HTV SILICONE COMPOSITE INSULATORS FOR HVDC APPLICATIONS - LONG- TERM EXPERIENCES WITH MATERIAL AND DESIGN FOR 500KV AND ABOVE

Size: px
Start display at page:

Download "HTV SILICONE COMPOSITE INSULATORS FOR HVDC APPLICATIONS - LONG- TERM EXPERIENCES WITH MATERIAL AND DESIGN FOR 500KV AND ABOVE"

Transcription

1 HTV SILICONE COMPOSITE INSULATORS FOR HVDC APPLICATIONS - LONG- TERM EXPERIENCES WITH MATERIAL AND DESIGN FOR 500KV AND ABOVE J. M. Seifert 1*, D. Stefanini and H. Janssen 2 1 Lapp Insulators GmbH, Bahnhofstrasse 5, D Wunsiedel, Germany 2 Dow Corning GmbH, Rheingaustrasse 34, D Wiesbaden, Germany * Jseifert@lappinsulators.de Abstract: Generation III silicone rubber composite insulators have been successfully applied in HVDC transmission lines for more than 3 decades [1]. The most popular installations are realised with the lines Pacific Intertie (±500kV) in Western USA, Cabora Bassa - Appollo (±533kV) in Mozambique/South Africa and in New Zealand (±270kV). The pollution severity for the HVDC line insulators at these installations can be evaluated in the range of light to medium, partly (locally) heavy in accordance with IEC The service experience with these line insulators has been very good regarding insulation performance and ageing resistance and forms an excellent base for further investigations and design reviews especially on material characteristics and creepage selection for future installations. Presently, several new HVDC lines are under construction or in the planning process in China, India, Brasil and South Africa. In contrast to the above mentioned existing lines, the pollution severity for the new projects is assumed to be much higher in the range of heavy to very heavy. This paper will give a design review of existing installations with silicone rubber composite insulators and will summarize the positive experience made with such insulators on HVDC lines during the last 30 years. During the design review the insulator characteristics will be investigated regarding creepage selection and housing design reflected by statistical methods applied to available pollution data. In addition to the electrical performance, the material ageing characteristic will be reviewed by laboratory experiments. Results of tracking and erosion material tests performed in similarity to IEC at DC voltage stress and those of a 5000 h multi-ageing test at DC voltage will be evaluated and discussed. The results will be compared to the behaviour of the insulators after 25 years of service in DC lines. 1. CASE STUDIES AND DESIGN REVIEW 1.1. Pacific Intertie ±500 kv Table 1: Line Data Parameter Line Voltage ±500 kv (before 1984: ±400 kv) Country USA, West Coast Year of installation 1984 (re-insulation of the former glass and porcelain discs with silicone rubber composite longrods) Service duration up to 24 years with silicone rubber composite Operated by LADWP, BPA Converter Stations Sylmar (Los Angeles, CA) Celeilo (Oregon) Pollution High in the Los Angeles area (industrial, pollution from traffic, natural) Medium in the desert/semi-desert area on the major line distance, dry arid, natural pollution Light, almost no pollution in the Oregon area ESDD [mg/cm²] and mg/cm² (in the LADWP district) [2], no available data from BPA Insulation HTV silicone rubber composite longrod, Generation III [1] Material HTV silicone compound with 48% ATH by weight Type 30/73 (168) mm, 30 mm FRP rod diameter, 73 sheds, uniform smooth shed profile, shed diameter 168 mm, connection length h1=4520 mm, creepage distance mm, 25.7 mm/kv Shed Profile Uniform, smooth sheds (open aerodynamic profile) Figure 1: ±500kV HVDC Pacific Intertie, CA, USA Figure 2: ±500kV HVDC Pacific Intertie Reinsulation, glass discs beeing substituted by silicone rubber longrod insulators, this procedure has been succesfully applied since 1984 [2]. Pg. 1 Paper C-12

2 Based on test station data (Koeberg Insulator Test Station, South Africa) the STRI Insulator Selection Tool (IST) was adapted to the type of silicone rubber composite insulator used in the Pacific Intertie line. The following calculations were performed using the STRI IST Ed. 2.0 for verification purpose: The service performance with silicone rubber composite insulators in this line is very good. Neither pollution flashovers nor tracking and erosion phenomena have been experienced during almost 30 years of application. Three different generations of composite insulators have been applied in this line which has globally the longest service records from all existing HVDC lines equipped with composite insulators. Although pollution severity is presently unknown and expected to be light-medium, the insulation described in this report is able to withstand pollution severities of the heavy-very heavy category. 2. LABORATORY TESTS Figure 3: IST Statistical Insulation Performance Calculation for the housing profile used in the Pacific Intertie Insulation, insulator type 30/73 (168) mm. number of insulators N=10000, Average ESDD value, NSDD/ESDD=5, based on test station data (KIPTS). The IST data shows that the insulation (red line) is well selected for the pollution conditions present. The choice of 25.7 mm/kv for silicone rubber composite insulators has been proven by 24 years of positive service experience. The theoretical approach for CD design can be confirmed by this case study also by applying statistical methods as indicated in IEC Cabora Bassa - Appollo ±533 kv Presently there are no IEC material and design test standards for HVDC composite insulators available, therefore established AC tests were modified for this work. Laboratory tests in accordance with modified tests similar to IEC [3] and IEC [4] were performed at DC voltage in order to compare excellent long-term in-service experience to the results obtained from artificial composite insulator material and design tests. 2.1 DC 5000 h Multi-Ageing (Design) Test A 5000 h DC test [4] was performed at STRI (Sweden) for the housing profile applied in the Cabora Bassa Appollo Line. The profile is an alterating one using shallow underibbed sheds (Type 1 acc. to Table 2). Table 2: Line Data Parameter Line Voltage ±533 kv Country Mocambique, South Africa Year of installation 1981/1996/1997/2002/2004 (various reinsulations / exchange of glass discs with silicone rubber composite longrods) Service duration up to 27 years with silicone rubber composite [2] Operated by ESKOM, RSA Converter Stations Cabora Bassa Dam (Mocambique), Appollo (Johannesburg, RSA) Pollution High in the Johannesburg area (industrial, pollution from traffic, natural) Light-Medium for the major line distance (natural pollution) ESDD [mg/cm²] Unknown, not determined systemically Insulation HTV silicone rubber composite longrod, Generation I-III [1] Material HTV silicone compound with 48% ATH by weight Type Type 1: 30/82 (178/138) mm (major type), 30 mm FRP rod diameter, 82 sheds, alternating shallow underrib shed profile, shed diameter 178 & 138 mm, connection length h1=4160 mm, creepage distance mm, 30.2 mm/kv Shed Profile Type 2: 30/127 (168/134) mm, 30 mm FRP rod diameter, 127 sheds, alternating smooth shed profile, shed diameter 168 & 134 mm, connection length h1=5100 mm, creepage distance mm, 33.4 mm/kv Alternating, shallow underrib sheds (open profile) and Alternating, smooth sheds (open aerodynamic profile) Figure 4: Leakage current measurement during DC 5000 h test, 14 kv DC test voltage. The highest peak value of 9 ma was recorded during 3340 and 3350 h in the salt fog phase. Summary of results: The maximum leakage current during the test was very low (9 ma) Pg. 2 Paper C-12

