G670 Intermittent Pilot Ignition Controls

Save this PDF as:
 WORD  PNG  TXT  JPG

Size: px
Start display at page:

Download "G670 Intermittent Pilot Ignition Controls"

Transcription

1 Installation Sheets Manual 121 Gas Combustion Combination Controls and Systems Section G Technical Bulletin Issue Date 0300 Intermittent Pilot Ignition Controls Figure 1: Intermittent Pilot Ignition Control Description Application Requirements The is a n-100% Lockout Intermittent Pilot Ignition (IPI) control that replaces the G67AG and G67BG ignition controls. The is used to automatically light a pilot burner and energize the main burner gas valve in response to a call for heat from the system thermostat. When the call for heat is satisfied, the thermostat opens and the de-energizes the pilot and main burner gas valves. Following are the application requirements of the control. The can be used with equipment with a maximum firing rate of 117 kw (400,000 Btu/hr). Any application greater than 117 kw (400,000 Btu/hr) must have written approval in advance from the Heating Products Engineering Department. All applications must use a redundant gas valve system with the main valve seats in series Johnson Controls, Inc. 1 Part , Rev. B Code. LIT

2 Table 1: Specifications Ignition Type Ignition Source High Voltage Cable Length Flame Detection Means Flame Detection Types Minimum Flame Current Flame Failure Response Time Spark Gap Ignition Trial Time Indirect High voltage spark, capacitive discharge 915 mm (36 in.) maximum Flame rectification Remote sensing 0.2 microampere 0.8 second, maximum 2.5 mm (0.1 in.) nominal Infinite Power Requirements Control: 24 VAC, 50/60 Hz, nominal Operation Current: 0.15A nominal + valves Contact Rating Main Valve: 2A continuous, 5A inrush Pilot Valve: 2A continuous, 5A inrush Ambient Operating and -40 to 66 C (-40 to 150 F) Storage Temperature Humidity 95% RH non-condensing Types of Gas Natural (Liquefied Petroleum [LP], manufactured, mixed, or LP gas-air mixture may be used in a well vented or outdoor application.) Agency Listing CSA (AGA/CGA) Certificate Number Specification Standards ANSI Standard Z21.20 CSA C The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these specifications, consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. Operating Mode Definitions The following definitions describe operating conditions. Trial for Ignition--Period during which the pilot valve and spark are activated attempting to ignite gas at the main burner. The trial-for-ignition period is infinite for the s and ends once the pilot flame is detected or the call for heat ends. Run--The main valve remains energized and the spark is turned off after successful ignition. Flameout--Loss of proven flame. Should a flameout occur, the main valve closes and the spark recurs within 0.8 second. 2 G Intermittent Pilot Ignition Controls Technical Bulletin

3 Sequence of Operation Figure 2 illustrates the sequence of operation for the ignition control. On a call for heat from the system thermostat, the simultaneously opens the pilot valve and supplies a continuous spark to the pilot burner s electrode. When the pilot burner gas ignites, the pilot flame sensor detects the pilot flame and signals the to energize the main gas valve and discontinue the spark. The main gas valve will not be energized until the flame sensor detects the presence of the pilot flame. If the pilot flame goes out (with the thermostat still calling for heat), the will de-energize the main gas valve and provide a continuous spark at the pilot burner s electrode. When the pilot flame is re-ignited and detected by the pilot flame sensor, the main gas valve is energized and the spark is shut off. The de-energizes the pilot gas valve and main burner gas valve when the thermostat stops calling for heat. Start Thermostat Call for Heat Flame Present? Trial for Ignition Pilot Flame Sensed? Energize Main Valve Run Flameout? De-energize Main Valve Thermostat Calling for Heat? De-energize Control Pilot and Main Valves End Figure 2: Sequence of Operation G Intermittent Pilot Ignition Controls Technical Bulletin 3

4 Installation IMPORTANT: These instructions are intended as a guide for qualified personnel installing or servicing Johnson Controls ignition controls. Carefully follow all instructions in this bulletin and all instructions on the appliance. Limit repairs, adjustments, and servicing to the operations listed in this bulletin or on the appliance.! WARNING: Fire or Explosion Hazard. Avoid serious injury by carefully following precautions in this bulletin and all instructions on the appliance. Limit repairs, adjustments, and servicing to the operations listed in this bulletin or on the appliance.! WARNING: Fire or Explosion Hazard. If the control is installed in an area that is exposed to water (dripping, spraying, rain, etc.), it must be protected. If the control has been exposed to water in any way, do not use it.! WARNING: Shock Hazard. Avoid electrical shock and equipment damage. Disconnect electrical power and turn off the gas before wiring the control.! CAUTION: Equipment Damage Hazard. Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation. Verify proper operation after servicing. Mounting Perform the following procedure to install the ignition control. 1. Shut off power to the appliance. 2. Turn off gas at the manual shutoff valve adjacent to the appliance. 3. Label each wire with the correct terminal designation prior to disconnection. 4. Disconnect the power supply (transformer) and the thermostat lead wire at the ignition control. 5. Disconnect the sensing probe lead from Terminal 4 on the ignition control. 6. Disconnect the high voltage cable from the spark transformer. 7. Disconnect the Pilot Valve 1 and Main Valve 3 leads from the ignition control. 8. Disconnect any wires connected to the ground terminals on the ignition control. 4 G Intermittent Pilot Ignition Controls Technical Bulletin

5 9. Remove the screws holding the ignition control assembly in place. 10. Remove the ignition control and discard. 11. Using the same holes as the old ignition, mount the new control on a grounded metal surface with metal screws or bolts through the mounting holes provided on the enclosure. Modifying Existing Ignition Cable All spark ignition controls have a spark transformer connected to a high voltage cable. There are three types of connection for the high voltage cable: Spike, Rajah, and 6.35 mm (1/4 in.) male spade (see Figure 3). The has a Spike transformer. When replacing a control that has a Rajah or male spade connection, the crimp-on connector must be cut off. 1. Slide the rubber boot up the cable. 2. Cut the lead just above the connector (see Figure 4). Make a straight cut perpendicular to the cable. 3. Center the exposed wire on the end of the lead over the spike in the spark transformer and push the wire lead down firmly over the spike (see Figure 5). 4. Ensure the lead is inserted all the way into the spark transformer. Slide the boot back down the cable and over the spark transformer. Spike Connection Rajah Connection 6.35 mm (1/4 in.) Male Spade Figure 3: High Voltage Cable Connectors High Voltage Cable Insulating Boot Crimp-on Connector Cut off connector here. Figure 4: High Voltage Cable with Crimp-On Connector High Voltage Cable Spike must be in contact with the center wires. Figure 5: Spark Transformer Connection G Intermittent Pilot Ignition Controls Technical Bulletin 5

6 Wiring! CAUTION: Equipment Damage Hazard. Connect the high voltage cable to the spark transformer terminal and spark electrode (pilot burner assembly) before applying power to the control. Ensure the ground wire is attached to the pilot burner and control ground terminal strip.! CAUTION: Equipment Damage Hazard. Locate all limit and operating controls in series with the thermostat terminal (THS 2) on the ignition control. Check the voltage rating marked on the control and make sure it is suited to the application. Use a National Electrical Code (NEC) Class 2 transformer to provide 24 VAC under maximum load, including valves. A transformer having excessive primary impedance due to poor coupling will affect the ignition potential. Refer to Figures 6 through 9 for wiring diagrams. All wiring should be in accordance with the NEC and all other local codes and regulations. The high voltage spark transformer cable must not be in continuous contact with a metal surface. Use standoff insulators. Ensure that the flame sensor wire and the high voltage spark transformer cable are separated from one another by a minimum distance of 6.35 mm (1/4 in.) and are not wrapped around any pipe, other wiring, or accessories. 6 G Intermittent Pilot Ignition Controls Technical Bulletin

