FPS4 APPENDIX A (INTERIM) SPECIFICATION FOR THE INSPECTION AND TESTING OF AUTOMATIC FIRE SPRINKLER SYSTEMS

Size: px
Start display at page:

Download "FPS4 APPENDIX A (INTERIM) SPECIFICATION FOR THE INSPECTION AND TESTING OF AUTOMATIC FIRE SPRINKLER SYSTEMS"

Transcription

1 FPS4 APPENDIX A (INTERIM) SPECIFICATION FOR THE INSPECTION AND TESTING OF AUTOMATIC FIRE SPRINKLER SYSTEMS To be used in conjunction with the Fire Protection Association Australia FPS4-2000: Agreement for the Inspection and Testing of Fire Protection Systems. All sprinkler systems shall be inspected and tested at the periodic intervals as required by AS1851.3: Maintenance of Fire Protection Equipment (Part 3: Automatic fire sprinkler systems) and as specified in the following Clauses. Inspections and tests shall be recorded in a manner specified in the relevant Australian Standard and kept at the control valve for this purpose. Details of all service calls required or undertaken shall be recorded in this log book. Tests shall be conducted in a manner acceptable to and conforming with the equipment and practices of the local fire brigade. SECTION A SCOPE OF WORK For the purpose of this specification Inspection and Testing routines shall be carried out as defined. Level 1 Routine Weekly Level 2 Routine Quarterly Level 3 Routine Annually Level 4 Routine Three Yearly Level 5 Routine Six Yearly The Contractor shall carry out all Routines during normal working hours. If work is required outside normal working hours this will be subject to a separate quotation and authority by the Client. LEVEL 1 ROUTINE - WEEKLY 1.1 All Wet Pipe Systems (e) (f) (g) (h) (i) (j) (k) Check that control valve/pump areas are unobstructed and are not used for storage. Notify fire brigade of intention to simulate a fire call where applicable. Record reading on all pressure gauges in log book. Operate alarm valve by opening the 15mm test valve or by other approved means. Check for correct operation of external and/or local alarms and direct brigade alarms and record results and activation times in log book. Close 15mm or other test valve and ensure that the alarm valve has reseated. Check that the simulated fire call has been transmitted to the fire brigade, indicated on the test apparatus and record result in log book. Restore installation pressure where necessary. Again record in log book reading on all pressure gauges. Check for correct operation of any facilities installed for the continuous monitoring of stop valves. Reset and secure all valves in the open or closed position as appropriate. Particular attention shall be given to the Main Stop Valve(s) and alarm cocks.

2 FPS4: Appendix A (Int.) Page 2 (l) (m) Check that stop valves on town main connections, pressure tank deliveries, pump suctions and deliveries are secured in the fully open position (with the exception of underground and elevated valves - refer Level 2 routine - item2.1. Check that spare sprinklers and sprinkler spanner(s) are on hand. 1.2 Additional Requirements where Remote Initiation Facilities are Installed Check the initiation facilities to operate remote control functions in accordance with the appropriate codes. It is recommended that where air-handling plant shutdown facilities are provided, these should be operated as required by the relevant Australian Standard. The client, however, shall be notified prior to shutdown and it shall be the responsibility of the client to provide qualified personnel to be in attendance to restart the plant. (Refer Section B - Client s Responsibilities Clause 7) 1.3 Additional Requirements Where Pump Suction or Pressure Tanks are Installed Pump Suction Tanks. Check that pump suction tank is full. Check for correct operation of automatic inflow valve(s) and water level indicator device(s). Visually check for obvious obstruction at the drain point from the tank overflow. Check that spare engine components are on hand Pressure Tanks Check for correct water level. Check for correct air pressure. Check air pressure and/or water level warning device(s) for correct operation. Check air compressor and water pump for correct operation. 1.4 Additional Requirements where Automatic Pumps are Installed Batteries and Equipment Check for correct operation of any facilities installed for the continuous monitoring of valves. Where installed, check the batteries and battery chargers for the following: (i) Freedom from corrosion in battery cabinet or compartment and security of battery in its position. (ii) Electrolyte level. Top up if necessary, neutralise and clean up any spilt electrolyte. (iii) Serviceability. (iv) Ventilation openings are clear. (v) Battery connections for tightness and cleanliness. (vi) Battery voltage. (vii) Check and record the corrected electrolyte density of each cell Pumpsets Start each pump set by reducing the applied water pressure to starting device(s). Where more than one starting device is installed for each pump set, this test may be carried out on a weekly rotating basis for each pump, but in no case shall the period between the exercising of each starting device exceed one month. A period of not less than 5 minutes shall elapse between successive starts on compression ignition driven pump. Compression ignition driven pump sets shall be run for a least 10 minutes and electric motor driven pump sets for at least 3 minutes continuously. /cont. FPS4 APPENDIX A FOR USE BY

3 FPS4: Appendix A (Int.) Page Electric Motor Driven Pump Pump starts at the nominated starting pressure. Pump gland and drain operate efficiently. Excessive vibration or noise is not evident. Both local and remote pump running alarms operate. (e) Phase failure alarm is operating correctly. (f) Water in priming tank is at correct level Compression Ignition Driven Pump Sets Check water, oil and fuel level prior to running, then check that: Pump starts at nominated starting pressure. Pump gland and drain operate efficiently. Both local and remote pump running alarms operate. Out of balance condition is not evident. (e) Running speed, oil pressure and temperature are correct. (f) Water, oil and fuel leaks are not evident and fittings on ancillary equipment are secure. (g) Engine stop mechanism automatically returns to the start position. (h) Battery charging alternator-generator is operating correctly. (i) Belt drives are in good conditions and correctly tensioned. (j) Battery charger power failure alarm operates correctly. (k) Water, oil and fuel levels are fully topped up. (l) Water in priming tank is at correct level. LEVEL 2 ROUTINE - QUARTERLY Level 2 routine consists of Level 1 routine together with the following: 2.1 All Wet Pipe Systems (e) Check correct operation of indicator panel. Test water flow alarm switches by the operation of a 10mm or 15mm test valve to simulate a sprinkler operation. NOTE: These may be tested on a weekly rotating basis, however, each switch must be tested quarterly. Operate and check to ensure that all street isolating valves on the town main connection, ring and loop mains and elevated tanks are fully open. Check to ensure that all water non-return valves are correctly seated. Clean the strainer and oil the external alarm water motor and gong. 2.2 Where Spray Booths are Internally Protected by Sprinklers. Check condition of sprinklers in spray booths to see that accumulated spraying residues have been removed and that protective coating such as petroleum jelly are in a satisfactory condition (refer Section B - Client s Responsibilities Clause 2). 2.3 Additional Requirements where Automatic Pumps are Installed. Electric Powered Pump. Where alternative power supplies are provided, the pump shall be run off the alternative supply. The pump shall be run for not less than three minutes. NOTE: The pump should be run under load where practicable. Compression-Ignition Engine Driven Pump. The engine shall be run at rated speed for a period of not less than 30 minutes and the operating temperature, oil pressure, tachometer reading and FPS4 APPENDIX A (Int.) FOR USE BY

