SAMPLE OF THE STUDY MATERIAL PART OF CHAPTER 3
|
|
- Cameron Dixon
- 7 years ago
- Views:
Transcription
1 SAMPLE OF THE STUDY MATERIAL PART OF CHAPTER Introduction SYMMETRICAL COMPONENTS & FAULTS CALCULATIONS Most of the faults occurring naturally are unbalanced faults. Analyzing unsymmetrical faults via KCL and KVL are very cumbersome Unsymmetrical faults create unbalanced voltage and current phasors. In order to tackle the complexity of network for unbalanced phasors, 3 ϕ phasors can be decomposed into symmetrical components (Fortesque s Theorem ) These symmetrical components are called positive sequence, negative sequence and zero sequence. Each component is analyzed separately. Analysis of each component is easy as it is balanced set of phasors. The output for each component can be subsequently added to obtain final values. Final values will be unbalanced. Individual component responses can be added only when N/W for each sequence component are perfectly decoupled i.e. the result of one is independent of the other. Fortunately in power system, positive sequence N/W, negative sequence N/W and zero sequence N/W are not mutually coupled. This makes symmetrical component decomposition for analyzing unbalanced fault an effective tool * Three sets of balanced phasors which are the symmetrical components of three unbalanced phasors. Shown in below figures. Page : 189
2 Positive Sequence Components Negative Sequence Components Zero Sequence Components Vc1 V a1 V a2 V co V b V b0 V a0 V b1 V c2 Fig Components Zero Sequence Components Considering the positive sequence components, the vector V lags behind V by 120 electrical and the vector V leads the vector V by 120 electrical since these three are also equal in magnitude V = V = V V = V 120 V = V 120 * For the positive sequence components, Stator and rotor field directions are same. Considering the negative sequence components, the vector V leads V by 120 electrical, and the vector V lags behind V by 120 electrical. * Since these three are also equal in magnitude V = V = V V = V 120 V = V 120 * For the negative sequence components, Stator and rotor field directions are reverse. For zero sequence components, we have V = V = V Page : 190
3 Since the three un balanced vectors V, V, and V can be resolved into three sets of balanced vectors, the vector V is equal to the sum of the positive sequence component V of phase a, the negative sequence component of phase a, and zero sequence component V of phase a.and zero sequence component V of phase a. i. e., V = V + V + V * Since all power systems considered to be linear, so superposition principle holds good. Similarly V = V + V + V V = V + V + V 3 unbalanced vectors (V, V, V )resolved into a total of 9 vectors, i.e, V, V, V and V, V, V and V, V, V. Out of these, only 3 are unknown. So, only three components are linearly independent. (i.e. from the knowledge of the three vectors V, V, V we can find out all the remaining vectors) OPERATORS: An operator 'a' is introduced, which when operates upon a phasor rotates it by +120 without changing the magnitude of the phasor upon which it operates. It is represented as, a = = e = J0.866 a = = e = 0.5 J0.886 a = = 1 0 = e = a + a = 0 a = a; a ; = a ; a = 1; 1 a = 3 30 ; a 1 = a 1 = a = 3 30 a a = J 3; a + a = 1 a a = J 3 * Assuming phases a as the reference, the relationship between the symmetrical components of phases 'b' and 'c' in terms of symmetrical component of phase 'a' can be written. (Phase sequence is abc) V = V + V + V V = a V + av + V or in matrix form V = av + a V + V Page : 191
4 V a V a0 V b = 1 a 2 a V a1 V c 1 a a 2 V a2 V abc = [T] V 012 Where, T = symmetrical transformation matrix V a0 = (1/3) [V a + V b + V c ] V a1 = (1/3) [V a +a V b +a 2 V c ] V a2 = (1/3) [V a +a 2 V b +a V c ] or in matrix form V a V a1 = (1/3) 1 a a 2 V a2 1 a 2 a V a V b V c V 012 = [T -1 ] V abc where, T -1 = inverse symmetrical transformation matrix Current instead of Voltage: I a = I a1 + I a2 + I a0 I b = a 2 I a1 +a I a2 + I a0 I c = a I a1 + a 2 I a2 + I a0 or in matrix form I a I a0 I b = (1/3) 1 a a I 1 I c 1 a a I 2 I abc = [T] I 012 Where, T symmetrical transformation matrix I a0 = (1/3) [ I a + I b + I c ] I a1 = (1/3) [ I a +a I b +a 2 I c ] I a2 = (1/3) [ I a +a 2 I b +a I c ] I a0 I a1 = I a2 or in matrix form (1/3) 1 a a 2 1 a 2 a I a I b I c Page : 192
5 I 012 = [T -1 ] I abc where, T -1 = inverse symmetrical transformation matrix Average 3 phase power in Terms of Symmetrical Components: P = 3 [ V a0 I a0 cos θ + V a1 I a1 cos θ + V a2 I a2 cos θ ] Impedance: V abc [T] V 012 V 012 = [Z abc ] I abc = [Z abc ] [T] I = [T -1 ] [Z abc ] [T] I Z 012 = [T -1 ] [Z abc ] [T] (since Z 012 = V 012 / I 012 ) Z s Z m Z m [Z abc ] = Z m Z s Z m Z m Z m Z s Z s & Z m are self & mutual impedances Z [Z 012 ] = 0 Z Z Sequence Impedance and Networks: The impedance of a circuit when positive sequence currents alone are flowing is called the impedance to positive sequence current. Similarly, when only negative sequence currents are present, the impedance is called the impedance to negative sequence current. When only zero sequence currents are present, the impedance is called the impedance to zero sequence current. Let Z a, Z b, Z c, & Z n are three phase impedances and neutral impedance Z a0 = 1/3 (Z a + Z b + Z c ) zero sequence Z a1 = 1/3 (Z a +az b +a 2 Z c ) positive sequence Z a2 = 1/3 (Z a +a 2 Z b +az c ) negative sequence 3.2 Sequence N/Ws of a synchronous Generator: Positive sequence Network: The positive sequence network of a synchronous generator is a balanced and symmetrical three phase network with positive sequence generated voltages (E a1, E b1, E c1 ) in the three phase, Page : 193
