1 SECTION VIBRATION ISOLATION PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Basic Requirements: Provisions of Section 15010, BASIC MECHANICAL REQUIREMENTS are a part of this Section SUMMARY A. General: Provide vibration hangers and isolation supports for equipment and piping as required to prevent transmission of vibration and structureborne noise to building structure ADDITIONAL REQUIREMENTS A. Related Sections: Other Sections of Division 15 which relate to the requirements of this Section may include but are not limited to the following: 1.02 SUBMITTAL , BASIC MECHANICAL MATERIALS AND METHODS , PUMPS , PLUMBING EQUIPMENT , HYDRONIC PIPING SYSTEM , AIR HANDLING UNIT , FANS , DUCTWORK , PERFORMANCE VERIFICATION A. General: Refer to paragraph entitled "SUBMITTAL" in Section In addition to those requirements, submit for review the following data: 1. Manufacturers Literature: a. Dimensional outline drawing for each vibration isolator. b. Spring diameter, free spring height, solid spring height, deflection, spring constant and efficiency for each spring isolator. c. Maximum design rated load for each spring isolator. 2. Performance Data: a. Maximum deflection at rated load. b. Load-versus-deflection curve. VIBRATION ISOLATION

2 2. Installation Instructions: a. Manufacturer's printed installation instructions including copies shipped with the isolators. b. Pre-adjustment procedure, intended to control direction of pipe movement and final operating deflection of the springs APPLICABLE STANDARDS A. General: All equipment, material, accessories, methods of construction and reinforcement, finish quality, workmanship and installation shall be in compliance with the paragraph entitled "Code Compliance" in Section B. Acceptance: All vibration isolation equipment shall be both recommended by the manufacturer and acceptable to the Architect for each particular application on this project. C. Elastomeric Isolators: Elastomeric isolators shall comply with ASTM D2240. PART 2 - PRODUCTS 2.01 GENERAL A. Manufacturers: Refer to paragraph entitled "MANUFACTURERS" in Section Vibration isolation equipment shall be provided by a single manufacturer BASIC REQUIREMENTS A. Location: Unless otherwise noted, spring type vibration isolators shall be used for all motor driven equipment. The vibration isolation manufacturer shall determine the amount of spring deflection required for each isolator to achieve optimum performance, prevent the transmission of objectionable vibration and meet noise criteria indicated. B. Selection: Unit designations are indicated in the section describing the equipment to be isolated. Each of the following basic isolators may not be applicable to a specific installation application. C. Operating Range: Isolators shall be selected to operate within the linear portion of their load-versus-deflection curve. D. Indication: Vibration isolators shall have known undeflected heights or calibration markings so the amount of deflection can be determined when carrying load. VIBRATION ISOLATION

3 2.02 SUPPORTS A. Equipment: 1. Type EVS-2: Neoprene pads; waffle or ribbed pattern neoprene pads shall be fabricated from 40 or 50 Durometer neoprene. 40 Durometer pad loading shall not exceed 60 pounds per square inch or 90 pounds per square inch for a 50 Durometer pad. a. Manufacturer and Model Number: Mason Industries Type W 2.04 PIPE CONNECTORS A. General: Flexible connectors shall be provided for all piping connections to rotating equipment. B. Internal Diameter: Connectors shall have the same internal diameter as the pipe in which it is installed (not necessarily internal diameters of inlets or outlets of equipment). C. Recommended Application: Flexible connectors shall both be recommended by the manufacturer and acceptable to the Architect for handling the conveyed fluid at all conditions (maximums and minimums of temperatures, pressures, velocities, etc.) encountered for each particular application. D. Design Requirements: Connectors shall be designed to absorb the combination of vibratory and expansion or contraction motions (lateral and axial and angular) encountered at each installation point (for example, do not use hose type where axial motion is encountered at the installation point unless so recommended by the manufacturer and acceptable to the Architect). E. Allowable Displacement: The allowable displacement of the flexible connector in all directions shall be greater than the maximum deflection in the same relative direction. The stiffness of the flexible connector shall be less than the stiffness of the isolators. F. Hose: 1. Type PVT-1: 304 or 316 Stainless steel hose type; rated to withstand 180 degrees F. operating temperature and 150 psig working pressure; have flanges except 2-1/2 inch and smaller sizes may have screw type fittings installed with a union at one end or with screw-on flanges at both ends; net flexible lengths shall be at least 6 pipe diameters for pipe up to 5 inch ID and not less than 36 inches VIBRATION ISOLATION

4 for pipe 6 inch ID and greater; corrugated bellows with stainless steel wire braid restraining sheath. PART 3 - EXECUTION 3.01 GENERAL A. Installation: Isolators shall be installed in strict accordance with the manufacturer's instructions and shall be adjusted prior to requesting final inspection or the performance of any vibration testing specified. If, in the opinion of the Architect, objectionable noise or vibration is produced or transmitted, necessary changes or additions shall be performed to eliminate the noise and vibration without additional cost to the Owner. B. Corrosion Protection: Steel components shall be phosphated and painted. All nuts, bolts and washers shall be zinc-electroplated. Structural steel bases shall be thoroughly cleaned of welding slag and primed with zinc-chromate or metal etching primer. C. Weather Protection: All isolators exposed to weather shall have steel parts PVC coated, neoprene coated or hot-dip galvanized. Aluminum components shall be etched and painted. Nuts, bolts and washers shall be zinc-electroplated. D. Positioning: Each item of equipment (machinery, piping, etc.) which is required to have vibration isolation equipment shall rest in its intended, operating position (i.e; exactly level, etc.) after installation of vibration isolation equipment. Acceptance of such vibration isolation equipment by the Architect shall not constitute a waiver of this responsibility. E. Pads: Rotating or vibrating equipment which is specified to rest on concrete housekeeping pads shall have minimum 5/16 inch thick Type EVS-2 isolation pads unless otherwise indicated. Loading shall not exceed manufacturer's recommended rating. F. Cleaning: Prior to start-up, clean out all foreign matter between isolators or bases and equipment and verify there are no isolation short-circuits in the installation PIPING IN MECHANICAL EQUIPMENT AND AIR HANDLING UNIT ROOMS A. General: 1. Isolators for equipment and piping are described elsewhere in this division. The vibration isolation manufacturer shall coordinate the selection of piping supports with equipment supports to provide a carefully engineered system designed to accommodate expansion VIBRATION ISOLATION

