Hawaii Alerton Hilton settles over moldy Hawaii hotel SEATTLE POST-INTELLIGENCER Saturday, December 24, 2005

2/10/2011. Toxic Mold Hilton Hotel Hawaii Alerton Hilton settles over moldy Hawaii hotel SEATTLE POST-INTELLIGENCER Saturday, December 24, 2005 2//11 Dew Point What is Dew Point? Kris Anderson, P.E What is Dew Point? Dew Point What is Dew Point? Dew point is the temperature at which dew starts to form or vapor to condense into a liquid. led Dehumidification

More information

CERTIFICATE OF COMPLIANCE Prescriptive Residential Re-roof Project Name:

CERTIFICATE OF COMPLIANCE Prescriptive Residential Re-roof Project Name: STATE OF CALIFORNIA RESIDENTIAL ALTERATIONS - RE-ROOF CERTIFICATE OF COMPLIANCE Prescriptive Residential Re-roof Project Name: CALIFORNIA ENERGY COMMISSION CF-1R-ALT-01-E (Page 1 of 2) Date Prepared: A.

More information

Schedule Method Summary Sheet

Schedule Method Summary Sheet Schedule Method Summary Sheet Address: House/Flat/Unit.: Street: Suburb: Climate Zone: Climate Zone 2 te: all Wellington Regions are Climate Zone 2) Glazing Provisions : see guidance notes for commentary

More information

EcoTouch Insulation with PureFiber Technology

EcoTouch Insulation with PureFiber Technology PROJECT ENGINEER RESPONSIBILITY: This is a general specification guide, intended to be used by experienced construction professionals, in conjunction with good construction practice and professional judgment.

More information

Table 1: Prescriptive Envelope Requirements: Residential WOOD FRAME WALL R-VALUE MASS WALL R-VALUE CEILING R-VALUE

Table 1: Prescriptive Envelope Requirements: Residential WOOD FRAME WALL R-VALUE MASS WALL R-VALUE CEILING R-VALUE June 24, 2011 North Carolina Has a New Energy Conservation Code! By R. Christopher Mathis Executive Summary On Friday, June 24, 2011, Governor Beverly Perdue signed SB 708 into law and, with it, approved

More information

Insulation R-Value Comparisons

Insulation R-Value Comparisons Insulation R-Value Comparisons American Ingenuity s component panels for the 22 48 domes contains seven inch thick rigid Expanded Polystyrene (E.P.S.) insulation which has an R value of 28. American Ingenuity

More information

BUILDING PERMIT SPECIFICATIONS

BUILDING PERMIT SPECIFICATIONS BUILDING PERMIT SPECIFICATIONS The below noted requirements are based upon La Plata County Building Code. These specifications are not intended as a complete set of requirements, but are intended to provide

More information

MBCI Insulated Metal Panels

MBCI Insulated Metal Panels MBCI Insulated Metal Panels White Paper What are Insulated Metal Panels? Insulated metal panels (IMPs) consist of two single-skin metal panels and a special foam insulation place between the two single-skin

More information

Comment Form on Proposed Gut Rehabilitation Alternatives

Comment Form on Proposed Gut Rehabilitation Alternatives Comment Form on Gut Rehabilitation Alternatives Name: Organization: Email: Instructions Submission: Please submit this form to energystarhomes@energystar.gov by October 10 th, 2012 with the subject line

More information

DuPont Tyvek Commercial Air Barrier Assemblies Exceed Air Barrier Association of America, ASHRAE 90.1

DuPont Tyvek Commercial Air Barrier Assemblies Exceed Air Barrier Association of America, ASHRAE 90.1 Building Science Bulletin DuPont Tyvek Commercial Air Barrier Assemblies Exceed Air Barrier Association of America, ASHRAE 90.1 and IECC Air Leakage Requirements When Tested in Accordance with ASTM E2357

More information

BPC Green Builders. Green building for new and existing homes. Health Comfort Energy

BPC Green Builders. Green building for new and existing homes. Health Comfort Energy BPC Green Builders Green building for new and existing homes Health Comfort Energy Mechanical Systems Installed HVAC Systems Primary energy source large, roof mounted, solar thermal array (AET flat plate)

More information

solutions & tips six Wise Energy Guide Building envelope solutions and simple tips AIR SEALING

solutions & tips six Wise Energy Guide Building envelope solutions and simple tips AIR SEALING Wise Energy Guide solutions & tips 32 AIR SEALING Is your house leaking money? six Building envelope solutions and simple tips If your home is like most, the greatest amount of heat loss is from air leakage;

More information

NEW SECTION ENERGY EFFICIENCY REQUIREMENTS DECEMBER 19, 2014

NEW SECTION ENERGY EFFICIENCY REQUIREMENTS DECEMBER 19, 2014 NEW SECTION 9.36. ENERGY EFFICIENCY REQUIREMENTS DECEMBER 19, 2014 The requirements apply to all proposed Part 9 buildings applied for building permits from Dec. 19, 2014 onward. Except: a) buildings or

More information

Masonry: Cavity Wall Insulation: Partial Fill Isometric cut-away view

Masonry: Cavity Wall Insulation: Partial Fill Isometric cut-away view Legend Insulation zone Blue text Air tightness barrier (note: this can also act as a vapour control layer) Guidance on thermal continuity Red text Guidance on air tightness Values used in psi calculations