6 symmetrical three phase star impedance Z, in each phase and positive sequence currents (I a1, I b1, I c1 ) flowing in the three phase of shown in the below figure. I a1 Z E C1 E a1 ~ ~ ~ E b1 + I b1 Z1 Z 1 I C1 Fig. 3.2 The three phase system can be replaced by a single phase network as shown in the below: I a1 + Z 1 E for the Generated voltage E a1 - ~ V a1 V for the Terminal voltage Fig. 3.3 The equation of the positive sequence network is V a1 = E a1 I a1. Z Negative sequence network: In any general synchronous generator which is designed to generate, balanced voltages the negative sequence generated voltages are always zero. The negative network containing negative sequence impedance Z 2 in each phase and negative sequence currents flowing through these carrying negative sequence voltage drops as shown below figure. Page : 194
7 I a2 Z 2 N Z 2 Z 2 I c2 I b2 Fig. 3.4 The three phase network can be replaced by a single phase network as shown in the below figure. Z 2 I a2 V a2 Fig. 3.5 The equation for the negative sequence network is V a2 = - I a2.z Zero sequence Network: The equation for the zero sequence network is V a0 = - I a0 Z 0 Z 0 I a0 V a0 Fig. 3.6 Page : 195
8 The equivalent circuit for the zero sequence networks is different from the positive and negative sequence networks the impedance offered to zero sequence currents depends on grounding of the star point. If the star point is not grounded, then the zero sequence impedance is infinity. If the star point is grounded through some impedance Zn, then the equivalent zero sequence impedance is equal to the sum of the zero sequence phase impedance and is equal to 3Z n. Balanced three phase system consists of positive sequence components only; the negative and zero sequence components being zero. The presence of negative or zero sequence currents in a three phase system introduces asymmetry and is indication of an abnormal condition of the circuit in which these components are found. The vector sum of the positive and negative sequence currents of an unbalanced three phase system is zero. The resultant solely consists of three zero sequence currents i.e., Vector sum of all sequence currents in three phase unbalanced system = I + I + I In a three phase, 4 wire unbalanced system, the magnitude of zero sequence component is one third of the current in the neutral wire. In a three phase unbalanced system, the magnitude of negative sequence component cannot exceed that of the positive sequence component. If the negative sequence component are greater, the phase sequence of the resultant system would be reversed. The current of a single phase load drawn from a three phase system comprises equal positive, negative and zero sequence component Sequence impedances of transformer for various configuration of 3-phase transformer connection Positive sequence and negative sequence impedances are same and equal to leakage inductance and winding resistance. However transformer zero sequence impedance depends upon the configuration of transformer connection. Configuration 1: Y Y transformer bank with any one neutral grounded. Page : 196
9 H L H reference bus L Z 0 Fig. 3.7 Configuration 2: Y Y transformer bank with both neutrals grounded. H L H L reference bus Z 0 Fig. 3.8 Configuration 3: Y transformer bank with grounded Y neutral. If the neutral of the star side is grounded, zero sequence currents can flow in star path and balancing zero sequence currents can flow in delta. But no zero sequence current can flow in lines of delta side. Page : 197
10 H L reference bus H Z 0 Fig. 3.9 L Configuration 4: Y transformer bank with ungrounded star, This is special case of configuration 3 where the neutral is grounded through Z =. Therefore no zero sequence current can flow in the transformer windings. H L reference bus H Z 0 Fig L Page : 198
11 Zero sequence impedance of an alternator is zero. If alternator is star connected and grounded with impedance Z then its zero sequence impedance is 3Z. Negative sequence impedance of an alternator is same as positive sequence impedance. But there is no negative sequence induced voltage E in an alternator. Positive sequence impedance and negative sequence impedance of transmission line are same. Zero sequence impedance of a transmission line is approximately three times its positive sequence impedance because of greater coupling. Example: The line to ground voltage on the high voltage side of a step up Transformer are 100 kv, 33 kv, 38 kv on phases a, b, & c respectively. The voltage of phase a leads That of phase b by 100 & lags That of phase c by Determine analytically The symmetrical component of voltage V = 100 0, V = , V = Solution: V = 1 3 (V + λ V + λ V ) 1 [ , ] J = V 1 3 [V + λ V + λ V ] 1 [ ] 3 V = J V = 1 3 (V + V + V ) J FAULT CALCULATIONS: Faults can be classified as two types: 1. Series faults 2. Shunt faults Shunt faults are characterized by increase in current and decrease in voltage, frequency and power factor. Page : 199
12 Series faults are characterized by decrease in current and increase in voltage, frequency and power factor. The series faults are classified as 1. One open conductor fault 2. Two open conductors fault The shunt type of faults are classified as: 1. Single line to ground fault 2. Line to Line fault 3. Double line to Ground fault 4. Three phase fault The first three faults are the unsymmetrical faults. The three phase fault is symmetrical faults. Severity & occurrence of Faults: power transfer slg II IIg 3- power Faults Time Fig Fault Severity Occurrence 1) 3- (LLL,LLLG) Severe 5% 2) Phase to phase ground (LLG) Severe 10% 3) Phase to phase fault (LL) Less Severe 15% 4) Single line to ground Faults (LG) Very less 70% * 1 cause of short circuit insulation failure. Overvoltage caused by lightning or switching surge. Insulation contamination salt spray, pollution. Mechanical causes overheating, abrasion. Page : 200