4 FPS4: Appendix A (Int.) Page 4 water temperature shall be recorded just prior to completion of the run. NOTE: This test should be carried out at not less than 60 percent of operating load where practicable. After stopping, restart the engine using the manual control to check for correct operation of the manual start system. LEVEL 3 ROUTINE - ANNUALLY Level 3 Routine consists of Levels 1 and 2 routines together with the following: 3.1 All Wet Pipe Systems (e) (f) (g) Carry out water supply periodic check test in accordance with the Rules under which the installation is installed to verify that the system pressure/flow requirements are satisfied. Check wiring connection to all direct brigade alarm units and that fire line is adequately supported and in good condition. Physically check all pressure switches to ensure that components are free of corrosion, securely mounted and in working order. Operate all pressure reducing valves to the full extent of piston movement and check for correct operation under flow conditions. Check readings in the low pressure side of the valves for deterioration from the original test readings. Check that block plan, location plate, and emergency instructions are legible and that all required information is incorporated. Check legibility of fire brigade booster connection markings. Check electric signal is generated at output of auxiliary start, shutdown and alarm switches. 3.2 Additional Requirements where Automatic Pumps are Installed. Service electric motor driven pump sets in the following sequence: (i) (ii) (iii) (iv) (v) (vi) Check circuit breaker and/or fuses protecting pump motor circuits to ensure that this equipment is of the correct type and rating as originally installed. With electrical equipment isolated from all power supplies, the motor starter shall be cleaned and the condition of all heavy-current-carrying contacts checked (any item showing signs of wear or corrosion should be immediately repaired or replaced). Check electric pump starter operation to ensure that the starting sequence is completed and the pump fully operational within 30 seconds. Check for correct rotation of pumps. After items (i), (ii), (iii) and (iv) above have been completed run the electric pump for a minimum period of 30 minutes under load conditions and check the load current per phase for variation from original test readings. Check that phase failure alarm is operating correctly. Service compression-ignition engine driven pump sets in the following sequence: (i) Check, clean and replace if required, engine fuel sludge and sediment trap and fuel, oil and air filters. (ii) Change engine oil. (iii) After items (i) and (ii) have been completed, run the pump for a minimum period of 30 minutes under load conditions and check as per Level 1 routine (iv) Check that - * the installed heating for maintaining engine room temperature above 10 o C is operating correctly; and * the ventilation for engine aspiration and for limiting room temperature rise to less than 10 o C above ambient temperature is satisfactory. FPS4 APPENDIX A FOR USE BY

5 FPS4: Appendix A (Int.) Page Additional Items as Applicable. Examine all water storage tanks and report on their condition. NOTE: Draining is not normally required for this inspection. Inspect all anti-freeze installations and devices including tail-end valve sets and check antifreeze solution levels, where applicable. 3.4 Sprinklers Under Cooking Hoods Sprinklers installed under cooking hoods should be replaced annually. This work will be subject to a separate quotation and authority by the client. LEVEL 4 ROUTINE - THREE YEARLY Level 4 routine consists of Levels 1, 2 and 3 routines together with the following: 4.1 All Wet Pipe Systems (e) (f) (g) (h) (i) (j) (k) (l) Renew alarm valve seatings and/or port seating, check and clean annular groove and outlet ports, polish and lubricate seating spindle/shaft and check operation of compensator valve if fitted. Renew alarm valve face plate gasket. Renew drain and test valve washers and examine seatings. Remove alarm and plug cock barrels, clean, lap-in grease and replace. Replace pump path cock washers and inspect seatings. Renew gland packing for path cocks, drain and test cocks, main stop valve and hand pump. Clean out well of D.B.A. clean water jet, renew gasket, flush drain pipe, remove gear train, check operation of main spindle, remove excess grease and lubricate where applicable. Clean strainer and orifice points on local and brigade alarms, clear water jet, flush drain, renew gasket, check operation of main spindle and striker, remove excess grease and lubricate where applicable. Renew water supply check valve seatings and gaskets, check seating and spindle. Remove and clean strainer and check operation of retard chamber, drain pipe and orifice points. Check recording gauges against a known tested gauge. Overhaul in accordance with the supplier s specifications all pressure reducing valves, deluge valves, tail-end dry pipe valves and any other special valves that may be installed. 4.2 Additional Requirement where Automatic Pumps are Installed. Replace booster pump gland packing to manufacturer s requirements and clean gland drain. Check pump coupling alignment and coupling. Compression ignition engine driven pumps: (REFER SECTION B: CLIENT S RESPONSIBILITIES CLAUSE 4 & 5) (i) (ii) (iii) (iv) Service pump motor in accordance with manufacturer s specifications. Flush cooling system to motor. Replace oil, fuel and air filters. Replace lead acid control and starter batteries. Clean valves, repaint if necessary and remove unnecessary equipment/rubbish from valve room. FPS4 APPENDIX A (Int.) FOR USE BY

6 FPS4: Appendix A (Int.) Page Additional Requirements where Water Supply Tanks are Installed. Inspect, internally and externally, for freedom from corrosion and internal accumulation of foreign matter including strainers and foot valves where fitted. NOTE: While this has normally required draining of the tank, it is recognised that there may be other means of complying with this requirement. For pump priming tanks inspect internally and externally for freedom from corrosion and internal accumulation of foreign matter. NOTE: Client is responsible for ascertaining structural integrity of water supply and priming tanks. 4.4 Fire Brigade Booster Coupling Check Operation of Fire Brigade booster coupling. 4.5 Anti-freeze Systems Drain tail-end anti-freeze systems including individual sprinkler heads on droppers and refill with new solution. 4.6 Recommissioning Recommission system ensuring that all valves are in the operational position and that the system is operational. 4.7 Maintenance Log Record three-yearly overhaul and maintenance in log book. LEVEL 5 ROUTINE 6 Yearly Level 5 Routine consists of levels 1, 2, 3 and 4 routines in addition to: For sprinkler heads 24 years or older remove a representative sample of not less than 10 sprinkler heads from each control valve installation and replace with new sprinkler head. Inspect, pressure test and test for operating characteristics of the sample sprinkler heads and submit report to client. For high temperature sprinkler heads 24 years or older with a nominal temperature rating exceeding 182 o C all sprinkler heads should be replaced SECTION B CLIENT S RESPONSIBILITIES It is required that the client assume the following responsibility and involvement to enable compliance with AS1851.3: Maintenance of Fire Protection Equipment (Part 3: Automatic fire sprinkler systems). 1 Drainage The client is to ensure that all floor, waste and test drains and the like are kept clear of obstructions and are of adequate capacity to discharge water under all conditions (refer Items Level 1 routine; 2.1 and Level 2 routine; 3.1(iv) and (iii) - Level 3 routine; 4.2(ii), 4.3 and, 4.4 and Level 4 routine. /cont. FPS4 APPENDIX A FOR USE BY