7 Thermostat Limits in the Thermostat Line Only W R Y MV Jumper PV in 24 VAC Power Supply Pilot Burner Ground Ground Terminals Flame Sensor High Voltage Cable Figure 6: ment Wiring Diagram if the Original Control is a G67AG Thermostat W R Y Limits in the Thermostat Line Only MV PV Jumper 5 24 VAC Power Supply Pilot Burner Ground Ground Terminals Flame Sensor Install the jumper supplied with the replacement control between Terminals 2 and 6. High Voltage Cable Figure 7: ment Wiring Diagram if the Original Control is a G67BG G Intermittent Pilot Ignition Controls Technical Bulletin 7

8 Thermostat High Limits In This Line Only W R Y MV Y79 MV PV Power Supply 24 VAC PV Jumper 5 Brown White Pilot Burner Ground Black Flame Sensor Install the jumper supplied with the replacement control between Terminals 2 and 6. High Voltage Cable Figure 8: Wiring Diagram for with Y79B Thermostat W R Y Y79 THS High Limits In This Line Only MV PV Jumper 5 24 VAC White Power Supply Pilot Burner Ground Red Black Flame Sensor High Voltage Cable Figure 9: Wiring Diagram for with a Y79A 8 G Intermittent Pilot Ignition Controls Technical Bulletin

9 Checkout and Startup Procedure! WARNING: Fire or Explosion Hazard. Avoid personal injury or property damage by making sure the control functions properly and there are no gas leaks. Follow this checkout and startup procedure before leaving the installation.! WARNING: Fire or Explosion Hazard. Do not attempt to check out this system by manually lighting the pilot. This could energize the main valve. Make sure all components are functioning properly by performing the following shutoff test. 1. With the gas and thermostat off, turn on power to the appliance. 2. Turn on the thermostat to the highest setting and verify that the control goes through the operating sequence to a shutoff condition. te: The burner will not light because the gas is off. 3. Turn off the thermostat. 4. Turn on the gas and purge gas lines of all air. 5. Test for gas leaks on all pipe joints and connections upstream of the gas valve with a soap solution. 6. Turn on the thermostat to the highest setting and verify successful ignition and a normal run condition for at least three minutes. If the appliance fails to run, see the Service Checkout Procedures section. 7. Test for leaks on all pipe joints and connections downstream of the gas valve with a soap solution. 8. Turn the thermostat down for at least 30 seconds and then back up again. Verify successful ignition at least three times. 9. Return the thermostat to a normal temperature setting before leaving the installation. G Intermittent Pilot Ignition Controls Technical Bulletin 9

10 Thermostat Heat Anticipator Settings The thermostat anticipator setting is normally equal to the ignition system current draw, plus that of the pilot and main valve. Due to variations in appliance wiring and valves, it is advisable to measure the actual current draw of the heating system at the thermostat location. Measuring this current can be accomplished by opening the thermostat contacts (lowering the set point) and installing an AC ammeter across the terminals, or by using a clamp-on ammeter with a 10-turn multiplier attached to the terminals (see Figure 10). IMPORTANT: Measuring the current with an ammeter will energize the system. Wait until the gas valve and inducer energize before taking a current draw measurement. To Heating System W R AC Ammeter Low Scale Setting To Heating System W R Ten Turns Clamp-on Ammeter (Divide reading by ten.) Figure 10: Measuring the Thermostat Current 10 G Intermittent Pilot Ignition Controls Technical Bulletin

11 Troubleshooting Procedure Preliminary Checks Failure Conditions and Corrective Action If the system does not function properly, determine the cause using the procedures in this section. Before proceeding with troubleshooting the system, check the following: Are all mechanical and electrical connections tight? Is the system wired correctly? Is the gas inlet pressure per the manufacturer s specifications? Is the system powered? Is the thermostat calling for heat? There are three potential system failure conditions: no spark, and system does not work spark is present, but pilot does not light pilot lights, but main valve does not come on Determine the failure condition, then use the respective flowcharts on the following pages to troubleshoot the system. Perform the procedures in the Checkout and Startup Procedure section after any servicing. Repairs and ment! CAUTION: Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation. Verify proper operation after servicing. Do not attempt field repairs. Use only exact or factory recommended replacement controls. All other accessories, such as flame sensors, electrode assemblies, pilot assemblies, and leads can be obtained through the original equipment manufacturer or a Johnson Controls distributor. G Intermittent Pilot Ignition Controls Technical Bulletin 11

12 Start Visually check. Is Lead 5 connected securely to ground? Connect securely Are thermostat and limit contacts closed? Is 24 VAC present between Terminal 2 and ground? Is 24 VAC present between Terminal 6 and ground? Close contacts Repair Is circuit wiring providing 24 VAC to Terminal 2? Is 24 VAC present between Terminal 1 and ground? Check for proper voltage at transformer primary and secondary te: In some instances a jumper is used between Terminals 2 and 6 to power Terminal 6. Is circuit wiring providing 24 VAC to Terminal 6? Repair Turn off supply voltage cable Is high voltage cable in good condition (not brittle, burnt, or cracked)? Is high voltage cable connected to spark transformer? Is spark gap 0.1 in. and located in pilot gas stream? Correct or replace pilot burner Is spark electrode ceramic cracked? pilot burner Connect securely Turn on supply voltage Turn on supply voltage Operate system several complete cycles End Figure 11: Spark, and System Does t Work 12 G Intermittent Pilot Ignition Controls Technical Bulletin

13 Start Is pilot valve wiring securely connected to Terminal 1 and ground? Connect securely Is 24 VAC present between Terminal 1 and ground?! WARNING: Explosion Hazard. Do not use a match to test for presence of gas. Is inlet gas pressure per manufacturer s specifications? Is gas at pilot? Make sure pilot line is not kinked or obstructed. Check for clean orifice. Correct gas pressure pilot valve Is pilot spark gap 0.1 in. and located in pilot gas stream? Correct or replace pilot Check for drafts. Shield as necessary and check for clean orifice. End Figure 12: Spark is Present, but Pilot Does t Light G Intermittent Pilot Ignition Controls Technical Bulletin 13

14 Start Does spark stay on for more than 30 seconds after the pilot lights? Is 24 VAC between Terminal 3 and ground? Is inlet gas pressure per manufacturer s specifications? Correct gas pressure Make sure sensor cable and high voltage cable are separated and not wrapped around any pipe or accessories. Is main valve wiring securely connected to Terminal 3 and ground? Connect securely Is sensor cable securely connected to Terminal 4 and flame sensor? Connect securely main valve Is sensor ceramic cracked? Is cable grounded out? Is sensor or sensor connector shorted out to metal surface? Correct sensor Correct Is there continuity and good insulation in the sensor cable? cable Connect DC microammeter between sensor cable terminal and Terminal 4. Observe correct polarity. See Figure 20. Disconnect sensor cable from Terminal 4 Disconnect main valve lead from Terminal 3 Is DC current 0.2 microamperes or greater with pilot only operation? Check for: - proper gas pressure - clean pilot assembly - tight mechanical and electrical connections If there is not improvement, change the flame sensor length or the orifice size and perform any necessary turn down tests. End Figure 13: Pilot Lights, but Main Burner Does t Come On 14 G Intermittent Pilot Ignition Controls Technical Bulletin

