Troubleshooting Variable Air Volume Modular Assembly (VMA) 1400 Series Controllers
|
|
|
- Allison Estella Preston
- 9 years ago
- Views:
Transcription
1 Technical Bulletin Issue Date 11/01/01 TECHNICAL BULLETIN Troubleshooting Variable Air Volume Modular Assembly (VMA) 1400 Series Controllers Troubleshooting VMA1400 Series Controllers...3 Introduction... 3 Key Concepts... 5 Troubleshooting VAV System Operation...5 Hardware Concerns...6 VMA Control Performance Measures...9 Occupant Hot/Cold Complaints...12 VMA LED Indicator Status...14 Tools for Detecting Communication Problems...14 N2 Bus Communication Problems...14 Zone Bus Problems...15 Lack of Heat During Commissioning...16 Detailed Procedures Detecting Airflow and Temperature Problems...17 Troubleshooting Airflow Leakage at a Fully Closed Damper...20 Troubleshooting Low Air Velocity...20 Correcting Distorted Flow Patterns Due to Duct Design...20 Correcting Unstable Sensor (AI) Readings...21 Checking Flow Problems by Verifying Velocity Pressure Sensor Operation...22 Checking Airflow Pickups for Debris or Water...22 Checking for Incorrectly Wired Sensors and Misapplied Room Assignments...23 Troubleshooting Balancer s Flow Reading...24 Detecting Communication Problems Using the VMA LED...24 Identifying N2 Bus Configuration Problems...25 Testing for N2 Bus Opens, Shorts, and Crossed Wires...26 Verifying Proper Transformer Installation Johnson Controls, Inc. Code No. LIT Software Release 5.0
2 2 Troubleshooting VMA1400 Series Controllers Technical Bulletin Checking for Proper Device Isolation and Ground Loops...27 Troubleshooting Heating Problems...28
3 Troubleshooting VMA1400 Series Controllers Technical Bulletin 3 Troubleshooting VMA1400 Series Controllers Introduction Although the Variable Air Volume Modular Assembly (VMA) has been designed to provide years of reliable service, problems can develop in the related building and Heating, Ventilating, and Air Conditioning (HVAC) systems. Problems involving the VMA usually surface in the form of occupant comfort issues or communication failures. The causes of these problems range from device failures to HVAC system maintenance and design issues, installation errors, or changes in use of a zone. Troubleshooting must consider all of these variables. Note: This document focuses on the VMA1410, 1420, and 1430 controllers. The VMA1400 Series also includes the VMA1440, which is used exclusively as part of the Metasys Zoning Package. See the Metasys Zoning Package Product Bulletin (LIT ) and the Metasys Zoning Package Overview Technical Bulletin (LIT ) for information on this specialized product. This document describes how to: detect airflow and temperature problems troubleshoot airflow leakage at a fully closed damper troubleshoot low air velocity correct distorted flow patterns due to duct design correct unstable sensor (Analog Input [AI]) readings check flow problems by verifying velocity pressure sensor operation check airflow pickups for debris or water
4 4 Troubleshooting VMA1400 Series Controllers Technical Bulletin check for incorrectly wired sensors and misapplied room assignments troubleshoot Balancer s flow reading detect communication problems using the VMA Light-Emitting Diode (LED) identify N2 Bus configuration problems test for N2 Bus opens, shorts, and crossed wires verify proper transformer installation check for proper device isolation and ground loops troubleshoot heating problems Note: Where this document refers to HVAC PRO software, substitute EURO PRO in Europe.
5 Troubleshooting VMA1400 Series Controllers Technical Bulletin 5 Key Concepts Troubleshooting Variable Air Volume (VAV) System Operation Controller Configuration Problems Mechanical, flow, and wiring problems occur far more often than configuration problems. This is especially true since Proportional-Integral-Derivative (PID) loop tuning is automatic with the VMA. As a rule of thumb, ensure all the equipment and wiring in the system checks out before investigating errant configuration parameters in HVAC PRO software. Refer to the HVAC PRO User s Guide for more information when reviewing VMA configuration parameters. HVAC PRO Software HVAC PRO software provides various diagnostics to help you pinpoint temperature and airflow control problems. Controller information, VAV Box Flow Test, Collect VAV Diagnostics, and the VMA Balancer Tool each have a role in diagnosis and correction of Variable Air Volume (VAV) system problems, whether mechanical, electrical, or configuration related. Collected and calculated data about VMA inputs, outputs, and control loop performance can be displayed through the Parameters list box in the Commissioning mode. Refer to the HVAC PRO User s Guide for more information when using HVAC PRO tools. VAV Box Flow Test This test is provided in HVAC PRO software to collect flow characteristics for the VMA. It can help determine if the VMA is maintaining minimum flow for ventilation and for staged electric reheat. It can also check for maximum flow and diagnose a starved box, reversed polarity, or a loose set screw on an actuator.
6 6 Troubleshooting VMA1400 Series Controllers Technical Bulletin Hardware Concerns Sensor Errors Zone temperature and pressure sensor errors can cause control problems. The Analog Input (AI) range may be improperly selected in the HVAC PRO configuration file. The sensor may need an offset for cable length. This offset, whose default value is -0.8 C (-1.5 F), is an attribute of the Zone Temperature AI. In addition, the sensor may be improperly installed or an element may be damaged. Sensor errors can occur when the temperature sensor is affected by the sun, other zones, or supply air from the diffuser. In the worst case, the Differential Pressure (DP) sensor may drift up to ± Pascal per C (± inch W.C. per F). This is usually insignificant. However, it may produce noticeable flow measurement error during periods of large ambient temperature change. Examples of such periods are transitions between unoccupied and occupied, or during project startup when electrical power may be off and building temperature is not controlled. The controller autocalibrates the DP sensor every two weeks by default to offset the long term affects of temperature and humidity changes. If greater flow measurement accuracy is required at low flow rates where box inlet velocity is under 1 m/s (200 fpm [feet per minute]), the Autocalibration Period can be reduced to recalibrate every three hours. IMPORTANT: During Autocalibration, airflow to the zone drops to zero for the following durations (worst case): VMA1410/1420 = 90 seconds (30 seconds to drive open + 30 seconds to drive close + 30 seconds sensor settle time) VMA1430 = the sum of the damper actuator stroke time and 30 seconds (amount of time to drive close + 30 seconds sensor settle time) Damper/Actuator Operation Damaged damper seals, bent damper blades, poorly designed dampers, or a mis-aligned actuators can cause air leakage during the fully closed position. This causes a small offset that the Balancer can usually compensate for. However, if tight shutoff is required for the application, replace the defective VAV box.
7 Troubleshooting VMA1400 Series Controllers Technical Bulletin 7 Ductwork Design Air velocity is non-uniform if turns or transitions in hard duct or sags in flexible duct are within close proximity to the flow pickups. In this case, the pickup ports may not represent the true average air velocity. In addition, different flow rates may distinctly change the velocity profile. A minimum of three duct diameters of straight, unrestricted duct upstream from the airflow pickups is recommended. The flow profile problem can be corrected by installing straightening vanes in the offending duct section or changing the duct configuration to provide greater separation between the transition and the pickup. Flow rate measurement problems can also be caused by a duct length that causes significant pressure drop or by sags present in flexible duct. This can also be avoided by installing hard duct three diameters in length, starting at the VAV box inlet. Flow Pickup Performance Flow pickup performance suffers when the device is not installed correctly. It can also collect debris and must be checked for plugged ports and leaks between the high and low-pressure sides. Static Pressure Air Flow Total Pressure Static Pressure Duct Wall Pickup High Pressure Manifold Pickup Low Pressure Manifold Area of Increased Velocity and Decreased Pressure Airflow Figure 1: Interaction of the Pickup and Air Stream Referencing Figure 1 above, the upstream ports are exposed to total pressure. In order to sense true static pressure, the pickup must have openings that are perpendicular to the direction of flow. The low-pressure ports open downstream, and the passing air exerts a pull on these openings, resulting in a pressure less than static. This results in airflow pickup gain, resulting in a differential pressure of 1.5- to 3-times the velocity pressure.
8 8 Troubleshooting VMA1400 Series Controllers Technical Bulletin Following are typical flow pickup designs. Usually the cross and ring types perform better than straight tubes because the sensing ports are better distributed across the duct area. Sensing Ports Cross Tubes Squared Rings Straight Tubes Sensing Figure 2: Common Flow Pickups VAV Box Size The VAV box size and flow pickup gain must be entered accurately for the controller to calculate proper airflow. VAV boxes may be oversized for quieter operation or to reserve cooling capacity. Inlet size and pickup gain for the VAV box are entered in HVAC PRO software during configuration. The size and capacity of the VAV box should match the zone loads. If the installed unit is too small, insufficient cooling results. In addition, high flow rates may cause the unit to emit an audible noise. If the installed unit is too large, then proper control of airflow is difficult.
