Understanding Insulation Resistance Testing

Size: px
Start display at page:

Download "Understanding Insulation Resistance Testing"

Transcription

1 Understanding Insulation Resistance Testing Why have an insulation testing program? A regular program of testing insulation resistance is strongly recommended to prevent electrical shocks, assure safety of personnel and to reduce or eliminate down time. It helps to detect deterioration of insulation in order to schedule repair work such as: vacuum cleaning, steam cleaning, drying and rewinding. It is also helpful when evaluating the quality of the repairs before the equipment is put back into operation. What causes insulation failure? Some of the more common causes of insulation failure include: excessive heat or cold, moisture, dirt, corrosive vapors, oil, vibration, aging and nicked wiring. What tests are used to detect insulation deterioration? There are numerous maintenance tests for assessing insulation quality. The three tests discussed here are used primarily to test motor, generator and transformer insulation. What equipment is necessary for conducting insulation resistance tests? Megohmmeter with a timed test function Temperature indicator Humidity meter (not necessary if equipment temperature is above the dew point) Test Currents in Insulation Total current in the body of the insulation is the sum of three components Capacitance Charging Current Absorption Current Leakage or Conduction Current Insulation Resistance Readings Readings are time dependent at the start, capacitance is what you see first at or about one minute, absorption at 10 minutes, reading is mainly leakage current These changing readings are best seen with analog bargraphs on digital instruments or needle movement on analog instruments. Spot Reading Test Method For this test, the megohmmeter is connected across the insulation of the windings of the machine being tested. A test voltage is applied for a fixed period of time, usually 60 seconds and a reading is taken. The spot reading test should only be carried out when the winding temperature is above the dew point 1. The operator should make a note of the winding temperature, so that it will be possible to correct the reading to a base temperature of 20 C. Test Duration To obtain comparable results, tests must be of the same duration. Usually the reading is taken after 60 seconds. Interpretation of Results Proper interpretation of spot reading tests requires access to records of results from previous spot reading tests. For conclusive results, only use results from tests performed at the same test voltage for the same amount of time, and under similar temperature and humidity conditions. These readings are used to plot a curve of the history of insulation resistance. A curve showing a downward trend usually indicates a loss of insulation resistance due to unfavorable conditions such as: humidity, dust accumulation, etc. A very sharp drop indicates an insulation failure. See Figure 1. Technical Assistance (800) of 6

2 such an instrument is better adapted for cables, bushings, transformers, and switchgear in the heavier-duty sizes. Test Methods Time-Resistant Tests Dielectric Absorption Ratio (DAR) The ratio of 60 seconds/30 seconds less than 1 = failed 1.0 to 1.25 = OK 1.4 to 1.6 = excellent Note: This is not a commonly used test Figure 1 Example of the variation of insulation resistance over a period of years: At A, the effect of aging and dust accumulation is shown by decreasing values. At B, the sharp drop indicates an insulation failure. At C, the insulation resistance value after the motor has been rewound. (1) Dew point temperature is the temperature at which the moisture vapor in the air condenses as a liquid. Time-Resistance Testing Method This method is fairly independent of temperature and often can give you conclusive information without records of past tests. It is based on the absorption effect of good insulation compared to that of moist or contaminated insulation. Simply take successive readings at specific times and note the differences in readings (see curves, Figure 2). Tests by this method are sometimes referred to as absorption tests. Good insulation shows a continual increase in resistance (see curve D) over a period of time (in the order of 5 to 10 minutes). This is caused by the absorption; good insulation shows this charge effect over a time period much longer that the time required to charge the capacitance of the insulation. Step Voltage Test Method In this test, the operator applies two or more test voltages in steps. The recommended ratio for the test voltage steps is 1 to 5. At each step, test voltage should be applied for the same length of time, usually 60 seconds. The application of increased voltage creates electrical stresses on internal insulation cracks. This can reveal aging and physical damage even in relatively dry and clean insulation which would not have been apparent at lower voltages. Test Duration A series of steps, each step lasting 60 seconds. Interpretation of Results Compare the readings taken at different voltage levels, looking for any excessive reduction in insulation resistance values at the higher voltage levels. Insulation that is thoroughly dry, clean, and without physical damage should provide roughly the same resistance values despite changes in test voltage levels. If resistance values decrease substantially when tested at higher voltage levels, this should serve as a warning that insulation quality may be deteriorating due to dirt, moisture, cracking, aging, etc. Polarization Index (PI) = 10-minute reading 1-minute reading The IEEE Std lists the following minimum values for the polarization index for AC and DC rotating machines: Class A: 1.5 Class B: 2.0 Class C: 2.0 If the insulation contains moisture or contaminants, the absorption effect is masked by a high leakage current which stays at a fairly constant value keeping the resistance reading low (R = E/I) (see curve E). The time-resistance testing is of value because it is independent of equipment size. The increase in resistance for clean and dry insulation occurs in the same manner whether a motor is large or small. You can compare several motors and establish standards for new ones, regardless of their horsepower ratings. Figure 2 shows how a 60-second test would appear for good and bad insulation. When the insulation is in good shape, the 60-second reading is higher that the 30-second reading. Reading in Megohms D E A further advantage of this two reading test is that it gives you a clearer picture, even when a spot reading says the insulation looks ok. Time-resistance tests on large rotating electrical machinery especially with high operating voltage require high insulation resistance ranges and a very constant test voltage. A heavy-duty megohmmeter serves this need. Similarly, Time in Minutes Figure 2 Absorption curve of test conducted on 350 HP Motor: Curve D indicates a good insulation with an excellent polarization index of 5. Curve E indicates a potential problem. The polarization index is only 140/95, or (2) IEEE Std , Recommended Practice for Testing Insulation Resistance of Rotating Machinery. Available from the Institute of Electrical and Electronics Engineers, Inc., 345 E. 47th St., New York, NY Technical Assistance (800) of 6