7 FPS4: Appendix A (Int.) Page 7 2 Spray Booths The client is to frequently clean all sprinkler heads installed in spray booths and connected exhaust ducts - ensuring that all accumulated spraying residues are removed and that all protective coatings such as petroleum jellies are in satisfactory condition (refer Item Level 2 routine). NOTE: The frequency of cleaning and re-coating of the sprinklers is dependent upon the amount of spraying and should be carried out on a once or twice weekly basis (but not less than quarterly) - during cleaning of the booth, exhaust ducting and motors (as may be required under spray-painting regulations). 3 Deep Fat Fryers / Exhaust Ducting Client to clean all sprinkler heads, in and over deep fat fryers / exhaust ducting. Sprinklers should be cleaned at the same time intervals as duct cleaning. (Refer Item 3.4) 4 Pumps Compression engines shall be overhauled in accordance with the manufacturer s requirements and any items showing signs of wear or corrosion should be immediately repaired or replaced. This overhaul and any subsequent repairs or replacements shall be subject to a separate quotation by the contractor and authority by the client. (refer Item Level 4 Routine). 5 Batteries The contractor will replace lead acid control and starter batteries during the Level 4 Routine (ie. three yearly) where necessary. If a battery requires replacement prior to or after the Level 4 Routine becomes due, this shall be subject to a separate quotation by the contractor and authority by the client (refer Item Level 4 Routine). 6 Pump, Valve and Tank Rooms The client is to maintain all pumps, valve and tank rooms in a clean condition and clear of obstruction (refer Item Level 4 Routine). 7 Remote Control Functions Where initiation facilities to operate control functions (such as smoke exhausts, stair pressurisation fans, air conditioning shut-down, automatic door closers, etc.) are installed - it shall be the client s responsibility to co-ordinate these tests and provide qualified personnel to be in attendance to reset such services (refer Item 1.2 Level 1 Routine). 8 Inspections The client is to arrange an examination of the exposed water distribution system including pipework, pipe supports, sprinklers, valves and heat collectors. Where corrosion, rusting, lack of supports or other damage is indicated, a more extensive examination of the distribution system shall be carried out, viz check within ceiling and floor spaces and ducts. Clean and rectify defects as required. Fit new sprinklers in place of sprinklers corroded or contaminated by paint. The costs of this examination and subsequent repairs or replacements shall be subject to a separate quotation by the contractor and authority by the client. /cont. FPS4 APPENDIX A (Int.) FOR USE BY

8 FPS4: Appendix A (Int.) Page 8 9 Alterations Whenever alterations, change of occupancy/storage/processes or rearrangement of premises is contemplated, the Client shall seek the advice of the Contractor as to the effect such alteration(s) may have on the sprinkler installation(s). 10 Special Quarterly Testing. At remote locations where it is not practicable for the Contractor to provide a weekly test, the Contractor shall not be obligated to do so. In such instances the Level 1 routine should be carried out by a nominated Representative of the Client after receiving instructions from the Contractor. Not withstanding this arrangement, the Contractor shall at quarterly intervals carry out full combined Levels 1 and 2 routines. Such testing to be known as Special Quarterly Testing and the Agreement shall be endorsed accordingly. 11 Notification The Fire Alarm Monitoring Station and Insurers shall be notified when any portion of the system is isolated for maintenance and likewise when this portion is reconnected. Where required by a relevant authority a copy of the Inspection and Testing Agreement contract form shall be filed with that Authority. The Authority shall be notified in the event that the contract is cancelled or lapses. Certification of compliance to maintenance standards when required by various authorities to be arranged by client. This Contract Document Is Copyright 2000 Fire Protection Association Australia ABN For questions concerning the application and use of this document please consult your legal advisor. All questions on reproduction of the document should be addressed to the association s national office at PO Box 1049, Box Hill, Vic, 3128 FPS4 APPENDIX A FOR USE BY

Important Ontario Fire Code Information for Building Owners in the City of Windsor

Important Ontario Fire Code Information for Building Owners in the City of Windsor Important Ontario Fire Code Information for Building Owners in the City of Windsor This information is intended to be used a reference only. For a complete listing consult the Ontario Fire Code or contact

More information

ALBERTA FIRE CODE SAFETY EQUIPMENT MAINTENANCE REQUIREMENTS

ALBERTA FIRE CODE SAFETY EQUIPMENT MAINTENANCE REQUIREMENTS ALBERTA FIRE CODE SAFETY EQUIPMENT MAINTENANCE REQUIREMENTS In this document are the fire safety equipment maintenance requirements that are found in Division B of the Alberta Fire Code (AFC 2006) for

More information

Winnipeg Fire Department Fire Prevention Branch

Winnipeg Fire Department Fire Prevention Branch Winnipeg Fire Department Fire Prevention Branch Manitoba Fire Code Life-Safety Equipment Maintenance Requirements The Fire Prevention Branch of the Winnipeg Fire Department has prepared this document of

More information

Model: 400E-2M. Bermad Electrically Controlled Deluge Valve with Easy Lock Manual Reset. Installation Operation Maintenance. Application Engineering

Model: 400E-2M. Bermad Electrically Controlled Deluge Valve with Easy Lock Manual Reset. Installation Operation Maintenance. Application Engineering Model: 400E-2M Bermad Electrically Controlled Deluge Valve with Easy Lock Manual Reset Installation Operation Maintenance Application Engineering BERMAD 1. Safety First BERMAD believes that the safety

More information

BERMAD Fire Protection

BERMAD Fire Protection Model: 400E-2M BERMAD Electrically Controlled Deluge Valve with Easy Lock Manual Reset Installation Operation Maintenance Safety First BERMAD believes that the safety of personnel working with and around

More information

SPECIFICATION TECHNICAL AIR-CONDITIONING UNITS SINGLE AND SPLIT (DUCTED) (AIR COOLED PACKAGED UNIT)

SPECIFICATION TECHNICAL AIR-CONDITIONING UNITS SINGLE AND SPLIT (DUCTED) (AIR COOLED PACKAGED UNIT) SPECIFICATION TECHNICAL AIR-CONDITIONING UNITS SINGLE AND SPLIT (DUCTED) (AIR COOLED PACKAGED UNIT) MAINTENANCE TYPE: STATUTORY 1.0 SCOPE OF SERVICES The Contractor shall provide maintenance Services for

More information

Competency Framework for Marine Engineer Class 6. Competency Framework for Marine Engineer Class 6

Competency Framework for Marine Engineer Class 6. Competency Framework for Marine Engineer Class 6 Table of Contents (MEC 6)... 1 Function: Operate Vessel Machinery and Systems... 1 Diesel engines.... 1 Operational procedures.... 3 Operate and monitor a vessel s engines and auxiliary equipment.... 4

More information

INSPECTION AND TESTING OF EMERGENCY GENERATORS

INSPECTION AND TESTING OF EMERGENCY GENERATORS INSPECTION AND TESTING OF EMERGENCY GENERATORS Certification requirements NFPA 101(00), Sec. 7.9.2.3 requires that emergency generators be installed, tested and maintained in accordance with NFPA 110,

More information

Fire Alarm System Monitoring - CAN/ULC-S561-03

Fire Alarm System Monitoring - CAN/ULC-S561-03 Fire Alarm System Monitoring - CAN/ULC-S561-03 Brian McBain ULC Regulatory Services May 4, 2011 Copyright 1995-2007 Underwriters' Laboratories of Canada. All rights reserved. No portion of this material

More information

BERMAD Fire Protection

BERMAD Fire Protection 400E-2M/700E-2M IOM Bermad Electrically Controlled Deluge Valve with EasyLock Manual Reset Model: 400E-2M/700E-2M INSTALLATION OPERATION MAINTENANCE Application Engineering BERMAD 400E-2M/700E-2M Bermad

More information

ELECTRIC/DIESEL FIRE PUMP CHECK LIST

ELECTRIC/DIESEL FIRE PUMP CHECK LIST BUILDING NAME: DESIGNER: SCO REPRESENTATIVE: PUMP MANUF.: LOCATION: INSTALLER: DATE: OWNER NAME: INSTALLATION Certificate for flushing and hydrostatic test furnished Piping been hydrostatically tested