9 Troubleshooting VMA1400 Series Controllers Technical Bulletin 9 VMA Control Performance Measures Temperature Control Measures Table 1 lists key parameters indicating temperature control problems. Table 1: Temperature Control Key Parameters Parameter MovAvg ZT Err MovAvg ABS ZT Err Inadequate Cooling Inadequate Heating Zone Temperature Status Description Average of the zone temperature control loop error (setpoint minus temperature) over the preceding eight hours of control in normal control modes. This calculation is stopped in Shutdown, Warmup, Low Limit, Water System Flush, and when the Zone Temperature sensor is unreliable. If the VMA is interlocked with supply air (fan) availability, and the zone is well designed, this measure should always be within ±0.5 C (±1 F). Since controller error is defined as setpoint minus process variable feedback, negative numbers indicate a warm zone and positive values indicate a cold zone. Average of the absolute or unsigned zone temperature control loop error (absolute value of setpoint minus temperature) over the preceding eight hours of control in normal control modes. This calculation is stopped in Shutdown, Warmup, Low Limit, Water System Flush, and when the Zone Temperature sensor is unreliable. It is just like the MovAvg ZT Err, except that the error is always considered positive. If the VMA is interlocked with supply air (fan) availability, and the zone is well designed, this measure should always be less than 0.5 C (1 F). Larger values may indicate a cooling or heating problem, a cycling control, an extended cooldown, or warmup in progress. When True, this indicates the zone cooling demand cannot be satisfied. Specifically, it means the following: the controller is calling for cooling the controller is in neither Unoccupied nor Shutdown mode the Zone Temperature is reliable the box is not starved the cooling PID has been saturated high for 15 minutes When True, this indicates the zone heating demand cannot be satisfied. Specifically, it means the following: the controller is not in Heating Lockout the controller is calling for heating the controller is in neither Unoccupied nor Shutdown mode the Zone Temperature is reliable the heating PID to be sequenced has been saturated high for ten minutes. This may indicate heating media is not available and Heating Lockout is False. If the sensed value of the zone temperature sensor is outside of the normal operating range -45 to 121 C (-50 to 250 F) for several readings, the Present Value of Temperature Loop is Unreliable. This condition is normally caused by an open or short in the sensor.
10 10 Troubleshooting VMA1400 Series Controllers Technical Bulletin Airflow Control Measures Table 2 lists key parameters that can indicate airflow control problems. Table 2: Airflow Control Key Parameters Parameter MovAvg Flow Err MovAvg ABS Flow Err Starved Box Delta P Status Description Average of the flow control loop error (setpoint minus calculated flow) over the preceding 20 minutes of control in normal control modes. This calculation is stopped in Shutdown, Warmup, Low Limit, Water System Flush, and when the Delta P sensor is unreliable. Since error is (SP flow), negative numbers indicate a zone with too much flow. Average of the absolute or unsigned flow control loop error (difference between setpoint and calculated) over the preceding 20 minutes of control in normal control modes. This calculation is stopped in Shutdown, Warmup, Low Limit, Water System Flush, and when the Delta P sensor is unreliable. It is just like the MovAvg Flow Err, except that the error is always considered positive. If the VMA is interlocked with supply air (fan) availability, and the supply system is well designed, this measure should always be less than the cfm calculated in MovAvg Flow Err above. Larger values may indicate a lack of supply air, duct blockage or disconnection, or a damper or actuation problem. When True, this indicates the airflow setpoint cannot be satisfied. Specifically, it means the controller has been calling for a 100% open damper position for at least ten minutes, and is in neither Unoccupied nor Shutdown, and the Delta P is reliable. If the sensed value of the velocity pressure (Delta P) sensor is outside of the normal operating range for several readings, the Present Value of Flow Loop is Unreliable. This condition is normally caused by an open or short in the sensor or too high a DP in duct. Balancing Errors Pressure independent VAV control jobs frequently require accuracy within 5-10% of actual flow and indicated flow. The balancing contractor must adjust and certify the flow rates specified by the consulting engineer. Sometimes the Balancer s readings disagree with flow indicated by the controller. When airflow readings disagree, a problem may exist or some air delivery system fact may not be known or understood. There are margins for error in the measurement equipment used by the controller, as well as that used by the Balancer. Therefore, it is important that both controls contractors and Balancers understand each other s equipment, techniques, and expectations.
11 Troubleshooting VMA1400 Series Controllers Technical Bulletin 11 Typical factors that contribute to Balancer flow reading errors include: not calibrating the flow hood as specified. Flow hood accuracy is specified by the manufacturer and may range from ±5% to ±3% of full scale reading on the better instruments. calibrating the flow hood on a different type of diffuser. Calibrating the hood with one type of diffuser and then taking measurements on a different type of diffuser results in less accurate values. using multiple diffusers supplied by a single VAV box. When the flow hood is placed over one diffuser, the hood may present a restriction, causing less flow from the measured diffuser and more flow from the others. In this case, the Balancer s sum of the readings taken at all diffusers served by the box is less than the actual flow. performing airflow measurements using a hood rather than a velocity probe type of instrument with a slotted diffuser. A slotted diffuser consists of one to three slots, each about one inch wide and four or more feet long. Tests show that hood readings of some slotted diffusers may be as much as 40% erroneous. The diffuser manufacturer s literature specifies how to measure airflow and what instrument to use. incorrectly mounting the balancing damper. If mounted directly on the diffuser, turbulent flow patterns entering the hood may occur, resulting in erroneous hood indication. mismatching the flow hood with the diffuser size such that the diffuser is not completely covered The Balancer may take two additional measurements to help find the cause of flow reading discrepancies: verifying the controller differential pressure reading with a high-accuracy differential pressure meter performing a duct traverse as detailed in 2001 ASHRAE Handbook Fundamentals, I-P Edition,
12 12 Troubleshooting VMA1400 Series Controllers Technical Bulletin Occupant Hot/Cold Complaints Zone temperature control problems, which are usually reported as occupant hot/cold complaints, can have causes ranging from the building or mechanical system to the control components. The following guide can help locate the cause of zone temperature control problems with Pressure Independent VAV Terminals. Table 3: Occupant Hot/Cold Complaints Symptom Cause Action Occupant Hot Complaints Occupant Hot Complaints or MovAvg ZT Err less than 1 C (-2 F) Continued on next page... Zone setpoint too high Controller not in Occupied mode Occupied Cooling Bias too large Insufficient airflow Airflow not in control. (Indicated by MovAvg Flow Err greater than sq ft Box Area * 40.) Reheat and/or supplemental heat stuck on, valve stuck open or wrong stroke time/range VAV box inlet air too warm Zoning problem - VAV box serves multiple rooms/areas Zone sensor placement resulting in non-representative temperature sensed Zone sensor wiring crossed VAV outlet duct crossed Cooling load exceeds design due to change in use, or added equipment or people Lower the common setpoint. Calibrate remote setpoint potentiometer. Check to see if mode is commanded by network features. Set Occupied Cooling Bias to 1 degree or less for greatest comfort. Check Starved Box. Check terminal box inlet obstructions. Tighten damper shaft coupling. Increase minimum flow setpoint. Reconnect duct. Check for differential pressure sensing problem (refer to Variable Air Volume Modular Assembly [VMA] 1400 Series Overview and Engineering Guidelines Technical Bulletin [LIT ]). Verify heating device operation. With the box at maximum cooling flow, verify diffuser air temperature is 10 to 15 C (50 to 60 F). Warmer air temperature may indicate supply air temperature problem, stuck reheat valve, or box series fan adjusted to flow higher than maximum cooling. See Zones in the Definition of Terms section of the Variable Air Volume Modular Assembly (VMA) 1400 Series Overview and Engineering Guidelines Technical Bulletin (LIT ). See Room Sensor Placement in the Variable Air Volume Modular Assembly (VMA) 1400 Series Overview and Engineering Guidelines Technical Bulletin (LIT ). Rewire VMA to appropriate sensor. Change duct routing or cross sensor wiring. Investigate possibility of increasing the Max Cooling Flow setpoint. (How much greater is present load than design? Is sufficient supply air available? Is box large enough?)