3 1000 G No Connection to Guard B 1 To Guard B I1 Reading in Megohms F To EARTH A i Ay Rx Rz C To LINE To EARTH A i Ay Rx Rz C To LINE Applied Voltage in kv Before and after repair: Curve F shows a downward trend of insulation resistance values as the test voltage is increased. This indicates a potential problem with the insulation. Curve G shows the same equipment after it has been repaired. Advantages of DC Testing Lighter size and weight of test equipment Non-destructive Historical data can be compiled Utilizing the Guard The guard terminal is useful when measuring very high resistance values. Transformer Testing Transformers are tested at or above the rated voltage to be certain there are no excessive leakage paths to ground or between windings. These are conducted with the transformer completely disconnected from the line and load. However, the case ground should not be removed. Single-Phase Transformer The following 5 tests and corresponding wiring diagrams will completely test a single-phase transformer. Allow at least 1 minute for each test or until the reading stabilizes. a. High voltage winding and ground b. Low voltage winding to high voltage winding and ground c. High voltage winding d. High voltage winding to ground e. Low voltage winding to ground What test voltage should I use? There are two schools of thought regarding the voltage to test insulation at. The first applies to new equipment or cable and can use AC or DC test voltages. When AC voltage is used, the rule of thumb is 2 x nameplate voltage When DC voltage is used (most common on megohmmeters manufactured today) the rule of thumb is simply 2 x nameplate voltage except when higher voltages are used. See chart below for suggested values. Equipment/Cable Rating DC Test Voltage 24 to 50V 50 to 100Vdc 50 to 100V 100 to 250Vdc 100 to 240V 250 to 500Vdc 440 to 550V 500 to 1000Vdc 2400V 1000 to 2500Vdc 4100V 1000 to 5000Vdc Three-Phase Transformer The following 5 tests and corresponding wiring diagrams will completely test a three-phase transformer. a. High voltage winding and ground b. High voltage winding to ground with low voltage winding to guard c. High voltage winding d. Low voltage winding to ground and high voltage winding to guard It is always advisable to contact the original equipment manufacturer to get their recommendation for the proper voltage to use when testing their equipment. Technical Assistance (800) of 6

4 Cable Testing Cables are tested at or above the rated voltage to be certain there are no excessive leakage paths to ground or between windings. These are conducted with the transformer completely disconnected from the line and load. However, the case ground should not be removed. Single Conductor Connect as shown in the diagram a. Conductor to Line (-) terminal and sheath to Earth (+) Motor and Generator Testing Before testing the above lift the rotor brushes, ground the starter terminal and frame and ground the motor shaft. Discharge the field winding by grounding. Then remove the field winding from ground and connect to the (-) Line connection on the megohmmeter. Connect the (+) Earth terminal to ground. The diagram shows the connection for testing the field insulation resistance. The stator winding may also be measured in a similar manner. Multi-Conductor a. Single conductor Stator b. One conductor to all c. One conductor to earth d. One conductor to others minus ground T 4 T 5 T 1 T 2 T 3 T 6 N Insulation Conductor ƒ 1 ƒ 2 Field Ground Sheath single conductor a. Single conductor Three-conductor cable = Earth = Line G = Guard b. One conductor to all 2012 Chauvin Arnoux, Inc. d.b.a. AEMC Instruments c. One conductor to earth Three-conductor cable d. One conductor to others minus ground Technical Assistance (800) of 6

5 Single-Phase Transformer Three-Phase Transformer a. High voltage winding and ground a. High voltage winding and ground b. Low voltage winding to high voltage winding and ground b. High voltage winding to ground with low voltage winding to guard c. High voltage winding c. High voltage winding d. Low voltage winding to ground and high voltage winding to guard d. High voltage winding to ground e. High voltage winding e. Low voltage winding to ground = Earth = Line G = Guard Technical Assistance (800) of 6

6 Contact Us United States & Canada: Chauvin Arnoux, Inc. d.b.a. AEMC Instruments 200 Foxborough Blvd. Foxborough, MA USA (508) Fax (508) Customer Support - for placing an order, obtaining price & delivery: customerservice@aemc.com Sales Department for general sales information: sales@aemc.com Repair and Calibration Service - for information on repair & calibration, obtaining a user manual: repair@aemc.com Technical and Product Application Support for technical and application support: techinfo@aemc.com Webmaster - for information regarding webmaster@aemc.com South America, Central America, Mexico, Caribbean, Australia & New Zealand: Chauvin Arnoux, Inc. d.b.a. AEMC Instruments 15 Faraday Drive Dover, NH USA (603) (x520) Fax (603) export@aemc.com All other countries: Chauvin Arnoux SCA 190, rue Championnet Paris Cedex 18, France Fax info@chauvin-arnoux.com Technical Assistance (800) of 6

Understanding Soil Resistivity Testing

Understanding Soil Resistivity Testing Technical Hotline: (00) -9 Technical Hotline: (00) -9 www.aemc.com www.aemc.com Understanding Testing Effects of on Ground Electrode Resistance Factors Affecting APPLICATION NOTES JULY rev.0 Understanding

More information

Digital Transformer Ratiometer DTR Model 8500

Digital Transformer Ratiometer DTR Model 8500 Digital Transformer Ratiometer DTR Model 8500 The DTR Model 8500 from AEMC Instruments is a portable digital transformer ratiometer designed for on-site testing of power, potential and current transformers.

