Overcurrent and Ground Fault Protection
|
|
- Abraham Tyler
- 7 years ago
- Views:
Transcription
1 Over and Ground Fault Protection Announcement: You are not supposed to prepare a pre-report. But there will be an oral examination, so you are strongly advised to study this note regarding to the pre-study questions below. After the lab, you will need to deliver a post-report which contains what you have done in the lab, data, related graphs and answers of the questions. Pre-Study Questions 1. Why do we use relays in the power systems? 2. What are the ANSI/IEEE codes of over relays? 3. What type of relay is over relay? 4. What is pick-up? How can it be selected regarding to fault and load? 5. How many types of over relays are there? 6. What are the differences between the types of over relays? 7. What is the purpose of using time delay in the over relays? 8. What are the types of inverse time over relay? 9. What is meant by time dial setting? 10. How the directionality of flow can be found in a power system? 11. Which types of over relays can be used for ground fault protection? 12. What are the meanings of DMT and IDMT? 1. Objective To study the principles of over and ground fault protection. 2. Theory [1, 2] Relays are used to detect abnormal conditions in the power systems. After detection of a fault, relays close circuit breakers and disconnect faulty circuits from the general supply system in order to minimize the damage. There is a list of ANSI/IEEE codes of different types of protection relays as follows [3, 4]: ANSI /IEEE Standard Device Numbers 2 - Time Delay Starting or Closing Relay 67 - AC Directional Over Relay 21 - Distance Relay 68 - Blocking or out of step Relay 25 - Synchronizing or Synchronism-Check Device 69 - Permissive Control Device 27 - Undervoltage Relay 74 - Alarm Relay 30 - Annunciator Relay 76 - DC Over Relay 32 - Directional Power Relay 78 - Phase-Angle Measuring Relay 37 - Under or Underpower Relay 79 - AC-Reclosing Relay 38 - Bearing Protective Device 81 - Frequency Relay 40 Field (over/under excitation) Relay 85 Pliot Comm., Carrier or Pilot-Wire Relay 46 Rev. phase or Phase-Bal. Current Relay 86 - Lockout Relay 47 - Phase-Seq. or Phase-Bal. Voltage Relay 87 - Differential Protective Relay 49 - Machine or Transformer Thermal Relay 94 - Tripping or Trip-Free Relay 50 - Instantaneous Over 51 - AC Time Over Relay B Bus 59 - Overvoltage Relay F - Field 60 - Voltage or Current Balance Relay G Ground or generator 63 - Pressure Switch N Neutral 64 - Ground Detector Relay T Transformer 1
2 2.1. Over Protection Over protection is practical application of magnitude relays since it picks up when the magnitude of exceeds some value (setting value). Over relays can be used to protect practically any power system elements, i.e. transmission lines, transformers, generators, or motors. As an example, a radial transmission line can be used. For a fault within the zone of protection, the fault is smallest at the end of the line and greatest at the relay end. If the minimum fault possible within the zone of protection is greater than the maximum possible load, it would be possible to define the operating principle as follows: fault zone, trip no fault in zone, do not trip. where is the in the relay and is the pickup setting of the relay. should be selected as: A B Ifault Iload max. R A location B (a) (b) Figure 1. Over protection of transmission lines. (a) Radial system protection. (b) Fault magnitude as a function of fault location. There are four types of over relays; instantaneous, definite time, inverse time and directional over relays Instantaneous Over Relays Its operation criterion is only magnitude (without time delay). This type is applied to the outgoing feeders. time no trip trip Ip Figure 2. Characteristic of instantaneous over relays Figure 3. Connection diagram of instantaneous over relays 2
3 Definite Time Over Relays In this type, two conditions must be satisfied for operation (tripping), must exceed the setting value and the fault must be continuous at least a time equal to time setting of the relay. Modern relays may contain more than one stage of protection each stage includes each own and time setting. time T3 T2 T1 I1 I2 I3 Figure 4. Characteristic of definite time over relays Definite time over relay is the most applied type of over. It is used as: 1. Back up protection of distance relay of transmission line with time delay. 2. Back up protection to differential relay of power transformer with time delay. 3. Main protection to outgoing feeders and bus couplers with adjustable time delay setting. Figure 5. Connection diagram of definite time over relay with internal timer Inverse Time Over Relays In this type of relays, operating time is inversely changed with. So, high will operate over relay faster than lower ones. There are standard inverse, very inverse and extremely inverse types. time inverse very inverse extremely inverse Figure 6. Characteristic of inverse time over relays 3