15 Start Is system wiring per manufacturer s instructions? Open thermostat contacts for 30 seconds Correct wiring Close thermostat contacts and wait 30% of the Y79 lockout time Is a spark present? System was in lockout Determine reason for lockout. Conduct microamperage test as outlined in Figure 16, starting at A. Is 24 VAC present between Terminal 2 and ground? Is 24 VAC present between Terminal 1 and ground? Turn off supply voltage Connect securely Check the high voltage cable. Is it securely connected to the spark transformer? Is 24 VAC present on secondary of transformer? Turn supply voltage on the transformer if proper voltage is present on primary of transformer. Is high limit closed? cable Is condition of high voltage cable good (not brittle, burnt, or cracked)? Reset high limit the Y79 with the appropriate G600 Ignition controls (contact Johnson Controls Technical Support). Is spark gap 0.1 in. and located in pilot gas stream? Correct or replace pilot burner Is spark electrode ceramic cracked? Turn supply voltage on pilot burner Operate system several complete cycles End Figure 14: /Y79B Spark, and System Does t Work G Intermittent Pilot Ignition Controls Technical Bulletin 15

16 Start Are pilot valve and main valve connections secured to the proper Y79 terminal and ground? Open thermostat contacts for 30 seconds Close thermostat contacts Connect securely Is 24 VAC present between ground and pilot valve terminals of Y79? Is 24 VAC present between Terminal 1 and ground on the? Wait 30% of the Y79 lockout time. the Y79 with the appropriate G600 ignition control (contact Johnson Controls Technical Support). Correct Is inlet pressure per manufacturer s specifications?! WARNING: Explosion Hazard. Do not use a match to test for presence of gas. Is gas at pilot? Is spark gap 0.1 in. and located in the pilot gas stream? Make sure the pilot line is not kinked or obstructed. Check for a clean orifice. Correct or replace pilot burner Check for drafts. Shield as necessary and check for clean orifice. If OK, replace pilot valve. End Figure 15: /Y79B Spark is Present, but Pilot Does t Light 16 G Intermittent Pilot Ignition Controls Technical Bulletin

17 Start Does spark stay on for more than 30 seconds after pilot lights? Is 24 VAC between Terminal 3 Is inlet gas pressure and ground? per manufacturer s specifications? Correct gas pressure Make sure sensor cable and high voltage cable are separated and not wrapped around any pipe or accessories. Is 24 VAC present between main valve terminal on the Y79 and ground terminal on the? Is sensor cable securely connected to Terminal 4 and flame sensor? Connect securely the Y79 with the appropriate G600 ignition control (contact Johnson Controls Technical Support). Is sensor ceramic cracked? Is main valve wiring securely connected to the main valve terminal on the Y79 and ground? Connect securely sensor Is cable grounded out? Is sensor or sensor connector shorted out to metal surface? Correct main valve Correct Is there continuity and good insulation in the sensor cable? cable Connect DC microammeter between sensor cable terminal and Terminal 4. Observe correct polarity. See Figure 20. Disconnect sensor cable from Terminal 4 Disconnect main valve lead from Terminal 3 A Is DC current 0.2 microamperes or greater with pilot only operation? Check for: - proper gas pressure - clean pilot assembly - tight mechanical and electrical connections If there is no improvement, change the flame sensor length or the orifice size, then perform any necessary turn down tests. End Figure 16: /Y79B Pilot Lights, but Main Burner Does t Come On G Intermittent Pilot Ignition Controls Technical Bulletin 17

18 Start Is system wiring per manufacturer s instructions? Open thermostat contact for 30 seconds Correct wiring Close thermostat contacts and wait 30% of the Y79 lockout time Is a spark present? Is 24 VAC present between Terminal 2 and ground? System was in lockout Is 24 VAC present between Terminal 1 and ground? Determine the reason for lockout. Conduct microamperage test as outlined in Figure 16, starting at A. Turn off supply voltage Is 24 VAC present on secondary of transformer? Connect securely Check the high voltage cable. Is it securely connected to the spark transformer? transformer if proper voltage is present on primary of transformer Reset high limit Is high limit closed? Turn supply voltage on cable Is condition of high voltage cable good (not brittle, burnt, or cracked)? the Y79 with the appropriate G600 ignition control (contact Johnson Controls Technical Support). Is spark gap 0.1 in. and located in pilot gas stream? Correct or replace pilot burner Is spark electrode ceramic cracked? pilot burner End Operate system several complete cycles Turn supply voltage on Figure 17: /Y79A Spark, and System Does t Work 18 G Intermittent Pilot Ignition Controls Technical Bulletin

19 Start Is pilot valve wiring securely connected to Terminal 1 and ground? Connect securely! WARNING: Explosion Hazard. Do not use a match to test for presence of gas. Is inlet gas pressure per manufacturer s specifications? Is gas at pilot? Make sure pilot line is not kinked or obstructed. Check for clean orifice. Correct gas pressure pilot valve Is pilot spark gap 0.1 in. and located in pilot gas stream? Correct or replace pilot Check for drafts. Shield as necessary and check for clean orifice. End Figure 18: /Y79A Spark is Present, but Pilot Will t Light G Intermittent Pilot Ignition Controls Technical Bulletin 19

20 Start Does spark stay on for more than 30 seconds after the pilot lights? Is 24 VAC between Terminal 3 and ground? Is inlet gas pressure per manufacturer s specifications? Correct gas pressure Make sure sensor cable and high voltage cable are separated and not wrapped around any pipe or accessories. Is main valve wiring securely connected to Terminal 3 and ground? Connect securely Is sensor cable securely connected to Terminal 4 and flame sensor? Connect securely main valve Is sensor ceramic cracked? Is cable grounded out? Is sensor or sensor connector shorted out to metal surface? Correct sensor Correct Is there continuity and good insulation in the sensor cable? cable Connect DC microammeter between sensor cable terminal and Terminal 4. Observe correct polarity. See Figure 20. Disconnect sensor cable from Terminal 4 Disconnect main valve lead from Terminal 3 Is DC current 0.2 microamperes or greater with pilot only operation? Check for: - proper gas pressure - clean pilot assembly - tight mechanical and electrical connections If there is not improvement, change the flame sensor length or the orifice size and perform any necessary turn down tests. End Figure 19: /Y79A Pilot Lights, but Main Burner Does t Come On 20 G Intermittent Pilot Ignition Controls Technical Bulletin

21 Y99AU-2 Multimeter Jumper 5 Electrode Pilot Burner Assembly Positive Lead to Terminal 4 Negative Lead to Flame Sensor Figure 20: Meter Hookup to Measure Flame Sensing Circuit G Intermittent Pilot Ignition Controls Technical Bulletin 21

22 tes 22 G Intermittent Pilot Ignition Controls Technical Bulletin

23 tes G Intermittent Pilot Ignition Controls Technical Bulletin 23

24 tes Controls Group E. Michigan Street FAN 121 P.O. Box 423 Installation Sheets Manual Milwaukee, WI Printed in U.S.A. 24 G Intermittent Pilot Ignition Controls Technical Bulletin

Gas fired boiler Control Supplement

Gas fired boiler Control Supplement LGB Gas fired boiler Control Supplement LGB-4-4 & LGB-5-5 Universal Control System -5 Series 2 Propane gas Contents Installation... 2 Conversion (Natural/Propane)... 2 Gas piping...3 Wiring...4 Operating

More information

Y99AW-1 Flame Simulator

Y99AW-1 Flame Simulator Installation Sheets Manual 121 Miscellaneous Products and Accessories Section Y Technical Bulletin Issue Date September 30, 2014 Flame Simulator Figure 1: Flame Simulator Application The Flame Simulator

More information

BGC278 Series BASOTROL CE Approved Gas Valve

BGC278 Series BASOTROL CE Approved Gas Valve Installation Instructions BGC278 Issue Date April 1, 2013 BGC278 Series BASOTROL CE Approved Gas Valve Installation IMPORTANT: These instructions are intended as a guide for qualified personnel installing

More information

SIMPLE ELECTRONIC IGNITION WIRE DIAGRAM THERMOSTAT (3) PV PILOT BURNER/IGNITOR - SENSOR Q345A (9) SPARK (4) GND (BURNER) CHASSIS GND