More information

5000V Graphical Megohmmeter Model 5070

5000V Graphical Megohmmeter Model 5070 5000V Graphical Megohmmeter Model 5070 The Model 5070, the latest design in 5000V Megohmmeters, is the most innovative product in its class on the market today. The features and functions incorporated

More information

Selection Guide to Clamp-On Current Probes

Selection Guide to Clamp-On Current Probes Selection Guide to Clamp-On Current Probes Selecting The Correct Clamp-On Current Probe Answering the following questions will help you to select the appropriate probe for your applications. 1. Determine

More information

Digital Ground Resistance Tester. Models 4620 & 4630. Digital Ground Resistance Tester

Digital Ground Resistance Tester. Models 4620 & 4630. Digital Ground Resistance Tester Digital Ground Resistance Tester Models 4620 & 4630 Digital Ground Resistance Tester Models 4620 and 4630 perform both ground resistance and soil resistivity tests. These testers measure from 0 to 2000Ω,

More information

The Complete Guide to Electrical Insulation Testing A STITCH IN TIME 1 WWW.MEGGER.COM

The Complete Guide to Electrical Insulation Testing A STITCH IN TIME 1 WWW.MEGGER.COM The Complete Guide to Electrical Insulation Testing A STITCH IN TIME 1 WWW.MEGGER.COM A Stitch In Time The Complete Guide to Electrical Insulation Testing Copyright 2006 WWW.MEGGER.COM A STITCH IN TIME

More information

Insulation resistance testing

Insulation resistance testing resistance testing Application Note Introduction resistance testers can be used to determine the integrity of windings or cables in motors, transformers, switchgear, and electrical installations. The test

More information

SYNCHRONOUS MACHINE TESTING WITH MOTOR CIRCUIT ANALYSIS INSTRUMENTATION

SYNCHRONOUS MACHINE TESTING WITH MOTOR CIRCUIT ANALYSIS INSTRUMENTATION SYNCHRONOUS MACHINE TESTING WITH MOTOR CIRCUIT ANALYSIS INSTRUMENTATION Introduction Howard W. Penrose, Ph.D., CMRP Vice President, Engineering and Reliability Services Dreisilker Electric Motors, Inc.

More information

AC-Synchronous Generator

AC-Synchronous Generator Design Description AC Generators come in two basic types synchronous and non-synchronous. Synchronous generators lock in with the fundamental line frequency and rotate at a synchronous speed related to

More information

SALVAGING FLOOD DAMAGED ELECTRICAL EQUIPMENT

SALVAGING FLOOD DAMAGED ELECTRICAL EQUIPMENT SALVAGING FLOOD DAMAGED ELECTRICAL EQUIPMENT Overview In all drying out of electrical windings, the regulation of temperature should be controlled carefully. Maximum drying temperatures on windings should

More information

A Practical Guide to Dielectric Testing

A Practical Guide to Dielectric Testing Chroma Systems Solutions, Inc. A Practical Guide to Dielectric Testing 19032 Series Electrical Safety Analyzer & 19050 Series Hipot Tester AC/DC/IR/SCAN Keywords: Dielectric tests, insulation resistance

More information

Unit 33 Three-Phase Motors

Unit 33 Three-Phase Motors Unit 33 Three-Phase Motors Objectives: Discuss the operation of wound rotor motors. Discuss the operation of selsyn motors. Discuss the operation of synchronous motors. Determine the direction of rotation

More information

MIT510/2, MIT520/2 and MIT1020/2

MIT510/2, MIT520/2 and MIT1020/2 99 Washington Street Melrose, MA 02176 Phone 781-665-1400 Toll Free 1-800-517-8431 Visit us at www.testequipmentdepot.com MIT510/2, MIT520/2 and MIT1020/2 Line supply or battery operated Digital/analog

More information

Multi-Function Ground

Multi-Function Ground Multi-Function Ground Resistance SOIL RESISTIVITY TEster Model 6470-B Now measure ground resistance, soil resistivity and bonding resistance with one instrument! 2- and 4-Wire Bond Resistance/Continuity

More information

1-866-254-0962. A Guide To Diagnostic Insulation Testing Above 1 kv TOLL FREE CUSTOMER SERVICE NUMBER. WWW.MEGGER.COM/us

1-866-254-0962. A Guide To Diagnostic Insulation Testing Above 1 kv TOLL FREE CUSTOMER SERVICE NUMBER. WWW.MEGGER.COM/us A Guide To Diagnostic Insulation Testing Above 1 kv TOLL FREE CUSTOMER SERVICE NUMBER 1-866-254-0962 The word Megger is a registered trademark WWW.MEGGER.COM/us Why a 10 kv Insulation Tester? Megger invented

More information

INSTALLATION AND MAINTENANCE INSTRUCTIONS FOR THREE PHASE INDUCTION MOTORS

INSTALLATION AND MAINTENANCE INSTRUCTIONS FOR THREE PHASE INDUCTION MOTORS INSTALLATION AND MAINTENANCE INSTRUCTIONS FOR THREE PHASE INDUCTION MOTORS Frames 143T - 449TZ 5100 North IH 35 Round Rock, Texas 78681 Phone: 800-451-8798 512-255-4141 Fax: 512-244-5512 RECEIVING 1. Check

More information

Power-factor testing of rotating machinery is another valuable test

Power-factor testing of rotating machinery is another valuable test Feature Power-Factor Testing of Stator Winding Insulation: Understanding the Test Technique and Interpretation of Results Power-factor testing of rotating machinery is another valuable test technique providing

More information

Insulation Resistance Testing of Low Voltage Cables in the Field

Insulation Resistance Testing of Low Voltage Cables in the Field Insulation Resistance Testing of Low Voltage Cables in the Field Table of Contents 1. Background...3 1.1. Before Making Measurements...3 1.2. How to Apply the Temperature Correction Factor...4 1.2.1. Calculation...4

More information

SUNON SPECIFICATION FOR APPROVAL

SUNON SPECIFICATION FOR APPROVAL SPECIFICATION FOR APPROVAL CUSTOMER : DESCRIPTION : DC BRUSHLESS FAN DIMENSIONS : 60X60X25 mm M O D E L : KDE2406PTB2 APPROVED NO : APPROVED BY : (AUTHORZIED) SPEC.NO D600732 ISSUE DATE 10.01.1998 DAWN.

More information

SUNON SPECIFICATION FOR APPROVAL DESCRIPTION : DC BRUSHLESS FAN. DIMENSIONS : 60X60X15 mm M O D E L : KD0506PHS2

SUNON SPECIFICATION FOR APPROVAL DESCRIPTION : DC BRUSHLESS FAN. DIMENSIONS : 60X60X15 mm M O D E L : KD0506PHS2 SPECIFICATION FOR APPROVAL CUSTOMER : DESCRIPTION : DC BRUSHLESS FAN DIMENSIONS : 60X60X15 mm M O D E L : KD0506PHS2 APPROVED NO : APPROVED BY : (AUTHORIZED) SPEC.NO D600023 ISSUE DATE 08.06.1998 DAWN.