4 The operating time of an over relay can be moved up (made slower) by adjusting the time dial setting. The lowest time dial setting (fastest operating time) is generally 1/2, and the slowest is Operating time in seconds /2 Time dial setting Multiples of pickup setting (I f/i p) Figure 7. A typical commercial time over relay characteristic Directional Over Relays When the power system is not radial (source on one side of the line), an over relay may not be able to provide adequate protection. This type of relay operates in on direction of flow and blocks in the opposite direction. Three conditions must be satisfied for its operation: magnitude, time delay and directionality. The directionality of flow can be identified using voltage as a reference of direction Ground Fault Protection Figure 8. Connection diagram of directional over relay Ground fault s are dependent upon system grounding and they produce zero sequence s whereas there is very little zero-sequence during normal operation. Thus the pick-up settings of the ground fault relays can be made more sensitive than those of phase fault relays. A separate relay responding to the zero sequence is provided for ground fault protection. Types of ground fault relays are similar to over relays but with only one coil for in the case of instantaneous, definite time or inverse time ground fault types. One voltage coil is added in the case of directional ground fault relays. 4
5 There are different connection types of circuits: Current coil may be connected to return path (neutral) of a transformer Current coil may be connected to the secondary side of transformer which is installed at the star point of power transformer Current coil may be connected to secondary side of ring type transformer installed at power cables Figure 9. Ground fault relay connected at the neutral point of transformer Figure 11. Ground fault relay connected to ring type transformer Figure 10. Ground fault relay connected star point of power transformer Figure 12. Connection diagram of directional ground fault relay 3. Practical Information In this lab, the over functions (50, 51) of SIPROTEC Compact 7SJ80 Multifunction Protection Relay will be used. Order number is as follows: 7SJ8031-1EB90-1FC1 Order number includes many information about the relay, such as; housing, binary inputs and outputs, measuring inputs, language settings and its functions. It can be seen in the catalog of the relay[5]. In the relay, three definite time over (DMT) protection elements are available both for the phase and ground elements. The threshold and delay set time can be set. Inverse time over protection characteristics (IDMT) can also be selected and activated. 5
6 4. Procedure You don t need to set up any connection. Only study the connection scheme. In the lab, you will measure several values and related time delays in the context of over protection. 5. Connection Scheme SIPROTEC Compact 7SJ80 -S2 190V AC (L-L) LA N P1 + P1 - A IL1 IL2 IL3 IE F1 F2 F3 F4 F5 F6 F7 F8 Circuit Breaker K1 A1 A2 B01 C9-NO C10-NC C11-COM NC Circuit Breaker CB off KE KE BI1 BI2 NC C3 C4 C5 C S4 24V DC 2L+ 2L- C1(+) PS C2(-) Figure 13. Connection scheme of the test set-up 6
7 6. References 1. Ahmed Safie Eldin, Practical Introduction to Power System Protection and Control, Arun G. Phadke, James S. Thorp, Computer Relaying for Power Systems, John Wiley & Sons, IEEE Standard C : IEEE Standard for Electrical Power System Device Function Numbers, Acronyms, and Contact Designations Catalog of SIPROTEC Compact 7SJ80 Multifunction Protection Relay 6. IEC :2009 : Functional requirements for over/under protection 7. Questions for the Post-Report 1. What do you understand by Primary relay? Secondary relay? Auxiliary relay? 2. What is meant by Pick-up? Drop out? Dropout ratio? 3. What are the equations of IEC normal inverse, very inverse and extremely inverse over relays? 7
TA Kahraman Yumak ELK412 - Distribution of Electrical Energy Lab. Notes v1.0 2013 Spring web.itu.edu.tr/yumakk. Distance Protection
Distance Protection Announcement: You are not supposed to prepare a pre-report. But there will be an oral examination, so you are strongly advised to study this note regarding to the pre-study questions
More informationOVERCURRENT & EARTH FAULT RELAYS. To study the protection of equipment and system by relays in conjunction with switchgear.
