1 SUMMARY REPORT A REVIEW OF FLARE AND VENT GAS EMISSIONS MONITORING AND REPORTING METHODS An Overview of Methods Used by Industry

2 The work described in this report was carried out by TUV SUD Ltd under contract to the Department for Business, Innovation & Skills ( the Department ) as part of the National Measurement Office s Engineering & Flow Programme. The Department has a free licence to copy, circulate and use the contents of this report within any United Kingdom Government Department, and to issue or copy the contents of the report to a supplier or potential supplier to the United Kingdom Government for a contract for the services of the Crown. For all other use, the prior written consent of TUV SUD Ltd shall be obtained before reproducing all or any part of this report. Applications for permission to publish should be made to: Contracts Manager NEL Scottish Enterprise Technology Park East Kilbride G75 0QF jduff@tuvnel.com Tel: +44 (0) TUV SUD Ltd 2013

3 NEL East Kilbride GLASGOW G75 0QF UK Tel: +44 (0) Fax: +44 (0) SUMMARY REPORT OF REVIEW OF FLARE AND VENT GAS EMISSIONS MONITORING AND REPORTING METHODS A Report for National Measurement Office Stanton Avenue Teddington TW11 0JZ Prepared by: Jeff Gibson Date: 6 June 2013 Approved by: Alick MacGillivray Date: 6 June 2013 for B Millington Director Project No: FHRE03 Page 1 of 26 June 2013

4 C O N T E N T S Page EXECUTIVE SUMMARY 3 1 INTRODUCTION 5 2 BACKGROUND Gas Flaring and Venting Processes Flare Gas and Vent Gas Composition Worldwide Flaring Statistics Flare Systems Reducing and Reusing the Gas Normally Flared 7 3 FLARE GAS REGULATION Flare and Vent Regulation 9 4 REGULATORY MEASUREMENT REQUIREMENTS FOR FLARING AND VENTING EU Emissions Trading Scheme Flare Measurement Requirements Prominent Flare Measurement Requirements in other regions FLARE GAS FLOW MEASUREMENT TECHNIQUES USED BY INDUSTRY General points to consider when measuring flare gas flow Flow Measurement methods available 15 6 DETERMINATION OF FLARE GAS COMPOSITION Manual Gas sampling, with Offline Analysis by Gas Chromatograph Automatic Gas Sampling and Offline Analysis by Gas Chromatograph Online Gas Chromatographs 21 7 DIRECT EMISSIONS MEASUREMENT TECHNIQUES Optical Remote Sensing (ORS) Techniques 22 8 CONCLUSIONS Meter Performance Improving Meter Performance Calculation Methodologies 25 9 RECOMMENDATIONS FOR FURTHER WORK REFERENCE Project No: FHRE03 Page 2 of 26 June 2013

5 EXECUTIVE SUMMARY This report provides a summary of the findings of a review undertaken by NEL to investigate the techniques used by industry to measure and report flare gas emissions; the work was funded by the National Measurement Office, an Executive Agency of the UK Department for Business, Innovation and Skills (BIS) [1]. The main objective of this work is to support industry in meeting their legal obligations for measuring and reporting flare gas emissions It is estimated that every year, some 360 million tonnes of CO 2 is released to the atmosphere through flaring and venting 1. This has a detrimental effect on the environment, contributing significantly to global warming and acidification of both land and sea. A considerable proportion of this CO 2 comes from the production of Oil and Gas. This report describes the legislation currently in place in different parts of the world to limit emissions from this sector and suggests modifications to existing techniques to improve measurement accuracy. Currently, the most prominent legislation has been developed in the European Union, the United States, Norway and Canada. The European Union Emission Trading Scheme (the EU ETS) is a mandatory cap-and-trade scheme that sets limits on the amount of greenhouse gas emissions from energy-intensive installations. Permit holders are allocated a set amount of EU allowances and can buy or trade them according to whether they are in deficit or surplus. Failure to comply with the agreed cap is met with financial penalties - principally a fine for every tonne of CO 2 for which the operator fails to surrender allowances; they must also make-up for the shortfall the following year. The legislation in the other parts of the world is also discussed in this document. To operate and further develop legislation in all of these areas, it is necessary to accurately determine the total mass of pollutant released to the atmosphere resulting from the practices of oil and gas production, refining, processing and transport. The most widely adopted approach for determining CO 2 emissions is often referred to as the Calculation Method whereby three separate parameters must be determined precombustion of the gas: The flowrate of the gas; The composition of the gas; The oxidation factor (a ratio of the amount of carbon converted to CO 2 linked to the flare efficiency) As far as the flowrate of the gas is concerned, the wide range in operating conditions encountered in flaring mean that the technologies used must have a broad range of application. The three principal technologies currently being deployed within emergency flare lines on large oil and gas facilities 2 are: Ultrasonic transit time meters, Thermal mass probes, Optical correlation meters These are generally single point or single path measurement devices that are sensitive to flow profile and installation effects. The study concluded that using multiple 1 Source: World Bank Global Gas Flaring Reduction partnership: 2 These include oil and gas production facilities, refineries and chemical plants. Other metering technology may be used in some circumstances or on smaller, more controlled flare and vent lines. Project No: FHRE03 Page 3 of 26 June 2013

6 measurement probes or meter technologies - each tuned to a different range (e.g. an ultrasonic meter for the low range and an optical meter for the high range flow) - could improve accuracy over the full operating range. It also concludes that operators should focus their efforts on optimising their meters to achieve maximum accuracy for the flow regions in which the majority of gas volume is flared over the reporting period. In addition to the flowrate, flare gas composition is required to determine the quantity of specific pollutants flared or vented to the atmosphere. It is normally determined from captured fuel gas samples using an analyser such as a gas chromatograph. Various types are available and are reviewed. However, sampling from the flare line itself is generally precluded owing to issues with health and safety, a lack of pressure in the line (or a risk of sudden, unpredictable rises in line pressure during incidents such as compressor trips, power failures or emergencies), and other technical issues. In addition to reviewing existing methods for determining flare emissions, the study also looks at novel and developing technologies. One such technique is Optical Remote Sensing (ORS) which potentially provides a means of directly measuring and tracking the emission of pollutants from a flare plume. The ORS method is very useful for both detecting and quantifying fugitive emissions. The key recommendations for further work are: An investigation into installation effects should be carried out for the most widely used flare gas meter technologies to derive the true measurement uncertainty. In many cases, a significant proportion of the total gas flared (and, hence, the CO 2 released) will emerge from the low-flow end. Therefore, there is a clear need for this region to be fully investigated, focussing on issues concerning: signal resolution, laminar/turbulent transition and temperature stratification. Meter errors arising from high and low flaring should be investigated and the associated measurement uncertainty accounted for in all calculation and reporting sheets. There needs to be a methodical and thorough test program investigating laminar-turbulent transition, stratification and installation effects at low velocities in large pipes simulating typically-sized flare lines. Gas tracer techniques offer a method of assessing flare gas flow meters in situ with the actual upstream pipe configuration and prevailing flow conditions. However, a comprehensive study assessing the technique as employed in flare gas lines is needed to fully assess the capabilities and a realistic uncertainty level in the technique. Issues relating to the uncertainty in the flare gas composition during process blowdowns should be investigated where it impacts density and emission factor Optical Remote Sensing technologies and other direct methods of determining gas emissions - should be further investigated where it may be applied to flare, vent and other fugitive gas emissions in the future. The most comprehensive approach to investigation of the above issues should ideally take the form of a large, collaborative project involving industry leaders, equipment supplier, regulators and technical consultants where possible. Project No: FHRE03 Page 4 of 26 June 2013

