Transformer Bushings IEEE/ANSI Standard, COTA 150 COTA 2050
|
|
- Elijah Alexander
- 7 years ago
- Views:
Transcription
1 Transformer Bushings IEEE/ANSI Standard, COTA 150 COTA 2050
2 Application Trench bushings, Type COTA, are designed for application on liquid filled power transformers and reactors. They are used to connect the power transformer or reactor to overhead lines or exposed bus in either outdoor or indoor conditions. Connection to the transformer winding leads can be accomplished by one of three methods: Bottom connected via a fixed conductor. Connected via a copper draw lead cable(s) supplied with the power transformer. Bottom connected via Trench s all copper Split-Conductor draw lead. (Up to 1300 kv BIL) The method selected depends on voltage rating, maximum through current or user preference. Connection to the power system is accomplished with an industry standard threaded top terminal. Applicable Standards Trench bushings Type COTA, are designed to meet or exceed the following industry standards for liquid filled power transformer or reactor applications: Design Active Part The active part of the COTA bushing is constructed of oil-impregnated paper with layers of aluminum foil. The position of the foil layers is computer optimized to ensure a homogenous electrical field, radially and axially controlled, providing extremely high dielectric resistance. The Trench active part design ensures that COTA bushings will last the life of your power transformer. Housing The housing is constructed of a head, outdoor insulator, mounting flange, ground sleeve (COTA 250 and above) and epoxy or fiberglass insulator, held together by either a central tube or a fixed conductor. Pre-tensioned cone spring washers provide mechanical stability over the entire temperature range, ensuring a leak free bushing with the highest possible mechanical strength. COTA bushings are sealed exclusively with 0-Ring gaskets and each bushing is hermetically sealed with its own independent oil reservoir. The interior of the aluminum castings are painted. Head The cast aluminum head contains an oil expansion chamber with an oil level indicator. The design of the head allows the bushings to be shipped and stored horizontally and mounted as follows: COTA 150 and above draw lead models and fixed conductor models above COTA 200: vertical to a maximum inclination of 40. For greater inclination, contact Trench for special instructions and limitations. ANSI/IEEE Standard C IEEE Standard General Requirements and Test Procedure for Outdoor Power Apparatus Bushings ANSI/IEEE Standard C IEEE Standard Performance Characteristics and Dimensions for Outdoor Apparatus Bushings IEEE Standard C R2002 IEEE Guide for Application of Power Apparatus Bushings COTA 150 and above draw lead models and fixed conductor models above COTA 200 COTA 150 and COTA 200 Fixed conductor models: vertical or horizontal 2 T R A N S F O R M E R B U S H I N G
3 Outdoor Insulator The outdoor insulator is either a high-grade electrotechnical porcelain or an insulator constructed from a explosion-resistant fiberglass epoxy resin tube with molded silicon-rubber sheds. Porcelain Insulators The standard porcelain insulator on COTA bushings is ANSI No.70, light gray. Brown porcelain is available upon request. One-piece porcelain is standard on COTA 150 though 750 and optional on COTA 900 and When the height of the bushing makes it necessary to use more than one porcelain element, Trench uses a special gluing procedure developed to ensure that the porcelain elements will exhibit the same level of performance as a single porcelain element. On bushing style COTA 250 and above, the porcelain insulator is cemented to the mounting flange using special cement and sealed with an 0-Ring gasket. To protect against corrosion, the mounting flange surface and porcelain that is in contact with the cement is treated with a special coating, ensuring a trouble free interface. Alternating sheds Porcelain insulator Portland cement Mounting flange O-Ring gasket Silicone Rubber Insulators Silicone rubber insulators used by Trench are specifically designed for use on high voltage bushings. These insulators demonstrate superior electrical and mechanical characteristics not found in other types of insulators. The physical properties of the silicone rubber provide many advantages over conventional porcelain insulators. The silicone rubber insulator has demonstrated superior performance in earthquake prone areas. Porcelain insulator Typical design COTA 250 COTA 900 Fiberglass - reinforced epoxy resin tube Silicone rubber sheds Portland cement Mounting flange O-Ring gasket Silicone rubber insulator Silicone Rubber insulator Typical design COTA 250 and above T R A N S F O R M E R B U S H I N G 3
4 Design Mounting Flange The mounting flange is a high quality aluminum casting, machined to exact dimensions, ensuring an excellent seal between the bushing and the transformer. Integrated into the mounting flange of COTA bushings through 69 kv are test taps. Above 69 kv the mounting flange is equipped with a voltage tap. Sealing cap Epoxy insulator Embedded End Shield (Draw Lead COTA 250 though 1175) Sealing cap Test Tap COTA 15O COTA 35O Oil plug High voltage bushings require an end shield to control the electrical field strength at the inboard end of the bushing. Instead of mounting this shield externally, Trench embeds the shield in the epoxy-resin inboard end insulator. This provides a more uniform distribution of the electrical forces and reduces the required clearances. The embedded end shield provides greater interchangeability with other bushings, making the Trench COTA bushings the ideal replacement bushing. Current Path Voltage Tap COTA 550 and above Shatter Resistant Inboard End Every Trench COTA bushing is offered with a shatter resistant in-board end insulator. These insulators are less susceptible to damage from handling. They will not shatter like porcelain preventing major transformer repair costs. Trench in-board end insulators have 25 years of proven field experience. The lower end of the COTA bushings (COTA 200 and below) are protected by an explosion resistant fiberglass-reinforced epoxy-resin tube or (COTA 250 and above) by a shatter resistant cone shaped vacuum molded epoxy resin insulator. Two current path options are available: Fixed conductor Current path via conductor that is fixed in place and has the active part wound on the conductor. The fixed conductor is either solid rod or a tube, depending on the specific bushing design. Draw lead Current path via the transformer s cable(s) to a silver-plated copper terminal through multi spring contacts to the copperalloy top terminal. Or via Trench s copper Split-Conductor draw lead through multi spring contacts to the copper-alloy top terminal. These insulators are designed to be installed during the intank drying process of the active part of the transformer and can withstand temperatures up to 130 C. 4 T R A N S F O R M E R B U S H I N G
