1 SECTION COMPRESSED-AIR EQUIPMENT FOR LABORATORY AND HEALTHCARE PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Packaged, oilless scroll air compressors. 1.2 DEFINITIONS A. Actual Air: Air delivered at air-compressor outlet. Flow rate is compressed air delivered and measured in acfm (actual L/s). B. Laboratory Air Equipment: Compressed-air equipment and accessories for nonmedical laboratory facilities. C. Low Voltage: As defined in NFPA 70 for circuits and equipment operating at less than 50 V or for remote-control, signaling power-limited circuits. D. Standard Air: Free air at 68 deg F (20 deg C) and 1 atmosphere (29.92 in. Hg) before compression or expansion and measured in scfm (standard L/s). 1.3 SUBMITTALS A. Product Data: For each type of product indicated. Include rated capacities, operating characteristics, electrical characteristics, and furnished specialties and accessories. 1. Wiring Diagrams: For power, signal, and control wiring. B. Qualification Data: For qualified Installer and testing agency. 1.4 QUALITY ASSURANCE A. Installer Qualifications: 1. Laboratory Air System Equipment for Nonmedical Laboratory Facilities: An employer of workers trained and approved by manufacturer. B. Testing Agency Qualifications: An independent testing agency, with the experience and capability to conduct the compressed-air equipment testing indicated, that is a member of the Medical Gas Professional Healthcare Organization or is an NRTL and that is acceptable to authorities having jurisdiction

2 1. Qualify testing personnel according to ASSE 6020 for inspectors and ASSE 6030 for verifiers. C. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and application. D. ASME Compliance: Fabricate and label receivers to comply with ASME Boiler and Pressure Vessel Code. 1.5 COORDINATION A. Coordinate sizes and locations of concrete bases with equipment provided. 1.6 EXTRA MATERIALS A. Furnish extra materials that match products installed and that are packaged with protective covering for storage and identified with labels describing contents. 1. Air-Compressor, Inlet-Air Filter Elements: Equal to percent of amount installed. 2. Belts: Two for each belt-driven compressor. PART 2 - PRODUCTS 2.1 OILLESS, SCROLL AIR COMPRESSORS A. Manufacturers: Subject to compliance with requirements, provide products by one of the following: 1. Allied Healthcare Products, Inc.; Chemetron Div. 2. BeaconMedaes. 3. Powerex, Inc. 4. Squire-Cogswell/Aeros Instruments, Inc. B. Description: Packaged unit, factory-assembled, -wired, -piped, and tested; electric-motordriven; air-cooled; continuous-duty air compressors and receivers that deliver air of quality equal to intake air. C. The control system is NEMA 12 and UL labeled. Provide in the control system: 1. Automatic lead/lag sequencing and alternation. 2. Circuit breaker disconnects for each compressor internal to the main control cabinet and protected by the safety interlock of that cabinet. 3. Full voltage motor starters with overload protection. 4. Redundant 120 Volt control circuit transformers 5. Phase reversal protection. 6. Visual and audible reserve unit alarm with isolated contacts for remote alarm and cancelable audio. 7. HOA lighted selector switches 8. Panel mounted pressure gauge

3 9. Runtime hourmeters for each compressor. 10. When HOA switches are in Hand mode, system will operate on pressure switch and compressors will not run if lead switch is satisfied. 11. Provide visual and audible alarm indication for high discharge air temperature shutdown with isolated contacts for remote alarm. 12. A temperature sensor is provided at the outlet of each compressor head to provide hitemp alarm and shutdown that compressor. Systems employing a single switch are not acceptable. 13. Compressor motors shall be a NEMA rated, open drip proof unit with 1.15 service factor suitable for 208 or 230/460 volt. 14. All moving parts (fans, pulleys and belts) shall be fully protected by a OSHA approved enclosure. 15. All support structures shall be a minimum of 10 Gauge Steel. 16. The compressor modules and motors shall be fully isolated from the main compressor base by means of a four point, heavy-duty isolation system for a minimum of 95% isolation efficiency. Engineering data shall be provided supporting isolation efficacy and equal weight distribution between supports. Pumps not having this feature shall have a inertia base sized for that system installed at this contractors expense. D. Provide redundant medical air treatment systems including desiccant dryers, filters, and purifiers sized for peak calculated demand. Include dew point and carbon monoxide monitoring Medical air treatment shall include: 1. See schedule for dryer package 2. All piping shall be factory complete including all valves per NFPA 99. E. System piping shall be brazed except where unions are required for service. Vibration flexes shall be all metal and of sufficient length to achieve full isolation. Systems using rubber tubing flex connectors with hose clamps are not acceptable. F. Provide a corrosion resistant, ASME Coded, National Board Certified, receiver rated for a minimum 150 PSIG design pressure. Include a liquid level glass, safety relief valve, manual drain valve, and a screened automatic solenoid valve. During normal operation the flow of air will travel through the tank to allow water to condense in tank. G. The complete medical air package shall be pre-wired, pre-piped and assembled on one common base with single point connections for electrical, intake air, discharge air, and condensate drains. All elements shall be factory installed including source valve. See drawings for details. H. The compressors shall be an continuous duty rated scroll type with sealed bearings. The design shall be single stage, air-cooled, consisting of one fixed and one orbiting scroll sealed with PTFE tip seals between the scroll halves and rated for 828 kpa (120 PSIG) discharge pressure. Orbiting bearings shall be grease filled and permanently sealed type requiring no lubrication at any time. Units requiring relubrication are not acceptable. Noise level shall not exceed 75 db(a) for duplex system with pumps running at peak demand. Belt tensioning shall be achieved with a pivoting motor mounting base adjustable with one tensioning screw. Each compressor shall be equipped with a integral air-cooled after cooler designed for a maximum approach temperature of 7 C (15 F) at 37.8 C (100 F) and complete with automatic drain valve. The discharge of piping of each compressor shall incorporate an integral valve to provide load-less starting and shall prevent less than 1/4 revolution of reverse rotation of the scroll at shutdown

