Monitoring Only Central Station Fire Alarm. Listing Evaluation

Size: px
Start display at page:

Download "Monitoring Only Central Station Fire Alarm. Listing Evaluation"

Transcription

1 Listing Evaluation A UL Listing project includes: Monitoring Only Central Station Fire Alarm Listing Evaluation 1. Evaluating the central station facility for compliance with UL 827, Central-Station Alarm Services 2. Analyzing the ability of central station staff to receive, process, and record signals received from selected systems in accordance with NFPA 72, The National Fire Alarm and Signaling Code. Standards UL Standards are available from COMM 2000, at or NFPA 72 may be purchased from the National Fire Protection Association at Evaluation Details In general, our Listing evaluation will consist of evaluating the monitoring facility for compliance with UL 827 and the ability of the central station staff to process signals in accordance with UL827 & NFPA 72. Central Station Facility Please complete a Fire Alarm Central Station Facility pre-evaluation data sheet and return it with the Listing Project quote acceptance. On the day of the central station facility evaluation, please have a technician available who has knowledge of the receivers, automation systems, your network, and all standby power systems If you have any questions, please contact UL Customer Service at , ext 40227

2 CENTRAL STATION FIRE ALARM (PROTECTIVE SIGNALING) SERVICE MONITORING STATION PRE-EVALUATION DATA SHEETS Completed forms must be returned to UL prior to the Evaluation Service Center Number: Central Station Co. Name: Service Center Address: Name of Contact: Phone Number: Address:

3 RUNNER INFORMATION Number of Runners per Shift: Qty. in Station #1 Location of Runner (Circle applicable and describe below) Central Station Runner Station Vehicle Other COMMUNICATION MEANS Communication Between the Serving Central Station and the Runner(s): (Note: The communication means must be two-way) Type Test Schedule (1) (2) (3) Location of Test log:

4 **** CENTRAL STATION BUILDING DESCRIPTION **** (Based on Fire Resistance Ratings UL 827, Tables 4.1) Occupancy Single Multiple Sprinkler System Yes No Automatic Fire Alarm System Yes No Exterior Bearing Wall Construction Interior Bearing Wall Construction Support Beams Construction Support Columns Construction Truss or Joist Construction Floor/ceiling construction (If multiple story, list each floor/ceiling assembly.) If known, please provide the following information: Design, or fire resistance ratings of any combustible structural members, which comprise the building (Design Ratings based on current UL Fire Resistance Directory Vols. 1 & 2, or an Architect s documentation)

5 Roof construction Roof covering Class A covering? NOTE: All interior doors and frames installed within walls that require a fire resistance rating; shall be UL fire rated for a minimum of 45 minutes. Location/Floor **** CENTRAL STATION OPERATING ROOM **** If central station is housed in a multiple occupancy building, please describe construction of any combustible walls, floors, and ceilings enclosing the central station operating room. Physical Security of the Station: Do walls enclosing Operating Room extend to the roofline or fixed assemblies? Yes No Construction of Entry Door(s): Is an Automatic Door Closer Installed? Yes No Is a manual means of identification installed? Yes No Can the door be readily left in an unlocked position? Yes No If an electric strike is used, is standby power provided? Yes No

6 Are there windows in the Operating Room? Yes No Describe the protection of any windows that are accessible from outside of the alarm service company s offices: **** POWER/GENERATOR ROOM (S) CONSTRUCTION **** Location/Floor Power Room Wall Construction Power Room Floor Construction Ceiling Construction

7 Door(s) & Frame(s) Construction If located indoors, are door(s) & frame(s) UL fire rated? Yes No Burglar Alarm Supervision Yes No Fire Alarm Supervision Yes No Ventilation Yes No If generator is located out of doors, please describe type of security: **** CENTRAL STATION STAFF **** No. on Duty per Shift Shift Operator(s) Runner(s) at Central Station Runner(s) at Runner Station

8 **** CENTRAL STATION EQUIPMENT **** TELEPHONE CABLE NOTE: Telephone conductors carrying signal and communications circuits into the building housing the central station shall be protected against mechanical damage, fire, and attack by methods outlined in UL 827, Section -10 Cable System. Please describe protection and routing of the telephone cable serving the central station: IF APPLICABLE: An antenna cable connecting a radio antenna to radio receiving and/or transmitting equipment located in a building housing the central station, and used to process UL Listed alarm signals shall be protected against fire, mechanical damage, and attack by the methods outlined in UL 827, Section Antenna Cable. Please describe protection and routing of the antenna cable serving the central station:

9 **** CENTRAL STATION RECEIVING EQUIPMENT **** RECEIVERS No. Units Manufacturer Model No. Connected to Automation System AUTOMATION EQUIPMENT Software Provider Version Main Computer Mfg. Model No. Redundant System? Yes No Total Systems Monitored Total Systems with Openings/Closings UPS Installed? Yes No

10 **** SECONDARY POWER SUPPLY **** NOTE: Required standby power shall be in accordance with UL 827, Section 9 Power Supply (Please check box which best describes standby power) 24 hour Battery Supply with Rectifiers (s) or UPS [ ] Generator and 4 hour Battery Supply [ ] Two generators, one with auto start [ ] BATTERY CHARGERS Internal to the Receivers Yes No (If chargers are part of the receivers, proceed to the next section) External to the Receivers Yes No No. Units Manufacturer Model No. Output Rating V A V A GENERATOR(S) Mfg. Model Rating Mfg. Model Rating

11 UNINTERRUPTIBLE POWER SOURCE Mfg. Model Rating Mfg. Model Rating Battery Mfg.: Model No. UPS Bypass Switch (For Routine Maintenance) Run Time on UPS Batteries Additional Comments about any part of the Central Station:

12 RECORDS DESCRIPTION SHEET Fire Alarm System Record of Completion A document that acknowledges the features of installation, operation, service, and equipment with representation by the property owner, system installer, system supplier, service organization and the authority having jurisdiction. An example of a record of completion form can be found in NFPA 72. As-Built (Record) Drawings As-Built drawings are drawings that document the location of all devices, appliances, wiring sequences, wiring methods and connections of the components of the fire alarm system as installed. These drawings must consist of current fire alarm system shop drawings, showing the location of fire alarm system components, remote power extenders, control units or modules. The drawings must also show the actual location of each alarm detection device, and audible appliance. Drawings provided must reflect the actual system installed. Where drawings are not available due to the extended life of the system installed, duplicate drawings must be produced depicting the current installation. Full-scale cad drawings are not required for the UL evaluation. Smaller versions may be submitted or made available at the time of our evaluation. The drawings should be done to scale and include a legend identifying all symbols that are used. Battery Calculations A battery calculation for a central station system consists of recording the current drain of each component of the fire alarm system in the normal supervisory load, totaling the supervisory loads and multiplying by 24 hours. In addition, the current drain of each individual component when in alarm mode is also recorded, totaled and multiplied by 5 minutes. The results of these calculations are combined and multiplied by a safety factor to establish the minimum amperehour capacity of the standby batteries. Acceptance Test Record An acceptance test is a test of all parts of the alarm system by the alarm service company that is maintaining the system. The test methods are described in NFPA 72 and the results shall be individually recorded for each component, device, appliance, and conductor. Copy of Original Equipment Submittals Original equipment submittals include a description of all devices that make up the fire alarm system. The listing category, visual description, power requirement for each device, and limits of usage must be included. These documents may be submitted prior to our on-site visit or made available at the time of our evaluation. Operational Manuals

13 Manuals defining the proper operation of all fire alarm system control equipment and peripheral devices must be provided for the end user. Documents must correspond with equipment models currently installed in the system. Manufacturer s Proper Testing and Maintenance Requirements Testing shall be performed in accordance with the schedules and tables found in NFPA 72 or on a frequency approved by the authority having jurisdiction. Fire alarm system equipment shall be maintained in accordance with the manufacturer s instructions. Methods and instruments that measure certain parameters as required by the manufacturer must be provided at the time of our evaluation. As part of the testing required during our evaluation, the retransmission signal and the time of the retransmission shall be recorded in the central station. A record of these tests must be provided upon completion of our field investigation. Periodic Test and Inspection Forms The forms that are used to record periodic tests and inspections of fire alarm systems are required to display the each component, device, appliance and wiring that was tested and the tests that were conducted. Contracts Central station service requires the alarm service company establish contracts with the subscriber for the performance of inspection, testing, maintenance, monitoring, signal processing and runner service. A Listed local company may in turn subcontract the monitoring and signal processing to a UL Listed central station.

14 PROTECTED PROPERTY EVALUATIONS CHECKLIST & DATA SHEETS One set of the following Checklist & Data Sheets should be completed for each fire alarm system to be evaluated. These must be returned with the pre-audit data sheets when you accept our quote. Confirmation Checklist Please confirm that all requested items will be available in your office at the time of our visit by placing a check mark to the right of each item, sign and date as indicated below. Required Documents Fire Alarm System Record of Completion As-built (Record Drawings) Operational Manuals, (Verified on hand at premise or at the alarm service company office) Manufacturer s Testing and Maintenance Requirements, (Verified on hand at premise or at the alarm service company office) Battery Calculations Copy of forms used to record periodic test and inspections Required Contracts Acceptance Test records (Signature) (Date)

15 UL LLC FIRE ALARM SYSTEM PRE-EVALUATION DATA SHEETS Please Return Completed Forms to UL Prior to Audit Name: PROTECTED PROPERTY Address: City: State: Zip Code: ALARM SERVICE COMPANY Service Center No: Name: Address: City: State: Zip Code: Representative: (Name & Title) Phone Number: ( ) COMMENTS AND CLARIFICATIONS Note: Clarify Location or Area of Coverage, as Needed

16 ALARM SYSTEM DESCRIPTION SYSTEM TYPE Select Type of System: CENTRAL STATION SERVICE - NFPA REMOTE SUPERVISING STATION NFPA PROPRIETARY SUPERVISING STATION - NFPA LOCAL ALARM SYSTEM - NFPA 72 Edition (year) Area Covered/Location: (Building(s), Floor(s), or Areas(s)) System Testing and Maintenance: Date of Periodic Testing and Maintenance Contract: Note: Variations in Testing and Maintenance Procedures from Standard shall be shown in Deviations Section: AUTHORITY HAVING JURISDICTION AHJ Responsible for System: (Specify Name and Phone Number) Responding Fire Department: AUTOMATIC FIRE DETECTION AND ALARM SERVICE Coverage: (Select One) Total Selected Area Partial Total Detectors are installed in all rooms, halls, storage areas, basements, attics, lofts, spaces above suspended ceilings, and other subdivisions and accessible spaces as well as the inside of all closets, elevator shafts, enclosed stairways, dumbwaiter shafts, and chutes. Selected Area Same code requirements as total coverage but protection is only provided for a specifically defined area(s) of the protected property. Indicate specific areas protected in Comments Section Page 1. Partial Deviations from Total or Selected Area coverage. Protection provided as required by the AHJ in areas such as common areas and work spaces, such as corridors, lobbies, storage rooms, equipment rooms, and other tenantless spaces. Quantity: Type: Smoke Detectors Heat Detectors Duct Detectors Other Specify:

17 SPRINKLER SYSTEM WATERFLOW ALARM AND SUPERVISORY SERVICE Note: If all sprinkler risers and waterflow shutoff valves are not supervised, show in Deviations Section Type of System: Wet Pipe Dry Pipe Quantity: Type: Waterflow Switches Sprinkler Valve Supervisory Switches Other Supervisory Services: Quantity: Type: Water Pressure Devices Water Temperature Devices Water Level Devices Air Pressure Devices Room Temperature Devices Fire Pump Power Devices Fire Pump Running Devices Other Specify: MANUAL FIRE ALARM AND GUARD S TOUR SUPERVISORY SERVICE Note: If proper number of fire alarm boxes required by standard is not installed, show in Deviations Section Quantity: Type: Manual Fire Alarm Boxes Guard Tour Stations Combination Manual Fire Alarm and Guard Tour Stations ALARM NOTIFICATION AND ANNUNCIATION DEVICES Note: If quantity and location of alarm notification devices does not comply with the Standard, show in Deviation Section Quantity: Type: Horns Bells Chimes Visual Signals Type: Strobe Light Graphic Audible/Visual Signals Type: Strobe Light Graphic Other Specify:

18 EMERGENCY VOICE ALARM SERVICE Quantity: Type: Speakers Voice Alarm channels Speaker Zones Telephone Jacks CONTROL PANEL COMPONENT DESCRIPTION Manufacturers and Model Numbers. Indicate model numbers and manufacturers of all control units, sub-controls, annunciators, transmission devices, power supplies, and any components used within these units. Quantity: Manufacturer & Model Number: Description: If Additional space is needed, please attach separate sheet ALARM TRANSMISSION METHOD Circle those that apply: Digital Alarm Communicator Radio System (two-way) Radio System (one-way) Cellular Digital Communicator Multiplex Derived Channel Direct Wire Internet

19 SUPERVISING MONITORING STATION Name: Address: City: State: Zip Code: UL File Number: Service Center Number: SYSTEM DOCUMENTATION Note: The following must be checked as available for all systems: Fire Alarm System Record of Completion As-Built (Record) Drawings Operational Manuals Manufacturer s Installation Instructions Battery Calculations Copy of Form used to Record Periodic Test and Inspection Required Contracts SYSTEM DEVIATIONS FROM REFERENCED NFPA STANDARDS Note: If service provided (i.e. periodic testing, maintenance, response, or coverage) is not in accordance with NFPA Standard specified, the details must be shown on this section.