13 3.3.1 Faults on T.L. Most common lines are exposed to elements of nature 60 70% lightning stroke over voltage causes insulation to flash over Line to ground short circuit or line to line s.c. High winds topple tower, tree falls on line. Winds an ice loading mechanical failure of insulation. For, salt spray, dirty insulation conduction path insulation failure. S. C. other elements. Cabels (10 15%), C.B. (10 12%) generator, motor, X-mer (10 15%) much less common over loading for extended periods deterioration of insulation Voltage of the Neutral: The potential of the neutral when it is grounded through some impedance or is isolated, will be at ground potential unbalanced conditions such as unsymmetrical faults. The potential of the neutral is given as V n =I n Z n where Z n is the neutral grounding impedance and I n is neutral current. Here negative sign is used as the current flow from the ground to the neutral of the system and potential of the neutral is lower than the ground. For a 3- phase system, I n = I a +I b +I c = (I a1 + Ia 2 + Ia 0 ) + (a Ia 1 +aia 2 Ia 0 ) + (a I a1 + a 2 Ia 2 + Ia 0 ) = I a1 (1+a+a 2 ) + Ia 2 (1+a+a 2 ) +3Ia 0 = 3Ia 0 V n = -3I a0 Z n Since the positive sequence and negative sequence components of currents through the neutral are absent, the drops due to these currents are also zero Single Line to Ground Fault: 1. Most frequently occurring fault. 2. Usually assumed the fault on phase a for analysis purpose, phase b and phase are healthy. The boundary conditions are a) V a = 0.(1) b) I b = 0.(2) c) I c = 0.(3) Page : 201
14 I a Z ~ - + E a + ~ - E c - - ~ E b + Z I b Z The sequence network equations are V a0 = - I a0 Z 0..(4) V a1 =E a -I a1 Z 1 (5) V a2 = I a2 Z 2....(6) Fig I c The solution of these six equations will give six unknowns V a0, V a1, V a2 and I a0, I a1, and I a2 Since I a1 = (1/3) [I a + a I b + a 2 I c ] I a2 = (1/3) [I a + a 2 I b + a I c ] I a0 = (1/3) [I a + I b + I c ] Substituting the values of I b and I c from equations (2), (3)in above three equations I a1 = I a2 = I a0 = I a /3.(7) Equation (1) can be written in terms of symmetrical components V a = 0 = V a1 + V a2 + V a0 Now substituting the values of V a0, V a1 and V a2 from the sequence network equation, E a - I a1 Z 1 I a2 Z 2 I a0 Z 0 = 0 (8) Since I a1 = I a2 = I a0 Equation (8) becomes Page : 202
15 E a I a1 Z 1 I a1 Z 2 - I a1 Z 0 =0 I a1 = I f = I a = I a1 + I a2 + I a0 ; I = I = I and +ve, ve and zero sequence networks are connected in series. I f = Single Line of Ground fault with Z f : I a1 = ( ) ~ Z 1 I a1 V a1 Z 2 I a2 V a2 Z 0 I a0 V a0 Conclusion: Fig The three sequence networks are connected in series. 2. If the neutral of the generator is not grounded, the Zero network is open circuited. Line to Line Fault The line to line fault takes place on phases b and c The boundary conditions are I a = 0. (1) I b + I c = 0. (2) V b = V c...(3) Page : 203
16 a I a E a Z E C C Z Z E b b I b I c Fig The sequence network equations are V a0 = -I a0 Z 0.. (4) V a1 = E a = I a1 Z 1 V a2 = - I a2 Z 2 (5) (6) The solution of these six equations will give six unknowns V a0, V a1, V a2, and I ao, I a1 and I a2 Since I a1 = (1/3) [I a + a I b + a 2 I c ] I a = (1/3) [I a + a 2 I b + a I c ] I a1 = (1/3) [I a + I b + I c ] Substituting the values of I a, I b and I c from equations in above three equations I a1 = (1/3) [0 +a I b - a 2 I b ] = (1/3) [a- a 2 ] I b I a2 = (1/3) [0 +a 2 I b - a I b ] = (1/3) [ a 2 - a] I b I a0 = (1/3) [0 + I b - I b ] I a0 = 0 Which means for a line to line fault the zero sequence component of current is absent and positive sequence component of current is equal in magnitude but opposite in phase to negative sequence component of current, i.e., Page : 204
17 Z 1 I a1 Z 2 I a2 E a V a1 V a2 Fig I a1 = -I a2 (7) Since V b = a 2 V a1 + av a2 + V a0.. (8) V C = av a1 + a 2 V a2 + V a0 Substituting the equations (8) and (9) equations (3) a 2 V a1 + av a2 + V a0 = av a1 + a 2 V a2 V a0..(9) V a1 = V a2 (10) i.e., positive sequence component of voltage equals the negative sequence component of voltage. This also means that the two sequence networks are connected in opposition. Now making use of the sequence network equation and the equation (10) V a1 = V a2. E a - I a1 Z 1 = -I a2 Z 2 = I a1 Z 2 I a1 = I f = I b = - I c = a 2 I a1 + ai a2 + I a0 (I a2 = - I a1, I a0 =0) = (a a)ia = J 3 I a1 = Conclusion: 1. The connection of sequence currents are connected in parallel. 2. The phase difference between I a1 and I a2 for line to line fault should be 180 (I a1 = I a2 ). Line to Line fault with Z f I a1 = ( ) Double Line to Ground Fault: Here sequence networks are connected in parallel. Page : 205
18 Double line to ground fault takes place on phases b and c The boundary conditions are I a = 0.(1) V b = 0.(2) V c = 0.(3) The sequence network equations are V a0 = -I a0 Z 0.(4) V a1 = E a I a1 Z 1.(5) V a2 = -I a2 Z 2...(6) I a Z + E a Z E c E b Z I b C b I c Fig The solution of these six equations will give six unknowns V a0, V a1, V a2 and I a0, I a1 and I a2. Since V a0 = (1/3) [V a + V b + V c ] V a1 = (1/3) [V a + av b + a 2 V c ] V a2 = (1/3) [V a + a 2 V b + a V c ] Using above three equations and substituting for V a, V b and V c from the equation (2) and (3) V a0 = (1/3) [V a ] = V a /3 V a1 = (1/3) [V a +a. 0 +a 2. 0 ] = V a /3 Page : 206
19 V a2 = (1/3) [V a +a a.0 ] = V a /3 V a0 = V a1 = V a2.(7) Using this relation of voltages and substituting in the sequence network equations V a0 = V a1 Similarly I a0 Z 0 = E a I a1 Z 1 I a0 = [ ]..(8) V a2 = V a1 I a2 Z 2 = E a I a1 Z 1 I a2 = [ ] Now from equation (1) I a = I a1 + I a2 +I a0 =0.(9) E a + Z1 V a1 Z 2 V a2 Z 0 + I a2 + I a0 I a1 Substituting values of I a2 and I a0 from the equation(9) and (8) Therefore I a1 = I a1 = [ ] [ ] = 0 I f =I b + I c = 3 I a0 I a0 = -I a1 Fig Page : 207
20 I f = -3 I a1 Conclusion: Zero sequence and negative sequence networks are parallel and this is in series to the positive sequence. Double line to ground fault with Z f I a1 = 3.4 Three Phase Fault The boundary conditions are I a + I b + I c = 0 V a = V b =V c I a is taken as reference I b = a 2 I a and I c = ai a a I a E a Z E C Z Z E b C b I b I c Fig I a1 =1/3 (I a + a I b + a 2. I c ) and substituting the values of I b and I c I a1 = 1/3 (I a + a. a 2 I a + a 2 a I a ) Ia 1 = Ia I a2 = 1/3 (I a + a 2 I b + a I c ) = 1/3 (I a + a 4 I b + a 2 I c ) Page : 208