13 Troubleshooting VMA1400 Series Controllers Technical Bulletin 13 Symptom (Cont.) Cause Action Occupant Cold Complaints Occupant Cold Complaints or MovAvg ZT Err Greater than 1 C (2 F) Zone setpoint too low Controller not in Occupied mode Occupied Heating Bias too large Airflow not in control (Indicated by MovAvg Flow Err greater than 40 times the Box Area [measured in sq ft].) Too much airflow Raise the Common Setpoint. Calibrate remote setpoint potentiometer. Check to see if mode is commanded by network features. Set Occupied Heating Bias to 1 degree or less for greatest comfort. Tighten damper, shaft coupling (refer to the Mounting the VMA1410/1420 section in Mounting and Wiring the Variable Air Volume Modular Assembly [VMA] 1400 Series Controllers [LIT ]). Decrease minimum flow setpoint. Check for differential pressure sensing problem (refer to Variable Air Volume Modular Assembly [VMA] 1400 Series Overview and Engineering Guidelines Technical Bulletin [LIT ]). Often due to minimum airflow when zone is not occupied. An occupancy sensor may help. VAV box inlet air too cold Supply air temperature too low. 10 to 15 C (50 to 60 F) is typical. When most boxes are operating near their minimum cooling flow, supply air temperature may be reset higher via network features. Reheat and/or supplemental heating media not available Reheat heating media available and QA path increases flow setpoint on full heating. Reheat media temperature too low. Reheat media not available and QA path increases flow setpoint on full heating. Cold spots or drafts due to low velocity air dropping on occupants Reheat and/or supplemental heat stuck off or valve stuck closed or wrong stroke time or range Zoning problem - VAV box serves multiple rooms/areas Zone sensor placement resulting in non-representative temperature sensed Zone sensor wiring crossed VAV outlet duct crossed Heating load exceeds design due to change in use or less equipment and lights or fewer people Often caused by disabling heating based on arbitrary means like calendar dates. Use network features to enable heating based on demand. If reheat water temperature is too low, or airflow is too great, zone does not warm. Verify water temperature and airflow against design specifications. Issue a Heating Lockout via network features to prevent increased cold airflow when heating is not available. Raise the supply air temperature, replace the diffuser with one designed for low velocity, install a series fan, or control a parallel fan from flow rather than temperature. Verify heating device operation. See the Zones topic in the Definition of Terms section in the Variable Air Volume Modular Assembly (VMA) 1400 Series Overview and Engineering Guidelines Technical Bulletin (LIT ). See Room Sensor Placement in the Variable Air Volume Modular Assembly (VMA) 1400 Series Overview and Engineering Guidelines Technical Bulletin (LIT ). Rewire VMA to appropriate sensor. Change duct routing or cross sensor wiring Investigate possibility of decreasing the Occ In Cooling Flow setpoint (how much ventilation is needed for the occupants?)
14 14 Troubleshooting VMA1400 Series Controllers Technical Bulletin VMA LED Indicator Status The VMA LED provides general diagnostics for VMA power supply and communication status. Viewing the LED signal and understanding what each type of signal indicates quickly isolates some problems. See Detecting Communication Problems Using the VMA LED in the Detailed Procedures section. Tools for Detecting Communication Problems Many communication problems can be detected with a DMM (digital voltmeter). Ordinarily, this is the only equipment needed to troubleshoot communication problems, such as shorts, opens, and crossed wires. Refer to the N2 Communications Bus Technical Bulletin (LIT ). N2 Bus Communication Problems N2 Bus Communications problems between the VMA and the supervisory system are related to improper N2 Bus installation, configuration errors, or both. Typical communications problems include: broken or frayed wires improper transformer installation (improper wiring length or gauge, improper termination, or wrong transformer type) incorrect End-of-Line (EOL) settings Note: Incorrect EOL settings may cause signal reflections that interfere with communication. The VMA is a self-terminating device, which means it has EOL terminations built in. However, the Metasys Network Control Module (NCM), as well as other devices, provide an EOL switch or jumper that the installer needs to set. internally shorted N2 device too many N2 devices N2 Bus too long T or Y connections on N2 Bus defective surge protector, defective repeater, or communications terminal board failure at the NCM
15 Troubleshooting VMA1400 Series Controllers Technical Bulletin 15 N2 address set to 0, 254, or 255 on the controller when software addressing is not used Note: Software addressing is enabled when hardware switches are set to 0 or 255 and when the VMA has B12 firmware or later and HVAC PRO Release 7.02 or later. Address 254 is reserved for VMA broadcast messages and should not be used. For more information on N2 addressing, refer to the N2 Address Switches topic in the Mounting and Wiring Variable Air Volume Modular Assembly (VMA) 1400 Series Controllers Technical Bulletin (LIT ). more than one controller set to the same N2 address ground loops Note: The N2 Bus shield, if used, must be earth-grounded at only one location, preferably at the Network Control Unit (NCU). The N2+, N2-, and REF lines can never be earth grounded. Tie the shield to the SHLD terminal (soft ground) on the N2 connector of the VMA. Refer to the N2 Communications Bus Technical Bulletin (LIT ) for more information. Zone Bus Problems The Zone Bus uses +15 Volts Direct Current (VDC) from the VMA to power the CablePRO or CVTPRO interface devices (24 Volts Alternating Current [VAC] is not required). A communication error may occur while using the HVAC PRO commissioning tool with the VMA over the Zone Bus. The cause of the error is often a loose or improper connection between the interface device, laptop Personal Computer (PC), and the controller. A defective COM port on the laptop could also be at fault. At other times, a defective controller can cause an error. Note: It takes 20 seconds for a VMA to reset and resume communication after being downloaded or after power up. An effective troubleshooting technique is to use a CBLCON and observe its LEDs. The red LED indicates power from the VMA and the green LED indicates that the Zone Bus is present. With no laptop connected to the Zone Bus, the green LED blinks once every 10 seconds. With a laptop connected, the LED blinks several times per second. If this is not the case, try exchanging a component that may be defective with an identical working component. A noisy wire adjacent to the Zone Bus can also cause communication errors. Noise can be periodically induced into the Zone Bus, thereby causing sporadic communication failures between the laptop and the VMA. Most often, noisy lines cause intermittent disruption, not total loss of communication.
16 16 Troubleshooting VMA1400 Series Controllers Technical Bulletin For more information on HVAC PRO software, refer to the HVAC PRO User s Guide. For more information on CablePRO and CVTPRO interface devices, see the Auxiliary Gear Technical Bulletin (LIT ). Lack of Heat During Commissioning A common method to enable heating during commissioning is to override the zone temperature to less than the actual heating setpoint. This method may not produce the expected results. The expectation with this tactic is that the heating will come on immediately. However, the VMA uses saturation timers to switch between modes, and these timers require a minimum of ten minutes before switching modes. Refer to the Application Logic section of the Variable Air Volume Modular Assembly (VMA) 1400 Series Application Note (LIT ) for a more detailed explanation of the theory behind the VMA State Machine. See the Detailed Procedures section of this document for appropriate troubleshooting tactics to address heating problems.
17 Troubleshooting VMA1400 Series Controllers Technical Bulletin 17 Detailed Procedures Detecting Airflow and Temperature Problems To detect airflow and temperature problems: 1. Connect a PC running HVAC PRO software to the VMA for the VAV box you are testing. 2. On the Options menu, click Commissioning View. 3. Click Parameters to view the Parameters list box. Scroll and observe parameters from Table 5 for problems. 4. On the Action menu, click VAV Box Flow Test to detect the problems listed in Table 5. Use the Flow Test Parameters in Table 4. Refer to the HVAC PRO User s Guide for more information on how to set up this diagnostic. Table 4: Flow Test Parameters Parameter Value Step Amount (%) 50% Settle Time (0-60 sec) 15 sec 5. On the Action menu, click Collect Diagnostics. Print out data graphing. Make any needed software adjustments.
18 18 Troubleshooting VMA1400 Series Controllers Technical Bulletin Table 5: Parameters Used to Detect Airflow and Temperature Problems If the Parameter Status Is Zone Temperature Present Value = Unreliable Zone Temperature Present Value = 37.8 C (100 F) Supply Delta P Present Value = Unreliable Damper Command Reliability = Stalled During Positioning If Starved Box = True If Inadequate Cooling = True If Inadequate Heating = True MovAvg ABS Flow Err = (is much larger than the deadband) Then Test for an open or a short on the zone temperature sensor. See Correcting Unstable Sensor (AI) Readings in this document. Check sensor for an open condition after confirming that 37.8 C (100 F) isn t the actual temperature and that Reliability = Reliable. See Correcting Unstable Sensor (AI) Readings, Checking Flow Problems by Verifying Velocity Pressure Sensor Operation, or Checking Airflow Pickups for Debris or Water in this document. Either the damper s movement is obstructed or the actuator has failed. Visually inspect the damper. Perform Box Flow Test. Check the damper linkage. Check the static pressure near the box. Refer to Troubleshooting Low Air Velocity section in this document. Check that the flow setpoints are realistic in comparison to the installed box dimensions. Check the Starved Box parameter to determine if this is a flow problem. If so, see the Starved Box parameter in this table for more information. Increase Flow Setpoint Cooling Max Flow. Check for adequate supply air temperature from fan system. Check for a stuck valve actuator, incorrect spring range on pneumatic valves, or other equipment related problems in the heating system or device. See Correcting Distorted Flow Patterns Due to Duct Design in this document to troubleshoot this problem.