5 and contraction without excessive stress or misalignment at equipment connections or in the piping. 2. Temporary anchors, where required, shall be installed to permit preadjustment of springs in risers. 3. Permanent limit stops shall be installed to prevent excessive vertical motion of risers in the event water is drained from system. Locations and other details of these limit stops shall be submitted to the Architect for acceptance. 4. Piping connected to vibration isolated equipment shall not strain or force out of alignment the vibration isolators supporting the basic equipment, nor shall pipes restrict such equipment from "floating" freely on its respective vibration isolation system. 5. Piping connected to vibrating equipment shall not physically contact any building construction or non-isolated systems or components. 6. The weight of the pipe shall not be carried by walls through which the pipe passes. B. Isolator Locations: 1. Hanger Boxes: Isolators shall be installed with the hanger box attached to or hung as close as possible to the structure. Hanger rods shall be aligned to clear the hanger box EQUIPMENT ISOLATION A. Vibration Measurement: No vibration amplitude measurement at driving (motor) or driven (pump, fan, etc.) speeds shall exceed manufacturers recommended values. No axial vibration shall exceed maximum radial (perpendicular to shaft) vibration at any bearing or measuring location. In no event shall any rotating equipment exceed 0.05 inches/second rms vibration amplitude under normal operating conditions. Whenever rotational speed is measured as the disturbing frequency, the lowest speed in the system shall be used. END OF SECTION VIBRATION ISOLATION

TCH ENGINEERING SPECIFICATIONS. Index. UL Classified V s, U s and Straight Flexible Connectors. Externally Pressurized Expansion Joints

TCH ENGINEERING SPECIFICATIONS. Index. UL Classified V s, U s and Straight Flexible Connectors. Externally Pressurized Expansion Joints Index UL Classified V s, U s and Straight Flexible Connectors Externally Pressurized Expansion Joints Flexible V and U Connectors Expansion Compensators Flexible Metal Braided Connectors PTFE Expansion

More information

SERIES ASM NEOPRENE/EPMD FLANGED SINGLE SPHERE CONNECTOR CONNECTORS. Pressures to 225 PSIG (15.51 barg) Temperatures to 230ºF (110ºC)

SERIES ASM NEOPRENE/EPMD FLANGED SINGLE SPHERE CONNECTOR CONNECTORS. Pressures to 225 PSIG (15.51 barg) Temperatures to 230ºF (110ºC) APPLICATIONS Process Industry Weak Acids Alkalies Compressed Air Pulp & Paper MODELS ASM - Flanged Connection OPTIONS Control Rods Oil & Gas Water & Waste Pump suction & discharge Sea water Chemical lines

More information

BSM PUMP CORPORATION INSTALLATION AND OPERATION MANUAL

BSM PUMP CORPORATION INSTALLATION AND OPERATION MANUAL INSTALLATION AND OPERATION MANUAL I. INTRODUCTION Properly selected, installed, and maintained, BSM Pumps will provide many years of trouble-free service. Improper selection and installation account for

More information

PIPES AND TUBES FOR HVAC PIPING AND EQUIPMENT

PIPES AND TUBES FOR HVAC PIPING AND EQUIPMENT PIPES AND TUBES FOR HVAC PIPING AND EQUIPMENT GENERAL INFORMATION 1.1 This section applies to piping systems for chilled water, hot water, condenser water, steam, condensate return, fuel oil, refrigerant

More information

M S. Laser Alignment Standards & Procedures

M S. Laser Alignment Standards & Procedures M M S Machine Monitoring Systems Ltd Tel: +44 (0) 1869 250801 Unit 4 Business Point Fax: +44(0) 1869 250802 P.O. Box 92 Bicester OX26 5EW Laser Alignment Standards & Procedures Contents Introduction Laser

More information

SECTION 15140 - PIPE HANGERS AND SUPPORTS

SECTION 15140 - PIPE HANGERS AND SUPPORTS Part I - GENERAL 1.01 SECTION INCLUDES A. The work covered under this section consists of the furnishing of all necessary labor, supervision, materials, equipment, and services to completely execute the

More information

PART 1 GENERAL 1.1 SECTION INCLUDES

PART 1 GENERAL 1.1 SECTION INCLUDES J-1 Section 09110 Long Form Specification INTERIOR METAL STUD FRAMING This section includes lightweight, usually 0.036 inch (0.9 mm) thick or lighter, non-axial load bearing metal stud framing including

More information

SECTION 26 05 49 VIBRATION AND SEISMIC CONTROLS FOR ELECTRICAL SYSTEMS

SECTION 26 05 49 VIBRATION AND SEISMIC CONTROLS FOR ELECTRICAL SYSTEMS SECTION 26 05 49 VIBRATION AND SEISMIC CONTROLS FOR ELECTRICAL SYSTEMS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes seismic restraints and other earthquake-damage-reduction measures for electrical

More information

Model 222S (Galvanized receiver optional) AURORA. 220 Series SINGLE STAGE CONDENSATE AND BOILER FEED PUMPS

Model 222S (Galvanized receiver optional) AURORA. 220 Series SINGLE STAGE CONDENSATE AND BOILER FEED PUMPS Model 222S (Galvanized receiver optional) AURORA 220 Series SINGLE STAGE CONDENSATE AND BOILER FEED PUMPS WWW.AURORAPUMP.COM AURORA 220 Series Single Stage Condensate and Boiler Feed Pumps 2 Introduction

More information

SECTION 08332 COILING COUNTER DOORS. Display hidden notes to specifier. (Don't know how? Click Here)