SIMPLE ELECTRONIC IGNITION WIRE DIAGRAM THERMOSTAT (3) PV PILOT BURNER/IGNITOR - SENSOR Q345A (9) SPARK (4) GND (BURNER) CHASSIS GND Honeywell Electronic Ignition Troubleshooting Tech Tip April 2007 The Honeywell S8610H Intermittent Pilot Module provides the ignition sequencing, pilot spark, pilot flame monitoring, Pilot Valve (PV)

More information

36G22, 36G23, 36G24 & 36G52 36J22, 36J23, 36J24 & 36J52 DSI and HSI Single Stage Combination Gas Valve

36G22, 36G23, 36G24 & 36G52 36J22, 36J23, 36J24 & 36J52 DSI and HSI Single Stage Combination Gas Valve Operator: Save these instructions for future use! FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE INSTALLING OR OPERATING THIS CONTROL COULD CAUSE PERSONAL INJURY AND/OR PROPERTY DAMAGE. DESCRIPTION

More information

CASE STUDY 1 COMMISSIONING A GAS FIRED STEAM BOILER

CASE STUDY 1 COMMISSIONING A GAS FIRED STEAM BOILER CASE STUDY 1 COMMISSIONING A GAS FIRED STEAM BOILER A steam boiler has been built and installed at a factory for the provision of process steam. The following lists the requirements used in the commissioning

More information

Operator: Save these instructions for future use!

Operator: Save these instructions for future use! WHITE-RODGERS 36C01 Combination Gas Valves (24 Volt and 120 Volt Models) INSTALLATI INSTRUCTIS FAILURE TO READ AND FOLLOW ALL INSTRUCTIS CAREFULLY BEFORE INSTALLING OR OPERATING THIS CTROL COULD CAUSE

More information

USER S, MAINTENANCE and SERVICE INFORMATION MANUAL

USER S, MAINTENANCE and SERVICE INFORMATION MANUAL CONTENTS SAFETY INFORMATION................ 2 FOR YOUR SAFETY....................... 2 SYSTEM OPERATION.................. 2 THERMOSTATS........................... 2 INTERMITTENT IGNITION DEVICE...........

More information

V4295A,S; V8295A,S Solenoid Gas Valves

V4295A,S; V8295A,S Solenoid Gas Valves V4295A,S; V8295A,S Solenoid Gas Valves INSTALLATION INSTRUCTIONS FEATURES APPLICATION The electrically operated V4295A, S and V8295A, S Solenoid Gas Valves control the flow of natural and LP (liquefied

More information

Model 7586. Description / Applications. Intermittent Pilot Gas Ignition Control

Model 7586. Description / Applications. Intermittent Pilot Gas Ignition Control PARTS & ACCESSORIES Model 7586 Intermittent Pilot Gas Ignition Control Description / Applications The Beckett GeniSys Intermittent Pilot Gas Ignition Control is a 24 Vac gas ignition and safety control.

More information

AC Electrical System Tests Sign-Off Sheet. STEP Initials Date

AC Electrical System Tests Sign-Off Sheet. STEP Initials Date AC Electrical System Tests Hot Skin Test Prepare Documentation? Make sure shore line is plugged into 120VAC source? Set VOM to AC voltage scale? Place one probe on a bare metal surface of the RV (i.e.,

More information

A319 Electronic Temperature Control

A319 Electronic Temperature Control FANs 216, 125, 195 Product/Technical Bulletin A319 Issue Date 0396 A319 Electronic Temperature Control The A319 Series is a line voltage, single-stage electronic temperature control with Single-Pole, Double-Throw

More information

I nstallation. M100Q Series Proportional Actuator with R81Q Controller Board for Thermistor Sensor Applications. Tools Needed.

I nstallation. M100Q Series Proportional Actuator with R81Q Controller Board for Thermistor Sensor Applications. Tools Needed. FANs 268.1, 1628.3 Installation Bulletin M100Q Issue Date 1099 M100Q Series Proportional Actuator with R81Q Controller Board for Thermistor Sensor Applications I nstallation Parts Included M110QGA-1 and

More information

prestige Condensing Water Boiler SERVICE TECHNICIAN S TROUBLE SHOOTING GUIDE 2008-36 TSG-PRESTIGE Date revised: 12/6/10

prestige Condensing Water Boiler SERVICE TECHNICIAN S TROUBLE SHOOTING GUIDE 2008-36 TSG-PRESTIGE Date revised: 12/6/10 prestige Condensing Water Boiler SERVICE TECHNICIAN S TROUBLE SHOOTING GUIDE Date revised: 12/6/10 2008-36 TSG-PRESTIGE Table of Contents INTRODUCTION Page 1-2 SERVICING TIPS AND INSTRUCTIONS Page 3-4

More information

S8910U Universal Hot Surface Ignition Module

S8910U Universal Hot Surface Ignition Module SUPER TRADELINE Universal Hot Surface Ignition Module INSTALLATION INSTRUCTIONS Installation Instructions for the Trained Service Technician. APPLICATION The SUPER TRADELINE Universal Hot Surface Ignition

More information

Q309A,B; Q335C; Q340A; Q390A Thermocouples and Q313A,B,C,F Thermopile Generators

Q309A,B; Q335C; Q340A; Q390A Thermocouples and Q313A,B,C,F Thermopile Generators Q309A,B; Q335C; Q340A; Q390A Thermocouples and Q313A,B,C,F Thermopile Generators FEATURES PRODUCT DATA Push-in clip, split nut, and adapter assembly for easy pilot burner installation. Q335 Spade or quick-connect

More information

http://waterheatertimer.org/how-to-troubleshoot-gas-water-heater.html

http://waterheatertimer.org/how-to-troubleshoot-gas-water-heater.html http://waterheatertimer.org/how-to-troubleshoot-gas-water-heater.html APPLY POWER TO APPLIANCE FIELD WIRING CORRECT? DPLAY ERROR CODE 1 OR 2 Intelli-Vent TM Sequence of Operation REQUEST FOR HEAT PRESENT?

More information

Your safety and the safety of others are very important.

Your safety and the safety of others are very important. NATURAL GAS TO PROPANE CONVERSION KIT 090 INSTALLATION INSTRUCTIONS FOR ALTITUDES 0 -,00 FT. ONLY PROPANE CONVERSION KIT SAFETY... INSTALLATION REQUIREMENTS... Tools and Parts... LP Gas Requirements...

More information

THC 85 INDUSTRIAL / COMMERCIAL SPACE HEATER

THC 85 INDUSTRIAL / COMMERCIAL SPACE HEATER THC 85 INDUSTRIAL / COMMERCIAL SPACE HEATER Certified to / Certifié à CGA 2.14 M2000 Conforms to / Conforme à ANSI std Z83.7 2000 Suitable for indoor or outdoor installation / Unvented / Unattended Type

More information

Air Conditioning Sign-Off Sheet

Air Conditioning Sign-Off Sheet Air Conditioning Sign-Off Sheet Printed Technician Name Address Social Security Number Telephone Number City State Zip Code Install Or Verify The Accuracy Of An Air Conditioner s Installation The candidate

More information

Cleaning Instructions for Burner, Pilot Assembly, and Emitter Screen. Series: 150000 200605 LP Gas

Cleaning Instructions for Burner, Pilot Assembly, and Emitter Screen. Series: 150000 200605 LP Gas Cleaning Instructions for Burner, Pilot Assembly, and Emitter Screen Series: 150000 200605 LP Gas Tools needed Bottle brush Non-abrasive scouring pad Small utility brush Heavy-duty pipe cleaners Air hose

More information

A99B Series Temperature Sensors

A99B Series Temperature Sensors FANs 125, 121, 930, 930.5 Product/Technical Bulletin A99 Issue Date 0615 A99B Series Temperature s The A99B Series Temperature s are passive PTC (Positive Temperature Coefficient) sensors. The A99B sensors

