SUITABILITY OF DIFFERENT TEST VOLTAGES FOR ON-SITE TESTING OF XLPE CABLE SYSTEMS
|
|
- Leon French
- 8 years ago
- Views:
Transcription
1 SUITABILITY OF DIFFERENT TEST VOLTAGES FOR ON-SITE TESTING OF XLPE CABLE SYSTEMS Michael Hensel HIGHVOLT Prüftechnik Dresden GmbH
2 2 3 Content 1 Introduction Test parameters and their significance Differences between AC/DC and MV/HV cables Comparison of test methods IEC Standard Suitability of different test voltages for on-site testing of XLPE cable systems 2
3 Testing Testing Testing Damage Mistake Ageing Repair Introduction Cable Life Manufacturing Transportation Cable life Installation Operation 50/60 Hz Powerfreq. 50/60 Hz Suitability of different test voltages for on-site testing of XLPE cable systems 3
4 Introduction Commissioning and Diagnostic Testing Commissioning test Quality control after installation of the cable system Aim Detecting all faults which would lead to a breakdown during service time of the cable system Diagnostic test Check of specific values of the cable system Aim Condition assessment for remaining life time estimation of the cable system Suitability of different test voltages for on-site testing of XLPE cable systems 4
5 2 3 Content 1 Introduction Test parameters and their significance Differences between AC/DC and MV/HV cables Comparison of test methods IEC Standard Suitability of different test voltages for on-site testing of XLPE cable systems 5
6 Test parameters and their significance Characteristics of Test Methods to be Assessed Comparison of test methods shall be based on parameters describing 1) The harmfulness for healthy insulation 2) The usefulness of a test method for an application, i.e. the capabilities to distinguish between healthy and defective insulation 3) The applicability (for example expressed by the equipment size, weight and its power consumption) Numbers 2 and 3 are only worth discussing if the previous numbers are answered satisfactorily Suitability of different test voltages for on-site testing of XLPE cable systems 6
7 Test parameters and their significance Why test with same Type of Stresses as in Service? A Cable System Will be used with constant AC stresses (with occasional switching and lightning overvoltages) Quality depends only on performance under these stresses A good cable is one that works well a long time, not one that passed a certain test A Test should therefore Produce the same dielectric effect the insulation as overvoltages... in service (IEC ) Thereby be sensitive to those faults dangerous during operation Suitability of different test voltages for on-site testing of XLPE cable systems 7
8 Test parameters and their significance Which parameters are interesting? Purpose of test Initiate discharges in defects so that they can be found Withstand test: Cause sufficient growth in the defects to lead to breakdown Influential test parameters: Test voltage value Test voltage duration (both for PD inception as for growth) Test voltage wave shape (type of stress) Type and amount of stress is important for significance of test Suitability of different test voltages for on-site testing of XLPE cable systems 8
9 Test parameters and their significance What is a Significant Test? Cable system without faults: Test result cable system is healthy Test result cable system is not healthy Cable system with faults: Test result cable system is not healthy Test result cable system is healthy Suitability of different test voltages for on-site testing of XLPE cable systems 9
10 2 3 Content 1 Introduction Test parameters and their significance Differences between AC/DC and MV/HV cables Comparison of test methods IEC Standard Suitability of different test voltages for on-site testing of XLPE cable systems 10
11 Differences between AC/DC and MV/HV cables Field Distribution in Layered Dielectrics XLPE Cable System AC Conditions: tan d = C R H V i c >> i r Capacitive field control DC conditions (without consideration of space charges): C becomes irrelevant Resistive field control Defects usually have lower resistance and lower field Suitability of different test voltages for on-site testing of XLPE cable systems 11
12 Differences between AC/DC and MV/HV cables Differences between MV, HV and EHV cables Examples for Typical Cable Geometry MV Cable: 24 kv, insulation thickness 5.5 mm, mean operational field strength at voltage peak 3.1 kv/mm HV Cable: 138 kv, insulation thickness 17.8 mm, mean operational field strength at voltage peak 6.3 kv/mm EHV Cable: 400 kv, insulation thickness 26 mm, mean operational field strength at voltage peak 12.6 kv/mm Suitability of different test voltages for on-site testing of XLPE cable systems 12
13 Differences between AC/DC and MV/HV cables Differences between MV, HV and EHV Cables Technical Consequences Field strength increases with cable voltage Recommended limit for test field strength (XLPE): kv/mm Allowed ratio between test voltages and operational voltages for MV 4 times and for HV 2 times higher than for EHV XLPE cables Test methods using higher overvoltage's can be applied for MV cables Using these methods for HV and EHV cables test voltages would have to be reduced, in turn reducing sensitivity of test Suitability of different test voltages for on-site testing of XLPE cable systems 13
14 2 3 Content 1 Introduction Test parameters and their significance Differences between AC/DC and MV/HV cables Comparison of test methods IEC Standard Suitability of different test voltages for on-site testing of XLPE cable systems 14
15 DC (1) Mainly used for testing of oil-paper cables (2) Experience and research showed that DC voltage creates space charges in solid, extruded insulations designed for AC applications (3) These space charges can lead to a breakdown when AC voltage is applied to the test object after the DC test Space charges endanger an otherwise healthy cable system DC voltage is therefore not used for commissioning and diagnosic tests on AC cable systems Suitability of different test voltages for on-site testing of XLPE cable systems 15
