Cabling Standards Update 2014

Size: px
Start display at page:

Download "Cabling Standards Update 2014"

Transcription

1 Cabling Standards Update 2014 Dimitris Filippou Technical Director, Ltd. IEEE Member, BICSI Country Chair, ELOT Technical Committee TC93 Member, CENELEC TC215 Delegate of Greek National Committee, CENELEC TC215 WG1, WG2 & WG3 Member

2 Dimitris Filippou Standards Activity Member TC215 WG1: Cabling Design TC215 WG2: Cabling Installation QA and Installation Practices TC215 WG3: Facilities and Infrastructures for Data Centres Delegate TC215: Electrotechnical Aspects of Telecommunications Equipment Dimitris Filippou Technical Director I2QS Ltd. Member TC93: Internal Networks of Electronic Communications for Houses and Buildings Tel.: Mob.: BICSI IEEE Country Chair Member Standard Committee for Cabling Design & Installation

3 Standards What are Standards? Standards represent the minimum required to maintain compliance. Principally about achieving minimum performance from products / standards driven by applications not end users. Standards are considered to be living documents. It is important that the region specific standards are quoted in the design and implementation.

4 Regional Standard Bodies Who are the national or regional standard bodies? USA INTERNATIONAL EUROPE ANSI/TIA ISO/IEC CENELEC The International Organization for Standardization (ISO) produces worldwide standards generated by country members. European Committee for Electrotechnical Standardization CENELEC produces European standards generated by EU country members. American National Standards Institute (ANSI) produces North American standards.

5 Who Else Is Out There? Standards and guidance is generated to support Design, Implementation, Methods and Products interoperability. There are many ways of doing the job: Trade Bodies and Standards publication. ETSI (European Telecommunications Standards Institute). ITU (International Telecommunications Union). IEEE (Institute of Electrical and Electronics Engineers, Inc). Manufacturers recommendations. Methods Manuals. Design Guidelines.

6 Cabling Design Standards CLC ISO/IEC ANSI/TIA General Requirements EN (11801) D, 2.D, 3.D, 4.D Office Premises EN (11801) D Industrial Premises EN (24702) 1005-B Homes EN (15018) 570-D Data Centres EN (24764) 942-B Distributed Building Services EN B

7 Cabling Link/Channel Configuration Interconnect Model Channel = 100m Link EQP EQP Cord C Horizontal Cable CP CP Cable TO WA Cord TE Cross-connect Model Channel = 100m Link EQP EQP Cord C Patch Cord C Horizontal Cable CP CP Cable TO WA Cord TE

8 Fundamental Principles ISO/IEC CLC ANSI/TIA Components Links/Channels Components Links/Channels Class A Class B Class C Category 3 Category 3 Category 5 Category 6 Category 6 A Category 7 Class D Class E Class E A Class F Performance Category 5 Category 5 Category 6 Category 6 Category 6A Category 6A Category 7 A Class F A Frequency Category 8.1 Class I Category 8.2 Class II Frequency

9 Fundamental Principles (cont.) Modular Plug/cord Category 5 Category 6 Category 6 A Category 7 Category 7 A Category 8.1 Category 8.2 ISO/IEC CLC Modular Connector Category A 7 7 A A 7 7 A Connection Category Modular Plug/cord Category 3 Category 5 Category 6 Category 6 A ANSI/TIA Modular Connector Category A 6 A A Connection Category Cables and connections of different Categories may be mixed within a channel, however the resultant cabling performance will be determined by the Category of the lowest performing component.

10 Cabling Installation Standards CLC ISO/IEC ANSI/TIA Specification and QA EN Inside Buildings EN Outside Buildings EN Partial Coverage in 569-D 758-C Administration TR C Explicit requirements of EN series but covering all telecommunications cabling Explicit requirements of ISO/IEC series Implicit requirements of ANSI/TIA-568 series Remote Powering CLC TR

11 Telecommunications Bonding Standards CLC ISO/IEC ANSI/TIA EN 50310: : C Application of equipotential bonding and earthing in buildings with information technology equipment Information technology Telecommunications bonding networks for buildings and other structures Generic telecommunications bonding and grounding (earthing) for customer premises

12 CENELEC

13 CENELEC EN Series There are 9 documents comprising EN 50173; the series includes: EN , Information Technology Generic Cabling Systems Part 1: General requirements. EN , Information Technology Generic Cabling Systems Part 2: Office premises. EN , Information Technology Generic Cabling Systems Part 3: Industrial premises. EN , Information Technology Generic Cabling Systems Part 4: Homes. EN , Information Technology Generic Cabling Systems Part 5: Data centres. EN , Information Technology Generic Cabling Systems Part 6: Distributed building systems. TR , Cabling guidelines in support of 10GBaseT. TR , Information Technology Implementation of BCT applications using cabling in accordance with EN TR , Information Technology Generic cabling systems Part 99-3: Home cabling infrastructures up to 50m in length to support simultaneous and non simultaneous provision of applications.

14 Highlights from EN Introduces the concept of environmental classification M.I.C.E. (Mechanical, Ingress, Climatic and Chemical, Electromagnetic). Environmental Class Mechanical rating M 1 M 2 M 3 Ingress rating I 1 I 2 I 3 Climatic and chemical rating C 1 C 2 C 3 Electromagnetic rating E 1 E 2 E 3 The requirements of a given classification cover the requirements of a lower classification, i.e. channels designed to operate under environmental conditions defined by M 2 shall continue to operate under environmental conditions by M 1. Specifies Channels for balanced and optical fibre cabling media. Specifies the minimum component requirements in support of these cabling elements. Provides a list of applications supported by generic cabling systems.

15 Highlights from EN (cont.) Classes for balanced cabling: Class A: specified up to 0.1MHz; Class B: specified up to 1MHz; Class C: specified up to 16MHz; Class D: specified up to 100MHz; Class E: specified up to 250MHz; Class E A : specified up to 500MHz; Class F: specified up to 600MHz; Class F A : specified up to 1000MHz; Class I: specified between 1600MHz and 2000MHz (TBD) ; Class II: specified between 1600MHz and 2000MHz (TBD). Channels of a given Class will support all applications of a lower Class.