19 Troubleshooting VMA1400 Series Controllers Technical Bulletin 19 Table 6: VAV Box Flow Test Results Symptom Cause Action Flow high at Position 0 and low at Position 100 Flow too high at Position 0 (Flow > Area * 80) No change in flow from Position 0 to 100 Unexpected stroke time (See Table 7.) Flow increases from Position 0 to 50 and decreases from Position 50 to 100 Actuator Direction Incorrect Change the Direction To Close attribute of the Damper Actuator Output or Stepper Motor Output (SMO). Damper Leakage Refer to Troubleshooting Airflow Leakage at a Fully Closed Damper section of this document. Loose Actuator Linkage Damper and Actuator stops not aligned Loose Actuator screw Refer to the Checking Flow Problems by Verifying Velocity Pressure Sensor Operation section of this document, or type in -100% to cause the damper actuator to close. 1. Reset stop positions. Refer to the Mounting and Wiring Variable Air Volume Modular Assembly (VMA) 1400 Series Controllers Technical Bulletin (LIT ). 2. Reset the controller using HVAC PRO software. On the Action menu, click Reset Controller. 1. Tighten screw. Refer to the Mounting and Wiring Variable Air Volume Modular Assembly (VMA) 1400 Series Controllers Technical Bulletin (LIT ). 2. Reset the controller using HVAC PRO software. On the Action menu, click Reset Controller. Bound Damper 1. Reset stop positions. Refer to Mounting and Wiring Variable Air Volume Modular Assembly (VMA) 1400 Series Controllers Technical Bulletin (LIT ). 2. Check for bent damper shaft. 3. Check for duct damage. 4. Reset the controller using HVAC PRO software. On the Action menu, click Reset Controller. Blockage in Duct 1. Open duct and clear blockage. 2. Reset the controller using HVAC PRO software. On the Action menu, click Reset Controller. Actuator travels past damper full open 45 box with damper stops set at Reset stop positions. Refer to Mounting and Wiring Variable Air Volume Modular Assembly (VMA) 1400 Series Controllers Technical Bulletin (LIT ). 2. Reset the controller using HVAC PRO software. On the Action menu, click Reset Controller. Reset stop positions. Refer to Mounting and Wiring Variable Air Volume Modular Assembly (VMA) 1400 Series Controllers Technical Bulletin (LIT ). Table 7: Actuator Rotation Stroke Times for the VMA1410/1420 (Damper full closed to full flow open) Damper Rotation (Degrees) Nominal Stroke Time (Seconds) Note: These times may vary when an external actuator is used (VMA1430).
20 20 Troubleshooting VMA1400 Series Controllers Technical Bulletin Troubleshooting Airflow Leakage at a Fully Closed Damper To troubleshoot airflow leakage at a fully closed damper: 1. Check damper stop positions. Refer to the Variable Air Volume Modular Assembly (VMA) 1400 Series Overview and Engineering Guidelines Technical Bulletin (LIT ). On a 90 box, install at the closed position. 2. Check that the actuator collar (or other linkage) is tightly locked to the damper shaft. Refer to the Variable Air Volume Modular Assembly (VMA) 1400 Series Overview and Engineering Guidelines Technical Bulletin (LIT ). Visually inspect for a damaged damper seal, bent damper blades, or a poorly designed damper. Replace if necessary. Troubleshooting Low Air Velocity To troubleshoot low air velocity: 1. Check airflow velocity in the Parameters list box in HVAC PRO software. Typical minimum is 2 m/s (400 fpm). 2. Check whether the flow is due to an oversized box. If so, check with the Balancer to determine if adjusting the box constant or other system changes are reasonable. Correcting Distorted Flow Patterns Due to Duct Design To correct distorted flow patterns due to duct design: 1. Observe whether flexible duct is installed and connected to the VAV box inlet. 2. Whether hard or flexible duct is installed, check if there is a duct transition less than three diameters in length upstream of the airflow pickups. 3. Check if inlet duct length is excessive. This also may result in pressure drops that restrict airflow. These design conditions can cause non-uniform air velocity across the flow pickup location. 4. To eliminate turbulent flow problems, install a section of straight hard duct between the VAV box inlet and the flexible duct (or duct transition). The straight hard duct must be at least three times the length of the duct diameter.
21 Troubleshooting VMA1400 Series Controllers Technical Bulletin 21 Correcting Unstable Sensor (AI) Readings To correct unstable sensor (AI) readings: 1. Within the HVAC PRO configuration file, verify that the AI range (temperature, cfm, gpm, etc.) is defined properly in the hardware tables. 2. Check sensor calibration. Verify that the input reading is the same as the standard. For temperature readings, a glass thermometer with 0.05 C (0.1 F) accuracy is necessary. Adjust the AI offset in the configuration file. For velocity pressure readings, ensure that Autocalibration was run from HVAC PRO software, then verify flow readings within 5% of balancing hood reading. 3. Use the HVAC PRO commissioning tool to verify that the AI point is reading steady (not unstable). If the velocity pressure is unstable, this could be due to turbulence in the duct. 4. Ensure that there are 3-5 duct diameters of straight ductwork upstream of the airflow pickups. 5. If AI point is still unstable, check the sensor for the following problems: Is the wrong type sensor installed or is it installed improperly? Is the averaging element securely fastened? Are the wires secure? 6. If AI point is still unstable, use the anti-spike filter in the Analog Input Modify option of HVAC PRO software to average out the peaks and valleys and eliminate instability. Select the AI screen then double click on the AI point. Set anti-spike to True and set the spike fraction between 0.0 (none) to 1.0 (any amplitude spike). The default attributes for zone temperature have anti-spike set to True and spike function set to 0.3. This should correct most problems. If not, increase the filter order from none to first or second order. The filter weight can be set from 0.0 (low) to 1.0 (high). Note: Filter values greater than 0.5 are not recommended and, if too large, could make the loop respond too slowly. Filtering must not be done on the velocity pressure sensor, because the P-adaptive algorithm uses air turbulence values to automatically tune.
22 22 Troubleshooting VMA1400 Series Controllers Technical Bulletin Checking Flow Problems by Verifying Velocity Pressure Sensor Operation Note: To ensure accurate readings of the velocity pressure sensor, allow at least 30 minutes stabilization time before installing a product that just came from a storage environment which differs from the installed temperature. To check flow problems by verifying velocity pressure sensor operation: 1. Recalibrate differential pressure by labeling and disconnecting the high and low side tubing from the box pickup pressure taps (preferred), or by commanding Autocalibration from HVAC PRO software, which closes the VAV box to obtain near-zero flow. 2. Autocalibrate the velocity pressure sensor while in Commissioning mode in HVAC PRO software by setting Autocalibration Request parameter to True. 3. Reconnect the high and low side tubing, ensuring the connections are correct. Checking Airflow Pickups for Debris or Water! WARNING: Never blow into the VMA tubing. The velocity pressure transducer is very sensitive and will be destroyed by as little as 70 mbar (1 psi) of pressure. To check airflow pickups for debris or water: 1. Examine the pickup pressure taps inside the VAV box. 2. Check for plugged pickup ports and internal leaks between the high-and low-pressure sides of the sensor. 3. Disconnect the high and low tubes between the VMA and box pickup pressure taps to observe if there is water or condensation disrupting the pressure reading. If necessary, clear water from the tubes and reconnect. 4. Ensure that the VMA is installed vertically on the duct for best performance. If mounted horizontally, Autocalibration adjusts for position effect.
23 Troubleshooting VMA1400 Series Controllers Technical Bulletin 23 Checking for Incorrectly Wired Sensors and Misapplied Room Assignments To check for incorrectly wired sensors and misapplied room assignments: 1. When experiencing problems with poor control, check that the room sensor is connected to the correct VMA. Sometimes sensors are miswired to an adjoining room s VAV box (see Figure 3). 2. Check that the VMA is controlling the right room. Crossed ductwork leads to mistakes similar to the one shown in Figure 4. VMA VMA Room Sensor Room Sensor Miswired Figure 3: Incorrectly Wired Sensors VMA VMA Room Sensor Room Sensor Crossed Figure 4: Crossed Ductwork
24 24 Troubleshooting VMA1400 Series Controllers Technical Bulletin Troubleshooting Balancer s Flow Reading To troubleshoot Balancer s flow reading: Determine if there is a discrepancy of more than 5 to 10% between the actual flow and Balancer s indicated flow. If so, speak with the Balancer about recalculating the Box Constant for the VAV Box Calculation in HVAC PRO software. The default is Detecting Communication Problems Using the VMA LED To detect communication problems using the VMA LED, use Table 8 to help to determine the source of the communications problem. Table 8: Checking Performance with the VMA LED If the LED Response Is Not lit Irregular flashing four times every second One flash every second On solid Rapid flashing 20 times per second Then Power is not applied to the VMA or +15 VDC is shorted. Communications between the VMA and the supervisory system is normal. The VMA is offline. Verify N2 address switches, and continue troubleshooting possible causes as discussed in the following sections of this document: Identifying N2 Bus Configuration Problems Testing for N2 Bus Opens, Shorts, and Crossed Wires Verifying Proper Transformer Installation Checking for Proper Device Isolation and Ground Loops If on steady for longer than 20 seconds, replace the VMA. The VMA memory is corrupted. Download the firmware code into the controller.
25 Troubleshooting VMA1400 Series Controllers Technical Bulletin 25 Identifying N2 Bus Configuration Problems To identify N2 Bus configuration problems, use Table 9 to troubleshoot common offline configuration problems: Table 9: Configuration Errors that Cause N2 Bus Communications Problems Error/Trouble Condition VMA cycles online and offline. VMA does not come online. Entire N2 Bus is offline. Possible Causes Solution Two or more controllers have the same address. A NCM process is using an unconfigured point (i.e., not listed in HVAC PRO.prn file). Change each duplicate address to a unique number. Delete the use of the unconfigured point in the NCM process. There are Y or T taps. Refer to the N2 Communications Bus Technical Bulletin (LIT ). The repeater lost power or is wired wrong. The EOL is not set at the NCM or N30. Two or more controllers have the same address. The address of the VMA was changed without its power being cycled afterward. Refer to the N2 Communications Bus Technical Bulletin (LIT ). Refer to the N2 Communications Bus Technical Bulletin (LIT ). Change each duplicate address to a unique number. Cycle power on the VMA. N2 Bus contains too many devices. A maximum of 100 N2 devices are allowed per NCM. VMA does not have power. Power the VMA. Remove the short from the +15 VDC to COM. N2 cable runs are broken. Locate and correct the wiring. EOL jumpers on NCM/N30 or Install EOL jumpers or W3 jumper properly. W3 jumper on MM-CVT101 are not installed. MM-CVT101 is not plugged into PC or 120 VAC source. There are Y or T taps or the repeater lost power or is wired wrong. N2 Bus wires open near the NCM. Connect the wires. Plug MM-CVT101 into PC or plug it into a 120 VAC source. Refer to the N2 Communications Bus Technical Bulletin (LIT ).