16 Very Low Frequency (VLF) (1) Continous voltage with a frequency between 0.01 to 1 Hz, typically used for testing 0.1 Hz (Europe) (2) Due to the low frequency the capacitive field control is not longer dominant reduced field strength in the faults higher voltage necessary in comparison with AC of power frequency Limit is here the max. field strength for XLPE of approx. 30 kv/mm (3) Due to the few voltage cycles PD measuring is not as sensitive as with power frequency (4) Experience shows that the detection/diagnostic of water trees with VLF works well (5) Comparability between different VLF test results is well given but the comparison to a test with AC power frequency is difficult due to the different field control effects (capacitive/resistive) (6) VLF testing in a well defined test procedure for MV applications For MV cable systems well established For EHV cable systems not standardized Suitability of different test voltages for on-site testing of XLPE cable systems 16
17 Very Low Frequency (VLF) Suitability of different test voltages for on-site testing of XLPE cable systems 17
18 OWTS/DAC (Oscillating wave) (1) Usage of the cable system as test energy storage by charging it with a DC current (2) The DC charging ramp poses the danger for creating space charges Might lead to a breakdown of a otherwise healthy insulation (3) Typical test procedure of 50 shots equals ~ 10 s of continuous AC voltage (depending on the capacitance of the cable system) Only faults with a PD inception time of ~ 10 s can be detected (4) Does not represent stress under service conditions (5) Test time highly depends on the parameters of the cable and the test system very bad repeatability and thus not comparable (6) Due to DC charging different behavior of insulation compared to power frequency AC test and contiuous AC test not comparable with factory test or other on-site tests Not standardized and not recommended for commissioning testing Typical usage for diagnostic testing of MV cables where the safety margin in the electrical field strength is bigger compared to HV and EHV cable systems Suitability of different test voltages for on-site testing of XLPE cable systems 18
19 OWTS/DAC (Oscillating wave) Suitability of different test voltages for on-site testing of XLPE cable systems 19
20 Continuous AC Hz (1) Usually resonant circuit with fixed inductance and frequency converter as supply (2) Test voltage very similar to service voltage. Even at 20 Hz, 1 hour is equivalent with oscillations high probability to initiate discharges in faults very good possibilities to detect faults / e.g. PD (3) Electric field distribution is very close to that under service voltage represents very well the stess under service conditions (4) Very high comparability with tests done at power frequency in the factory (5) Test can be repeated even on other cables very good repeatability (6) Test is very well defined in the standards and the existing experience of ~ test conducted worldwide with continous AC between Hz shows similar performance like the tests done in the factories Standardized and well suitable for commissioning and diagnostic testing of MV/HV/EHV cable systems Suitability of different test voltages for on-site testing of XLPE cable systems 20
21 Continuous AC Hz Suitability of different test voltages for on-site testing of XLPE cable systems 21
22 24 h rated voltage (1) Voltage form and frequency identical to service conditions (2) Only faults which lead to a breakdown withhin 24 h of cable system service voltage can be found (3) PD measuring increases the chance to find more defects, but still all the faults with a PD inception time >24 h remain undetected Commissioning testing with 24 h of rated voltage is like a 1 day guarantee Well suitable for diagnostic testing of MV/HV/EHV cable systems Not recommended for commissioning testing Suitability of different test voltages for on-site testing of XLPE cable systems 22
23 2 3 Content 1 Introduction Test parameters and their significance Differences between AC/DC and MV/HV cables Comparison of test methods IEC Standard Suitability of different test voltages for on-site testing of XLPE cable systems 23
24 IEC Standard IEC old version Suitability of different test voltages for on-site testing of XLPE cable systems 24
25 IEC Standard IEC new version IEC Suitability of different test voltages for on-site testing of XLPE cable systems 25
26 IEC Standard IEC new version IEC Suitability of different test voltages for on-site testing of XLPE cable systems 26
27 IEC Standard IEC latest version IEC Suitability of different test voltages for on-site testing of XLPE cable systems 27
28 IEC Standard IEC latest version IEC Suitability of different test voltages for on-site testing of XLPE cable systems 28
29 IEC Standard IEC latest version IEC Suitability of different test voltages for on-site testing of XLPE cable systems 29
30 IEC Standard IEC latest version IEC Suitability of different test voltages for on-site testing of XLPE cable systems 30
31 THANK YOU FOR YOUR ATTENTION Michael Hensel HIGHVOLT Prüftechnik Dresden GmbH
32 MV cable test van 36 kv / 10 A Suitability of different test voltages for on-site testing of XLPE cable systems 32
33 HV cable test system 260/80 kv 83 A Suitability of different test voltages for on-site testing of XLPE cable systems 33
34 Parallel and Series Connections for long HV Cable Test L1 + L4 L2 + L5 L3 + L6 6 x WRV 83/260 T L4 II L5 II L6 Cable type: Cable length: Cable capacitance: Test voltage: Test duration: 400kV XLPE 16km 2360nF 260kV 1 hour Suitability of different test voltages for on-site testing of XLPE cable systems 11
F05D Meeting on Damped AC Voltage Testing
October 28 th, 2008 from 03.30-5.30 pm in San Antonio, TX Agenda F05D Damped AC Voltage Testing 1 Agenda F05D Damped AC Voltage Testing Welcome: Introduction On-site testing voltages e.g. IEC 60060-3 High
More informationTAN δ (DELTA) CABLE TESTING OVERVIEW AND ANSWERS TO FREQUENTLY ASKED QUESTIONS. What Is Tan δ, Or Tan Delta?