FIRE ALARM SYSTEM RECORD OF COMPLETION

FIRE ALARM SYSTEM RECORD OF COMPLETION FUNDAMENTALS OF FIRE ALARM SYSTEMS 72 33 FIRE ALARM SYSTEM RECORD OF COMPLETION To be completed by the system installation contractor at the time of system acceptance and approval. 1. PROTECTED PROPERTY

More information

FIRE ALARM SYSTEM RECORD OF COMPLETION

FIRE ALARM SYSTEM RECORD OF COMPLETION FIRE ALARM SYSTEM RECORD OF COMPLETION To be completed by the system installation contractor at the time of system acceptance and approval. 1. Protected Property Information Name of property: Description

More information

TAMARAC FIRE RESCUE INSTRUCTIONS FOR FIRE ALARM PRE-SUBMITTAL CHECKLIST

TAMARAC FIRE RESCUE INSTRUCTIONS FOR FIRE ALARM PRE-SUBMITTAL CHECKLIST TAMARAC FIRE RESCUE INSTRUCTIONS FOR FIRE ALARM PRE-SUBMITTAL CHECKLIST In order to provide a comprehensive plan review in a timely manner, and to insure the design and installation of fire alarm systems

More information

DELAWARE STATE FIRE MARSHAL FIRE ALARM SYSTEM CERTIFICATE OF INSTALLATION

DELAWARE STATE FIRE MARSHAL FIRE ALARM SYSTEM CERTIFICATE OF INSTALLATION Phone System Owner Phone System Engineered by: of Record Drawings: of System Manuals: of Test Reports: System Installer 1. GENERAL INFORMATION Phone Delaware License No: Certificate Holder No. System Supplier

More information

FIRE ALARM SYSTEMS PERMIT APPLICATION, PLAN SUBMITTAL, DESIGN, INSTALLATION AND INSPECTION REQUIREMENTS Effective Date: January, 2011

FIRE ALARM SYSTEMS PERMIT APPLICATION, PLAN SUBMITTAL, DESIGN, INSTALLATION AND INSPECTION REQUIREMENTS Effective Date: January, 2011 Office of the Fire Marshal 1.0 PERMITS FIRE ALARM SYSTEMS PERMIT APPLICATION, PLAN SUBMITTAL, DESIGN, INSTALLATION AND INSPECTION REQUIREMENTS Effective Date: January, 2011 1.1 To acquire an installation

More information

INSTRUCTIONS FOR BUILDINGS WITH FIRE PROTECTION EQUIPMENT

INSTRUCTIONS FOR BUILDINGS WITH FIRE PROTECTION EQUIPMENT INSTRUCTIONS FOR BUILDINGS WITH FIRE PROTECTION EQUIPMENT FIRE EXTINGUISHERS,SPRINKLER SYSTEMS AND FIRE ALARMS Attachment #1 Inspection of Fire Extinguishers Fire Extinguishers must be tested according

More information

FIRE ALARM AND EMERGENCY COMMUNICATION SYSTEM RECORD OF COMPLETION

FIRE ALARM AND EMERGENCY COMMUNICATION SYSTEM RECORD OF COMPLETION FIRE ALARM AND EMERGENCY COMMUNICATION SYSTEM RECORD OF COMPLETION To be completed by the system installation contractor at the time of system acceptance and approval. It shall be permitted to modify this

More information

Module 4, Lesson 12 Fire Alarm Systems

Module 4, Lesson 12 Fire Alarm Systems Student Manual Module 4, Lesson 12 Fire Alarm Systems Performance Objectives At the conclusion of this lesson, you will be able to: Identify the components and functions of a fire alarm system and determine

More information

Fire Alarm System Plans Submittal Guidelines For New and Existing Systems

Fire Alarm System Plans Submittal Guidelines For New and Existing Systems Fire Alarm System Plans Submittal Guidelines For New and Existing Systems SCOPE The Temecula Fire Prevention Bureau (TFPB) has established the following requirements for the submittal of all fire alarms,

More information

CLARK COUNTY FIRE DEPARTMENT Fire Hazard & Prevention Services

CLARK COUNTY FIRE DEPARTMENT Fire Hazard & Prevention Services CLARK COUNTY FIRE DEPARTMENT Fire Hazard & Prevention Services 575 E. Flamingo Road, Las Vegas, NV 89119 (702) 455-7316 FAX (702) 455-7347 105.8a-6.1 TITLE: FIRE ALARM SYSTEM REQUIREMENTS SCOPE: This guideline

More information

EXHIBIT A SCOPE OF WORK

EXHIBIT A SCOPE OF WORK EXHIBIT A SCOPE OF WORK 1. (Contractor) shall provide fire alarm system maintenance/repair/testing services as described herein to the California Department of Veterans Affairs (hereinafter CDVA, CalVet,

More information

CHANGES IN NFPA 72 NATIONAL FIRE ALARM CODE 1999 2002

CHANGES IN NFPA 72 NATIONAL FIRE ALARM CODE 1999 2002 CHANGES IN NFPA 72 NATIONAL FIRE ALARM CODE 1999 2002 Three new chapters were added. What was chapter 1 in 1999 was reorganized into chapters 1 (Fundamentals), 2 (Referenced Publications), and 3 (Definitions).

More information

Rancho Cucamonga Fire Protection District Prevention Bureau Standard

Rancho Cucamonga Fire Protection District Prevention Bureau Standard Rancho Cucamonga Fire Protection District Prevention Bureau Standard Title: Fire Alarm and Monitoring Systems Standard # 9-3 Effective: May 2002 Number of Pages: 7 Revised: January 2014 INTENT The intent

More information

PLAN REVIEW GUIDE FOR FIRE ALARM

PLAN REVIEW GUIDE FOR FIRE ALARM PLAN REVIEW GUIDE FOR FIRE ALARM PROJECT NAME: PERMIT # PROJECT ADDRESS: CONTACT PERSON: PHONE Fire alarm system installation information shall be provided on the appropriate architectural and electrical

More information

HERNANDO COUNTY FIRE ALARM GUIDELINES

HERNANDO COUNTY FIRE ALARM GUIDELINES HERNANDO COUNTY FIRE ALARM GUIDELINES To be used for all commercial building fire alarm system plan review. The procedures set forth in this document are the minimum requirements necessary to ensure a

More information

NFPA 72. Exception No. 1: Where ambient conditions prohibit installation of automatic smoke detection, automatic heat detection shall be permitted.