5 Fixed Conductor When a fixed conductor bushing is selected the connection to the transformer winding leads will be at the bottom of the bushing. The terminal configuration at the bottom of fixed conductor bushing will depend on the current rating and/or the desired application and the requirements of the ANSI/IEEE Standards. Draw Lead Cable(s) When the application is less than 800 amperes, draw lead cable(s), provided with the transformer, can be used. For recommendations on selecting the draw lead cable(s) for COTA bushings refer to the Trench COTA Instruction Manual. When applying draw lead cable(s) on bushings with a vacuum molded epoxy resin insulator the embedded end shield provides for a simple, space-saving assembly without additional shielding or barriers. Refer to the Trench COTA Instruction Manual for additional details on this feature. Top Terminal Unlike other bushing designs, where the top terminal is threaded onto the bushing, the Trench COTA bushing utilizes a top terminal that is bolted to the head of the bushing. This feature eliminates the requirement to check the top terminal for tightness, increasing reliability and providing a truly maintenance free bushing. The top terminal is designed to accept either a draw lead terminal or the Trench s Split-Conductor. On fixed conductor COTA bushings the top terminal is an integral part of the bushing s conductor. Top terminal Lock pin Split-Conductor Super Draw Lead Historically bushings through 69 kv only offered a draw lead rating of 400 amps. Today, using the Trench Split-Conductor in COTA bushings you now have draw lead ratings to 3,000 amps. Now almost all, medium power transformers through 100 MVA can have all draw lead bushings. The Split- Conductor draw lead feature provides increased safety for personnel, shorter installation times and ensures factory tested transformer lead connections. For Split-Conductor applications the termination of the transformer or reactor winding leads will be at the bottom of the bushing. The type of termination required will depend on the maximum through current, operating voltage and mounting position. Additional measures (shielding, barriers, etc.) may be required. Contact Trench for available terminals and shields for your specific application of the Split- Conductor. Split conductor upper part Mounting flange 4 Hex-socket screws M10 with disk spring washers torque 17 ft.lb. (23 Nm) Split conductor lower part Epoxy insulator Bottom terminal Split-Conductor & Top terminal T R A N S F O R M E R B U S H I N G 5
6 Cut Views Top terminal Top terminal Draw lead stud Oil level indicator Head housing Oil level indicator Head housing Insulator Active part Insulator Active part Name plate Test tap Voltage Tap (COTA 550 and above) Air escape plug (COTA 1050 and above) Mounting flange Mounting flange FRP tube Grounding sleeve Test tap (COTA 350 and below) Conductor Epoxy insulator Bottom terminal Typical design COTA 150 & COTA 200 Fixed Conductor Typical design COTA 250 COTA 1175 Draw lead 6 T R A N S F O R M E R B U S H I N G
7 Quality Top terminal Oil level indicator Head housing Insulator Active part Voltage Tap (COTA 550 and above) Mounting flange Grounding sleeve Epoxy insulator Name plate Air escape plug (COTA 1050 and above) Test tap (COTA 350 and below) Everyone talks about quality; nearly everyone is ISO 9001 certified including Trench but that is not the whole picture. Quality starts at the beginning, it starts with the design. When you compare a Trench COTA bushing with other brands you will find quality design features not offered by the others. These include O-ring gaskets instead of flat gaskets, the interior of all castings painted, easy to read prismatic oil level indicators and stainless steel test tap caps just to mention a few. Quality is the reason Trench offers the only standard three-year bushing warranty in the business. 85 years in the bushing business and still growing, Trench, the quality choice for bushings. Standardization Trench COTA bushings were developed to promote the concept of standardization. The designs detailed in this catalog will cover nearly 100% of the bushing requirements for liquid filled power transformers or reactors rated through 2500 MVA, three-phase, 2050 kv BIL. (Excluding high current bushings for GSU transformers) All COTA bushings though 900 kv BIL are designed for operation, without de-rating, to an altitude of 10,000 feet. COTA bushings above 900 kv BIL are offered with altitude ratings based on the BIL rating of the specific bushing. Example; a COTA 1050 may be rated for 10,000 feet while the same bushing rated at 1300 kv BIL will only be rated for operation at 3,300 feet. COTA bushings (COTA 200 and above) have as standard, extra-creep porcelain in accordance with the heavy contamination level as described in the IEEE Guide for Application of Power Apparatus Bushings, C R2002. Bottom Terminal COTA bushings present a level of standardization that will reduce inventories while meeting the most demanding requirements. Typical design COTA 550 and above Fixed conductor T R A N S F O R M E R B U S H I N G 7