More information

Fire Pump Plan Review March 2010

Fire Pump Plan Review March 2010 Fire Pump Plan Review March 2010 Date of Review: / / Permit Number: Business/Building Name: Address of Project: Designer Name: Designer s Phone: Contractor: Contractor s Phone: Occupancy Classification:

More information

BUILDING OWNERS - SERVICE RELATED ISSUES FOR FIRE ALARM SYSTEMS

BUILDING OWNERS - SERVICE RELATED ISSUES FOR FIRE ALARM SYSTEMS BUILDING OWNERS - SERVICE RELATED ISSUES FOR FIRE ALARM SYSTEMS Owners have numerous responsibilities as it pertains to the maintenance and operation of a building s fire safety equipment. The liabilities

More information

Maintaining Fire Protection Systems

Maintaining Fire Protection Systems Maintaining Fire Protection Systems Fire continues to be a major threat to your business and your personal safety. Each year several thousand people are injured or killed by fires and billions of dollars

More information

INSPECTION, TESTING AND MAINTENANCE OF FIRE PROTECTION SYSTEMS AND EQUIPMENT

INSPECTION, TESTING AND MAINTENANCE OF FIRE PROTECTION SYSTEMS AND EQUIPMENT CITY OF SPRING LAKE PARK Code Enforcement Department 1301 81 st Avenue NE Spring Lake Park MN 55432 Business Phone 763-784-6491 Fax 763-792-7257 INSPECTION, TESTING AND MAINTENANCE OF FIRE PROTECTION SYSTEMS

More information

Risk Control Bulletin Inspection, Testing & Maintenance (ITM) of Water-Based Fire Protection Systems

Risk Control Bulletin Inspection, Testing & Maintenance (ITM) of Water-Based Fire Protection Systems Risk Control Bulletin Inspection, Testing & Maintenance (ITM) of Water-Based Fire Protection Systems Introduction Fire protection systems are provided in or at a building to safeguard the lives of building

More information

ENGINE COOLING SYSTEM

ENGINE COOLING SYSTEM ENGINE COOLING SYSTEM 1988 Toyota Celica 1987-88 TOYOTA Engine Cooling Systems Celica DESCRIPTION The basic liquid cooling system consists of a radiator, water pump, thermostat, cooling fan, pressure cap,

More information

EXHIBIT A SCOPE OF WORK

EXHIBIT A SCOPE OF WORK EXHIBIT A SCOPE OF WORK 1. (Contractor) shall provide fire alarm system maintenance/repair/testing services as described herein to the California Department of Veterans Affairs (hereinafter CDVA, CalVet,

More information

MAINTENANCE AND SERVICE OF AUTOMATIC FIRE EXTINGUISHING SYSTEMS

MAINTENANCE AND SERVICE OF AUTOMATIC FIRE EXTINGUISHING SYSTEMS FIRE DEPARTMENT Bureau of Fire Protection and Life Safety www.cityofsanmateo.org 1900 O Farrell, Suite 140 San Mateo, CA 94403-1332 (650) 522-7940 FAX: (650) 522-7941 TDD: (650) 522-7047 MAINTENANCE AND

More information

Evaluate, Clean, and Tune Guidance

Evaluate, Clean, and Tune Guidance Evaluate, Clean, and Tune Guidance The Evaluate, Clean and Tune (ECT) process serves three essential purposes in the Weatherization Assistance Program (WAP). The first is to evaluate the existing system

More information

CDS TROUBLESHOOTING SECTION I. VACUUM. 1.0. Weak vacuum at wand. Gauge reads normal (10hg to 14hg)

CDS TROUBLESHOOTING SECTION I. VACUUM. 1.0. Weak vacuum at wand. Gauge reads normal (10hg to 14hg) CDS TROUBLESHOOTING SECTION I. VACUUM 1.0. Weak vacuum at wand. Gauge reads normal (10hg to 14hg) 1.1. Clogged hoses or wand tube. Disconnect hoses and carefully check for an obstruction. 1.2. Excessive

More information

Oil and Coolant Circulating Heating System. Model - OCSM

Oil and Coolant Circulating Heating System. Model - OCSM Oil and Coolant Circulating Heating System Model - OCSM Installation & Operation Manual 216280-000 REV 2 Identifying Your System The HOTSTART heating system is designed to heat fluids for use in marine

More information

Fire Alarm System Standpipes Sprinkler Systems Fire Drills Commercial Cooking Hood and more

Fire Alarm System Standpipes Sprinkler Systems Fire Drills Commercial Cooking Hood and more FIRE PROTECTION SYSTEMS Fire protection systems, measures and equipment are all related to the safety of the occupants and the protection of the property. As part of a building design and its intended

More information

Inspection and Testing of Water-Based Systems

Inspection and Testing of Water-Based Systems Inspection and Testing of Water-Based Systems Standard Model/Computer-Based Testing Level III Content Outline The candidate for NICET certification at Level III in the Inspection and Testing of Water-Based

More information

INSTRUCTIONS FOR BUILDINGS WITH FIRE PROTECTION EQUIPMENT

INSTRUCTIONS FOR BUILDINGS WITH FIRE PROTECTION EQUIPMENT INSTRUCTIONS FOR BUILDINGS WITH FIRE PROTECTION EQUIPMENT FIRE EXTINGUISHERS,SPRINKLER SYSTEMS AND FIRE ALARMS Attachment #1 Inspection of Fire Extinguishers Fire Extinguishers must be tested according

More information

Consortiwm Awdurdodau Lleol Cymru Consortium Local Authorities Wales

Consortiwm Awdurdodau Lleol Cymru Consortium Local Authorities Wales Consortiwm Awdurdodau Lleol Cymru Consortium Local Authorities Wales SPECIFICATION FOR LAUNDRY EQUIPMENT MAINTENANCE Maintenance Module 32 March 2011 issue This document has been compiled by the Engineering

More information

COMMISSIONING OF HVAC SYSTEMS

COMMISSIONING OF HVAC SYSTEMS FORM CL-01 SYSTEMS / EQUIPMENT INCLUDED : SYSTEM STARTUP CHECKLIST I - PRE - STARTUP INSPECTION EQUIPMENT MOUNTING & SETTING CONTROL, INTERLOCK & POWER WIRING ALIGNMENT OF MOTORS & DRIVES PIPING, CONNECTIONS

More information

MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION

MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION Fire Pump Plan Review 2009 International Fire Code and NFPA 20 Date of Review / / BLD201 - Project Address: Project Name: Contractor s Business

More information

26 3213.13 Diesel Engine Driven Generators Page 1 of 6

26 3213.13 Diesel Engine Driven Generators Page 1 of 6 Last Update: December 8, 2014 A. Description of System Consultant s Handbook Page 1 of 6 1. Provide a diesel engine driven electric generating unit, factory assembled, tested and certified to operate at

More information

32:(5#5$7,1* 4833#USP283#+] 4;33#USP293#+] 3ULPH 113 kva, 90 kw 124 kva, 99 kw 6WDQGE\ 114 kva, 91 kw 125 kva, 100 kw

32:(5#5$7,1* 4833#USP283#+] 4;33#USP293#+] 3ULPH 113 kva, 90 kw 124 kva, 99 kw 6WDQGE\ 114 kva, 91 kw 125 kva, 100 kw ,1'8675,$/#*(16(7 6HULHV#'9#448 32:(5#5$7,1* 4833#USP283#+] 4;33#USP293#+] 3ULPH 113 kva, 90 kw 124 kva, 99 kw 6WDQGE\ 114 kva, 91 kw 125 kva, 100 kw Generator set consisting of engine and alternator mounted

More information

SPECIAL CLAUSES/WARRANTIES THESE ARE OPERATIVE ONLY IF SHOWN IN THE SCHEDULE OR IN AN ENDORSEMENTFORMING PART OF THE SCHEDULE

SPECIAL CLAUSES/WARRANTIES THESE ARE OPERATIVE ONLY IF SHOWN IN THE SCHEDULE OR IN AN ENDORSEMENTFORMING PART OF THE SCHEDULE SPECIAL CLAUSES/WARRANTIES THESE ARE OPERATIVE ONLY IF SHOWN IN THE SCHEDULE OR IN AN ENDORSEMENTFORMING PART OF THE SCHEDULE CL2 - Pipe and Tank Lagging Warranty Underwriters will not be liable for loss

More information

Depending on your facility and the equipment contained within, all or part of the checklists/logs can be printed for use.