21 = 1/3 (I a + a I a + a 2 I c ) = (1 + a + a2 ) = 0 I a0 = 1/3 (I a + I b +I c ) = 0 V a1 = 1/3 (V a + a V b + a 2 V c ) = 1/3 (V a + a V a + a 2 V a ) = V a (1 + a + a 2 ) = 0 V a1 = 1/3 (V a + a 2 V b + a.v c ) = 0 Since V a1 = 0 = E a I a1 Z 1, I a1 = E a / Z 1 The frequent fault in transformer line is single line to ground fault. The most severe fault is 3-phase fault. The most severe fault nearer to generator is single line to ground fault. From the analysis of the various faults, the following observations are made: 1. Positive sequence currents are present in all types of faults. 2. Negative sequence currents are present in all unsymmetrical faults. 3. Zero sequence currents are present when the neutral of the system is grounded and the fault also involves the ground, and magnitude of the neutral current is equal to 3 I a0. When currents are entering a delta connected winding, positive sequence components of line currents lead the corresponding positive sequence components of phase currents (winding current) in delta winding by 90. Positive sequence components of line currents on the star side of a star delta transformer, lead the corresponding positive sequence line currents on the delta side by 90. Positive sequence components of line and phase voltages on the star side of a star delta transformer lead the corresponding positive sequence line and equivalent phase voltages respectively on the delta side by 90. Proof: Balanced three phase system consists of positive sequence components only; the negative and zero sequence components being zero. Balanced system, Voltages must be in the form of V b = a 2 V a V c = av a Page : 209
22 From Inverse symmetrical transformation, V 012 = [T -1 ] V abc V V = (1/3) V a a 1 a a V V V V = (1/3) 1 a a a V 1 a a a V = (1/3) 1 a a a V a 1 a a a 0 = 1/33 V a 1 + a + a 2 = 0 0 a 3 = 1, a 4 = a 3. a = a V V = V 0 0 V Load Flow So for balanced 3 ϕ system, V a0 = V a2 = 0; V a1 =V a * Load cannot be same for all time in the system. The power flow idea is to find out the voltage at different bus bar, sub - station, node point & the flow of power on these lines, with given constraints and specifications. Types of Buses: 1. Load bus: In this type of bus, P and Q are known. The unknowns are V and δ. 2. Slack Bus/Reference Bus/Swing Bus:- This bus is a special type of bus. Here real and reactive powers are not specified only V and δ are known. 3. Generator/Voltage control/pv Bus:- In this type of bus, P and V are known. Q and δ are not known. Page : 210
23 3.5 Power System Network P G1, Q G1 1 generator ~ ~ bus burs L 2 P L3, Q L3 P G3, Q G3 3 L 1 L 3 L 6 L 4 L P G2, Q G2 ~ P L2, Q L2 P L4, Q L4 P L5, Q L5 L Load Fig G Generator [Those bus who has self generator are called generated bus bar.] [Who s don t have generator called load bus bar.] Page : 211
24 to bus m to bus s to bus V k = V k δ P LK Q LK P GK gen Q GK Load P K = P GK P LK Q K = Q GK Q LK Where P injected power (real) in to bus. Fig & Q injected (reactive) power into bus. For load bus P = Q = 0 So we can write P = P (i) Q = Q (ii) On the behalf of equation (i) and (ii) load bus are drawing the power. Example: P km, Q km to bus m P kj, Q kj to bus J P ki, Q ki to bus i Bus K V k = V k δ P K Q K Fig Page : 212
25 P = P P P = P + P + P Q = Q Q Q = Q + Q + Q Static analysis of Power Network. Mathematical model of the Network T.L. nominal π model. Bus power injection S = V i = P + JQ. P = P Q, Q = Q Q. But Admittance matrix Taking small example P 1, Q 1 P 3, Q 3 1 L 2 3 L 1 L 3 2 P 2, Q 2 Fig Page : 213
26 Equivalent π model: P 3, Q 3 P 1 Q 1 Y 130 Y 310 I 1 3 Y 120 Y 13 Y 12 Y 23 Y 210 Y Y 230 Shunt admittance P 2, Q 2 Fig Now, power equation converting in current equation. So we can write equation. I = Y V + Y (V V ) + Y V + Y (V V ) I = Y V + Y (V V ) + Y V + Y (V V ) I = Y V + Y (V V ) + Y V + Y (V V ) I Y + Y + Y + Y Y Y (Y I = + Y + Y + Y ) V Y Y I Y V V Y Y (Y + Y + Y + Y ) I Y Y Y V I = Y Y Y V I Y Y Y V Y = Y = Y self admittance. (Driving point admittance) Y = Y = X transfer admittance or mutual adce. Y Page : 214
27 I = Y V V = Z I Z = [Y ] 1. Y formatting is so easy & & Z matrix comp. 2. Y is symmetric matrix Y = Y = Y Y = Y = Y Y = Y = Y Y matrix is sparse matrix. (Sparse means most of the elements of Y matrix are zero) Because there are 90% elements are zero. 3. Dimension of Y is (N N) N = No. of bus Power Flow Equation I = Y V I = Y V S = P + JQ = V I P + JQ = V Y V = V e. V Y = Y e, k, n = 1, 2, N. P + JQ = V Y P = V V Q = V V, K = 1, 2, N. V e ( ) Y cos (δ δ θ ) Y sin(δ δ θ ) Characteristics of power flow equation Power flow equation are algebraic static system. nonlinear Iterative solution Relate P, Q in terms of V, δ & Y elements P, Q f (V, δ) There are two methods to solve these non linear equations: Page : 215
28 1. Newton Raphson method 2. Gauss Seidal method Newton Raphson (N.R.) method has got quadratic convergence and is fast as compared to Gauss Seidal and always converge. But N.R. method requires more time per iteration. Gauss Seidal has got linear convergence, convergence is affected by choice of slack bus and the presence of sense capacitor. Example: Assume a three phase system with a sustained supply voltage of 2,300 volts from line to neutral and with line impedance Z = j 10Ω, Z = j10ω and Z = (10 + j 10)Ω. Compute the magnitude of fault current for a single line to ground fault at the end of the line. Solution: Supply voltage = 2300 V line/neutral Z = j 10 Ω Z = j 10 Ω Z = (10 + j 10)Ω For a single line to ground fault at a in Figure below. a I a b I b c I c I = 0, I = 0, V = 0 Fig then I = I = I V I = Z + Z + Z where V is prefault voltage 2300 = j10 + j j10 = j30 Also I = I + I + I = 3I = = A 10 + j30 Page : 216
SAMPLE OF THE STUDY MATERIAL PART OF CHAPTER 3. Symmetrical Components & Faults Calculations
SAMPLE OF THE STUDY MATERIAL PART OF CHAPTER 3 3.0 Introduction Fortescue's work proves that an unbalanced system of 'n' related phasors can be resolved into 'n' systems of balanced phasors called the
More informationThe following table shows approximate percentage wise the
SHORT-CIRCUIT CALCULATION INTRODUCTION Designing an electrical system is easy and simple, if only the normal operation of the network is taken into consideration. However, abnormal conditions which are
More information1 Introduction. 2 The Symmetrical Component Transformation. J.L. Kirtley Jr.