8 COTA Technical Specification Sheets C Style Number 150-H AG F AG H DG4-01 Drawing Number 025D001A 025F002A 025S011A Current Path (copper) draw lead fixed draw lead Insulation Class (kv) Max. L to G Voltage (kv) Max. Current Rating (A) 1,500 2,700 3,000 CT Pocket Length (inches) BIL (kv) s dry (kv) s wet (kv) Min. Creep Distance (inch) Min. Arcing Distance. (Inch) Approximate Weight (lb.) Mounting vertical vertical/horizontal Vertical Style Number Drawing Number 200-H AG D001A 200-F AG F002A 200-H DG S013A Current Path (copper) draw lead fixed draw lead Insulation Class (kv) Max. L to G Voltage (kv) Max. Current Rating (A) 1,500 2,350 3,000 CT Pocket Length (inches) BIL (kv) s dry (kv) s wet (kv) Min. Creep Distance (inch) Min. Arcing Distance. (Inch) Approximate Weight (lb.) Mounting vertical vertical/horizontal vertical Style Number 250-H AG H AG F AG3-01 Drawing Number 046D001A 046S004A 046F003A Current Path (copper) draw lead draw lead fixed Insulation Class (kv) Max. L to G Voltage (kv) Max. Current Rating (A) 1,400 2,000 3,000 CT Pocket Length (inch) BIL (kv) s dry (kv) s wet (kv) Min. Creep Distance (inch) Min. Arcing Distance (inch) Approximate Weight (lb.) T R A N S F O R M E R B U S H I N G
9 COTA Technical Specification Sheets Style Number Drawing Number 350-H AG D002A 350-H AG S008A 350-F AG F002A Current Path (copper) draw lead draw lead fixed Insulation Class (kv) Max. L to G Voltage (kv) Max. Current Rating (A) 1,400 2,000 3,000 CT Pocket Length (inch) BIL (kv) s dry (kv) s wet (kv) Min. Creep Distance (inch) Min. Arcing Distance (inch) Approximate Weight (lb.) Style Number 550-H AG F AG F AG3-01 Drawing Number 115D002A 115F001A 115F002A Current Path (copper) draw lead fixed fixed Insulation Class (kv) Max. L to G Voltage (kv) Max. Current Rating (A) 1,400 2,000 3,000 CT Pocket Length (inches) BIL (kv) s dry (kv) s wet (kv) Min. Creep Distance (inch) Min. Arcing Distance. (Inch) Approximate Weight (lb.) Style Number Drawing Number 650-H AG D002A 650-F AG F002A 650-F AG F001A Current Path (copper) draw lead fixed fixed Insulation Class (kv) Max. L to G Voltage (kv) Max. Current Rating (A) 1,400 2,000 3,000 CT Pocket Length (inches) BIL (kv) s dry (kv) s wet (kv) Min. Creep Distance (inch) Min. Arcing Distance. (Inch) Approximate Weight (lb.) T R A N S F O R M E R B U S H I N G 9
10 COTA Technical Specification Sheets C Style Number 750-H AG F AG F AG3-01 Drawing Number 161D001A 161F001A 161F002A Current Path (copper) draw lead fixed fixed Insulation Class (kv) Max. L to G Voltage (kv) Max. Current Rating (A) 1,400 2,000 3,000 CT Pocket Length (inches) BIL (kv) s dry (kv) s wet (kv) Min. Creep Distance (inch) Min. Arcing Distance. (Inch) Approximate Weight (lb.) Style Number Drawing Number 900-H AG D003A 900-F AG F003A 900-F AG F005A Current Path (copper) draw lead fixed fixed Insulation Class (kv) Max. L to G Voltage (kv) Max. Current Rating (A) 1,600 2,000 3,000 CT Pocket Length (inch) BIL (kv) s dry (kv) s wet (kv) Min. Creep Distance (inch) Min. Arcing Distance (inch) Approximate Weight (lb.) Style Number Drawing Number 1175-H AG D002A 1175-F AG F001A 1175-F AG F004A Current Path (copper) draw lead fixed Fixed Insulation Class (kv) Max. L to G Voltage (kv) Max. Current Rating (A) 1,600 2,000 3,000 CT Pocket Length (inch) BIL (kv) 1,175 1,175 1, s,dry (kv) Wet switching impulse (kv) Min. Creep Distance (inch) Min. Arcing Distance (inch) Max. Altitude (feet) 3,300 3,300 3,300 Approximate Weight (lb.) T R A N S F O R M E R B U S H I N G
11 COTA Technical Specification Sheets Style Number 1675-F AG F AG F AG3-01 Drawing Number 500F001A 500F005A 765F001A Current Path (copper) fixed fixed fixed Insulation Class (kv) Max. L to G Voltage (kv) Max. Current Rating (A) 2,000 3,000 2,000 CT Pocket Length (inch) BIL (kv) 1,675 1,675 2, s,dry (kv) Wet switching impulse (kv) 1,175 1,175 1,450 Min. Creep Distance (inch) Min. Arcing Distance (inch) Max. Altitude (feet) 5,000 5,000 3,300 Approximate Weight (lb.) 2,119 2,120 3,040 T R A N S F O R M E R B U S H I N G 11
12 Trench Austria GmbH Paschinger Strasse 49 Postfach 13 A-4060 Linz-Leonding Austria Phone: Fax: Trench Brasil Ltda Via Expressa de Contagem, 2685 Contagem, Minas Gerais CEP Brazil Phone: Fax: Trench China MWB (Shanghai) Co., Ltd No Jiangcheng Road Minhang, Shanghai, Peoples Republic of China Phone: Fax: Trench Fushun Dong Er Dao, Shuncheng District, Fushun, Liaoning Province, Peoples Republic of China Phone: / Fax: Trench Limited Bushing Division 432 Monarch Avenue Ajax, Ontario Canada L1S 2G7 Phone: Fax: Trench Limited Instrument Transformer Division 390 Midwest Road Scarborough, Ontario Canada M1P 3B5 Phone: Fax: Trench France S.A. 16, Rue du Général Cassagnou B. P. 70 F St. Louis, Cedex France Phone: Fax: Trench Germany GmbH Nürnberger Strasse 199 D Bamberg Germany Phone: Fax: Trench Switzerland AG Lehenmattstrasse 353 CH-4028 Basel Switzerland Phone: Fax: Trench (UK) Limited South Drive Hebburn Tyne & Wear NE 31 1 UW Phone: Fax: Trench Limited Coil Product Division 71 Maybrook Drive Scarborough, Ontario Canada M1V 4B6 Phone: Fax: Subject to change without notice E Printed in Canada
25-kV Apparatus Bushings B Series (bolt-in) for Elbow to Air-Insulated Service 200 Amp, 600 Amp and 1250 Amp
Page 1 2015 Grounded Metal Equipment Plate Equipment Connection Bus Bar or Other Component 15 kv or 25 kv Separable Insulated Connector (elbow) Equipment Connection Power Cable Power Cable Grounded Metal
More information1ZSC000563-AAC en, Rev. 7. Resin impregnated paper bushing, oil to air, type GSB Technical guide
1ZSC000563-AAC en, Rev. 7 Resin impregnated paper bushing, oil to air, type GSB Technical guide Original instruction The information provided in this document is intended to be general and does not cover
More informationMiCAFIL. 1 RIP Technology. Bushings. Z. Zic 09/2003
MiCAFIL 1 RIP Technology Z. Zic 09/2003 )XQFWLRQRI+LJK9ROWDJH%XVKLQJ Uncontrolled (natural) electrical field Capacity-controlled electrical field %XVKLQJV0DLQ,QVXODWLRQ6\VWHPV 7\SH 0DLQ,QVXODWLRQ +RXVLQJFRYHU
More informationPPS-PPQ-BT-PIAS RESIN INSULATORS FOR OIL INSULATED ELECTRICAL MACHINES