More information

SXB40 Series Self-Contained Split-Core kw Transducers (4-20mA)

SXB40 Series Self-Contained Split-Core kw Transducers (4-20mA) SXB40 Series Self-Contained Split-Core kw Transducers (4-20mA) INSTALLATION INSTRUCTIONS APPLICATION The SXB40 Series combines a microprocessor based kw transducer and high accuracy split-core instrument

More information

XP Series. Preventive Maintenance Guide. 480 V Models. PCXP-xxkW-yyyA-zzV Felland Road, Suite 116 Madison, WI USA. Power Designers USA LLC

XP Series. Preventive Maintenance Guide. 480 V Models. PCXP-xxkW-yyyA-zzV Felland Road, Suite 116 Madison, WI USA. Power Designers USA LLC XP Series 480 V Models PCXP-xxkW-yyyA-zzV Preventive Maintenance Guide 4005 Felland Road, Suite 116 Madison, WI 53718 USA Power Designers USA LLC MAN-220002-00 REV A TABLE OF CONTENTS SAFETY PRECAUTIONS...

More information

Automatic Humidifier Control SEH-7100-000

Automatic Humidifier Control SEH-7100-000 TM Automatic Humidifier Control SEH-7100-000 by Skuttle Indoor Air Quality Products Safety and Installation Instructions* INSTALLER: READ COMPLETE INSTALLATION INSTRUCTIONS BEFORE BEGINNING INSTALLATION.

More information

Propane Conversion Kit PROPANE CONVERSION KIT INSTALLATION MANUAL

Propane Conversion Kit PROPANE CONVERSION KIT INSTALLATION MANUAL Propane Conversion Kit Supersedes: 145.25-IOM2 (708) Form 145.25-IOM2 (908) PROPANE CONVERSION KIT INSTALLATION MANUAL "LPKIT " - PROPANE CONVERSION KIT Kits are available for field conversion from natural

More information

VLT Series 300 Watt True Sine Wave Inverter

VLT Series 300 Watt True Sine Wave Inverter VLT Series 300 Watt True Sine Wave Inverter PURE SINE WAVE INVERTER I ON 0 OFF REMOTE CONTROL AC OUTPUT POWER STATUS Vout Vin Models VLT12-300 VLT24-300 300 Watt VLT Series Inverter - 1 - TABLE OF CONTENTS

More information

Cleaning Instructions, Pilot Replacement and Valve Change. Model No.: 233010 Natural Gas

Cleaning Instructions, Pilot Replacement and Valve Change. Model No.: 233010 Natural Gas Cleaning Instructions, Pilot Replacement and Valve Change Model No.: 233010 Natural Gas 8mm open-end wrench 9mm open-end wrench 10mm open-end wrench 12mm open-end wrench 13mm open-end wrench Phillips screw

More information

Aprilaire Dehumidifier Troubleshooting Manual Models 1710A, 1750A, 1770A

Aprilaire Dehumidifier Troubleshooting Manual Models 1710A, 1750A, 1770A Aprilaire Dehumidifier Troubleshooting Manual Models 1710A, 1750A, 1770A Table of Contents Troubleshooting Fault Codes... 1 1 blink... 2 2 blinks... 2 3 blinks... 2 4 blinks... 2 5 blinks... 6 6 blinks...

More information

OBSOLETE. VS8420 Millivolt Gas Valve

OBSOLETE. VS8420 Millivolt Gas Valve APPLICATION The VS8420 Millivolt Gas Valve is compact and has a 60,000 Btuh capacity (1 in. pressure drop for straightthrough configuration). The design makes it ideal for fireplace and space heating applications.

More information

CARING FOR YOUR WATER HEATER

CARING FOR YOUR WATER HEATER http://waterheatertimer.org/troubleshoot-rheem-tankless-water-heater.html Water Heater Inspections CARING FOR YOUR WATER HEATER Venting System (Direct Vent Only) The venting system should be inspected

More information

DPT-2015 Differential Pressure Transmitter for VAV Box Applications

DPT-2015 Differential Pressure Transmitter for VAV Box Applications FANs 216, 1628.3 Product/Technical Bulletin DPT-2015 Issue Date 1298 DPT-2015 Differential Pressure Transmitter for VAV Box Applications The DPT-2015 Differential Pressure Transmitter senses differential

More information

Installation Instructions for Alarm Module Kit A043F059

Installation Instructions for Alarm Module Kit A043F059 Instruction Sheet 07-2013 Installation Instructions for Alarm Module Kit A043F059 1 Introduction The information contained within is based on information available at the time of going to print. In line

More information

Small Packaged Products Gas Heating/Electric Cooling Accessory LP Conversion Kit

Small Packaged Products Gas Heating/Electric Cooling Accessory LP Conversion Kit Small Packaged Products Gas Heating/Electric Cooling Accessory LP Conversion Kit Cancels: IIK 582A-18-5 Installation Instructions Part Number: CPLPCONV005A00 1 1/2 to 5 Tons IIK 582A-18-6 7-00 NOTE: Read

More information

-1- - a solenoid (electromagnet) with its core; and - a valve body containing one or more orifices.

-1- - a solenoid (electromagnet) with its core; and - a valve body containing one or more orifices. Switch Heater Solenoid Valves Inspection and Maintenance Procedures Electric solenoid valves are used in gas-fired switch heaters to provide a means to effectively control the flow of gas into the burner.

More information

Fossil fuel heating equipment

Fossil fuel heating equipment Fossil fuel heating equipment principles and troubleshooting techniques Application Note This application note was written to provide you with an understanding of the basic principles of fossil fuel heating

More information

Fast Track Troubleshooting

Fast Track Troubleshooting Model: FX510BGS/XAA FX710BGS/XAA WARNING Fast Track Troubleshooting IMPORTANT SAFETY NOTICE For Technicians Only This service data sheet is intended for use by persons having electrical, electronic, and

More information

PRESSURE AND TEMPERATURE SENSORS FOR THE E340 BOILER ROOM CONTROL

PRESSURE AND TEMPERATURE SENSORS FOR THE E340 BOILER ROOM CONTROL ES-3481 JUNE 27, 2005 PRESSURE AND TEMPERATURE SENSORS FOR THE E340 BOILER ROOM CONTROL DESCRIPTION The PS348 and TS348 Series of pressure and temperature sensors are designed for use with the E340 Boiler

More information

http://waterheatertimer.org/how-to-troubleshoot-gas-water-heater.html

http://waterheatertimer.org/how-to-troubleshoot-gas-water-heater.html http://waterheatertimer.org/how-to-troubleshoot-gas-water-heater.html TECHNICAL SERVICE DEPARTMENT Effective October 2007, we transitioned to the White Rodgers (Intelli-Vent TM )Thermostat Control for

More information

PROFLAME GTM SYSTEM USE AND INSTALLATION INSTRUCTIONS

PROFLAME GTM SYSTEM USE AND INSTALLATION INSTRUCTIONS 9.957.036 05 PROFLAME GTM SYSTEM USE AND INSTALLATION INSTRUCTIONS Read the instructions before use. This control must be installed in accordance with the rules in force. English 2-12 The Proflame GTM

More information

INTELLIGENT SERVER. Model: BMS-LSV6E

INTELLIGENT SERVER. Model: BMS-LSV6E INSTALLATION MANUAL INTELLIGENT SERVER Model: BMS-LSV6E Thank you very much for purchasing this TOSHIBA INTELLIGENT SERVER. Please read this manual carefully beforehand for proper installation of the SERVER.