4 I. Air Compressor(s): Two-stage, oilless (nonlubricated), scroll type, with sealed oil-free bearings, that will deliver air of quality equal to intake air. J. Capacities and Characteristics: 1. Compressed-Air Service: Medical laboratory air. 2. Air Compressor(s): Two. 3. Discharge-Air Pressure: 125 psig (860 kpa). 4. Mounting: Freestanding. 5. Motor (Each Air Compressor): 6. Receiver: ASME construction steel tank. a. Orientation: Horizontal arrangement. b. Pressure Rating: 150 psig (1035 kpa) minimum. c. Drain: Automatic valve. PART 3 - EXECUTION 3.1 PREPARATION A. Clean compressed-air equipment, accessories, and components that have not been cleaned for oxygen service and sealed or that are furnished unsuitable for laboratory air and medical air applications, according to CGA G-4.1, "Cleaning Equipment for Oxygen Service." 3.2 COMPRESSED-AIR EQUIPMENT INSTALLATION A. General Requirements for Compressed-Air Equipment Installation: 1. Install compressed-air equipment to allow maximum headroom unless specific mounting heights are indicated. 2. Install equipment level and plumb, parallel and perpendicular to other building systems and components in exposed interior spaces unless otherwise indicated. 3. Install mechanical equipment to facilitate service, maintenance, and repair or replacement of components. Connect equipment for ease of disconnecting, with minimum interference to other installations. Extend grease fittings to accessible locations. 4. Install equipment to allow right of way for piping installed at required slope. 5. Install the following devices on compressed-air equipment: a. Thermometer, Pressure Gage, and Safety Valve: Install on each compressed-air receiver. b. Pressure Regulators: Install downstream from air compressors, dryers, purification units, and filter assemblies. c. Drain Valves: Install on aftercoolers, receivers, and dryers. Discharge condensate over nearest floor drain. B. Nonmedical Laboratory Compressed-Air Equipment Installation: 1. Install compressed-air equipment, except wall-mounting equipment, on concrete bases. Install units anchored to substrate in locations indicated. Maintain manufacturers'

5 recommended clearances. Orient equipment so controls and devices are accessible for servicing. a. Anchor equipment to concrete bases according to manufacturer's written instructions. 1) For supported equipment, install epoxy-coated anchor bolts that extend through concrete base and anchor into structural concrete floor. 2) Place and secure anchorage devices. Use setting drawings, templates, diagrams, instructions, and directions furnished with items to be embedded. 3) Install anchor bolts to elevations required for proper attachment to supported equipment. 3.3 CONNECTIONS A. Comply with requirements for compressed-air piping specified in Division 22 Section "Compressed-Air Piping for Laboratory and Healthcare Facilities." Drawings indicate general arrangement of piping, fittings, and specialties. B. Install piping adjacent to equipment to allow service and maintenance. C. Connect compressed-air piping to compressed-air equipment, accessories, and specialties with shutoff valve and union or flanged connection. 3.4 IDENTIFICATION A. Identify nonmedical laboratory compressed-air equipment system components. Comply with requirements for identification specified in Division 22 Section "Identification for Plumbing Piping and Equipment." 3.5 FIELD QUALITY CONTROL FOR COMPRESSED-AIR EQUIPMENT A. Perform tests and inspections. 1. Manufacturer's Field Service: Engage a factory-authorized service representative to inspect components, assemblies, and equipment installations, including connections, and to assist in testing. B. Tests and Inspections: 1. Compressed-Air Equipment Testing Coordination: Perform tests, inspections, verifications, and certification of compressed-air equipment concurrently with tests, inspections, and certification of vacuum equipment, vacuum piping, compressed-air piping, and gas piping systems. 2. Preparation: Perform compressed-air equipment tests according to requirements in NFPA 99 for the following: a. Air-quality purity test. b. System operation test

6 3. Equipment Verification: Comply with requirements in ASSE 6020, ASSE 6030, and NFPA 99 for verification of medical compressed-air equipment. 4. Replace damaged and malfunctioning controls and equipment. 5. Testing Certification: Certify that specified tests, inspections, and procedures have been performed and certify report results. Include the following: a. Inspections performed. b. Procedures, materials, and gases used. c. Test methods used. d. Results of tests. C. Components will be considered defective if they do not pass tests and inspections. D. Prepare test and inspection reports. 3.6 STARTUP SERVICE A. Engage a factory-authorized service representative to perform startup service. 1. Complete installation and startup checks according to manufacturer's written instructions. 2. Check for lubricating oil in lubricated-type equipment. 3. Check belt drives for proper tension. 4. Verify that air-compressor inlet filters and piping are clear. 5. Check for equipment vibration-control supports and flexible pipe connectors and verify that equipment is properly attached to substrate. 6. Check safety valves for correct settings. Ensure that settings are higher than aircompressor discharge pressure but not higher than rating of system components. 7. Drain receiver tanks. 8. Operational Test: After electrical circuitry has been energized, start units to confirm proper motor rotation and unit operation. 9. Test and adjust controls and safeties. 3.7 DEMONSTRATION A. Engage a factory-authorized service representative to train Owner's maintenance personnel to adjust, operate, and maintain air compressors. END OF SECTION

Medical Air Systems: Scroll

Medical Air Systems: Scroll GENERAL The Chemetron skid mount scroll medical air system is designed to provide medical breathing air for hospital and medical institutions. This system meets NFPA 99 requirements for Level 1 breathing

More information

Medical Air Systems Product Selection Guide

Medical Air Systems Product Selection Guide Medical Air Systems Product Selection Guide Oil-less Scroll... Oil-less Reciprocating... Enclosed Scroll... WHY POWEREX? SERVICE Powerex has an extensive network of trained sales and service dealers over

More information

Element D Services Plumbing

Element D Services Plumbing Medical Vacuum and Gas PART 1 - GENERAL 1.01 OVERVIEW A. This section addresses medical vacuum, waste anesthetic gas disposal, compressed air, oxygen, nitrous oxide, nitrogen and carbon dioxide systems.