NFPA 72. Exception No. 1: Where ambient conditions prohibit installation of automatic smoke detection, automatic heat detection shall be permitted. NFPA 72 3.3.7.2 3.3.7.2 False Alarm. Activation or reporting of an alarm for which no such alarm condition, fire or emergency actually exists. Additionally, False Alarm is the willful and knowing initiating

More information

FIRE ALARM AND DETECTION SYSTEMS SECTION 16721

FIRE ALARM AND DETECTION SYSTEMS SECTION 16721 PART 1 - GENERAL 1.01 WORK INCLUDED FIRE ALARM AND DETECTION SYSTEMS SECTION 16721 A. Provide a complete fully addressable, power limited, fire detection and evacuation system. The system shall be connected

More information

Module 5. Fire and Emergency Alarm System Part I- Basics

Module 5. Fire and Emergency Alarm System Part I- Basics Module 5 Fire and Emergency Alarm System Part I- Basics 1 This module will describe: 1. Components and the arrangements of components in fire and emergency alarm systems. 2. How these systems work. 3.

More information

FIRE ALARM SYSTEM SUBMITTAL CHECKLIST AND APPLICATION

FIRE ALARM SYSTEM SUBMITTAL CHECKLIST AND APPLICATION PERMITS AND INSPECTIONS FIRE ALARM SYSTEM SUBMITTAL CHECKLIST AND APPLICATION 911 Assigned PROJECT LOCATION Subdivision: Lot: Blk: Sec: PROJECT New Construction Addition/Remodel Demolition Other: Number

More information

FLORIDA ATLANTIC UNIVERSITY FIRE ALARM SYSTEM INSTALLATION MANUAL

FLORIDA ATLANTIC UNIVERSITY FIRE ALARM SYSTEM INSTALLATION MANUAL FLORIDA ATLANTIC UNIVERSITY FIRE ALARM SYSTEM INSTALLATION MANUAL January, 2003 Environmental Health and Safety Florida Atlantic University 777 Glades Rd. Boca Raton, FL 33431 Phone: 561-297-3129 Fax:

More information

SARATOGA FIRE DISTRICT EARLY WARNING FIRE ALARM SYSTEM STANDARDS AND REQUIRMENTS CONTENTS

SARATOGA FIRE DISTRICT EARLY WARNING FIRE ALARM SYSTEM STANDARDS AND REQUIRMENTS CONTENTS SARATOGA FIRE DISTRICT EARLY WARNING FIRE ALARM SYSTEM STANDARDS AND REQUIRMENTS CONTENTS I. APPLICATION AND DEFINITIONS 1.01 Authorization for Standards 1.02 Application of Standards 1.03 Definitions

More information

SECTION 16721 FIRE ALARM AND DETECTION SYSTEMS

SECTION 16721 FIRE ALARM AND DETECTION SYSTEMS SECTION 16721 FIRE ALARM AND DETECTION SYSTEMS The equipment requirements of this section apply to the IUB Campus. The IUPUI Campus has a preferred vendor agreement for fire alarm systems. Contact Pat

More information

NC State University Design and Construction Guidelines Division 26 Fire Alarm Systems

NC State University Design and Construction Guidelines Division 26 Fire Alarm Systems NC State University Design and Construction Guidelines Division 26 Fire Alarm Systems 1.0 Purpose A. The following guideline provides the minimum standards and requirements for fire alarm systems. 2.0

More information

Finance and Administration Department 907 Billy Mitchell Blvd. P: (210) 228-1022 Fire Alarm Permit Application

Finance and Administration Department 907 Billy Mitchell Blvd. P: (210) 228-1022 Fire Alarm Permit Application PERMIT FEE: $ Finance and Administration Department 907 Billy Mitchell Blvd. P: (210) 228-1022 Fire Alarm Permit Application PAYMENT TYPE: Check Credit Card Charge to Job #: (Please complete all of the

More information

FIRE ALARM APPLICATION

FIRE ALARM APPLICATION FIRE ALARM APPLICATION ENUMCLAW FIRE DEPARTMENT 1330 Wells St, Enumclaw, WA 98022 Phone: 360-825-5544 Fax: 360-825-9442 COMMUNITY DEVELOPMENT, BUILDING DEPARTMENT 1309 Myrtle Ave Enumclaw WA 98022 Phone:

More information

Fire Alarm System Plans Review Checklist Property location Date of Review

Fire Alarm System Plans Review Checklist Property location Date of Review Fire Alarm System Plans Review Checklist Property location Date of Review 1. Is application completed in entirety? 2. Are the plans review fee submitted with the application? 3. Does floor plan include

More information

Fire Alarm and Detection Systems And Central Station Monitoring Plan Submittal Guidelines

Fire Alarm and Detection Systems And Central Station Monitoring Plan Submittal Guidelines Fire Alarm and Detection Systems And Central Station Monitoring Plan Submittal Guidelines Red Oak Fire Rescue Office of the Fire Marshal 547 N. Methodist Red Oak, TX 75154 Phone: 469-218-7713 Fax: 468-218-7719

More information

FIRE DETECTION AND ALARM

FIRE DETECTION AND ALARM Scope Provide a fire alarm system, or expand the existing system, as required by Code, the requirements in the Special Instructions to Designers (SID) of the Design Guidelines, and/or as noted in the Program

More information

C. Conform to requirements of Americans with Disabilities Act (ADA).

C. Conform to requirements of Americans with Disabilities Act (ADA). SECTION 28 31 00 - FIRE ALARM AND DETECTION SYSTEMS PART 1 - GENERAL 1.1 SECTION INCLUDES A. Fire alarm and detection systems 1.2 REFERENCES A. NFPA 70 - National Electrical Code B. NFPA 72 - National

More information

Attachment 9. Trouble signals. Interfaced equipment. Primary (main) power supply

Attachment 9. Trouble signals. Interfaced equipment. Primary (main) power supply FIRE DETECTION, ALARM AND MASS NOTIFICATION SYSTEMS Inspection, testing, and maintenance of fire detection, alarm and Mass Notification systems shall be performed in accordance with the manufacturer's