SECTION 08332 COILING COUNTER DOORS. Display hidden notes to specifier. (Don't know how? Click Here) SECTION 08332 COILING COUNTER DOORS Display hidden notes to specifier. (Don't know how? Click Here) PART 1 GENERAL 1.1 SECTION INCLUDES A. Coiling Metal Counter Doors. B. Coiling Counter Fire Doors. 1.2

More information

SECTION 11014 WINDOW WASHING SYSTEMS

SECTION 11014 WINDOW WASHING SYSTEMS SECTION 11014 WINDOW WASHING SYSTEMS PART 1 - GENERAL 1.1 SUMMARY A. Section includes, but is not limited to, design and furnishing portable davits, davit sleeves, dvit bases, four (4) removable outriggers,

More information

A. ASME Compliance: Fabricate and install hydronic piping in accordance with ASME B31.9 "Building Services Piping.

A. ASME Compliance: Fabricate and install hydronic piping in accordance with ASME B31.9 Building Services Piping. PART 1: GENERAL 1.01 Purpose: A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design. The responsibility of the engineer is

More information

LOBEE VERTICAL SUMP PUMP LOBEE MODEL S/SH AND SA/SHA SUMP PUMPS INSTALLATION AND OPERATING INSTRUCTIONS

LOBEE VERTICAL SUMP PUMP LOBEE MODEL S/SH AND SA/SHA SUMP PUMPS INSTALLATION AND OPERATING INSTRUCTIONS SPT3/2010 LOBEE VERTICAL SUMP PUMP LOBEE MODEL S/SH AND SA/SHA SUMP PUMPS INSTALLATION AND OPERATING INSTRUCTIONS These instructions are important - please read them thoroughly before installing your Lobee

More information

Mechanical Installation

Mechanical Installation Page -1-1. INTRODUCTION AND PURPOSE 1.1. This specification covers the installation, testing and precommissioning of mechanical equipment. Work is to be performed in conjunction with the manufacturer s

More information

SUPPLEMENTAL TECHNICAL SPECIFICATIONS BI-DIRECTIONAL STATIC LOAD TESTING OF DRILLED SHAFTS

SUPPLEMENTAL TECHNICAL SPECIFICATIONS BI-DIRECTIONAL STATIC LOAD TESTING OF DRILLED SHAFTS July 14, 2015 1.0 GENERAL BI-DIRECTIONAL STATIC LOAD TESTING OF DRILLED SHAFTS This work shall consist of furnishing all materials, equipment, labor, and incidentals necessary for conducting bi-directional

More information

MATERIAL SPECIFICATIONS

MATERIAL SPECIFICATIONS FENCING - 1 2-11-1 CHAIN LINK FENCE AND GATE(S) A. SCOPE MATERIAL SPECIFICATIONS This section covers the work necessary for the chain link fence gate(s), complete. General Like items of materials provided

More information

SECTION 02832 CHAIN LINK FENCE AND GATES

SECTION 02832 CHAIN LINK FENCE AND GATES SECTION 02832 CHAIN LINK FENCE AND GATES PART 1 GENERAL 1.01 SECTION INCLUDES A. Fabrication, furnishing and installation of chain link fence, chain link gates, and extension brackets with barbed wire.

More information

Flexider USA, An IMC Company

Flexider USA, An IMC Company Flexider USA, An IMC Company Flexider I N D U S T R I A L Industrial Manufacturing Company (IMC) and Industrial Manufacturing Company International (IMCI) are a proud family of companies that produce a

More information

SECTION 710 GUARDRAIL MATERIALS

SECTION 710 GUARDRAIL MATERIALS 710.08 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 SECTION 710 GUARDRAIL MATERIALS 710.01 General. Metal beam

More information

THERMAL EXPANSION OF BOILERS

THERMAL EXPANSION OF BOILERS THERMAL EXPANSION OF BOILERS INTRODUCTION Boiler is made up of plates, tubes, pipes and simple steel of various grades depending upon the duty conditions. Depending on the service such as cold air / hot

More information

SECTION 32 31 13 CHAIN LINK FENCES AND GATES

SECTION 32 31 13 CHAIN LINK FENCES AND GATES SECTION 32 31 13 CHAIN LINK FENCES AND GATES PART 1 GENERAL 1.1 SUMMARY A. Section Includes: 1. Fence framework, fabric, and accessories. 2. Excavation for post bases. 3. Concrete foundation for posts

More information

SECTION 15076 CEMENT-MORTAR LINED AND COATED STEEL PIPE

SECTION 15076 CEMENT-MORTAR LINED AND COATED STEEL PIPE SECTION 15076 CEMENT-MORTAR LINED AND COATED (CML&C) STEEL PIPE PART 1 GENERAL 1.01 DESCRIPTION This section designates the requirements for steel pipe fabrication, test in shop, installation of steel

More information

SECTION 27 05 36 CABLE TRAYS FOR COMMUNICATIONS SYSTEMS

SECTION 27 05 36 CABLE TRAYS FOR COMMUNICATIONS SYSTEMS SECTION 27 05 36 CABLE TRAYS FOR COMMUNICATIONS SYSTEMS PART 1 GENERAL 1.01 DESCRIPTION A. The work covered by this section of the Specifications includes all labor necessary to perform and complete such

More information

Spring-Flex Hangers Series SH/RSH

Spring-Flex Hangers Series SH/RSH Bulletin No. SH/14 Spring-Flex Hangers Series SH/RSH Two Basic Designs Effective Isolation of Noise and Vibration Loads to 5,000 pounds Static Deflections to 5 inches Quickly and Easily Installed Color

More information

Application Guide. Compensators Hose Assemblies Expansion Joints FLEX-WELD INCORPORATED FLEX-WELD.COM. Manufactured By:

Application Guide. Compensators Hose Assemblies Expansion Joints FLEX-WELD INCORPORATED FLEX-WELD.COM. Manufactured By: Compensators Hose Assemblies Expansion Joints Manufactured By: FLEX-WELD INCORPORATED FLEX-WELD.COM What we need to know... A. Physical / System Parameters 1 Size of Assembly: Measure Pipe size (ID) of