More information

LAKE COUNTY ANIMAL SERVICES EXPANSION SECTION 15459

LAKE COUNTY ANIMAL SERVICES EXPANSION SECTION 15459 SECTION 15459 PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. Drawings and general provisions of Contract, including General and Supplementary Conditions and Division-1 Specification sections, apply to work

More information

SECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM

SECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM SECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Packaged rooftop air conditioning unit (5 tons and smaller). 2. Roof curb. 1.2

More information

SECTION 226113 MEDICAL COMPRESSED-AIR PIPING FOR HEALTHCARE FACILITIES PART 1 - GENERAL

SECTION 226113 MEDICAL COMPRESSED-AIR PIPING FOR HEALTHCARE FACILITIES PART 1 - GENERAL SECTION 226113 MEDICAL COMPRESSED-AIR PIPING FOR HEALTHCARE FACILITIES PART 1 - GENERAL 1.1 SUMMARY A. This Section includes the following: 1. Medical air piping and specialties, designated "medical air,"

More information

A. This Section includes packaged, air-cooled, electric-motor-driven, rotary-screw water chillers with the following features:

A. This Section includes packaged, air-cooled, electric-motor-driven, rotary-screw water chillers with the following features: - ROTARY-SCREW WATER CHILLERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections,

More information

Element D Services Plumbing

Element D Services Plumbing Laboratory Vacuum and Gas PART 1 - GENERAL 1.01 OVERVIEW A. This section addresses laboratory vacuum, compressed air, gaseous nitrogen, and carbon dioxide systems within and to five feet beyond building

More information

SECTION 23 00 01 HEATING, VENTILATION AND AIR CONDITIONING EQUIPMENT

SECTION 23 00 01 HEATING, VENTILATION AND AIR CONDITIONING EQUIPMENT SECTION 23 00 01 HEATING, VENTILATION AND AIR CONDITIONING EQUIPMENT PART 1 - GENERAL 1.1 DESCRIPTION A. The Work specified in this Section consists of designing, furnishing and installing factory-assembled

More information

SECTION 15750 PACKAGED ROOFTOP AIR CONDITIONING UNITS

SECTION 15750 PACKAGED ROOFTOP AIR CONDITIONING UNITS SECTION 15750 PART 1 - GENERAL 1.01 DESCRIPTION A. Section includes requirements for roof mounted, self-contained units, with electric cooling, and electric or reverse refrigeration cycle (heat pump) heating

More information

SECTION (16289) - SURGE PROTECTION FOR LOW VOLTAGE ELECTRICAL POWER CIRCUITS

SECTION (16289) - SURGE PROTECTION FOR LOW VOLTAGE ELECTRICAL POWER CIRCUITS SECTION 26 43 13 (16289) - SURGE PROTECTION FOR LOW VOLTAGE ELECTRICAL POWER CIRCUITS PART 1 GENERAL 1.01 SUMMARY A. Section Includes: 1. Transient Voltage Surge Suppressors for Low-Voltage Power, Control,

More information

BC & BCH SERIES INDOOR / OUTDOOR INSTALLATION

BC & BCH SERIES INDOOR / OUTDOOR INSTALLATION Air Conditioning Central Heating & Cooling BC & BCH SERIES INDOOR / OUTDOOR INSTALLATION INSTALLATION AND SERVICE MANUAL 2 PROJECT: ADDRESS: MODEL: SERIAL NUMBER: INSTALLER: ADDRESS: PHONE NUMBER: INSTALLATION

More information

For us, it s not just business. It s personal.

For us, it s not just business. It s personal. For us, it s not just business. It s personal. CLIMATE CONTROL SERIES - SIMPLEX TANK MOUNTED Quiet operation. Heavy duty single and two stage high efficiency air compressors. Durable cast iron pumps for

More information

CASE STUDY 1 COMMISSIONING A GAS FIRED STEAM BOILER

CASE STUDY 1 COMMISSIONING A GAS FIRED STEAM BOILER CASE STUDY 1 COMMISSIONING A GAS FIRED STEAM BOILER A steam boiler has been built and installed at a factory for the provision of process steam. The following lists the requirements used in the commissioning

More information

For us, it s not just business. It s personal.

For us, it s not just business. It s personal. For us, it s not just business. It s personal. HEAVY DUTY SERIES - VERTICAL TANK MOUNTED Quiet operation. Heavy duty two stage high efficient air compressors. All units factory set at 120-150psi. All units

More information

A. This Section includes SPDs for low-voltage power, control, and communication equipment.

A. This Section includes SPDs for low-voltage power, control, and communication equipment. PART 1 - GENERAL... 1 1.1 RELATED DOCUMENTS... 1 1.2 SUMMARY... 1 1.3 REFERENCES... 1 1.4 DEFINITIONS... 2 1.5 SUBMITTALS... 2 1.6 QUALITY ASSURANCE... 2 1.7 PROJECT CONDITIONS... 3 1.8 COORDINATION...

More information

ELECTRICAL CONTRACTORS THE UNIVERSITY OF TENNESSEE KNOXVILLE, TENNESSEE SECTION 16050 PAGE 1

ELECTRICAL CONTRACTORS THE UNIVERSITY OF TENNESSEE KNOXVILLE, TENNESSEE SECTION 16050 PAGE 1 KNOXVILLE, TENNESSEE SECTION 16050 PAGE 1 PART 1 - GENERAL 1.01 RELATED DOCUMENTS: SECTION 16050 A. Drawings and general provisions of Contract, including General and Supplementary Conditions and Division-1

More information

Oil and Coolant Circulating Heating System. Model - OCSM

Oil and Coolant Circulating Heating System. Model - OCSM Oil and Coolant Circulating Heating System Model - OCSM Installation & Operation Manual 216280-000 REV 2 Identifying Your System The HOTSTART heating system is designed to heat fluids for use in marine

More information

AUTOMATIC FUEL OIL TRANSFER PUMP SET

AUTOMATIC FUEL OIL TRANSFER PUMP SET AUTOMATIC TRANSFER PUMP SET The Automatic Fuel Oil Transfer Pump Set is a state-ofthe-art duplex pump sequencing and monitoring system. This system includes automatic lag pump backup features that improve

More information

C. Burner management system to follow requirements of Industrial Risk Insurers (IRI).

C. Burner management system to follow requirements of Industrial Risk Insurers (IRI). SECTION 23 52 30 PART 1 - GENERAL 1.01 RELATED WORK A. Section 23 05 00: Common Work Results for HVAC B. Section 23 25 00: Chemical Water Treatment C. Section 23 51 23: Flue Piping 1.02 QUALITY ASSURANCE

More information

DESIGN STANDARDS SECTION 23 60 00

DESIGN STANDARDS SECTION 23 60 00 PART 1 - GENERAL 1.01 Work included: A. Piping, tubing and fittings. B. Piping specialties. C. Special duty valves. D. Refrigerants. E. Chillers. F. Refrigerant monitors. 1.02 General requirements: A.