7 1 INTRODUCTION This report provides a summary of the findings of a thorough review undertaken by NEL to investigate the techniques used by industry to measure and report flare gas emissions [1]. The main objective of this work is to support industry in meeting their legal obligations for measuring and reporting flare gas emissions; in particular, it will assist in moving towards CO 2 trading within Phase III of the EU Emissions Trading Scheme (ETS), due to commence on 1 January The findings of this report will assist operators and stakeholders of oil and gas facilities to identify key areas for improvement in the method of determining flare gas quantities and, where appropriate, the amount of CO 2 released through combustion of the gas. 2 BACKGROUND It is estimated that over 150 billion cubic meters (bcm) of natural gas is flared or vented globally every year. To put this in to context, this is some 30% of the European Union s annual gas consumption, or an amount worth approximately $30.6 billion - enough gas to supply the entire US economy for three months. Over the next two to three decades, global energy demand is predicted to double, while oil and gas reserves are largely depleting. It is a widely held opinion that renewable energy sources, which currently only supply a small proportion of the world s energy, will not be in a position to make up the shortfall in the foreseeable future. In addition to wasting valuable energy resources, flaring also contributes to climate change and global warming. The World Bank estimates that around 360 million tonnes of CO 2 is emitted from gas flares each year. The focus of this report is on CO 2 emissions, since the reporting of emissions of the other pollutants from flares is not as stringent in EU legislation (except for highly toxic gases such as H 2 S) and are, as yet, excluded from the EU ETS. However, reference is made to these gases where it is deemed applicable. 2.1 Gas Flaring and Venting Processes Flaring is a necessary process by which excess gases can be evacuated quickly and safely in emergency situations; it is also used to facilitate depressurization of plant for maintenance and inspection during shutdown. It takes place across a number of industries and activities - including oil and gas production, refineries and petrochemical plants. Flares are also to be found at coal bed methane facilities, steel production plants and landfill sites. The flare, which often takes the form of a flame burning at the tip of an elevated stack, primarily acts as a safety relief valve. It also allows the system pressure to be regulated across the plant and prevents machinery and components from being over-pressurised. In many cases, a portion of the gas flared is taken from the fuel gas system and used to maintain a positive pressure at the tip, thus keeping air out of the system avoiding potential blow-back of the gas. This process is often Offshore Flaring referred to as purging. Gas production facilities tend to flare less than their oil counterparts due to their inherent connection to existing gas pipeline or gas processing plants. Gas venting releases gas directly into the atmosphere and tends to be more prevalent on gas production than for oil wells. Since Project No: FHRE03 Page 5 of 26 June 2013

8 its environmental impact can be greater than if the equivalent amount of gas was flared, venting should only be used as a last resort. 2.2 Flare Gas and Vent Gas Composition Gas Flaring The emissions from flares and vents depend on a number of factors, one of the most important of which is the composition of the waste gas being burned or vented. On offshore platforms the bulk of gas routed through the flare is often made up of methane and lower fractions of various other higher alkane hydrocarbons, hydrogen sulphide (H 2 S) and inert gases - typically in smaller fractions. Flare gas composition tends to be more complex onshore than offshore owing to the processes involved. Flaring is largely considered less harmful to the environment than venting. This is, in part, due to the fact that the Global Warming Potential of natural gas is higher than that of CO 2. Highly acidic compounds, such as carbonic acid (H 2 CO 3 ), sulphuric acid (H 2 SO 4 ) and nitric acid (HNO 3 ) may also be formed if the flare gas stream contains high enough fractions of water. These will cause pipework and fittings to erode unless acidresistant alloys, or coatings, are used. Flaring does not only produce CO 2. Inefficient flaring also generates unburned hydrocarbons and pollutants, such as nitrous oxides produced at flame temperatures in excess of about 1200 C. It also produces sulphur dioxide (SO 2 ), formed by combustion of H 2 S, or other sulphur compounds inherent in the fuel; carbon monoxide (CO), and particulates (smoke). The fraction of these components will be higher when the combustion efficiency is not 100% - where flame temperatures can be too high and oxygen levels too low to completely oxidise all of the VOCs (Volatile Organic Compounds) present in the gas stream Gas venting According to DECC (Department of Energy and Climate Change), Venting in the UK reportedly makes up only 0.05% of total emissions from offshore sites and onshore terminals collectively - expressed as a mass of equivalent CO (tco 2 e). In contrast, offshore flaring makes up 21% of total CO 2 emissions. However, in the USA offshore operators are venting, on average, about 70% more than they are flaring. There is evidence to suggest that fugitive emissions (which are invisible to the naked eye and difficult to both detect and measure) could be even more of an issue worldwide. This situation is exacerbated by the increased effect the direct release of VOCs and other gases has on the environment and the increased global warming this causes compared with CO 2. Project No: FHRE03 Page 6 of 26 June 2013

9 2.3 Worldwide Flaring Statistics Table 1 lists the ten largest flaring countries as presented by the World Bank Global Gas Flaring Reduction Partnership (GGFR) for the year These countries constitute around 70% by-volume of global flaring. It should be noted that Table 1 is dominated by developing countries. The USA is only fifth on the list, making-up just over 5% of worldwide flaring in There has been an increase in flaring from 2010 to 2011 of about 2 bcm overall, largely resulting increased hydrocarbon production in Russia, and the increase in shale oil and gas production in the USA. Table 1: Ten Largest Flaring Nations Country World flaring (% by volume) 1 Russia Nigeria Iran Iraq USA Algeria Kazakhstan Angola Saudi Arabia Venezuela 2.5 TOTAL Flare Systems A flare system generally comprises: pressure relief valves feeding into the flare header, piping runs to direct the gas to the flare line, knock-out drums (cylindrical vessels which are used to separate-out liquids and any solids), and a pilot system to ignite the gas on exit from the stack. The design of flare systems varies significantly from one plant or process to another. In addition to elevated flare stacks (prevalent on most offshore oil platforms and also used onshore), ground-based flares are often used at onshore oil and gas facilities to dispose of excess gas under more routine operations. Elevated flares on oil and gas facilities are typically 30 to 100 metres high and are generally used for higher volumes of gas. Ground flares can be open (so-called pit flares ) or contained within refractorylined steel enclosures. They typically comprise a number of burners set out in a matrix arrangement which promote air inspiration, increasing combustion efficiency without the need for air/steam injection. Many flare systems in developing countries such as Nigeria, comprise little more than open pipes burning-off the gas over a cooling pond, with no fencing or barriers to prohibit the public from exposure to naked flame, or the harmful gases and smoke produced. 2.5 Reducing and Reusing the Gas Normally Flared A number of methods can be used to reduce gas flaring on individual installations, although some require much greater levels of investment than others. The most basic approach is to simply reduce leakage from plant and equipment by instigating preventative maintenance measures. Using efficient plant design and equipment can also significantly reduce the throughput of gas flared. There are a number of relatively low-cost techniques available to identify leakage from pipework, valves and fittings on plants. Traditionally gas-leak detectors ( sniffers ) have been used in the oil and gas industry to detect fugitive leaks from relief valves etc. Systems are available that can both identify and measure the leakage rate of gas passing from the plant. Some use ultrasonic or acoustic sensors to both detect and quantify leaks. Project No: FHRE03 Page 7 of 26 June 2013