26 26 Troubleshooting VMA1400 Series Controllers Technical Bulletin Testing for N2 Bus Opens, Shorts, and Crossed Wires! CAUTION: To avoid electrical shocks when troubleshooting, measure the voltage of each N2 wire to earth ground with a 100 K ohm resistor at the DMM. If line-voltage is measured, have a qualified electrician locate the fault. Test for N2 Bus opens, shorts, and crossed wires by either selecting all of the N2 devices and performing a CommDisable at the Operator Workstation (OWS), or by connecting an MM-CVT101 in place of the NCM and verifying the NCM/N30 EOL separately. Use a DMM (digital voltmeter) to detect polarity, shorts, crossed wires, and grounds. To test for N2 Bus opens, shorts, and crossed wires: 1. Connect the DMM across the N2+ and REF screws on the N2 terminal block. 2. Write down the DC voltage reading. Repeat for N2- and REF, then for N2+ and N Compare the voltages on the DMM to the following values: N2+ to REF = to 2.98 VDC N2 to REF = to 2.54 VDC N2+ to N2 = to 0.92 VDC If the DMM readings are not approximately within the ranges listed above, the wire is grounded, shorted, or crossed with another wire. 4. Perform the following checks: Check that the polarity of the wiring is consistent from device to device all along the N2 Bus. Check for breaks in the 24 American Wire Gauge (AWG) (0.6 mm) wire. Check if the VMA is internally shorted by unplugging the N2 connector and measuring the voltages from Step 3 on the pins of the VMA. If these do not match Step 3 with power on the VMA, replace it. N2 Bus is improperly terminated. There must be one switched end-of-line device on each N2 Bus, typically the NCM or N30. N2 Bus wiring has T or Y connections installed.
27 Troubleshooting VMA1400 Series Controllers Technical Bulletin Correct and measure again. If the readings are approximately within the ranges listed above, the Bus is properly wired. Otherwise, proceed to Checking for Proper Device Isolation and Ground Loops. Verifying Proper Transformer Installation To verify proper transformer installation: 1. Connect the DMM across the 24 VAC and the 24 VAC common terminal of the VMA. Read the voltage with all typical loads energized. A reading of VAC is required when the line voltage is nominal. If the DMM reads a value less than 22 VAC, split the load in half and add a second transformer. 2. Check if the primary voltage matches the transformer s voltage rating. 3. Check the 24 VAC cable length versus wire gauge. 4. Recalculate the power requirements for the VMAs and loads on that transformer. If the procedures above did not correct the communications problem, refer to the N2 Bus Communications Technical Bulletin (LIT ) for more information. Checking for Proper Device Isolation and Ground Loops To check for proper device isolation and ground loops: 1. Connect the leads of the DMM in parallel with the 100 K ohm resistor from the DC power supply (+15 VDC) output terminal of the VMA to earth ground. 2. Read the voltage. If the voltage is 5 VDC/VAC or greater, the circuit is improperly isolated or a valve actuator is connected, which ties COM to an earth grounded Terminal 1. A single earth ground is allowed. 3. Remove all the field wires and N2 Bus wires from the VMA, but leave the transformer wires attached. 4. With the DMM still connected, reconnect each set of field wires one at a time until the voltage is 5 VDC/VAC or greater. At this point, you have discovered one cause of the ground loop. 5. Correct the problem. Continue to reconnect each set of field wires until all ground loops are found and corrected. All grounds are corrected when the voltage is less than 5 VDC/VAC on the DMM.
28 28 Troubleshooting VMA1400 Series Controllers Technical Bulletin Troubleshooting Heating Problems To troubleshoot heating problems: 1. In HVAC PRO software, switch to Commissioning view. 2. Check the VAV Box Mode Present Value parameter. Use Table 10 below to determine the next step based on the value of this parameter. Table 10: VAV Box Mode Present Value If the VAV Box Mode Present Value Is Then Cooling Check the Cooling PID Present Value. Go to Table 11. Satisfied Heating Check the Heating Available parameter (in the Command Mode parameter group) and the Actual Heating Setpoint parameter (in the Temperature Setpoint parameter group). Go to Table 13. Check the Box Heating PID Present Value. Go to Table 14. Note: The logic in this procedure also applies for supplemental heating. Table 11: Cooling PID Present Value If the Cooling PID Present Value Is Then = 0% Check the Cooling PID Saturation Status. Go to Table 12. > 0% VAV Box Mode does not switch to Satisfied until: PID deintegrates to 0% Saturation Status = Low (Saturation Status switches from Normal to Low after Cooling PID Present Value is equal to 0% for ten minutes.) Note: To test the heating mode and save time during commissioning, override the VAV Box Mode Present Value to Satisfied with the Zone Temperature less than the Actual Heating Setpoint. This bypasses the Cooling mode saturation timers.
29 Troubleshooting VMA1400 Series Controllers Technical Bulletin 29 Table 12: Cooling PID Saturation Status If the Cooling PID Saturation Status Is Normal Low Note: Then Wait ten minutes for Low Saturation time to expire. Note: Saturation times can be viewed in the Diagnostic View. On the Options menu, click View to change to Diagnostic view. Recheck VAV Box Mode Present Value. It now equals Satisfied. To test the heating mode and save time during commissioning, override the VAV Box Mode Present Value to Satisfied with the Zone Temperature less than the Actual Heating Setpoint. This bypasses the Cooling mode saturation timers. Table 13: Heating Available and Actual Heating Setpoint If Heating Available = False Actual Heating Setpoint > Zone Temperature and VAV Box Mode Present Value = Satisfied Then BD169 is being commanded from Metasys Supervisory System. Configuration was generated using HVAC PRO software Release 7.00 and saved using Release Workaround: Upgrade the controller in HVAC PRO software Release On the Upload menu, click Upgrade Controllers. See the Troubleshooting section of the Variable Air Volume Modular Assembly (VMA) 1400 Series Application Note (LIT ) for more information. Table 14: Box Heating PID Present Value If Box Heating PID Present Value is Then =0% Check Box Heating PID Saturation Status. Go to Table 15. >0% and Box Heating = either Binary Output (normally open valve) or Binary Output (normally closed valve) >0% and Box Heating = Electric 1-stage Check the Box Heating Make Limit parameter (in the Box Heating Output parameter group). The Box Heating PID Present Value must exceed the Box Heating Make Limit before the Box Heating Command Output will become active. Check the Box Heating Make Limit parameter (in the Box Heating Output parameter group). The Box Heating PID Present Value must exceed the Box Heating Make Limit before the Box Heating Output Present Value and EHS Box Heating Command Output will change from Off to Stage 1.
30 30 Troubleshooting VMA1400 Series Controllers Technical Bulletin Table 15: Box Heating PID Saturation Status If Box Heating PID Saturation Status is Low Normal Then Wait 60 seconds and recheck Box Heating PID Saturation Status. The status should change to normal. The period for the PID is 60 seconds, and it may take the full time to switch to Normal and begin to ramp up the PID. Wait for 60 seconds and recheck Box Heating PID Present Value. The period for the PID is 60 seconds, and it may take the full time to begin to ramp up the PID. Controls Group 507 E. Michigan Street P.O. Box 423 Milwaukee, WI Printed in U.S.A.
NEBB STANDARDS SECTION-8 AIR SYSTEM TAB PROCEDURES
NEBB STANDARDS SECTION-8 AIR SYSTEM TAB PROCEDURES 8.1 INTRODUCTION Testing, adjusting, and balancing of HVAC systems can best be accomplished by following a series of systematic procedures. The NEBB TAB
SLIM LINE FUME HOOD MONITOR
SLIM LINE FUME HOOD MONITOR Phoenix Controls FHM420 Fume Hood Monitor is sized to fit any fume hood and includes icons for simple and universal operation. The FHM420 slim line monitor works in conjunction
T 3 Series VAV Diffusers Analog Diffuser Steel Square Panel Horizontal Pattern Model: T 3 SQ
TSQ--0 7-7-07 T Series VAV Diffusers Analog Diffuser Steel Square Panel Horizontal Pattern Model: T SQ Model Configuration T SQ- Heating / Cooling Border Type (Lay-In) Full Face Nominal Round Duct Size
I nstallation. M100Q Series Proportional Actuator with R81Q Controller Board for Thermistor Sensor Applications. Tools Needed.