OVERCURRENT & EARTH FAULT RELAYS Objective: To study the protection of equipment and system by relays in conjunction with switchgear. Theory: The function of a relay is to detect abnormal conditions in
More informationTransmission Protection Overview
Transmission Protection Overview 2012 Hands-On Relay School Brian Smyth Schweitzer Engineering Laboratories Pullman, WA Transmission Line Protection Objective General knowledge and familiarity with transmission
More information100% Stator Ground Fault Detection Implementation at Hibbard Renewable Energy Center. 598 N. Buth Rd 3215 Arrowhead Rd
100% Stator Ground Fault Detection Implementation at Hibbard Renewable Energy Center Introduction Roger Hedding Steven Schoenherr, P.E. ABB Inc. Minnesota Power 598 N. Buth Rd 3215 Arrowhead Rd Dousman,
More informationEaton s E-Series protective relay family
E-Series protective relays Feeder distribution relays Motor relays Transformer relays Generator relays Eaton s E-Series protective relay family Microprocessor-based design Eaton s E-Series relay family
More informationGenerator Stator Protection, under/over voltage, under /over frequency and unbalanced loading. Ramandeep Kaur Aujla S.NO 250447392
1 Generator Stator Protection, under/over voltage, under /over frequency and unbalanced loading By Ramandeep Kaur Aujla S.NO 250447392 ES 586b: Theory and applications of protective relays Department of
More informationUnified requirements for systems with voltages above 1 kv up to 15 kv
(1991) (Rev.1 May 2001) (Rev.2 July 2003) (Rev.3 Feb 2015) Unified requirements for systems with voltages above 1 kv up to 15 kv 1. General 1.1 Field of application The following requirements apply to
More informationIAV. Time Delay Voltage. For AC and DC circuit applications. GE Multilin 1. Protection and Control. Features and Benefits.
IAV Time Delay Voltage For A and D circuit applications. Features and Benefits Frequency compensation (optional) Target seal-in unit (most units) Instantaneous units (optional) Applications A Generators
More informationThe following table shows approximate percentage wise the
SHORT-CIRCUIT CALCULATION INTRODUCTION Designing an electrical system is easy and simple, if only the normal operation of the network is taken into consideration. However, abnormal conditions which are
More informationHow To Choose A Transformer
Consider open loop MV network as an example source 1 source 2 NC NC NC or NO main MV switchboard A B Detail design of substation NC NC NC NO NC NC switchboard 1 switchboard 2 switchboard 3 MV MV MV LV
More informationGE Protection and Control Business Department. Page 1 Date 5/11/99
GE Protection and Control Business Department Page 1 GE Protection and Control Business Department Proven Overcurrent Protection with Power Management Communication The The Advantages of Microprocessor
More informationINTRODUCTION TO SYSTEM PROTECTION. Hands-On Relay School 2012
INTRODUCTION TO SYSTEM PROTECTION Hands-On Relay School 2012 CONGRATULATIONS On choosing the field of system protection. It is an exciting, challenging profession. System protection has changed considerably
More informationSPECIAL TOPICS ON GROUND FAULT PROTECTION AND PROTECTION COORDINATION IN INDUSTRIAL AND COMMERCIAL POWER SYSTEMS
SPECIAL TOPICS ON GROUND FAULT PROTECTION AND PROTECTION COORDINATION IN INDUSTRIAL AND COMMERCIAL POWER SYSTEMS Claudio S. Mardegan claudio.mardegan@engepower.com www.engepower.com Phone: 55 3579-8777
More informationSUBJECT: How to wire a motor starter Number: AN-MC-004 Date Issued: 2/08/2005 Revision: Original
SUBJECT: How to wire a motor starter Number: AN-MC-004 Date Issued: 2/08/2005 Revision: Original A motor starter is a combination of devices to allow an induction motor to start, run and stop according
More informationDistribution Operations with High-penetration of Beyond the Meter Intermittent Renewables. Bob Yinger Southern California Edison April 15, 2014
1 Distribution Operations with High-penetration of Beyond the Meter Intermittent Renewables Bob Yinger Southern California Edison April 15, 2014 Southern California Edison SCE provides power to: Nearly
More informationE-Series protective relay family
E-Series protective relays Feeder distribution relays Motor relays Transformer relays Generator relays E-Series protective relay family Reliable protection for every application Eaton s E-Series relay
More informationFIT TIER 2 Application
FIT TIER 2 Application Application Information The below information Auto-Fills from your registration information: Building Permit Application Date: Project Completion Date: Name: Address: City: State:
More informationT 3000. Substation Maintenance and Commissioning Test Equipment
T 3000 Substation Maintenance and Commissioning Test Equipment Multi function system for testing substation equipment such as: current, voltage and power transformers, all type of protection relays, energy
More informationGENERATOR DIFFERENTIAL PROTECTION RELAY STABILITY VIS-A -VIS SELECTION OF CTS MR. H. C. MEHTA & MR. JAY MEHTA Power Linker Group Co.