10 One of the key methods enabling the capture of substantial amounts of flare gas is Flare Gas Recovery (FGR). FGR systems effectively allow the flare to be shut-off under normal, low-pressure operation, with the gas thereafter compressed and rerouted for other uses. These systems have been installed in a number of facilities and can ultimately lead to near-zero flaring from oil and gas facilities, refineries and processing plants. One of the main problems of implementing FGR systems can be the required space. Space and weight is often at a premium on offshore facilities. It will also be expensive to install and the benefits of installing the technology need to be assessed over the remaining life of the facility. The scope for reducing flaring comes from reusing the gas normally sent to the flare. This can be achieved by one or more of the following methods: Table 2: Methods for Flare Reduction Export by pipeline Power generation Re-injection LNG and Gas to Liquids (GTLs) Either: a) re-compressing and treating the gas to sales pressure and quality or b) exporting for use to generate power on a neighbouring facility as a fuel. This involves reusing the gas to power equipment on the installation (such as gas turbines-driving-compressors, boilers and engines etc.), or by providing energy to local communities. This involves re-injecting the gas back into the formation to promote Enhanced Oil Recovery (EOR) or into the annulus of the well bore to facilitate Gas Lift. In the absence of a gas pipeline, consideration can be given to producing Liquefied Natural Gas (LNG) or Gas to Liquids (GTLS), such as Methanol or Dimethyl Ether, and exporting via ship or road. Project No: FHRE03 Page 8 of 26 June 2013

11 3 FLARE GAS REGULATION Although there are clear arguments for reducing gas flaring based on energy waste and environmental impact alone, incentives have to be in place to ensure industry meets their emissions reduction targets. Flare gas reduction and utilisation is highest in developed countries which have an established gas infrastructure. For example, the utilisation of gas produced in Russia and Nigeria as a percentage of the volume of actual gas produced is only about 25% and 60% respectively (i.e. about 75% and 40% of the associated gas is flared), compared with % in many other regions. These are consequently the two largest flaring nations in the world. Naturally, the effective regulation of gas flaring relies heavily on accurate measurement. This is essential to ensure fair and transparent trading, and to help reduce financial exposure to stakeholders. 3.1 Flare and Vent Regulation To-date the most prominent regulatory regimes exist in the EU, Norway, Canada and the United States, although just about all countries now at least accept that flaring has to be reduced European Union (EU Emission Trading Scheme (ETS) The EU ETS is a mandatory scheme that sets limits on the amount of greenhouse gas emissions emitted from energy-intensive installations. Ultimately this allows an emission ceiling to be established at all levels including, company, sector, member state and European level. Introduced in 2005, the EU ETS was originally aimed at targeting all six greenhouse gases identified under the Kyoto protocol, but has thus far concentrated mainly on CO 2. It covers CO 2 emissions from installations such as power stations, combustion plants, oil and gas facilities and iron and steel works. The EU ETS is in three Phases as illustrated in Table 3; Table 3: Description of Stages of EU Emissions Trading Scheme Phase of Scheme Phase I ( ) Phase II ( ) Phase III ( and onwards) Description Essentially a trial period designed to get operators and regulators used to trading before commencement of Phase II Timed to coincide with the Kyoto period, Phase II included offshore gas flaring as mandatory, and introduced revised Monitoring and Reporting Guidelines (MRG 2007) which focused on verification and integrity of measured data. Phase III of the EU ETS commenced in January 2013 and sees many having to buy allowances from the registry (via auctioning) for the first time. A new Monitoring and Reporting Regulation (MRR), and more stringent guidelines for verifiers have also been introduced. The basis of the EU ETS is to control the level of emissions through greenhouse gas permits (allowances). The permit holders (i.e. operators and stakeholders) are Project No: FHRE03 Page 9 of 26 June 2013

12 allocated a set amount of EU allowances (EUAs) with 1 allowance = 1 tonne of CO 2. At the end of the reporting period the permit holder can either buy EUAs from the registry to make up any shortfall, or sell surplus EUAs back into the scheme at the going market value. Fines are imposed on permit holders emitting more than their agreed limits set by the regulator, or for misreported data. It is hoped that Phase III will see the EU achieve two-thirds of its required unilateral emissions reduction target of 20% by 2020, based on 1990 levels (equating to 500 million tonnes of tco 2 per year) Other International Legislation Table 4: Description of International Flare Gas Legislation Country USA Canada Norway Description of Legislation The US Environmental Protection Agency (EPA) have the authority under the Clean Air Act (as Amended, 1990) to request emissions data from operators under the requirements of federal Rule 40 CFR 98 Subpart W, which includes flare emissions. There are two government departments regulating safety and the environment: The Bureau of Safety and Environmental Enforcement (BSEE) is responsible for regulating offshore federal leases, and the Bureau of Land Management (BLM) regulates onshore federal lands. The majority of oil and gas lies offshore. BLM is responsible for more than 63,000 federal onshore oil and gas wells (about 11% of all gas production in the US and 5% of oil). EPA Final Rule 40 CFR, Part 60 subpart Ja details New Source Performance Standards (NSPS) targeting refineries with new or reconstructed flare systems, or those existing, constructed or modified after June , that have been altered to increase flow, or have had new connections added. Some 400 refineries across the US are affected by the Rule. Canada is the third largest gas producing country in the world after Saudi Arabia and Venezuela; a large proportion of this gas is to be found in the landlocked province of Alberta, which has a large number of sour gas wells with particularly high fractions of sulphur present. Canada has had legislation in place for a number of years governing flaring largely developed from the need to reduce and control emissions from sour gas. The legal requirements in Alberta are laid down in the Energy Resources Conservation Board (ERCB) Directive D060. The legislation provides a comprehensive approach for reducing and measuring flare gas emissions. D060 requires operators of installations exceeding 100 standard m 3 /month of gas flared, incinerated or vented, to report these quantities to the regulator. The Norwegian Government will not approve oil and gas development plans without there being provisions in place for reducing gas flaring. Even though Norway has doubled its oil production over the last two decades, it has managed to do this whilst significantly reducing gas flaring through a number of successful regulatory measures. Norway joined the EU ETS in 2008, However, despite this a CO 2 taxation scheme, introduced in 1991, still continues, together with a NOx tax more recently introduced in These are based on the amount of gas burned in flares, engines and turbines. The CO 2 tax has also contributed to the successful reduction of flaring. In Norway, a large amount of gas is re-injected for Enhanced Oil Recovery (EOR) and other purposes. Project No: FHRE03 Page 10 of 26 June 2013