More information

SECTION 15410 GROUND WATER STORAGE TANKS

SECTION 15410 GROUND WATER STORAGE TANKS SECTION 15410 GROUND WATER STORAGE TANKS PART 1 GENERAL.01 SCOPE A. Section Includes Requirements for designing, fabricating, and erecting a welded steel ground storage tank..02 SYSTEM DESCRIPTION A. Design

More information

PART 7: VENTING, COMBUSTION AIR, AND CONDENSATE REMOVAL

PART 7: VENTING, COMBUSTION AIR, AND CONDENSATE REMOVAL 41 PART 7: VENTING, COMBUSTION AIR, AND CONDENSATE REMOVAL The heater must be vented as detailed in this Venting Section. Ensure exhaust and intake piping complies with these instructions regarding vent

More information

Preformed Metal Roofing and Siding

Preformed Metal Roofing and Siding Page -1-1. GENERAL 1.1. Description This specification along with the drawings covers the furnishing of all material, products, equipment, accessories, tools, services, transportation, labor and supervision

More information

PART 8 VENTING, COMBUSTION AIR AND CONDENSATE REMOVAL

PART 8 VENTING, COMBUSTION AIR AND CONDENSATE REMOVAL 32 PART 8 VENTING, COMBUSTION AIR AND CONDENSATE REMOVAL The heater must be vented as detailed in this Venting Section. Ensure exhaust and intake piping complies with these instructions regarding vent

More information

SECTION 02630 STORM DRAINAGE SYSTEM

SECTION 02630 STORM DRAINAGE SYSTEM SECTION 02630 PART 1 - GENERAL 1.01 DESCRIPTION A. Section includes specifications for storm drainage systems including modifications and connections to existing storm drainage systems. 1.02 REFERENCE

More information

SECTION STANDING SEAM METAL ROOFING

SECTION STANDING SEAM METAL ROOFING PART 1 - GENERAL 1.1 DESCRIPTION SECTION 07 41 13 SPEC WRITER NOTES: 1. Use this section only for NCA projects. 2. Use for roofing sloped 1 in 4 (3 in/ft) or greater. 3. Delete between // // if not applicable

More information

VXT. Open Cooling Towers. Open Cooling Towers. Product Detail VXT - B 1. Engineering Data... B2. Structural Support... B6

VXT. Open Cooling Towers. Open Cooling Towers. Product Detail VXT - B 1. Engineering Data... B2. Structural Support... B6 - B 1 Product Detail Engineering Data... B2 Structural Support... B6 Engineering Specifications... B9 - B 2 Engineering Data REMARK: Do not use for construction. Refer to factory certified dimensions &

More information

SECTION 02563 SANITARY SEWER FORCE MAINS

SECTION 02563 SANITARY SEWER FORCE MAINS SECTION 02563 SANITARY SEWER FORCE MAINS 1.0 GENERAL A. Description Sanitary sewer force main installation shall include, but not necessarily be limited to, furnishing and installing pressure rated pipe,

More information

BLADDER SURGE CONTROL SYSTEM

BLADDER SURGE CONTROL SYSTEM PART I GENERAL 1.01 Description BLADDER SURGE CONTROL SYSTEM This specification describes the requirements for a Bladder Surge Control System. The purpose of the system is to minimize transient pressures

More information

PTS HELICAL PIERS INSTALLATION SPECIFICATIONS NOTICE

PTS HELICAL PIERS INSTALLATION SPECIFICATIONS NOTICE FORM A PTS HELICAL PIERS INSTALLATION SPECIFICATIONS NOTICE The following suggested specifications are written as a guide to assist the specifier in writing his own specifications. Specific circumstances

More information

PTFE Slide Bearings 04/10 149

PTFE Slide Bearings 04/10 149 04/10 149 1.0 GENERAL INFORMATION In a wide range of applications, PTFE Slide bearings are superior to conventional expansion plates, rollers and rocker arm type supports. They support petrochemical plant,

More information

Belleville Spring Washer Series

Belleville Spring Washer Series Belleville Spring Washer Series High Load in Small Spaces VARIOUS CONFIGURATIONS OF BELLEVILLE WASHERS Single ONE WASHER Parallel ALL WASHERS STACKED THE SAME WAY Series ALL WASHERS STACKED OPPOSITE EACH

More information

Prefabricated FRP Lift Station Sample Specifications Section 1 General

Prefabricated FRP Lift Station Sample Specifications Section 1 General Section 1 General 1. Description 1.1 Scope of Work: Contractor shall furnish all labor, materials, equipment and performance of all work necessary or incidental to furnish and install a simplex/duplex

More information

SECTION 05 42 16 COLD-FORMED METAL DECK FRAMING Elevations Steel Deck Framing by Trex

SECTION 05 42 16 COLD-FORMED METAL DECK FRAMING Elevations Steel Deck Framing by Trex (Specifier Note: The purpose of this guide specification is to assist the specifier in correctly specifying cold-formed metal deck framing products and execution. The specifier needs to edit the guide

More information

Suggested Specification for Hot-Dip Galvanizing Revised May 2002

Suggested Specification for Hot-Dip Galvanizing Revised May 2002 Suggested Specification for Hot-Dip Galvanizing Revised May 2002 This suggested specification is provided as a guide to producing a quality document calling for after-fabrication hot-dip galvanizing of

More information

ARCHITECTURAL SPECIFICATIONS RHINO ADO 7000

ARCHITECTURAL SPECIFICATIONS RHINO ADO 7000 ARCHITECTURAL SPECIFICATIONS RHINO ADO 7000 LOW-ENERGY ELECTRIC SWING DOOR OPERATOR PART I - GENERAL 1.01 SUMMARY A. SECTION INCLUDES: Access Automation s low energy swing door operator. 1.02 REFERENCES