16 Highlights from EN Supports two architectures: Type A: Generic cabling extends from the Service Distributor (SD) to the Service Outlet (SO). Channel = 100m Link EQP EQP Cord SD Horizontal Cable The generic cabling shall be able to support the broadest set of existing and emerging application within the environmental conditions: Considerations for Cat.6A (Class E A ) and Cat.7A (Class F A ). Consideration for PoE applications and remote powered devices. SCP SCP Cable SO SA Cord TE

17 Highlights from EN (cont.) Type B: Generic cabling extends from an SD to the Service Concentration Point (SCP) provide the opportunity for: Application specific cabling to be installed between the SCP and terminal equipment. Application specific cabling to be connected at the SCP. SCP Cable SO SA Cord TE TE connection configured as Plug Socket EQP EQP Cord SD Horizontal Cable SCP SCP Cable SCP Cable SA Cord TE TE TE connections directly attached to cabling

18 Highlights from EN (cont.) SCP advantages: An SCP allows coverage area connections to be easily reconfigured. Consolidation Points (CP) for voice and data and SCPs for BAS applications can coexist within the same zone box. We need to think only for the number of IP applications/services needed.

19 CENELEC Installation Standards There are 4 documents comprising EN 50174; the series includes: EN , Information Technology Cabling installation Part 1: Installation specification and quality assurance. EN , Information Technology Cabling installation Part 2: Installation planning and practices inside buildings. EN , Information Technology Cabling installation Part 3: Installation planning and practices outside buildings. TR , Information Technology Cabling installation Remote Powering (TBD).

20 Highlights from TR Thermal measurements to date on ventilated bundles Partially ventilated Reflects real installation practices Unventilated Insulated

21 Highlights from TR i c Current feed using 37 cable bundle... i c Cable 1 Cable 2 Cable 37 T 2c T 2d T 2b T 1, T 2a and T 3 Thermocouples T 1 0,6 0,05 m T 2x 0,6 0,05 m T 3 T a Ambient 1,2 m 1,2 m perfect bundle

22 CENELEC Installation Standards CENELEC EN 50310, Application of equipotential bonding and earthing in buildings with information technology equipment. This European standard specifies minimum requirements for earthing networks and connections (bonds) in buildings in which information technology equipment is intended to be installed to protect that equipment and interconnecting cabling from electrical hazards.

23 New EN Data Center Design Standard CLC TC215 WG3 has started a new project EN Data Centre facilities and infrastructures: EN Part 1: General concepts (Published). EN Part 2-1: Building construction. EN Part 2-2: Power distribution. EN Part 2-3: Environmental control. EN Part 2-4: Telecommunications cabling infrastructure. EN Part 2-5: Physical security. EN Part 2-6: Management and operational information. EN Part 3-1: General design principles. EN Part 3-2: Measurements methodologies, test methods and report formats. This series of European Standards does not address the selection of information technology and network telecommunications equipment, software and associated configuration issues.

24 ISO/IEC

25 ISO/IEC Series ISO/IEC rd Edition series: ISO/IEC , Generic Cabling; ISO/IEC , Enterprise; ISO/IEC , Industrial; ISO/IEC , Homes ; ISO/IEC , Data Centre. ISO/IEC TR , Technical Report for the next generation Twisted-pair cabling, for supporting 40Gb/s applications (in support of the IEEE 802.3bq project for 40GBASE-T, next generation 40G Ethernet over-twisted-pair). ISO/IEC , 2 nd Edition This document is similar to EN and EN ISO/IEC , 2 nd Edition Test method improvements to support component and channel performance for OM4 optical fiber media classes.

26 ISO/IEC Standards Automated Infrastructure Management (AIM) systems Automated cabling administration systems: intelligent patchpanels, management program interface. Two open projects: ISO/IEC Amd. 1, adds informative text covering AIM functional guidelines. ISO/IEC 18598, requirements of AIM elements supporting cabling systems within buildings. ISO/IEC Telecommunications Bonding Requirements of bonding-to-earth systems supporting cabling within buildings.

27 Highlights from ISO/IEC Copper Cabling Items Defines the component, Link and Channel performance for balanced twisted pair copper. Class C up to 16MHz; Class D up to 100MHz; Class E up to 250MHz; Class E A up to 500MHz; Class F up to 600MHz; Class F A up to 1000MHz; Class I between 1600MHz and 2000MHz; Class II between 1600MHz and 2000MHz.

28 Highlights from ISO/IEC (cont.) Copper Cabling Items New IEC definitions of cable construction/design with corresponding IEC definitions for performance.

29 Highlights from ISO/IEC (cont.)

30 Highlights from ISO/IEC (cont.) Copper Testing Issues If the coupling attenuation of Class E A or F A permanent links or CP links is at least 10dB better than the corresponding channel coupling attenuation requirements, and Class F A permanent links or CP Links are at least 25dB better than the corresponding channel coupling attenuation requirements, then the ANEXT requirements are met by design. Effectively this means that testing and validation for ANEXT is not required on site.

31 Highlights from ISO/IEC (cont.) Optical Fibre Cabling Items Optical fibre adapters and connectors should be protected from dust and other contaminants, specifically while they are in an unmated state. End faces of connectors shall be inspected according to ISO/IEC and subsequently cleaned when necessary, prior to connection. Maximum mated connector insertion loss: 100% 0.75dB; 95% 0.50dB; 50% 0.35dB. The TO shall present a duplex LC connector that complies with IEC

32 Questions Dimitris Filippou Technical Director, Ltd. IEEE Member, BICSI Country Chair, ELOT Technical Committee TC93 Member, CENELEC TC215 Delegate of Greek National Committee, CENELEC TC215 WG1, WG2 & WG3 Member

Dat Da a t Cen t Cen er t St andar St d andar s d R o R undup o BICSI, TIA, CENELEC CENELE, ISO Steve Kepekci, RCDD

Dat Da a t Cen t Cen er t St andar St d andar s d R o R undup o BICSI, TIA, CENELEC CENELE, ISO Steve Kepekci, RCDD Data Center Standards Roundup BICSI, TIA, CENELEC, ISO Steve Kepekci, RCDD Introduction Regardless of business activity or size, all information technology (IT) groups have similar needs Provide secure,

More information

Mixed High-Speed Ethernet Operations over Different Categories of Bundled UTP Cable

Mixed High-Speed Ethernet Operations over Different Categories of Bundled UTP Cable Mixed High-Speed Ethernet Operations over Different Categories of Bundled UTP Cable June 10, 2010 Contributors: Yinglin (Frank) Yang CommScope, Inc. Charles Seifert Ixia Ethernet Alliance 3855 SW 153 rd