13 4 REGULATORY MEASUREMENT REQUIREMENTS FOR FLARING AND VENTING The common feature across most regulatory regimes is the requirement for operators to report their emissions using transparent and robust methods that are, ultimately, verifiable. The specific requirements set out by different countries are described below. 4.1 EU Emissions Trading Scheme Flare Measurement Requirements Operators must currently comply with the requirements of the EU ETS Monitoring and Reporting Regulations (MRR). The CO 2 emission from flares is determined by the calculation method, whereby the volume of gas flared is measured and the amount of CO 2 produced by combustion (and any inherent CO 2 in the gas) is calculated through the use of an emission factor (the tco 2 e emitted per unit quantity of gas flared) and oxidation factor (the amount of carbon oxidised to form CO 2 during combustion). The MRR is underpinned by strict measurement uncertainty targets and a newly introduced set of guidelines for verifiers to ensure a more consistent approach is applied across the member states. Although the minimum uncertainty limits for flare were actually increased from Phase I to Phase II (and remain unchanged for the quantity (activity data) in Phase III, the requirements for verification have become progressively more stringent. The reporting of all flaring from offshore facilities became mandatory during Phase II. Phase III sees the introduction of flaring from chemical plants which was previously excluded. However, flare is, for now, given free allocation. The guidelines are not prescriptive in terms of specifying any one type of technology over another, nor do they require dedicated flow meters to be installed in the flare line. Operators have the option of using a combination of approaches, which often entails both direct metering and indirect estimation techniques, and may, if properly implemented, provide a robust reporting system. The uncertainty requirements are detailed below in Table 4 for each parameter, where applicable. Table 5: Uncertainty values for Measured Parameters Activity Data (Volume or Mass) Emission Factor (EF) Oxidation Factor 3 Tier System Larger installations (> 500 ktco 2 /year) Medium-sized installations ( ktco 2 /year) Small sized installations (< 50 ktco 2 /year) ± 7.5% ± 12.5% ± 17.5% In EU ETS Phase II, the uncertainty in the flare emissions factor was required to be one-third of the uncertainty in activity data, which, strictly speaking, is ± 7.5% / 3 = ± 2.5% if the top tier is to be met. This requirement has been removed from the MRR for flare where it is stated that process modelling techniques may be used to calculate EF There is no requirement to determine the oxidation factor to any given accuracy in the MRR and it is generally considered to be equal to 1.0 for gas flares (a value of 0.98 is used in the UK since baseline figures were calculated assuming 98% conversion of carbon to CO 2 by combustion Some studies have shown that the efficiency of flares can be considerably less than 100%, particularly in the presence of high winds, liquids and over-steaming. Project No: FHRE03 Page 11 of 26 June 2013

14 4.1.1 Current UK Position within the EU ETS In the UK most upstream facilities are currently reporting flare to Tier 2 requirements (12.5%) under Phase II, with a few meeting top-tier requirements and all are using the calculation approach. However, some still rely on engineering calculation or estimation techniques to determine gas to flare. To address this issue, the UK regulator (DECC) requires yearly improvement plans to be submitted detailing how the operator plans to achieve their monitoring and reporting requirements Phase III Implications for Gas Flaring The Phase III Monitoring and Reporting Regulation replaced the MRG from the start of 2013 and aims to provide better harmonisation in the methods applied across Europe. Some of the pertinent changes to the monitoring and reporting plan in Phase III that will affect gas flaring to some degree are listed. New Requirement for Consistent Determination of Unreasonable Costs In the Phase III MRG, unreasonable cost is determined by calculating the cost involved with implementing the changes required to move to the higher tier and comparing this against the financial benefits in achieving that tier. Promotion of consistent application of the required monitoring tiers Measurement-based methodologies have been significantly updated Direct measurement of CO 2 emissions from flares can only be practically carried out in the few isolated situations where the flame is enclosed within a flue allowing sampling of the exhaust gases to be carried out, along with the flow rate. However, bespoke field studies have been undertaken in the US (notably in Texas), and some other countries, in order to analyse emission plumes from various emissions sources as a means of determining emission factors for various pollutants some of which are at the ppm level. These surveys have generally been undertaken using Optical Remote Sensing (ORS) techniques. New provisions to allow more pragmatic demonstration of equivalence where non-accredited laboratories are employed A combination of approaches can now be used to determine emissions on the condition that no data gaps or double accounting occur as a result. Reduced requirements for minor source streams contributing less than 5,000 tonnes CO 2 per year, or up to 10% of the total CO 2 emissions over the year Introduction of Regulation on the Verification and Accreditation of EU ETS emission reports This regulation has been introduced to ensure that verifiers possess the technical competence to perform the entrusted task in an independent and impartial manner and in conformity with the requirements and principles set out by the EU ETS. Project No: FHRE03 Page 12 of 26 June 2013

15 4.2 Prominent Flare Measurement Requirements in other regions The monitoring and reporting requirements in three key regions are listed in the Table below. Table 6: Prominent Flare and Vent Monitoring and Reporting Regimes USA Canada Norway Federal Rule 30 CFR 250, Subpart K (introduced in 2010), requires flare gas quantities to be accurately measured by facilities located offshore in the Gulf of Mexico and US Offshore Continental Shelf (OCS) processing more than 2,000 barrels of oil per day. The measurement uncertainty is set at ± 5% on flow rate. The regulations require that flow meters are calibrated every 12 months. Operators were required to install flare meters on all qualifying installations within 180 days after the release of the regulations. Onshore, recently amended Federal Rule 40 CFR Part 60, subpart Ja promulgates New Source Performance Standards (NSPS) targeting emissions from flare and process heaters with a view to monitoring, reporting and reducing sulphur, NOx and VOC emissions from refineries. Amongst the requirements are that flow and sulphur monitors are now mandatory for all continuous flaring excluding intermittent, emergency-only flaring with limited release. Flare Gas Recovery systems are seen as a key technology for reducing emission from larger flares and providing some level of offset to the cost of installation through increased sales revenue of the captured gas and, to a lesser degree, performance improvements through the improved monitoring and reporting regime. In Canada the most comprehensive monitoring and reporting requirements are set by the Energy Resources Conservation Board (ERCB) in Alberta. Directive 060 contains the requirements for flaring, incinerating, and venting activities conducted in Alberta by all upstream petroleum industry wells and facilities. Directive D017 details the monitoring and reporting requirements and specifies that, for facilities flaring more than 500 m 3 /day (and all flaring from sour gas wells, regardless of volume), the operator must meter the volume to ± 5% uncertainty on a single point, and a maximum uncertainty of ± 20% over a monthly period. In Norway, offshore operators are expected to have ultrasonic transittime flowmeters installed as the primary measurement device in all flare lines as per NORSOK I-SR-103. In addition to setting a measurement uncertainty target of ± 5% on measured volume, the Norwegian regulators also require the sensors to be checked every 6- months. 5 FLARE GAS FLOW MEASUREMENT TECHNIQUES USED BY INDUSTRY Despite the fact that flare gas measurement has been carried out by industry for many years, it is still very much considered a relatively new science owing to the complexities and challenges involved. The measurement of emissions from flares is different to other gas flow measurement and emissions measurement applications. The unpredictable nature of flaring, and often hostile environment, amongst other things, makes measurement extremely difficult and complex. Project No: FHRE03 Page 13 of 26 June 2013

16 5.1 General points to consider when measuring flare gas flow Meter Rangeability It is essential that any measurement equipment installed in the flare stack does not obstruct gas flow in any way and incur significant pressure drop. The large variation in flare operating conditions can lead to a wide range of gas flow velocities, particularly if only one flare is being used on the plant. It is therefore essential that the flow meter(s) installed in the flare have the rangeability to cope with these sorts of excessive measurement ranges and, moreover, will not be permanently damaged by the forces generated on transducers during such events Physical Properties Changes in viscosity and density have a significant effect on the flow profile through variations in Reynolds Number. Also, at low velocities, stratification, transient and reverse flows are common. All of these conditions give rise to complex flow measurement. The changing operating conditions can also induce large variations in gas temperature, and the gas composition can change dramatically - especially during blowdown conditions Pipe Geometry The diameter of flare lines can range from as little as 4-inches (0.1 m), on some small onshore wells, up to 72-inches (1.8 m), or even larger, in refinery and offshore flares, although flare lines typically tend to range between perhaps 12- and 40-inches. This will also limit the choice of many flow metering technologies. When flare gas meters are required to be retrofitted to existing flare stacks - which is often the case offshore - space (and weight constraints) can be a serious issue, particularly offshore. Inadequate straight lengths of pipe upstream (and downstream) will result in asymmetrical flow profiles and swirl that will affect the meters performance and introduce a measurement error Sampling Obtaining a composition measurement, or extracting a representative sample direct from the flare stack for analysis, especially during emergency blow-down events, can be an impossible task. In any case the gas will likely be too wet, dirty or at too low a pressure to allow onsite analysis using Gas Chromatographs (GCs). Environmental factors also have to be considered when selecting measurement equipment. This includes the explosive environment and the presence of corrosive components in the gas stream (e.g. H 2 S and CO 2 ) plus potentially highly corrosive acids and other dangerous substances Flow Profile Issues One of the key issues in flare gas measurement is the failure to quantify upstream installation effects on flow profile, and the subsequent impact this has on the measurement uncertainty. Bends, valve, tees and reducers disturb the flow such that the velocity profile deviates from the ideal. For example, the flow profile can become skewed, with non-axial flow components (swirl) present. Meter manufacturers generally advise having at least 20 diameters of straight length pipeline upstream of the meter (and, typically, 5 to 10 downstream of it although this is less important). Project No: FHRE03 Page 14 of 26 June 2013