More information

MiniTec TM Series Manual Ranging Mini MultiMeter Model MN35 USER MANUAL

MiniTec TM Series Manual Ranging Mini MultiMeter Model MN35 USER MANUAL MiniTec TM Series Manual Ranging Mini MultiMeter Model MN35 USER MANUAL Introduction Congratulations on your purchase of Extech s MN35 Manual Ranging Multimeter. This meter measures AC/DC Voltage, DC Current,

More information

INSTALLATION & SERVICE MANUAL. Display Panel

INSTALLATION & SERVICE MANUAL. Display Panel INSTALLATION & SERVICE MANUAL Display Panel The PowerLine EMS TM is a specialized power distribution and energy management system intended to be used in recreational vehicles. The Control Module is housed

More information

VLT Series 300 Watt True Sine Wave Inverter

VLT Series 300 Watt True Sine Wave Inverter VLT Series 300 Watt True Sine Wave Inverter PURE SINE WAVE INVERTER I ON 0 OFF REMOTE CONTROL AC OUTPUT POWER STATUS Vout Vin Models VLT12-300 VLT24-300 300 Watt VLT Series Inverter - 1 - TABLE OF CONTENTS

More information

Product Manual (Revision NEW) Original Instructions. 28 Vdc Power Supply with Optional Battery Charger Circuits.

Product Manual (Revision NEW) Original Instructions. 28 Vdc Power Supply with Optional Battery Charger Circuits. Product Manual 82372 (Revision NEW) Original Instructions with Optional Battery Charger Circuits Operation Manual General Precautions Read this entire manual and all other publications pertaining to the

More information

OBSOLETE. VS8510,VS8520 Millivolt Gas Valve

OBSOLETE. VS8510,VS8520 Millivolt Gas Valve APPLICATION The VS8510, VS8520 Millivolt Gas Valve is compact and has a 60,000 Btuh capacity (1 in. pressure drop for straight through configuration). Its design makes it ideal for fireplace and space

More information

PART 8: FIELD WIRING. n WARNING NOTICE. Boiler Manual

PART 8: FIELD WIRING. n WARNING NOTICE. Boiler Manual PART 8: FIELD WIRING A. INSTALLATION MUST COMPLY WITH: 1. National Electrical Code and any other national, state, provincial or local codes or regulations. 2. In Canada, CSA C22.1 Canadian Electrical Code

More information

K Series BASO Thermocouples

K Series BASO Thermocouples Heating Line Product Guide 435.0 Thermocouples Section Product Bulletin K Series Issue Date 1098 K Series BASO Thermocouples The K Series Thermocouples are designed for use in standing pilot ignition systems.

More information

INTERMITTENT PILOT MODULES S8600, S8610, S8660, S8670

INTERMITTENT PILOT MODULES S8600, S8610, S8660, S8670 INTERMITTENT MODULES S8600, S860, S8660, S8670 APPLICATION These ignition modules provide ignition sequence, flame monitoring and safety shutoff for intermittent pilot central furnaces and heating appliances.

More information

Instruction Bulletin. MCS025 Sync-Check Module Installation Sheet

Instruction Bulletin. MCS025 Sync-Check Module Installation Sheet Instruction Bulletin 63230-216-244B1 LaVergne, TN, USA MCS025 Sync-Check Module Installation Sheet Retain for future use. DANGER HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH Only qualified electrical

More information

OWNER MANUAL INSTALLATION INSTRUCTIONS

OWNER MANUAL INSTALLATION INSTRUCTIONS RIELLO BURNER SYSTEM mectron 3M TYPE 215 OWNER MANUAL INSTALLATION INSTRUCTIONS We are delighted that you have chosen the Riello burner. It is modern. clean, efficient and like any quality product. must

More information

L-5 Liter Outdoor Tankless Water Heater

L-5 Liter Outdoor Tankless Water Heater 8. Turn the spray nozzle to the on and adjust to the desired water pattern on the shower head. 9. There will be a series of audible clicks and the burner will ignite. (Should the burner not ignite after

More information

VR8304 Intermittent Pilot Combination Gas Control

VR8304 Intermittent Pilot Combination Gas Control VR8304 Intermittent Pilot Combination Gas Control APPLICATION These intermittent pilot gas controls are used in gas-fired appliances with capacities up to 300 ft 3 /hr at in. WC pressure drop (8.5 m 3

More information

Setting Up the Polycom RealPresence Utility Cart 500

Setting Up the Polycom RealPresence Utility Cart 500 Setting Up the Polycom RealPresence Utility Cart 500 Polycom EagleEye TM IV camera 27 display or (2) 22 displays Microphone and 25 cable Base cart with laptop/accessory shelf Storage drawer Accessory basket

More information

User's Guide. Model and Single Output Laboratory Grade Switching DC Power Supply

User's Guide. Model and Single Output Laboratory Grade Switching DC Power Supply User's Guide Model 382275 and 382276 Single Output Laboratory Grade Switching DC Power Supply Introduction Congratulations on your purchase of the Extech 382275 Single Output Laboratory Grade DC Power

More information

SERVICE MANUAL 12VDC WALL THERMOSTAT AIR CONDITIONING SYSTEMS ROOFTOP UNITS ONLY

SERVICE MANUAL 12VDC WALL THERMOSTAT AIR CONDITIONING SYSTEMS ROOFTOP UNITS ONLY SERVICE MANUAL 12VDC WALL THERMOSTAT AIR CONDITIONING SYSTEMS ROOFTOP UNITS ONLY! WARNING - SHOCK HAZARD! TO PREVENT THE POSSIBILITY OF SEVERE PERSONAL INJURY, DEATH, OR EQUIPMENT DAMAGE DUE TO ELECTRICAL

More information

Manual Ranging MultiMeter

Manual Ranging MultiMeter Owner s Manual Manual Ranging MultiMeter Model 82345 CAUTION: Read, understand and follow Safety Rules and Operating Instructions in this manual before using this product.! Safety! Operation! Maintenance!

More information

37E73A-903 & 906 INTELLI-VENT

37E73A-903 & 906 INTELLI-VENT 37E73A-903 & 906 INTELLI-VENT Water Heater Thermostat Control Installation Instructions For Natural Gas Only Operator: Save these instructions for future use FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS

More information

Installation Instructions

Installation Instructions Installation Instructions This document provides you with the following information: Because of the variety of uses for the products described in this publication, those responsible for the application

More information

San josé OWNER S MANUAL

San josé OWNER S MANUAL San josé OWNER S MANUAL Assembling & operating manual San josé 30 mbar - PORTABLE GAS BARBECUE 1. 2. 3. Improper installation, adjustment, alteration, service or maintenance can injury or property damage.

More information

(for Intelligent Server model BMS-LSV4E only)

(for Intelligent Server model BMS-LSV4E only) INSTALLATION MANUAL BACnet TM SOFTWARE Model: BMS-STBN E (for Intelligent Server model BMS-LSV4E only) Thank you very much for purchasing this TOSHIBA BACnet Software. Please read this manual carefully

More information

12 Volt 30 Amp Digital Solar Charge Controller

12 Volt 30 Amp Digital Solar Charge Controller 12 Volt 30 Amp Digital Solar Charge Controller User s Manual WARNING Read carefully and understand all INSTRUCTIONS before operating. Failure to follow the safety rules and other basic safety precautions

More information

GSX GAS BOILERS USER S INFORMATION MANUAL

GSX GAS BOILERS USER S INFORMATION MANUAL S-GSXUM-3 00-GSXUM GSX GAS BOILERS USER S INFORMATION MANUAL WARNING: If the information in this manual is not followed exactly, a fire or explosion may result causing property damage, personal injury

More information

ARCO Electric Products Installation and Maintenance Manual Low Voltage Automatic Power Factor Correction Capacitor Systems 2013

ARCO Electric Products Installation and Maintenance Manual Low Voltage Automatic Power Factor Correction Capacitor Systems 2013 ARCO Electric Products Installation and Maintenance Manual Low Voltage Automatic Power Factor Correction Capacitor Systems 2013 READ CAREFULLY These instructions are intended to cover good practices in

More information

Installation Instructions

Installation Instructions H5HK Series Installation Instructions 3 Phase Electric Heater Kits 7.5 and 0 TON Package A/C Systems Description Installation of 08/40V and 480V H5HK 3 Phase Heater Kits in 7.5 and 0 TON Packaged Air Conditioners.