GENERATOR DIFFERENTIAL PROTECTION RELAY STABILITY VIS-A -VIS SELECTION OF CTS MR. H. C. MEHTA & MR. JAY MEHTA Power Linker Group Co., Mumbai ABSTRACT : For generator differential protection, one set of
More informationStep Voltage Regulators
Step Voltage Regulators Don Wareham Field Application Engineer Today s Agenda Introduction Voltage Regulator theory Voltage Regulator application considerations Installation and proper bypassing Wrap-up/questions
More informationSIPROTEC Protection Technology
SIPROTEC Protection Technology The Basis for Highest Availability of Supply Siemens AG 2012. Siemens All rights reserved. AG 2012 Infrastructure and Cities Objectives of this Brochure Objective The following
More informationVOLTAGE REGULATOR AND PARALLEL OPERATION
VOLTAGE REGULATOR AND PARALLEL OPERATION Generator sets are operated in parallel to improve fuel economy and reliability of the power supply. Economy is improved with multiple paralleled generators by
More informationSystem Grounding and Ground-Fault Protection Methods for UPS-Supplied Power Systems
System Grounding and Ground-Fault Protection Methods for -Supplied Power Systems Bill Brown, P.E., Square D Critical Power Competency Center 1. INTRODUCTION The use of solid grounding for -supplied power
More informationLocal Back-up Protection for an Electric Power System
MULTILIN GER-3178 GE Power Management Local Back-up Protection for an Electric Power System LOCAL BACK UP PROTECTION FOR AN ELECTRIC POWER SYSTEM J. BERDY TABLE OF CONTENTS Transmission Line Back-Up Protection...............................................
More informationPilot-wire differential relay for lines with two or more terminals
Pilot-wire differential relay for lines with two or more terminals Page 1 Issued: March 2003 Revision: A Data subject to change without notice Pilot-wire differential relay with RXHL 401 Features Phase
More informationSentron Series Circuit Breakers
Sentron Series Circuit Breakers Siemens Sentron Series circuit breakers are available in nine frame sizes: ED, FD, JD, LD, LMD, MD, ND, PD, and RD. Sentron Series circuit breakers have a wide range of
More informationEVALUATION OF ALTERNATIVE BACKUP PROTECTION SCHEMES ON A 66KV DISTRIBUTION NETWORK
EVALUATION OF ALTERNATIVE BACKUP PROTECTION SCHEMES ON A 66KV DISTRIBUTION NETWORK F. Malone*, P.D. Doyle *ESB International, Ireland fergus.malone@esbi.ie ESB International, Ireland paul.d.doyle@esbi.ie
More informationDigital Energy ITI. Instrument Transformer Basic Technical Information and Application
g Digital Energy ITI Instrument Transformer Basic Technical Information and Application Table of Contents DEFINITIONS AND FUNCTIONS CONSTRUCTION FEATURES MAGNETIC CIRCUITS RATING AND RATIO CURRENT TRANSFORMER
More informationCIRCUIT BREAKER INTERRUPTING CAPACITY AND SHORT-TIME CURRENT RATINGS
CIRCUIT BREAKER INTERRUPTING CAPACITY AND SHORT-TIME CURRENT RATINGS David D. Roybal, P.E. Senior Member, IEEE Eaton Electrical 3697 Mount Diablo Boulevard Lafayette, CA 94549 Abstract Low-voltage circuit
More information..OR How To Protect your 3-Phase Equipment Investment with 3-Phase Monitors from Time Mark...
..OR How To Protect your 3-Phase Equipment Investment with 3-Phase Monitors from Time Mark... TIME MARK CORPORATION 11440 EAST PINE STREET TULSA, OK 74116 USA tel 918 438-1220 fax 918 437-7584 www.time-mark.com
More informationSpeed Control Relays SX2
SX2 File 850 CONENS Description.....................................................Page General Information................................................ 2-3 SX2DV General Information...........................................
More informationMONITORING RELAYS. w VOLTAGE MONITORING RELAY UR5U1011. w SCHRACK-INFO. w TECHNICAL DATA
w VOLTAGE MONITORING RELAY UR5U1011 w SCHRACK-INFO AC/DC voltage monitoring in 1-phase mains Undervoltage monitoring 1 change over contact Width 17.5 mm Installation design w TECHNICAL DATA 502 1. Functions
More informationTABLE OF CONTENTS 1.0 INTRODUCTION... 2 1.1 PURPOSE... 2 1.2 DEVIATION... 2 4.0 INTERTIE PROTECTION REQUIREMENTS... 4
Page: 1 of 14 KEY BULLETIN POINTS: THIS GUIDE OUTLINES MINIMUM REQUIREMENTS FOR CONNECTION OF CUSTOMER-OWNED EMERGENCY AND STANDBY (ESG) TO THE GEORGIA POWER COMPANY (GPC) DISTRIBUTION SYSTEM. THESE ARE
More informationSingle-phase (220...240 V) voltage monitoring: Undervoltage Overvoltage Window mode (overvoltage + undervoltage) Voltage fault memory selectable
Features 70.11 70.31 70.41 Electronic voltage monitoring relays for single and three-phase applications Multifunctional types, providing the flexibility of monitoring Undervoltage, Overvoltage, Window
More informationPermissible ambient temperature Operation Storage, transport
The Sitras PRO combined DC protective unit and controller is used in the power supply for DC railways in mass transit and main-line systems up 3,000 V DC. It protects DC switch gear and contact line systems
More informationGENERATOR START CONTROL MODULE - MINI (2 Wire to 3 Wire)
FEATURES & APPLICATIONS Inexpensive 2 wire to 3 wire start controller for electric start high speed gas generators. Optimized for use with Outback Invertors. Supports three types of 3 wire generator control
More informationThe generation and supply of electricity within the U.K is achieved through the use of a 3-phase system.