More information

Innovation. Volition Network Solutions. Leading the way in Network Migration through Innovative Connectivity Solutions. 3M Telecommunications

Innovation. Volition Network Solutions. Leading the way in Network Migration through Innovative Connectivity Solutions. 3M Telecommunications 3M Telecommunications Solutions for Networks Volition Network Solutions Leading the way in Network Migration through Innovative Connectivity Solutions Innovation The Broadband Migration Path 3M TM Volition

More information

Data Centre Cabling. 20 August 2015 Stefan Naude RCDD The SIEMON Company

Data Centre Cabling. 20 August 2015 Stefan Naude RCDD The SIEMON Company Data Centre Cabling 20 August 2015 Stefan Naude RCDD The SIEMON Company Agenda 1. Data Centre Standards 2. The Need for Speed 3. Copper in the Data Centre 4. Fibre in the Data Centre 5. Top of Rack vs

More information

Evolution of Cabling Standards TIA/EIA ISO/IEC CENELEC. by Paul Kish NORDX/CDT Chair TIA TR 41.8

Evolution of Cabling Standards TIA/EIA ISO/IEC CENELEC. by Paul Kish NORDX/CDT Chair TIA TR 41.8 Evolution of Cabling Standards TIA/EIA ISO/IEC CENELEC by Paul Kish NORDX/CDT Chair TIA TR 41.8 Outline Market trends Standards development where we were where we are where we are going Beyond Category

More information

Data Centers Re-Enforce Best Practices To Assure Optimal Installation Quality and Maximize Margins For 10GBASE-T"

Data Centers Re-Enforce Best Practices To Assure Optimal Installation Quality and Maximize Margins For 10GBASE-T Data Centers Re-Enforce Best Practices To Assure Optimal Installation Quality and Maximize Margins For 10GBASE-T" Christian Schillab Product Manager InfrastructureSuperVision Fluke Networks Europe Member

More information

European Normative EN50173-1. system

European Normative EN50173-1. system European Normative EN50173-1 for generic/structured cabling system Pietro Nicoletti Studio Reti s.a.s piero[at]studioreti.it www.studioreti.it Cabl-New-2003-Engl - 1 P. Nicoletti: see note pag. 2 Copyright

More information

HIGHSPEED ETHERNET THE NEED FOR SPEED. Jim Duran, Product Manager - Americas WHITE PAPER. Molex Premise Networks

HIGHSPEED ETHERNET THE NEED FOR SPEED. Jim Duran, Product Manager - Americas WHITE PAPER. Molex Premise Networks HIGHSPEED ETHERNET THE NEED FOR SPEED Jim Duran, Product Manager - Americas WHITE PAPER Molex Premise Networks EXECUTIVE SUMMARY Over the years structured cabling systems have evolved significantly. This

More information

The Evolution of Copper Cabling Systems from Cat5 to Cat5e to Cat6 Copper Cabling Standards and Technical Aspects

The Evolution of Copper Cabling Systems from Cat5 to Cat5e to Cat6 Copper Cabling Standards and Technical Aspects The Evolution of Copper Cabling Systems from Cat5 to Cat5e to Cat6 Copper Cabling Standards and Technical Aspects White Paper /7/0 Executive Summary Now that the TIA/EIA-568-B.- Category 6 Copper Cabling

More information

Session 2; Cabling Technology in the Data Centre Media Choices; Copper Twisted Pair

Session 2; Cabling Technology in the Data Centre Media Choices; Copper Twisted Pair Presentation; Session 2; Cabling Technology in the Data Centre Media Choices; Copper Twisted Pair 5 th April 2010 Paul Mathews MInstSMM, CCNA, MIEEE Global Channel Manager Media Types Physical Layer Cabling;

More information

Highlights: ISO/IEC SC25/WG3 Meeting Berlin: 02-06 06 May 2011. - Customer Premises Cabling -

Highlights: ISO/IEC SC25/WG3 Meeting Berlin: 02-06 06 May 2011. - Customer Premises Cabling - 1 ISO/IEC SC25/WG3 Meeting Berlin: 02-06 06 May 2011 - Customer Premises Cabling - Highlights: 1. ISO/IEC 24764 Data Centre Cabling Am.1 2. ISO/IEC 14763-2 Plan. & Install. final draft 3. ISO/IEC 14763-3

More information

with Component Rating A Simple Perspective

with Component Rating A Simple Perspective Cat-6A UTP and Shielded with Component Rating A Simple Perspective Asef Baddar RCDD, DCD Sr. Technical Manager Leviton Middle East Category Specifications Agenda Terminology International & North America

More information

Cabling for 10GBASE-T and Beyond - A Tangled Web

Cabling for 10GBASE-T and Beyond - A Tangled Web Augmented Category 6 Category 6 A CLC TR 50173-99-1 TIA/EIA-TSB-155 TIA/EIA-568-B.2-10 ISO/IEC 11801 A1.1 Class E A Class F A ISO/IEC 11801 A1.2 Category 7 A ISO/IEC TR 24750 ISO/IEC 11801 Cabling for

More information

CATEGORY 8: UNDERSTANDING THE NEW CATEGORY OF PERFORMANCE FOR BALANCED TWISTED PAIR CABLE

CATEGORY 8: UNDERSTANDING THE NEW CATEGORY OF PERFORMANCE FOR BALANCED TWISTED PAIR CABLE ORTRONICS : UNDERSTANDING THE NEW CATEGORY OF PERFORMANCE FOR BALANCED TWISTED PAIR CABLE Cindy Montstream, RCDD/NTS, EE, CPLP Director of elearning and Standards DATA COMMUNICATIONS Legrand, North America

More information

Requirements for Modular Patch Cords (e.g. RJ45 patch cords for Cat5 and Cat6 cabling systems)

Requirements for Modular Patch Cords (e.g. RJ45 patch cords for Cat5 and Cat6 cabling systems) Requirements for Modular Patch Cords (e.g. RJ45 patch cords for Cat5 and Cat6 cabling systems) Introduction The purpose of this document is to: 1) provide background information beneficial to specifiers

More information

Category-6 / Class-E Cabling

Category-6 / Class-E Cabling Category-6 / Class-E Cabling IEEE 802 Tutorial July 7, 1998 San Diego, CA by: Luc Adriaenssens SYSTIMAX Systems Applications Director Bell Labs of Lucent Technologies How were the ISO Cat-6 Targets set?