3 No flashover occurred, no tracking and erosion, no sheds were punctured, no core rod became visible There was only a slight reduction in hydrophobicity class (HC), HC=1 (before test), HC=2-4 (after the test) The hydrophobicity has not been lost during the test and the slight reduction after the test has fully been recovered to HC=1 some days after the end of the test. Within the tested parameter spectrum the erosion depth and length reach a maximum at DC+5,5 kv. Both DC polarities lead to significant higher erosions than obtained at AC voltage. For DC+ voltage stress the erosion severity increases steadily with the test voltage. For DC- voltage stress a clear tendency can not be recognized, but the severity is at high level independent of the test voltage level. For AC voltage stress the already known erosion maximum in the range of 3,5 4,5 kv [5] has been confirmed. 2.2 Inclined Plane Test at DC Voltage In order to obtain an orientation regarding severity of DC voltage stress compared to AC stress (reference), the inclined plane test in accordance with IEC was applied. Presently, this test procedure is standardised only for AC voltage stress. Three test series were performed where both polarities of the DC voltage (DC+/DC-) and AC (r.m.s) voltage were applied to the HV electrode of the test setup [3]. The test voltage was varied at constant conductivity of the electrolytic test liquid. Tab. 3 summarizes the main test parameters. In deviation to the line insulator material, these test samples are made with 58 % (by weight) of ATH content as it is standard today. The 10 % point higher level typically gives a slightly improved T+E performance in the inclined plane test. Table 3: Test setup and test samples [3] Test procedure: IEC modified, DC+, DC-, AC (r.m.s.) Test samples: HTV silicone rubber, 58% ATH filled (by weight) Voltage [kv]: Flow rate [ml/min]: 0,15 0,30 0,60 0,90 R [k ]: Conductivity [ms/cm] 2,5 Test duration [h] 6 The individual tests were evaluated regarding erosion depth and erosion length. In order to obtain a comprehensive survey, the test results were normalised to the erosion maximum found at DC+ (5,5 kv) and expressed in per unit (p.u.). Fig. 5 shows the average erosion depth and Fig. 6 the respective average erosion length obtained from each test Erosion Depth [p.u.] 1,0 0,8 0,6 0,4 0,2 0,0 Test Voltage [kv] DC+ AC Figure 5: Erosion depth at DC+, DC- and AC (r.m.s.) depending on the test voltage. Erosion Length [p.u.] 1,0 0,8 0,6 0,4 0,2 0,0 Test Voltage [kv] DC+ DC- DC- AC Figure 6: Erosion length at DC+, DC- and AC (r.m.s.) depending on the test voltage. It can be concluded that the erosion severity in the inclined plane test at DC voltage stress is generally much higher than for AC (r.m.s.) stress. Even with 10 % points more ATH filled material much higher erosion depth values occur compared to AC tests and compared to DC service experience. In consequence, while the inclined plane test according to IEC is a helpful and commonly accepted tool in the evaluation and selection process for AC outdoor housing materials, it seems not to reflect the same correlation for DC stress. The experience from other ageing tests (5000 h DC test) and those from service performance show no correlation to the results of the DC modified inclined plane test. The applicability and representativity of the test at DC has therefore to be questioned critically and especially can not be used for any standardization today. 2.3 DC Performance and Hydrophobicity Fig. 7 was derived from former investigations regarding hydrophobicity, hydrophobicity transfer mechanism (HTM) and tracking and erosion resistance for HTV silicone rubber material compounds that are filled with ATH (alumina tri-hydrate, Al(OH) 3 ) [5]. Both, HTM and tracking and erosion resistance are indispensable features that influence the long-term performance of housing materials. The outdoor performance, respectively general dependence (black curve with a maximum between 55 and 60% b.w. ATH content) is the same for AC and DC stress, but the individual features (red and blue) differ of course depending on the relevant stress type (AC or DC). Pg. 3 Paper C-12

4 Performance 1 p.u. 0,9 0,8 0,7 0,6 0,5 0,4 0,3 0,2 0,1 HTM Tracking & Erosion Resistance Outdoor performance % ATH content (by weight) Figure 7: Outdoor performance of HTV silicone rubber compounds [5]. We assume that the hydrophobicity and the HTM behave completely differently under DC than under AC stress. One indication is the leakage current development in the 5000 h DC test and the observed hydrophobicity after the test as described in Chapter 2.1. A loss of hydrophobicity under DC stress here seems to be more unlikely than under AC stress, referring to available results from 5000 h AC tests. For a better comprehension the detailed coherences have to be studied in future scientific work. The data from service experience as well as laboratory tests clearly show that suitable HTV silicone rubber housing materials filled with suitable ATH can be used for AC as well as DC applications. The tracking and erosion resistance can be adapted by adding ATH filler while good hydrophobicity properties are in a well balanced setup. Furtheron, the ATH mineral filler is antistatic and avoids the formation and storage of critical space charges inside the material or on the housing surface. No additional antistatica are therefore necessary. 3. DISCUSSION 3.1 Simplified DC partial arc model Housing erosion is regarded as the most severe and critical ageing mechanism that could occur on composite insulators under DC and AC stress. Erosion processes and mechanisms are initiated by surface pollution and driven by effects such as pre-arcing and there mainly by stable low current partial arcs [5] also known as dry band arcing (DBA). To understand the differences in dry band arcing at AC and DC stress the simplified model according to Obenaus shown in Fig. 8 can be applied. Pollution driven DBA takes place with discharges to earth ground. R P is representing the ohmic resistance which is given majorily by the surface pollution of the insulator part that is free of discharges and supplying ohmic leakage current to the plasma discharges in the DBA zone(s). C D is the operating capacity of the discharge free parts of the insulator, e.g. between end fittings and DBA discharge zone(s). At AC stress a significant amount of capacitive leakage current can be supplied to the discharges in the DBA zone(s). Since =o and the impedance over Z D = for DC voltage, all the feeding current for potential DBA discharges has to be supplied via R P. R P on the other hand strongly depends on two parameters: the conductivity of surface pollution (pollution severity expressed in ESDD or surface conductivity) and on the hydrophobicity. Thus, critical feeding currents for DC DBA in present installations (Pacific Intertie, Cabora Bassa) seem to be avoided by both, non-critical surface pollution and/or intact surface hydrophobicity. Therefore no critical damages can be observed. Figure 8: Simplified partial arc model. The modified inclined plane test results at DC show severe damages at both polarities, but no correlation to real HVDC line installations can be derived as they do not show erosion. This can be explained also with the Obenaus model in Fig. 8: the inclined plane test suppresses intentionally all hydrophobicity effects and is performed at relative high surface conductivity, also the local stability of pre-arcs and partial discharges that cause the damages are very high since there is no current zero at DC stress. R P is low and sufficient leakage current is supplied for critical stable discharges with sufficient energy that will lead to severe erosions. Therefore one interesting question has to be placed: what is the critical value of R P, Crit for real HVDC line insulators? Here, it should be kept in mind that R P is mainly dependent on surface pollution severity and hydrophobicity effects. 3.2 Critical pollution stress situations The HVDC results from service experience and laboratory tests are obviously contradictionary. The following questions / concerns are therefore raised for further research and development: 1. is the modified inclined plane test at DC voltage stress with the present test setup and parameters representative for the material selection process for DC materials? 2. if yes, then a critical pollution condition is mainly dominated by R p, Crit. If R P < R p, Crit then severe damages have to be expected for HVDC line insulators at high/very high pollution severities. 3. since existing installations are presently operating at light/medium pollution severity and show no traces of ageing but excellent insulation characteristics, it has to be assumed that in these cases they operate at R p > R p, Crit? 4. is it possible to develop a future artificial pollution / ageing test that is evaluating these effects and finally allow proper material and insulator design selection? Pg. 4 Paper C-12