More information

Model 222S (Galvanized receiver optional) AURORA. 220 Series SINGLE STAGE CONDENSATE AND BOILER FEED PUMPS

Model 222S (Galvanized receiver optional) AURORA. 220 Series SINGLE STAGE CONDENSATE AND BOILER FEED PUMPS Model 222S (Galvanized receiver optional) AURORA 220 Series SINGLE STAGE CONDENSATE AND BOILER FEED PUMPS WWW.AURORAPUMP.COM AURORA 220 Series Single Stage Condensate and Boiler Feed Pumps 2 Introduction

More information

NFPA and Beyond

NFPA and Beyond NFPA 20 2016 and Beyond Gayle Pennel, P.E. - Aon Fire Protection Engineering Aon Fire Protection Engineering Corporation NFPA 20-2016 Major Changes Automatic Supervision of Pressure Transducers Connectivity

More information

SECTION 23 64 10 AIR COOLED WATER CHILLERS

SECTION 23 64 10 AIR COOLED WATER CHILLERS PART 1 GENERAL 1.1 SECTION INCLUDES A. Chiller package B. Charge of refrigerant and oil C. Controls and control connections D. Chilled water connections E. Starters F. Electrical power connections 1.2

More information

D. Open hydronic systems, including [condenser] [fluid-cooler spray] water, shall have the following water qualities:

D. Open hydronic systems, including [condenser] [fluid-cooler spray] water, shall have the following water qualities: SECTION 232500 - PART 1 - GENERAL 1.1 SUMMARY A. This Section includes the following HVAC water-treatment systems: 1. Open Loop Chemical Treatment Systems. 2. Closed Loop Chemical Treatment Systems. 3.

More information

National Competency Based Skill Training Refrigeration and Air-conditioning Mechanic Logbook

National Competency Based Skill Training Refrigeration and Air-conditioning Mechanic Logbook National Competency Based Skill Training Refrigeration and Air-conditioning Mechanic Logbook Trainee:... Training Provider:... Year:... Trainee Contact no:... Competency Based Skill Training Logbook Introduction

More information

SECTION 23 81 43 HEAT PUMPS

SECTION 23 81 43 HEAT PUMPS SECTION 23 81 43 HEAT PUMPS PART 1 GENERAL 1.1 SUMMARY A. Section Includes: 1. Packaged rooftop heat pumps. 1.2 REFERENCES A. American Society of Heating, Refrigerating and Air-Conditioning Engineers:

More information

26 3213.13 Diesel Engine Driven Generators Page 1 of 6

26 3213.13 Diesel Engine Driven Generators Page 1 of 6 Last Update: December 8, 2014 A. Description of System Consultant s Handbook Page 1 of 6 1. Provide a diesel engine driven electric generating unit, factory assembled, tested and certified to operate at

More information

Nortrax 23 52 23 190 David Manchester Road, Ottawa FAN ASSISTED COPPER TUBE BOILERS 21 May 2014 Project: 13-104-070 PART 1 - GENERAL...

Nortrax 23 52 23 190 David Manchester Road, Ottawa FAN ASSISTED COPPER TUBE BOILERS 21 May 2014 Project: 13-104-070 PART 1 - GENERAL... 21 May 2014 PART 1 - GENERAL... 1 1.1. WORK INCLUDED... 1 1.2. QUALITY ASSURANCE... 1 1.3. APPROVALS... 1 PART 2 - PRODUCTS... 1 2.1. HEATING BOILERS... 1 2.2. BOILER SEQUENCE CONTROL... Error! Bookmark

More information

1.02 Scope of Work A. Provide a complete fire pump system as defined by the latest edition of NFPA 20

1.02 Scope of Work A. Provide a complete fire pump system as defined by the latest edition of NFPA 20 PART 1 GENERAL 1.01 Scope of Standard A. This standard provides general requirements of The Sam Houston State University for fire pumps. This document is not intended to serve as a guide specification.

More information

3. Central control and monitoring system. 4. Water based fire suppression systems. C. Reference Standards (Utilize latest editions available):

3. Central control and monitoring system. 4. Water based fire suppression systems. C. Reference Standards (Utilize latest editions available): PART 1 GENERAL 1.01 Scope of Standard A. This standard provides general requirements of The University of Texas at Austin for fire pumps. This document is not intended to serve as a guide specification.

More information

Atlas Copco Oil-free Scroll Compressors. SF 1-15 1.5-15 kw/2-20 hp

Atlas Copco Oil-free Scroll Compressors. SF 1-15 1.5-15 kw/2-20 hp Atlas Copco Oil-free Scroll Compressors SF -.- kw/-0 hp Total capability, total responsibility Right at the heart of your business, Atlas Copco delivers quality compressed air for superior operational

More information

NFPA31FuelOilPiping 1 Revised 3-1-11

NFPA31FuelOilPiping 1 Revised 3-1-11 NFPA 31 Fuel Oil Piping, Installation and Testing Chapter 8 Fuel Piping Systems and Components 8.1 Scope. This chapter shall apply to piping systems and their components used to transfer fuel oil from

More information

FAIRBANKS NIJHUIS FIRE PUMPS. www.fairbanksnijhuis.com

FAIRBANKS NIJHUIS FIRE PUMPS. www.fairbanksnijhuis.com FAIRBANKS NIJHUIS FIRE PUMPS www.fairbanksnijhuis.com FAIRBANKS NIJHUIS Long established as a leading fire pump manufacturer, Fairbanks Nijhuis offers a broad range of horizontal and vertical split case,