More information

City of Bettendorf Fire Alarm System Requirements

City of Bettendorf Fire Alarm System Requirements City of Bettendorf Fire Alarm System Requirements Section 907 of the 2009 Edition of the International Fire Code (IFC) and Section 10-7-3 of the Municipal Code provide fire alarm requirements. IFC Section

More information

FIRE ALARM SYSTEMS PERMIT APPLICATION, PLAN SUBMITTAL, DESIGN, INSTALLATION AND INSPECTION REQUIREMENTS Effective Date: January 2014

FIRE ALARM SYSTEMS PERMIT APPLICATION, PLAN SUBMITTAL, DESIGN, INSTALLATION AND INSPECTION REQUIREMENTS Effective Date: January 2014 Office of the Fire Marshal 1.0 PERMITS FIRE ALARM SYSTEMS PERMIT APPLICATION, PLAN SUBMITTAL, DESIGN, INSTALLATION AND INSPECTION REQUIREMENTS Effective Date: January 2014 1.1 To acquire an installation

More information

SECTION 16721 FIRE ALARM AND DETECTION SYSTEM

SECTION 16721 FIRE ALARM AND DETECTION SYSTEM 1. GENERAL 1.1. Related Documents: 1.2. Scope: 1.1.1. The general provisions of the Contract, including General and Supplementary Conditions and General Requirements apply to the work specified in this

More information

Telluride Fire Protection District Fire Alarm Systems Policy Version 03/2007

Telluride Fire Protection District Fire Alarm Systems Policy Version 03/2007 Telluride Fire Protection District Fire Alarm Systems Policy Version 03/2007 FIRE ALARM SYSTEMS POLICY TELLURIDE FIRE PROTECTION DISTRICT TABLE OF CONTENTS FIRE ALARM PROTECTION POLICY PLAN REVIEW SUBMITTAL

More information

SECTION 16720 - FIRE AND SMOKE ALARM SYSTEM. City of San Diego, CWP Guidelines

SECTION 16720 - FIRE AND SMOKE ALARM SYSTEM. City of San Diego, CWP Guidelines PART 1 -- GENERAL 1.1 WORK OF THIS SECTION SECTION 16720 - City of San Diego, CWP Guidelines A. The WORK of this Section includes providing manual and automatic fire alarm and smoke detection systems meeting

More information

TESTING, INSPECTION, AND MAINTENANCE FREQUENCIES FOR FIRE DETECTION AND ALARM SYSTEMS

TESTING, INSPECTION, AND MAINTENANCE FREQUENCIES FOR FIRE DETECTION AND ALARM SYSTEMS TESTING, INSPECTION, AND MAINTENANCE FREQUENCIES FOR FIRE DETECTION AND ALARM SYSTEMS The following information regarding testing frequencies for fire detection and alarm systems. All of the following

More information

Original Document 10/16/07 Revised 01/30/09 2 nd Revision 01-23-12 3 rd Revision- 12/18/14

Original Document 10/16/07 Revised 01/30/09 2 nd Revision 01-23-12 3 rd Revision- 12/18/14 North Collier Fire Control & Rescue District Greater Naples Fire Rescue District Immokalee Fire Control & Rescue District 2800 North Horseshoe Drive Naples, Florida 34104 SYSTEM REHABILITATION PLAN CHECKLIST

More information

Commercial Fire Alarm Standards July 1, 2010 Edition Page 1 of 14

Commercial Fire Alarm Standards July 1, 2010 Edition Page 1 of 14 City of Mercer Island Development Services Group Fire Code Review and Inspection 9611 SE 36 th Street Mercer Island, WA 98040-3732 PHONE (206) 275-7605 FAX (206) 275-7726 www.mercergov.org Commercial Fire

More information

FIRE ALARM SYSTEM PLAN SUBMITTAL CHECKLIST

FIRE ALARM SYSTEM PLAN SUBMITTAL CHECKLIST FIRE ALARM SYSTEM PLAN SUBMITTAL CHECKLIST All fire alarm system plan submittals must include this Fire Alarm System Plan Submittal Checklist. PLAN APPROVAL - No work shall be performed until plans are

More information

Agenda. Agenda (continued) Fundamentals of Fire Alarm Systems

Agenda. Agenda (continued) Fundamentals of Fire Alarm Systems Fundamentals of Fire Alarm Systems Sponsored by UL SFPE Austin/San Antonio Chapter San Marcos, Texas 7 January 2015 Agenda Introduction and Administration Historical Context of Today s NFPA 72 Fire Alarm

More information

Fire Alarm Systems Certification

Fire Alarm Systems Certification Fire Alarm Systems Certification The skills and knowledge listed under each task are suggestive of those involved in that task, but are not intended to constitute an exhaustive listing. 2.1 Submittal Preparation

More information

FIREFINDER XLS ADDRESSABLE FIRE ALARM SYSTEM SECTION 13851

FIREFINDER XLS ADDRESSABLE FIRE ALARM SYSTEM SECTION 13851 FIREFINDER XLS ADDRESSABLE FIRE ALARM SYSTEM SECTION 13851 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and

More information

CITY OF PHILADELPHIA DEPARTMENT OF LICENSES AND INSPECTIONS ANNUAL CERTIFICATION FOR FIRE ALARM SYSTEMS

CITY OF PHILADELPHIA DEPARTMENT OF LICENSES AND INSPECTIONS ANNUAL CERTIFICATION FOR FIRE ALARM SYSTEMS CITY OF PHILADELPHIA DEPARTMENT OF LICENSES AND INSPECTIONS ANNUAL CERTIFICATION FOR FIRE ALARM SYSTEMS PROPERTY ADDRESS (BRT Address Required) TESTING CONTRACTOR (Name and Address) License No. ANNUAL

More information

University Design Standard. Fire Alarm Systems

University Design Standard. Fire Alarm Systems University Design Standard Fire Alarm Systems 1.0 Overview This document provides Virginia Tech s standards for the design and installation of fire alarm systems and equipment in new construction, retrofit

More information

DTW Works Master Specification Version 2006

DTW Works Master Specification Version 2006 Issued 2006/08/01 Section 13852 Multiplex Fire Alarm System Page 1 of 10 PART 1 GENERAL 1.1 RELATED WORK.1 Section 01330 Submittal Procedures..2 Section 01780 Closeout Procedures..3 Section 01810 Commissioning..4

More information

BASIC FIRE ALARM TRAINING

BASIC FIRE ALARM TRAINING BASIC FIRE ALARM TRAINING What is a fire alarm system? Per the defini+on in NFPA 72 A system or por+on of a combina+on system that consists of components and circuits arranged to monitor and annunciate