More information

DC MOTOR ANALYSIS & TROUBLESHOOTING

DC MOTOR ANALYSIS & TROUBLESHOOTING DC MOTOR ANALYSIS & TROUBLESHOOTING By Don Shaw Condition assessment of DC motors requires a basic understanding of the design and operating characteristics of the various types available: the series motor,

More information

Specifying a Variable Frequency Drive s

Specifying a Variable Frequency Drive s Specifying a Variable Frequency Drive s Put on by Bruce Reeves and Jeremy Gonzales Dykman Electrical Covering the Western US For all of your VFD and Soft Start and Motor Needs How To Specify a Variable

More information

KEEPING MOTOR WINDINGS DRY

KEEPING MOTOR WINDINGS DRY FACILITIES INSTRUCTIONS, STANDARDS, AND TECHNIQUES Volume 3-4 KEEPING MOTOR WINDINGS DRY Internet Version of This Manual Created September 2000 FACILITIES ENGINEERING BRANCH DENVER OFFICE DENVER, COLORADO

More information

User Guide. Model 380260 Insulation Tester / Megohmmeter

User Guide. Model 380260 Insulation Tester / Megohmmeter User Guide Model 380260 Insulation Tester / Megohmmeter Introduction Congratulations on your purchase of Extech s Insulation Tester/Megohmmeter. The Model 380260 provides three test ranges plus continuity

More information

Single-Phase AC Synchronous Generator

Single-Phase AC Synchronous Generator ST Series Single-Phase AC Synchronous Generator Instructions for Operation and Maintenance English to English translation by R.G. Keen, May 2004. ST Series of Single-Phase AC Synchronous Generators Description

More information

ELECTRIC HEATER COMPANY Operating and Maintenance Manual For Immersion Heating Elements

ELECTRIC HEATER COMPANY Operating and Maintenance Manual For Immersion Heating Elements ELECTRIC HEATER COMPANY Operating and Maintenance Manual For Immersion Heating Elements HUBBELL ELECTRIC HEATER COMPANY P.O. BOX 288 STRATFORD, CT 06615 PHONE: (203) 378-2659 FAX: (203) 378-3593 INTERNET:

More information

Rotary Phase Converters

Rotary Phase Converters FACTS from Ronk Electrical Industries, Inc. Bulletin 11981 Rotary Phase Converters ROTOVERTER Pat. No. 3,670,238 ROTO-CON Pat. No. 4,158,225 What are the ROTO-CON and ROTOVERTER power converters? The ROTO-CON

More information

REVIEWED BY CAPITAL PROJECTS MANAGER (DAN REDDY) GENERAL MANAGER EQUIPMENT ENGINEERING & ASSET MANAGEMENT (HAMILTON NXUMALO)

REVIEWED BY CAPITAL PROJECTS MANAGER (DAN REDDY) GENERAL MANAGER EQUIPMENT ENGINEERING & ASSET MANAGEMENT (HAMILTON NXUMALO) SA Port Operations DOCUMENT TYPE: REFERENCE EEAM-Q-014 (ORIGINAL SPECIFICATION HE8.2.3 Ver5) REVISION 0 SPECIFICATION TITLE: SPECIFICATION FOR ELECTRICAL MOTORS AND GENERATORS PAGE 0 of 07 COMPILED BY

More information

Insulation resistance testing. A complete solution for every person.

Insulation resistance testing. A complete solution for every person. Insulation resistance testing. A complete solution for every person. Insulation resistance. The latest test tools from the testing experts. You asked. We responded. Now you have more insulation testing

More information

Equipment: Power Supply, DAI, Synchronous motor (8241), Electrodynamometer (8960), Tachometer, Timing belt.

Equipment: Power Supply, DAI, Synchronous motor (8241), Electrodynamometer (8960), Tachometer, Timing belt. Lab 9: Synchronous motor. Objective: to examine the design of a 3-phase synchronous motor; to learn how to connect it; to obtain its starting characteristic; to determine the full-load characteristic of

More information

MEGGER 210170 Insulation & Low Resistance Tester

MEGGER 210170 Insulation & Low Resistance Tester MEGGER 210170 Insulation & Low Resistance Tester User Guide SAFETY WARNINGS Safety Warnings and Precautions must be read and understood before the instrument is used. They must be observed during use.

More information

AC Electric Motors best practice

AC Electric Motors best practice If you want to learn more about best practice machinery maintenance, or world class mechanical equipment maintenance and installation practices, follow the link to our Online Store and see the Training

More information

WIRE AND CABLE ENGINEERING GUIDE

WIRE AND CABLE ENGINEERING GUIDE DC Hi Pot Testing Excerpt from PRYSMIAN S WIRE AND CABLE ENGINEERING GUIDE (FOR INFORMATIONAL PURPOSES ONLY) Page 1 of 6 DC HIGH POTENTIAL TESTING DC Hi-Pot testing can be applied as a withstand test (a

More information

A Guide To Diagnostic Insulation Testing Above 1 kv

A Guide To Diagnostic Insulation Testing Above 1 kv A Guide To Diagnostic Insulation Testing Above 1 kv Table of Contents INTRODUCTION... 2 WHAT IS INSULATION?... 3 What Causes Insulation to Degrade?... 3 Electrical Stress... 3 Mechanical Stress... 3 Chemical

More information

(3) Explosion proof. Designed to prevent ignition of any explosive gases or dust and dirt which may surround the motor.