More information

Trends and Standards In Cabling Systems

Trends and Standards In Cabling Systems Trends and Standards In Cabling Systems Agenda Trends and Standards in Intelligent Buildings And Data Center Trends Update RJ45 supports 10BASE T to 40GBASE T Enterprise LAN trends BYOD (Bring Your Own

More information

R&Mfreenet Advanced Cat 6 A Unshielded Connection Module

R&Mfreenet Advanced Cat 6 A Unshielded Connection Module R&Mfreenet Advanced R&Mfreenet Advanced Cat 6 A Connection Module The R&Mfreenet Cat 6 A unshielded connection modules, part of the Advanced cabling system, are ideal for voice, fast data transmissions

More information

White Paper: 10 Gigabit Ethernet over Twisted Pair Copper Systems

White Paper: 10 Gigabit Ethernet over Twisted Pair Copper Systems White Paper: 10 Gigabit Ethernet over Twisted Pair Copper Systems Asef Baddar, RCDD Principal Engineer / Applications Engineering Supervisor Leviton Network Solutions C/7 - #1928 Table of Contents Background

More information

Migration to 40/100G in the Data Center with OM3 and OM4 Optical Connectivity

Migration to 40/100G in the Data Center with OM3 and OM4 Optical Connectivity Migration to 40/100G in the Data Center with OM3 and OM4 Optical Connectivity Needs in the Data Center With the continued requirement for expansion and growth in the data center, infrastructures must provide

More information

BICSI :Building Industry Consulting Service International

BICSI :Building Industry Consulting Service International BICSI :Building Industry Consulting Service International - Lead the information and communications technology community with excellence in publications, education and knowledge assessment. - Advance our

More information

White Paper: What Component Compliance Means for CAT6A System Performance

White Paper: What Component Compliance Means for CAT6A System Performance White Paper: What Component Compliance Means for CAT6A System Performance Gary Bernstein, RCDD Director of Product Management Copper Systems Leviton Network Solutions Jeff Seefried Development Engineering

More information

The Permanent Link in Field Certification Reasons, Advantages, Testing Challenges

The Permanent Link in Field Certification Reasons, Advantages, Testing Challenges The Permanent Link in Field Certification Reasons, Advantages, Testing Challenges Table of contents Channel, Basic Link and Permanent Link defined....................... 2 Critical Performance Parameters......

More information

Cable Sharing in Commercial Building Environments

Cable Sharing in Commercial Building Environments Cable Sharing in Commercial Building Environments Reducing Cost, Simplifying Cable Management, and Converging Applications onto Twisted-Pair Media Cable sharing describes the practice of running more than

More information

Industry Standards Activity Overview

Industry Standards Activity Overview Industry Standards Activity Overview TIA Most Recent Plenary Meeting: June 13-17, 2016 in Tigard, OR Updated: July 18, 2016 TR-42.1 Commercial Building Cabling: TSB-185 Environmental Classification (MICE)

More information

EN 50174-1 and EN 50174-2: 2008 Integrated standards for telecommunications cabling installation

EN 50174-1 and EN 50174-2: 2008 Integrated standards for telecommunications cabling installation EN 50173-1 EN 50173-2 EN 50173-3 EN 50173-4 EN 50173-5 EN 50346 EN 50174-1 EN 50174-2 EN 50174-3 DESIGN INSPECTION TESTING PLANNING INSTALLATION National Standards National Regulations EN 50174-1 and EN

More information

Cat 5, 6 or 7? Standards. Background. A University Standard for Structured Wiring. Network Points Installed. British Standards.

Cat 5, 6 or 7? Standards. Background. A University Standard for Structured Wiring. Network Points Installed. British Standards. Cat 5, 6 or 7? A University Standard for Structured Wiring. Background isolutions recently formed Incorporates all IT service providers within the University. Focus on all ICT needs of the user and the

More information

INTERNATIONAL STANDARD

INTERNATIONAL STANDARD INTERNATIONAL STANDARD ISO/IEC 11801 Second edition 2002-09 Information technology Generic cabling for customer premises Reference number ISO/IEC 11801:2002(E) INTERNATIONAL STANDARD ISO/IEC 11801 Second

More information

Structured Cabling, Earthing & Equipotential Bonding

Structured Cabling, Earthing & Equipotential Bonding White Paper Information and Communication Technology Structured Cabling, Earthing & Equipotential Bonding English Rev. 1.0.1 / 2012-06-01 1 Abstract All Dallmeier network products (PoE cameras, recorders,

More information

Physical Infrastructure trends and evolving certification requirements for Datacenters Ravi Doddavaram

Physical Infrastructure trends and evolving certification requirements for Datacenters Ravi Doddavaram Physical Infrastructure trends and evolving certification requirements for Datacenters Ravi Doddavaram www.psiberdata.com Agenda Market Market Trend and Trend business and and business case for case higher

More information

Trends and Standards in LAN Cabling Systems Intelligent Buildings

Trends and Standards in LAN Cabling Systems Intelligent Buildings Trends and Standards in LAN Cabling Systems Intelligent Buildings A Sitaramaiah Managing Director CommScope Solutions India Intelligent Buildings Smart Cities Opportunities in Systems Integration Smart

More information

The High Cost of a Low-Cost Cable Certification Tester

The High Cost of a Low-Cost Cable Certification Tester The High Cost of a Low-Cost Cable Certification Tester How much does it cost? That is typically the first question a cabling contractor or network owner asks when considering a new certification tester

More information

Accelerating Light. Copper Cabling Solutions. Category 6A

Accelerating Light. Copper Cabling Solutions. Category 6A Accelerating Light Copper Cabling Solutions Category 6A Category 6A Copper Cabling Solutions Fibernet designs and manufactures premium, high performance copper communication infrastructure and connectivity

More information

Resolution of comments 242 and 267 on Insertion loss measurements of installed fiber cables. Steve Swanson May 5, 2009

Resolution of comments 242 and 267 on Insertion loss measurements of installed fiber cables. Steve Swanson May 5, 2009 Resolution of comments 242 and 267 on Insertion loss measurements of installed fiber cables Steve Swanson May 5, 2009 Current text in 86.10.1 Insertion loss measurements of installed fiber cables are made

More information

Testing 10 Gb/s Performance of Category 6 and 6A Structured Copper Cabling Systems within the Unified Physical Infrastructure SM (UPI)