5 3.3 DC Ageing and Pollution Test Presently, CIGRE WG C is developing a pollution / ageing test [6]. The experiences, findings and ideas of this paper should be considered for the definition of test parameters and conditions. 4. CONCLUSION Long-term service experience with existing silicone rubber composite suspension/tension insulators in HVDC overhead transmission lines is excellent. The direct evidence is the superior service performance of the overhead transmission lines Cabora Bassa Apollo and Pacific Intertie. Both lines have successfully been in service for more than 25 years insulated with silicone rubber composite insulators [2]. A review on the insulator designs showed that 25 years ago the selection of creepage distance and shed profile has been done adequately and even in accordance with today's knowledge and new draft IEC standards for HVDC insulators. This is as well confirmed by application of statistical design methods by means of IST software [6]. Both lines are operating under light/medium (partly/locally high) pollution conditions. The hydrophobicity of the silicone rubber housing and the hydrophobicity transfer effect was maintained over the whole service period at both lines up to now. A 5000 h multi-ageing (design) test was performed at DC test voltage. The leakage current during the test was much lower than in comparable AC tests in accordance with IEC [4]. The hydrophobicity of the silicone rubber housing was maintained during the whole test period and resulted in HC=2-4 obtained after the test in the final evaluation. The low leakage current during the test was a result of the maintained surface hydrophobicity. No damages caused by tracking and erosion were detected. The characteristics of these test results indicate that the hydrophobicity loss mechanism is apparently completely different at DC than at AC voltage stress. The test results of the 5000 h test are fully reflecting the long-term service experience of the HVDC lines presented above and in [2]. Material tests were performed using the inclined plane test in accordance with IEC which was modified for DC test voltage. A variation of voltage stress was done for both polarities of the DC voltage from 2,5 to 5,5 kv. For reference purpose, also a series of AC test voltage was tested with the same voltage interval and steps. The material tested was a typical high quality HTV silicone rubber compound filled with 58 % (by weight) with ATH filler for extrusion processing. Such materials are applied for more than 25 years and are also used in today s Generation III silicone rubber composite longrod insulators for HVDC and HVAC applications [1]. The obtained inclined plane test results which show severe erosion at DC are in complete contradiction to the excellent service performance and the results of the 5000 h DC test. The test erosion severities at both DC polarities are signficantly higher those at AC. The dependence on voltage level is also different for DC and AC. The surface hydrophobicity is intentionally fully suppressed during the inclined plane test. Since the hydrophobicity seems to be the protecting feature in real service and also during the 5000 h test, the results of the inclined plane DC test likely will mislead if applied for the material selection process for DC materials. Nevertheless, the inclined plane test has been accepted and shown representativity for the material selection process for AC materials. With the results obtained in this study it has to be regarded as not representative for DC applications. This must be considered if a DC material test for tracking and erosion is discussed for future standardisation process. A simple model for leakage current supply of partial arcs has been introduced and discussed. Since at DC voltage stress there is no capacitive part of the leakage current, the feeding current for partial arc is only supplied via the ohmic current (represented by R P in the equivalent circuit scheme). R P is mainly dependent on the surface pollution of the silicone rubber housing and its hydrophobic effects (intrinsic hydrophobicity and hydrophobicity transfer mechanism). As long as these hydrophobic effects are able to suppress the ohmic leakage currents, no critical leakage currents, dry band and/or partial arcs come into effectiveness and in such a state no critical tracking and erosion effects are expected. Theoretically, the existence of a critical value for R P can be derived from this simplified model. This fundamental theoretical insight is very important and has to be considered when line insulation design is made for heavy and very heavy pollution severities or if critical hydrophobicity states have to be expected from environmental or climatic impacts. This should be considered in future standardisation work within CIGRE and IEC, namely when IEC will be discussed. For the time being, worldwide there is no report about negative performance of silicone rubber longrod insulators at HVDC. On the other hand, there are very positive long-term service experiences with Generation III silicone rubber longrod insulators over more than 25 years at HVDC. Since the dominating problems of conventional insulators (hardware corrosion, cement growth, electrolytic elements and accumulation effects) are per se avoided with composite insulators, these products offer the best alternative for such line insulations and are superior to glass and porcelain disk insulators. HTV silicone rubber with ATH filler are suitable for both AC and DC applications. The results of this study are very encouraging to apply these products for future HVDC installations for 500 kv and above. Very special care has to be taken if for material testing existing AC tests are applied similarly with DC voltage. The results may be misleading and not transferable to real insulator applications. 5. REFERENCES [1] J. M. Seifert, Innovations in the Field of Composite Insulators Review on 40 Years of Pg. 5 Paper C-12

6 Experience, LAPP RODURFLEX 40 Years Convention, th February 2008, Tröstau, Germany. [2] CIGRE WG B2.03, Service Performance of Composite Insulators used on HVDC lines, ELECTRA No. 161, August [3] IEC 60587, Electrical insulating materials used under severe ambient conditions - Test methods for evaluating resistance to tracking and erosion (IEC 60587:2007). [4] IEC 62217, Polymeric insulators for indoor and outdoor use with a nominal voltage > 1000 V - General definitions, test methods and acceptance criteria (IEC 62217:2005). [5] J. M. Seifert, D. Stefanini, High Pollution Resistant Composite Insulators, ICHVE 2008, Nov th, 2008, Chongqing, China. [6] CIGRE WG C , A laboratory test method for polymeric insulators, IWD draft [7] W.L. Vosloo, R. Stephen, P. Naidoo, I. Gutman, D. Muftic, N. Ijumba, External Insulation Functional Specification for the Upgrade of a 400 kv AC Transmission Line to 500 kv, DC, SAUPEC 2007, South Africa. Pg. 6 Paper C-12

produces and delivers products worldwide can provide the optimal are dedicated to supplying you with superior advice and global support.

produces and delivers products worldwide can provide the optimal are dedicated to supplying you with superior advice and global support. www.ppcinsulators.com The very Best. The very Best. That s what we deliver. ong od Insulators Only a company that develops, produces and delivers products worldwide can provide the optimal solution for

More information

Design and testing of polymer-housed surge arresters with special emphasize on seismic stresses and selection of specific creepage in costal areas.

Design and testing of polymer-housed surge arresters with special emphasize on seismic stresses and selection of specific creepage in costal areas. 108 Design and testing of polymer-housed surge arresters with special emphasize on seismic stresses and selection of specific creepage in costal areas. S. Narita, A. Sawada, L. Stenström H. Watanabe, B.