Depending on your facility and the equipment contained within, all or part of the checklists/logs can be printed for use. Large Facility Fire Safety Checklists and Logs This package contains checklists to ensure that all fire and life safety equipment are properly inspected. There are also logs on which to record the inspections

More information

PUMP MAINTENANCE SCHEDULE AND CHECKLISTS

PUMP MAINTENANCE SCHEDULE AND CHECKLISTS PUMP MAINTENANCE SCHEDULE AND CHECKLISTS Providing a maintenance schedule defined specifically by run hours or yardage pumped serves only as a general guideline given the large amount of variables a unit

More information

SELF-INSPECTION PROGRAM FOR FIRE PROTECTION EQUIPMENT

SELF-INSPECTION PROGRAM FOR FIRE PROTECTION EQUIPMENT SELF-INSPECTION PROGRAM FOR FIRE PROTECTION EQUIPMENT INTRODUCTION No matter how reliable fire protection equipment may seem, periodic maintenance is needed to ensure proper operation. Fire protection

More information

ISLE OF MAN FIRE & RESCUE SERVICE FIRE PRECAUTIONS LOGBOOK. Website www.iomfire.com

ISLE OF MAN FIRE & RESCUE SERVICE FIRE PRECAUTIONS LOGBOOK. Website www.iomfire.com ISLE OF MAN FIRE & RESCUE SERVICE FIRE PRECAUTIONS LOGBOOK Website www.iomfire.com ADDRESS OF PREMISES FIRE CERTIFICATE No. (where applicable).. LOCATION OF LOG BOOK. CONTENTS OF LOG BOOK Useful telephone

More information

3620 W 11th Streetб Houston, TX 77008 Telephone: 713-635-6291 Email: sales@kellogg-american.com Website: www.kellogg-american.com

3620 W 11th Streetб Houston, TX 77008 Telephone: 713-635-6291 Email: sales@kellogg-american.com Website: www.kellogg-american.com Unpackaging & Handling Be sure to carefully inspect the unit before accepting the shipment. If any damage has occurred document it with the trucking company immediately. Contact your Kellogg Distributor

More information

Maintenance Report MEDIUM VOLTAGE POWER STATION 500SC / 630SC / 800SC / 900SC / 1000 1SC / 1000 2SC / 1250SC / 1600SC / 1800SC / 2000SC

Maintenance Report MEDIUM VOLTAGE POWER STATION 500SC / 630SC / 800SC / 900SC / 1000 1SC / 1000 2SC / 1250SC / 1600SC / 1800SC / 2000SC Maintenance Report MEDIUM VOLTAGE POWER STATION 500SC / 630SC / 800SC / 900SC / 1000 1SC / 1000 2SC / 1250SC / 1600SC / 1800SC / 2000SC Project name: Customer: Address, location of the system: Serial number

More information

National Competency Based Skill Training Refrigeration and Air-conditioning Mechanic Logbook

National Competency Based Skill Training Refrigeration and Air-conditioning Mechanic Logbook National Competency Based Skill Training Refrigeration and Air-conditioning Mechanic Logbook Trainee:... Training Provider:... Year:... Trainee Contact no:... Competency Based Skill Training Logbook Introduction

More information

REFRIGERATION & AIR-CONDITIONING UNIT IIT KHARAGPUR

REFRIGERATION & AIR-CONDITIONING UNIT IIT KHARAGPUR REFRIGERATION & AIR-CONDITIONING UNIT IIT KHARAGPUR Sub.: Day-to-Day operation contract & maintenance for 2 X 40 TR &1 X 20 TR DX type Central AC Plant of Netaji Auditorium of IIT Kharagpur Ref.: IIT/RAC/Netaji/OC

More information

Fire Safety Log Book. Premises Name: Premises Address: Date From: Date To: Location of Log Book:

Fire Safety Log Book. Premises Name: Premises Address: Date From: Date To: Location of Log Book: Fire Safety Log Book Premises Name: Premises Address: Date From: Date To: Location of Log Book: CONTENTS PART 1 FIRE SAFETY ADVICE 1 PART 2 FIRE PRECAUTIONS 2 Section 1 Guidance on Fire Risks and Preventative

More information

Heating, Ventilation, Air Conditioning and Refrigeration (HVACR)

Heating, Ventilation, Air Conditioning and Refrigeration (HVACR) Heating, Ventilation, Air Conditioning and Refrigeration (HVACR) I. Demonstrate safety skills in typical HVACR work situations to NATE Core Installer Knowledge Areas for Technician Excellence for Safety

More information

Chapter 7 Hydraulic System Troubleshooting

Chapter 7 Hydraulic System Troubleshooting Chapter 7 Hydraulic System Troubleshooting General The following troubleshooting information is provided as a general guide to identify, locate and correct problems that may be experienced with the hydraulic

More information

FIVE YEAR CERTIFICATION REPORT

FIVE YEAR CERTIFICATION REPORT GARDEN GROVE FIRE DEPARTMENT FIRE PREVENTION DIVISION FIVE YEAR CERTIFICATION REPORT Service and maintenance report of automatic fire extinguishing systems, including fire sprinklers, dry, deluge, and

More information

Restaurant & café guide

Restaurant & café guide 'Helping our customers stay in business by reducing risk' NZI Risk Solutions TM About NZI Risk Solutions NZI has extensive experience in providing expert risk management advice to help our commercial customers

More information

WALLACE MAXIPUMP 3000, 5000, 6000 and HYDROJET 30P, 30C AND HJ400 INSTALLATION AND MAINTENANCE INSTRUCTIONS

WALLACE MAXIPUMP 3000, 5000, 6000 and HYDROJET 30P, 30C AND HJ400 INSTALLATION AND MAINTENANCE INSTRUCTIONS 1 WALLACE MAXIPUMP 3000, 5000, 6000 and HYDROJET 30P, 30C AND HJ400 INSTALLATION AND MAINTENANCE INSTRUCTIONS Please read and follow all these instructions carefully before proceeding with the installation,

More information

Fire Sprinkler System Maintenance and Testing Page 1 MAINTENANCE AND TESTING OF FIRE SPRINKLER SYSTEMS

Fire Sprinkler System Maintenance and Testing Page 1 MAINTENANCE AND TESTING OF FIRE SPRINKLER SYSTEMS Page 1 MAINTENANCE AND TESTING OF FIRE SPRINKLER SYSTEMS Introduction When properly installed and maintained, automatic fire sprinkler systems have proven to be the most effective means for protecting