Testing 10 Gb/s Performance of Category 6 and 6A Structured Copper Cabling Systems within the Unified Physical Infrastructure SM (UPI) within the Unified Physical Infrastructure SM (UPI) www.panduit.com WP-11 April 2007 Introduction With the ratification of the IEEE 802.3an 10GBASE-T copper standard, end users now have more media options

More information

BICSI NxtGEN & Global Data Center Standards Update

BICSI NxtGEN & Global Data Center Standards Update BICSI NxtGEN & Global Data Center Standards Update Bob Faber, RCDD/NTS Siemon Global Accounts Manager Chair NEMA High Performance Wire & Cable Chair BICSI Standards Committee Vice Chair BICSI TI&M Committee

More information

European Standards Reference Guide. A Reference Guide To:

European Standards Reference Guide. A Reference Guide To: ISO 11801 EN 50174 ISO 18010 ISO/IEC 24764 EN 50310 EN 50173 ANSI/TIA-568-C ANSI/TIA-606-A ANSI/TIA-942 IEEE 802.3af IEEE 802.3at IEEE 802.3an IEEE 802.3ba IEEE 802.11 European Standards Reference Guide

More information

FIA FIA. Installation Standards - 2004. e-ready Building Next Generation IT infrastructures. ϕ The Cabling Partnership AGENDA

FIA FIA. Installation Standards - 2004. e-ready Building Next Generation IT infrastructures. ϕ The Cabling Partnership AGENDA Installation Standards - 2004 January 2004, Issue 1 Mike Gilmore Standards Activities Member: ISO/IEC JTC1 SC25 WG3: Generic Cabling ISO/IEC JTC1 SC25 Project Team: SOHO Convenor: ISO/IEC JTC1 SC25 WG3

More information

ANSI/TIA/EIA - 568-A, Commercial Building Telecommunications Cabling Standard.

ANSI/TIA/EIA - 568-A, Commercial Building Telecommunications Cabling Standard. WIRING STANDARD INTRODUCTION This standard defines a telecommunications wiring system for North Dakota State Agencies, offices or buildings that will support a multi-product environment. The purpose of

More information

Laying the groundwork for a new level of Power over Ethernet

Laying the groundwork for a new level of Power over Ethernet White Paper Laying the groundwork for a new level of Power over Ethernet June, 2014 Contents Laying the groundwork for a new level of Power over Ethernet 3 PoE basics 4 PoE standards development 5 Four-pair

More information

Future Proofing with Category 7 and 7A Cabling for 25 and 40GBASE-T Carries High Levels of Risk

Future Proofing with Category 7 and 7A Cabling for 25 and 40GBASE-T Carries High Levels of Risk Future Proofing with Category 7 and 7A Cabling for 25 and 40GBASE-T Carries High Levels of Risk Introduction At the IEEE 802.3 Working Group meeting in July of 2012, the Next Generation BASE-T Call for

More information

IT Cabling Solutions

IT Cabling Solutions IT Cabling Solutions Signamax & Hitachi Cable America System Performance Signamax & Hitachi Cable America (Hitachi) system quality assurance testing is based on the worst-case model - four-connector 100-meter

More information

MTP Optical Fibre Configurations

MTP Optical Fibre Configurations MTP Optical Configurations ackground The Excelerator MPO range from Excel utilises the MTP Elite connector manufactured by US Conec. The range is made up of: MTP to MTP Trunk Cables MTP to LC s MTP Patch

More information

The Quality Connection. Industrial IT cabling ISO/IEC 24702 / EN 50 173-3

The Quality Connection. Industrial IT cabling ISO/IEC 24702 / EN 50 173-3 The Quality Connection Industrial IT cabling ISO/IEC 24702 / EN 50 173-3 LEONI Kerpen & HARTING worldwide LEONI Kerpen and HARTING... For more than 85 years now, LEONI Kerpen as one of the leading companies

More information

ANSI/TIA-942 Telecommunications Infrastructure Standards for Data Centers

ANSI/TIA-942 Telecommunications Infrastructure Standards for Data Centers ANSI/TIA-942 Telecommunications Infrastructure Standards for Data Centers Jonathan Jew jew@j-and and-m.com J&M Consultants, Inc Co-chair TIA TR-42.1.1 data center committee Co-chair BICSI data centers

More information

Data Center Standards Making Progress on Many Fronts. Jonathan Jew J&M Consultants, Inc jew@j-and-m.com

Data Center Standards Making Progress on Many Fronts. Jonathan Jew J&M Consultants, Inc jew@j-and-m.com Data Center Standards Making Progress on Many Fronts Jonathan Jew J&M Consultants, Inc jew@j-and-m.com J&M Consultants - 2008 Speaker Jonathan Jew Co-chair TIA TR-42.1.1 Data Center working group ANSI/TIA-942

More information

Enhanced Category 5 Cabling System Engineering for Performance

Enhanced Category 5 Cabling System Engineering for Performance Engineering for Performance Table of Contents 2 Introduction 2 Where Did It Come From? 2 Enhanced Category 5 Performance What to Test The Link The Channel Don t Forget the Cable Assembly 4 Performance

More information

White Paper. Power over Ethernet Plus Update and Cabling Considerations

White Paper. Power over Ethernet Plus Update and Cabling Considerations White Paper Power over Ethernet Plus Update and Cabling Considerations Power over Ethernet Plus Update and Cabling Considerations TABLE OF CONTENTS 1. Introduction...3 2. Application Objectives...5 3.

More information

White Paper. Cat. 6A vs. Cat. 6 A. What s the Difference and Why Should I Care?