More information

Section Fiberglass Reinforced Plastic Grating and Structural Fabrications

Section Fiberglass Reinforced Plastic Grating and Structural Fabrications Section 06600 Fiberglass Reinforced Plastic Grating and Structural Fabrications Part 1. General 1.01 Related documents: A. Contract drawings, including general drawings and addenda drawings. B. General

More information

SAMPLE GUIDE SPECIFICATIONS FOR OSTERBERG CELL LOAD TESTING OF DEEP FOUNDATIONS

SAMPLE GUIDE SPECIFICATIONS FOR OSTERBERG CELL LOAD TESTING OF DEEP FOUNDATIONS Page 1 of 9 SAMPLE GUIDE SPECIFICATIONS FOR OSTERBERG CELL LOAD TESTING OF DEEP FOUNDATIONS 1. GENERAL REQUIREMENTS 1. Description of Work: This work consists of furnishing all materials, equipment and

More information

CEILING CASSETTE FAN COIL UNIT

CEILING CASSETTE FAN COIL UNIT CEILING CASSETTE FAN COIL UNIT Operation and Installation Manual MHCFC4W-04, 08, 12, 16 Four way ceiling cassette fan coil unit Please read this manual before using the fan coil unit. Installation and

More information

D Youville College July 31, 2008 New Academic Building Cannon Design Project No. 002935.00

D Youville College July 31, 2008 New Academic Building Cannon Design Project No. 002935.00 SECTION 22 6119 - COMPRESSED-AIR EQUIPMENT FOR LABORATORY AND HEALTHCARE PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Packaged, oilless scroll air compressors. 1.2 DEFINITIONS A. Actual Air: Air

More information

3-Part Specification Railing Cable Systems

3-Part Specification Railing Cable Systems 3-Part Specification Railing Cable Systems GENERAL NOTES TO SPECIFIER: THIS SPECIFICATION SECTION HAS BEEN PREPARED TO ASSIST DESIGN PROFESSIONALS IN THE PREPARATION OF PROJECT OR OFFICE MASTER SPECIFICATIONS.

More information

SECTION VALVE BOXES AND METER VAULTS

SECTION VALVE BOXES AND METER VAULTS SECTION 03 48 20 VALVE BOXES AND METER VAULTS PART 1: GENERAL 1.01 SECTION INCLUDES A. Valve boxes for water and cleanout boxes for wastewater service. B. Meter boxes for water service. C. Meter vaults

More information

1. Division 2 Section "Earthwork" for filling and for grading work. 2. Division 3 Section "Cast-in-Place Concrete" for concrete

1. Division 2 Section Earthwork for filling and for grading work. 2. Division 3 Section Cast-in-Place Concrete for concrete SECTION 02821 - FENCES AND GATES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections,

More information

SECTION 02720 SANITARY SEWER AND STORM DRAIN SYSTEMS

SECTION 02720 SANITARY SEWER AND STORM DRAIN SYSTEMS SECTION 02720 SANITARY SEWER AND STORM DRAIN SYSTEMS PART 1 GENERAL 1.01 SECTION INCLUDES A. The requirements for pipe material and installation in sewer and drainage collection systems. All materials

More information

Building Guide ILLOWA Chapter of ICC. Single Family Residential Uncovered Deck and Porches

Building Guide ILLOWA Chapter of ICC. Single Family Residential Uncovered Deck and Porches Building Guide ILLOWA Chapter of ICC Single Family Residential Uncovered Deck and Porches How to use this guide: This guide was designed to assist the do-it-yourselfer create a construction plan to build

More information

C. CR: Chlorosulfonated polyethylene synthetic rubber. E. EPDM: Ethylene-propylene-diene terpolymer rubber.

C. CR: Chlorosulfonated polyethylene synthetic rubber. E. EPDM: Ethylene-propylene-diene terpolymer rubber. PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section.

More information

MEZZANINE SPECIFICATIONS PART 1 GENERAL 1.1 SCOPE 1.2 APPROVED MANUFACTURER 1.3 REGULATORY ORGANIZATIONS AND GROUPS 1.4 QUALITY ASSURANCE

MEZZANINE SPECIFICATIONS PART 1 GENERAL 1.1 SCOPE 1.2 APPROVED MANUFACTURER 1.3 REGULATORY ORGANIZATIONS AND GROUPS 1.4 QUALITY ASSURANCE MEZZANINE SPECIFICATIONS PART 1 GENERAL 1.1 SCOPE This specification is intended to describe the general requirements applicable to a proper structural mezzanine design. In addition, it is to serve as

More information

All work must conform to the National Electric Code, latest edition, and all other applicable codes and regulations.

All work must conform to the National Electric Code, latest edition, and all other applicable codes and regulations. DIVISION 16 ELECTRICAL SECTION 16100 - ELECTRICAL PART 1 - GENERAL SCOPE All electrical work as shown on the drawings and as necessary to provide a complete electrical system. Include primary service,

More information

SECTION 08332 COILING COUNTER DOORS. Display hidden notes to specifier. (Don't know how? Click Here)

SECTION 08332 COILING COUNTER DOORS. Display hidden notes to specifier. (Don't know how? Click Here) SECTION 08332 COILING COUNTER DOORS Display hidden notes to specifier. (Don't know how? Click Here) PART 1 GENERAL 1.1 SECTION INCLUDES A. Coiling Metal Counter Doors. B. Coiling Counter Fire Doors. 1.2

More information

James M. Pleasants Company

James M. Pleasants Company James M. Pleasants Company SUBMITTAL DATA GAINESVILLE MECHANICAL DECEMBER 20, 2013 PROJECT: GSU: J-183 HUMANITIES LAW BLDG. QUOTE NO:12116 ENGINEER: STEVENS & WILKINSON GASKETED PLATE HEAT EXCHANGER Tag:

More information

SECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM

SECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM SECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Packaged rooftop air conditioning unit (5 tons and smaller). 2. Roof curb. 1.2