More information

A. Accessible Fixture: Emergency plumbing fixture that can be approached, entered, and used by people with disabilities.

A. Accessible Fixture: Emergency plumbing fixture that can be approached, entered, and used by people with disabilities. SECTION 224500 - EMERGENCY PLUMBING FIXTURES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

TABLE OF CONTENTS. SECTION 1 General Information: Pg 2 Description of Operation

TABLE OF CONTENTS. SECTION 1 General Information: Pg 2 Description of Operation GTRDD SERIES HEATLESS DRYER INSTALLATION, OPERATION & MAINTENANCE MANUAL TABLE OF CONTENTS SECTION 1 General Information: Pg 2 Description of Operation SECTION 2 Safety Instructions: Pg 3 Installation

More information

MEDICAL AIR STATIONS FOR MEDICAL GAS PIPING SYSTEM. Key features: NOVAIR quality and service: www.novairmedical.com

MEDICAL AIR STATIONS FOR MEDICAL GAS PIPING SYSTEM. Key features: NOVAIR quality and service: www.novairmedical.com MEDICAL AIR STATIONS FOR MEDICAL GAS PIPING SYSTEM Designed for centralized medical air production in hospitals and clinics, NOVAIR medical air stations ensure the continuous supply of the medical gas

More information

HYDRYER TYPE P Heat Regenerative Dryers ISO 9001 CERTIFIED

HYDRYER TYPE P Heat Regenerative Dryers ISO 9001 CERTIFIED HYDRYER TYPE P Heat Regenerative Dryers ISO 9001 CERTIFIED General Air Type P Hydryer Heat Regenerative Systems Introduction General Air Type P Hydryers are electric heat regenerative dryers, designed

More information

MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION

MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION Fire Pump Plan Review 2009 International Fire Code and NFPA 20 Date of Review / / BLD201 - Project Address: Project Name: Contractor s Business

More information

SECTION 23 05 12 GENERAL PROVISIONS FOR HVAC WORK

SECTION 23 05 12 GENERAL PROVISIONS FOR HVAC WORK SECTION 23 05 12 GENERAL PROVISIONS FOR HVAC WORK 1 GENERAL 1.1 GENERAL REQUIREMENTS A. This Section is coordinated with and complementary to the General Conditions and Supplementary General Conditions

More information

Fire Pump Plan Review March 2010

Fire Pump Plan Review March 2010 Fire Pump Plan Review March 2010 Date of Review: / / Permit Number: Business/Building Name: Address of Project: Designer Name: Designer s Phone: Contractor: Contractor s Phone: Occupancy Classification:

More information

ECOCIAT. Domestic hot water heat recovery unit

ECOCIAT. Domestic hot water heat recovery unit Heat recovery unit Domestic hot water High energy efficiency with R410A Compact and quiet Scroll compressors Brazed-plate heat exchangers Heating Heat recovery ENVIRONMENTALLY HFC R410A PROTECTION DE FRIENDLY

More information

5.23.22 STEAM AND CONDENSATE PIPING AND PUMPS DESIGN AND CONSTRUCTION STANDARD PART 1: GENERAL. 1.01 Purpose:

5.23.22 STEAM AND CONDENSATE PIPING AND PUMPS DESIGN AND CONSTRUCTION STANDARD PART 1: GENERAL. 1.01 Purpose: PART 1: GENERAL 1.01 Purpose: A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design. The responsibility of the engineer is

More information

A. Section includes air conditioning units, controls and control panels.

A. Section includes air conditioning units, controls and control panels. SECTION 23 81 23 - COMPUTER-ROOM AIR-CONDITIONERS PART 1 - GENERAL 1.1 SUMMARY A. Section includes air conditioning units, controls and control panels. 1.2 REFERENCES A. Air-Conditioning, Heating, and

More information

FOAM SYSTEM SPECIFICATION

FOAM SYSTEM SPECIFICATION FOAM SYSTEM SPECIFICATION WET PIPE AFFF SPRINKLER SYSTEM The sprinkler system shall be a closed-head wet pipe AFFF foam water sprinkler system designed to provide adequately proportioned foam water solution

More information

Heating, Ventilation, Air Conditioning and Refrigeration (HVACR)

Heating, Ventilation, Air Conditioning and Refrigeration (HVACR) Heating, Ventilation, Air Conditioning and Refrigeration (HVACR) I. Demonstrate safety skills in typical HVACR work situations to NATE Core Installer Knowledge Areas for Technician Excellence for Safety

More information

Commercial Gas Furnace Upflow

Commercial Gas Furnace Upflow Commercial Gas Furnace Upflow Model G24-200 80% A.F.U.E. 200,000 Btuh Input Heating Cap. 7.5 or 10 Tons Nominal Add-On Cooling GUK FEATURES Certified by A.G.A./C.G.A. Laboratories. Heavy gauge painted

More information

All work must conform to the National Electric Code, latest edition, and all other applicable codes and regulations.

All work must conform to the National Electric Code, latest edition, and all other applicable codes and regulations. DIVISION 16 ELECTRICAL SECTION 16100 - ELECTRICAL PART 1 - GENERAL SCOPE All electrical work as shown on the drawings and as necessary to provide a complete electrical system. Include primary service,

More information

REFRIGERATED TYPE COMPRESSED AIR DRYERS INSTRUCTION MANUAL. For Sales & Service please contact:

REFRIGERATED TYPE COMPRESSED AIR DRYERS INSTRUCTION MANUAL. For Sales & Service please contact: 7610.478.16 8/99 INSTRUCTION MANUAL Models 8005, 8010, 8015 For Sales & Service please contact: CENTRAIR Air Systems & Supplies Phone: 705-722-5747 Fax: 705-722-5458 Email: sales@centrair.ca Website: www.centrair.ca

More information

Ingersoll Rand Providing Customer-Driven Air System Solutions for More Than 100 Years

Ingersoll Rand Providing Customer-Driven Air System Solutions for More Than 100 Years Ingersoll Rand Type-30 Air Ingersoll Rand Providing Customer-Driven Air System Solutions for More Than 100 Years Back then, we called it serving the customer. Today, we call it Solutionizing because your

More information

A. Accessible Fixture: Emergency plumbing fixture that can be approached, entered, and used by people with disabilities.

A. Accessible Fixture: Emergency plumbing fixture that can be approached, entered, and used by people with disabilities. SECTION 22 45 00 - (ADD#2) PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

Design & Construction Standards, Revised January 2013 5.21.30-1

Design & Construction Standards, Revised January 2013 5.21.30-1 PART 1 GENERAL 1.01 Scope of Standard A. This standard provides general requirements of The University of Texas at Austin for fire pumps. This document is not intended to serve as a guide specification.