Three Phase Electricity Supplies and Systems The generation and supply of electricity within the U.K is achieved through the use of a 3-phase system. This consists of 3 separate phase conductors along
More informationCENTERLINE Motor Control Centers Bulletin 2100 Smoke Detector Unit
Instructions CENTERLINE Motor Control Centers Bulletin 2100 Smoke Detector Unit Catalog Number 2100-SD1 Description The Bulletin 2100 smoke detector unit is a 0.5 space factor unit for use in Bulletin
More informationEarth Fault Detection Basics in Theory
Earth Fault Detection Basics in Theory Author: Dipl.-Ing. Ingo Kühnen Woodward Power Solutions Krefelder Weg 47 47906 Kempen, Germany Kempen, 16.04.2010 Earth_Fault_Detection_20100416.doc page 1 1. Star
More informationTrip circuit supervision relay. Type RXTCS
Trip circuit supervision relay Type RXTCS ABB a global technology leader ABB is a global leader in Power and Automation technologies that enable utility and industry customers to improve performance while
More informationProtection of a Three- Winding Transformer
Protection of a Three- Winding Transformer Three-winding transformer 110 kv/25 kv/10 kv Yyn0d5 25 kv-side: Solidly earthed Protection functions ANSI 87 T - Differential protection ANSI 87 N - Earth-fault
More informationBus differential relay REB 103 3-phase 1MRK 505 007-BEN Page 1 Issued: September 2006 Revision: C Data subject to change without notice
Bus differential REB 103 3-phase Page 1 Issued: September 2006 Revision: C Data subject to change without notice (SE970146) Features Percentage restrained differential for phase-to-phase and phase-to-earth
More informationSECTION 26 29 23 VARIABLE FREQUENCY DRIVES
SECTION 26 29 23 VARIABLE FREQUENCY DRIVES PART 1 GENERAL 1.01 SCOPE A. Furnish and install individual freestanding variable frequency AC drives (VFD) as shown on the Drawings and specified herein. 1.02
More informationChallenges of Protection and Control System Verification on DP3 vessels with Focus on Ride Through Fault and Blackout
Author s Name Name of the Paper Session DYNAMIC POSITIONING CONFERENCE October 15-16, 2013 POWER SESSION Challenges of Protection and Control System Verification on DP3 vessels with Focus on Ride Through
More informationDIMENSIONING OF CURRENT TRANSFORMERS FOR PROTECTON APPLICATION
ÿþ üûúùø öõöôùóùõò CT Dimensioning DIMENSIONING OF CURRENT TRANSFORMERS FOR PROTECTON APPLICATION Application note GER3973 1 CT Dimensioning ÿþ üûúùø öõöôùóùõò GER-3973 Application note ÿþ üûúùø öõöôùóùõò
More informationUL guidelines, chapter 6.2 / 6.3 Motor Branch Circuits acc. to UL
UL guidelines, chapter 6.2 / 6.3 Motor Branch Circuits acc. to UL Definition of Terms / Explanations Overview of Basic Devices Construction Types acc. to UL 508 Self-Protected Combination Motor Controller
More informationABB 1. Three-phase monitoring relay CM-PFS. Data sheet. Features. Approvals. Marks. Order data. Order data - Accessories. Application.