More information

GAS DISTRIBUTION PRODUCTS METER RISERS

GAS DISTRIBUTION PRODUCTS METER RISERS METER RISERS INDUSTRIES ABOUT US THE ULTIMATE CONNECTION Our Company Continental Industries, headquartered in Tulsa, Oklahoma, was formed in 1958 and is today a leading manufacturer of connectors for the

More information

SECTION 23 81 43 HEAT PUMPS

SECTION 23 81 43 HEAT PUMPS SECTION 23 81 43 HEAT PUMPS PART 1 GENERAL 1.1 SUMMARY A. Section Includes: 1. Packaged rooftop heat pumps. 1.2 REFERENCES A. American Society of Heating, Refrigerating and Air-Conditioning Engineers:

More information

Section 02702 SEWER PIPE INSTALLATION AND TESTING

Section 02702 SEWER PIPE INSTALLATION AND TESTING PART 1 - GENERAL Section 02702 SEWER PIPE INSTALLATION AND TESTING 1-1. SCOPE. This section covers the installation and testing of all sewer pipe furnished under the following specification sections: Concrete

More information

ITEM #0702770 OSTERBERG CELL LOAD TESTING OF DRILLED SHAFT

ITEM #0702770 OSTERBERG CELL LOAD TESTING OF DRILLED SHAFT ITEM #0702770 OSTERBERG CELL LOAD TESTING OF DRILLED SHAFT Description: This work shall consist of furnishing all materials, equipment and labor necessary for conducting an Osterberg Cell (O-Cell) Load

More information

Q&A Session for Advanced Ball Screws 102: Troubleshooting for Design Engineers

Q&A Session for Advanced Ball Screws 102: Troubleshooting for Design Engineers Q&A Session for Advanced Ball Screws 102: Troubleshooting for Design Engineers Topic: Noise Q: Is there a way to predict/calculate noise on a ball screw? A: No, there is no way to calculate the noise of

More information

SECTION ANCHOR BOLTS. A. Provide bolts and nuts that meet the standards given in Table 1.

SECTION ANCHOR BOLTS. A. Provide bolts and nuts that meet the standards given in Table 1. SECTION 16449 PART 1 DESCRIPTION A. Fabricate and install anchor bolts to be embedded in or attached to concrete. PART 2 MATERIALS 2.01 BOLTS AND NUTS A. Provide bolts and nuts that meet the standards

More information

Wall Panel Design Considerations UC-500 and UC-501 Panel Systems

Wall Panel Design Considerations UC-500 and UC-501 Panel Systems Wall Panel Design Considerations UC-500 and UC-501 Panel Systems Design Considerations for Specified Vertical Concealed Fastener Wall Panels Recent construction trends have shown an increased popularity

More information

KS Vertical In-Line Pump

KS Vertical In-Line Pump KS Vertical In-Line Pump 302-032 Installation, Operation & Maintenance Manual SUPERSEDES: July 1, 2010 EFFECTIVE: August 1, 2012 Plant ID No. 001-1014 SAFETY REQUIREMENTS 1. IMPORTANT! These instructions

More information

B. Trenching, Backfilling, and Compacting: STD SPEC 02223. A. Submit submittal packages in accordance with Standard Specification Section 01300

B. Trenching, Backfilling, and Compacting: STD SPEC 02223. A. Submit submittal packages in accordance with Standard Specification Section 01300 STANDARD SPECIFICATION SECTION 15065 PLASTIC (PVC) GRAVITY SEWER PIPE PART 1 - GENERAL 1.01 DESCRIPTION A. This section includes materials, installation, and testing of PVC gravity sewer pipe conforming

More information

5.23.22 STEAM AND CONDENSATE PIPING AND PUMPS DESIGN AND CONSTRUCTION STANDARD PART 1: GENERAL. 1.01 Purpose:

5.23.22 STEAM AND CONDENSATE PIPING AND PUMPS DESIGN AND CONSTRUCTION STANDARD PART 1: GENERAL. 1.01 Purpose: PART 1: GENERAL 1.01 Purpose: A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design. The responsibility of the engineer is

More information

Installation guide for the SafeLine type anchorage device. Tested in compliance with EN 795: 1996. No.: SE-...

Installation guide for the SafeLine type anchorage device. Tested in compliance with EN 795: 1996. No.: SE-... Installation guide for the SafeLine type anchorage device Tested in compliance with EN 795: 1996 No.: SE-... Version: 09.10.2008 SE 67 Subject to technical alterations! Contents 1. General information

More information

Do not locate the pump unit in a pit unless provisions have been made for proper drainage and ventilation.

Do not locate the pump unit in a pit unless provisions have been made for proper drainage and ventilation. Chemical Gear Pumps Installation Operation Repair Maintenance Installation Principal of Operation All Oberdorfer Chemical Gear pumps are the positive displacement type. A definite amount of liquid is displaced

More information

PIPING SYSTEM - ABRASIVE SLURRIES Engineering Standard Specification. 96 B. Riutta

PIPING SYSTEM - ABRASIVE SLURRIES Engineering Standard Specification. 96 B. Riutta PIPING SYSTEM - ABRASIVE SLURRIES Engineering Standard Specification Number: 3503-11.2.610 Rev. 2 Rubber Lined Steel Pipe and Fittings Mechanically Coupled Plain End Type System Issued Revised Approved

More information

2-42 Flanged Vacuum Breaker. Operation, Maintenance and Installation Manual

2-42 Flanged Vacuum Breaker. Operation, Maintenance and Installation Manual Manual No. VB-OM1-1 2-42 Flanged Vacuum Breaker Operation, Maintenance and Installation Manual INTRODUCTION... 1 RECEIVING AND STORAGE... 1 DESCRIPTION OF OPERATION... 1 INSTALLATION... 2 DRAWING SS-1381...