More information

DESIGN GUIDE. Thermal Design and Code Compliance for Cold-Formed Steel Walls. 2015 Edition

DESIGN GUIDE. Thermal Design and Code Compliance for Cold-Formed Steel Walls. 2015 Edition DESIGN GUIDE Thermal Design and Code Compliance for Cold-Formed Steel Walls 2015 Edition Steel Framing Alliance 25 Massachusetts Avenue, NW Suite 800 Washington, DC 20001 Thermal Design and Code Compliance

More information

REFLECTIVE INSULATION, RADIANT BARRIERS,

REFLECTIVE INSULATION, RADIANT BARRIERS, REFLECTIVE INSULATION, RADIANT BARRIERS, AND INTERIOR RADIATION CONTROL COATINGS FOR USE IN PRE-ENGINEERED METAL BUILDINGS Technical Bulletin #107 Scope: In both the United States and Canada there is significant

More information

Explanation of Blower Door Terms and Results. Information taken from TECTITE BUILDING AIRTIGHTNESS TEST by The Energy Conservatory

Explanation of Blower Door Terms and Results. Information taken from TECTITE BUILDING AIRTIGHTNESS TEST by The Energy Conservatory Explanation of Blower Door Terms and Results Information taken from TECTITE BUILDING AIRTIGHTNESS TEST by The Energy Conservatory AIRFLOW AT 50 PASCALS CFM50: This is the airflow (in Cubic Feet per Minute)

More information

Chapter 5: Air Leakage and Moisture Control

Chapter 5: Air Leakage and Moisture Control Chapter 5: Air Leakage and Moisture Control [502.1.6] Vapor Retarders. A vapor retarder is a material placed to minimize vapor movement through the diffusion process. Types of vapor retarders include:

More information

Preparation for 2015 Residential Code Changes Discussion with Local Builders and Designers

Preparation for 2015 Residential Code Changes Discussion with Local Builders and Designers City of Duluth Preparation for 2015 Residential Code Changes Discussion with Local Builders and Designers Thank you for taking the time to join us today. We know you are busy and your time is valuable.

More information

Spray Polyurethane Foam. Insulation and Air Barrier Requirements of the 2012 I-Codes. Spray Foam Coalition

Spray Polyurethane Foam. Insulation and Air Barrier Requirements of the 2012 I-Codes. Spray Foam Coalition Spray Polyurethane Foam Design Guidance Insulation and Air Barrier Requirements of the 2012 I-Codes Spray Foam Coalition about the collaboration the center for the polyurathanes industry (CPI) of the american

More information

Renovating Your Basement

Renovating Your Basement building science.com 2006 Building Science Press All rights of reproduction in any form reserved. Renovating Your Building America Report - 0309 2003 (revised 2007) Building Science Corporation Abstract:

More information

Construction Industry Issues With Air Barriers

Construction Industry Issues With Air Barriers Construction Industry Issues With Air Barriers Presented by: Len Anastasi EXO-TEC Consulting, Inc. www.exo -tec.biz len@exo-tec.biz Industry Issue 1 Why do I want to make my building air tight? How is

More information

Home Energy Evaluation Report for Fritz Kreiss and Catherine McQueen

Home Energy Evaluation Report for Fritz Kreiss and Catherine McQueen Home Energy Evaluation Report for Fritz Kreiss and Catherine McQueen May 2008 Wisconsin Area PO BOX 115 Lake Geneva, WI 53147 CELL (414) 550-4765 Home Performance with ENERGY STAR Evaluation Report Customer

More information

Category Measure Minimum Efficiency / Certification Requirements

Category Measure Minimum Efficiency / Certification Requirements ENERGYSMART and DENVER ENERGY CHALLENGE RESIDENTIAL LOAN ELIGIBLE MEASURES s! Please check https://www.elevationscu.com/energyloans/home-loans to ensure you are using the most up to date version of the

More information

Use of Symbols UNIT. Objectives. Door and Window Symbols

Use of Symbols UNIT. Objectives. Door and Window Symbols UNIT Use of Symbols An alphabet of lines allows for clear communication through drawings; the use of standard symbols makes for even better communication. Many features of construction cannot be drawn

More information

The Case for Cross Laminated Timber: Part 2

The Case for Cross Laminated Timber: Part 2 Learning Objectives The Case for Cross Laminated Timber: Part 2 Opportunities and Challenges for a New Class of Timber Product 1. Review answers to common questions regarding the design and construction

More information

Product Test Summaries

Product Test Summaries Sierra Premium TM Product Test Summaries ASTM C 1185 Physical Properties Tests ASTM E 84/CAN/ULC S102-07 Surface Burning Characteristics ASTM E 228 Physical Properties Tests ASTM E 119/CAN/ULC S101-07

More information

NCMA TEK CONCRETE MASONRY FOUNDATION WALL DETAILS. TEK 5-3A Details (2003)

NCMA TEK CONCRETE MASONRY FOUNDATION WALL DETAILS. TEK 5-3A Details (2003) NCMA TEK National Concrete Masonry Association an information series from the national authority on concrete masonry technology CONCRETE MASONRY FOUNDATION WALL DETAILS TEK 5-3A Details (2003) Keywords:

More information