(3) Explosion proof. Designed to prevent ignition of any explosive gases or dust and dirt which may surround the motor. ELECTRIC MOTORS Enclosures for Motors Types of motor enclosures generally used in farm applications: (1) Open type; drip proof or splash-proof. A general purpose motor for use in dry locations which are

More information

Enhance Power Equipment Reliability with Predictive Maintenance Technologies

Enhance Power Equipment Reliability with Predictive Maintenance Technologies Enhance Power Equipment Reliability with Predictive Maintenance Technologies November 2012/1910DB1208 by S. Frank Waterer, Electrical Engineerinig, Fellow Schneider Electric USA, Inc. Make the most of

More information

AC and DC Drive System Installation Information

AC and DC Drive System Installation Information Purpose This document contains the Parker SSD Drives recommendations for installing drive systems. These instructions must be followed for safe and reliable operation. Instructions CODES AND REGULATIONS

More information

CORE LOSS TESTING THEORY CORE LOSS TESTING IN THE PRACTICAL MOTOR REPAIR ENVIRONMENT ABSTRACT

CORE LOSS TESTING THEORY CORE LOSS TESTING IN THE PRACTICAL MOTOR REPAIR ENVIRONMENT ABSTRACT CORE LOSS TESTING IN THE PRACTICAL MOTOR REPAIR ENVIRONMENT ABSTRACT LEXSECO developed the first commercial Core Loss Tester over thirty five years ago. Since inception, LEXSCO has performed core loss

More information

Welcome to Linear Controls Quarterly Training

Welcome to Linear Controls Quarterly Training Welcome to Linear Controls Quarterly Training Introduction to Power Generation Objectives Supply attendees with basic knowledge of power generators and voltage regulators and provide the fundamentals of

More information

Single and Three Phase Transformer Testing Using Static Motor Circuit Analysis Techniques

Single and Three Phase Transformer Testing Using Static Motor Circuit Analysis Techniques Single and Three Phase Transformer Testing Using Static Motor Circuit Analysis Techniques Howard W. Penrose, Ph.D On behalf of ALL-TEST Pro, LLC Old Saybrook, CT Introduction Field and shop testing of

More information

Occupational Profile: Electrical & Electronics Engineering Technician

Occupational Profile: Electrical & Electronics Engineering Technician Occupational Profile: Electrical & Electronics Engineering Technician A competent Electrical & Electronics Engineering Technician should be able to demonstrate the following skills and competences: 1.

More information

Table of Contents. The Basics of Electricity 2. Using a Digital Multimeter 4. Testing Voltage 8. Testing Current 10. Testing Resistance 12

Table of Contents. The Basics of Electricity 2. Using a Digital Multimeter 4. Testing Voltage 8. Testing Current 10. Testing Resistance 12 Table of Contents The Basics of Electricity 2 Using a Digital Multimeter 4 IDEAL Digital Multimeters An Introduction The Basics of Digital Multimeters is designed to give you a fundamental knowledge of

More information

Application Information

Application Information Moog Components Group manufactures a comprehensive line of brush-type and brushless motors, as well as brushless controllers. The purpose of this document is to provide a guide for the selection and application

More information

Guidance for upgrading to GB4943.1-2011 (IEC 60950-1: 2005, MOD)

Guidance for upgrading to GB4943.1-2011 (IEC 60950-1: 2005, MOD) Guidance for upgrading to GB4943.1-2011 (IEC 60950-1: 2005, MOD) Note: This guidance document is a translation of official Chinese document which is issued by CQC (China Quality Certification Center) on

More information

A Guide To Diagnostic Insulation Testing Above 1 kv US $9.95 GBP 5.95

A Guide To Diagnostic Insulation Testing Above 1 kv US $9.95 GBP 5.95 A Guide To Diagnostic Insulation Testing Above 1 kv US $9.95 GBP 5.95 TABLE OF CONTENTS Introduction.................................... 2 What is Insulation?.............................. 2 What Causes

More information

SYNCHRONOUS MACHINES

SYNCHRONOUS MACHINES SYNCHRONOUS MACHINES The geometry of a synchronous machine is quite similar to that of the induction machine. The stator core and windings of a three-phase synchronous machine are practically identical

More information

Power supply unit Model: PAC-SC50KUA

Power supply unit Model: PAC-SC50KUA Building Air Conditioning Control System Power supply unit Model: PAC-SC50KUA Installation Manual Contents 1. Safety precautions... 1 2. Product feature... 2 1. Specification... 2 2. Appearance... 2 3.

More information

GENERAL POWER SYSTEM WIRING PRACTICES APPLIED TO TECNADYNE DC BRUSHLESS MOTORS

GENERAL POWER SYSTEM WIRING PRACTICES APPLIED TO TECNADYNE DC BRUSHLESS MOTORS 1/5/2006 Page 1 of 6 GENERAL POWER SYSTEM WIRING PRACTICES APPLIED TO TECNADYNE DC BRUSHLESS MOTORS 1. Introduction The purpose of this application note is to describe some common connection and filtering

More information

EVANS ENTErprises, Inc.

EVANS ENTErprises, Inc. EVANS ENTErprises, Inc. Since 1954 THE LEADER IN ELECTRO-MECHANICAL SALES, SERVICE AND INTERGRATION Our Mission Our purpose at Evans Enterprises is to serve customers by providing increased value of product

More information

The Charging System. Section 5. Charging System. Charging System. The charging system has two essential functions:

The Charging System. Section 5. Charging System. Charging System. The charging system has two essential functions: The Charging System Charging System The charging system has two essential functions: Generate electrical power to run the vehicle s electrical systems Generate current to recharge the vehicle s battery

More information

World Leader in HV Testing Technology

World Leader in HV Testing Technology World Leader in HV Testing Technology Cable Fault Locators w/tdr Oil/Fluid Dielectric Testers Very Low Frequency AC Technology W/TD & PD Diagnostics Portable AC Hipots ---------------------------------

More information

6/14/02 Chapter 14: Use of Electrical Test Equipment 1/20

6/14/02 Chapter 14: Use of Electrical Test Equipment 1/20 USE OF ELECTRICAL TEST EQUIPMENT Test equipment is necessary for determining proper set-up, adjustment, operation, and maintenance of electrical systems and control panels. The following is a general procedure