More information

SECTION 16853 ZONED (DC LOOP) FIREALARM SYSTEM

SECTION 16853 ZONED (DC LOOP) FIREALARM SYSTEM SECTION 16853 ZONED (DC LOOP) FIRE-ALARM SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1

More information

Bold items are particular to the City of Euless

Bold items are particular to the City of Euless EULESS FIRE DEPARTMENT FIRE MARSHAL S OFFICE INFORMATION LINE: Revised 2/12 Fire Chief Wes Rhodes Fire Marshal Paul Smith EFD-FMO 3-2 2009 International Fire & Building Code as Amended NFPA Standards Adopted

More information

Life Safety Code Enabling References

Life Safety Code Enabling References SUPPLEMENT 4 Life Safety Code Enabling References Editor s Note: Supplement 4 provides users of NFPA 72, National Fire Alarm and Signaling Code, with a summary of requirements from NFPA 101, Life Safety

More information

Fire Alarm Submittal Requirements and Acceptance Testing

Fire Alarm Submittal Requirements and Acceptance Testing Lubbock Fire Marshal s Office 1601 Mac Davis Lane Lubbock, Texas 79401 806-775-2646 Fax 806-775-3508 fireprevention@mylubbock.us Fire Alarm Submittal Requirements and Acceptance Testing To all Registered

More information

Michael Catalano 24 Nassau Avenue, Islip NY 11751 Phone (631) 224-5477 Chief Fire Marshal fireprevention@islipny.gov Fax (631) 224-5458

Michael Catalano 24 Nassau Avenue, Islip NY 11751 Phone (631) 224-5477 Chief Fire Marshal fireprevention@islipny.gov Fax (631) 224-5458 OFFICE OF THE FIRE MARSHAL BUREAU OF FIRE PREVENTION Michael Catalano, Phone Chief Fire Marshal fireprevention@islipny.gov Fax To whom it may concern: Enclosed please find the NFPA 72 forms needed for

More information

CHAPTER. Fire Alarm Systems APPROVAL AND ACCEPTANCE. Shop Drawings

CHAPTER. Fire Alarm Systems APPROVAL AND ACCEPTANCE. Shop Drawings Fire Alarm Systems CHAPTER 2 The information contained in this chapter is intended to assist the registered design professional (RDP), commissioning agent, authority having jurisdiction (AHJ), and the

More information

Approval Standard for Central Station Service for Fire Alarms and Protective Equipment Supervision

Approval Standard for Central Station Service for Fire Alarms and Protective Equipment Supervision Approval Standard for Central Station Service for Fire Alarms and Protective Equipment Supervision Class Number 3011 April 1999 2002 FM Approvals LLC. All rights reserved. Foreword The FM Approvals certification

More information

FVSU-33201301 REPAIR & UPGRADE FIBER OPTIC 280000-1 SECTION 280000 FIRE ALARM SYSTEM CONNECTIVITY

FVSU-33201301 REPAIR & UPGRADE FIBER OPTIC 280000-1 SECTION 280000 FIRE ALARM SYSTEM CONNECTIVITY FVSU-33201301 REPAIR & UPGRADE FIBER OPTIC 280000-1 SECTION 280000 FIRE ALARM SYSTEM CONNECTIVITY PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Fire-alarm control unit. 2. Addressable interface

More information

SECTION 16721 FIRE ALARM AND SMOKE DETECTION SYSTEMS

SECTION 16721 FIRE ALARM AND SMOKE DETECTION SYSTEMS SECTION 16721 PART 1 - GENERAL 1.1 SECTION INCLUDES A. Fire Alarm Control Panels B. Manual Fire Alarm Stations C. Automatic Smoke D. Fire Alarm Notification Appliances E. Auxiliary Fire Alarm Equipment

More information

FIRE ALARM SYSTEM. A. Shop drawings shall be submitted as follows: 1. Manufacturer's published literature. for aspproval.

FIRE ALARM SYSTEM. A. Shop drawings shall be submitted as follows: 1. Manufacturer's published literature. for aspproval. Polk School District Specifications for the New Fire Alarm in the Existing Building Eastside Elementary School FIRE ALARM SYSTEM 1.01 SUBMITTALS A. Shop drawings shall be submitted as follows: 1. Manufacturer's

More information

Fire Alarm Systems Permit Packet. City of Greer Fire Department

Fire Alarm Systems Permit Packet. City of Greer Fire Department Fire Alarm Systems Permit Packet City of Greer Fire Department Updated July 2004 If you have any questions or comments regarding the information contained within; or of you need assistance interpreting

More information

1. The objective of this guideline is to provide minimum standards for design and installation of fire alarm systems for the University of Missouri.

1. The objective of this guideline is to provide minimum standards for design and installation of fire alarm systems for the University of Missouri. GENERAL: 1. The objective of this guideline is to provide minimum standards for design and installation of fire alarm systems for the University of Missouri. 2. Fire alarm systems are Life Safety Systems

More information

Reference numbers following checklist statements represent an NFPA code section unless otherwise specified.

Reference numbers following checklist statements represent an NFPA code section unless otherwise specified. Fire Alarm System Plan Review Checklist 2010 OFC and 2007 NFPA 72 This checklist is for jurisdictions that permit the use of the 2007 NFPA 72 in lieu of IFC s referenced 2002 NFPA 72. Date of Review: Permit

More information

INSPECTION AND TESTING FORM

INSPECTION AND TESTING FORM INSPECTION AND TESTING FORM SERVICE ORGANIZATION PROPERTY NAME (USER) DATE: 08-04-15 TIME: 8:00 Name: Siemens Industries Inc. Name: Kcvtcs Madisonville Tech, School Bldg. Address: 2700 Stanley Gault Pkwy

More information

Fire Alarm System Monitoring - CAN/ULC-S561-03

Fire Alarm System Monitoring - CAN/ULC-S561-03 Fire Alarm System Monitoring - CAN/ULC-S561-03 Brian McBain ULC Regulatory Services May 4, 2011 Copyright 1995-2007 Underwriters' Laboratories of Canada. All rights reserved. No portion of this material

More information

NATIONAL FIRE ALARM AND SIGNALING CODE

NATIONAL FIRE ALARM AND SIGNALING CODE GAP.11.1.1.0 A Publication of Global Asset Protection Services LLC NATIONAL FIRE ALARM AND SIGNALING CODE INTRODUCTION National Fire Protection Association (NFPA) documents describe a level of fire protection