1SR 430 824 F9300 Features Monitoring of three-phase mains for phase sequence and failure Powered by the measuring circuit 2 c/o (SPDT) contacts 1 LED for status indication Approvals R: yellow LED - relay
More informationECE 586b Course Project Report. Auto-Reclosing
ECE 586b Course Project Report Auto-Reclosing Srichand Injeti May 5, 2008 Department Of Electrical and computer Engineering University Of Western Ontario, London Ontario Table of contents 1. Introduction...1
More informationISIO 200. Binary Input/Output (I/O) Terminal with IEC 61850 Interface
ISIO 200 Binary Input/Output (I/O) Terminal with IEC 61850 Interface Compact and Easy ISIO 200 Put your Binary I/Os where you need them ISIO 200 is a simple and versatile binary I/O terminal with IEC 61850
More informationNu-Lec Training Modules
PTCC Controller Nu-Lec Training Modules Product Training Operator Training PTCC The Basics An overview of the construction and physical features of the Pole Top Control Cubicle PTCC Operation and Features
More informationCT Application Guide for the 489 Generator Management Relay
g GE Power Management Technical Notes CT Application Guide for the 489 Generator Management Relay GE Publication No. GET-8402 Copyright 2002 GE Power Management Introduction A protection scheme operates
More informationFundamentals of Power
Fundamentals of Power Fundamentals of Power 2008 American Power Conversion Corporation. All rights reserved. All trademarks provided are the property of their respective owners. Learning Objectives At
More informationBus Protection Considerations for Various Bus Types
Bus Protection Considerations for Various Bus Types Caitlin Martin Bonneville Power Administration Steven Chase, Thanh-Xuan Nguyen, Dereje Jada Hawaz, Jeff Pope, and Casper Labuschagne Schweitzer Engineering
More informationFREJA 300 Relay Testing System
Relay Testing System A Megger Group Company FREJA 300 Relay testing system The FREJA 300 relay testing system is a computer-aided relay testing and simulation system. The weight of FREJA 300 is only 15
More informationCapacitor Protection Relay SPAJ 160 C. Product Guide
Issued: April 1999 Status: Updated Version: C/19.04.2006 Data subject to change without notice Features One-, two- and three-phase overload stage with definite time characteristic One-, two- and three-phase
More informationINSTRUCTIONS FOR MAGNUM DS TRIP UNIT TESTING USING TEST KIT SYLES 140D481G02R, 140D481G02RR, 140D481G03 AND 140D481G04
I.L. 32-693 A INSTRUCTIONS FOR MAGNUM DS TRIP UNIT TESTING USING TEST KIT SYLES 140D481G02R, 140D481G02RR, 140D481G03 AND 140D481G04 DANGER DO NOT ATTEMPT TO INSTALL OR PERFORM MAINTE- NANCE ON EQUIPMENT
More information30 ms High Speed Transfer System (HSTS) Product Description
30 ms High Speed Transfer System (HSTS) Product Description 2 30 ms High Speed Transfer System (HSTS) Product Description Content Page 1 General 5 1.1 Description of the 30 ms high speed transfer system
More informationInductive Sensors Single or Dual Loop Detectors Type LD with teach-in
Inductive Sensors Single or Dual Loop Detectors Type LD with teach-in Single or Dual loop detector Automatically adjustment of detection level Manual sensitivity for compensations of variations Easy installation
More informationGrounding of AC generators and switching the neutral in emergency and standby power systems
Power topic #6006 Part 2 of 2 Technical information from Cummins Power eneration rounding of AC generators and switching the neutral in emergency and standby power systems > White paper By Lawrence A.
More informationMedium voltage circuit breaker
Medium voltage circuit breaker IEC 60 056 and ANSI C37-06 define on one hand the operating conditions, the rated characteristics, the design and the manufacture; and on the other hand the testing, the
More informationElectronic overload relay EF65, EF96 and EF146
Data sheet Electronic overload relay EF65, EF96 and EF146 Electronic overload relays offer reliable protection in case of overload and phase-failure. They are the alternative to thermal overload relays.
More informationTransformerless UPS systems and the 9900 By: John Steele, EIT Engineering Manager
Transformerless UPS systems and the 9900 By: John Steele, EIT Engineering Manager Introduction There is a growing trend in the UPS industry to create a highly efficient, more lightweight and smaller UPS
More informationDRTS 33. The new generation of advanced test equipments for Relays, Energy meters, Transducers and Power quality meters
The new generation of advanced test equipments for Relays, Energy meters, Transducers and Power quality meters Testing all relay technologies: electromechanical, solid state, numerical and IEC61850 Manual
More informationRelion 605 series. Self-powered feeder protection REJ603 Product Guide
Relion 605 series Relion 605 series Relion 605 series Self-powered feeder protection Product Guide Product version: 3.0 Contents 1.... 3 2. Relay functions... 3 3. Protection functions... 4 4. Application...
More informationBoth variants can be used for measuring the positive sequence voltage Up or the negative sequence voltage Un.