More information

OASIS SERVICE & TROUBLESHOOTING MANUAL (WITH DM10 OR DM12)

OASIS SERVICE & TROUBLESHOOTING MANUAL (WITH DM10 OR DM12) OASIS SERVICE & TROUBLESHOOTING MANUAL (WITH DM10 OR DM12) Revision 1.0 Page 1 of 50 THE INFORMATION CONTAINED IN THIS DOCUMENT IS THE SOLE PROPERTY OF INTERNATIONAL THERMAL RESEARCH, LTD. ANY REPRODUCTION

More information

543-0032-00, 943-0032-00. User s Manual

543-0032-00, 943-0032-00. User s Manual 543-0032-00, 943-0032-00 User s Manual 1 Comfort Alert Diagnostics Faster Service And Improved Accuracy The Comfort Alert diagnostics module is a breakthrough innovation for troubleshooting heat pump and

More information

GeniSys 12V. Model 7556. Description / Applications. Advanced 12 Vdc Burner Control

GeniSys 12V. Model 7556. Description / Applications. Advanced 12 Vdc Burner Control PARTS & ACCESSORIES GeniSys 12V Model 7556 Advanced 12 Vdc Burner Control Description / Applications The Beckett GeniSys TM 12V Advanced Burner Control is a 12 Vdc primary safety control for oil burners

More information

Series P215PR/RM Direct- and Remote-Mount Pressure-Actuated Condenser Fan Speed Controllers for Single-Phase Motors

Series P215PR/RM Direct- and Remote-Mount Pressure-Actuated Condenser Fan Speed Controllers for Single-Phase Motors European Refrigeration Controls Catalogue Catalogue Section 4 Product Bulletin P215PR/RM Issue 01/03/2013 Series P215PR/RM Direct- and Remote-Mount Pressure-Actuated Condenser Fan Speed Controllers for

More information

Square D Clipsal C-Bus Network Analyzer

Square D Clipsal C-Bus Network Analyzer Square D Clipsal C-Bus Network Analyzer for Use with C-Bus Wired Networks Instruction Bulletin Retain for future use. Square D Clipsal C-Bus Network Analyzer 63249-420-234A1 Instruction Bulletin 12/2006

More information

Energy Saver SERVICE MANUAL COMMERCIAL 24 VOLT FLUE DAMPER SERIES WATER HEATER ATMOSPHERIC GAS WATER HEATERS

Energy Saver SERVICE MANUAL COMMERCIAL 24 VOLT FLUE DAMPER SERIES WATER HEATER ATMOSPHERIC GAS WATER HEATERS Energy Saver COMMERCIAL 24 VOLT FLUE DAMPER SERIES WATER HEATER ATMOSPHERIC GAS WATER HEATERS SERVICE MAUAL Troubleshooting Guide and Instructions for Service (To be performed OL by qualified service providers)

More information

1F Non-programmable Electronic Digital Heat Pump Thermostat INSTALLATION AND OPERATION INSTRUCTIONS

1F Non-programmable Electronic Digital Heat Pump Thermostat INSTALLATION AND OPERATION INSTRUCTIONS 1F89-211 Non-programmable Electronic Digital Heat Pump Thermostat INSTALLATION AND OPERATION INSTRUCTIONS Operator: Save these instructions for future use! FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY

More information

A Guide To Operating and Maintaining Your Gas Heating/Electric Cooling Unit

A Guide To Operating and Maintaining Your Gas Heating/Electric Cooling Unit 48SS 48SX Combination Gas Heating/Electric Cooling Units A Guide To Operating and Maintaining Your Gas Heating/Electric Cooling Unit NOTE TO INSTALLER This manual should be left with the equipment owner.

More information

INSTALLATION, OPERATING & MAINTENANCE INSTRUCTIONS FOR 870 SERIES INDUSTRIAL CONTROL PANELS

INSTALLATION, OPERATING & MAINTENANCE INSTRUCTIONS FOR 870 SERIES INDUSTRIAL CONTROL PANELS INSTALLATION, OPERATING & MAINTENANCE INSTRUCTIONS FOR 870 SERIES INDUSTRIAL CONTROL PANELS GENERAL HEATREX Industrial Control Panels are designed to provide years of trouble free operation if properly

More information

Installation Guide TH3210D. Non-programmable Digital Thermostat

Installation Guide TH3210D. Non-programmable Digital Thermostat Installation Guide TH3210D Non-programmable Digital Thermostat Product Application This thermostat provides electronic control of 24 VAC heat pump systems with auxiliary heat (2 heat/1 cool). Power Type

More information

SV9501/SV9502/SV9601/SV9602 SmartValve TM System Control

SV9501/SV9502/SV9601/SV9602 SmartValve TM System Control SV950/SV9502/SV960/SV9602 SmartValve TM System Control APPLICATION The Honeywell TRADELINE SmartValve TM System Controls provide easy field replacement of a wide range of SV9500, SV950, SV9502 and SV9602

More information

Marsal Deck Ovens: MB42, MB60, MB236, MB866, SD236, SD248, SD260, SD448, SD660, SD1048, SD1060, SD866, SD10866, WF42, WF60

Marsal Deck Ovens: MB42, MB60, MB236, MB866, SD236, SD248, SD260, SD448, SD660, SD1048, SD1060, SD866, SD10866, WF42, WF60 OVEN SERVICE MANUAL Marsal Deck Ovens: MB42, MB60, MB236, MB866, SD236, SD248, SD260, SD448, SD660, SD1048, SD1060, SD866, SD10866, WF42, WF60 RETAIN THIS MANUAL FOR FUTURE REFERENCE 2016 Marsal Pizza

More information

Installation Guide TH3110D. Non-programmable Digital Thermostat

Installation Guide TH3110D. Non-programmable Digital Thermostat Installation Guide TH3110D Non-programmable Digital Thermostat Product Application This thermostat provides electronic control of 24 VAC single-stage heating and cooling systems, or 750 mv heating systems.

More information

PREPIPED LIQUID FUEL MANIFOLDS PLPM

PREPIPED LIQUID FUEL MANIFOLDS PLPM PREPIPED LIQUID FUEL MANIFOLDS PLPM INSTRUCTIONS WARNING These instructions are intended for use only by experienced, qualified combustion start-up personnel. Adjustment of this equipment and its components,

More information

SERVICE MANUAL FOR 12 VDC WALL THERMOSTAT AIR CONDITIONING SYSTEMS ROOF TOP UNITS ONLY

SERVICE MANUAL FOR 12 VDC WALL THERMOSTAT AIR CONDITIONING SYSTEMS ROOF TOP UNITS ONLY RV Products Division SERVICE MANUAL FOR 12 VDC WALL THERMOSTAT AIR CONDITIONING SYSTEMS ROOF TOP UNITS ONLY Airxcel, Inc. RV Products Division P.O. Box 4020 Wichita, KS 67204 1976A376 (1-11) TABLE OF CONTENTS

More information

AutoRanging Digital MultiMeter

AutoRanging Digital MultiMeter Owner's Manual AutoRanging Digital MultiMeter Model No. 82139 CAUTION: Read, understand and follow Safety Rules and Operating Instructions in this manual before using this product. Safety Operation Maintenance

More information

Digi-Motor Installation Guide

Digi-Motor Installation Guide Digi-Motor Installation Guide Installation Video...located at marsdelivers.com Digi-Motor Installation Guide Digi-Motor For technical assistance with your Azure Digi-Motor, call the MARS technical support

More information

/ Marley Electric Basin Heater / User Manual C

/ Marley Electric Basin Heater / User Manual C / Marley Electric Basin Heater / User Manual 92-1322C / Receiving and Inspection / The heater package is shipped directly from the vendor. 1. Check all parts for any damage in transit. The carrier is

More information

Owner Retain this manual in a safe place to provide your serviceman information if it becomes necessary.