PPS-PPQ-BT-PIAS RESIN INSULATORS FOR OIL INSULATED ELECTRICAL MACHINES BUSHING WITH PLUG CONNECTION WITH OUTER CONE PPS CHARACTERISTICS The PPS bushing can be used as a fixed section for the entry of medium
More informationTransmission Silicone Insulators Line Post 69 kv to 161 kv
K-LINE INSULATORS LIMITED Catalogue T-LP Transmission Silicone Insulators Line Post 69 kv to 161 kv ISO9001 SAI GLOBAL FILE No. 000117 Transmission Silicone Insulators Line Post Today transmission lines
More informationTransformer Bushings for GIS
Transformer Bushings for GIS Oil to SF6 Connections GARIP RTKG 725-55 kv SQS certified ISO 91 / ISO 141 Bushings RIP - Technology for SF6 / Oil - Bushings In modern metal enclosed switchgear SF6 -gas is
More information1ZSE 2750-105 en, Rev. 8. Transformer bushings, type GOE and GOE(2) Technical guide
1ZSE 2750-105 en, Rev. 8 Transformer bushings, type GOE and GOE(2) Technical guide Original instruction The information provided in this document is intended to be general and does not cover all possible
More informationVertical Break Parallel (VBP) / Vertical Break Slant (VBS)
August, 2009 Vertical Break Parallel (VBP) / Vertical Break Slant (VBS) Type VBPA (Aluminum) / Type VBPC (Copper) Type VBSA (Aluminum) / Type VBSC (Copper) PASCOR Air Break Switch Technology PASCOR offers
More informationAn Overview of Lapp Insulator High Voltage Bushing Design
An Overview of Lapp Insulator High Voltage Bushing Design W.A. Young Lapp Insulator Company LeRoy, NY 14482 USA INTRODUCTION High voltage bushings are devices designed to transmit electric energy through
More informationPump Specifications 405 Series Commercial Drain Pump (High-Temp) 2 Solids handling
Pump Specifications 405 Series Commercial Drain Pump (High-Temp) 2 Solids handling 405_P1 R1/27/2012 Copyright 2012 Liberty Pumps Inc. All rights reserved. Specifications subject to change without notice.
More informationPump Specifications 250 Series Submersible Sump / Effluent Pump 2 Solids handling
Pump Specifications 250 Series Submersible Sump / Effluent Pump 2 Solids handling 250_P1 R10/7/2015 Copyright 2015 Liberty Pumps Inc. All rights reserved. Specifications subject to change without notice.
More informationToroidal Conductivity Sensor
Instruction Sheet PN 51A-/rev.C June 2012 Toroidal Conductivity Sensor For additional information, please visit our website at www.emersonprocess.com/rosemountanalytical.com SPECIFICATIONS Wetted Materials:
More informationJames M. Pleasants Company
James M. Pleasants Company SUBMITTAL DATA GAINESVILLE MECHANICAL DECEMBER 20, 2013 PROJECT: GSU: J-183 HUMANITIES LAW BLDG. QUOTE NO:12116 ENGINEER: STEVENS & WILKINSON GASKETED PLATE HEAT EXCHANGER Tag:
More informationCAUTION. 4. Cable Connections DANGER WARNING CAUTION. 3. Bushing Components
Instruction Manual for POC Bushings 1. Scope This instruction contains general procedures to be followed during receiving, installation, storage and maintenance of all PCORE POC bushings. This instruction
More informationproduces and delivers products worldwide can provide the optimal are dedicated to supplying you with superior advice and global support.
www.ppcinsulators.com The very Best. The very Best. That s what we deliver. ong od Insulators Only a company that develops, produces and delivers products worldwide can provide the optimal solution for
More information2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV 16346-1. 2a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std.
2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV 16346-1 2a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std. Relays) Part 1 General 1.1 CONDITIONS AND REQUIREMENTS: A. Refer to
More informationAutoLink Three-Phase Sectionalizer Specifications. Scope. General. Applicable Standards. Operating principle
Scope This specification stipulates the minimum requirements for mechanically linked three-phase electronic sectionalizers, for use on outdoor medium voltage overhead lines of 15, 27, and 38 kv. Electronic
More informationMEDIUM AND HIGH VOLTAGE CAPACITORS, CAPACITOR BANKS AND SYSTEMS
MEDIUM AND HIGH VOLTAGE CAPACITORS, CAPACITOR BANKS AND SYSTEMS Meher Capacitors offers reliable and innovative products and solutions in the fields of Reactive Power Compensation, Power Quality and Energy
More informationV47 Series Temperature Actuated Modulating Water Valves
V47 Series Temperature Actuated Modulating Water Valves Master Catalog 125 Valves, Miscellaneous (Other Than Gas) Section V Product Bulletin V47 Issue Date 0286 Application The V47 modulating valves regulate
More informationMetal Clad Indoor Instrument Transformer for Plug-In Systems
Metal Clad Indoor Instrument Transformer for Plug-In Systems RITZ Instrument Transformers GmbH Core competency Under the trading name RITZ Instrument Transformers GmbH RITZ has been pooling its activities
More informationPower Voltage Transformers for Air Insulated Substations. THE PROVEN POWER.
Power Voltage Transformers for Air Insulated Substations THE PROVEN POWER. Introduction Trench Power Voltage Transformers (Power VTs) combine the attributes of an inductive voltage transformer with the
More informationSECTION 16461 DRY-TYPE TRANSFORMERS
SECTION 16461 PART 1 - GENERAL 1.1 SECTION INCLUDES A. Furnishing and installation of and testing of cast resin dry type MV/LV distribution transformer in accordance with specifications and drawings. Any
More informationSF 6 Gas Insulated Switchgear Type SDF for 170 kv
Three Phase Encapsulated Type SF 6 Gas Insulated Switchgear Type SDF for 170 kv 06B1-E-0001 With Trustworthy Technology, Structure Fuji Electric as a manufacturer of comprehensive substation equipment
More informationSecondary Unit Substations
14 SWITCHGEAR Secondary Unit Substations Overview Siemens offers a wide variety of unit substation designs to meet customer requirements. A unit substation consists of one or more transformers mechanically
More informationPump Specifications 2448LSG, 2448LSGX Series Omnivore 2HP Simplex Grinder Packages
Pump Specifications 2448LSG, 2448LSGX Series Omnivore 2HP Simplex Grinder Packages 2448LSG_P1 R4/2/2012 Copyright 2012 Liberty Pumps Inc. All rights reserved. Specifications subject to change without notice.