More information

IEC/CIGRE UHV Symposium Beijing 2007-07-23 3-1-4 800KVDC: EXTERNAL INSULATION, INSULATION COORDINATION, TEST LEVELS

IEC/CIGRE UHV Symposium Beijing 2007-07-23 3-1-4 800KVDC: EXTERNAL INSULATION, INSULATION COORDINATION, TEST LEVELS IEC/CIGRE UHV Symposium Beijing 2007-07-23 3-1-4 800KVDC: EXTERL INSULATION, INSULATION COORDITION, TEST LEVELS D. Wu (*) U. Åström V. F. Lescale ABB Power Systems, HVDC Ludvika, Sweden SUMMARY The use

More information

The very Best. ANSI Post Insulators 2016

The very Best. ANSI Post Insulators 2016 The very Best. ANSI Post Insulators 2016 Introduction ANSI Post Insulators High Tech TR Post Never comprom Better Design enables higher performances with less weight Under normal service conditions, the

More information

HV glass suspension insulator U70BS and U70BL type Ball and socket type Standard profile

HV glass suspension insulator U70BS and U70BL type Ball and socket type Standard profile U70BS and U70BL type IEC 60305 U70BS U70BL GOST 27661 ПС70Е ПС70Е Minimum mechanical failing load kn 70 70 Minimum mechanical residual strength kn 56 56 Diameter of the insulating part, D mm 255 255 Nominal

More information

Electricity. Confirming Coulomb s law. LD Physics Leaflets P3.1.2.2. 0909-Wie. Electrostatics Coulomb s law

Electricity. Confirming Coulomb s law. LD Physics Leaflets P3.1.2.2. 0909-Wie. Electrostatics Coulomb s law Electricity Electrostatics Coulomb s law LD Physics Leaflets Confirming Coulomb s law P3... Measuring with the force sensor and newton meter Objects of the experiments Measuring the force between two charged

More information

Composite Insulators Suspensions Line Posts Brace Posts Station Posts

Composite Insulators Suspensions Line Posts Brace Posts Station Posts Composite Insulators Suspensions Line Posts Brace Posts Station Posts Quality, reliability and consistency for over four decades As an alternative and complement to our range of proven ceramic insulators,

More information

EFFECTS OF CORONA RING DESIGN ON ELECTRIC FIELD INTENSITY AND POTENTIAL DISTRIBUTION ALONG AN INSULATOR STRING

EFFECTS OF CORONA RING DESIGN ON ELECTRIC FIELD INTENSITY AND POTENTIAL DISTRIBUTION ALONG AN INSULATOR STRING EFFECTS OF CORONA RING ESIGN ON ELECTRIC FIEL INTENSITY AN POTENTIAL ISTRIUTION ALONG AN INSULATOR STRING Suat İlhan Aydoğan Özdemir e-mail: ilhan@elk.itu.edu.tr e-mail: ozdemir@elk.itu.edu.tr Electrical

More information

Guidance for upgrading to GB4943.1-2011 (IEC 60950-1: 2005, MOD)

Guidance for upgrading to GB4943.1-2011 (IEC 60950-1: 2005, MOD) Guidance for upgrading to GB4943.1-2011 (IEC 60950-1: 2005, MOD) Note: This guidance document is a translation of official Chinese document which is issued by CQC (China Quality Certification Center) on

More information

A Practical Guide to Dielectric Testing

A Practical Guide to Dielectric Testing Chroma Systems Solutions, Inc. A Practical Guide to Dielectric Testing 19032 Series Electrical Safety Analyzer & 19050 Series Hipot Tester AC/DC/IR/SCAN Keywords: Dielectric tests, insulation resistance

More information

Aluminum Electrolytic Capacitors Radial Miniature, Low Impedance, High Vibration Capability

Aluminum Electrolytic Capacitors Radial Miniature, Low Impedance, High Vibration Capability Aluminum Electrolytic Capacitors Radial Miniature, Low Impedance, High Vibration Capability 048 RML 48 RUS lower longer life 36 RVI miniaturize 50 RMI high vibration FEATURES Very long useful life: 7000

More information

Electrical Considerations for HVDC Transmission Lines. Joe Mooney, PE

Electrical Considerations for HVDC Transmission Lines. Joe Mooney, PE Electrical Considerations for HVDC Transmission Lines Joe Mooney, PE POWER Engineers has met the standards and requirements of the Registered Continuing Education Program. Credit earned on completion of

More information

Condition Monitoring of equipment to improve quality of supply to customers by averting failures

Condition Monitoring of equipment to improve quality of supply to customers by averting failures Condition Monitoring of equipment to improve quality of supply to customers by averting failures Author & presenter: Patrick O Halloran BTECH Manager Technology Services at City Power Johannesburg Abstract

More information

White Paper. Safety Considerations When Using Optocouplers and Alternative Isolators for Providing Protection Against Electrical Hazards.

White Paper. Safety Considerations When Using Optocouplers and Alternative Isolators for Providing Protection Against Electrical Hazards. Safety Considerations When Using Optocouplers and Alternative Isolators for Providing Protection Against Electrical Hazards White Paper Introduction Optocouplers and alternative isolation technologies

More information

High-Voltage Compact Switchgear 3AP1 DTC for 145 kv and 245 kv

High-Voltage Compact Switchgear 3AP1 DTC for 145 kv and 245 kv High-Voltage Compact Switchgear AP1 DTC for 1 kv and kv Answers for energy. The AP1 DTC Complying with our Customers demands Experience you can rely on - at anytime, anywhere Decades of experience in high-voltage

More information

Aluminum Capacitors Solid Axial

Aluminum Capacitors Solid Axial SAL-A End of Life. Last Available Purchase Date is -December- Radial higher CV/volume Fig. QUICK REFERENCE DATA DESCRIPTION VALUE Maximum case size (Ø D x L in mm) 6.7 x. to.9 x. Rated capacitance range

More information

ACCESSORIES FOR HV CABLES WITH EXTRUDED INSULATION

ACCESSORIES FOR HV CABLES WITH EXTRUDED INSULATION ACCESSORIES FOR HV CABLES WITH EXTRUDED INSULATION Ref: WG 21.06 (TB 177) JTF 21.15 (TB 210) TF B1.10 (Electra 212) Henk Geene Presentation overview Accessories function Accessory design Accessory types

More information

2013 RESIBLOC transformers Product presentation. ABB Group October 2, 2013 Slide 1

2013 RESIBLOC transformers Product presentation. ABB Group October 2, 2013 Slide 1 2013 RESIBLOC transformers Product presentation October 2, 2013 Slide 1 Dry-type transformers For customers with high requirements Does your transformer application requires one of the following characteristic?

More information

MiCAFIL. 1 RIP Technology. Bushings. Z. Zic 09/2003

MiCAFIL. 1 RIP Technology. Bushings. Z. Zic 09/2003 MiCAFIL 1 RIP Technology Z. Zic 09/2003 )XQFWLRQRI+LJK9ROWDJH%XVKLQJ Uncontrolled (natural) electrical field Capacity-controlled electrical field %XVKLQJV0DLQ,QVXODWLRQ6\VWHPV 7\SH 0DLQ,QVXODWLRQ +RXVLQJFRYHU

More information

Digital Energy ITI. Instrument Transformer Basic Technical Information and Application

Digital Energy ITI. Instrument Transformer Basic Technical Information and Application g Digital Energy ITI Instrument Transformer Basic Technical Information and Application Table of Contents DEFINITIONS AND FUNCTIONS CONSTRUCTION FEATURES MAGNETIC CIRCUITS RATING AND RATIO CURRENT TRANSFORMER

More information

Adaption of Cable Accessories for Onshore and Offshore Substation

Adaption of Cable Accessories for Onshore and Offshore Substation Adaption of Cable Accessories for Onshore and Offshore Substation www.pfisterer.com the power connection Impressum Editor PFISTERER Holding AG Rosenstraße 44 73650 Winterbach Phone +49 7181 7005-0 Fax

More information

Understanding Insulation Resistance Testing

Understanding Insulation Resistance Testing Understanding Insulation Resistance Testing Why have an insulation testing program? A regular program of testing insulation resistance is strongly recommended to prevent electrical shocks, assure safety