Massachusetts Institute of Technology Department of Electrical Engineering and Computer Science 6.06 Introduction to Power Systems Class Notes Chapter 4 Introduction To Symmetrical Components J.L. Kirtley
More informationPower measurement in balanced 3 phase circuits and power factor improvement. 1 Power in Single Phase Circuits. Experiment no 1
Experiment no 1 Power measurement in balanced 3 phase circuits and power factor improvement 1 Power in Single Phase Circuits Let v = m cos(ωt) = cos(ωt) is the voltage applied to a R-L circuit and i =
More informationThree phase circuits
Three phase circuits THREE PHASE CIRCUITS THREE-PHASE ADVANTAGES 1. The horsepower rating of three-phase motors and the kva rating of three-phase transformers are 150% greater than single-phase motors
More informationSteady-State Power System Security Analysis with PowerWorld Simulator
Steady-State Power System Security Analysis with PowerWorld Simulator S: Power System Modeling Methods and Equations 00 South First Street Champaign, Illinois 680 + (7) 384.6330 support@powerworld.com
More informationChapter 12: Three Phase Circuits
Chapter 12: Three Phase Circuits 12.1 What Is a Three Phase Circuit? 12.2 Balance Three Phase Voltages 12.3 Balance Three Phase Y to Y Connection 12.4 Other Balance Three Phase Connections 12.5 Power in
More informationDigital Energy ITI. Instrument Transformer Basic Technical Information and Application
g Digital Energy ITI Instrument Transformer Basic Technical Information and Application Table of Contents DEFINITIONS AND FUNCTIONS CONSTRUCTION FEATURES MAGNETIC CIRCUITS RATING AND RATIO CURRENT TRANSFORMER
More informationBasic Laws Circuit Theorems Methods of Network Analysis Non-Linear Devices and Simulation Models
EE Modul 1: Electric Circuits Theory Basic Laws Circuit Theorems Methods of Network Analysis Non-Linear Devices and Simulation Models EE Modul 1: Electric Circuits Theory Current, Voltage, Impedance Ohm
More informationGenerator Stator Protection, under/over voltage, under /over frequency and unbalanced loading. Ramandeep Kaur Aujla S.NO 250447392
1 Generator Stator Protection, under/over voltage, under /over frequency and unbalanced loading By Ramandeep Kaur Aujla S.NO 250447392 ES 586b: Theory and applications of protective relays Department of
More informationScholars Research Library
Available online at www.scholarsresearchlibrary.com Scholars Research Library Archives of Applied Science Research, 2010, 2 (2):380-387 (http://scholarsresearchlibrary.com/archive.html) ISSN 0975-508X
More informationChapter 9 Balanced Faults
Chapter 9 alanced Faults 9.1 Introduction The most common types of fault are (in order) single-line-to-ground fault, line-to-line fault, and double-line-to-ground fault. All of these are unbalanced faults.
More informationSYNCHRONOUS MACHINES
SYNCHRONOUS MACHINES The geometry of a synchronous machine is quite similar to that of the induction machine. The stator core and windings of a three-phase synchronous machine are practically identical
More information13 ELECTRIC MOTORS. 13.1 Basic Relations
13 ELECTRIC MOTORS Modern underwater vehicles and surface vessels are making increased use of electrical actuators, for all range of tasks including weaponry, control surfaces, and main propulsion. This
More informationDHANALAKSHMI COLLEGE OF ENGINEERING DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING EE2302 - ELECTRICAL MACHINES II UNIT-I SYNCHRONOUS GENERATOR
1 DHANALAKSHMI COLLEGE OF ENGINEERING DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING Constructional details Types of rotors EE2302 - ELECTRICAL MACHINES II UNIT-I SYNCHRONOUS GENERATOR PART A 1.
More informationBALANCED THREE-PHASE CIRCUITS
BALANCED THREE-PHASE CIRCUITS The voltages in the three-phase power system are produced by a synchronous generator (Chapter 6). In a balanced system, each of the three instantaneous voltages have equal
More informationANN Based Fault Classifier and Fault Locator for Double Circuit Transmission Line
International Journal of Computer Sciences and Engineering Open Access Research Paper Volume-4, Special Issue-2, April 2016 E-ISSN: 2347-2693 ANN Based Fault Classifier and Fault Locator for Double Circuit
More informationA Direct Numerical Method for Observability Analysis
IEEE TRANSACTIONS ON POWER SYSTEMS, VOL 15, NO 2, MAY 2000 625 A Direct Numerical Method for Observability Analysis Bei Gou and Ali Abur, Senior Member, IEEE Abstract This paper presents an algebraic method
More informationChapter 3 AUTOMATIC VOLTAGE CONTROL
Chapter 3 AUTOMATIC VOLTAGE CONTROL . INTRODUCTION TO EXCITATION SYSTEM The basic function of an excitation system is to provide necessary direct current to the field winding of the synchronous generator.
More informationLecture 7 Circuit analysis via Laplace transform
S. Boyd EE12 Lecture 7 Circuit analysis via Laplace transform analysis of general LRC circuits impedance and admittance descriptions natural and forced response circuit analysis with impedances natural
More information2.1 Introduction. 2.2 Terms and definitions
.1 Introduction An important step in the procedure for solving any circuit problem consists first in selecting a number of independent branch currents as (known as loop currents or mesh currents) variables,
More informationW03 Analysis of DC Circuits. Yrd. Doç. Dr. Aytaç Gören
W03 Analysis of DC Circuits Yrd. Doç. Dr. Aytaç Gören ELK 2018 - Contents W01 Basic Concepts in Electronics W02 AC to DC Conversion W03 Analysis of DC Circuits (self and condenser) W04 Transistors and
More informationBasic Electrical Technology Dr. L. Umanand Department of Electrical Engineering Indian Institute of Science, Bangalore. Lecture - 33 3 phase System 4
Basic Electrical Technology Dr. L. Umanand Department of Electrical Engineering Indian Institute of Science, Bangalore Lecture - 33 3 phase System 4 Hello everybody. So, in the last class we have been
More informationModeling of Transmission Lines
Modeling of Transmission Lines Electric Power Transmission The electric energy produced at generating stations is transported over high-voltage transmission lines to utilization points. The trend toward
More informationPower System review W I L L I A M V. T O R R E A P R I L 1 0, 2 0 1 3
Power System review W I L L I A M V. T O R R E A P R I L 1 0, 2 0 1 3 Basics of Power systems Network topology Transmission and Distribution Load and Resource Balance Economic Dispatch Steady State System
More informationINTRODUCTION TO SYSTEM PROTECTION. Hands-On Relay School 2012
INTRODUCTION TO SYSTEM PROTECTION Hands-On Relay School 2012 CONGRATULATIONS On choosing the field of system protection. It is an exciting, challenging profession. System protection has changed considerably
More informationOpen Phase Conditions in Transformers Analysis and Protection Algorithm