More information

Mechanical Installation

Mechanical Installation Page -1-1. INTRODUCTION AND PURPOSE 1.1. This specification covers the installation, testing and precommissioning of mechanical equipment. Work is to be performed in conjunction with the manufacturer s

More information

DELAWARE STATE FIRE MARSHAL FIRE ALARM SYSTEM CERTIFICATE OF INSTALLATION

DELAWARE STATE FIRE MARSHAL FIRE ALARM SYSTEM CERTIFICATE OF INSTALLATION Phone System Owner Phone System Engineered by: of Record Drawings: of System Manuals: of Test Reports: System Installer 1. GENERAL INFORMATION Phone Delaware License No: Certificate Holder No. System Supplier

More information

Bradlee Boilers Ltd. Instruction Manual for starting up Bradlee Hire Boiler from Cold

Bradlee Boilers Ltd. Instruction Manual for starting up Bradlee Hire Boiler from Cold Bradlee Boilers Ltd Instruction Manual for starting up Bradlee Hire Boiler from Cold To be read in conjunction with Bradlee Boiler guide to Commissioning Boilers Document Ref: HM001 1. Ensure that all

More information

NFPA 25 FAQs. 1. When inspecting an old system (60 years or older), when/where does NFPA 25 require a system to be upgraded to present standards?

NFPA 25 FAQs. 1. When inspecting an old system (60 years or older), when/where does NFPA 25 require a system to be upgraded to present standards? NFPA 25 FAQs Responses to FAQs are prepared by NFPA technical staff to assist users in reading and understanding NFPA codes and standards. The responses, however, are not Formal Interpretations issued

More information

Section 6 Fire Detection and Alarm Systems Russell Porteous Chief Executive Officer Firewize Services

Section 6 Fire Detection and Alarm Systems Russell Porteous Chief Executive Officer Firewize Services Section 6 Fire Detection and Alarm Systems Russell Porteous Chief Executive Officer Firewize Services General Information Section 6 of AS1851-2012 covers: Fire Detection and Alarms Systems Electrical Detection

More information

HVAC Checklist - Long Form

HVAC Checklist - Long Form HVAC Checklist - Long Form Page 1 of 14 Appendix B discusses HVAC system components in relation to indoor air quality. utside Air Intake Location pen during occupied hours? Unobstructed? Standing water,

More information

COMMERCIAL REPORT / STOCK CONDITION SURVEY. Sydenham Hill Estate Sydenham Hill London SE 23

COMMERCIAL REPORT / STOCK CONDITION SURVEY. Sydenham Hill Estate Sydenham Hill London SE 23 COMMERCIAL REPORT / STOCK CONDITION SURVEY For Sydenham Hill Estate Sydenham Hill London SE 23 Submission Prepared by Gas Advisory Services Limited Date: 4 th June 2013 Gas Advisory Services Limited Phoenix

More information

DLW 8. POWER RATING 1500 rpm/50 Hz 1800 rpm/60 Hz Prime 7.5 kva, 6 kw 9.1 kva, 7.3 kw Standby 8.5 kva, 6.8 kw 10.1 kva, 8.1 kw

DLW 8. POWER RATING 1500 rpm/50 Hz 1800 rpm/60 Hz Prime 7.5 kva, 6 kw 9.1 kva, 7.3 kw Standby 8.5 kva, 6.8 kw 10.1 kva, 8.1 kw DLW 8 POWER RATING 1500 rpm/50 Hz 1800 rpm/60 Hz Prime 7.5 kva, 6 kw 9.1 kva, 7.3 kw Standby 8.5 kva, 6.8 kw 10.1 kva, 8.1 kw Generator set consisting of engine and alternator mounted on a fabricated steel

More information

Diameter 3" 4" 6" 8" Flange type PN 16 PN 16 PN 16 PN 16. Orange-red ( RAL 2002) Height (cm) 27,70 26,30 28,70 29.70

Diameter 3 4 6 8 Flange type PN 16 PN 16 PN 16 PN 16. Orange-red ( RAL 2002) Height (cm) 27,70 26,30 28,70 29.70 Description Usually, a wet alarm valve station comprise: a Rolland wet alarm valve linked to the water motor gong. a set of valves and by pass used to test the system. a drain valve. a test valve gauges

More information

Restaurant and Café Risk Management Guide. Don t Risk It!

Restaurant and Café Risk Management Guide. Don t Risk It! property & liability Restaurant and Café Risk Management Guide Don t Risk It! About Lumley Insurance Lumley Insurance has extensive experience in restaurant insurance and risk management. This experience

More information

SOLAR PV SYSTEM MAINTENANCE GUIDE

SOLAR PV SYSTEM MAINTENANCE GUIDE SOLAR PV SYSTEM MAINTENANCE GUIDE GUYANA HINTERLANDS STAND-ALONE SOLAR PV INSTALLATIONS IMPROVING HEALTH FACILITY INFRASTRUCTURE (IHFI) GUYANA CONTRACT NO. EPP-I-00-03-00008-00, TASK ORDER 07 APRIL 2013

More information

Operating instructions

Operating instructions 6300 9681 02/2006 GB For the user Operating instructions Logano GE315 Boiler for oil-/gas-fired pressure jet burners Please read thoroughly before use. Operating instructions Logano GE315 Dear Customer,

More information

PLAN SUBMITTAL REQUIREMENTS FOR SPRAY BOOTHS AND SPRAYING ROOMS EXTINGUISHING SYSTEMS

PLAN SUBMITTAL REQUIREMENTS FOR SPRAY BOOTHS AND SPRAYING ROOMS EXTINGUISHING SYSTEMS January 1997 PLAN SUBMITTAL REQUIREMENTS FOR SPRAY BOOTHS AND SPRAYING ROOMS EXTINGUISHING SYSTEMS 1.0 PERMIT 1.1 After receipt of a Building Permit from the City of San Jose Building Department, submit

More information

Air Conditioning Equipment

Air Conditioning Equipment 1. PURPOSE OF THIS DOCUMENT This document has been written to assist DCC Premises Managers in obtaining quotations for the ongoing servicing and maintenance of where fitted to their premises. Specialist

More information

The State Fire Marshal's Office and the VDH/Office of Licensure and Certification. Generator Testing in Nursing Facilities

The State Fire Marshal's Office and the VDH/Office of Licensure and Certification. Generator Testing in Nursing Facilities Generator Testing in Nursing Facilities Introduction Recent emergencies and natural disasters have emphasized the need to ensure that nursing facilities have an adequate EPSS in place should the loss of

More information

PC1131 Electric Air Compressor

PC1131 Electric Air Compressor Senco Products Inc. 8485 Broadwell Road Cincinnati, Ohio 45244 PC1131 Electric Air Compressor Operating Instructions 2006 by Senco Products, Inc. Warnings for the safe use of this tool are included in

More information

A.Y. McDonald Mfg. Co. Troubleshooting Submersible and Jet Pumps

A.Y. McDonald Mfg. Co. Troubleshooting Submersible and Jet Pumps A.Y. McDonald Mfg. Co. Troubleshooting Submersible and Jet Pumps Troubleshooting Submersible Pumps Fuse overload or circuit breaker trips when motor is started 1. Incorrect line voltage. Check the line

More information

3", 4", 6" & 8" Model H Series Alarm Check Valve Installation and Maintenance Guide