17 A flowmeter may under-read or over-read depending on the installation, flow conditions and orientation and location of the measurement sensors and the permutations are numerous. At high flow rates this error will tend to be steady, but it may fluctuate at lower flow rates due to instability in the flow profile. Computational Fluid Dynamics (CFD) simulation offers a very flexible and cost-effective alternative to determining meter error for all types of flow meter. CFD involves modelling the velocity and turbulence through a 3-Dimensional grid representing the flare header and flowmeter installed within it. The uncertainty in the CFD method can only be validated by comparing its predictions against relevant test data from technical papers and journals. Figure 1 below shows the predicted streamlines through a pipework header and the resulting distortion to the velocity profile the velocity contours are clearly asymmetric at the flow meter position compared to the ideal, fully developed case. Flow Profile at meter position Flowmeter position Fully Developed Profile (Reference) Figure 1: CFD Modelling of the Flow (Streamlines) through a Pipe Header and the resulting Velocity Contours at the meter (Red/Blue = high/low velocity) 5.2 Flow Measurement methods available Although there are a number of different flow metering technologies that may potentially be used for flare gas measurement, the most widely used flow meter is the time-of-flight Ultrasonic Meter (USM). Its main advantage is its very wide turndown ratio (quoted as up to 2,500:1 and even higher), reportedly low measurement uncertainty, absence of moving parts, non-invasive design and, thus, suitability in large diameter pipelines. Other dedicated flare gas metering technologies that can be considered are thermal mass probes and optical meters. Other insertion probes, such as averaging pitots, turbines and vortex meters, have low rangeability compared with the aforementioned meters. They are not as commonly used as a single, dedicated flare meter, however, they may be effectively used as a secondary meter to target a specific range (e.g. an averaging pitot scaled for high velocity use) Flare Gas Ultrasonic Meters (USMs) Most flare gas USMs employ single beam-paths, mostly due to cost. Unfortunately, this means that they are particularly sensitive to the flow profile compared with multiple path meters (usually restricted to higheraccuracy custody transfer and fiscal applications). Project No: FHRE03 Page 15 of 26 June 2013

18 Some two-path flare gas USMs are in use which, in theory (and assuming uncertainties to be uncorrelated), reduce the uncertainty in the average velocity by about 30% compared with a single path, but if the flow is approaching fully developed without swirl or significant asymmetry. The main issues associated with this type of meter are detailed in the table below. Table 7: Measurement Issues for Ultrasonic Flare Meters (USMs) High flow rates Ultrasonic Noise Beam Drift at High Velocity (Mach Number) Low Flow Issues Effect of Gas Composition on Volume Flowrate Measurement (USMs) The main issues at high flow are: signal-to-noise ratio (SNR), beam drift and response to sudden changes in flow all of which may also cause a misreading or loss of signal. Provided enough samples are taken, a good averaged velocity will be obtained using the meter s digital signal processing algorithms. This can cause problems with the signal resolution and may result in a failure of reading. Care should be taken during installation and set-up to ensure all potential sources of noise leakage through the pipework, bosses and couplings are eliminated. A key issue exclusive to ultrasonic meters is beam drift at high flowrates. The simplistic view that the ultrasonic signal travels along a direct path between the faces of the two opposing ultrasonic transducers is only true at low velocities (and, more correctly, low Mach numbers). The path direction is affected by both the Mach number and the shape of the velocity profile. At the very high velocities experienced in flare gas lines, the ultrasonic signal can be so badly affected by this it can be lost entirely effectively blown away by the flowing gas. Besides the large uncertainty that can be apparent in low flow associated with the instability and variability in the flow profile at low Reynolds number the resolution of the meter will also be a key issue at low flow. In theory, the reading of velocity should be independent of the gas composition. However, one exception is where the gas contains CO 2 which can absorb ultrasound at frequencies in a similar range to where flare meters normally operate due to a phenomena called signal relaxation that occurs CO 2 with some other gases at specific frequencies. This issue can be relatively easily resolved using special transducers with a modified frequency Thermal Mass Probes The basic principle of operation of a Thermal Mass Flowmeter (TMF) is that the convection from a heated Resistance Temperature Detector (RTD) is proportional to the mass flow rate of the flowing gas. In theory, no measurements of pressure or temperature are needed to get an accurate measurement of mass flow rate. Thermal mass probes typically comprise two (or more) cylindrical sensor probes mounted on the end of an insertion bar. One of the probes in a sensor pair is electrically heated and acts as the active sensor, whilst the other measures the local static temperature. Sensors specifically targeted at flare gas application tend to use the constant power method. Project No: FHRE03 Page 16 of 26 June 2013

19 The output from a thermal mass probe is non-linear and varies as a function of both thermal properties (i.e. gas specific heat capacity, thermal conductivity) and the probe Reynolds number. They are therefore inferential mass flow meters that, whilst their output is proportional to mass flow, are affected to some degree by process conditions and gas composition. One particular model of TMF specifically targeted at flare gas applications includes a method of compensating for changes in gas composition. These meters comprise a second set of measurement sensors located in separate chamber; the sensors respond to changes in gas composition and allowing online correction to be applied to the output signal Optical Correlation Flowmeters Optical meters are velocity (volumetric) meters and operate on the principle that localised disturbances - such as turbulence, or tiny particles inherent in the gas stream - perturb one or more incident light beams which then provide a signature pattern that can be tracked between two optical sensors placed a known distance apart. Correction factors are then applied to determine average velocity and volumetric flow rate if the pipe diameter is known. Like ultrasonic technology, optical meters also have the ability to measure bi-directional flows and, therefore, detect potential problems with backdraft and/or instabilities arising from insufficient purge rates. A major advantage of optical meters is that they do not interact with the flow and are, thus, insensitive to changes in gas composition, pressure or temperature. Unlike ultrasonic meters, they are, therefore, less prone to loss of signal at very high flowrates. Several commercial designs of optical meter are currently available. One such type uses high-intensity laser light beams focussed onto two small photo-detectors located side-by-side in the gas stream. Microscopic particles inherent in the gas stream pass through the two laser beams causing the light to be scattered onto the detectors providing a characteristic signal pattern that can be used to determine the gas velocity. A correlation technique is then used to determine the time-of-flight of the gas between these two positions, thus allowing velocity to be determined. This meter is available as a single insertion probe for large line sizes, or a flanged wafer design for line sizes below 6-inch (the latter allowing the meter to be installed between two existing flanges during a shutdown). In the case of the insertion probe design, the measurement window is small and, thus, provides only a point-velocity measurement. The advantage of the single insertion probe design is its ease of installation, especially compared with the precision welding required for flange connections for ultrasonic probes. Being effectively a point-measurement device, this meter is sensitive to flow profile (although this is true of all flare gas meters to some degree). Test data has been made available by the manufacturer, including data showing installation effect due to upstream headers and double-bend configurations carried out in 6- and 12-inch line. Similar velocity and accompanying uncertainty ranges are quoted for this technique as for the laser-based technology. A major advantage of optical meters is that they do not interact with the flow and are, thus, in the first instance, not sensitive to changes in gas composition, pressure or temperature. A second type of optical meter specifically marketed at flare gas incorporates a visible L.E.D. light beam that passes through the gas from one side of the pipe to the other. The light beam falls onto two detectors placed a known distance apart in the axial direction. The detection method in this case is the scintillation (i.e. twinkling ) of the light in response to changes in gas density due to temperature changes and/or Project No: FHRE03 Page 17 of 26 June 2013