More information

Standard for an Electrical Preventive Maintenance (EPM) Program

Standard for an Electrical Preventive Maintenance (EPM) Program Recommended Maintenance Practices for Electrical Distribution System Equipment Hartford Steam Boiler One State Street P.O. Box 5024 Hartford, CT 06102-5024 Tel: (800) 472-1866 www.hsb.com April 2013 Introduction

More information

Rutland 913 Windcharger Fault Finding Guide

Rutland 913 Windcharger Fault Finding Guide Rutland 913 Windcharger Fault Finding Guide Document No. SM-133 Issue A LOW VOLTAGE CHARGE CURRENT? TE 4 REGULATOR TE 5 REG RETURN REG TO MANUFACTURER CHARGE CURRENT INTERMITTENT CHARGE CURRENT SUFFICIENT

More information

Load Cell Troubleshooting

Load Cell Troubleshooting VPG TRANSDUCERS Load Cells and Weigh Modules Technical Note VPGT-08 Scope Load cells are designed to sense force or weight under a wide range of adverse conditions; they are not only the most essential

More information

Troubleshooting accelerometer installations

Troubleshooting accelerometer installations Troubleshooting accelerometer installations Accelerometer based monitoring systems can be tested to verify proper installation and operation. Testing ensures data integrity and can identify most problems.

More information

any electrical system depends upon knowledge, preventive maintenance and subsequently the test equipment used to monitor that system.

any electrical system depends upon knowledge, preventive maintenance and subsequently the test equipment used to monitor that system. Understanding Power & Power Quality Measurements is the actual transformer voltage. This system is frequently used for power loads in commercial and industrial buildings. In such cases, service to the

More information

Pump Maintenance - Repair

Pump Maintenance - Repair Pump Maintenance - Repair Brian Trombly Mo Droppers Cummins Bridgeway, Gaylord, Mi The basic centrifugal pump consists of two main elements: 1. The rotating element which includes an impeller and a shaft.

More information

PANCAKE CAPACITOR GENERATOR Installation, Operation and Maintenance Manual

PANCAKE CAPACITOR GENERATOR Installation, Operation and Maintenance Manual PANCAKE CAPACITOR GENERATOR Installation, Operation and Maintenance Manual A Regal Brand TABLE OF CONTENTS INTRODUCTION 2 General Data 2 Initial Inspection 2 SAFETY 2 INSTALLATION 3 Location / Environment

More information

Three-phase AC circuits

Three-phase AC circuits Three-phase AC circuits This worksheet and all related files are licensed under the Creative Commons Attribution License, version 1.0. To view a copy of this license, visit http://creativecommons.org/licenses/by/1.0/,

More information

FAULT FINDING MANUAL. For Stamford AC Generators

FAULT FINDING MANUAL. For Stamford AC Generators FAULT FINDING MANUAL For Stamford AC Generators 1 SAFETY PRECAUTIONS Test procedures recommended in this manual assume that the reader is fully conversant with electrical safety principles, and is familiar

More information

SECTION 4 ELECTRIC MOTORS UNIT 17: TYPES OF ELECTRIC MOTORS

SECTION 4 ELECTRIC MOTORS UNIT 17: TYPES OF ELECTRIC MOTORS SECTION 4 ELECTRIC MOTORS UNIT 17: TYPES OF ELECTRIC MOTORS UNIT OBJECTIVES After studying this unit, the reader should be able to Describe the different types of open single-phase motors used to drive

More information

Failure code manual. content

Failure code manual. content Failure code manual content 一 wall split AC series 2 二 floor standing AC series. 4 三 portable AC series.. 5 四 dehumidifer 6 五 DC inverter single split series...7 六 DC inverter multi-split series 10 1 一

More information

EVALUATION OF ON-SITE DIELECTRIC RESPONSE METHODS FOR NON- DESTRUCTIVE TESTING OF WATER TREED MV XLPE CABLES

EVALUATION OF ON-SITE DIELECTRIC RESPONSE METHODS FOR NON- DESTRUCTIVE TESTING OF WATER TREED MV XLPE CABLES EVALUATION OF ON-SITE DIELECTRIC RESPONSE METHODS FOR NON- DESTRUCTIVE TESTING OF WATER TREED MV XLPE CABLES Sverre Hvidsten*, Peter Werelius**, Jørgen Christensen*** * SINTEF Energy Research (SEfAS),

More information

Application Note. So You Need to Measure Some Inductors?

Application Note. So You Need to Measure Some Inductors? So You Need to Measure Some nductors? Take a look at the 1910 nductance Analyzer. Although specifically designed for production testing of inductors and coils, in addition to measuring inductance (L),

More information

BOWL ASSEMBLY SELECTION Select impeller in exactly the same manner as for lineshaft type pump. Note comments under WELL SIZE.

BOWL ASSEMBLY SELECTION Select impeller in exactly the same manner as for lineshaft type pump. Note comments under WELL SIZE. SUBMERSIBLE PUMP selection A submersible pump consists of the following basic elements: < Bowl Assembly < Motor < Cable < Drop Pipe < Surface Plate (with)(without) discharge elbow DATA REQUIRED FOR SELECTION

More information

Short Circuit Current Calculations

Short Circuit Current Calculations Introduction Several sections of the National Electrical Code relate to proper overcurrent protection. Safe and reliable application of overcurrent protective devices based on these sections mandate that

More information

UNIT 3 AUTOMOBILE ELECTRICAL SYSTEMS

UNIT 3 AUTOMOBILE ELECTRICAL SYSTEMS UNIT 3 AUTOMOBILE ELECTRICAL SYSTEMS Automobile Electrical Structure 3.1 Introduction Objectives 3.2 Ignition System 3.3 Requirement of an Ignition System 3.4 Types of Ignition 3.4.1 Battery or Coil Ignition

More information

Agilent Technologies. Troubleshooting Three-Phase AC Motors with U1210 Series Handheld Clamp Meters. Application Note