Owner Retain this manual in a safe place to provide your serviceman information if it becomes necessary. INSTALLATION, OPERATING AND SERVICE MANUAL FOR EASY RADIANT WORKS HEATWAVE MODEL GH-25-40 GAS FIRED, VENTED INFRARED TUBE HEATER FOR RESIDENTIAL & COMMERCIAL / INDUSTRIAL APPLICATIONS. For Your Safety

More information

DT830 Series 3 1/2 Digital Multimeter

DT830 Series 3 1/2 Digital Multimeter DT830 Series 3 1/2 Digital Multimeter Owner's operation manual for 830 series Read this owner's manual thoroughly before use D C V 20 1000 OFF 750 A C V µ D C A 0m 0µ m B 0k E k E B C C E E N P N P N P

More information

GAS SAFETY PRECAUTIONS

GAS SAFETY PRECAUTIONS GAS SAFETY PRECAUTIONS Instructions on what to do when a user smells gas can be obtained from the local gas supplier. These instructions must be posted in a prominent location where the unit is to be operated.

More information

OWNER S MANUAL. Model AE150/AE300/AE500 1.5AMP MULTI-USE SMART BATTERY CHARGER READ ENTIRE MANUAL BEFORE USING THIS PRODUCT

OWNER S MANUAL. Model AE150/AE300/AE500 1.5AMP MULTI-USE SMART BATTERY CHARGER READ ENTIRE MANUAL BEFORE USING THIS PRODUCT Model AE150/AE300/AE500 MULTI-USE SMART BATTERY CHARGER Certified by Californiia BCS Regulations AE300E AE500E 5AMP MULTI-USE AUTOMOTIVE BATTERY CHARGER 3AMP MULTI-USE SMART BATTERY CHARGER AE500E 5AMP

More information

Advantium 2 Plus Alarm

Advantium 2 Plus Alarm ADI 9510-B Advantium 2 Plus Alarm INSTALLATION AND OPERATING INSTRUCTIONS Carefully Read These Instructions Before Operating Carefully Read These Controls Corporation of America 1501 Harpers Road Virginia

More information

User Manual. CDM250 Digital Multimeter 070-6736-03

User Manual. CDM250 Digital Multimeter 070-6736-03 User Manual CDM250 Digital Multimeter 070-6736-03 Copyright Tektronix, Inc. 1987. All rights reserved. Tektronix products are covered by U.S. and foreign patents, issued and pending. Information in this

More information

SL280UHV SERIES GAS FURNACE WARNING

SL280UHV SERIES GAS FURNACE WARNING 2010 Lennox Industries Inc. Dallas, Texas, USA 506677 01 11/2010 Supersedes 506409 01 SL280UHV SERIES GAS FURNACE Litho U.S.A. FIRE OR EXPLOSION HAZARD. Failure to follow safety warnings exactly could

More information

Introduction. Refrigerant Leak Detecting System. Feature and Benefits

Introduction. Refrigerant Leak Detecting System. Feature and Benefits PSC European Refrigeration Controls Catalogue Catalog Section 9 Product Bulletin PD-GAS-E Refrigerant Leak Detecting System Introduction This range of refrigerant leak detecting systems is designed for

More information

TECHNICAL SERVICE DEPARTMENT Technical Service Bulletin 1-800-432-8373. 2 Inch PowerVent LED Indicator Explanations & Troubleshooting Table

TECHNICAL SERVICE DEPARTMENT Technical Service Bulletin 1-800-432-8373. 2 Inch PowerVent LED Indicator Explanations & Troubleshooting Table New Robertshaw control valve was introduced in May 2008 as a replacement part. See last page for troubleshooting this replacement part. All voltage inputs are 120V. All electrical connectors are Molex

More information

SIT SIGMA

SIT SIGMA SIT 4-43- SIGMA M U LT I F U N C T I O N A L C O N T R O L F O R G A S B U R N I N G A P P L I A N C E 9.955.42 1 Subject to change without notice Application Domestic gas appliances: central heating boilers,

More information

Troubleshooting Guide for Installers and Call Center

Troubleshooting Guide for Installers and Call Center Required Tools: Troubleshooting Guide for Installers and Call Center 1. Clip on ammeter/voltmeter 2. #2 Phillips screwdriver 3. Needle nose pliers 4. Slip joint pliers 5. 2¼ c-clamp (or equivalent device

More information

True RMS Multimeter. Owner's Manual. Model No Safety Operation Maintenance Español

True RMS Multimeter. Owner's Manual. Model No Safety Operation Maintenance Español Owner's Manual True RMS Multimeter Model No. 81077 CAUTION: Read, understand and follow Safety Rules and Operating Instructions in this manual before using this product. Safety Operation Maintenance Español

More information

Owner s Manual. Send in your Warranty Card TODAY! NG200 NG400. Drop Cord 120 Volt Plug In Model. 120 Volt Hardwire Model (rev A) Test/Essai

Owner s Manual. Send in your Warranty Card TODAY! NG200 NG400. Drop Cord 120 Volt Plug In Model. 120 Volt Hardwire Model (rev A) Test/Essai TM MC Owner s Manual Drop Cord 120 Volt Plug In Model NG200 120 Volt Hardwire Model NG400 Test/Essai Power Alimentation Alarm Alarme Malfunction Défaillance 1500-0022 (rev A) Send in your Warranty Card

More information

K Series BASO Thermocouples

K Series BASO Thermocouples Product Bulletin Issue Date May 20, 2013 K Series BASO Thermocouples The K Series Thermocouples are designed for use in standing pilot ignition systems. They are used primarily with BASO brand automatic

More information

HANDHELD DIGITAL MULTIMETER OPERATOR S INSTRUCTION MANUAL

HANDHELD DIGITAL MULTIMETER OPERATOR S INSTRUCTION MANUAL HANDHELD DIGITAL MULTIMETER OPERATOR S INSTRUCTION MANUAL Table of Contents Table of Contents TITLE PAGE TITLE PAGE 1. GENERAL INSTRUCTIONS 1 1.1 Precaution safety measures 1 1.1.1 Preliminary 1 1.1.2

More information

TB-A028-06 - A. O. SMITH - FVIR INTELLI-VENT TROUBLESHOOTING CHART # LED STATUS PROBLEM SOLUTION

TB-A028-06 - A. O. SMITH - FVIR INTELLI-VENT TROUBLESHOOTING CHART # LED STATUS PROBLEM SOLUTION 1 2 3 4 5 Inadequate or no earth ground sensed by the Intelli-Vent control. Power supply to Intelli-Vent control has reversed polarity. Pressure switch circuit remaining closed for more than 5 seconds

More information

INSTALLATION INSTRUCTIONS FOR HIGH ALTITUDE KITS: RXGY-F04, F05, F06 & F07

INSTALLATION INSTRUCTIONS FOR HIGH ALTITUDE KITS: RXGY-F04, F05, F06 & F07 INSTALLATION INSTRUCTIONS FOR HIGH ALTITUDE KITS: RXGY-F04, F05, F06 & F07 FOR MOST 90 PLUS GAS FURNACE MODELS (NOT FOR USE WITH (-)GRK AND (-)GGD MODELS) Recognize this symbol as an indication of Important

More information