3, 4, 6 & 8 Model H Series Alarm Check Valve Installation and Maintenance Guide ", ", " & " Model H Series Alarm Check Valve Installation and Maintenance Guide 077 AIRPARK DRIVE STANDISH, MICHIGAN PHONE 99-- 00-2-0 FAX 99--92 www.globesprinkler.com OCTOBER 2 C- BULLETIN A.C.V.I.M.,

More information

Volkswagen Jetta, Golf, GTI 1999, 2000 2.8 Liter VR6 2V Engine Mechanical, Engine Code(s): AFP 17 Engine-Lubrication (Page GR-17)

Volkswagen Jetta, Golf, GTI 1999, 2000 2.8 Liter VR6 2V Engine Mechanical, Engine Code(s): AFP 17 Engine-Lubrication (Page GR-17) 17 Engine-Lubrication (Page GR-17) Lubrication system components, removing and installing Oil filter housing, disassembling and assembling Oil pan, removing and installing Oil pressure and oil pressure

More information

32:(5#5$7,1* 4833#USP283#+] 4;33#USP293#+] 3ULPH 10.4 kva, 8.3 kw 12.9 kva, 10.3 kw 6WDQGE\ 11.3 kva, 9 kw 14.4 kva, 11.5 kw

32:(5#5$7,1* 4833#USP283#+] 4;33#USP293#+] 3ULPH 10.4 kva, 8.3 kw 12.9 kva, 10.3 kw 6WDQGE\ 11.3 kva, 9 kw 14.4 kva, 11.5 kw ,QGXVWULDO#*HQHUDWRU 32:(5#5$7,1* 4833#USP283#+] 4;33#USP293#+] 3ULPH 10.4 kva, 8.3 kw 12.9 kva, 10.3 kw 6WDQGE\ 11.3 kva, 9 kw 14.4 kva, 11.5 kw Generator set consisting of engine and alternator mounted

More information

INSPECTION AND TESTING OF FIRE ALARM SYSTEMS

INSPECTION AND TESTING OF FIRE ALARM SYSTEMS Page 1 January 2, 2009 INSPECTION AND TESTING OF FIRE ALARM SYSTEMS Introduction Early warning plays a key role in a healthcare facility s ability to safely evacuate its residents during a fire emergency.

More information

Consortiwm Awdurdodau Lleol Cymru Consortium Local Authorities Wales

Consortiwm Awdurdodau Lleol Cymru Consortium Local Authorities Wales Consortiwm Awdurdodau Lleol Cymru Consortium Local Authorities Wales SPECIFICATION FOR BOILER SERVICING MAINTENANCE Maintenance Module 11 March 2012 issue This document has been compiled by the Engineering

More information

Wet alarm valves. Wet alarm valves. FM trim

Wet alarm valves. Wet alarm valves. FM trim Description Usually, a wet alarm valve station comprise: - a Rolland wet alarm valve linked to the water motor gong. - a set of valves and by pass used to test the system. - a drain valve. - a test valve

More information

Fire Safety Plan (Single-Stage Fire Alarm System - Small Establishment)

Fire Safety Plan (Single-Stage Fire Alarm System - Small Establishment) 1 Fire Safety Plan (Single-Stage Fire Alarm System - Small Establishment) Fire Safety Plan Single-Stage Fire Alarm System (small establishment) for: (Business Name) (Business Address) The reproduction

More information

Federal Wage System Job Grading Standards for Air Conditioning Equipment Operating, 5415. Table of Contents

Federal Wage System Job Grading Standards for Air Conditioning Equipment Operating, 5415. Table of Contents Federal Wage System Job Grading Standards for Air Conditioning Equipment Operating, 5415 Table of Contents WORK COVERED... 2 WORK NOT COVERED...2 TITLES... 2 GRADE LEVELS... 2 HELPER AND INTERMEDIATE JOBS...

More information

CARING FOR YOUR WATER HEATER

CARING FOR YOUR WATER HEATER http://waterheatertimer.org/troubleshoot-rheem-tankless-water-heater.html Water Heater Inspections CARING FOR YOUR WATER HEATER Venting System (Direct Vent Only) The venting system should be inspected

More information

Name Of Occupancy Date. Yes No Describe

Name Of Occupancy Date. Yes No Describe FIRE PREVENTION INSPECTION CHECKLIST For Class A Occupancy (For Assembly Buildings, Bars, Restaurants, Gyms, Churches, Arenas, Theatres or wherever people gather) Name Of Occupancy Date Physical Address

More information

Information Bulletin. Sprinkler System Component Fault Monitoring. Version 1.1 Approved for release September 2013

Information Bulletin. Sprinkler System Component Fault Monitoring. Version 1.1 Approved for release September 2013 Version 1.1 Approved for release September 2013 Table of contents 1.0 Purpose Statement... 3 2.0 Audience... 3 3.0 Why is sprinkler system component fault monitoring important?... 3 4.0 Communication of

More information

Hydraulic Trouble Shooting

Hydraulic Trouble Shooting Hydraulic Trouble Shooting Hydraulic systems can be very simple, such as a hand pump pumping up a small hydraulic jack, or very complex, with several pumps, complex valving, accumulators, and many cylinders

More information

Attachment J-C18.1. HVAC Work Instructions

Attachment J-C18.1. HVAC Work Instructions . RFP: Attachment J-C18.1 HVAC Work Instructions NNC13ZFD017J SOW Item No. Title Page C18-02 Control Air Systems Annual PM 2 C18-03 Split System AC Indoor Section Annual PM 3 C18-04 Condensing Unit Semi-Annual

More information

Table Z. Troubleshooting Chart for Air Conditioners. Cause

Table Z. Troubleshooting Chart for Air Conditioners. Cause Troubleshooting Chart for Air Conditioners Type of Unit Complaint Cause With open-type compressor Electric motor will not start Power failure Check circuit for power source Compressor stuck Locate cause

More information

Table V. Troubleshooting Checklist for Refrigeration Systems. Air or non-condensable gas in system. Inlet water warm.

Table V. Troubleshooting Checklist for Refrigeration Systems. Air or non-condensable gas in system. Inlet water warm. Table V Troubleshooting Checklist for Refrigeration Systems TROUBLE POSSIBLE CAUSE CORRECTIVE MEASURE High condensing pressure. Low condensing pressure. Air or non-condensable gas in system. Inlet water

More information

Boiler and Burner Cleaning and Servicing Specifications

Boiler and Burner Cleaning and Servicing Specifications Boiler and Burner Cleaning and Servicing Specifications The Town of Groton of Public Works Department is requesting bids to provide manufacturers recommended maintenance, repairs and emergency service

More information

A Guide to Trouble-Free Cooling Towers

A Guide to Trouble-Free Cooling Towers A Guide to Trouble-Free Cooling Towers A basic understanding of cooling tower operation and maintenance will help keep a cooling water system running in top condition, year after year By David M. Suptic

More information

SECTION 23 00 01 HEATING, VENTILATION AND AIR CONDITIONING EQUIPMENT

SECTION 23 00 01 HEATING, VENTILATION AND AIR CONDITIONING EQUIPMENT SECTION 23 00 01 HEATING, VENTILATION AND AIR CONDITIONING EQUIPMENT PART 1 - GENERAL 1.1 DESCRIPTION A. The Work specified in this Section consists of designing, furnishing and installing factory-assembled

More information

PC1130 Electric Air Compressor

PC1130 Electric Air Compressor Senco Products Inc. 8485 Broadwell Road Cincinnati, Ohio 45244 PC1130 Electric Air Compressor Operating Instructions 2006 by Senco Products, Inc. Warnings for the safe use of this tool are included in

More information

VOLVO PENTA DIESEL AND GASOLINE ENGINES LAYING-UP AND LAUNCHING GUIDE

VOLVO PENTA DIESEL AND GASOLINE ENGINES LAYING-UP AND LAUNCHING GUIDE VOLVO PENTA DIESEL AND GASOLINE ENGINES LAYING-UP AND LAUNCHING GUIDE TIME WELL INVESTED This guide covers most of the items to be checked and seen to on your engine and drive when laying up and launching.