20 turbulence. The scintillation produces a characteristic pattern on the first beam which is then picked up a short time after by the second. Once again, cross-correlation is used to get the time-of-flight between the two detectors and, hence, velocity. Figure 2: Cross correlation technique Indirect Measurement Techniques Indirect measurement techniques involve estimation of the flare gas flow rate using other measurements on platform or facility or a combination of measurement and estimation techniques. These can be combined with process modelling and engineering calculations for determining gas composition, pressure and temperature at key points in the system. By-Difference Calculation Method The by-difference method works on the premise that the gas flared can be calculated from measuring and comparing the other contributing gas streams i.e. the gas produced minus the gas reused is equal to that flared. If there is a blowdown event, the reading from all of the relevant meters just before this happened can be used to determine the gas flared, although it may be more prudent to use inventory calculations in such instances where known volumes of gas have been vented down the flare. Where there is a dedicated flare gas meter installed in the flare line, the by-difference method can also be used as either a check of the meter results, or as a back-up should the meter signal go out of range or fail entirely. Great care must be taken when attempting to determine flare quantities using the by-difference technique. Whilst it may be suitable for higher flaring cases, and may even indeed be the only option available if the flowmeter has over-ranged, extremely high uncertainty will result when flaring is low. This is due to the fact that the gas flared is calculated as the difference between two much larger numbers causing the uncertainty to scale up in relative terms. It can cause gross under- or over-estimation in the flare figure and can even result in falsely negative flare flow rates in the extreme. Inventory Calculation Method - Gas Flowrate The inventory calculation method entails estimating the standard volume of those parts of the system that are blown-down at process conditions. The mass of gas sent to flare can also be determined if the density can be calculated with some degree of confidence. The quantity of gas flared over a period is the difference between the quantity contained in the inventory volume at the start of the process with that at the end. This is calculated using the inventory volume (which can be estimated from geometry or measured at commissioning) and the pressure and temperature measured within it. Project No: FHRE03 Page 18 of 26 June 2013

Thermal Mass Flow Meters

Thermal Mass Flow Meters Thermal Mass Flow Meters for Greenhouse Gas Emissions Monitoring Natural Gas Measurement for Emissions Calculations Flare Gas Monitoring Vent Gas Monitoring Biogas and Digester Gas Monitoring Landfill

More information

F ox W hi t e Paper. Reduce Energy Costs and Enhance Emissions Monitoring Systems

F ox W hi t e Paper. Reduce Energy Costs and Enhance Emissions Monitoring Systems F ox W hi t e Paper Reduce Energy Costs and Enhance Emissions Monitoring Systems A Technical White Paper from Fox Thermal Instruments Rich Cada, VP Sales & Marketing, Fox Thermal Instruments, Inc. 399

More information

Control Device Requirements Charts For Oil and Gas Handling and Production Facilities

Control Device Requirements Charts For Oil and Gas Handling and Production Facilities Device Charts For Oil and Gas Handling and Production Facilities Purpose/Scope: The purpose of this document is to provide standardized guidance for use by the regulated community and air permit reviewers,

More information

SNAP CODE: 090206. SOURCE ACTIVITY TITLE: Flaring in Gas and Oil Extraction NOSE CODE: 109.03.14

SNAP CODE: 090206. SOURCE ACTIVITY TITLE: Flaring in Gas and Oil Extraction NOSE CODE: 109.03.14 SNAP CODE: 090206 SOURCE ACTIVITY TITLE: WASTE INCINERATION Flaring in Gas and Oil Extraction NOSE CODE: 109.03.14 NFR CODE: 1 B 2 c 1 ACTIVITIES INCLUDED Flaring is gas combusted without utilisation of

More information

NSPS Subpart OOOO: Applicability and Compliance Basics

NSPS Subpart OOOO: Applicability and Compliance Basics NSPS Subpart OOOO: Applicability and Compliance Basics Kentucky Oil & Gas Association 2013 Western Kentucky Meeting September 12, 2013 Roy Rakiewicz All4 Inc. Rob Flynn Environmental Standards, Inc. www.all4inc.com

More information

HEAVY OIL FLOW MEASUREMENT CHALLENGES

HEAVY OIL FLOW MEASUREMENT CHALLENGES HEAVY OIL FLOW MEASUREMENT CHALLENGES 1 INTRODUCTION The vast majority of the world s remaining oil reserves are categorised as heavy / unconventional oils (high viscosity). Due to diminishing conventional

More information

Fiscal Measurement Natural Gas

Fiscal Measurement Natural Gas White Paper FSG-WP-0012 February 2014 Fiscal Measurement Natural Gas Fiscal Measurement How much? Fiscal Measurement must not be confused with Custody Transfer; in fact, fiscal measurement is a more general

More information

THE DETECTION OF GREENHOUSE GASES

THE DETECTION OF GREENHOUSE GASES THE DETECTION OF GREENHOUSE GASES Roy Montemarano Heath Consultants Incorporated KEYWORDS: greenhouse gas, remote detection, leak, natural gas, infrared, optical, imaging ABSTRACT Natural gas providers

More information

HSE information sheet. Fire and explosion hazards in offshore gas turbines. Offshore Information Sheet No. 10/2008

HSE information sheet. Fire and explosion hazards in offshore gas turbines. Offshore Information Sheet No. 10/2008 HSE information sheet Fire and explosion hazards in offshore gas turbines Offshore Information Sheet No. 10/2008 Contents Introduction.. 2 Background of gas turbine incidents in the UK offshore sector...2

More information

Global Gas Flaring Reduction Partnership & Measurement of Flare/Vent Volumes. World Bank Francisco J. Sucre

Global Gas Flaring Reduction Partnership & Measurement of Flare/Vent Volumes. World Bank Francisco J. Sucre Global Gas Flaring Reduction Partnership & Measurement of Flare/Vent Volumes World Bank Francisco J. Sucre Content Global Gas Flaring Reduction (GGFR) Gas Flaring in Mexico Global Voluntary Flaring Reduction

More information

Michael Montgomery Marketing Product Manager Rosemount Inc. Russ Evans Manager of Engineering and Design Rosemount Inc.

Michael Montgomery Marketing Product Manager Rosemount Inc. Russ Evans Manager of Engineering and Design Rosemount Inc. ASGMT / Averaging Pitot Tube Flow Measurement Michael Montgomery Marketing Product Manager Rosemount Inc. Russ Evans Manager of Engineering and Design Rosemount Inc. Averaging Pitot Tube Meters Introduction

More information

BEST PRACTICES IN LEAK DETECTION AND REPAIR (LDAR) PROGRAMS. November 06, 2014 By: François Thibodeau, Eng.