More informationOLI. Oil level indicator
OLI Oil level indicator Oil level indicator Unexpected or accidental oil leakages may occur randomly along transformer s lifetime. Clear indication of oil level inside transformer tank and on load tap
More informationType K current limiting fuse canister Technical information and installation guide
Transformer components Type K current limiting fuse canister Technical information and installation guide The Type K current limiting fuse canister provides an air-insulated receptacle for general-purpose
More informationELECTRIC METERING COMMERCIAL & INDUSTRIAL
ELECTRIC METERING COMMERCIAL & 1.0 INDEX 1.0 INDEX 2.0 SCOPE 3.0 GENERAL REQUIREMENTS 4.0 METER LOCATIONS 5.0 UNDERGROUND TERMINATIONS 6.0 METERING TRANSFORMER ENCLOSURES 7.0 SINGLE CUSTOMER METER INSTALLATIONS
More informationSERIES ASM NEOPRENE/EPMD FLANGED SINGLE SPHERE CONNECTOR CONNECTORS. Pressures to 225 PSIG (15.51 barg) Temperatures to 230ºF (110ºC)
APPLICATIONS Process Industry Weak Acids Alkalies Compressed Air Pulp & Paper MODELS ASM - Flanged Connection OPTIONS Control Rods Oil & Gas Water & Waste Pump suction & discharge Sea water Chemical lines
More informationTechnical Specification for Oil insulated Transformers U m < 24 kv up to 1250 kva
to 1250 kva Page 1/10 Technical Specification for Oil insulated Transformers U m < 24 kv up to 1250 kva This technical specification is valid for the business unit E.ON Sweden of the market unit E.ON Nordic.
More informationCable Accessories. for Extruded Dielectric Cable 69kV - 230kV Rated. Catalog Python13
Cable Accessories for Extruded Dielectric Cable 69kV - 230kV Rated Components used in cable systems 100% Tested Factory Molded For outdoor applications through 230kV For gas insulated substations and transformers
More informationComposite Insulators Suspensions Line Posts Brace Posts Station Posts
Composite Insulators Suspensions Line Posts Brace Posts Station Posts Quality, reliability and consistency for over four decades As an alternative and complement to our range of proven ceramic insulators,
More informationExplosion proof enclosures
1 of 7 Explosion proof enclosures DE8 C 2 of 7 The Ex d enclosures are rugged and designed for harsh environment like: Oil and gas industry Chemical industry Pharmaceutical industry Agribusiness Without
More informationLow Voltage Transformers Sealed, General Purpose, Dry Type
Low Voltage Transformers Sealed, General Purpose, Dry Type Catalog 7400CT9601R4/08 08 Class 7400 CONTENTS Description..............................................Page Introduction.................................................
More informationHYDRAULIC TABLE CART 500-LB.
HYDRAULIC TABLE CART 500-LB. OWNER S MANUAL WARNING: Read carefully and understand all MACHINE ADJUSTMENT AND OPERATION INSTRUCTIONS before operating. Failure to follow the safety rules and other basic
More informationBUTTERFLY VALVES. An industry leader in underground and in-plant applications. STYLE 4500 3 24 STYLE 1450 30 54. Consult factory for sizes 60 120
An industry leader in underground and in-plant applications. BUTTERFLY VALVES STYLE 4500 3 24 STYLE 1450 30 54 Consult factory for sizes 60 120 C504 Class 150B & 250B M&H Valve is a division of McWane,
More informationBUTTERFLY VALVES. An industry leader in underground and in-plant applications. STYLE 4500 3 24 STYLE 1450 30 54. Consult factory for sizes 60 120
An industry leader in underground and in-plant applications. BUTTERFLY VALVES STYLE 4500 3 24 STYLE 1450 30 54 Consult factory for sizes 60 120 C504 Class 150B & 250B M&H Valve is a division of McWane,
More informationC O N V E Y O R C O M P O N E N T S C H A I N S B E L T S B E A R I N G S
C O N V E Y O R C O M P O N E N T S C H A I N S B E L T S B E A R I N G S January 2009 Issue 6 Valu Guide Brackets The Ultimate in Adjustability and Cost Savings Valu Guide brackets are part of a family
More informationCABLE ACCESSORIES 110-220 kv
CABLE ACCESSORIES 110-220 kv Termination 110 kv Technical description Termination MKB 126 / 145 with composite type insulator uses for cable line joints with other elements of power-supply systems. Termination
More informationKuhlman Electric Corporation. 25000 Volt Instrument Transformers
Kuhlman Electric Corporation 25000 Volt Instrument Transformers 25000 Volt Table of Contents Description Model Page Wound, Dry-Type VT Y Burden (High Accuracy available) PTT-150-9710(H) 3-4 Wound, Oil-Filled
More informationInstallation and Operating Instructions Installation Instructions for SS EPE-316L Series
INSTR3010 0406 Installation and Operating Instructions Installation Instructions for SS EPE-316L Series Congratulations on your purchase of this Aqua-Pure high flow, single housing filtration system. This
More informationOutdoor Use Waterproof I/O Connectors (Optical / Modular / Electrical) FO-BH, FO-BC, NT5, JN2 / W Series
COMPONENTS PRODUCT INFORMATION RoHS Compliant NEW Outdoor Use Waterproof I/O Connectors (Optical / Modular / Electrical) FO-BH, FO-BC, NT5, JN2 / W Series Optical FO-BH Series (Compact Type) CONNECTOR
More informationFAG Hydraulic nuts. Technical Product Information
FAG Hydraulic nuts Technical Product Information Contents Application 2 Design 2 Design variants 3 Pressure generators, connectors 4 Dimension tables for FAG hydraulic nuts (metric) 6 Dimension tables
More informationWATER & SEWER CORROSIVE RESISTANT PRODUCTS
WATER & SEWER CORROSIVE RESISTANT PRODUCTS The Standard of Excellence in the Industry CASING SPACERS COUPLINGS & FLANGE COUPLING ADAPTERS REPAIR CLAMPS DUCTILE IRON SADDLES STAINLESS STEEL SADDLES TAPPING
More informationBaumann 87000 Flexsleev Sanitary Control Valve
Product Bulletin D103345X012 Baumann 87000 Flexsleev Sanitary Control Valve The Baumann 87000 control valve (figures 1 and 2) is excellent for throttling high purity liquid or gaseous media commonly found
More informationCAST IRON THE BASICS. Heatline - Cast Iron Radiators SMOOTH FLAT FILE TO REMOVE ANY SWARF. ONE TIME. ASSEMBLY. JOINTS SHOULD BE TIGHTENED.