More information

USER S, MAINTENANCE and SERVICE INFORMATION MANUAL

USER S, MAINTENANCE and SERVICE INFORMATION MANUAL CONTENTS SAFETY INFORMATION................ 2 FOR YOUR SAFETY....................... 2 SYSTEM OPERATION.................. 2 THERMOSTATS........................... 2 INTERMITTENT IGNITION DEVICE...........

More information

Ontario Fire Code SECTION 5.13 DIP TANKS. Illustrated Commentary. Office of the Ontario Fire Marshal

Ontario Fire Code SECTION 5.13 DIP TANKS. Illustrated Commentary. Office of the Ontario Fire Marshal Ontario Fire Code SECTION 5.13 DIP TANKS Illustrated Commentary Office of the Ontario Fire Marshal Dip Tanks Illustrated Commentary 1 5.13.1. Location 5.13.1.1. Dip tank operations involving flammable

More information

Trouble Shooting. Pump

Trouble Shooting. Pump Trouble Shooting Pump Trouble Possible Cause Remedy Oil leaking in the area of water pump crankshaft Worn crankshaft seal, bad bearing, grooved shaft, or failure of retainer o-ring. Excessive play on crankshaft

More information

FIRE SAFETY PRECAUTIONS

FIRE SAFETY PRECAUTIONS FIRE SAFETY PRECAUTIONS LOG BOOK PLEASE KEEP AVAILABLE 1 Business Name Premises Information Building / Unit Number Property Name Road: (Address Line 1) (Address Line 2) Locality: Town: Post Code: Name

More information

MAP KEYS GLOSSARY FOR THE DRAINAGE AND WATER REPORT

MAP KEYS GLOSSARY FOR THE DRAINAGE AND WATER REPORT Record MAP KEYS GLOSSARY FOR THE DRAINAGE AND WATER REPORT Abandoned Gravity Private Combined Gravity Private Foul Gravity Private Surface Water Gravity Public Combined Gravity Public Foul Gravity Public

More information

Fire Safety Plan (Single-Stage Fire Alarm System) (Small Establishment):

Fire Safety Plan (Single-Stage Fire Alarm System) (Small Establishment): Fire Safety Plan (Single-Stage Fire Alarm System) (Small Establishment): Fire Safety Plan Single-Stage Fire Alarm System for: (Business Name) (Business Address) Submission Date - Submitted by - Signature

More information

USF St. Petersburg Operations & Maintenance of Facilities Preventative Maintenance Guide

USF St. Petersburg Operations & Maintenance of Facilities Preventative Maintenance Guide USF St. Petersburg Operations & Maintenance of Facilities Preventative Maintenance Guide GUIDE EQUIPMENT TYPE & TASKS FREQUENCY A-1 Air Dryer 1. Lubricate valves and replace packing, if necessary 2. Check

More information

OPERATIONS & MAINTENANCE (O&M) FOR PROPANE STORAGE FACILITIES

OPERATIONS & MAINTENANCE (O&M) FOR PROPANE STORAGE FACILITIES OPERATIONS & MAINTENANCE (O&M) FOR PROPANE STORAGE FACILITIES Reference: National Fire Protection Association (NFPA) Pamphlet No. 58 Liquefied Petroleum Gas Code, 2001, Chapter 11 Type of Facility: Petroleum

More information

6.7L Diesel Fuel System Contamination Diagnosis and Service Procedure Job Aid (Revised March, 2012)

6.7L Diesel Fuel System Contamination Diagnosis and Service Procedure Job Aid (Revised March, 2012) 6.7L Diesel Fuel System Contamination Diagnosis and Service Procedure Job Aid (Revised March, 2012) Fuel contamination on 6.7L diesel engines can damage fuel system components including the High Pressure

More information

Automatic fire-extinguishing systems for commercial cooking

Automatic fire-extinguishing systems for commercial cooking Automatic fire-extinguishing systems for commercial cooking Leading Items First Ignited in Eating and Drinking Establishment Structure Fires, 2000-2004 Annual Averages Cooking materials, incl. food and

More information

D. Infrared scanning reports with pictures printed in a final report with any deficiencies and actions taken to rectify.

D. Infrared scanning reports with pictures printed in a final report with any deficiencies and actions taken to rectify. SECTION 263354 STATIC UPS TESTING AND COMMISSIONING PART 1 - GENERAL 1.1 SUMMARY A. Section Includes 1. System start-up services. 2. Battery charging. 3. Load bank testing. 4. Battery load testing. 5.

More information

Basic Hydraulics and Pneumatics

Basic Hydraulics and Pneumatics Basic Hydraulics and Pneumatics Module 1: Introduction to Pneumatics PREPARED BY IAT Curriculum Unit March 2011 Institute of Applied Technology, 2011 ATM 1122 Basic Hydraulics and Pneumatics Module 1:

More information

UDOT RPMS VEHICLE RECORDS, PREVENTIVE MAINTENANCE & SURVEILLANCE

UDOT RPMS VEHICLE RECORDS, PREVENTIVE MAINTENANCE & SURVEILLANCE UDOT RPMS VEHICLE RECORDS, PREVENTIVE MAINTENANCE & SURVEILLANCE VEHICLE RECORDS AND PREVENTIVE MAINTENANCE Prepared by: UTAH DEPARTMENT OF TRANSPORTATION OFFICE OF PLANNING AND PROGRAMMING IN COOPERATION

More information

KODAK VERSAMARK, INC.

KODAK VERSAMARK, INC. KODAK VERSAMARK, INC. PREPARED BY : Gary Rowland 6/6/06 Kodak Versamark, Inc. 3000 Research Blvd. Dayton, Ohio 45420 APPROVED BY : Fire Suppression System Inspection, Testing and Maintenance SHEET 1 OF

More information

SECTION 16721 FIRE ALARM AND DETECTION SYSTEM

SECTION 16721 FIRE ALARM AND DETECTION SYSTEM 1. GENERAL 1.1. Related Documents: 1.2. Scope: 1.1.1. The general provisions of the Contract, including General and Supplementary Conditions and General Requirements apply to the work specified in this

More information

FIRE SAFETY RECORD OF TESTS LOGBOOK

FIRE SAFETY RECORD OF TESTS LOGBOOK FIRE SAFETY RECORD OF TESTS LOGBOOK PREMISES ADDRESS: Responsible person AN INTRODUCTION TO YOUR LOG BOOK The Regulatory Reform (Fire Safety) Order 2005 requires the responsible person for a premises to

More information

Mechanical Engineering Technician- Plant Technician

Mechanical Engineering Technician- Plant Technician Mechanical Engineering Technician- Plant Technician A competent Mechanical Engineering Technician- Plant Maintenance is expected to: 1. Ability to plan and execute work in a safe and responsible manner

More information