BEST PRACTICES IN LEAK DETECTION AND REPAIR (LDAR) PROGRAMS. November 06, 2014 By: François Thibodeau, Eng. BEST PRACTICES IN LEAK DETECTION AND REPAIR (LDAR) PROGRAMS November 06, 2014 By: François Thibodeau, Eng. 2 PRESENTATION OVERVIEW 1. Essential Components of a LDAR Program 2. LDAR Best Practices a. A

More information

Determination of Flared Gas Volumes Offshore Norway. By Stig Arvid Knutsson Principal Engineer Fiscal Metering Norwegian Petroleum Directorate

Determination of Flared Gas Volumes Offshore Norway. By Stig Arvid Knutsson Principal Engineer Fiscal Metering Norwegian Petroleum Directorate Determination of Flared Gas Volumes Offshore Norway By Stig Arvid Knutsson Principal Engineer Fiscal Metering Norwegian Petroleum Directorate Presentation Outline Regulatory requirements Flaring of Associated

More information

Gas Standards and Safety. Guidance Note GAS INSTALLATIONS SUPPLIED FROM BIOGAS FACILITIES - ACCEPTANCE REQUIREMENTS GAS ACT 2000

Gas Standards and Safety. Guidance Note GAS INSTALLATIONS SUPPLIED FROM BIOGAS FACILITIES - ACCEPTANCE REQUIREMENTS GAS ACT 2000 Gas Standards and Safety Guidance Note January 2015 (GN106) Version 1.0 GAS INSTALLATIONS SUPPLIED FROM BIOGAS FACILITIES - ACCEPTANCE REQUIREMENTS GAS ACT 2000 A guide to assist in the design of biogas

More information

(Adopted July 7, 1989)(Amended December 7, 1990) (Amended May 13, 1994) FUGITIVE EMISSIONS OF VOLATILE ORGANIC COMPOUNDS

(Adopted July 7, 1989)(Amended December 7, 1990) (Amended May 13, 1994) FUGITIVE EMISSIONS OF VOLATILE ORGANIC COMPOUNDS (Adopted July 7, 1989)(Amended December 7, 1990) (Amended May 13, 1994) RULE 1173. FUGITIVE EMISSIONS OF VOLATILE ORGANIC COMPOUNDS (a) (b) Purpose This rule is intended to control volatile organic compounds

More information

Texas Commission on Environmental Quality Page 1 Chapter 117 - Control of Air Pollution from Nitrogen Compounds

Texas Commission on Environmental Quality Page 1 Chapter 117 - Control of Air Pollution from Nitrogen Compounds Texas Commission on Environmental Quality Page 1 SUBCHAPTER G: GENERAL MONITORING AND TESTING REQUIREMENTS DIVISION 1: COMPLIANCE STACK TESTING AND REPORT REQUIREMENTS 117.8000, 117.8010 Effective June

More information

Energy Efficient Operations and Maintenance Strategies for Boilers

Energy Efficient Operations and Maintenance Strategies for Boilers Energy Efficient Operations and Maintenance Strategies for Boilers Large, complex and widely used, industrial boilers are major consumers of fuel. Proper operations and maintenance (O&M) procedures must

More information

Advances in Thermal Dispersion Mass Flow Meter Accuracy

Advances in Thermal Dispersion Mass Flow Meter Accuracy Advances in Thermal Dispersion Mass Flow Meter Accuracy By Dan McQueen President Fluid Components International (FCI) Advances in Thermal Dispersion Mass Flow Meter Accuracy By Dan McQueen President Fluid

More information

Fixing the Leaks: What Would it Cost to Clean Up Natural Gas Leaks?

Fixing the Leaks: What Would it Cost to Clean Up Natural Gas Leaks? FACT SHEET AND ANALYSIS Fixing the Leaks: What Would it Cost to Clean Up Natural Gas Leaks? About the Authors: The study was designed, carried out, and written by Carbon Limits, a Norwegian consulting

More information

Instrument Gas to Instrument Air Conversion Protocol October 2009 SPECIFIED GAS EMITTERS REGULATION OCTOBER 2009. Version 1.0.

Instrument Gas to Instrument Air Conversion Protocol October 2009 SPECIFIED GAS EMITTERS REGULATION OCTOBER 2009. Version 1.0. SPECIFIED GAS EMITTERS REGULATION QUANTIFICATION PROTOCOL FOR INSTRUMENT GAS TO INSTRUMENT AIR CONVERSION IN PROCESS CONTROL SYSTEMS Version 1.0 OCTOBER 2009 Page 1 Disclaimer: The information provided

More information

Continuous flow direct water heating for potable hot water

Continuous flow direct water heating for potable hot water Continuous flow direct water heating for potable hot water An independently produced White Paper for Rinnai UK 2013 www.rinnaiuk.com In the 35 years since direct hot water systems entered the UK commercial

More information

Revision to the approved baseline methodology AM0011

Revision to the approved baseline methodology AM0011 CDM Executive Board AM00011 / Version 02 Source Revision to the approved baseline methodology AM0011 Landfill gas recovery with electricity generation and no capture or destruction of methane in the baseline

More information

Communicating Your Commitment: Your Guide to Clean Energy Messaging

Communicating Your Commitment: Your Guide to Clean Energy Messaging Communicating Your Commitment: Your Guide to Clean Energy Messaging Congratulations on your recent purchase of clean energy from Renewable Choice! Whether you ve purchased green power in the form of renewable

More information

Sulfur Tail Gas Thermal Oxidizer Systems By Peter Pickard

Sulfur Tail Gas Thermal Oxidizer Systems By Peter Pickard Sulfur Tail Gas Thermal Oxidizer Systems By Peter Pickard Introduction SRU s (Sulfur Recovery Units) are critical pieces of equipment in refineries and gas plants. SRUs remove sulfur compounds from certain

More information

Putting a chill on global warming

Putting a chill on global warming Carbon capture and storage Putting a chill on global warming SABINE SULZER SULZER PUMPS MARKUS DUSS SULZER CHEMTECH Whenever fuel is burned, carbon dioxide (CO ) is emitted into the atmosphere. The subsequent

More information

Custody Transfer Measurement. with the V-Cone Flowmeter

Custody Transfer Measurement. with the V-Cone Flowmeter Custody Transfer Measurement with the V-Cone Flowmeter Stephen A. Ifft McCrometer Inc. Hemet, California, USA Abstract This paper will discuss the approval of the McCrometer V-Cone flowmeter for custody

More information

SULFUR RECOVERY UNIT. Thermal Oxidizer

SULFUR RECOVERY UNIT. Thermal Oxidizer SULFUR RECOVERY UNIT Thermal Oxidizer BURNERS FLARES INCINERATORS PARTS & SERVICE SULFUR RECOVERY UNIT Thermal Oxidizer Tail Gas Thermal Oxidizer designed and built to GOST-R requirements. Zeeco can meet

More information

Chapter 19 Purging Air from Piping and Vessels in Hydrocarbon Service

Chapter 19 Purging Air from Piping and Vessels in Hydrocarbon Service BP Lower 48 Onshore Operations Safety Manual Page 4.19 1 Chapter 19 Purging Air from Piping and Vessels in Hydrocarbon Service I. General Requirements A. After motor vehicle accidents and underground excavation

More information

Ultrasonic Gas Leak Detection

Ultrasonic Gas Leak Detection Ultrasonic Gas Leak Detection What is it and How Does it Work? Because every life has a purpose... Ultrasonic Gas Leak Detection Introduction Ultrasonic gas leak detection (UGLD) is a comparatively recent

More information

Reducing CO2 emissions for Offshore oil and gas Operations under ETS. Margaret Christie, Environmental Advisor, UK Business Unit, Premier Oil UK Ltd

Reducing CO2 emissions for Offshore oil and gas Operations under ETS. Margaret Christie, Environmental Advisor, UK Business Unit, Premier Oil UK Ltd Reducing CO2 emissions for Offshore oil and gas Operations under ETS Margaret Christie, Environmental Advisor, UK Business Unit, Premier Oil UK Ltd Reducing CO2 emissions for Offshore operations under

More information

Stainless Steel Pipe Fabrication

Stainless Steel Pipe Fabrication Stainless Steel Pipe Fabrication Dr M J Fletcher, Delta Consultants, Rutland UK We are now all too familiar with demands to reduce manufacturing costs. Fabrication of stainless steel poses particular problems.