More information

FORM FOR INSPECTION, TESTING AND MAINTENANCE OF FIRE PUMPS DIESEL

FORM FOR INSPECTION, TESTING AND MAINTENANCE OF FIRE PUMPS DIESEL Information on this form covers the minimum requirements of NFPA 25-1998 for centrifugal fire pumps. This form does not relieve the owner of the responsibility of complying with the other requirements

More information

BLADDER SURGE CONTROL SYSTEM

BLADDER SURGE CONTROL SYSTEM PART I GENERAL 1.01 Description BLADDER SURGE CONTROL SYSTEM This specification describes the requirements for a Bladder Surge Control System. The purpose of the system is to minimize transient pressures

More information

ELECTRIC/DIESEL FIRE PUMP CHECK LIST

ELECTRIC/DIESEL FIRE PUMP CHECK LIST BUILDING NAME: DESIGNER: SCO REPRESENTATIVE: PUMP MANUF.: LOCATION: INSTALLER: DATE: OWNER NAME: INSTALLATION Certificate for flushing and hydrostatic test furnished Piping been hydrostatically tested

More information

Pipeline. Medical Gas Pipeline Products

Pipeline. Medical Gas Pipeline Products Pipeline Medical Gas Pipeline Products w w w. a m i c o. c o m The Amico Group Manufactures the Building Blocks of the Hospital Architectural Beds Lights Interiors Accessories Patient Care Diagnostic OR

More information

The city of Milwaukee s Sample Preventative maintenance manual for Electronically monitored boilers

The city of Milwaukee s Sample Preventative maintenance manual for Electronically monitored boilers The city of Milwaukee s Sample Preventative maintenance manual for Electronically monitored boilers Table of Contents Introduction... 1 Intention... 2 Authority and responsibility letter... 3 Organizational

More information

2010 Residential Water Heater Replacement Check List

2010 Residential Water Heater Replacement Check List 2010 Residential Water Heater Replacement Check List The intent of this check list is to provide installers a general reference for the enforcement of code requirements in the Greater San Diego Area. This

More information

CPX/HT Series. REFRIGERATED AND HIGH TEMPERATURE DRYER 12 to 2400 CFM. High-performance products. Designed for you!

CPX/HT Series. REFRIGERATED AND HIGH TEMPERATURE DRYER 12 to 2400 CFM. High-performance products. Designed for you! CPX/HT Series REFRIGERATED AND HIGH TEMPERATURE DRYER 12 to 2400 CFM High-performance products. Designed for you! COMPRESSED AIR WATER CONTAMINATION Atmospheric air contains water in vapor form in different

More information

ENDURAIR BASE-MOUNTED & TANK MOUNTED COMPRESSOR

ENDURAIR BASE-MOUNTED & TANK MOUNTED COMPRESSOR GARDNER DENVER 13-19-504 Version: 02 February 7, 2007 ENDURAIR BASE-MOUNTED & TANK MOUNTED COMPRESSOR MODELS ELC99A 20 HP PARTS LIST MAINTAIN COMPRESSOR RELIABILITY AND PERFORMANCE WITH GENUINE GARDNER

More information

TABLE 1. Rugged cast aluminum alloy casing,celcon waterways with nichrome parts White (unless stainless steel housing)

TABLE 1. Rugged cast aluminum alloy casing,celcon waterways with nichrome parts White (unless stainless steel housing) CHRONOMITE INSTANT-FLOW MICRO WATER HEATER INSTALLATION AND OPERATION INSTRUCTIONS - (LOW FLOW MODELS) (Before installation, compare electrical needed for the model of heater selected) TABLE 1 Model No.

More information

Arapahoe County Residential Water Heater Installation and Inspection Guide

Arapahoe County Residential Water Heater Installation and Inspection Guide Arapahoe County Residential Water Heater Installation and Inspection Guide The attached handout is designed to be a general permit submittal and inspection guide covering most installation instances, however

More information

14. Troubleshooting Guide

14. Troubleshooting Guide 14. Guide 14.1 Refrigeration Cycle System In order to diagnose malfunctions, ensure the air conditioner is free from electrical problems before inspecting the refrigeration cycle. Such problems include

More information

Recommended Product Specifications Fuel Day Tank System Tramont UTRS Fuel Day Tank

Recommended Product Specifications Fuel Day Tank System Tramont UTRS Fuel Day Tank Recommended Product Specifications Fuel Day Tank System Tramont UTRS Fuel Day Tank This specification describes requirements for a Diesel Fuel Day Tank System consisting of one or more fuel tanks, an Electronic

More information

CHAPTER 10 BOILERS, WATER HEATERS AND PRESSURE VESSELS

CHAPTER 10 BOILERS, WATER HEATERS AND PRESSURE VESSELS CHAPTER 10 BOILERS, WATER HEATERS AND PRESSURE VESSELS SECTION 1001 GENERAL 1001.1 Scope. This chapter shall govern the installation, alteration and repair of boilers, water heaters and pressure vessels.