More information

CHAPTER 5 PHOTOVOLTAIC SYSTEM DESIGN

CHAPTER 5 PHOTOVOLTAIC SYSTEM DESIGN CHAPTER 5 PHOTOVOLTAIC SYSTEM DESIGN 5.1 Introduction So far in the development of this research, the focus has been to estimate the available insolation at a particular location on the earth s surface

More information

WIRE AND CABLE ENGINEERING GUIDE

WIRE AND CABLE ENGINEERING GUIDE DC Hi Pot Testing Excerpt from PRYSMIAN S WIRE AND CABLE ENGINEERING GUIDE (FOR INFORMATIONAL PURPOSES ONLY) Page 1 of 6 DC HIGH POTENTIAL TESTING DC Hi-Pot testing can be applied as a withstand test (a

More information

Fault location on power cables. Fault location on power cables

Fault location on power cables. Fault location on power cables Fault location on power cables Fault location on power cables Contents: 1. Introduction 2. Construction of power cables 3. Cable faults 01. Introduction Fault location on communication and power cables

More information

Guide to the electrical parameter classifications of IEC 60950 and IEC 62368 safety standards

Guide to the electrical parameter classifications of IEC 60950 and IEC 62368 safety standards Guide to the electrical parameter classifications of IEC 60950 and IEC 62368 safety standards Abstract This Guide is an informative listing of selected terms and definitions found in IEC Glossary entry

More information

DISCONNECTORS AND LOAD SWITCHES for railways

DISCONNECTORS AND LOAD SWITCHES for railways DISCONNECTORS AND LOAD SWITCHES for railways GRID Disconnectors and load switches for railways Alstom Grid delivers transmission solutions worldwide to utility and large industrial customers seeking smarter,

More information

INTERNATIONAL STANDARD

INTERNATIONAL STANDARD INTERNATIONAL STANDARD IEC 60071-2 Third edition 1996-12 Insulation co-ordination Part 2: Application guide This English-language version is derived from the original bilingual publication by leaving out

More information

Type: EASY719 DC RC Article No.: 274119. Ordering information Relay outputs Quantity 6 Power supply V DC 24 V DC. Description

Type: EASY719 DC RC Article No.: 274119. Ordering information Relay outputs Quantity 6 Power supply V DC 24 V DC. Description Type: EASY719 DC RC Article.: 274119 Ordering information Relay outputs Quantity 6 Power supply V DC 24 V DC Description 12 digital inputs (4 inputs available as analog inputs) 6 relay outputs LCD display

More information

Fuzzy Data Mining as a Tool to Infer Pollution Severity of Power Transmission Line System

Fuzzy Data Mining as a Tool to Infer Pollution Severity of Power Transmission Line System Journal of Applied Science and Engineering, Vol. 16, No. 1, pp. 79 87 (2013) 79 Fuzzy Data Mining as a Tool to Infer Pollution Severity of Power Transmission Line System K. Karpagavani 1 * and A. Kumaravel

More information

uclamp3301h Low Voltage μclamp TM for ESD and CDE Protection PRELIMINARY Features

uclamp3301h Low Voltage μclamp TM for ESD and CDE Protection PRELIMINARY Features PROTECTION PRODUCTS -MicroClamp Description The μclamp series of Transient Suppressors (TVS) are designed to replace multilayer varistors (MLVs) in portable applications such as cell phones, notebook computers,

More information

Product Safety Considerations for Insulation Coordination of Low- Voltage Equipment. Scott Aldous, Compliance Engineer

Product Safety Considerations for Insulation Coordination of Low- Voltage Equipment. Scott Aldous, Compliance Engineer Product Safety Considerations for Insulation Coordination of Low- Voltage Equipment Scott Aldous, Compliance Engineer What is Insulation Coordination? From IEC 60664-1, Edition 1.2: So what does that mean

More information

New Distribution Class Arrester Ground Lead Disconnector Design Enhances Detonation Reliability and Improves Arrester Performance

New Distribution Class Arrester Ground Lead Disconnector Design Enhances Detonation Reliability and Improves Arrester Performance New Distribution Class Arrester Ground Lead Disconnector Design Enhances Detonation Reliability and Improves Arrester Performance Dennis W. Lenk, Fellow, IEEE Abstract-- This paper examines performance

More information

High-ohmic/high-voltage resistors

High-ohmic/high-voltage resistors FEATURES These resistors meet the safety requirements of: UL1676 (range 510 kω to 11 MΩ) EN60065 BS60065 (U.K.) NFC 92-130 (France) VDE 0860 (Germany) High pulse loading capability Small size. APPLICATIONS

More information

High-ohmic/high-voltage resistors

High-ohmic/high-voltage resistors FEATURES High pulse loading capability Small size. APPLICATIONS Where high resistance, high stability and high reliability at high voltage are required High humidity environment White goods Power supplies.

More information

Transmission Silicone Insulators Line Post 69 kv to 161 kv

Transmission Silicone Insulators Line Post 69 kv to 161 kv K-LINE INSULATORS LIMITED Catalogue T-LP Transmission Silicone Insulators Line Post 69 kv to 161 kv ISO9001 SAI GLOBAL FILE No. 000117 Transmission Silicone Insulators Line Post Today transmission lines

More information

Performance of Carbon-PTFE Electrodes and PTFE Separators in Electrochemical Double Layer Capacitors (EDLCs)

Performance of Carbon-PTFE Electrodes and PTFE Separators in Electrochemical Double Layer Capacitors (EDLCs) Performance of Carbon-PTFE Electrodes and PTFE Separators in Electrochemical Double Layer Capacitors (EDLCs) David Zuckerbrod, Robert Sassa, Marianne Szabo, Meagan Mizenko Abstract: W. L. Gore & Associates

More information

Power Voltage Transformers for Air Insulated Substations. THE PROVEN POWER.

Power Voltage Transformers for Air Insulated Substations. THE PROVEN POWER. Power Voltage Transformers for Air Insulated Substations THE PROVEN POWER. Introduction Trench Power Voltage Transformers (Power VTs) combine the attributes of an inductive voltage transformer with the

More information

Design Test Report Report No. EU1531-H ANSI C29.18 PROTOTYPE/ CEA LWIWG 02 DESIGN TEST REPORT Silicone Rubber 69 kv Veri*Lite Line Post 80S069

Design Test Report Report No. EU1531-H ANSI C29.18 PROTOTYPE/ CEA LWIWG 02 DESIGN TEST REPORT Silicone Rubber 69 kv Veri*Lite Line Post 80S069 Design Test Report Report No. EU1531-H ANSI C29.18 PROTOTYPE/ CEA LWIWG 02 DESIGN TEST REPORT Silicone Rubber 69 kv Veri*Lite Line Post 80S069 This test report records the results of laboratory tests made

More information

08. SEK IDC CONNECTORS

08. SEK IDC CONNECTORS . IDC CONNECTORS connectors for flat cables enable simple and, cost-optimized device configuration. connectors are preferably used for connection within the device. HARTING offers a broad range of these

More information

LUXEON LEDs. Circuit Design and Layout Practices to Minimize Electrical Stress. Introduction. Scope LED PORTFOLIO

LUXEON LEDs. Circuit Design and Layout Practices to Minimize Electrical Stress. Introduction. Scope LED PORTFOLIO LED PORTFOLIO LUXEON LEDs Circuit Design and Layout Practices to Minimize Electrical Stress Introduction LED circuits operating in the real world can be subjected to various abnormal electrical overstress

More information

Using Equotip Hardness Test Blocks Abstract 1. Introduction 2. Verification of Leeb hardness testers according to standards