TAN δ (DELTA) CABLE TESTING OVERVIEW AND ANSWERS TO FREQUENTLY ASKED QUESTIONS What Is Tan δ, Or Tan Delta? Tan Delta, also called Loss Angle or Dissipation Factor testing, is a diagnostic method of testing
More informationMOBILE SYSTEM FOR DIAGNOSIS OF HIGH VOLTAGE CABLES (132KV/220KV) VLF-200 HVCD
MOBILE SYSTEM FOR DIAGNOSIS OF HIGH VOLTAGE CABLES (132KV/220KV) VLF-200 HVCD VERY LOW FREQUENCY (VLF) - PARTIAL DISCHARGES AND TANGENT DELTA HV/EHV POWER CABLES DIAGNOSTIC AND ON-SITE FIELD TESTING WITH
More informationWorld Leader in HV Testing Technology
World Leader in HV Testing Technology Cable Fault Locators w/tdr Oil/Fluid Dielectric Testers Very Low Frequency AC Technology W/TD & PD Diagnostics Portable AC Hipots ---------------------------------
More informationHow To Test For Safety On A Power Cable
T H E M A G A Z I N E O F 7 x 2 4 E X C H A N G E I N T E R N AT I O N A L A Green Approach to Building a Superior Data Center S P R I N G 0 9 BUILD FOR TODAY. EXPAND ON DEMAND. Modularity in the data
More informationEVALUATION OF ON-SITE DIELECTRIC RESPONSE METHODS FOR NON- DESTRUCTIVE TESTING OF WATER TREED MV XLPE CABLES
EVALUATION OF ON-SITE DIELECTRIC RESPONSE METHODS FOR NON- DESTRUCTIVE TESTING OF WATER TREED MV XLPE CABLES Sverre Hvidsten*, Peter Werelius**, Jørgen Christensen*** * SINTEF Energy Research (SEfAS),
More informationWhy Buy HVI VLF Products?
Very Low Frequency AC Hipots AC testing of cables and electrical apparatus is now easier than ever. Since the introduction of the High Voltage, Inc. line of portable and affordable VLF hipots, there is
More informationPC software icos Advanced
HIGHVOLT Prüftechnik Dresden GmbH Marie-Curie-Straße 10 01139 Dresden, Phone +49 351 8425 700 Fax +49 351 8425 679 E-mail sales@highvolt.de Website http://www.highvolt.de Data Sheet 12.21/1 PC software
More informationD1-306. Session 2004 CIGRÉ. 50 kv. 150 kv. Condition Assessment of High Voltage Power Cables. The Netherlands. E. Gulski * F.J.
21, rue d'artois, F-75008 Paris http://www.cigre.org D1-306 Session 2004 CIGRÉ Condition Assessment of High Voltage Power Cables E. Gulski * F.J. Wester Ph. Wester E.R.S. Groot J. W. van Doeland Delft
More informationInvestigation of the Residual-charge Technique for Diagnosis of Water-tree Deteriorated Cross-linked Polyethylene Cable
Investigation of the Residual-charge Technique for Diagnosis of Water-tree Deteriorated Cross-linked Polyethylene Cable Dr. Uchida Katsumi*, Youichi Katou*, Dr. Hiroyuki Kon, Dr. Kazuo Watanabe and Takenori
More informationTWENTIES WORKSHOP, EWEA 2012 Unveiling the future energy system: full scale demonstrations to reach 2020 targets. 17th April 2012
TWENTIES WORKSHOP, EWEA 2012 Unveiling the future energy system: full scale demonstrations to reach 2020 targets 17th April 2012 Session 2 Technological challenges to cope with in TWENTIES field tests
More informationCABLE DIAGNOSIS USING VARIABLE FREQUENCY AND PARTIAL DISCHARGE DIAGNOSIS WITH DEFECT LOCATION AND CHARACTERIZATION G.C. Montanari J. Rickman D.