White Paper. Cat. 6A vs. Cat. 6 A. What s the Difference and Why Should I Care? White Paper Cat. 6A vs. Cat. 6 A What s the Difference and Why Should I Care? Cat. 6A vs. Cat. 6 A What s the Difference and Why Should I Care? TABLE OF CONTENTS 1. Introduction...3 2. Component Standards

More information

Performance Verification of GigaSPEED X10D Installations with Fluke Networks DTX 1800 CableAnalyzer

Performance Verification of GigaSPEED X10D Installations with Fluke Networks DTX 1800 CableAnalyzer SYSTIMAX Solutions Performance Verification of GigaSPEED X10D Installations with Fluke Networks DTX 1800 CableAnalyzer Issue 2 Draft 1 June 2010 Contents Overview 3 GigaSPEED X10D Guaranteed Channel Performance

More information

Data Center Design for 40/100G

Data Center Design for 40/100G Data Center Design for 40/100G With the continued requirement for expansion and scalability in the data center, infrastructures must provide reliability, manageability and flexibility. Deployment of an

More information

Gigabit Passive Optical Networks

Gigabit Passive Optical Networks White Paper Gigabit Passive Optical Networks Passive Optical LAN Solutions (POLS) Theory, Design, and Installation Considerations Sean McCloud, RCDD Senior Applications Engineer, Leviton Network Solutions

More information

Simpler all over. Simpler all round. 500 MHz. 10 GB ether. fully shielded. Poe+ Cat.6 A. Data Voice. MFP8 Cat.6 A Field assembly RJ45 plug

Simpler all over. Simpler all round. 500 MHz. 10 GB ether. fully shielded. Poe+ Cat.6 A. Data Voice. MFP8 Cat.6 A Field assembly RJ45 plug Simpler all over. Simpler all round. No special tools required for field ASSEMBLY Cat.6 A 10 GB ether. 500 MHz fully shielded Poe+ Data Voice MFP8 Cat.6 A Field assembly RJ45 plug Less fuss. More flexibility.

More information

Migration Strategy for 40G and 100G Ethernet over Multimode Fiber

Migration Strategy for 40G and 100G Ethernet over Multimode Fiber Introduction Migration Strategy for 0G and 00G Ethernet over Multimode Fiber There is a need for increased network bandwidth to meet the global IP traffic demand, which is growing at a rate of 0% per year

More information

Data Center. Pre-terminated. Patch Panel System. Cabling Systems Simplified. Patch Panels. 10G + Gigabit. Patch Cords. Plug & Play Installation

Data Center. Pre-terminated. Patch Panel System. Cabling Systems Simplified. Patch Panels. 10G + Gigabit. Patch Cords. Plug & Play Installation Data Center Pre-terminated Patch Panel System Patch Panels Plug & Play Installation 10G + Gigabit Patch Cords Bundled + Labeled Cabling Systems Simplified Our Mission At Cablesys, our mission is to simplify

More information

Total Solutions Verification

Total Solutions Verification Total Solutions Verification 3rd Party Electrical Performance Testing Author: Tom Boucino Applications Engineer Uniprise Solutions CommScope has always designed cables with connectivity in mind. Our engineers

More information

Open System Architecture

Open System Architecture Open System Architecture What is Open System Architecture? If you are installing a Category 5e, 6 or 6A infrastructure, there is a sizeable selection of well know products available. What makes one product

More information

SHEET 1 COMMUNICATION NETWORKS COMPUTER AND TELEPHONE SYSTEMS

SHEET 1 COMMUNICATION NETWORKS COMPUTER AND TELEPHONE SYSTEMS STRUCTURED CABLING SHEET 1 COMMUNICATION NETWORKS COMPUTER AND TELEPHONE SYSTEMS INTRODUCTION In recent years, communications have taken on a crucial role in development for businesses. Communications

More information

Fibre optic testing best practices

Fibre optic testing best practices Fibre optic testing best practices Adrian Young Senior Technical Support Engineer Fluke Networks November 2011 Singapore Inspecting and cleaning Keeping the output port on your test equipment clean is

More information

802.3bp Baseline Optional Link segment

802.3bp Baseline Optional Link segment 802.3bp Baseline Optional Link segment San Diego, A July 2014 hris DiMinico M ommunications/panduit cdiminico@ieee.org 1 Purpose Development of baseline for the 802.3bp optional Link Segment (ScTP/Shielded)

More information

Method for improving Return Loss in order to reduce PHY power Ron Nordin Panduit Bob Wagner Panduit Paul Vanderlaan Berk-Tek

Method for improving Return Loss in order to reduce PHY power Ron Nordin Panduit Bob Wagner Panduit Paul Vanderlaan Berk-Tek Method for improving Return Loss in order to reduce PHY power Ron Nordin Panduit Bob Wagner Panduit Paul Vanderlaan Berk-Tek Supporters Mike Grimwood Broadcom Will Bliss Broadcom Dariush Dabiri APM Dan

More information

IEEE 802.11ac 5 GHz Wireless Update and Structured Cabling Implications

IEEE 802.11ac 5 GHz Wireless Update and Structured Cabling Implications Killer App Alert! IEEE 802.11ac 5 GHz Wireless Update and Structured Cabling Implications Killer app alert! The newly published IEEE 802.11ac Very High Throughput wireless LAN standard 1 has far reaching

More information

Running 1000BASE-T Gigabit Ethernet over Copper Cabling 30 March 1999 Colin Mick/The Mick Group with Bruce Tolley/3Com and Willem Wery/Intel

Running 1000BASE-T Gigabit Ethernet over Copper Cabling 30 March 1999 Colin Mick/The Mick Group with Bruce Tolley/3Com and Willem Wery/Intel Running 1000BASE-T Gigabit Ethernet over Copper Cabling 30 March 1999 Colin Mick/The Mick Group with Bruce Tolley/3Com and Willem Wery/Intel Introduction When network managers decide on a cabling system,

More information

Data Centre Link Survey

Data Centre Link Survey Data Centre Link Survey Alan Flatman Principal Consultant LAN Technologies, UK a_flatman@compuserve.com Contribution to IEEE 82.3ba Higher Speed Ethernet Task Force 23-25 Jan 8, Portland, OR Survey Objectives

More information

Giganet Copper Cabling Training

Giganet Copper Cabling Training Giganet Copper Cabling Training Giganet Certified Installer Course 5/14/2012 This manual has been produced as supporting documentation for the Giganet Fibre Optic Certification Course. Course attendees

More information

OSMIUM HIGH DENSITY FIBER OPTIC CHASSIS

OSMIUM HIGH DENSITY FIBER OPTIC CHASSIS OSMIUM HIGH DENSITY FIBER OPTIC CHASSIS OSMIUM HIGH DENSITY FIBER OPTIC CHASSIS The Osmium high density fiber optic chassis is based upon a modular and scalable system composed of 19 unloaded chassis,

More information

STRUCTURED CABLE SPECIFICATION INFORMATION SYSTEMS AND SERVICES ISSUE 1 NOVEMBER 2011

STRUCTURED CABLE SPECIFICATION INFORMATION SYSTEMS AND SERVICES ISSUE 1 NOVEMBER 2011 STRUCTURED CABLE SPECIFICATION INFORMATION SYSTEMS AND SERVICES ISSUE 1 NOVEMBER 2011 Project Ref. Project Name Project Manager Date issued... Consultant/Contractor... 1 CONTENTS 1000 GENERAL OVERVIEW

More information

ARE YOU WIRING FOR A SMART HOME? Guidelines for homeowners on the wiring requirements for telecommunications and other wired services.