More information

Fire Alarm Engineering Best Practices. CFAA NCA Technical Seminar 2014

Fire Alarm Engineering Best Practices. CFAA NCA Technical Seminar 2014 Fire Alarm Engineering Best Practices CFAA NCA Technical Seminar 2014 2 Overview Code Compliance Equipment Selection and Layout Drawings, Specifications Commissioning and Acceptance Miscellaneous Goals

More information

The Evolution of Requirements for Supervising Station Alarm Systems

The Evolution of Requirements for Supervising Station Alarm Systems The Evolution of Requirements for Supervising Station Alarm Systems Fire Marshal s Association of Colorado January 18, 2013 Warren Olsen, CFPS CBCO FSCI wolsen@firesafetyfsci.com 1 Disclaimer: The comments

More information

The Mission Critical Fire Protection Experts

The Mission Critical Fire Protection Experts The Mission Critical Fire Protection Experts Protection Systems Protection Systems HFC-227ea / FM200 / FE-227 FE-25 / ECARO-25 Novec 1230 Inergen / Argonite Halon Drop-in Systems High and Low Pressure

More information

FIRE ALARM PLAN REVIEW. Office of the State Fire Marshal Massachusetts Department of Fire Services December 2009

FIRE ALARM PLAN REVIEW. Office of the State Fire Marshal Massachusetts Department of Fire Services December 2009 FIRE ALARM PLAN REVIEW Office of the State Fire Marshal Massachusetts December 2009 SURPRISE QUIZ 1. A fire alarm system is required to be installed by the MSBC, what edition of NFPA 72 do you use? 2.

More information

IR F-1 EMERGENCY VOICE/ALARM COMMUNICATION SYSTEMS

IR F-1 EMERGENCY VOICE/ALARM COMMUNICATION SYSTEMS IR F-1 Disciplines: Fire/Life Safety History: Revised 10-01-15 Issued 06-23-15 PURPOSE: This Interpretation of Regulations (IR) is being issued by the Division of the State Architect (DSA) to clarify when

More information

BS5839 Part 1:2002 Overview

BS5839 Part 1:2002 Overview BS5839 Part 1:2002 Overview 1 Contents Introduction So why is the current standard being revised? The brief for the new standard Changes to structure of current Standard Enhanced certification of Fire

More information

527 CMR: BOARD OF FIRE PREVENTION REGULATIONS

527 CMR: BOARD OF FIRE PREVENTION REGULATIONS 527 CMR 31.00: CARBON MONOXIDE ALARMS Section 31.01: Purpose and Scope 31.02: Definitions 31.03: General Installation Provisions 31.04: Specific Installation Provisions 31.05: Carbon Monoxide Protection:

More information

FIRE-FIGHTING DESIGN BRIEF REPORT

FIRE-FIGHTING DESIGN BRIEF REPORT P a g e 1 SECTION 04 (Doc.No.A/DBR 001) FIRE-FIGHTING DESIGN BRIEF REPORT P a g e 2 1.0 SCOPE 2.0 STANDARDS AND CODES 3.0 TYPES OF SYSTEM PROPOSED 4.0 FIRE HYDRANT SYSTEM 5.0 AUTOMATIC SPRINKLER SYSTEM

More information

Sprinkler and Fire Alarm Systems for the Building Official

Sprinkler and Fire Alarm Systems for the Building Official Sprinkler and for the Building Official Randall Kovacs, P.Eng., CP, FEC Gage-Babcock & Associates, Ltd. Topics Coordinated System Testing 1 Wet Dry Pre-action Deluge Wet System: Pipes filled with water

More information

CAN/ULC-S561-03 Installation and Services for Fire Signal Receiving Centres and Systems- Ottawa 2013

CAN/ULC-S561-03 Installation and Services for Fire Signal Receiving Centres and Systems- Ottawa 2013 CAN/ULC-S561-03 Installation and Services for Fire Signal Receiving Centres and Systems- Ottawa 2013 Alan Cavers, Engineering Manager Underwriters Laboratories of Canada Dec. 2013 Copyright 1995-2007 Underwriters'

More information

Engineers Edge, LLC PDH & Professional Training

Engineers Edge, LLC PDH & Professional Training 510 N. Crosslane Rd. Monroe, Georgia 30656 (770) 266-6915 fax (678) 643-1758 Engineers Edge, LLC PDH & Professional Training Copyright, All Rights Reserved Engineers Edge, LLC An Introduction to Communication

More information

2007 ICC FINAL ACTION AGENDA

2007 ICC FINAL ACTION AGENDA 907.2.1.1 System initiation in Group A occupancies with an occupant load of 1,000 or more. Activation of the fire alarm in Group A occupancies with an occupant load of 1,000 or more shall initiate a signal

More information

Automatic Fire Sprinkler Submittal Requirements

Automatic Fire Sprinkler Submittal Requirements Automatic Fire Sprinkler Submittal Requirements All commercial and industrial buildings with a total floor area of 5000 sq. ft. shall have an approved automatic sprinkler system installed. The Windsor-Severance

More information

MERCER ISLAND FIRE DEPARTMENT FIRE COMMERCIAL SPRINKLER STANDARDS

MERCER ISLAND FIRE DEPARTMENT FIRE COMMERCIAL SPRINKLER STANDARDS MERCER ISLAND FIRE DEPARTMENT FIRE COMMERCIAL SPRINKLER STANDARDS COMMERCIAL FIRE SPRINKLER SYSTEMS Page 1-5 SCOPE: Fire sprinkler systems in the City of Mercer Island shall meet the criteria as set forth

More information

SECTION 13850 DETECTION AND ALARM

SECTION 13850 DETECTION AND ALARM SECTION 13850 DETECTION AND ALARM PART 1 GENERAL 1.01 SUMMARY A. Section Includes 1. Control Panel 2 Associated Equipment B. Products Installed But Not Supplied Under This Section 1. Section 16140 - Wiring

More information

SECTION 16721 FIRE ALARM AND DETECTION SYSTEM

SECTION 16721 FIRE ALARM AND DETECTION SYSTEM SECTION 16721 FIRE ALARM AND DETECTION SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. Drawings and general provisions of Contract, including General and Supplementary Conditions and Division-1 Specification

More information

LOUISVILLE FIRE PROTECTION DISTRICT 895 West Via Appia, Louisville, Colorado 80027 303-666-8809

LOUISVILLE FIRE PROTECTION DISTRICT 895 West Via Appia, Louisville, Colorado 80027 303-666-8809 LOUISVILLE FIRE PROTECTION DISTRICT 895 West Via Appia, Louisville, Colorado 80027 303-666-8809 Contractor s Checklist and Installation Guide TABLE OF CONTENTS Fire Protection Narrative........... 3 Fire

More information

Fire Alarm FAQs. Q: How many zone/circuit fire alarm panel do I need? Q: What candela strobes do I need?