CABLE DIAGNOSIS USING VARIABLE FREQUENCY AND PARTIAL DISCHARGE DIAGNOSIS WITH DEFECT LOCATION AND CHARACTERIZATION G.C. Montanari J. Rickman D. Kremer Abstract A new approach to cable diagnostics is discussed
More informationELECTRICAL INSULATION TESTING OF HV EQUIPMENT UP TO 33kV
1. SCOPE This document details PowerSystems requirements for electrical testing of HV Equipment up to and including 33kV. 2. ISSUE RECORD This is a Reference document. The current version of Controlled
More informationTHE USE OF AFTER-INSTALLATION COMMISSIONING TESTS TO ASSURE MV POWER CABLE SYSTEMS MEET MANUFACTURERS STANDARDS
THE USE OF AFTER-INSTALLATION COMMISSIONING TESTS TO ASSURE MV POWER CABLE SYSTEMS MEET MANUFACTURERS STANDARDS Stefaan JESPERS (1), Massimo VANOSSI (2), Marco GREEN (3), Benjamin Lanz (4) 1 Cegelec, Brussels,
More informationDDX 7000 & 8003. Digital Partial Discharge Detectors FEATURES APPLICATIONS
DDX 7000 & 8003 Digital Partial Discharge Detectors The HAEFELY HIPOTRONICS DDX Digital Partial Discharge Detector offers the high accuracy and flexibility of digital technology, plus the real-time display
More informationWIRE AND CABLE ENGINEERING GUIDE
Excerpt From Prysmian s WIRE AND CABLE ENGINEERING GUIDE Page 1 of 8 CABLE TESTING Testing represents an integral part in the life of a cable. A cable will be subjected to multiple tests in its lifetime
More informationHV Submarine Cable Systems Design, Testing and Installation
HV Submarine Cable Systems Design, Testing and Installation CIGRE Ireland Technical Seminar 6 th October 2010 Robert Donaghy Senior Consultant Engineer, ESB International Presentation Overview Applications
More informationEMTP STUDIES PERFORMED TO INSERT LONG AC CABLES IN THE FRENCH GRID
Tension (kv) Impedance (Ohms) EMTP STUDIES PERFORMED TO INSERT LONG AC CABLES IN THE FRENCH GRID frequency (Hz) Simon DESCHANVRES Yannick VERNAY RTE, CNER, Substations Department t (ms) EMTP-RV Users Group
More informationBAUR cable testing and diagnostics. Networks are sensitive. We help you protect them. USA Distributor:
BAUR cable testing and diagnostics. Networks are sensitive. We help you protect them. USA Distributor: HV TECHNOLOGIES,Inc. Tel:+1-703-365-2330 www.hvtechnologies.com hvsales@hvtechnologies.com Improved
More informationHigh Voltage Test Equipment. Product Catalogue
High Voltage Test Equipment Product Catalogue High Voltage Test Equipment Innovative, proven, economic HV Testing from b2 High Voltage HVA VLF-High Voltage Test Systems from page 3 TD Tan Delta Diagnostic
More informationA Practical Guide to Dielectric Testing
Chroma Systems Solutions, Inc. A Practical Guide to Dielectric Testing 19032 Series Electrical Safety Analyzer & 19050 Series Hipot Tester AC/DC/IR/SCAN Keywords: Dielectric tests, insulation resistance
More information48 SERIES Relay interface modules 10 A
48 Relay interface modules 10 A 1 CO relay interface modules, mm wide Ideal interface for PLC and electronic systems Type 48.P3 1 CO 10 A s Type 48.31 1 CO 10 A s AC coils or DC sensitive coils Supply
More informationWIRE AND CABLE ENGINEERING GUIDE
DC Hi Pot Testing Excerpt from PRYSMIAN S WIRE AND CABLE ENGINEERING GUIDE (FOR INFORMATIONAL PURPOSES ONLY) Page 1 of 6 DC HIGH POTENTIAL TESTING DC Hi-Pot testing can be applied as a withstand test (a
More informationDDX 7000 & 8003. Digital Partial Discharge Detectors FEATURES APPLICATIONS
DDX 7000 & 8003 Digital Partial Discharge Detectors The HAEFELY HIPOTRONICS DDX Digital Partial Discharge Detector offers the high accuracy and flexibility of digital technology, plus the real-time display
More informationPOWER SYSTEM CONSULTANTS POWER-LINKER
GROUP POWER SYSTEM CONSULTANTS POWER-LINKER REFERENCE LIST : VERY LOW FREQUENCY (VLF) Given below is a list of Very Low Frequency (VLF) job executed by us: SR. 40.0 Cairn India Ltd., MPT Barmer Cable 6.6
More informationCondition Monitoring of equipment to improve quality of supply to customers by averting failures
Condition Monitoring of equipment to improve quality of supply to customers by averting failures Author & presenter: Patrick O Halloran BTECH Manager Technology Services at City Power Johannesburg Abstract
More informationInvestigation of VLF Test Parameters. Joshua Perkel Jorge Altamirano Nigel Hampton
Investigation of VLF Test Parameters Joshua Perkel Jorge Altamirano Nigel Hampton 1 Introduction - why IEEE400.2 is in use with recommendations of test times and test voltages At the start of the CDFI
More information48.12. 2 pole, 8 A Safety relay. Screw terminal. 35 mm rail (EN 60715) mounting. 2 CO (DPDT) 8/15 250/400 2,000 500 0.37 8/0.65/0.
48 Series - Relay interface modules 8 A Features 48.12 2 Pole Safety relay interface modules, 15.8 mm wide 48.12-2 Pole 8 A (screw terminal) DC sensitive coils Relay with forcibly guided contacts according
More information6 ELECTRICAL PARAMETERS
6 ELECTRICAL PARAMETERS For power, low voltage and medium voltage cables, cross section nominal areas are calculated in taking into account several parameters as: permissible current carrying capacities
More information38 Series - Relay interface modules 0.1-2 - 3-5 - 6-8 A
38 Series - Relay interface modules 0.1-2 - 3-5 - 6-8 A Common features Instant ejection of relay by plastic retaining clip Integral coil indication and protection circuit EMR Electromechanical Relays
More informationDiscussion on Class I & II Terminology. IEEE PES Transformers Committee Fall Meeting 2011 Boston, MA
Discussion on Class I & II Terminology IEEE PES Transformers Committee Fall Meeting 2011 Boston, MA What is Class I & II? C57.12.00 2010 is the only document we have that defined these terms. 5.10 Insulation
More informationRM35UA13MW. range 15..600 V. Main. Product or component type. Relay monitored parameters
Characteristics multifunction voltage control relay RM35-U - range 15..600 V Complementary Reset time Maximum switching voltage [Us] rated supply voltage Supply voltage limits Power consumption in W Main
More informationBAUR Cable Testing & Diagnostics. Networks are sensitive. We help you to protect them.