ARE YOU WIRING FOR A SMART HOME? Guidelines for homeowners on the wiring requirements for telecommunications and other wired services. ARE YOU WIRING FOR A SMART HOME? Guidelines for homeowners on the wiring requirements for telecommunications and other wired services. INTRODUCTION Installing the right wiring when building or renovating

More information

An Engineer s Guide to Full Compliance for CAT 6A Connecting Hardware

An Engineer s Guide to Full Compliance for CAT 6A Connecting Hardware for CAT 6A Connecting Hardware Written by: Antoine Pelletier Engineer, Global Cabling Products Intertek www.intertek-etlsemko.com 1-800-WORLDLAB Introduction The telecommunication industry recently achieved

More information

SUBJECT: CENELEC VOTE FINAL DRAFT PR EN 50173-1 INFORMATION TECHNOLOGY -GENERIC CABLING SYSTEMS PART 1:GENERAL REQUIREMENTS AND OFFICE AREAS

SUBJECT: CENELEC VOTE FINAL DRAFT PR EN 50173-1 INFORMATION TECHNOLOGY -GENERIC CABLING SYSTEMS PART 1:GENERAL REQUIREMENTS AND OFFICE AREAS Private circulation BCBritish Standards BSI British Standards 389 Chiswick High Road London W4 4AL Tel: 020 8996 9000 Fax: 020 8996 7448 Web: http://bsi-global.com DIRECT Tel: +44(0) 20 8996 7416 Fax:

More information

Installation and Testing Guideline

Installation and Testing Guideline Installation and Testing Guideline Generic Cabling Headquarters Hauptsitz Reichle & De-Massari AG Binzstrasse 32 CHE-8620 Wetzikon/Switzerland Phone Telefon +41 (0)44 933 81 11 Fax Telefax +41 (0)44 930

More information

AMP NETCONNECT Data Center Cabling Solutions

AMP NETCONNECT Data Center Cabling Solutions AMP NETCONNECT Data Center Cabling Solutions Modern business and administrative environments require today more and more sophisticated IT services, what leads to an increasing demand for data provision

More information

AMP CO Plus Insert for Cat. 6 A Applications

AMP CO Plus Insert for Cat. 6 A Applications Product Specification 108-93039 10/Mar/2011 Rev F AMP CO Plus Insert for Cat. 6 A Applications 1. SCOPE 1.1 Content This specification covers performance, tests and quality requirements for AMP* CO Plus

More information

Physical Infrastructure trends and certification requirements for Datacenters. Psiber s Global Village

Physical Infrastructure trends and certification requirements for Datacenters. Psiber s Global Village Brno, Marec 2014 Physical Infrastructure trends and certification requirements for Datacenters Ing. Peter Potrok PROFiber Networking s.r.o. Psiber s Global Village London Munich San Diego Boston Paris

More information

Power over Ethernet with Panduit Copper Cabling

Power over Ethernet with Panduit Copper Cabling Power over Ethernet with Panduit Copper Cabling Introduction Power over Ethernet (PoE) is a common way to reduce installation costs and time by allowing power and data onto a single twisted-pair cable.

More information

How To Properly Maintain A Fiber Optic Infrastructure

How To Properly Maintain A Fiber Optic Infrastructure How To Properly Maintain A Fiber Optic Infrastructure Best Practices to Minimize Damage and Failures in Fiber Optic Infrastructures White Paper Rodney Casteel, RCDD, NTS, OSP, Technical Manager, CommScope

More information

Panduit 28 AWG Patch Cords Installation Guideline

Panduit 28 AWG Patch Cords Installation Guideline Panduit 28 AWG Installation Guideline Introduction Panduit is a leading supplier of Structured Cabling Systems and Unified Physical Infrastructure. Panduit solutions enable the physical infrastructure

More information

10 Gigabit Ethernet over copper: Unshielded, unprotected?

10 Gigabit Ethernet over copper: Unshielded, unprotected? Technical Article 10 Gigabit Ethernet over copper: Unshielded, unprotected? Copyright 2005 Reichle & De-Massari AG (R&M). All rights reserved. Transmission and reproduction of this publication or parts

More information

Network Topologies and Distances

Network Topologies and Distances Network Topologies and Distances Chris Di Minico MC Communications cdiminico@ieee.org 1 Presentation objectives Considerations for 802.3ba fiber link distance objectives 2 HSSG Objectives Support full-duplex

More information

NUIG Campus Network - Structured Cabling System Standards Information s Solutions & Services (ISS)

NUIG Campus Network - Structured Cabling System Standards Information s Solutions & Services (ISS) NUIG Campus Network - Structured Cabling System Standards Information s Solutions & Services (ISS) Revision date 28 th January 2014 The purpose of this document is to assist Building Refurbishment and

More information

DIVISION 26 - ELECTRICAL SECTION 26 05 20 CABLES FOR INSTRUMENTATION

DIVISION 26 - ELECTRICAL SECTION 26 05 20 CABLES FOR INSTRUMENTATION DIVISION 26 - ELECTRICAL PART 1 - GENERAL 1.01 SUMMARY A. Section Includes 1. Instrumentation Cables 1.02 SUBMITTALS A. Submit in accordance with requirements of Section 01 33 00. B. Product Data: Submit

More information

Category 8 Cabling Standards Update

Category 8 Cabling Standards Update White Paper Category 8 Cabling Standards Update TIA TR42.7 Study Group for Class II Limits Contents 1 Background 3 2 Impact of this approval on Category 7 A cabling 3 3 Differences between Class I and

More information

The Need for Speed Drives High-Density OM3/OM4 Optical Connectivity in the Data Center

The Need for Speed Drives High-Density OM3/OM4 Optical Connectivity in the Data Center The Need for Speed Drives High-Density OM3/OM4 Optical Connectivity in the Data Center Doug Coleman, Manager, Technology & Standards, Corning Cable Systems Optical connectivity with OM3/OM4 laser-optimized

More information

USE OF FIBRE OPTICS INTERNATIONAL STANDARDS FOR CALIBRATION LABORATORY ACCREDITATION INTERNATIONAL ELECTROTECHNICAL COMMISSION