Agilent Technologies. Troubleshooting Three-Phase AC Motors with U1210 Series Handheld Clamp Meters. Application Note Agilent Technologies Troubleshooting Three-Phase AC Motors with U1210 Series Handheld Clamp Meters Application Note INTRODUCTION In today s world, the three-phase AC induction motors are widely used in

More information

NATIONAL CERTIFICATE (VOCATIONAL)

NATIONAL CERTIFICATE (VOCATIONAL) NATIONAL CERTIFICATE (VOCATIONAL) SUBJECT GUIDELINES ELECTRICAL PRINCIPLES AND PRACTICE NQF Level 4 September 2007 ELECTRICAL PRINCIPLES AND PRACTICE LEVEL 4 CONTENTS INTRODUCTION 1 DURATION AND TUITION

More information

FAULT FINDING MANUAL For Self Excited and Separately Excited Generators

FAULT FINDING MANUAL For Self Excited and Separately Excited Generators FAULT FINDING MANUAL For Self Excited and Separately Excited Generators SAFETY PRECAUTIONS Before testing the generating set, read the generating set Installation Manual, and this Fault Finding Manual,

More information

MEMBRANE VACUUM MINI PUMPS

MEMBRANE VACUUM MINI PUMPS MEMBRANE VACUUM MINI PUMPS The mini pumps described in this page are membrane-type. They can be used both as vacuum pumps and compressors. In the latter version they can supply compressed air 100% oil-free

More information

3. ELECTRICAL PERFORMANCE PROPERTY TEST CONDITION PERFORMANCE 3. 1 Contact Resistance 1) Center Push 100mΩ Max

3. ELECTRICAL PERFORMANCE PROPERTY TEST CONDITION PERFORMANCE 3. 1 Contact Resistance 1) Center Push 100mΩ Max 1. GENERAL 1. 1 Application : This specification is applied to MULTI WAY SWITCH for electronic equipment. 1. 2 Operating Temperature Range :-25 ~ 70 1. 3 Storage Temperature Range :-0 ~ 85. However, 96

More information

OPERATING MANUAL. Table of contents. 2 Phase Stepping Motor Driver 2M542. Rev. A. Introduction page 2. Specifications page 2 Timing chart page 3

OPERATING MANUAL. Table of contents. 2 Phase Stepping Motor Driver 2M542. Rev. A. Introduction page 2. Specifications page 2 Timing chart page 3 2 Phase Stepping Motor Driver 2M542 OPEATING MANUAL Table of contents Introduction page 2 Specifications page 2 Timing chart page 3 Setting page 4 Current set page 4 educe current function page 4 Micro

More information

X8 X13A X14 - AC Gearless

X8 X13A X14 - AC Gearless This manual is to be given to the end user X8 X13A X14 - AC Gearless Installation and maintenance THIS MANUAL MUST REMAINS WITH THE MACHINE. THE TABLE (page 4) MUST BE SUPPLEMENTED TO ATTEST GOOD REALIZATION

More information

12V Portable Diaphragm Compressor Operating and Maintenance Instructions

12V Portable Diaphragm Compressor Operating and Maintenance Instructions 12V Portable Diaphragm Compressor Operating and Maintenance Instructions (Part No. DC2) Part No. Serial Number Date Purchased Table of Contents Page Safety Messages...2 Guidelines for Product Use...2 Operation

More information

ETC TWO STAGE ELECTRONIC TEMPERATURE CONTROL

ETC TWO STAGE ELECTRONIC TEMPERATURE CONTROL RANCO INSTALLATION INSTRUCTIONS ETC TWO STAGE ELECTRONIC TEMPERATURE CONTROL Relay Electrical Ratings PRODUCT DESCRIPTION The Ranco ETC is a microprocessor-based family of electronic temperature controls,

More information

CAUTION OPC-LM1-ID. Option Card for Frequency Divider. Fuji Electric FA Components & Systems Co., Ltd. Instruction Manual

CAUTION OPC-LM1-ID. Option Card for Frequency Divider. Fuji Electric FA Components & Systems Co., Ltd. Instruction Manual Instruction Manual Option Card for Frequency Divider Deliver this instruction manual without fail to those who actually operate the equipment. Read this operation manual and understand the description

More information

2. A conductor of length 2m moves at 4m/s at 30 to a uniform magnetic field of 0.1T. Which one of the following gives the e.m.f. generated?

2. A conductor of length 2m moves at 4m/s at 30 to a uniform magnetic field of 0.1T. Which one of the following gives the e.m.f. generated? Extra Questions - 2 1. A straight length of wire moves through a uniform magnetic field. The e.m.f. produced across the ends of the wire will be maximum if it moves: a) along the lines of magnetic flux

More information

SECTION 16999 ELECTRICAL ACCEPTANCE TESTS

SECTION 16999 ELECTRICAL ACCEPTANCE TESTS SECTION 16999 ELECTRICAL ACCEPTANCE TESTS PART 1 2. AND 3. COMBINED 1.1 SUMMARY A. Description of Systems 1. Furnish all labor, materials, test equipment, and technical supervision to perform and record

More information

Stator Winding Hipot (High Potential) Testing

Stator Winding Hipot (High Potential) Testing 2009 IEEE Electrical Insulation Conference, Montreal, QC, Canada, 31 May - 3 June 2009 Stator Winding Hipot (High Potential) Testing B.K. Gupta G.C. Stone J. Stein AOK Technologies Iris Power Engineering

More information

Motor Fundamentals. DC Motor

Motor Fundamentals. DC Motor Motor Fundamentals Before we can examine the function of a drive, we must understand the basic operation of the motor. It is used to convert the electrical energy, supplied by the controller, to mechanical

More information

Table V. Troubleshooting Checklist for Refrigeration Systems. Air or non-condensable gas in system. Inlet water warm.