BAUR Cable Testing & Diagnostics. Networks are sensitive. We help you to protect them. Improved security and cost-effectiveness of cable networks High voltage testing and diagnostics with BAUR Underground
More information38 Series - Relay interface modules 0.1-2 - 3-5 - 6-8 - 16 A
38 Series - Relay interface modules 0.1-2 - 3-5 - 6-8 - 16 A 38 SERIES Common features Instant ejection of relay by plastic retaining clip Integral coil indication and protection circuit EMR Electromechanical
More informationKNOW YOUR OPTIONS: 230 KV POWER CABLES
KNOW YOUR OPTIONS: 230 KV POWER CABLES 71 CONDUCTOR MATERIAL AND SIZE Conductor material is a matter of both customer preference and required current carrying capacity At 230 kv, copper is most common
More informationOn-line PD Monitoring Makes Good Business Sense
On-line PD Monitoring Makes Good Business Sense An essential tool for asset managers to ensure reliable operation, improve maintenance efficiency and to extend the life of their electrical assets. Executive
More informationTransformer Bushings for GIS
Transformer Bushings for GIS Oil to SF6 Connections GARIP RTKG 725-55 kv SQS certified ISO 91 / ISO 141 Bushings RIP - Technology for SF6 / Oil - Bushings In modern metal enclosed switchgear SF6 -gas is
More informationRM17TE 183...528 V AC. Main. Product or component type. Product specific application. Relay monitored parameters 250 V DC 5 A DC
Characteristics multifunction control relay RM17-TE - range 183..528 V AC Complementary Reset time Maximum switching voltage Minimum switching current Maximum switching current [Us] rated supply voltage
More informationHOW GOOD ARE ELECTRICAL DIAGNOSTIC TESTS TO PREDICT WATER TREES IN HV CABLES AN EVALUATION USING OPTICAL MICROSCOPY
Journal of ELECTRICAL ENGINEERING, VOL. 56, NO. 1-2, 25, 31 35 HOW GOOD ARE ELECTRICAL DIAGNOSTIC TESTS TO PREDICT WATER TREES IN HV CABLES AN EVALUATION USING OPTICAL MICROSCOPY Motaheruddin Ahmed Mohammad
More information49 Series - Relay interface modules 8-10 - 16 A. Features
Features 1 & 2 Pole relay interface modules 5 µm Gold plate contacts for low level switching capability 49.31-50x0-1 Pole 10 A (screw terminal) 49.52-50x0-2 Pole 8 A (screw terminal) 49.72-50x0-2 Pole
More informationRM4TG20 three-phase network control relay RM4-T - range 200..500 V
Characteristics three-phase network control relay RM4-T - range 200..500 V Complementary [Us] rated supply voltage Output contacts Setting accuracy of time delay Delay at power up Measuring cycle Marking
More informationAssessment of the Technical Issues relating to Significant Amounts of EHV Underground Cable in the All-island Electricity Transmission System
Assessment of the Technical Issues relating to Significant Amounts of EHV Underground Cable in the All-island Electricity Transmission System Summary Report November 2009 Technical Report on using EHV
More informationSection 5 161 kv Power Cables
Know Your Options: 161 kv Power Cable 61 material and size material is a matter of both customer preference and required current carrying capacity Copper conductor common for larger loads When both copper
More informationEMOSAFE EN-100. Network Isolators for PCB assembly 1 GENERAL DESCRIPTION. Product Data Sheet ENGLISH
ENGLISH EMOSAFE EN-100 Product Data Sheet Network Isolators for PCB assembly November 2013 1 GENERAL DESCRIPTION The EMOSAFE EN-100 Network Isolator interrupts all galvanically conducting connections (conductors
More informationINTERNATIONAL STANDARD
INTERNATIONAL STANDARD IEC 60071-2 Third edition 1996-12 Insulation co-ordination Part 2: Application guide This English-language version is derived from the original bilingual publication by leaving out
More informationA Study of a MV Cable Joint
SERBIAN JOURNAL OF ELECTRICAL ENGINEERING Vol. 7, No. 1, May 2010, 1-11 UDK: 621.315.35:537.212 A Study of a MV Cable Joint Radiša Dimitrijević 1, Neda Pekarić-Nađ 2, Miodrag Milutinov 3 Abstract: Construction
More informationHigh Voltage Electrical Equipment Failure Diagnosis. Presented by: Spencer Tang & Terence Ng T&T Inspection & Engineering Sdn Bhd
High Voltage Electrical Equipment Failure Diagnosis Presented by: Spencer Tang & Terence Ng T&T Inspection & Engineering Sdn Bhd High Voltage Electrical Equipment Failure Diagnosis Definition of High Voltage
More informationTechnical Data. General specifications Switching element function Rated operating distance s n 15 mm
0102 Model Number Features Comfort series 15 mm flush Accessories MHW 01 Modular mounting bracket MH 04-2057B Mounting aid for VariKont and +U1+ Technical Data General specifications Switching element
More informationElectronic timer CT-VBS.17+18 OFF-delayed without auxiliary voltage, for DC contactors Data sheet
Characteristics Single-function OFF-delay timer for DC contactors, without auxiliary voltage Width.5 mm CDC 5 6 F3 Approvals A culus E CCC CT-VBS a Circuit diagram b Marker label Marks a CE b C-Tick Order
More informationIDEAL INDUSTRIES, INC. TECHNICAL MANUAL MODELS: 61-763 61-765