Open Phase Conditions in Transformers Analysis and Protection Algorithm Amir Norouzi GE Digital Energy Markham, ON amir.norouzi@ge.com Abstract This paper first provides an in-depth analysis of open phase
More informationGenetic Algorithm approach to find excitation capacitances for 3- phase smseig operating single phase loads
Genetic Algorithm approach to find excitation capacitances for 3- phase smseig operating single phase loads Authors & Affiliation: V.Ravi Kiran, V.Manoj and P.Praveen Kumar Asst. Professor, EEE Dept GMRIT,
More informationFault Analysis I13-1. 2008 PowerWorld Corporation
Fault Analysis Analysis of power system parameters resulting from a ground or line to line fault somewhere in the system Simulator contains a tool for analyzing faults in an automatic fashion Can perform
More informationINDUCTION REGULATOR. Objective:
INDUCTION REGULATOR Objective: Using a wound rotor induction motor an Induction Regulator, study the effect of rotor position on the output voltage of the regulator. Also study its behaviour under load
More informationPower Quality Paper #3
The Effect of Voltage Dips On Induction Motors by: M D McCulloch 1. INTRODUCTION Voltage depressions caused by faults on the system affect the performance of induction motors, in terms of the production
More informationChapter 12 Three-Phase Circuit
Chapter 12 Three-Phase Circuit 馮 武 雄 教 授 長 庚 大 學 電 子 系 1 Chapter 12 Three-Phase Circuits 12.1 What is a Three-Phase Circuit? 12.2 Balance Three-Phase oltages 12.3 Balance Three-Phase Connection 12.4 Power
More informationSingle and Three Phase Transformer Testing Using Static Motor Circuit Analysis Techniques
Single and Three Phase Transformer Testing Using Static Motor Circuit Analysis Techniques Howard W. Penrose, Ph.D On behalf of ALL-TEST Pro, LLC Old Saybrook, CT Introduction Field and shop testing of
More informationUCI274C - Technical Data Sheet
- Technical Data Sheet SPECIFICATIONS & OPTIONS STANDARDS Newage Stamford industrial generators meet the requirements of BS EN 60034 and the relevant section of other international standards such as BS000,
More informationUCI274H - Technical Data Sheet
- Technical Data Sheet SPECIFICATIONS & OPTIONS STANDARDS Newage Stamford industrial generators meet the requirements of BS EN 60034 and the relevant section of other international standards such as BS000,
More informationMotor Fundamentals. DC Motor
Motor Fundamentals Before we can examine the function of a drive, we must understand the basic operation of the motor. It is used to convert the electrical energy, supplied by the controller, to mechanical
More informationElectron S.R.L. A29 ELECTRICAL POWER SYSTEM TRAINERS. Production Transmission Distribution
lectron S..L. Design Production & Trading of ducational quipment A29 LCTICAL POW SYSTM TAINS Production Transmission Distribution FAX 9065 980 - -mail: electron@electron.it Web: www.electron.it ev 02 Specifications
More informationPI144K - Winding 311 APPROVED DOCUMENT. Technical Data Sheet. Generator Solutions AS
PI144K - Winding 311 Technical Data Sheet PI144K SPECIFICATIONS & OPTIONS STANDARDS TERMINALS & TERMINAL BOX Stamford industrial generators meet the requirements of BS EN 60034 and the relevant section
More informationPI044E - Winding 311 APPROVED DOCUMENT. Technical Data Sheet
PI044E - Winding 311 Technical Data Sheet PI044E SPECIFICATIONS & OPTIONS STANDARDS Stamford industrial generators meet the requirements of BS EN 60034 and the relevant section of other international standards
More informationPHASOR DIAGRAMS HANDS-ON RELAY SCHOOL WSU PULLMAN, WA. RON ALEXANDER - BPA
PHASOR DIAGRAMS HANDS-ON RELAY SCHOOL WSU PULLMAN, WA. RON ALEXANDER - BPA What are phasors??? In normal practice, the phasor represents the rms maximum value of the positive half cycle of the sinusoid
More informationCircuit Analysis using the Node and Mesh Methods
Circuit Analysis using the Node and Mesh Methods We have seen that using Kirchhoff s laws and Ohm s law we can analyze any circuit to determine the operating conditions (the currents and voltages). The
More informationChapter 11 Balanced Three-Phase Circuits
Chapter 11 Balanced Three-Phase Circuits 11.1-2 Three-Phase Systems 11.3 Analysis of the Y-Y Circuit 11.4 Analysis of the Y- Circuit 11.5 Power Calculations in Balanced Three-Phase Circuits 11.6 Measuring
More informationHCM434F - Winding 311 APPROVED DOCUMENT. Technical Data Sheet
HCM434F - Winding 311 Technical Data Sheet HCM434F SPECIFICATIONS & OPTIONS STANDARDS Marine generators may be certified to Lloyds, DnV, Bureau Veritas, ABS, Germanischer-Lloyd or RINA. Other standards
More informationTHREE PHASE CIRCUITS
THREE PHASE CIRCUITS A. PREPARATION 1. Three Phase Voltages and Systems 2. The Determination of Phase Sequence 3. Blondel's Theorem and Its Consequences 4. References B. EXPERIMENT 1. Equipment List 2.
More informationChapter 24. Three-Phase Voltage Generation
Chapter 24 Three-Phase Systems Three-Phase Voltage Generation Three-phase generators Three sets of windings and produce three ac voltages Windings are placed 120 apart Voltages are three identical sinusoidal
More informationSimulation of Ungrounded Shipboard Power Systems in PSpice
Simulation of Ungrounded Shipboard Power Systems in PSpice Haibo Zhang IEEE Student Member Karen L.Butler IEEE Member Power System Automation Lab Electrical Engineering Department Texas A&M University
More information8 Speed control of Induction Machines
8 Speed control of Induction Machines We have seen the speed torque characteristic of the machine. In the stable region of operation in the motoring mode, the curve is rather steep and goes from zero torque
More informationPrinciples of Adjustable Frequency Drives
What is an Adjustable Frequency Drive? An adjustable frequency drive is a system for controlling the speed of an AC motor by controlling the frequency of the power supplied to the motor. A basic adjustable
More informationElectrical Fault Level Calculations Using the MVA Method
J.M. PNG & SH PT LTD Chapter lectrical ault Level Calculations Using the Method 5 With modern day personal computers, hand calculations for electrical fault level are becoming a thing of the past. The
More informationLIMITING SHORT-CIRCUIT CURRENTS IN MEDIUM-VOLTAGE APPLICATIONS
LIMITING SHORT-CIRCUIT CURRENTS IN MEDIUM-VOLTAGE APPLICATIONS Terence Hazel Senior Member IEEE Schneider Electric 38050 Grenoble France Abstract The power requirements for large industrial sites is increasing.
More informationNeutral to Earth Voltage Reduction Methods in Three-Phase Four Wire Distribution Systems
Neutral to Earth oltage Reduction Methods in ThreePhase Four Wire Distribution Systems G. Ahmadi and S.M. Shahrtash ran University of Science and Technology (UST) gahmadi@ieee.org Center of Excellence
More information1 Introduction. 2 Two Phases. J.L. Kirtley Jr.