Using Equotip Hardness Test Blocks Abstract 1. Introduction 2. Verification of Leeb hardness testers according to standards Using Equotip Hardness Test Blocks Heinz-Horst Pollok, consultant for material testing and instrument electronics (Cologne, Germany) Dr. Ralph T. Mennicke, product manager for material testing, Proceq

More information

LEP 4.4.07. Rectifier circuits

LEP 4.4.07. Rectifier circuits Related topics Half-wave rectifier, full-wave rectifier, Graetz rectifier, diode, Zener diode, avalanche effect, charging capacitor, ripple, r.m.s. value, internal resistance, smoothing factor, ripple

More information

Power transformers. Special transformers Railway

Power transformers. Special transformers Railway Power transformers Special transformers Railway A leader in railway systems Our compact and low-weight transformers fully comply with the customer s specifications. The products are developed together

More information

Handheld portable appliance testers

Handheld portable appliance testers PAT100 SERIES Handheld portable appliance testers PAT100 SERIES Handheld portable appliance testers Simple Tick/Cross, pass/fail indication plus measurement Battery powered with rechargeable options Includes

More information

Medium voltage insulator

Medium voltage insulator Medium voltage insulator Line post insulators type R-ET Commercial designation LPI 24 N ET 1) LPI 24 L ET/5 1)2) LPI 24 L ET/6 1)2) LPI 38 L ET 1) esignation acc. to IEC 720 R 12,5 ET 125 N R 12,5 ET 125

More information

HVDC Technology for Large Scale Offshore Wind Connections

HVDC Technology for Large Scale Offshore Wind Connections HVDC Technology for Large Scale Offshore Wind Connections Nandan Mahimkar, Gunnar Persson,Claes Westerlind, ABB AB, SE-771 80, Ludvika, Sweden, nandan.mahimkar@in.abb.com, gunnar.persson@se.abb.com,claes.westerlind@se.abb.com,

More information

Modeling of Transmission Lines

Modeling of Transmission Lines Modeling of Transmission Lines Electric Power Transmission The electric energy produced at generating stations is transported over high-voltage transmission lines to utilization points. The trend toward

More information

www.siemens.com/energy/arresters A full range of monitoring solutions for surge arresters Answers for energy.

www.siemens.com/energy/arresters A full range of monitoring solutions for surge arresters Answers for energy. www.siemens.com/energy/arresters A full range of monitoring solutions for surge arresters Answers for energy. Highly reliable equipment monitoring with added value ACM advanced ACM basic and LCM 500 Overview

More information

Length measuring instruments

Length measuring instruments INTERNATIONAL OIML R 66 RECOMMENDATION Edition 1985 (E) Length measuring instruments Instruments mesureurs de longueurs OIML R 66 Edition 1985 (E) ORGANISATION INTERNATIONALE DE MÉTROLOGIE LÉGALE INTERNATIONAL

More information

S P E C I F I C A T I O N F O R L I T H I U M B A T T E R Y. M o d e l : C R 2 0 3 2

S P E C I F I C A T I O N F O R L I T H I U M B A T T E R Y. M o d e l : C R 2 0 3 2 S P E C I F I C A T I O N F O R L I T H I U M B A T T E R Y M o d e l : C R 2 0 3 2 Approved By Department Name Title Signature/Date (Remarks: The above table shall be filled by customer) POWER GLORY BATTERY

More information

CABLE ACCESSORIES 110-220 kv

CABLE ACCESSORIES 110-220 kv CABLE ACCESSORIES 110-220 kv Termination 110 kv Technical description Termination MKB 126 / 145 with composite type insulator uses for cable line joints with other elements of power-supply systems. Termination

More information

Design qualification and type approval of PV modules

Design qualification and type approval of PV modules Design qualification and type approval of PV modules TÜV Immissionsschutz und Energiesysteme GmbH Test Centre for Energy technologies May 2003 Design qualification and type approval of PV-modules in accordance

More information

Calculating Creepage and Clearance Early Avoids Design Problems Later Homi Ahmadi

Calculating Creepage and Clearance Early Avoids Design Problems Later Homi Ahmadi Calculating Creepage and Clearance Early Avoids Design Problems Later Homi Ahmadi One of the most common errors uncovered by product safety engineers stems from manufacturers and designers failing to fully

More information

For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit.

For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit. Current Transducer HO-P series I PN = 6, 10, 25 A Ref: HO 6-P, HO 10-P, HO 25-P For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary

More information

No Heat. No Flames. No Shoving. No Special Tools. 3M Cold Shrink. 3M Cold Shrink. Medium Voltage Joints & Terminations. 3M Cold Shrink Joint

No Heat. No Flames. No Shoving. No Special Tools. 3M Cold Shrink. 3M Cold Shrink. Medium Voltage Joints & Terminations. 3M Cold Shrink Joint M Cold Shrink Medium Voltage Joints & Terminations M Cold Shrink Joint Splice bodies 00% factory tested - ensures reliability Capacitive Stress Relief No Heat No Flames No Special Tools No Shoving Unique

More information

Electrical Safety Products

Electrical Safety Products Electrical Safety Products Trelleborg Electrical Safety Products A safe working environment is important in all industries, but in the electrical generation and supply industry, it is paramount. Trelleborg

More information

DC Film Capacitors MKT Radial Potted Type

DC Film Capacitors MKT Radial Potted Type DC Film Capacitors MKT Radial Potted Type FEATURES 15 mm to 27.5 mm lead pitch. Supplied loose in box and taped on reel Material categorization: for definitions of compliance please see www.vishay.com/doc?99912

More information

Axial and Radial Leaded Multilayer Ceramic Capacitors for Automotive Applications Class 1 and Class 2, 50 V DC, 100 V DC and 200 V DC

Axial and Radial Leaded Multilayer Ceramic Capacitors for Automotive Applications Class 1 and Class 2, 50 V DC, 100 V DC and 200 V DC Axial and Radial Leaded Multilayer Ceramic Capacitors for Automotive Applications Class 1 and Class 2, 5 V DC, 1 V DC and 2 V DC DESIGNING For more than 2 years Vitramon has supported the automotive industry

More information

Magnetic and Hydraulic-Magnetic Circuit Breaker 8340-G2...

Magnetic and Hydraulic-Magnetic Circuit Breaker 8340-G2... Magnetic and Hydraulic-Magnetic Circuit Breaker 840-G2... Description Single, two and three pole magnetic circuit breakers with trip-free mechanism and push/pull on/off manual actuation. A choice of fast

More information

Application Bulletin AB-2 Isolator High Voltage Safety Standards

Application Bulletin AB-2 Isolator High Voltage Safety Standards Application Bulletin AB-2 Isolator High Voltage Safety Standards IsoLoop Isolators have exceptional high-voltage performance and meet applicable safety standards. The standards summarized in this Bulletin

More information

IEC and IEEE Standards for High-Voltage Switchgear and Controlgear Present Situation and Future Evolution

IEC and IEEE Standards for High-Voltage Switchgear and Controlgear Present Situation and Future Evolution IEC and IEEE Standards for High-Voltage Switchgear and Controlgear Present Situation and Future Evolution Denis Dufournet Chairman IEC TC 17 & SC17A Fellow IEEE Senior Expert Areva T&D Mumbai, January,

More information

Preliminary Results from Present Cigre Survey

Preliminary Results from Present Cigre Survey Cigre WG A3-06 HV Equipment Reliability Preliminary Results from Present Cigre Survey Gas Insulated Substations (GIS) DB status : August 2007 Focus on population cards and major failure cards (namely 2004