More information

Element D Services Heating, Ventilating, and Air Conditioning

Element D Services Heating, Ventilating, and Air Conditioning PART 1 - GENERAL 1.01 OVERVIEW A. This section supplements Design Guideline Element D3041 on air handling distribution with specific criteria for projects involving design of a Data Center spaces B. Refer

More information

A. Accessible Fixture: Emergency plumbing fixture that can be approached, entered, and used by people with disabilities.

A. Accessible Fixture: Emergency plumbing fixture that can be approached, entered, and used by people with disabilities. SECTION 224500 - EMERGENCY PLUMBING FIXTURES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

Element D Services Plumbing

Element D Services Plumbing PART 1 - GENERAL 1.01 OVERVIEW A. This section addresses domestic cold, hot and hot water return distribution systems within and to five feet beyond building perimeter. PART 2 - DESIGN CRITERIA 2.01 GENERAL

More information

SECTION 15732 AIR CONDITIONING UNIT

SECTION 15732 AIR CONDITIONING UNIT SECTION 15732 AIR CONDITIONING UNIT PART 1 GENERAL 1.01 SUMMARY A. Section includes: 1. Packaged, split system air conditioning unit No. 1. 1.02 REFERENCES A. Air-Conditioning, Heating, and Refrigeration

More information

INDUSTRIAL DIRECT DRIVEN PISTON COMPRESSORS CL - CH - CK

INDUSTRIAL DIRECT DRIVEN PISTON COMPRESSORS CL - CH - CK INDUSTRIAL DIRECT DRIVEN PISTON COMPRESSORS CL - CH - CK CL - CH - CK Direct driven solution for industry Proven technology, solid construction The CL - CH - CK units are directly driven air-cooled, single

More information

Pump Specifications 250 Series Submersible Sump / Effluent Pump 2 Solids handling

Pump Specifications 250 Series Submersible Sump / Effluent Pump 2 Solids handling Pump Specifications 250 Series Submersible Sump / Effluent Pump 2 Solids handling 250_P1 R10/7/2015 Copyright 2015 Liberty Pumps Inc. All rights reserved. Specifications subject to change without notice.

More information

BERMAD Fire Protection

BERMAD Fire Protection 400E-2M/700E-2M IOM Bermad Electrically Controlled Deluge Valve with EasyLock Manual Reset Model: 400E-2M/700E-2M INSTALLATION OPERATION MAINTENANCE Application Engineering BERMAD 400E-2M/700E-2M Bermad

More information

RECOMMENDED INSTALLATION & MAINTENANCE

RECOMMENDED INSTALLATION & MAINTENANCE FOR NEW OR REPLACEMENT SEWAGE PUMPS RECOMMENDED INSTALLATION & MAINTENANCE AB SUMP & SEWAGE PUMP MANUFACTURERS ASSOCIATION P.O. BOX 647 NORTHBROOK, IL 60065-0647 The materials contained in this document

More information

CONSTRUCTION STANDARD SPECIFICATION SECTION FM-200 CLEAN-AGENT EXTINGUISHING SYSTEM

CONSTRUCTION STANDARD SPECIFICATION SECTION FM-200 CLEAN-AGENT EXTINGUISHING SYSTEM Septmber 16, 2009 CONSTRUCTION STANDARD SPECIFICATION SECTION 13967 Page PART 1 - GENERAL 2 1.01 Summary...2 1.02 References...3 1.03 System Description...3 1.04 Submittals...4 1.05 Quality Assurance...6

More information

CEILING CASSETTE FAN COIL UNIT

CEILING CASSETTE FAN COIL UNIT CEILING CASSETTE FAN COIL UNIT Operation and Installation Manual MHCFC4W-04, 08, 12, 16 Four way ceiling cassette fan coil unit Please read this manual before using the fan coil unit. Installation and

More information

Evaluate, Clean, and Tune Guidance

Evaluate, Clean, and Tune Guidance Evaluate, Clean, and Tune Guidance The Evaluate, Clean and Tune (ECT) process serves three essential purposes in the Weatherization Assistance Program (WAP). The first is to evaluate the existing system

More information

AFHX Guide Specifications

AFHX Guide Specifications AFHX Guide Specifications Part 1: General 1.01 Work Included A. Provide a complete Air Cooled Packaged Chiller utilizing rotary screw compressors suitable for outdoor installation and be controlled by

More information

Compressor Service & Maintenance Manual

Compressor Service & Maintenance Manual Compressor Service & Maintenance Manual C Series COMPRESSOR (D)C1103 (D)C1203 (D)C2106 (D)C2206 (D)C3210 Copyright 2006 DCI. All Rights Reserved. 92311, Rev. C, 08/13 1 C1000 Series Service & Maintenance

More information

PC1131 Electric Air Compressor

PC1131 Electric Air Compressor Senco Products Inc. 8485 Broadwell Road Cincinnati, Ohio 45244 PC1131 Electric Air Compressor Operating Instructions 2006 by Senco Products, Inc. Warnings for the safe use of this tool are included in

More information

FLASH TANK ECONOMIZER PRODUCT GUIDE

FLASH TANK ECONOMIZER PRODUCT GUIDE FLASH TANK ECONOMIZER PRODUCT GUIDE Overview A flash tank is used to recover blowdown energy in the form of flash steam and blowdown. This can only be used with a deaerator or some other pressurized device.

More information

EnviroAire Series. 15kW 110kW Oil-Less Rotary Screw Compressors ILLESS

EnviroAire Series. 15kW 110kW Oil-Less Rotary Screw Compressors ILLESS EnviroAire Series 15kW 110kW Oil-Less Rotary Screw Compressors ILLESS 2 Gardner Denver Oil-Less Rotary Screw Compressors A Diverse Range of Industries Industries, both large and small, rely on Gardner

More information

INSTALLATION AND OPERATION INSTRUCTIONS - (LOW FLOW MODELS) (Before installation, compare electrical needed for the model of heater selected)

INSTALLATION AND OPERATION INSTRUCTIONS - (LOW FLOW MODELS) (Before installation, compare electrical needed for the model of heater selected) CHRONOMITE INSTANT-FLOW WATER HEATER INSTALLATION AND OPERATION INSTRUCTIONS - (LOW FLOW MODELS) (Before installation, compare electrical needed for the model of heater selected) TABLE 1 Model No. Wattage

More information

CARING FOR YOUR WATER HEATER

CARING FOR YOUR WATER HEATER http://waterheatertimer.org/troubleshoot-rheem-tankless-water-heater.html Water Heater Inspections CARING FOR YOUR WATER HEATER Venting System (Direct Vent Only) The venting system should be inspected

More information

FIRING RANGE PHASE 1 DESIGN 224500-1

FIRING RANGE PHASE 1 DESIGN 224500-1 FIRING RANGE PHASE 1 DESIGN 224500-1 SECTION 224500 - PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