FANs 268.1, 1628.3 Installation Bulletin M100Q Issue Date 1099 M100Q Series Proportional Actuator with R81Q Controller Board for Thermistor Sensor Applications I nstallation Parts Included M110QGA-1 and
Thermo Top - Troubleshooting Tree
Thermo Top - Troubleshooting Tree 07-15-2002 CAUTION Troubleshooting requires comprehensive knowledge about the structure and theory of operation of the Thermo Top heater. Troubleshooting and repairs may
Fan Coil EC Motor Control
Fan Coil EC Motor Control G3 PWM BARD The Enviro-Tec Generation 3 PWM (G3 PWM) board provides a pulse-width modulated (PWM) signal to the EC motor to control fan speed. The board is factory programmed
Variable Air Volume - VAV
Mode Enable Sensor Options Variable Air Volume - VAV The temperature of this sensor will determine if the unit is in heating, cooling or vent mode during occupied operation. The following options are available:
DPT-2015 Differential Pressure Transmitter for VAV Box Applications
FANs 216, 1628.3 Product/Technical Bulletin DPT-2015 Issue Date 1298 DPT-2015 Differential Pressure Transmitter for VAV Box Applications The DPT-2015 Differential Pressure Transmitter senses differential
EVANS ELECTRONIC TEMPERATURE CONTROL TROUBLESHOOTING GUIDE for systems equipped with electric coolant valve and external PC board.
EVANS ELECTRONIC TEMPERATURE CONTROL TROUBLESHOOTING GUIDE for systems equipped with electric coolant valve and external PC board. This Troubleshooting Guide covers the electric coolant valve and control
Troubleshooting and Diagnostics
Troubleshooting and Diagnostics The troubleshooting and diagnostics guide provides instructions to assist in tracking down the source of many basic controller installation problems. If there is a problem
Heater and Air Conditioner, Blend Air System, Troubleshooting 83.06
A/C Performance Diagnosis Problem Warm Airflow When the Air Conditioner is On, A/C Not Working, or Poor A/C Performance (dash outlet temperature is too high) Problem Warm Airflow When the Air Conditioner
T7560A,B,C Digital Wall Module
T7560A,B,C Digital Wall Module HONEYWELL EXCEL 5000 OPEN SYSTEM BEFORE INSTALLATION All wiring must comply with local electrical codes and ordinances or as specified on installation wiring diagrams. Digital
TAC I/NETTM MR-VAV-AX. Application Specific MicroRegulator TM
TAC I/NETTM TM TAC s TM has an extensive range ofpre-engineered VAV control sequences, which combined with a fully integrated actuator and airflow transducer, makes it a low Total Installed Cost solution
MP-4000 Alarm List (Software version 2.4.3 or later)
Service Bulletin SUBJECT: MP4000 Alarm s BULLETIN: C 100 DATE: June 19, 2013 ALARM LIST Where it is possible the alarm number is kept the same as for MP-3000. MP-3000 holds alarm number from 0 to 127.
R22. K Control. Indoor Unit. Nomenclature. Compatibility PL H 3 G K H B. Unit style Heat Pump Horse Power
R22. K Control. Indoor Unit. Nomenclature. PL H 3 G K H B Compatibility Unit style Heat Pump Horse Power Control Boost Heaters R22. K Control. Outdoor Unit. Nomenclature. PU H 3 Y K A Compatibility Outdoor
G670 Intermittent Pilot Ignition Controls
Installation Sheets Manual 121 Gas Combustion Combination Controls and Systems Section G Technical Bulletin Issue Date 0300 Intermittent Pilot Ignition Controls Figure 1: Intermittent Pilot Ignition Control
12 Volt 30 Amp Digital Solar Charge Controller
12 Volt 30 Amp Digital Solar Charge Controller User s Manual WARNING Read carefully and understand all INSTRUCTIONS before operating. Failure to follow the safety rules and other basic safety precautions
LG Air Conditioning Multi F(DX) Fault Codes Sheet. Multi Split Units
Multi Split Units If there is a fault on any LG Multi unit, an Error mark is indicated on the display window of the indoor unit, wired-remote controller, and LED s of outdoor unit control board. A two
Hydraulic Troubleshooting PRESENTED BY
Hydraulic Troubleshooting PRESENTED BY NORMAN KRONOWITZ Introduction Welcome to the CMA/Flodyne/Hydradyne s Hydraulic Troubleshooting presentation. We will introduce many aspects of troubleshooting hydraulic
ASC and N2 Bus Networking and Troubleshooting Guide
Application Specific Controllers Technical Manual 636.3 Introduction Section Technical Bulletin Issue Date 0995 ASC and N2 Bus Networking and Troubleshooting Guide Introduction Page 3 Overview *3 Who Should
Modular I/O System Analog and Digital Interface Modules
OPERATING INSTRUCTIONS Modular I/O System Analog and Digital Interface Modules Installation Operation Maintenance Document Information Document ID Title: Operating Instructions Modular I/O System Part
Non-Isolated Analog Voltage/Current Output module IC695ALG704 provides four configurable voltage or current output channels. Isolated +24 VDC Power
July 2010 PACSystems* RX3i Non-Isolated Analog Output Module with HART Communications, IC695ALG728 Non-Isolated Analog Output Modules, IC695ALG704, IC695ALG708 MODULE OK FIELD STATUS TB IC695ALG708 Q1
Digi-Motor Installation Guide
Digi-Motor Installation Guide Installation Video...located at marsdelivers.com Digi-Motor Installation Guide Digi-Motor For technical assistance with your Azure Digi-Motor, call the MARS technical support
Duct Humidity Transmitter
SDC-H Duct Humidity Transmitter Features Replaceable sensor element Humidity measurement for air ducts Minimum and maximum value memory 0 0V, 0 0mA or 0V, 4 0mA measuring signals selectable with jumpers
ABB Drives. User s Manual. Pulse Encoder Interface Module RTAC-01
ABB Drives User s Manual Pulse Encoder Interface Module RTAC-0 Pulse Encoder Interface Module RTAC-0 User s Manual 3AFE 64486853 REV A EN EFFECTIVE:.5.00 00 ABB Oy. All Rights Reserved. Safety instructions
A99B Series Temperature Sensors
FANs 125, 121, 930, 930.5 Product/Technical Bulletin A99 Issue Date 0615 A99B Series Temperature s The A99B Series Temperature s are passive PTC (Positive Temperature Coefficient) sensors. The A99B sensors
ECM. Service Guide. www.thedealertoolbox.com
ECM Service Guide www.thedealertoolbox.com ECM Table of Contents Service Guide Working on the motor with power connected may result in electrical shock or other conditions that may cause personal injury,
PRODUCT PROFILE FEATURES
PRODUCT PROFILE Pressure Transmitters & Pneumatic Transducer Airflow Transmitter, Differential Air Pressure Transmitter and Differential & Gauge Liquid/Gas Pressure Transmitter FEATURES AIRFLOW TRANSMITTER
PNEUMATIC CONTROLS Selection and Description
PNEUMATIC CONTROLS Selection and Description Carnes pneumatic controlled throttling units are suitable for a standard 20 psi control system and may be supplied with pressure dependent or pressure independent
T-4000 Series Room Thermostat Adjusting Instructions*
Pneumatic Control Manual 717.1 Room Devices Section Technical Bulletin T-4000 Issue Date 0814 T-4000 Series Room Thermostat Adjusting Instructions* The T-4000 Series Pneumatic Room Thermostats are factory
A/C-HEATER SYSTEM - AUTOMATIC
A/C-HEATER SYSTEM - AUTOMATIC 1995 Volvo 850 1995-96 Auto. A/C-Heater Systems Volvo 850 * PLEASE READ THIS FIRST * WARNING: To avoid injury from accidental air bag deployment, read and carefully follow
Service Information CALIBRATION PROCEDURE AND TROUBLESHOOTING FOR LINEAR GOVERNOR CONTROLLERS NOTE
Service Information Calibration & Adjustments CALIBRATION PROCEDURE AND TROUBLESHOOTING FOR LINEAR GOVERNOR CONTROLLERS Part Number DYN1-10752-000-0-12/24 DYN1-10752-001-0-12/24* DYN1-10753-000-0-12/24
PRODUCTIVITY THROUGH INNOVATION 600 CONTROL DIRECT DRIVE TECHNICAL/OPERATION MANUAL
Rev. D PRODUCTIVITY THROUGH INNOVATION 600 CONTROL DIRECT DRIVE TECHNICAL/OPERATION MANUAL 10 BORIGHT AVENUE, KENILWORTH NEW JERSEY 07033 TELEPHONE: 800-524-0273 FAX: 908-686-9317 TABLE OF CONTENTS Page
TECHNICAL SERVICE DEPARTMENT Technical Service Bulletin 1-800-432-8373. 2 Inch PowerVent LED Indicator Explanations & Troubleshooting Table
New Robertshaw control valve was introduced in May 2008 as a replacement part. See last page for troubleshooting this replacement part. All voltage inputs are 120V. All electrical connectors are Molex
All of the above software and firmware are included in the VAV-B Package. Contact Customer Service or Technical Support for this, or for cables.