CAST IRON THE BASICS 1. DO NOT LIFT ON YOUR OWN. 2. ONLY LIFT THE RADIATOR VERTICALLY. 3. DO NOT LIFT MORE THAN 8/10 SECTIONS AT ANY ONE TIME. 4. POSITION THE RADIATOR BEFORE FINAL ASSEMBLY. 5. THIS PRODUCT
More information4. Combi valves. 7. Fire hydrants. 8. Check valves. 9. Air valves
1. General company and product information 2. Flanged gate valves for water 3. Other gate valves for water 4. Combi valves 5. Service connection valves for water 6. Valves and fittings for gas 7. Fire
More informationMETAL-CLAD AND METAL-ENCLOSED SWITCHGEAR 3.6KV~40.5KV. tgood.com. Energy. Fast.
METAL-CLAD AND METAL-ENCLOSED SWITCHGEAR 3.6KV~40.5KV tgood.com Energy. Fast. TGOOD produces over 5000 switchgear units annually for projects around the globe PRODUCT OVERVIEW Integral substation component
More informationCRN32-2-2 A-F-G-E-HQQE 3x400D 50 HZ
GRUNDFOS DATA BOOKLET CRN32-2-2 A-F-G-E-HQQE 3x4D 5 HZ Grundfos Pump 96122352 Thank you for your interest in our products Please contact us for more information, or visit our website http://www.lenntech.com/grundfos/crn32/96122352/crn-32-2-2-a-f-g-e-hqqe.html
More informationMueller. Pipe Repair Products. Saddles Tapping Sleeves Pipe Repair Clamps A complete selection for all types of pipe... all from a single source.
Mueller Pipe Repair Products Saddles Tapping Sleeves Pipe Repair Clamps A complete selection for all types of pipe... all from a single source. SERVICE SADDLES Mueller service saddles, available in bronze,
More informationSOHOline and SOHO Slimline The SOHOline and SOHO Slimline offer a modular, sturdy and compact design
SOHOline and SOHO Slimline The SOHOline and SOHO Slimline offer a modular, sturdy and compact design Ideal installation for; Offices Branch Offices Schools Computer Aided Classes Government Offices Hotels
More informationPneumatic actuators The Original! Technics of the top class.
Automatic valves Actuators Accessories Pneumatic actuators The Original! Technics of the top class. Leaflet no. S1-01e-13 Table of contents Advantages and your benefits...page 3 Figure: actuator...page
More informationSubmit shop drawings for equipment provided under this section Shop drawings shall indicate:
Section 16435 - SWITCHBOARDS Introduction Part 1 - General Reference The work under this section is subject to requirements of the Contract Documents including the General Conditions, Supplementary Conditions,
More informationAM/FM ANTENNA RELOCATION KIT
-J0 REV. 008-09-0 AM/FM ANTENNA RELOCATION KIT GENERAL Kit Number 766-09 Models This kit is used to relocate a fender-mounted AM/FM antenna to a Detachable Tour-Pak on specific model motorcycles. For model
More informationSolenoid valves 2/2-way direct-operated Type EV210A
Solenoid valves 2/2-way direct-operated Type EV210A Features EV210A NC and NO Very compact valves for industrial application, such as control and dosage For water, oil, compressed air and similar neutral
More informationMasterclad Medium Voltage Passive Arc-Resistant Switchgear
Masterclad Medium Voltage Passive Arc-Resistant Switchgear Square D Masterclad medium voltage passive arc-resistant (AR) switchgear is designed with utilities and industrial customers in mind who demand
More informationPackaged Terminal Air Conditioner Wall Sleeve Installation
Installation & Maintenance Data IM 1196 Group: PTAC Part Number: 910141799 Date: October 2013 Packaged Terminal Air Conditioner Installation x 42" PGAN with Top-Mounted Hydronic Heat Note: Installation
More informationMustang Series PRESSURE REDUCING CONTROL VALVE WITH PRESSURE SUSTAINING FEATURE. M115-2 (Globe) M1115-2 (Angle) Schematic. Standard Components
Schematic Throttles to reduce high upstream pressure to constant lower downstream pressure Throttles to maintain minimum upstream pressure PRESSURE REDUCING CONTROL VALVE WITH PRESSURE SUSTAINING FEATURE
More informationFire Hydrant Troubleshooting
Fire Hydrant Troubleshooting Pulsation or chatter during opening and flow of water from hydrant. Loose condition in stem at lower valve plate nut. Tighten lower valve plate nut and secure with SS lock
More informationHYDRAULIC LIFT TABLE CART 2200-LB.
HYDRAULIC LIFT TABLE CART 2200-LB. OWNER S MANUAL WARNING: Read carefully and understand all MACHINE ADJUSTMENT AND OPERATION INSTRUCTIONS before operating. Failure to follow the safety rules and other
More informationWINDING RESISTANCE TESTING
WINDING RESISTANCE TESTING WINDING RESISTANCE TEST SET, MODEL WRT-100 ADWEL INTERNATIONAL LTD. 60 Ironside Crescent, Unit 9 Scarborough, Ontario, Canada M1X 1G4 Telephone: (416) 321-1988 Fax: (416) 321-1991
More informationIMPORTANT DOCUMENTATION DO NOT DISCARD!