Health Choice Enterprises ASSE Medical Gas Course

Health Choice Enterprises ASSE Medical Gas Course Course Description This course is divided into the following Two Sections The main focus of this 32 hour Medical Gas Course is to provide training and testing regarding the operation, application and code

More information

Attachment J-C18.1. HVAC Work Instructions

Attachment J-C18.1. HVAC Work Instructions . RFP: Attachment J-C18.1 HVAC Work Instructions NNC13ZFD017J SOW Item No. Title Page C18-02 Control Air Systems Annual PM 2 C18-03 Split System AC Indoor Section Annual PM 3 C18-04 Condensing Unit Semi-Annual

More information

1. Conductivity < 15 micro ohms/cm 2. ph of 6.0 to 9.0 3. Nonvolatile TOC content < 1.0 ppm

1. Conductivity < 15 micro ohms/cm 2. ph of 6.0 to 9.0 3. Nonvolatile TOC content < 1.0 ppm PART 1: GENERAL 1.01 Purpose: A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design. The responsibility of the engineer is

More information

Maintenance. Recommended minimum maintenance

Maintenance. Recommended minimum maintenance Maintenance Diamond High Efficiency Filter Systems are designed for low maintenance. The following maintenance procedures outline recommended minimum frequency to help ensure continued trouble-free operation

More information

LOADING DOCK EQUIPMENT. A. Section 03100 - Concrete Forms and Accessories: Placement of anchors into concrete.

LOADING DOCK EQUIPMENT. A. Section 03100 - Concrete Forms and Accessories: Placement of anchors into concrete. LOADING DOCK EQUIPMENT PART 1 GENERAL 1.1 SECTION INCLUDES A. Loading dock equipment of the following types: 1. Dock lifts. 2. Control stations. 1.2 RELATED SECTIONS A. Section 03100 - Concrete Forms and

More information

SECTION 23 34 13. A. Horsepower: Do not increase or decrease fan motor horsepower without written approval from Engineer.

SECTION 23 34 13. A. Horsepower: Do not increase or decrease fan motor horsepower without written approval from Engineer. PART 1 GENERAL SECTION 23 34 13 HVAC FANS 1.01 SUMMARY A. Section Includes: 1. Exhaust fans. 2. Transfer fans. B. Related Documents: 1. Drawings and general provisions of the Contract, including General

More information

ice 3 FLUID TO FLUID HEAT PUMP

ice 3 FLUID TO FLUID HEAT PUMP ice 3 FLUID TO FLUID HEAT PUMP SUBMITTAL DATA (888) 530-7713 P O Box 5, Wentworth, H 03282 Rev.3 (5-30-14) ice 3, IC-2040 Fluid-to-Fluid R-410a Heat Pump Engineering Guide Specifications General otes:

More information

REMOVAL AND INSTALLATION

REMOVAL AND INSTALLATION 303-01C-1 REMOVAL AND INSTALLATION Engine Body On Special Tool(s) Adapter For 303-D043 303-D043-02 or equivalent Special Tool(s) 303-01C-1 Turbocharger Lifting Bracket 303-1266 Wrench, Fan Clutch Nut 303-214

More information

SECTION 7: MAINTENANCE

SECTION 7: MAINTENANCE 125/160/185 UD SULLAIR POWERTECH SECTION 7 7.1 GENERAL A good maintenance program is the key to long compressor life. Below is a program that when adhered to, should keep the compressor in top operating

More information

DESCRIPTION. Refer to Figure 2 below. 1. The low pressure compressor stage (A) compresses the air to about 43.5 psi (3 Bar[g]).

DESCRIPTION. Refer to Figure 2 below. 1. The low pressure compressor stage (A) compresses the air to about 43.5 psi (3 Bar[g]). DESCRIPTION The N 2 Nitrogen Generator is designed for use on tap changers, breakers, main tanks or any other electrical device requiring a gas blanketed enclosure. The unit produces nitrogen by separating

More information

Why and How we Use Capacity Control

Why and How we Use Capacity Control Why and How we Use Capacity Control On refrigeration and air conditioning applications where the load may vary over a wide range, due to lighting, occupancy, product loading, ambient weather variations,

More information

PC1130 Electric Air Compressor

PC1130 Electric Air Compressor Senco Products Inc. 8485 Broadwell Road Cincinnati, Ohio 45244 PC1130 Electric Air Compressor Operating Instructions 2006 by Senco Products, Inc. Warnings for the safe use of this tool are included in

More information

RP OIL PUMP AND MOTOR SET

RP OIL PUMP AND MOTOR SET INSTRUCTIONS RP OIL PUMP AND MOTOR SET Fig. 1 Typical RP Pump Set WARNING These instructions are intended for use only by experienced, qualified combustion start-up personnel. Adjustment of this equipment

More information

Service manual. Website: www.andico.com.au CAUTION - BEFORE SERVICING THE UNIT, READ THE SAFETY - PRECAUTIONS IN THIS MANUAL.

Service manual. Website: www.andico.com.au CAUTION - BEFORE SERVICING THE UNIT, READ THE SAFETY - PRECAUTIONS IN THIS MANUAL. Website: www.andico.com.au Service manual CAUTION - BEFORE SERVICING THE UNIT, READ THE SAFETY - PRECAUTIONS IN THIS MANUAL. - ONLY FOR AUTHORISED SERVICE PERSONNEL. MODELS: MPK1-09CR-QB8 MPK1-12ER-QB6

More information

The Breather Box. High Performance Grade-D Breathing Air Filtration system. BB50-cO

The Breather Box. High Performance Grade-D Breathing Air Filtration system. BB50-cO The Breather Box High Performance Grade-D Breathing Air Filtration system Specifications Filter change Indicators Incoming Air Plug 1/2 Industrial Interchange 2 Automatic Drains with Discharge tubes 3

More information

Request for Proposal (RFP)

Request for Proposal (RFP) =============================================================== Request for Proposal (RFP) CBDHA12-0039 Glace Bay General Hospital Medical Vacuum System Issued Dec. 24, 2012 CLOSING Friday, Jan. 18, 2013

More information