USE OF FIBRE OPTICS INTERNATIONAL STANDARDS FOR CALIBRATION LABORATORY ACCREDITATION INTERNATIONAL ELECTROTECHNICAL COMMISSION USE OF FIBRE OPTICS INTERNATIONAL STANDARDS FOR CALIBRATION LABORATORY ACCREDITATION INTERNATIONAL ELECTROTECHNICAL COMMISSION USE OF FIBRE OPTICS INTERNATIONAL STANDARDS FOR CALIBRATION LABORATORY ACCREDITATION

More information

HARTING Ethernet Cabling 8-poles Overview

HARTING Ethernet Cabling 8-poles Overview Ethernet Cabling 8-poles Overview RJ45 Connectors [on page 8] System cables [on page 12] Distribution modules and Outlets [on page 17] Connectors [on page 20] System cables [on page 26] Panel feed-throughs

More information

TIA Fiber Optics LAN Section (FOLS) LAN Standards, News & Trends Report

TIA Fiber Optics LAN Section (FOLS) LAN Standards, News & Trends Report TIA Fiber Optics LAN Section (FOLS) LAN Standards, News & Trends Report Peter L. Pondillo Standards Committee Chairman Corning Incorporated March 2012 Liz to update Fiber Optics LAN Section Overview: Part

More information

FullAXS CONNECTOR SEALING & CABLE ASSEMBLY

FullAXS CONNECTOR SEALING & CABLE ASSEMBLY FullAXS CONNECTOR SEALING & CABLE ASSEMBLY System Solution Guide Next Generation x-tta Solution Next generation WiMAX and Long Term Evolution (LTE) Fiber/Power/Signal To The Antenna (x-tta) connectivity

More information

428 MY HOME Structured cabling system for the home sector

428 MY HOME Structured cabling system for the home sector 428 MY HOME Structured cabling system for the home sector CONTENTS MY HOME Structured cabling system for the home sector General features. 384 General rules for installation. 400 Wiring diagrams. 404 Structured

More information

Obsolete Fiber Technology? Not in my Data Center!

Obsolete Fiber Technology? Not in my Data Center! Obsolete Fiber Technology? Not in my Data Center! White Paper October 2011 Author: James Young Technical Director, Asia Pacific www.commscope.com Do you remember when people used to say fiber optics are

More information

Nexus Technology Review -- Exhibit A

Nexus Technology Review -- Exhibit A Nexus Technology Review -- Exhibit A Background A. Types of DSL Lines DSL comes in many flavors: ADSL, ADSL2, ADSL2+, VDSL and VDSL2. Each DSL variant respectively operates up a higher frequency level.

More information

ABOUT ANIXTER UNIVERSITY

ABOUT ANIXTER UNIVERSITY Q3 2015 ABOUT ANIXTER UNIVERSITY Anixter University TM is the educational initiative of Anixter, a leading global supplier of communications and security products, electrical and electronic wire and cable,

More information

Managing Physical Security Risk in Physical Layer Infrastructure Solutions

Managing Physical Security Risk in Physical Layer Infrastructure Solutions Managing Physical Security Risk in Physical Layer Infrastructure Solutions Protecting Against Network Intrusion Using Keyed Connectivity Systems www.panduit.com WP-05 November 2008 Introduction Industries

More information

ANSI/TIA-942 Telecommunications Infrastructure Standard for Data Centers

ANSI/TIA-942 Telecommunications Infrastructure Standard for Data Centers ANSI/TIA-942 Telecommunications Infrastructure Standard for Data Centers Jonathan Jew jew@j-and-m.com J&M Consultants, Inc Co-chair TIA TR-42.1.1 data center working group Co-chair BICSI data centers standards

More information

Trial Exams C. Standards and Regulations. Examination No: GH-08-C- 1 hour and 5 minutes plus 10 minutes reading time

Trial Exams C. Standards and Regulations. Examination No: GH-08-C- 1 hour and 5 minutes plus 10 minutes reading time Trial Exams C Standards and Regulations Examination No: GH-08-C- This test is intended to gauge your knowledge of essential information contained within AS/CA S009:2013. To qualify for an allpication to

More information

DESKTOP TO DATA CENTRE - THE REAL BATTLELINES FOR COPPER AND OPTICAL FIBRE. by Mike Phillips Chairman of the FIA Council

DESKTOP TO DATA CENTRE - THE REAL BATTLELINES FOR COPPER AND OPTICAL FIBRE. by Mike Phillips Chairman of the FIA Council FIA www.fibreoptic.org.uk Secretary: Jane Morrison The Manor House BUNTINGFORD Hertfordshire SG9 9AB United Kingdom Tel: +44 (0) 1763 273039 Fax: +44 (0) 1763 273255 e-mail: jane@fiasec.demon.co.uk DESKTOP

More information

Specifying an IT Cabling System

Specifying an IT Cabling System Specifying an IT Cabling System This guide will help you produce a specification for an IT cabling system that meets your organisation s needs and gives you value for money. You will be able to give your

More information

Structured and Point to Point Network Cabling for Industrial Automation

Structured and Point to Point Network Cabling for Industrial Automation Structured and Point to Point Network Cabling for Industrial Automation Introduction Industrial automation systems are undergoing dramatic transformations that require businesses to adopt new strategies

More information

Planning, Designing and Installing a Pre-Terminated Copper and Optical Cabling System for the Data Center

Planning, Designing and Installing a Pre-Terminated Copper and Optical Cabling System for the Data Center Planning, Designing and Installing a Pre-Terminated Copper and Optical Cabling System for the Data Center Presenters Charlie Bogolawski, RCDD, CDT Director of Technical Sales, Leviton Danbury, CT Bo Conrad,

More information

White Paper: 10GbE Fiber A Practical Understanding and Functional Approach

White Paper: 10GbE Fiber A Practical Understanding and Functional Approach White Paper: 10GbE Fiber A Practical Understanding and Functional Approach Dennis Manes, RCDD Senior Applications Engineer Leviton Network Solutions E/8 #2509 Table of Contents Introduction 3 Types of

More information

BICSI Data Center Standard. Presented by: Stephen Banks, RCDD CDCDP

BICSI Data Center Standard. Presented by: Stephen Banks, RCDD CDCDP BICSI Data Center Standard Presented by: Stephen Banks, RCDD CDCDP BICSI Data Center Standard BICSI 002, Data Center Design and Implementation Best Practices Used in conjunction with other standards ANSI/TIA-942

More information