PART NO.: 6441-263C SERIES GRT 3 JAW PARALLEL GRIPPERS INFORMATION SHEET IMPORTANT DOCUMENTATION DO NOT DISCARD! Use this information sheet to assist with gripper installation and setup. File with maintenance
More informationMany Products...One Source
PRESSURE GAUGES Dedicated Sales Rep for Your Area 97%Fill Rate Shipping within 24 Hours State of the Art Warehouse System Technical Support Quality Control Program 25 Whaley Avenue Milverton, Ontario N0K
More informationPRESSURE REDUCING CONTROL VALVE
Schematics Throttles to reduce high upstream pressure to constant lower downstream pressure Low Flow By-Pass controls at low flows 4 PRESSURE REDUCING CONTROL VALVE with LOW FLOW BY-PASS FEATURE Main Line
More informationNo Heat. No Flames. No Shoving. No Special Tools. 3M Cold Shrink. 3M Cold Shrink. Medium Voltage Joints & Terminations. 3M Cold Shrink Joint
M Cold Shrink Medium Voltage Joints & Terminations M Cold Shrink Joint Splice bodies 00% factory tested - ensures reliability Capacitive Stress Relief No Heat No Flames No Special Tools No Shoving Unique
More informationThis section applies to the design and installation of transformers.
ELECTRICAL: TRANSFORMERS BASIS OF DESIGN This section applies to the design and installation of transformers. Design Criteria 13.8-kV equipment shall be 15-kV class. Coordinate with short-circuit studies
More information-1- SPECIFICATIONS 002085 CONE SETTER PLATFORM ATTACHMENT INDEX
-1-002085 CONE SETTER PLATFORM ATTACHMENT INDEX I. GENERAL EQUIPMENT : A. Intent Statement B. Cone Setter Platform II. III. 1. Understructure Frame 2. Mounting Components 3. Paint 4. Basket 5. Labels 6.
More informationHVL 5 38 kv Load Interrupter Switchgear. The Standard for Performance, Protection and Dependability
HVL 5 38 kv Load Interrupter Switchgear The Standard for Performance, Protection and Dependability For a generation of engineers, Square D High Voltage Load (HVL ) Interrupter Switchgear by Schneider Electric
More informationDYNA RIDER FOOTBOARD KIT
-J0 REV. 0-0-0 DYNA RIDER FOOTBOARD KIT GENERAL Kit Number 000 Models For model fitment information, see the P&A Retail Catalog or the Parts and Accessories section of www.harley-davidson.com (English
More informationCRN5-5 A-FGJ-G-E-HQQE 3x230/400 50HZ
GRUNDFOS DATA BOOKLET CRN5-5 A-FGJ-G-E-HQQE 3x23/4 5HZ Grundfos Pump 96517184 Thank you for your interest in our products Please contact us for more information, or visit our website http://www.lenntech.com/grundfos/crn5/96517184/crn-5-5-a-fgj-g-e-hqqe.html
More informationInstallation. Smart-UPS VT MGE Galaxy 3500. Maintenance Bypass Panel. 10-40 kva 400 V
Installation Smart-UPS VT MGE Galaxy 3500 Maintenance Bypass Panel 10-40 kva 400 V Contents Safety.................................................. 1 Save these instructions...................................
More informationTMC CableReady Connectors For Jacketed Metal Clad Cable TMC For Non-Hazardous Locations
TMC CableReady Connectors For Jacketed Metal Clad Cable TMC For Non-Hazardous Locations CableReady connectors are designed for use with the following cables: Type MC jacketed corrugated aluminum, interlocked
More informationAdaption of Cable Accessories for Onshore and Offshore Substation
Adaption of Cable Accessories for Onshore and Offshore Substation www.pfisterer.com the power connection Impressum Editor PFISTERER Holding AG Rosenstraße 44 73650 Winterbach Phone +49 7181 7005-0 Fax
More informationElectrical for Detached Garages: Updated Feb 19, 2016 for 2015 CE Code in force Jan. 1, 2016. Underground branch circuit feeding a detached garage:
Electrical for Detached Garages: Updated Feb 19, 2016 for 2015 CE Code in force Jan. 1, 2016 * Garage construction requires permits (electrical, building) * Permits must be applied for at the time. * Dial
More information18 AWG thru 8 AWG Not greater than 100/30 100/30. 6 AWG thru 1/0 AWG Not greater than 200/60 100/30
Commercial Products COMMERCIAL PRODUCTS: RIGID AND IMC FITTINGS s Used to support cables in vertical raceways or risers. Relieves the strain that would be placed on terminations, the interior of panels,
More informationPrimary and Secondary Electrical Distribution Systems
Primary and Secondary Electrical Distribution Systems Critical Facilities Round Table 12th Quarterly Membership Meeting June 2, 2006 David D. Roybal. P.E. Eaton Electrical Cutler-Hammer Products Utility
More informationVacuum drying oven for non-flammable solvents
VD series 53 Vacuum drying ovens Vacuum drying oven for non-flammable solvents A BINDER vacuum drying oven of the VD series is impressive while gently drying with its homogeneous temperature distribution.