Rev. - 2004-10-22 Page 1(5) General RXTBA 1 is a three-phase phase sequence voltage filter built up by resistors and capacitors. The filter is available in two voltage variants; one for rated voltage 3x110
More informationOPTIMIZING POWER SYSTEM PROTECTION FOR MODERN DATA CENTERS
OPTIMIZING POWER SYSTEM PROTECTION FOR MODERN DATA CENTERS Data center power systems are constructed with a premium on reliability at a significant cost. The return on this investment is realized if it
More informationRM17TE 183...528 V AC. Main. Product or component type. Product specific application. Relay monitored parameters 250 V DC 5 A DC
Characteristics multifunction control relay RM17-TE - range 183..528 V AC Complementary Reset time Maximum switching voltage Minimum switching current Maximum switching current [Us] rated supply voltage
More informationIntegration of Distributed Generation in the Power System. IEEE Press Series on Power Engineering
Brochure More information from http://www.researchandmarkets.com/reports/2171489/ Integration of Distributed Generation in the Power System. IEEE Press Series on Power Engineering Description: A forward
More informationThree-phase monitoring relay CM-PFE
Data sheet Three-phase monitoring relay CM-PFE The CM-PFE is a three-phase monitoring relay that monitors the phase parameter phase sequence and phase failure in three-phase mains. 2CDC 251 005 S0012 Characteristics
More informationElectrical auxiliaries 0 For i DPN (DPN), C60 and C120
Circuit protection For i DPN (DPN), C60 and C120 Function They remotely trip or indicate circuit-breakers, with or without Vigi module. Description b They are mounted to the left of the circuit-breaker
More informationSafety technique. Emergency stop module BO 5988 safemaster
Safety technique Emergency stop module BO 5988 safemaster 0221562 Function diagram Pushbutton on Mains or emergencystop () K1 According to EC Directive for machines 98/37/EG According to IEC/E 60204-1
More informationProtection of Phase Angle Regulating Transformers
Protection of Phase Angle Regulating Transformers A report to the Substation Subcommittee of the IEEE Power System Relaying Committee prepared by Working Group K1 IEEE Special Publication Members of the
More informationTransfer Equipment Controls
Control Types Manual Transfer Switches Nonautomatic Transfer Switches Automatic Transfer Switches The type of control system for the transfer switch will vary depending on the type of switching equipment
More informationPrepared By: Sheilani Binti Shaari Department of Electrical Engineering/PKB
Prepared By: Sheilani Binti Shaari Department of Electrical Engineering/ Course Learning Outcome (CLO) Upon completion of this course, students should be able to: Apply the principles of three phase systems,
More informationTest & Data Management Software
Test & Data Management Software TDMS protective relays energy meters transducers power quality CT-VT-PT transformers ground grid circuit breakers batteries surge arresters The Integrated Testing Solution
More informationInverter / Charger Installation General Operations and AC and DC Connections
Inverter / Charger Installation General Operations and AC and DC Connections The Inverter is just one piece. Sometimes, a tendency is to mount the inverter and batteries, and make it work It is better
More informationIndoor coil is too warm in cooling mode or too cold in heating mode. Reversing valve or coil thermistor is faulty
Codes Room Air Conditioner range: Indoor unit alarm s If timer lamp flashes for 1 second on, 1 second off, this indicates pre heating on the coil during heating mode and is not an error. If timer lamp
More information2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV 16346-1. 2a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std.
2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV 16346-1 2a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std. Relays) Part 1 General 1.1 CONDITIONS AND REQUIREMENTS: A. Refer to
More informationNuclear Power Plant Electrical Power Supply System Requirements
1 Nuclear Power Plant Electrical Power Supply System Requirements Željko Jurković, Krško NPP, zeljko.jurkovic@nek.si Abstract Various regulations and standards require from electrical power system of the
More informationProduct Data Bulletin
Product Data Bulletin Power System Harmonics Causes and Effects of Variable Frequency Drives Relative to the IEEE 519-1992 Standard Raleigh, NC, U.S.A. INTRODUCTION This document describes power system
More informationElectrical Shore Connections / Cold Ironing
STANDARD FOR CERTIFICATION No. 2.25 Electrical Shore Connections / Cold Ironing JULY 2014 The electronic pdf version of this document found through http://www.dnv.com is the officially binding version
More informationDC TRANSMISSION BASED ON VOLTAGE SOURCE CONVERTERS
DC TRANSMISSION BASED ON VOLTAGE SOURCE CONVERTERS by Gunnar Asplund, Kjell Eriksson, Hongbo Jiang, Johan Lindberg, Rolf Pålsson, Kjell Svensson ABB Power Systems AB Sweden SUMMARY Voltage Source Converters
More informationElectronic overload relay EF19 and EF45
Data sheet Electronic overload relay EF19 and EF45 Electronic overload relays offer reliable protection in case of overload and phase-failure. They are the alternative to thermal overload relays. Motor
More informationINTRODUCTION TO SYNCHRONIZING AUTOMATIC SYNCHRONIZING CONSIDERATIONS AND APPLICATIONS
INTRODUCTION TO SYNCHRONIZING AUTOMATIC SYNCHRONIZING CONSIDERATIONS AND APPLICATIONS INTRODUCTION It is the intention of this presentation to provide an explanation of the automatic synchronizing process,
More informationSubmit shop drawings for equipment provided under this section Shop drawings shall indicate:
Section 16435 - SWITCHBOARDS Introduction Part 1 - General Reference The work under this section is subject to requirements of the Contract Documents including the General Conditions, Supplementary Conditions,
More informationELR: ABB range of front panel residual current relays Protection device according to IEC/EN 60947-2 Annex M
ELR: ABB range of front panel residual current relays Protection device according to IEC/EN 60947-2 Annex M Tested, certified, reliable Network monitoring and protection The electronic residual current
More informationLab 8: DC generators: shunt, series, and compounded.