Massachusetts Institute of Technology Department of Electrical Engineering and Computer Science 6.061 Introduction to Power Systems Class otes Chapter 3 Polyphase etworks J.L. Kirtley Jr. 1 Introduction
More informationLecture Notes ELE A6
ecture Notes EE A6 Ramadan El-Shatshat Three Phase circuits 9/12/2006 EE A6 Three-phase Circuits 1 Three-phase Circuits 9/12/2006 EE A6 Three-phase Circuits 2 Advantages of Three-phase Circuits Smooth
More informationModule 2. DC Circuit. Version 2 EE IIT, Kharagpur
Module DC Circuit Lesson 4 Loop Analysis of resistive circuit in the context of dc voltages and currents Objectives Meaning of circuit analysis; distinguish between the terms mesh and loop. To provide
More informationHow To Understand And Understand The Theory Of Electricity
DIRECT CURRENT AND ALTERNATING CURRENT SYSTEMS N. Rajkumar, Research Fellow, Energy Systems Group, City University Northampton Square, London EC1V 0HB, UK Keywords: Electrical energy, direct current, alternating
More informationDIRECT CURRENT GENERATORS
DIRECT CURRENT GENERATORS Revision 12:50 14 Nov 05 INTRODUCTION A generator is a machine that converts mechanical energy into electrical energy by using the principle of magnetic induction. This principle
More informationRadial Distribution Test Feeders
Radial Distribution Test Feeders Distribution System Analysis Subcommittee Report Abstract: Many computer programs are available for the analysis of radial distribution feeders. In 1992 a paper was published
More informationPM734F - Technical Data Sheet Winding 28
- Technical Data Sheet Winding 28 SPECIFICATIONS & OPTIONS STANDARDS STAMFORD AC generators are designed to meet the performance requirements of IEC EN 60034-1. Other international standards, including
More informationLab 8: DC generators: shunt, series, and compounded.
Lab 8: DC generators: shunt, series, and compounded. Objective: to study the properties of DC generators under no-load and full-load conditions; to learn how to connect these generators; to obtain their
More informationDesign and Analysis of Switched Reluctance Motors
Design and Analysis of Switched Reluctance Motors İbrahim ŞENGÖR, Abdullah POLAT, and Lale T. ERGENE Electrical and Electronic Faculty, İstanbul Technical University, 34469, Istanbul, TURKEY sengoribrahim@gmail.com,
More informationThe generation and supply of electricity within the U.K is achieved through the use of a 3-phase system.
Three Phase Electricity Supplies and Systems The generation and supply of electricity within the U.K is achieved through the use of a 3-phase system. This consists of 3 separate phase conductors along
More informationMotors and Generators
Motors and Generators Electro-mechanical devices: convert electrical energy to mechanical motion/work and vice versa Operate on the coupling between currentcarrying conductors and magnetic fields Governed
More information3-Phase AC Calculations Revisited
AN110 Dataforth Corporation Page 1 of 6 DID YOU KNOW? Nikola Tesla (1856-1943) came to the United States in 1884 from Yugosiavia. He arrived during the battle of the currents between Thomas Edison, who
More information2. A conductor of length 2m moves at 4m/s at 30 to a uniform magnetic field of 0.1T. Which one of the following gives the e.m.f. generated?
Extra Questions - 2 1. A straight length of wire moves through a uniform magnetic field. The e.m.f. produced across the ends of the wire will be maximum if it moves: a) along the lines of magnetic flux
More informationElectrical safety requirements in DC distribution systems
Electrical safety requirements in DC distribution systems PAUL J.L.AN TICHELEN, DOMINIQUE WEYEN ITO Boeretang 200, 2400 Mol BELGIUM Abstract: This paper focuses on the safety requirements for the DC bus
More informationCoupled Inductors. Introducing Coupled Inductors
Coupled Inductors From power distribution across large distances to radio transmissions, coupled inductors are used extensively in electrical applications. Their properties allow for increasing or decreasing
More informationSeries and Parallel Resistive Circuits
Series and Parallel Resistive Circuits The configuration of circuit elements clearly affects the behaviour of a circuit. Resistors connected in series or in parallel are very common in a circuit and act
More informationGrounding of Electrical Systems NEW CODE: Grounding and Bonding
Grounding of Electrical Systems NEW CODE: Grounding and Bonding Presented By Scott Peele PE Grounding of Electrical Systems Outline Defining the Terms Why should I Ground? Types of Grounding Systems Separately
More informationCircuits with inductors and alternating currents. Chapter 20 #45, 46, 47, 49
Circuits with inductors and alternating currents Chapter 20 #45, 46, 47, 49 RL circuits Ch. 20 (last section) Symbol for inductor looks like a spring. An inductor is a circuit element that has a large
More informationThree Phase Circuits. Three Phase Circuits
Three Phase Circuits 1 Three Phase Circuits Chater Objectives: Be familiar with different three-hase configurations and how to analyze them. Know the difference between balanced and unbalanced circuits
More informationPI734D - Technical Data Sheet
PI734D - Technical Data Sheet PI734D SPECIFICATIONS & OPTIONS STANDARDS Newage Stamford industrial generators meet the requirements of BS EN 60034 and the relevant sections of other national and international
More informationPI734B - Technical Data Sheet
PI734B - Technical Data Sheet PI734B SPECIFICATIONS & OPTIONS STANDARDS Newage Stamford industrial generators meet the requirements of BS EN 60034 and the relevant sections of other national and international
More informationExample: Determine the power supplied by each of the sources, independent and dependent, in this circuit:
Example: Determine the power supplied by each of the sources, independent and dependent, in this circuit: Solution: We ll begin by choosing the bottom node to be the reference node. Next we ll label the
More informationIntroduction to PowerWorld Simulator: Interface and Common Tools
Introduction to PowerWorld Simulator: Interface and Common Tools 2001 South First Street Champaign, Illinois 61820 +1 (217) 384.6330 support@powerworld.com http://www.powerworld.com Fault Analysis Analysis
More informationLoad Flow Analysis on IEEE 30 bus System
International Journal of Scientific and Research Publications, Volume 2, Issue 11, November 2012 1 Load Flow Analysis on IEEE 30 bus System Dharamjit *, D.K.Tanti ** * Department of Electrical Engineering,
More informationEarth Fault Detection Basics in Theory
Earth Fault Detection Basics in Theory Author: Dipl.-Ing. Ingo Kühnen Woodward Power Solutions Krefelder Weg 47 47906 Kempen, Germany Kempen, 16.04.2010 Earth_Fault_Detection_20100416.doc page 1 1. Star