More informationMueller B-101 and A-3 Drilling and Tapping Machines
TM TM Mueller and Drilling and Tapping Machines A guide to selecting Mueller Equipment Mueller TM TM and Drilling and Tapping Machines When it comes to line stopping and drilling and tapping technology
More informationAM/FM ANTENNA KIT (TOUR-PAK MOUNT)
-J077 REV. 008-0-0 AM/FM ANTENNA KIT (TOUR-PAK MOUNT) GENERAL Kit Number 7-98A Models For model fitment information, see the P&A Retail Catalog or the Parts and Accessories section of www.harley-davidson.com
More informationTakfan Machinery and Mould Co Ltd. Plug in Bushing. LV Monoblock. RMU Bushing. 4 Way CT Terminal. www.takfanmakina.com.tr
www.takfanmakina.com.tr Plug in Bushing LV Monoblock RMU Bushing 4 Way CT Terminal Solution Partner of Medium Voltage Insulation and Epoxy Casting Design *Medium voltage Switching Equipments Design *Load
More information60.12. Depend-O-Lok FxE Expansion Coupling. System No. Submitted By Spec Sect Para Location Date Approved Date. DEPEND-O-LOK FxE EXPANSION COUPLING
60.1 D-O-L FxE expansion couplings are a bolted, split-sleeve design that provides for expansion and contraction at the coupled joint. These couplings are furnished with restraint rings that, when affixed
More informationVolkswagen New Beetle 2.0 Liter 4-cyl General, Engine (Engine Code AEG) 17 Engine-Lubrication system (Page GR-17)
17 Engine-Lubrication system (Page GR-17) Lubrication system components, removing and installing Oil pan, removing and installing Oil pressure and oil pressure switch, checking Dynamic oil pressure warning
More informationSMA Connectors. RF Coax Connectors. Product Facts
SMA Connectors Product Facts Performance to 12.4 GHz and beyond Available in various base metal options, including stainless steel, brass and zinc diecast Uses industry standard crimp tools and processes
More informationAPI Flanged Safety Relief Valves Series 526 CATALOG
API Flanged Safety Relief Valves Series 26 CATALOG The-Safety-Valve.com 1 Valve finder How to find the right product group High operating to set pressure ratio, high backpressure or low total height? Yes
More informationData Sheet PS1B Pressure Switch
Data Sheet PS1B Pressure Switch Main Features Pressure Ranges 0 to 6 up to 0 to 600 bar (gage) Electrical Connection G 1/4 A DIN 3852-E or -A Pressure Connection Output Signal M12-4 Pin 4-20 ma, Programmable
More informationDead Tank Circuit Breaker 72PM40-C Proven reliability through common platforms
Dead Tank Circuit Breaker 72PM40-C Proven reliability through common platforms ABB innovations for changing demands ABB (www.abb.com) is a leader in power and automation technologies that enables utility
More informationTABLE OF CONTENTS" SECTION 3: Comparing Standing Seam Metal to Other Metal Roofs PAGE 7"
2 TABLE OF CONTENTS SECTION 1: What is a Standing Seam Metal Roof PAGE 3 SECTION 2: Common Types of Standing Seam Metal Roofs..PAGE 5 SECTION 3: Comparing Standing Seam Metal to Other Metal Roofs PAGE
More informationINSTRUCTIONS AND PARTS LIST FOR MODEL 70H & 75H HAND-OPERATED HYDRAULIC PRESS
INSTRUCTIONS AND PARTS LIST FOR MODEL 70H & 75H HAND-OPERATED HYDRAULIC PRESS SETTING UP THE PRESS FOR OPERATION For shipping convenience, the gauge, pump handle, hoist crank, screw nose and base angles
More informationSMA Interface Mating Dimensions (Per MIL-STD-348)
SMA Series SMA 6 SMA Interface Mating Dimensions (Per MIL-STD-348) SMA Interface Dimensions MALE Inches/Millimeters 3 Minimum Nominal Maximum LTR in. mm in. mm in. mm A.250 6.35.263 6.68.. B.1790 4.55.1808
More informationThe very Best. ANSI Post Insulators 2016
The very Best. ANSI Post Insulators 2016 Introduction ANSI Post Insulators High Tech TR Post Never comprom Better Design enables higher performances with less weight Under normal service conditions, the
More informationRUBBER SLEEVE KNIFE GATE VALVE
RUBBER SLEEVE KNIFE GATE VALVE The model knife gate is a wafer valve designed for a wide range of industrial applications. The double-seated design provides bi-directional shut off. The design of the valve
More informationMedium Voltage Terminations, 5 kv 46 kv
Medium Voltage Terminations, 5 kv 46 kv Over 30 years ago, 3M pioneered cold shrink technology. Since then, field use and laboratory analysis have repeatedly proven its merits and reliability. Through
More informationOne Year Warranty. Stock U.S. # of Volts Weight CONN. Height Dia. Watts # GAL. Elements INS. Inches NATURAL GAS* Six Year Warranty
One Year Warranty ELECTRIC Stock U.S. # of Volts Weight CONN. Height Dia. Watts # GAL. Elements INS. Inches Fused Ceramic Shield tank lining is corrosion-resistant for years of dependability. Adjustable
More informationEDITION 2012 CABLE SYSTEMS
EDITION 2012 CABLE SYSTEMS Cable fittings for high voltage networks Welcome to the CABLE SYSTEMS Centre of Competence. Our range of cable accessories offers solutions for virtually all applications in
More informationDigital Energy ITI. Instrument Transformer Basic Technical Information and Application
g Digital Energy ITI Instrument Transformer Basic Technical Information and Application Table of Contents DEFINITIONS AND FUNCTIONS CONSTRUCTION FEATURES MAGNETIC CIRCUITS RATING AND RATIO CURRENT TRANSFORMER
More informationENGINEERING COMMITTEE
ENGINEERING COMMITTEE Interface Practices Subcommittee AMERICAN NATIONAL STANDARD ANSI/SCTE 02 2006 Specification for F Port, Female, Indoor NOTICE The Society of Cable Telecommunications Engineers (SCTE)
More informationLightning Arresters P30027 18 KVA P30038 10 KVA. Description & Installation
Lightning Arresters P30027 18 KVA P30038 10 KVA Description & Installation Printed in USA 09/11 TO330 Rev. B Table of Contents Page 1.0 SCOPE 2 2.0 PRODUCT OVERVIEW 2 2.1 Intended Uses 2 2.2 Lightning
More informationExplosion-Proof Electric Unit Heaters
Type FX4 FX4 Explosion-Proof Electric Air Heaters FX4 heaters are UL listed and/or CSA certified for use in hazardous locations. They are designed for dry indoor industrial applications such as oil refineries,
More information3.1.1 Full Type Tests & Routine Tests according to Clause 8 2 & 8 3. 4.0 Instructions For Installation, Operation & Maintenance
SPECIFICATION FOR LOW VOLTAGE SWITCHBOARD SEN I N D E X Description 10 STANDARD TECHNICAL REQUIREMENTS 11 Standards 12 General Operating Conditions 13 General Description Of Switchboard 131 Structure 132
More informationHigh-Voltage Compact Switchgear 3AP1 DTC for 145 kv and 245 kv
High-Voltage Compact Switchgear AP1 DTC for 1 kv and kv Answers for energy. The AP1 DTC Complying with our Customers demands Experience you can rely on - at anytime, anywhere Decades of experience in high-voltage
More information