Fire Alarm FAQs. Q: How many zone/circuit fire alarm panel do I need? Q: What candela strobes do I need? 5/2/2014 Fire Alarm FAQs Question Answer Q: How many zone/circuit fire alarm panel do I need? Q: What candela strobes do I need? A: The size of a fire alarm panel is determined by a number of factors,

More information

Understanding Fire Alarm Requirements & Inspections. Presented By Bill Conroy Technical Sales For Briscoe Protective Systems Inc

Understanding Fire Alarm Requirements & Inspections. Presented By Bill Conroy Technical Sales For Briscoe Protective Systems Inc Understanding Fire Alarm Requirements & Inspections Presented By Bill Conroy Technical Sales For Briscoe Protective Systems Inc Introduction Fire Alarm Requirements are structured through a system of codes.

More information

B. NICET: National Institute for Certification in Engineering Technologies.

B. NICET: National Institute for Certification in Engineering Technologies. PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section.

More information

FireSeeker Fire Alarm Control Panel Model FS-250 Programming Manual

FireSeeker Fire Alarm Control Panel Model FS-250 Programming Manual FireSeeker Fire Alarm Control Panel Model FS-250 Programming Manual P/N 315-049403-1 Siemens Building Technologies Fire Safety Table Of Contents Introduction...1 The Access levels...1 User Level...1 Maintenance

More information

Commercial Fire Inspections

Commercial Fire Inspections Commercial Fire Inspections Fire Department Inspection Requests and Procedures The following guidelines shall be used when calling for inspection requests: 1. All inspection requests shall be coordinated

More information

NMSU FIRE DEPARTMENT Commercial Kitchen Fire Suppression Worksheet

NMSU FIRE DEPARTMENT Commercial Kitchen Fire Suppression Worksheet This Commercial Kitchen Automatic Fire has been created to assure all documentation has been submitted to assist you in assuring proper plans and documentations has been submitted and reviewed by New Mexico

More information

1.0 General. Inspection, Testing, and Maintenance 1 of 8

1.0 General. Inspection, Testing, and Maintenance 1 of 8 1.0 General 1.1 Scope This specifications covers the minimum requirements for the inspection, testing, and maintenance of the existing Notifier fire alarm systems at Bergen Community College (BCC) campus

More information

PLAN SUBMITTAL REQUIREMENTS FOR SPRAY BOOTHS AND SPRAYING ROOMS EXTINGUISHING SYSTEMS

PLAN SUBMITTAL REQUIREMENTS FOR SPRAY BOOTHS AND SPRAYING ROOMS EXTINGUISHING SYSTEMS January 1997 PLAN SUBMITTAL REQUIREMENTS FOR SPRAY BOOTHS AND SPRAYING ROOMS EXTINGUISHING SYSTEMS 1.0 PERMIT 1.1 After receipt of a Building Permit from the City of San Jose Building Department, submit

More information

Mobile Fire Rescue Department Bureau of Fire Prevention

Mobile Fire Rescue Department Bureau of Fire Prevention 222 Mobile Fire Rescue Department Bureau of Fire Prevention Samuel L. Jones Mayor Stephen A. Dean Fire Chief February 2011 2009 International Fire Code Fire Alarm and Detection Systems 907.1 General. This

More information

FIRE ALARM AND EMERGENCY COMMUNICATION SYSTEM INSPECTION AND TESTING FORM

FIRE ALARM AND EMERGENCY COMMUNICATION SYSTEM INSPECTION AND TESTING FORM FIRE ALARM AND EMERGENCY COMMUNICATION SYSTEM INSPECTION AND TESTING FORM To be completed by the system inspector or tester at the time of the inspection or test. It shall be permitted to modify this form

More information

COMMISSIONING OF FIRE ALARM SYSTEMS

COMMISSIONING OF FIRE ALARM SYSTEMS COMMISSIONING OF FIRE ALARM SYSTEMS OWNER FURNISHED The owner directly contracts an independent third party commissioning agent for this project. This Commissioning Plan has been included for reference

More information

FIRE ALARM SYSTEM CHECKLIST For Addressable Systems PRIOR TO INSPECTION

FIRE ALARM SYSTEM CHECKLIST For Addressable Systems PRIOR TO INSPECTION Building Name/Location: Installing Company: Observation By: Date: Time: 1 Building Occupants, Authorities and Alarm Monitoring Co Have Been Notified 2 FACP Manufacturer and Panel is Approved for NCSU Campus

More information

NATIONAL INSTITUTE FOR CERTIFICATION IN ENGINEERING TECHNOLOGIES. Level III Content Outline

NATIONAL INSTITUTE FOR CERTIFICATION IN ENGINEERING TECHNOLOGIES. Level III Content Outline Fire Alarm Systems Level III Content Outline The skills and knowledge listed under each task are suggestive of those involved in that task, but are not intended to constitute an exhaustive listing. 3.1

More information

AETNA FIRE ALARM SERVICE CO., INC.

AETNA FIRE ALARM SERVICE CO., INC. FIRE ALARM AND EMERGENCY COMMUNICATION SYSTEM INSPECTION AND TESTING FORM To be completed by the system inspector or tester at the inspection or test. It shall be permitted to modify this form as needed

More information

Design Options (Tradeoffs) Allowed by the 2012 Building Codes for Properties with Sprinkler Systems. April 2013

Design Options (Tradeoffs) Allowed by the 2012 Building Codes for Properties with Sprinkler Systems. April 2013 Design Options (Tradeoffs) Allowed by the 2012 Building Codes for Properties with Sprinkler Systems April 2013 The National Multi Housing Council and the National Apartment Association (NMHC/NAA) have

More information

HOW TO ESTIMATE THE COST OF A COMMERCIAL FIRE ALARM SYSTEM

HOW TO ESTIMATE THE COST OF A COMMERCIAL FIRE ALARM SYSTEM HOW TO ESTIMATE THE COST OF A COMMERCIAL FIRE ALARM SYSTEM By Robert Tranford DATE WRITTEN: MAY 25, 2004 The author is Robert Tranford. He obtained an Electrical Masters in 1981. He then founded and served

More information

ENGINEERING SPECIFICATIONS

ENGINEERING SPECIFICATIONS ENGINEERING SPECIFICATIONS FM-200 CLEAN-AGENT FIRE SUPPRESSION SYSTEM with PYRO-CHEM DETECTION/RELEASE SYSTEM March 2001 SECTION 1 - GENERAL I. SCOPE This specification outlines the requirements for a

More information