More informationProduct Data Bulletin
Product Data Bulletin Power System Harmonics Causes and Effects of Variable Frequency Drives Relative to the IEEE 519-1992 Standard Raleigh, NC, U.S.A. INTRODUCTION This document describes power system
More informationEEL303: Power Engineering I - Tutorial 4
1. Determine the voltage at the generating station and the efficiency of the following system (Figure 1): Both transformers have ratio of 2kV/11kV. The resistance on LV side of both Figure 1: transformers
More informationPrepared By: Sheilani Binti Shaari Department of Electrical Engineering/PKB
Prepared By: Sheilani Binti Shaari Department of Electrical Engineering/ Course Learning Outcome (CLO) Upon completion of this course, students should be able to: Apply the principles of three phase systems,
More informationCircuits 1 M H Miller
Introduction to Graph Theory Introduction These notes are primarily a digression to provide general background remarks. The subject is an efficient procedure for the determination of voltages and currents
More information100% Stator Ground Fault Detection Implementation at Hibbard Renewable Energy Center. 598 N. Buth Rd 3215 Arrowhead Rd
100% Stator Ground Fault Detection Implementation at Hibbard Renewable Energy Center Introduction Roger Hedding Steven Schoenherr, P.E. ABB Inc. Minnesota Power 598 N. Buth Rd 3215 Arrowhead Rd Dousman,
More informationLine Reactors and AC Drives
Line Reactors and AC Drives Rockwell Automation Mequon Wisconsin Quite often, line and load reactors are installed on AC drives without a solid understanding of why or what the positive and negative consequences
More informationInduction Motor Theory
PDHonline Course E176 (3 PDH) Induction Motor Theory Instructor: Jerry R. Bednarczyk, P.E. 2012 PDH Online PDH Center 5272 Meadow Estates Drive Fairfax, VA 22030-6658 Phone & Fax: 703-988-0088 www.pdhonline.org
More informationThree-phase AC circuits
Three-phase AC circuits This worksheet and all related files are licensed under the Creative Commons Attribution License, version 1.0. To view a copy of this license, visit http://creativecommons.org/licenses/by/1.0/,
More information(3 )Three Phase Alternating Voltage and Current
EEE 2015 EECTRCS (3) Monophase 1 Three phase Three phase electric power is a common method of alternating current electric power generation, transmission, and distribution. t is a type of polyphase system
More informationVOLTAGE REGULATOR AND PARALLEL OPERATION
VOLTAGE REGULATOR AND PARALLEL OPERATION Generator sets are operated in parallel to improve fuel economy and reliability of the power supply. Economy is improved with multiple paralleled generators by
More informationKeywords: synchronous generator, synchronous motor, automatic voltage regulator, V- curves, synchronizing power, hunting, excitation system
SYNCHRONOUS MACHINES Tze-Fun Chan Hong Kong Polytechnic University, Hong Kong, China Keywords: synchronous generator, synchronous motor, automatic voltage regulator, V- curves, synchronizing power, hunting,
More informationIV. Three-Phase Induction Machines. Induction Machines
IV. Three-Phase Induction Machines Induction Machines 1 2 3 4 5 6 7 8 9 10 11 12 13 Example 1: A 480V, 60 Hz, 6-pole, three-phase, delta-connected induction motor has the following parameters: R 1 =0.461
More informationThe Importance of the X/R Ratio in Low-Voltage Short Circuit Studies
The Importance of the X/R Ratio in Low-Voltage Short Circuit Studies DATE: November 17, 1999 REVISION: AUTHOR: John Merrell Introduction In some short circuit studies, the X/R ratio is ignored when comparing
More informationKirchhoff's Current Law (KCL)
Kirchhoff's Current Law (KCL) I. Charge (current flow) conservation law (the Kirchhoff s Current law) Pipe Pipe Pipe 3 Total volume of water per second flowing through pipe = total volume of water per
More informationTRANSFORMER: THREE PHASE
CONTENTS Transformer : Three Phase 1211 C H A P T E R 33 Learning Objectives Three-phase Transformers Three-phase Transformer Connections Star/Star or Y/Y Connection Delta-Delta or Connection Wye/Delta
More informationThree-phase analysis of unbalanced systems
Exercises of course ELEC0029 - Electric power systems analysis and operation Three-phase analysis of unbalanced systems Thierry Van Cutsem t.vancutsem@ulg.ac.be www.montefiore.ulg.ac.be/~vct March 205
More informationCharged cable event. 1 Goal of the ongoing investigation. 2 Energy sources for the CDE. Content
Charged cable event David Pommerenke, david_pommerenke@hp.com, 916 785 4550 Last update: Feb.23, 2001 Content Goal Energy sources, which may lead to CDE. Complexity of the different discharge modes. Possible
More informationSYNCHRONOUS MACHINE TESTING WITH MOTOR CIRCUIT ANALYSIS INSTRUMENTATION
SYNCHRONOUS MACHINE TESTING WITH MOTOR CIRCUIT ANALYSIS INSTRUMENTATION Introduction Howard W. Penrose, Ph.D., CMRP Vice President, Engineering and Reliability Services Dreisilker Electric Motors, Inc.
More informationAC Generators. Basic Generator
AC Generators Basic Generator A basic generator consists of a magnetic field, an armature, slip rings, brushes and a resistive load. The magnetic field is usually an electromagnet. An armature is any number
More informationLecture - 4 Diode Rectifier Circuits
Basic Electronics (Module 1 Semiconductor Diodes) Dr. Chitralekha Mahanta Department of Electronics and Communication Engineering Indian Institute of Technology, Guwahati Lecture - 4 Diode Rectifier Circuits
More informationEquipment: Power Supply, DAI, Wound rotor induction motor (8231), Electrodynamometer (8960), timing belt.
Lab 13: Wound rotor induction motor. Objective: to examine the construction of a 3-phase wound rotor induction motor; to understand exciting current, synchronous speed and slip in this motor; to determine
More informationCOMPUTER AIDED ELECTRICAL DRAWING (CAED) 10EE65
COMPUTER AIDED ELECTRICAL DRAWING (CAED) EE Winding Diagrams: (i) DC Winding diagrams (ii) AC Winding Diagrams Terminologies used in winding diagrams: Conductor: An individual piece of wire placed in the
More informationBasic Electronics Prof. Dr. Chitralekha Mahanta Department of Electronics and Communication Engineering Indian Institute of Technology, Guwahati
Basic Electronics Prof. Dr. Chitralekha Mahanta Department of Electronics and Communication Engineering Indian Institute of Technology, Guwahati Module: 2 Bipolar Junction Transistors Lecture-2 Transistor
More informationAND8008/D. Solid State Control Solutions for Three Phase 1 HP Motor APPLICATION NOTE
Solid State Control Solutions for Three Phase 1 HP Motor APPLICATION NOTE INTRODUCTION In all kinds of manufacturing, it is very common to have equipment that has three phase motors for doing different
More information