Updated 03-07-2012 VAV-B Programming Manual CBAS version 11.1.9 or newer Firmware version 13.7 or newer on Host controller USB to 485 commissioning cable (need part number) or USB Isolator (B&B Electronics
GPD 506/P5 Start-up Procedure and Checklist
GPD 506/P5 Start-up Procedure and Checklist Preparation for GPD506/P5 Drive Start-Up...2 HVAC Start-Up Procedure for GPD 506/P5 WITH Bypass Option:...4 HVAC Start-Up Procedure for GPD 506/P5 WITHOUT Bypass
ABB Drives. User s Manual HTL Encoder Interface FEN-31
ABB Drives User s Manual HTL Encoder Interface FEN-31 HTL Encoder Interface FEN-31 User s Manual 3AUA0000031044 Rev B EN EFFECTIVE: 2010-04-06 2010 ABB Oy. All Rights Reserved. 5 Safety instructions
Troubleshooting accelerometer installations
Troubleshooting accelerometer installations Accelerometer based monitoring systems can be tested to verify proper installation and operation. Testing ensures data integrity and can identify most problems.
SX460. Generator Automatic Voltage Regulator Operation Manual
SX460 Generator Automatic Voltage Regulator Operation Manual Self Excited Automatic Voltage Regulator Compatible with Newage SX460* * Use for reference purpose only and not a genuine Newage product. 1.
Section 7. Evaporator thermistor. Under-and-over pressure safety switches. Connections to the ECU
Automatic Temperature Control Diagnosis and Repair Diagnosis of Automatic A/C Systems The most common automatic A/C system malfunctions tend to be the result of basic air conditioning problems. These problems
543-0032-00, 943-0032-00. User s Manual
543-0032-00, 943-0032-00 User s Manual 1 Comfort Alert Diagnostics Faster Service And Improved Accuracy The Comfort Alert diagnostics module is a breakthrough innovation for troubleshooting heat pump and
M9102-AGA-2S, -3S and M9104-xxA-2S, -3S Series Electric Non-Spring Return Actuators
M9102-AGA-2S, -3S and M9104-xxA-2S, -3S Series Electric Non-Spring Return Actuators Product Bulletin Code No. LIT-1201742 Issued February 12, 2015 The M9102 and M9104 Series Actuators are directmount,
CDS TROUBLESHOOTING SECTION I. VACUUM. 1.0. Weak vacuum at wand. Gauge reads normal (10hg to 14hg)
CDS TROUBLESHOOTING SECTION I. VACUUM 1.0. Weak vacuum at wand. Gauge reads normal (10hg to 14hg) 1.1. Clogged hoses or wand tube. Disconnect hoses and carefully check for an obstruction. 1.2. Excessive
* DISCLAIMER: Contents. How to Use This Guide: COMMERCIAL INSTALL GUIDE 2
COMMERCIAL INSTALL GUIDE 2 Contents How to Use This Guide: The first section of this guide is designed to assist you with the installation of your DECK Monitoring hardware. The revenue grade meter and
Pneumatic Control Module User s Guide
Pneumatic Control Module User s Guide Revision 1.3 Cross The Road Electronics www.crosstheroadelectronics.com Cross The Road Electronics Page 1 1/24/2016 Table of Contents 1. Pneumatics Control Module
Workshop 7 PC Software - Tracker
Workshop 7 PC Software - Tracker Goal: You will startup and perform advanced setup functions using Tracker PC software. You will also setup equations to control MP503 binary outputs. The Binary Output
Radiant Temperature Sensor TY7321
AB-5361-U Specifications/Instructions Radiant Temperature TY7321 General TY7321 Radiant Temperature s are designed to measure infrared radiation from perimeter windows and walls and provide a proportional
PIEZOMETER AIRFLOW MEASURING RING
PIEZOMETER AIRFLOW MEASURING RING M.K. Plastics is pleased to introduce The Piezometer Airflow Measuring Ring, now available as an accessory for our steel Axijet fans. The system consists of a Piezometer
E-PDD Duct Smoke Detector Installation Sheet
E-PDD Duct Smoke Installation Sheet Operation The duct smoke detector's primary purpose is to provide early warning of an impending fire and shut down the HVAC unit in order to prevent smoke from circulating
Oil and Coolant Circulating Heating System. Model - OCSM
Oil and Coolant Circulating Heating System Model - OCSM Installation & Operation Manual 216280-000 REV 2 Identifying Your System The HOTSTART heating system is designed to heat fluids for use in marine
Chapter 7 Hydraulic System Troubleshooting
Chapter 7 Hydraulic System Troubleshooting General The following troubleshooting information is provided as a general guide to identify, locate and correct problems that may be experienced with the hydraulic
Manual Ranging MultiMeter
Owner s Manual Manual Ranging MultiMeter Model 82345 CAUTION: Read, understand and follow Safety Rules and Operating Instructions in this manual before using this product.! Safety! Operation! Maintenance!
Whale 3. User Manual and Installation Guide. DC Servo drive. Contents. 1. Safety, policy and warranty. 1.1. Safety notes. 1.2. Policy. 1.3. Warranty.
Whale 3 DC Servo drive User Manual and Installation Guide Contents 1. Safety, policy and warranty. 1.1. Safety notes. 1.2. Policy. 1.3. Warranty. 2. Electric specifications. 2.1.Operation ranges. 3. Connections
TECHNICAL SERVICE DEPARTMENT Technical Service Bulletin 1-800-432-8373. Tankless Electric (RTE) Troubleshooting
Sequence of Operations 1 Power supply and field wiring block 2 Energy Cut Off (ECO) 3 Water flow plunger and cold inlet 4 Magnetic flow switch 5 Water temperature thermistor 6 Control panel and circuit
Instruction Manual. 2in1 LAN Tester & Multimeter. Model: LA-1011
Instruction Manual 2in1 LAN Tester & Multimeter Model: LA-1011 1 Contents Introduction... Features... Safety Precautions.. Meter Description... Electrical Specification... Operation.. AutoRanging Multimeter.
CONNECTOR AMPLIFIER FOR PROPORTIONAL VALVES (4-20 ma Input Version)
TECHNICAL DATASHEET #TD1102AX CONNECTOR AMPLIFIER FOR PROPORTIONAL VALVES (4-20 ma Input Version) Part Number: Connector Amplifier CAPV-H-4-20MA-x complete with cable CAPV-4C-yM Where: x = current output
Appliance Diagnostic Modes Microwave. GE Consumer & Industrial Technical Training
Appliance Diagnostic Modes Microwave GE Consumer & Industrial Technical Training Range Table of Contents General Microwave JVM230/240/250B Series (#31-20100) JVM2070 Series (#31-9111) ZMC3000B Series (#31-1461)
Single Channel Loop Detector
Single Channel Loop Detector Model - LD100 Series The LD100 is a single channel inductive loop detector designed for parking and access control applications. The detector is connected to an inductive loop
Model 201 Wiegand Touchpad Reader Installation Guide
Model 201 Wiegand Touchpad Reader Installation Guide P/N 460353001C 15AUG11 2011 UTC Fire & Security. All rights reserved. This document may not be copied in whole or in part or otherwise reproduced without
System 350 A350E Electronic Cooling Control
FANs 930, 930.5, 125, 121 Product/Technical Bulletin A350E Issue Date 0899 System 350 A350E Electronic Cooling Control The A350E is an on/off, electronic, cooling-only control with Single-Pole, Double-Throw
NC-12 Modbus Application
NC-12 Modbus Application NC-12 1 Table of Contents 1 Table of Contents... 2 2 Glossary... 3 SCADA...3 3 NC-12 Modbus in general... 3 4 Entire system... 4 4.1 PFC to PC connection alternatives...4 4.1.1
T0118 T2118 T3118. Instruction Manual
Programmable indoor transmitter of temperature T0118 Programmable indoor transmitter of atmospheric pressure T2118 Programmable indoor transmitter of temperature, relative humidity and other derived humidity
General Information... 2
Pneumatic VAV Reset Volume Controllers CSC 2000 Series Applications Guide General Information... 2 CSC 2000 Series Overview...2 odels and Specifications...3 ounting...4 Connections...4 All Units...4 Beige
A.Y. McDonald Mfg. Co. Troubleshooting Submersible and Jet Pumps
A.Y. McDonald Mfg. Co. Troubleshooting Submersible and Jet Pumps Troubleshooting Submersible Pumps Fuse overload or circuit breaker trips when motor is started 1. Incorrect line voltage. Check the line
Allen-Bradley/Rockwell
MANUFACTURER DATA SHEET High Speed Counter Manufacturer: Allen-radley/Rockwell Model Number: 1746-HSCE See www.geomartin.com for additional PDF datasheets Martin Part Number: E-014901-03 VendorPartNumber:
FAQ s on Siemens Magmeters
FAQ s on Siemens Magmeters 1. The cables for the coils and electrodes for the magmeters look the same. Does it matter which cable is used for coils and which one is used for the electrodes? Both cables
PD 100A. Printing data system
PD 100A Printing data system Operating instructions ENGLISH IMPORTANT: Read these instructions carefully before installing and using the device; do not forget following all additional information. Keep
Electronic Control Devices The European Product Catalogue 2007