Lab 8: DC generators: shunt, series, and compounded. Objective: to study the properties of DC generators under no-load and full-load conditions; to learn how to connect these generators; to obtain their
More informationData Sheet. Electro-mechanical counters Hengstler 800 series
Data Pack D Issued March 00 504897 Data Sheet Electro-mechanical counters Hengstler 800 series The 800 series totalising and predetermining batch counters, manufactured by Hengstler, is available from
More informationThe electrical energy produced at the gen
300 300 Principles of Power System CHAPTER CHAPTER 12 Distribution Systems General 12.1 Distribution System 12.2 Classification of Distribution Systems 12.3 A.C. Distribution 12.4 D.C. Distribution 12.5
More informationACS-30-EU-EMDR-10-MOD
Multi-application heat tracing Control and Monitoring in commercial and residential buildings Roof & Gutter de-icing sensor module Technical Information Approvals Module IP rating Ambient operating temperature
More informationArc Terminator Active Arc-Resistant Switchgear
Arc Terminator Active Arc-Resistant Switchgear Increasing safety and productivity by extinguishing internal arcing faults within the switchgear. The Square D Arc Terminator from Schneider Electric offers
More informationNew Supervisory Control and Data Acquisition (SCADA) Based Fault Isolation System for Low Voltage Distribution Systems
International Conference on Computer and Communication Engineering (ICCCE 2010), 11-13 May 2010, Kuala Lumpur, Malaysia New Supervisory Control and Data Acquisition (SCADA) Based Fault Isolation System
More informationWHITE PAPER GROUND FAULT. Lowering the Limits for Ground Fault Detection
WHITE PAPER GROUND FAULT Lowering the Limits for Ground Fault Detection Current flowing to ground has only two paths it can flow to ground through a ground fault, or it can flow to ground through distributed
More informationDISTRIBUTION TRANSFORMER OVERLOAD PROTECTION TRIPPING CIRCUIT
DISTRIBUTION TRANSFORMER OVERLOAD PROTECTION TRIPPING CIRCUIT Dr. Dipesh Patel 1, Jigar Juthani 2, Harsh Parikh 3, Rushit Bhavsar 4, Ujjaval Darbar 5 1 Head of Electrical Department, BITS edu campus, Vadodara
More informationBasics of Electricity
Basics of Electricity Generator Theory PJM State & Member Training Dept. PJM 2014 8/6/2013 Objectives The student will be able to: Describe the process of electromagnetic induction Identify the major components
More informationIntroduction to Paralleling of LTC Transformers by the Circulating Current Method
TAPCHANGER CONTROLS Application Note #11 Introduction to Paralleling of LTC Transformers by the Circulating Current Method 1.0 ABSTRACT This Application Note discusses the elements of paralleling load
More informationVEO. V4PF480Y/277VSYTK02 Art.Nr.: 2104200. V4PF480Y/277VSYTK02P Art.Nr.: 2104210 TECHNICAL DATA
Monitoring of phase sequence and phase loss Monitoring of asymmetry Temperature monitoring (PTC) Supply voltage 208-480 V AC Supply circuit = measuring circuit 2 change-over contacts Width 45 mm Control
More informationFor a phase-to-phase voltage between 100 V and 1000 V. The standard ratings are: 400 V - 690 V - 1000 V (at 50 Hz)
24 1. NETWORK CONFIGURATIONS definition Standard IEC 38 defines voltage ratings as follows: - Low voltage () For a phase-to-phase voltage between 100 V and 1000 V. The standard ratings are: 400 V - 690
More informationCahier technique no. 196
Collection Technique... Cahier technique no. 196 Integration of local power generation in industrial sites and commercial buildings T. Hazel "Cahiers Techniques" is a collection of documents intended for
More informationElectronic Trip Circuit Breaker Basics Circuit Breaker Application Guide Class 0600
Electronic Trip Circuit Breaker Basics Circuit Breaker Application Guide Class 0600 Data Bulletin 0600DB1104 03/2012 Retain for future use. Electronic Trip Circuit Breaker Basics 0600DB1104 Table of Contents
More information