IDEAL INDUSTRIES, INC. TECHNICAL MANUAL MODELS: 61-763 61-765 The Service Information provides the following information: Precautions and safety information Specifications Performance test procedure Calibration
More informationKNOW YOUR OPTIONS: 69 KV XLPE POWER CABLE
Know Your Options: 69 kv XLPE Power Cable 3 material and size material is a matter of both customer preference and required current carrying capacity Copper conductor common for larger loads When both
More informationTwo different types of cables are used in primary airfield lighting circuits: - unshielded cables and - shielded cables
Two different types of cables are used in primary airfield lighting circuits: - unshielded cables and - shielded cables Classically both cables have a single AWG 8 copper conductor or a cross section of
More informationApplication Guide Film Capacitors
Capacitance Change vs. Temperature Insulation Resistance vs. Temperature Polyester Typical Characteristics at 1 khz % Capacitance Change % Capacitance Change Polypropylene Typical Characteristics at 1
More informationA Power Cable Reliability Solution
A Power Cable Reliability Solution IEEE Insulated Conductors Committee Subcommittee C October 30, 2006 Benjamin Lanz Some of the technologies referenced herein are patented and proprietary IMCORP technology.
More informationTechnical Specification for 5VDC/2A +12VDC/2A Adapter
Technical Specification for 5VDC/2A +12VDC/2A Adapter Contents 1. SCOPE This specification defines the performance characteristics of a grounder,single phase, 34 Watt,2 outputs power supply.this specification
More informationAMSC s Superconductor Cable Technologies for Electric Utilities
International Workshop 2014 AMSC s Superconductor Cable Technologies for Electric Utilities Michael Ross, P.E. Managing Director of Superconductor Power Systems AMSC Corporate Facts Headquartered in MA,
More informationBulletin 150 SMC Flex Smart Motor Controller Specifications
Specifications Specifications Standard Features Optional Features Installation Setup Communications Power Wiring Control Wiring Keypad Software Starting and Stopping Modes Protection and Diagnostics Metering
More informationTesting of Power Transformers. Routine tests, Type tests and Special tests
Testing of Power Transformers Routine tests, Type tests and Special tests Testing of Power Transformers Routine tests, Type tests and Special tests Testing of Power Transformers Routine tests, Type tests
More informationInductive Sensors Single or Dual Loop Detectors Type LD with teach-in
Inductive Sensors Single or Dual Loop Detectors Type LD with teach-in Single or Dual loop detector Automatically adjustment of detection level Manual sensitivity for compensations of variations Easy installation
More informationSession Five: Modern XLPE Materials for Extruded Energy Cable Systems
Session Five: Modern XLPE Materials for Extruded Energy Cable Systems Abstract Hakan Lennartsson Senior Technical Service Manager, Borouge Hong Kong Pte. Ltd. The first medium voltage cables using extruded
More informationSafety technique. Emergency stop module BO 5988 safemaster
Safety technique Emergency stop module BO 5988 safemaster 0221562 Function diagram Pushbutton on Mains or emergencystop () K1 According to EC Directive for machines 98/37/EG According to IEC/E 60204-1
More informationSub sea Cable Technology
EERA DeepWind 2014 Sub sea Cable Technology Hallvard Faremo SINTEF Energy Research Brief presentation of: Wind Farm Cable R&D project Technology for a better society 1 High Voltage Subsea Cables Networking
More informationIntroduction. Harmonics and IEEE 519 Page 1 of 19
Introduction In an ideal power system, the voltage supplied to customer equipment, and the resulting load current are perfect sine waves. In practice, however, conditions are never ideal, so these waveforms
More informationAdoption of Best Practices for Cable Testing and Condition Monitoring in the Offshore Renewables Market
Adoption of Best Practices for Cable Testing and Condition Monitoring in the Offshore Renewables Market Presented by: Dr Lee Renforth Managing Director, HVPD Ltd CONTENTS Why do we need improved commissioning
More informationPreliminary Results from Present Cigre Survey
Cigre WG A3-06 HV Equipment Reliability Preliminary Results from Present Cigre Survey Gas Insulated Substations (GIS) DB status : August 2007 Focus on population cards and major failure cards (namely 2004
More informationProperties of electrical signals
DC Voltage Component (Average voltage) Properties of electrical signals v(t) = V DC + v ac (t) V DC is the voltage value displayed on a DC voltmeter Triangular waveform DC component Half-wave rectifier
More informationCharged cable event. 1 Goal of the ongoing investigation. 2 Energy sources for the CDE. Content
Charged cable event David Pommerenke, david_pommerenke@hp.com, 916 785 4550 Last update: Feb.23, 2001 Content Goal Energy sources, which may lead to CDE. Complexity of the different discharge modes. Possible
More informationThe standards mentioned in this document