FX14 Field Controller (1/4) FX14 Field Controller The FX14 is an equipment field controller in the Facility Explorer range of products. The controller is designed specifically for commercial Heating, Ventilating,
RI-215A Operator s Manual. Part Number: 71-0045RK Revision 0 Released: 10/3/05
RI-215A Operator s Manual Part Number: 71-0045RK Revision 0 Released: 10/3/05 Warranty RKI Instruments, Inc., warrants gas alarm equipment sold by us to be free from defects in materials and workmanship,
PID Microprocessor temperature controllers CTD43 - CTD46 - CTH46
PID Microprocessor temperature controllers CTD43 - CTD46 - CTH46 Display 1. Red measurement display (or the set point for CTD 43 by pressing, indicated by a flashing decimal point). 2. Green display of
Essential Electrical Concepts
Essential Electrical Concepts Introduction Modern vehicles incorporate many electrical and electronic components and systems: Audio Lights Navigation Engine control Transmission control Braking and traction
THERMAL ANEMOMETRY ELECTRONICS, SOFTWARE AND ACCESSORIES
TSI and TSI logo are registered trademarks of TSI Incorporated. SmartTune is a trademark of TSI Incorporated. THERMAL ANEMOMETRY ELECTRONICS, SOFTWARE AND ACCESSORIES IFA 300 Constant Temperature Anemometry
Evaluate, Clean, and Tune Guidance
Evaluate, Clean, and Tune Guidance The Evaluate, Clean and Tune (ECT) process serves three essential purposes in the Weatherization Assistance Program (WAP). The first is to evaluate the existing system
Installation Manual. Rental Services. Air Handling Units CHS-SVN01A-EN. July 2008
Installation Manual Rental Services Air Handling Units July 2008 CHS-SVN01A-EN Copyright 2008 Trane All rights reserved This document and the information in it are the property of Trane and may not be
Technical Information
Date of last update: Oct-11 Ref: D7.8.4/1011/E Application Engineering Europe CORESENSE DIAGNOSTICS FOR STREAM REFRIGERATION COMPRESSORS CoreSense Diagnostics for Stream Refrigeration Compressors... 1
LS1024B / LS2024B/ LS3024B. Solar Charge Controller USER MANUAL
EPSOLAR LS1024B / LS2024B/ LS3024B Solar Charge Controller USER MANUAL Thank you very much for selecting our product! This manual offers important information and suggestions with respect to installation,
AXIS T81B22 DC 30W Midspan
INSTALLATION GUIDE AXIS T81B22 DC 30W Midspan ENGLISH About this Document This document includes instructions for installing AXIS T81B22 on your network. Previous experience of networking will be beneficial
Installing the Tracer ZN517 Unitary Controller Ordering number: 4950 0496, 4950 0596
Installing the Tracer ZN517 Unitary Controller Ordering number: 4950 0496, 4950 0596 Product overview The Tracer ZN517 controller is a field-installed, application-specific controller that provides directdigital
EMBEDDED ACCESS CONTROL Hardware Installation Guide
EMBEDDED ACCESS CONTROL Hardware Installation Guide Lenel goentry Hardware Installation Guide, product version 1.00. This guide is item number DOC- ENHW-ENU, revision 1.003, April 2009 Copyright 2009 Lenel
OPL BASIC. Dosing System for Professional Laundry machines. Contents
OPL BASIC Dosing System for Professional Laundry machines Contents 1 Getting Started. Page 2 2 Installation. Page 4 3 Set Up & Operation. Page 8 4 Maintenance & Accessories. Page 10 5 Troubleshooting Page
ECM Blower Motor Replacement Controls Programming Process
COMPONENT PARTS SERIES Installation, Operation & Maintenance Instructions TABLE OF CONTENTS Section 1: Field Troubleshooting Procedures 2 Section 2: Field Control Replacement Procedure 3 ECM Connections
Operational Overview and Controls Guide
DOCUMENT: ECSEQ2-1 EFFECTIVE: 02/14/07 SUPERSEDES: 02/26/03 Operational Overview and Controls Guide Standard Two or Three Pump Type VFD Booster Controls 6700 Best Friend Road. Norcross, GA 30071. (770)
Installation Instructions. Before Installation. Read these installation instructions carefully before commissioning the pressure transmitter.
Installation Instructions Differential Air-pressure Transmitter Catalog Numbers 1414-IPZ10FODAA, 1414-IPZ10FNDAA, 1414-IPD10FNRAA, 1414-CPZ10FODAA, 1414-CPZ10FNDAA, 1414-CPD10PNRAA Topic Page Before Installation
User Manual for CH-PFC76810
AA Portable Power Corp www.batteryspace.com, Email: [email protected] User Manual for CH-PFC76810 1. Overview The CH-PFC76810 charger is suitable for charging lithium ion battery packs such as those
Technical Manual. FAN COIL CONTROLLER COOLING or HEATING ANALOG or PWM Art. 119914 631001A
COOLING or HEATING ANALOG or PWM Art. 119914 631001A TOTAL AUTOMATION GENERAL TRADING CO. LLC SUITE NO.506, LE SOLARIUM OFFICE TOWER, SILICON OASIS, DUBAI. UAE. Tel. +971 4 392 6860, Fax. +971 4 392 6850
Fossil fuel heating equipment
Fossil fuel heating equipment principles and troubleshooting techniques Application Note This application note was written to provide you with an understanding of the basic principles of fossil fuel heating
KNX TH65-AP. Thermo-Hygrometer. Technical specifications and installation instructions Item number 70184
EN KNX TH65-AP Thermo-Hygrometer Technical specifications and installation instructions Item number 70184 Elsner Elektronik GmbH Control and Automation Engineering Herdweg 7 D 75391 Gechingen Phone +49
ESPD8-301R MODEL ESP-D FAN COIL UNIT TROUBLESHOOTING GUIDE
ESPD8-301R MODEL ESP-D FAN COIL UNIT TROUBLESHOOTING GUIDE Protected by one or more of the following U.S. Patents (3,507,354; 3,575,234; 3,596,936; 3,605,797; 3,685,329; 4,045,977; 4,698,982; 926,673 and
*.ppt 11/2/2009 12:48 PM 1
Digital Compressor Controller *.ppt 11/2/2009 12:48 PM 1 Copeland Scroll Digital Controller Simple Controller That Enables OEM s To Use Digital Scrolls Relieves OEM From Developing Special Controllers
Trouble Shooting BD & TW Compressor Systems 12 and 24 Volt
Trouble Shooting BD & TW Compressor Systems 12 and 24 Volt Determine the Model. The data plate is on the left end near the wiring entrance. BD - BD air* TW - Tradewinds air** BDAW - BD air/water TWAW -
Installation and Operation Manual Back-UPS BX800CI-AS/BX1100CI-AS
+ Installation and Operation Manual Back-UPS BX800CI-AS/BX1100CI-AS Inventory Safety and General Information bu001c This unit is intended for indoor use only. Do not operate this unit in direct sunlight,
LG Air Conditioning - Universal Split Fault Codes Sheet. Universal Split Systems
Universal Split Systems If there is a fault on any LG Universal unit, a two digit number will appear on the remote controllers led display. If the unit does not have a remote controller the fault will
Commercial Refrigeration Temperature and Defrost Controls
Commercial Refrigeration Temperature and Defrost Controls UNI-LINE PRODUCT KNOWLEDGE 2010 Invensys. All Rights Reserved. The names, logos, and taglines identifying the products and services of Invensys
http://waterheatertimer.org/how-to-troubleshoot-gas-water-heater.html
http://waterheatertimer.org/how-to-troubleshoot-gas-water-heater.html TECHNICAL SERVICE DEPARTMENT Effective October 2007, we transitioned to the White Rodgers (Intelli-Vent TM )Thermostat Control for
User Manual. Air-conditioner Controller SB-DN-HVAC (MAC01.331) www.hdlautomation.com
Air-conditioner Controller SB-DN-HVAC (MAC01.331) www.hdlautomation.com Document updates: Version Data Description V1.0 2015.05.25 Finish new document HVAC Controller User Manual INDEX 1. Overview...1
INTRODUCTION WARNING S!!! VOC SHOULD BE BETWEEN 78 95. MUST NOT EXCEED 96 VOC USE DC CIRCUIT BREAKER/ISOLATOR BETWEEN SOLAR PANELS & CONTROLLER
INTRODUCTION Thank you for purchasing a WATERBOY pumping system. We set the standard for quality and economy in solar pumping. The WATERBOY range incorporates the best solar pump technologies that were
Contents. Document information
User Manual Contents Document information... 2 Introduction... 3 Warnings... 3 Manufacturer... 3 Description... Installation... Configuration... Troubleshooting...11 Technical data...12 Device Scope: PCB
Central Plant Air Systems: Keeping the Heart and. Title Style. Better Buildings Summit May 2016
Central Plant Air Systems: Keeping the Heart and Click Lungs To Healthy Edit Master Title Style Better Buildings Summit May 2016 Introductions Michael Deru National Renewable Energy Laboratory New Resources
4 Troubleshooting Your Projector
4 Troubleshooting Your Projector If you experience problems with your projector, see the following troubleshooting tips. If the problem persists, contact Dell (see Contacting Dell on page 57). Problem