Table V. Troubleshooting Checklist for Refrigeration Systems. Air or non-condensable gas in system. Inlet water warm. Table V Troubleshooting Checklist for Refrigeration Systems TROUBLE POSSIBLE CAUSE CORRECTIVE MEASURE High condensing pressure. Low condensing pressure. Air or non-condensable gas in system. Inlet water

More information

Unified requirements for systems with voltages above 1 kv up to 15 kv

Unified requirements for systems with voltages above 1 kv up to 15 kv (1991) (Rev.1 May 2001) (Rev.2 July 2003) (Rev.3 Feb 2015) Unified requirements for systems with voltages above 1 kv up to 15 kv 1. General 1.1 Field of application The following requirements apply to

More information

WINDING RESISTANCE TESTING

WINDING RESISTANCE TESTING WINDING RESISTANCE TESTING WINDING RESISTANCE TEST SET, MODEL WRT-100 ADWEL INTERNATIONAL LTD. 60 Ironside Crescent, Unit 9 Scarborough, Ontario, Canada M1X 1G4 Telephone: (416) 321-1988 Fax: (416) 321-1991

More information

MV, HV AND EHV SWITCHGEAR TESTING & COMMISSIONING

MV, HV AND EHV SWITCHGEAR TESTING & COMMISSIONING Training Title MV, HV AND EHV SWITCHGEAR TESTING & COMMISSIONING Training Duration 5 days Training Date MV, HV and EHV Switchgear Testing & Commissioning 5 20 24 Apr $3,750 Dubai, UAE In any of the 5 star

More information

AC generator theory. Resources and methods for learning about these subjects (list a few here, in preparation for your research):

AC generator theory. Resources and methods for learning about these subjects (list a few here, in preparation for your research): AC generator theory This worksheet and all related files are licensed under the Creative Commons Attribution License, version 1.0. To view a copy of this license, visit http://creativecommons.org/licenses/by/1.0/,

More information

Operating Instructions Split System Air Conditioner

Operating Instructions Split System Air Conditioner Operating Instructions Split System Air Conditioner Model No. Indoor Unit Type Indoor Unit Type Nominal Capacity 26 36 F2 Low Silhouette Ducted S-26PF2U6 S-36PF2U6 Connectable outdoor unit lineup This

More information

ELECTRICAL INSULATION TESTING OF HV EQUIPMENT UP TO 33kV

ELECTRICAL INSULATION TESTING OF HV EQUIPMENT UP TO 33kV 1. SCOPE This document details PowerSystems requirements for electrical testing of HV Equipment up to and including 33kV. 2. ISSUE RECORD This is a Reference document. The current version of Controlled

More information

CAUTION OPC-LM1-IL. Option Card for Encoder of Line Driver Output. Instruction Manual

CAUTION OPC-LM1-IL. Option Card for Encoder of Line Driver Output. Instruction Manual Instruction Manual OPC-LM1-IL Option Card for Encoder of Line Driver Output CAUTION Deliver this instruction manual without fail to those who actually operate the equipment. Read this operation manual

More information

PART 1 - INTRODUCTION...

PART 1 - INTRODUCTION... Table of Contents PART 1 - INTRODUCTION... 3 1.1 General... 3 1.2 Sensor Features... 3 1.3 Sensor Specifications (CDE-45P)... 4 Figure 1-1 CDE-45P Sensor Dimensions (standard, convertible style)... 4 PART

More information

Equipment: Power Supply, DAI, Wound rotor induction motor (8231), Electrodynamometer (8960), timing belt.

Equipment: Power Supply, DAI, Wound rotor induction motor (8231), Electrodynamometer (8960), timing belt. Lab 13: Wound rotor induction motor. Objective: to examine the construction of a 3-phase wound rotor induction motor; to understand exciting current, synchronous speed and slip in this motor; to determine

More information

Electrical Safety Tester Verification

Electrical Safety Tester Verification Ensuring Validity of Regulatory Tests Verification of electrical safety testing equipment is a procedure that is often overlooked by manufacturers. Running test verification is crucial to ensuring that

More information

Mounting Instructions. Torque Transducer. A0329 3.2 en

Mounting Instructions. Torque Transducer. A0329 3.2 en Mounting Instructions Torque Transducer T5 T5 Contents 3 Page Safety instructions.............................................. 4 1 Measuring characteristics..................................... 7 2 Mounting.....................................................

More information

Chapter 24. Three-Phase Voltage Generation

Chapter 24. Three-Phase Voltage Generation Chapter 24 Three-Phase Systems Three-Phase Voltage Generation Three-phase generators Three sets of windings and produce three ac voltages Windings are placed 120 apart Voltages are three identical sinusoidal

More information

MT MOTORI ELETTRICI. Installation, operation, maintenance and safety manual for motors used in hazardous areas 1-II-2G 21-II-2D

MT MOTORI ELETTRICI. Installation, operation, maintenance and safety manual for motors used in hazardous areas 1-II-2G 21-II-2D MT MOTORI ELETTRICI Installation, operation, maintenance and safety manual for motors used in hazardous areas 1-II-2G 21-II-2D TABLE OF CONTENTS 1. Introduction 2. Scope of application 3. Installation

More information

Condition Monitoring of equipment to improve quality of supply to customers by averting failures

Condition Monitoring of equipment to improve quality of supply to customers by averting failures Condition Monitoring of equipment to improve quality of supply to customers by averting failures Author & presenter: Patrick O Halloran BTECH Manager Technology Services at City Power Johannesburg Abstract

More information

Electric Motor Brake Horsepower Calculations

Electric Motor Brake Horsepower Calculations Electric Motor Brake Horsepower Calculations By Norm Christopherson These motor calculations are contained here as they apply to the changing conditions of the blower motor when pulley adjustments are

More information

Model 1756 Test Lead Kit

Model 1756 Test Lead Kit Keithley Instruments 28775 Aurora Road Cleveland, Ohio 44139 1-888-KEITHLEY http://www.keithley.com Model 1756 Test Lead Kit Gerneral Purpose Test Lead Information Description These test leads allow you

More information

. Failure. Analysis... Report...

. Failure. Analysis... Report... . Failure. Analysis... Report..... for (Generation Company) (Station) Purchase Order Number XXXX (Dated XX/XX/XXXX) Report N-XXXX-FA, Revision 0 Schulz Electric Company Job Number N-XXXX Motor ID Number

More information