The standards mentioned in this document Where can you order IEC publications? Central Offices of the International Electrotechnical Commission 1, rue de Varembé Geneva - Switzerland. The documentation
More informationType: EASY719 DC RC Article No.: 274119. Ordering information Relay outputs Quantity 6 Power supply V DC 24 V DC. Description
Type: EASY719 DC RC Article.: 274119 Ordering information Relay outputs Quantity 6 Power supply V DC 24 V DC Description 12 digital inputs (4 inputs available as analog inputs) 6 relay outputs LCD display
More informationPB POWER ISLAND OF IRELAND CAVAN-TYRONE AND MEATH-CAVAN 400KV PROJECTS PRELIMINARY BRIEFING NOTE OVERHEAD AND UNDERGROUND ENERGY TRANSMISSION OPTIONS
ISLAND OF IRELAND CAVAN-TYRONE AND MEATH-CAVAN 400KV PROJECTS PRELIMINARY BRIEFING NOTE OVERHEAD AND UNDERGROUND ENERGY TRANSMISSION OPTIONS FEBRUARY 2008 PB POWER PB Power Page i EXECUTIVE SUMMARY General
More informationHigh Voltage Systems. Today. The history of cables
High Voltage Cables High Voltage Systems Today Prysmian Cables and Systems B.V. is part of the Prysmian Group, a leading player in the industry of high-technology cables and systems for energy and telecommunications,
More informationFault location on power cables. Fault location on power cables
Fault location on power cables Fault location on power cables Contents: 1. Introduction 2. Construction of power cables 3. Cable faults 01. Introduction Fault location on communication and power cables
More informationHow To Build A Low Voltage Capacitor Lvcp
Low Voltage Capacitor LVCP The new choice for Power Factor Correction LVCP : the new choice for Power Factor Correction The LVCP is a compact and powerful capacitor. It offers high modularity, unmatched
More informationANN Based Fault Classifier and Fault Locator for Double Circuit Transmission Line
International Journal of Computer Sciences and Engineering Open Access Research Paper Volume-4, Special Issue-2, April 2016 E-ISSN: 2347-2693 ANN Based Fault Classifier and Fault Locator for Double Circuit
More informationIEEE802.3poep Study Group Revision of isolation requirements in IEEE802.3 clause 33.
IEEE802.3poep Study Group Revision of isolation requirements in IEEE802.3 clause 33. San Francisco, July 2005 Arkadiy Peker Powerdsine Arkadiyp@powerdsineusa.com Yair Darshan Powerdsine Yaird@powerdsine.com
More informationPower transformers. Special transformers Railway
Power transformers Special transformers Railway A leader in railway systems Our compact and low-weight transformers fully comply with the customer s specifications. The products are developed together
More informationALTERNATIVE METHODS FOR INTERNAL ARC TESTS ON 12 KV AND 24 KV METAL-ENCLOSED SWITCHGEARS WITH COMPACT RMU
ALTERNATIVE METHODS FOR INTERNAL ARC TESTS ON 12 KV AND 24 KV METAL-ENCLOSED SWITCHGEARS WITH COMPACT RMU George CURCANU, Constantin ILINCA, Ilie SBORA ICMET Craiova, Romania, Calea Bucuresti 144, phone:
More informationRelés e Contatores de Estado Sólido SIRIUS
Relés e Contatores de Estado Sólido SIRIUS Coletânea de dados técnicos ( product data sheet ) Agosto/212 SSR - 3RF21 22,5 mm Ponto Zero SSR - 3RF2 45 mm Ponto Zero SSR - 3RF22 45 mm Ponto Zero Trifásico
More informationi410/i1010 AC/DC Current Clamp
/i1010 AC/DC Current Clamp Instruction Sheet Safety Information XW Read First: Safety Information To ensure safe operation and service of the current clamp, follow these instructions: Read all operating
More informationHow to design SMPS to Pass Common Mode Lightning Surge Test
Application Note, V1.0, September 2006 How to design SMPS to Pass Common Mode Lightning Surge Test Power Management & Supply N e v e r s t o p t h i n k i n g. Edition 2006-09-06 Published by Infineon
More information1 Form A Solid State Relay
1 Form A Solid State Relay Vishay Semiconductors DIP i1791- SMD DESCRIPTION Vishay solid state relays (SSRs) are miniature, optically coupled relays with high-voltage MOSFET outputs. The LH1518 relays
More informationThree-phase monitoring relay CM-PFE
Data sheet Three-phase monitoring relay CM-PFE The CM-PFE is a three-phase monitoring relay that monitors the phase parameter phase sequence and phase failure in three-phase mains. 2CDC 251 005 S0012 Characteristics
More informationThe evolution of medium voltage power cables up to 36 kv
The evolution of medium voltage power cables up to 36 kv by Patrick O Halloran, City Power This paper will cover the evolution of MV power cables over the last century and will cover some pros and cons
More informationTISP4600F3, TISP4700F3 OBSOLETE
*RoHS COMPLIANT TISP4600F3, TISP4700F3 HIGH OLTAGE BIDIRECTIONAL THYRISTOR OEROLTAGE PROTECTORS TISP4600F3, TISP4700F3 Ion-Implanted Breakdown Region Precise and Stable oltage Low oltage Overshoot under
More informationThermistor motor protection
Thermistor motor protection CM-E Range Thermistor motor protection Thermistor motor protection relays Benefits and advantages Selection table Operating principle and fields of application for thermistor
More information38 SERIES. Relay interface modules 0.1-2 - 3-5 - 6-8 - 16 A. EMR Electromechanical Relays. Common features. SSR Solid State Relays. 6.