More information

Gas Distribution and Transportation

Gas Distribution and Transportation Piping System Includes: Pipe Fittings (e.g. elbows, reducers, branch connections, etc.) Flanges, gaskets, bolting Valves Associations involved in generating Codes for piping Design Engineering: ASME ANSI

More information

specifications A*COM SYSTEM bridging the gap. A*COM Commercial Ramp System PART 1 General

specifications A*COM SYSTEM bridging the gap.  A*COM Commercial Ramp System PART 1 General specifications A*COM Commercial Ramp System This section is based on products manufactured by A*COM and distributed by AlumiRamp, Inc., located at the following address: 855 Chicago Road, Quincy, MI 49082,

More information

UNIVERSITY OF ROCHESTER DESIGN STANDARDS OCTOBER 18, 2013

UNIVERSITY OF ROCHESTER DESIGN STANDARDS OCTOBER 18, 2013 SECTION 233416 - CENTRIFUGAL HVAC FANS PART 1 GENERAL 1.01 GENERAL REQUIREMENTS A. Fans shall be dynamically balanced and factory-tested and certified in accordance with applicable AMCA test codes. All

More information

Technical Specification. Transport and Main Roads Specifications MRTS82 Bridge Deck Expansion Joints

Technical Specification. Transport and Main Roads Specifications MRTS82 Bridge Deck Expansion Joints Technical Specification Transport and Main Roads Specifications MRTS82 Bridge Deck Expansion Joints June 2009 Copyright http://creativecommons.org/licenses/by/3.0/au/ State of Queensland (Department of

More information

APPENDIX F VIBRATION TESTING PROCEDURE

APPENDIX F VIBRATION TESTING PROCEDURE APPENDIX F VIBRATION TESTING PROCEDURE Appendix F SPS-F-1 of 14 VIBRATION PERFORMANCE TESTING I. General Perform a vibration analysis on all motor driven equipment listed below after it is installed and

More information

San Antonio Water System Standard Specifications for Construction ITEM NO. 1100 SLIP-LINING SANITARY SEWERS

San Antonio Water System Standard Specifications for Construction ITEM NO. 1100 SLIP-LINING SANITARY SEWERS ITEM NO. 1100 SLIP-LINING SANITARY SEWERS 1100.1 DESCRIPTION: This item shall consist of slip-lining sanitary sewer pipe, which is accomplished by pulling or pushing liner pipe into existing sewers by

More information

HYDRONIC PIPING SPECIALTIES AND PIPING GUIDELINES

HYDRONIC PIPING SPECIALTIES AND PIPING GUIDELINES HYDRONIC PIPING SPECIALTIES AND PIPING GUIDELINES GENERAL INFORMATION 1.1 This section applies to piping systems specialties for hot water heating, chilled water cooling, condenser water, make-up water

More information

Page 1 of 5

Page 1 of 5 SPECIFICATIONS METAL COMPOSITE MATERIAL WALL PANELS ESTOLGA 3000 DRY SEAL SYSTEM PART 1 GENERAL 1.01 SECTION INCLUDES A. Exterior cladding consisting of formed metal composite material (MCM) sheet, secondary

More information

FOUNDATION & LOAD BEARING ELEMENTS 02450

FOUNDATION & LOAD BEARING ELEMENTS 02450 210 N. Allen St. Centralia, MO 65240 Phone: (573) 682-8414 Fax: (573) 682-8660 E-mail: hpscontact@hps.hubbell.com www.abchance.com This MANU-SPEC utilizes the Construction Specifications Institute (CSI)

More information

SECTION 02400 - STORM DRAIN SYSTEM

SECTION 02400 - STORM DRAIN SYSTEM SECTION 02400 - STORM DRAIN SYSTEM CONTENTS: Part 1 - General... 1 1.01 Work Included... 1 1.02 Related Requirements... 1 1.03 Reference Standards... 1 1.04 Quality Assurance... 1 1.05 Measurement And

More information

Wastewater Capital Projects Management Standard Construction Specification

Wastewater Capital Projects Management Standard Construction Specification CITY AND COUNTY OF DENVER ENGINEERING DIVISION Wastewater Capital Projects Management Standard Construction Specification 10.1 Precast Concrete Pipe 10.1.1 General This section covers material requirements,

More information

SECTION 230529 - HANGERS AND SUPPORTS FOR HVAC PIPING AND EQUIPMENT

SECTION 230529 - HANGERS AND SUPPORTS FOR HVAC PIPING AND EQUIPMENT SECTION 230529 - PART 1 - GENERAL 1.1 SUMMARY A. This Section includes the following: 1. Steel pipe hangers and supports. 2. Metal framing systems. 3. Thermal-hanger shield inserts. 4. Fastener systems.

More information

SECTION 23 05 29 - HANGERS AND SUPPORTS FOR HVAC PIPING AND EQUIPMENT

SECTION 23 05 29 - HANGERS AND SUPPORTS FOR HVAC PIPING AND EQUIPMENT SECTION 23 05 29 - HANGERS AND SUPPORTS FOR HVAC PIPING AND EQUIPMENT PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Pipe hangers and supports. 2. Hanger rods. 3. Inserts. 4. Flashing. 5. Equipment

More information

Galvanized Pipe. Standard pipe is 16 gauge galvanized construction. Standard lengths are five feet and 20 feet. Heavier gauges are also available.

Galvanized Pipe. Standard pipe is 16 gauge galvanized construction. Standard lengths are five feet and 20 feet. Heavier gauges are also available. Galvanized Pipe Standard pipe is 16 gauge galvanized construction. Standard lengths are five feet and 20 feet. Heavier gauges are also available. Angle rings are needed to secure connections. See pages

More information

Section Fiberglass Reinforced Plastic Grating and Structural Fabrications

Section Fiberglass Reinforced Plastic Grating and Structural Fabrications Section 06600 Fiberglass Reinforced Plastic Grating and Structural Fabrications Part 1. General 1.01 Related documents: A. Contract drawings, including general drawings and addenda drawings. B. General

More information

SECTION 05 7360 ALUMINUM HANDRAIL AND RAILING SYSTEMS WITH DECORATIVE METAL PANEL INFILLS

SECTION 05 7360 ALUMINUM HANDRAIL AND RAILING SYSTEMS WITH DECORATIVE METAL PANEL INFILLS 1 SECTION 05 7360 ALUMINUM HANDRAIL AND RAILING SYSTEMS WITH DECORATIVE METAL PANEL INFILLS PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and