More information

SINEAX U553 Transducer for AC Voltage

SINEAX U553 Transducer for AC Voltage With power supply RMS value measurement Carrying rail housing P/0 Application he transducer SINEAX U55 (Fig. ) converts a sinusoidal or a distorted AC voltage into a load independent DC current or a load

More information

WW12X, WW08X, WW06X, WW04X ±1%, ±5% Thick Film Low ohm chip resistors

WW12X, WW08X, WW06X, WW04X ±1%, ±5% Thick Film Low ohm chip resistors WW12X, WW08X, WW06X, WW04X ±1%, ±5% Thick Film Low ohm chip resistors Size 1206, 0805, 0603, 0402 *Contents in this sheet are subject to change without prior notice. Page 1 of 8 ASC_WWxxX_V12 Nov.- 2011

More information

High-Voltage Circuit-Breakers 3AP1/2 72.5 kv up to 550 kv. Power Transmission and Distribution

High-Voltage Circuit-Breakers 3AP1/2 72.5 kv up to 550 kv. Power Transmission and Distribution High-Voltage Circuit-Breakers AP/ 7.5 kv up to 550 kv Power Transmission and Distribution The AP/ High-Voltage Circuit-Breakers Now Applicable for 550 kv Decades of our experience in high-voltage switching

More information

PB POWER ISLAND OF IRELAND CAVAN-TYRONE AND MEATH-CAVAN 400KV PROJECTS PRELIMINARY BRIEFING NOTE OVERHEAD AND UNDERGROUND ENERGY TRANSMISSION OPTIONS

PB POWER ISLAND OF IRELAND CAVAN-TYRONE AND MEATH-CAVAN 400KV PROJECTS PRELIMINARY BRIEFING NOTE OVERHEAD AND UNDERGROUND ENERGY TRANSMISSION OPTIONS ISLAND OF IRELAND CAVAN-TYRONE AND MEATH-CAVAN 400KV PROJECTS PRELIMINARY BRIEFING NOTE OVERHEAD AND UNDERGROUND ENERGY TRANSMISSION OPTIONS FEBRUARY 2008 PB POWER PB Power Page i EXECUTIVE SUMMARY General

More information

State, trends and evolutions of HV/EHV power cables systems and contributions of SC B1 to their ongoing progress

State, trends and evolutions of HV/EHV power cables systems and contributions of SC B1 to their ongoing progress 0611-048-Mep229 12/12/06 6:44 Page 22 State, trends and evolutions of HV/EHV power cables systems and contributions of SC B1 to their ongoing progress Reinhard SCHROTH, Chairman of SC B1 2002-2006 High

More information

6 ELECTRICAL PARAMETERS

6 ELECTRICAL PARAMETERS 6 ELECTRICAL PARAMETERS For power, low voltage and medium voltage cables, cross section nominal areas are calculated in taking into account several parameters as: permissible current carrying capacities

More information

MONITORING OF LEAKAGE CURRENT FOR COMPOSITE INSULATORS AND ELECTRICAL DEVICES

MONITORING OF LEAKAGE CURRENT FOR COMPOSITE INSULATORS AND ELECTRICAL DEVICES Monitoring Rev.Adv.Mater.Sci. of leakage 21(2009) current 75-89 for composite insulators and electrical devices 75 MONITORING OF LEAKAGE CURRENT FOR COMPOSITE INSULATORS AND ELECTRICAL DEVICES Muhammad

More information

VIPERFLEX ELECTRIC CABLE

VIPERFLEX ELECTRIC CABLE VIPERFLEX Flexible Low Voltage Electric Cable - 0.6/1kV (Rubber insulated) H07 RN-F & H07 BN-F Single Core 2-Core 2-Core and Earth 3-Core and Earth 4-Core and Earth Multi-Core and Earth H07 RCN-F & H07

More information

AC and Pulse Film Foil Capacitors KP Radial Potted Type

AC and Pulse Film Foil Capacitors KP Radial Potted Type AC and Pulse Film Foil Capacitors KP Radial Potted Type 0.5 L max. W max. Marking H max. FEATURES 5 mm lead pitch, supplied loose in box taped in ammopack or reel Material categorization: for definitions

More information

Optocoupler, Phototransistor Output, AC Input

Optocoupler, Phototransistor Output, AC Input Optocoupler, Phototransistor Output, AC Input DESCRIPTION The SFH62A (DIP) and SFH626 (SMD) feature a high current transfer ratio, low coupling capacitance and high isolation voltage. These couplers have

More information

Aluminum Electrolytic Capacitors Power Eurodin Printed Wiring

Aluminum Electrolytic Capacitors Power Eurodin Printed Wiring Aluminum Electrolytic Capacitors Power Eurodin Printed Wiring 00/0 PEDPW Fig. QUICK REFERENCE DATA DESCRIPTION VALUE 00 0 Nominal case size (Ø D x L in mm) x 0 to 0 x 00 Rated capacitance range 0 μf to

More information

SUITABILITY OF DIFFERENT TEST VOLTAGES FOR ON-SITE TESTING OF XLPE CABLE SYSTEMS

SUITABILITY OF DIFFERENT TEST VOLTAGES FOR ON-SITE TESTING OF XLPE CABLE SYSTEMS SUITABILITY OF DIFFERENT TEST VOLTAGES FOR ON-SITE TESTING OF XLPE CABLE SYSTEMS Michael Hensel HIGHVOLT Prüftechnik Dresden GmbH 2 3 Content 1 Introduction Test parameters and their significance Differences

More information

DS 600. A contact free flux gate based current measurement sensor 600A rms

DS 600. A contact free flux gate based current measurement sensor 600A rms DS 600 A contact free flux gate based current measurement sensor 600A rms DS 600 is member of the small housing sensor family. The family includes a 200A and a 600A version. 600A rms - 900A peak Maximum

More information

Part Marking Instructions Chip Resistors

Part Marking Instructions Chip Resistors Chip Resistors Part Marking Instructions Part Marking Instructions Chip Resistors 1% Marking The nominal resistance is marked on the surface of the overcoating with the use of 4 digit markings. 0201 and

More information

AMSC s Superconductor Cable Technologies for Electric Utilities

AMSC s Superconductor Cable Technologies for Electric Utilities International Workshop 2014 AMSC s Superconductor Cable Technologies for Electric Utilities Michael Ross, P.E. Managing Director of Superconductor Power Systems AMSC Corporate Facts Headquartered in MA,

More information

ENERGY. TECWATER S1BN8-F 0,6/1 kv. Cable for Water Application

ENERGY. TECWATER S1BN8-F 0,6/1 kv. Cable for Water Application ENERGY TECWATER S1BN8-F 0,6/1 kv Cable for Water Application Technical Data Electrical parameters Thermal parameters Trademark Type designation Specification Approval Application Rated voltage Maximum

More information

Circulating Current Relay. Type IRXm

Circulating Current Relay. Type IRXm Circulating Current Relay Type IRXm ABB a global technology leader ABB is a global leader in Power and Automation technologies that enable utility and industry customers to improve performance while lowering

More information

Submarine Power Cables. State-of-the-art production facility, more than 100 years of experience and reference installations around the world.

Submarine Power Cables. State-of-the-art production facility, more than 100 years of experience and reference installations around the world. Submarine Power Cables State-of-the-art production facility, more than 100 years of experience and reference installations around the world. Reliable submarine power cables ABB is one of the world s most

More information

Zhao et al. 2.2 Experimental Results in Winter Season The analysis given below was based on the data collected from Nov. 2003 to Mar. 15, 2004.