38 Relay interface modules 0.1-2 - 3-5 - 6-8 - 16 A 38 Common features Instant ejection of relay by plastic retaining clip Integral coil indication and protection circuit 6.2 mm wide EMR - DC, AC or AC/DC
More informationSURGE PROTECTIVE DEVICES
SURGE PROTECTIVE DEVICES 1. INTRODUCTION In order to ensure safety of people, protection of equipment and, to a certain extent, continuity of supply, insulation co-ordination aims at reducing the likelihood
More informationFor the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit.
Current Transducer HO-P series I PN = 6, 10, 25 A Ref: HO 6-P, HO 10-P, HO 25-P For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary
More informationMV CABLE TYPE C 33-226
MV CABLE TYPE C 33-226 Standards : CENELEC HD 620 C 33-226 Rated voltage Rated voltage : 12/20 (24) kv Design 1 Stranded aluminium, class 2 conductor 2 Extruded conducting screen on conductor 3 XLPE insulation
More informationAssessment ASSET MANAGEMENT SERVICES. Benefits: > Optimal Exploitation > Increased Reliability > Reduced Unplanned Outages Time.
Benefits: > Optimal Exploitation > Increased Reliability Applications The Condition services include all of those activities aimed at defining the conditions of all the components of a link before it is
More informationDo s and don'ts of connection systems Are there any options when the clearance and creepage distances are not sufficient for UL 1059?
Do s and don'ts of connection systems Are there any options when the clearance and creepage distances are not sufficient for UL 1059? Speaker: Wolfgang Sichmann, Product Manager PCB Plug-In Connectors,
More informationABB i-bus KNX Switch Actuator, x-fold, 16/20 A, MDRC SA/S x.16.6.1, 2CDG 110 1xx R0011
, 2CDG 110 1xx R0011 SA/S 8.16.6.1 2CDC 071 006 S0010 The 16/20 A Switch actuators are modular installation devices in Pro M Design for installation in the distribution board. The devices are especially
More informationEDS 02-0027 11KV TRIPLEX CABLE
THIS IS AN UNCONTROLLED DOCUMENT, THE READER MUST CONFIRM ITS VALIDITY BEFORE USE Document Number: EDS 02-0027 ENGINEERING DESIGN STANDARD EDS 02-0027 11KV TRIPLEX CABLE Network(s): EPN, LPN, SPN Summary:
More informationThe full wave rectifier consists of two diodes and a resister as shown in Figure
The Full-Wave Rectifier The full wave rectifier consists of two diodes and a resister as shown in Figure The transformer has a centre-tapped secondary winding. This secondary winding has a lead attached
More informationType: DILM50(230V50HZ,240V60HZ) Article No.: 277830
Type: DILM50(230V50HZ,240V60HZ) Article No.: 277830 Ordering information Rated operational current AC 3 400 V I e A 50 Max. rating for three phase motors, 50 60 Hz AC 3 230 V Max. rating for three phase
More informationDevelopment of a 500-kV DC XLPE Cable System
by Satoru Maruyama *, Noboru Ishii *, Michihiro Shimada *, Shinji Kojima * 2, Hideo Tanaka * 3, Mitsumasa Asano * 4, Tetsuya Yamanaka * 4, and Shin ichi Kawakami * 4 This paper describes development work
More informationWINGLIKE ELECTRONICS CO.,LTD
WINGLIKE ELECTRONICS CO.,LTD SPECIFICATION FOR APPROVAL AC/DC ADAPTOR CUSTOMER: CUSTOMER SPECS INPUT: 100-240V AC 50-60HZ, 5V/2A ADAPTOR OUR MODEL NO.: GM-050200 (UL) E321192 SPECIFICATION NO.: WL1105102
More informationI-PEX MHF4 Micro Coaxial Connector
PRODUCT SPECIFICATION I-PEX MHF4 Micro Coaxial Connector Plug P/N 20448-001R-81 Receptacle P/N 20449-001E RF Connector, RF Cable & Antenna Manufacturer E-mail: sales@wellshow.com.tw Tel: +886-2-24239376
More informationUnified requirements for systems with voltages above 1 kv up to 15 kv
(1991) (Rev.1 May 2001) (Rev.2 July 2003) (Rev.3 Feb 2015) Unified requirements for systems with voltages above 1 kv up to 15 kv 1. General 1.1 Field of application The following requirements apply to
More informationAMP CO Plus Insert for Cat. 6 A Applications
Product Specification 108-93039 10/Mar/2011 Rev F AMP CO Plus Insert for Cat. 6 A Applications 1. SCOPE 1.1 Content This specification covers performance, tests and quality requirements for AMP* CO Plus
More information