More information

BUILT-IN DISHWASHER INSTALLATION INSTRUCTIONS

BUILT-IN DISHWASHER INSTALLATION INSTRUCTIONS BUILT-IN DISHWASHER INSTALLATION INSTRUCTIONS PLEASE READ COMPLETE INSTRUCTIONS BEFORE YOU BEGIN LEAVE INSTALLATION INSTRUCTIONS AND USER'S GUIDE WITH OWNER ALL ELECTRIC WIRING AND PLUMBING MUST BE DONE

More information

CONTRACT SPECIFICATIONS - SEISMIC ISOLATION BEARINGS

CONTRACT SPECIFICATIONS - SEISMIC ISOLATION BEARINGS CONTRACT SPECIFICATIONS - SEISMIC ISOLATION BEARINGS 1.0 DESIGN 1.1 Scope of Work 1.1.1 This work shall consist of furnishing Isolation Bearings and installing Isolation Bearing Assemblies at the locations

More information

SECTION 02845 GUARDRAILS

SECTION 02845 GUARDRAILS SECTION 02845 GUARDRAILS PART 1 - GENERAL 1.01 SCOPE OF WORK A. Furnish all labor, materials, equipment and incidentals necessary and repair, replace or install all types of guardrails as specified herein

More information

CLEAR-DIVISIONS CENTERFOLD

CLEAR-DIVISIONS CENTERFOLD CLEAR-DIVISIONS CENTERFOLD Introduction: The following three (3) part specification offers the Standard and Optional features for the CLEAR-DIVISIONS CENTERFOLD moveable The yellow highlighted areas in

More information

SECTION 15 AIR RELEASE VALVE ASSEMBLIES. 15-1 General

SECTION 15 AIR RELEASE VALVE ASSEMBLIES. 15-1 General SECTION 15 AIR RELEASE VALVE ASSEMBLIES 15-1.01 Scope 15-1 General This section describes the requirements for furnishing and installing Air Release Valve Assemblies of the size and type shown on the plans,

More information

Chapter 3 Pre-Installation, Foundations and Piers

Chapter 3 Pre-Installation, Foundations and Piers Chapter 3 Pre-Installation, Foundations and Piers 3-1 Pre-Installation Establishes the minimum requirements for the siting, design, materials, access, and installation of manufactured dwellings, accessory

More information

SPECIFICATION DIVISION 23 SECTION DESCRIPTION DIVISION 23 HEATING, VENTILATING AND AIR CONDITIONING (HVAC) SECTION 238221 - BLOWER COIL UNITS

SPECIFICATION DIVISION 23 SECTION DESCRIPTION DIVISION 23 HEATING, VENTILATING AND AIR CONDITIONING (HVAC) SECTION 238221 - BLOWER COIL UNITS ARCHITECTURE, ENGINEERING AND CONSTRUCTION P00000000 0000 DOCUMENTS ARCHITECTURE & ENGINEERING 326 East Hoover, Mail Stop B Ann Arbor, MI 48109-1002 Phone: 734-764-3414 Fax: 734-936-3334 SPECIFICATION

More information

Installation and Operating Instructions Installation Instructions for SS EPE-316L Series

Installation and Operating Instructions Installation Instructions for SS EPE-316L Series INSTR3010 0406 Installation and Operating Instructions Installation Instructions for SS EPE-316L Series Congratulations on your purchase of this Aqua-Pure high flow, single housing filtration system. This

More information

VCS. MASON INDUSTRIES, Inc. COMPLETE HVAC ENGINEERING SPECIFICATIONS VCS-100-13 BULLETIN

VCS. MASON INDUSTRIES, Inc. COMPLETE HVAC ENGINEERING SPECIFICATIONS VCS-100-13 BULLETIN First Printing 1965 Revised 1973, 1974, 1975, 1976, 1979, 1982, 4/2001, 9/2001, 11/2003, 8/2005. 11/06, 1/08, 9/10 & MARCH 2014 MASON INDUSTRIES, Inc. Manufacturers of Vibration Control Products 350 Rabro

More information

KINETICS TM. 1" and 2" Deflection Isolation Hangers Model SRH. Polyester Powder Coated Bracket and Spring Coil Self-Centering Cap Patent No.

KINETICS TM. 1 and 2 Deflection Isolation Hangers Model SRH. Polyester Powder Coated Bracket and Spring Coil Self-Centering Cap Patent No. Polyester Powder Coated Bracket and Sprg Coil Self-Centerg Cap Patent No. 5,6,426 Application Ketics Model SRH hangers are used to isolate suspended sources of both noise and vibration. Suspended mechanical

More information

TABLE OF CONTENT

TABLE OF CONTENT Page : 1 of 21 Project Engineering Standard www.klmtechgroup.com KLM Technology #03-12 Block Aronia, Jalan Sri Perkasa 2 Taman Tampoi Utama 81200 Johor Bahru Malaysia TABLE OF CONTENT SCOPE 2 REFERENCES

More information

Coupling Alignment Fundamentals

Coupling Alignment Fundamentals Page (1 of 14) CONTENTS I. Why Align Rotating Equipment? II. Defining Shaft Misalignment III. Alignment Methods Poor, Fair, Good and Best IV. Pre-Alignment Considerations V. Alignment Methods A. Rim and

More information

DIVISION 8, METAL SOUND CONTROL DOOR ASSEMBLIES PART 1 GENERAL 1.1 RELATED DOCUMENTS

DIVISION 8, METAL SOUND CONTROL DOOR ASSEMBLIES PART 1 GENERAL 1.1 RELATED DOCUMENTS DIVISION 8, METAL SOUND CONTROL DOOR ASSEMBLIES PART 1 GENERAL 1.1 RELATED DOCUMENTS Drawings and general provisions of the contract, including general and supplementary conditions and other Division 1

More information