Zhao et al. 2.2 Experimental Results in Winter Season The analysis given below was based on the data collected from Nov. 2003 to Mar. 15, 2004. Proceedings World Geothermal Congress 2005 Antalya, Turkey, 24-29 April 2005 A Case Study of Ground Source Heat Pump System in China Jun Zhao, Chuanshan Dai, Xinguo Li, Qiang Zhu and Lixin Li College of

More information

EMTP STUDIES PERFORMED TO INSERT LONG AC CABLES IN THE FRENCH GRID

EMTP STUDIES PERFORMED TO INSERT LONG AC CABLES IN THE FRENCH GRID Tension (kv) Impedance (Ohms) EMTP STUDIES PERFORMED TO INSERT LONG AC CABLES IN THE FRENCH GRID frequency (Hz) Simon DESCHANVRES Yannick VERNAY RTE, CNER, Substations Department t (ms) EMTP-RV Users Group

More information

Estimation of electrical losses in Network Rail Electrification Systems

Estimation of electrical losses in Network Rail Electrification Systems Estimation of electrical losses in Network Rail Electrification Systems Page 1 of 16 Contents 1. BACKGROUND...3 2. PURPOSE...3 3. SCOPE...3 4. DEFINITIONS & ABBREVIATIONS...4 5. NETWORK RAIL INFRASTRUCTURE

More information

Transmissão em Corrente Contínua em Ultra-Alta Tensão

Transmissão em Corrente Contínua em Ultra-Alta Tensão Transmissão em Corrente Contínua Panorama Atual e Perspectias Futuras no Brasil Siemens AG 2012 Energy Sector Ultra-High Voltage Transmission Systems 2 Brazilian SC B4 Multiterminal HVDC Systems / VSC

More information

2. INDUCTIVE VOLTAGE TRANSFORMERS Oil-paper insulation Gas insulation

2. INDUCTIVE VOLTAGE TRANSFORMERS Oil-paper insulation Gas insulation 2. INDUCTIVE VOLTAGE TRANSFORMERS Oil-paper insulation Gas insulation 123 kv Inductive Fingrid (Finland). 18 Instrument transformers igh voltage INTRODUCTION Inductive voltage transformers are designed

More information

Two Position Cable-to-Board Power Connector System (Right Angle/Straight) with Coding Contacts

Two Position Cable-to-Board Power Connector System (Right Angle/Straight) with Coding Contacts Product Specification 108-19346 17 APR 2013 Rev F Two Position Cable-to-Board Power Connector System (Right Angle/Straight) with Coding Contacts 1. SCOPE 1.1. Content NOTE The product may not perform according

More information

Q1. The graph below shows how a sinusoidal alternating voltage varies with time when connected across a resistor, R.

Q1. The graph below shows how a sinusoidal alternating voltage varies with time when connected across a resistor, R. Q1. The graph below shows how a sinusoidal alternating voltage varies with time when connected across a resistor, R. (a) (i) State the peak-to-peak voltage. peak-to-peak voltage...v (1) (ii) State the

More information

HV Submarine Cable Systems Design, Testing and Installation

HV Submarine Cable Systems Design, Testing and Installation HV Submarine Cable Systems Design, Testing and Installation CIGRE Ireland Technical Seminar 6 th October 2010 Robert Donaghy Senior Consultant Engineer, ESB International Presentation Overview Applications

More information

World Leader in HV Testing Technology

World Leader in HV Testing Technology World Leader in HV Testing Technology Cable Fault Locators w/tdr Oil/Fluid Dielectric Testers Very Low Frequency AC Technology W/TD & PD Diagnostics Portable AC Hipots ---------------------------------

More information

Multi-Function Ground

Multi-Function Ground Multi-Function Ground Resistance SOIL RESISTIVITY TEster Model 6470-B Now measure ground resistance, soil resistivity and bonding resistance with one instrument! 2- and 4-Wire Bond Resistance/Continuity

More information

Using Thermocouple Sensors Connecting Grounded and Floating Thermocouples

Using Thermocouple Sensors Connecting Grounded and Floating Thermocouples Connecting Grounded and Floating Thermocouples For best performance, Thermocouple sensors should be floating. This will ensure that no noise currents can flow in the sensor leads and that no common-mode

More information

Power chip resistor size 2512 PRC221 5%; 2% FEATURES Reduced size of final equipment Low assembly costs Higher component and equipment reliability.

Power chip resistor size 2512 PRC221 5%; 2% FEATURES Reduced size of final equipment Low assembly costs Higher component and equipment reliability. FEATURES Reduced size of final equipment Low assembly costs Higher component and equipment reliability. APPLICATIONS Power supplies Printers Computers Battery chargers Automotive Converters CD-ROM. QUICK

More information

Metal-Oxide Varistors (MOVs) Surface Mount Multilayer Varistors (MLVs) > MLN Series. MLN SurgeArray TM Suppressor. Description

Metal-Oxide Varistors (MOVs) Surface Mount Multilayer Varistors (MLVs) > MLN Series. MLN SurgeArray TM Suppressor. Description MLN SurgeArray TM Suppressor RoHS Description The MLN SurgeArray Suppressor is designed to help protect components from transient voltages that exist at the circuit board level. This device provides four

More information

Power transformers. Generator step-up and system intertie power transformers Securing high-quality AC transmission

Power transformers. Generator step-up and system intertie power transformers Securing high-quality AC transmission Power transformers Generator step-up and system intertie power transformers Securing high-quality AC transmission Generator step-up transformers Built to withstand continuous full load Generator step-up

More information

Development of a 500-kV DC XLPE Cable System

Development of a 500-kV DC XLPE Cable System by Satoru Maruyama *, Noboru Ishii *, Michihiro Shimada *, Shinji Kojima * 2, Hideo Tanaka * 3, Mitsumasa Asano * 4, Tetsuya Yamanaka * 4, and Shin ichi Kawakami * 4 This paper describes development work

More information

1 Form A Solid State Relay

1 Form A Solid State Relay Form A Solid State Relay VOAT, VOAABTR FEATURES 9 S S DC S' 3 S' High speed SSR - t on /t off < 8 μs Maximum R ON. Isolation test voltage 3 V RMS Load voltage V Load current A DC configuration DIP- package

More information

ELECTRICAL INSULATION TESTING OF HV EQUIPMENT UP TO 33kV

ELECTRICAL INSULATION TESTING OF HV EQUIPMENT UP TO 33kV 1. SCOPE This document details PowerSystems requirements for electrical testing of HV Equipment up to and including 33kV. 2. ISSUE RECORD This is a Reference document. The current version of Controlled

More information

State of the art in reactive magnetron sputtering

State of the art in reactive magnetron sputtering State of the art in reactive magnetron sputtering T. Nyberg, O. Kappertz, T. Kubart and S. Berg Solid State Electronics, The Ångström Laboratory, Uppsala University, Box 534, S-751 21 Uppsala, Sweden D.

More information

Mylar polyester film. Electrical Properties. Product Information. Dielectric Strength. Electrode Size. Film Thickness

Mylar polyester film. Electrical Properties. Product Information. Dielectric Strength. Electrode Size. Film Thickness Product Information Mylar polyester film Electrical Properties Mylar offers unique design capabilities to the electrical industry due to the excellent balance of its electrical properties with its chemical,

More information