More information

HEAT RECOVERY OPTIONS FOR DRYERS AND OXIDIZERS

HEAT RECOVERY OPTIONS FOR DRYERS AND OXIDIZERS HEAT RECOVERY OPTIONS FOR DRYERS AND OXIDIZERS William K. Scullion, Application Engineering Leader, MEGTEC Systems, De Pere, WI Introduction Competitive pressures continuously motivate us to examine our

More information

Electronic Flow Switches

Electronic Flow Switches Industries Electronic Flow Switches Petrochemical Refining Oil Production Water Treatment Pharmaceutical Food and Beverage Pulp and Paper Power Production Gas Processing Mining Biotechnology Semiconductor

More information

191: Calibration and Standards in Flow Measurement. Richard Paton National Engineering Laboratory, Scotland, UK 1 GENERAL PRINCIPLES

191: Calibration and Standards in Flow Measurement. Richard Paton National Engineering Laboratory, Scotland, UK 1 GENERAL PRINCIPLES 191: Calibration and Standards in Measurement Richard Paton National Engineering Laboratory, Scotland, UK 1 General Principles 1 2 Gravimetric Calibration of Liquid meters 2 3 Volumetric Calibration of

More information

THE THERMAL FLOW METER, A GAS METER FOR ENERGY MEASUREMENT

THE THERMAL FLOW METER, A GAS METER FOR ENERGY MEASUREMENT THE THERMAL FLOW METER, A GAS METER FOR ENERGY MEASUREMENT Kazuto Otakane, Tokyo Gas Co., Ltd Katsuhito Sakai, Tokyo Gas Co., Ltd Minoru Seto, Tokyo Gas Co., Ltd 1. INTRODUCTION Tokyo Gas s new gas meter,

More information

SPECIAL APPLICATIONS

SPECIAL APPLICATIONS Page 1 SPECIAL APPLICATIONS The protection of microelectronics clean rooms using aspirating smoke detection systems requires special consideration. The physical configuration of the room(s) and the direction

More information

PSAC/SAIT Well Testing Training Program Learning Outcomes/Objectives Level B

PSAC/SAIT Well Testing Training Program Learning Outcomes/Objectives Level B s/objectives Level B CHEM 6014: Properties and Characteristics of Natural Gases Discuss the pertinent properties and uses of natural gases as they occur in gas processing. 1. Describe the physical properties

More information

6 CONSIDERATION OF ALTERNATIVES

6 CONSIDERATION OF ALTERNATIVES 6 CONSIDERATION OF ALTERNATIVES 6.1.1 Schedule 4 of the Town and Country Planning (Environmental Impact Assessment) (Scotland) Regulations 2011 sets out the information for inclusion in Environmental Statements

More information

Offshore Gas Turbines and Dry Low NOx Burners. An analysis of the Performance Improvements (PI) Limited Database

Offshore Gas Turbines and Dry Low NOx Burners. An analysis of the Performance Improvements (PI) Limited Database Offshore Gas Turbines and Dry Low NOx Burners An analysis of the Performance Improvements (PI) Limited Database Date Rev October 2014 0 February 2015 1 Technical Note [ENV002] Rev01 Page 1 of 29 February

More information

Grant Agreement No. 228296 SFERA. Solar Facilities for the European Research Area SEVENTH FRAMEWORK PROGRAMME. Capacities Specific Programme

Grant Agreement No. 228296 SFERA. Solar Facilities for the European Research Area SEVENTH FRAMEWORK PROGRAMME. Capacities Specific Programme Grant Agreement No. 228296 SFERA Solar Facilities for the European Research Area SEVENTH FRAMEWORK PROGRAMME Capacities Specific Programme Research Infrastructures Integrating Activity - Combination of

More information

Supporting document to NORSOK Standard C-004, Edition 2, May 2013, Section 5.4 Hot air flow

Supporting document to NORSOK Standard C-004, Edition 2, May 2013, Section 5.4 Hot air flow 1 of 9 Supporting document to NORSOK Standard C-004, Edition 2, May 2013, Section 5.4 Hot air flow A method utilizing Computational Fluid Dynamics (CFD) codes for determination of acceptable risk level

More information

A GUIDANCE NOTE ON THE BEST PRACTICABLE MEANS FOR ELECTRICITY WORKS BPM 7/1 (2014)

A GUIDANCE NOTE ON THE BEST PRACTICABLE MEANS FOR ELECTRICITY WORKS BPM 7/1 (2014) A GUIDANCE NOTE ON THE BEST PRACTICABLE MEANS FOR ELECTRICITY WORKS (COAL-FIRED PLANT, GAS-FIRED GAS TURBINE, AND OIL-FIRED GAS TURBINE (PEAK LOPPING PLANT)) BPM 7/1 (2014) Environmental Protection Department

More information

INDEX 9-7-100 GENERAL

INDEX 9-7-100 GENERAL REGULATION 9 INORGANIC GASEOUS POLLUTANTS RULE 7 NITROGEN OXIDES AND CARBON MONOXIDE FROM INDUSTRIAL, INSTITUTIONAL AND COMMERCIAL BOILERS, STEAM GENERATORS AND PROCESS HEATERS INDEX 9-7-100 GENERAL 9-7-101

More information

SIX REASONS TO DRY BIOGAS To A LOW DEWPOINT BEFORE COMBUSTION IN A CHP ENGINE STEVEN SCOTT MARKET DEVELOPMENT MANAGER ALTERNATIVE ENERGIES

SIX REASONS TO DRY BIOGAS To A LOW DEWPOINT BEFORE COMBUSTION IN A CHP ENGINE STEVEN SCOTT MARKET DEVELOPMENT MANAGER ALTERNATIVE ENERGIES SIX REASONS TO DRY BIOGAS To A LOW DEWPOINT BEFORE COMBUSTION IN A CHP ENGINE STEVEN SCOTT MARKET DEVELOPMENT MANAGER ALTERNATIVE ENERGIES Filippo Turra Product Manager Cooling Technology INTRODUCTION

More information

Accurate Air Flow Measurement in Electronics Cooling

Accurate Air Flow Measurement in Electronics Cooling Accurate Air Flow Measurement in Electronics Cooling Joachim Preiss, Raouf Ismail Cambridge AccuSense, Inc. E-mail: info@degreec.com Air is the most commonly used medium to remove heat from electronics

More information

INDIAN STANDARDS FOR NATURAL GAS PIPELINE SYSTEM

INDIAN STANDARDS FOR NATURAL GAS PIPELINE SYSTEM INDIAN STANDARDS FOR NATURAL GAS PIPELINE SYSTEM 1. IS 15663(Part 1):2006 This code covers requirements and recommendations for the design, materials, construction and testing of pipelines made of steel

More information

Boiler efficiency for community heating in SAP

Boiler efficiency for community heating in SAP Technical Papers supporting SAP 2009 Boiler efficiency for community heating in SAP Reference no. STP09/B06 Date last amended 26 March 2009 Date originated 28 May 2008 Author(s) John Hayton and Alan Shiret,

More information

Methane emissions trading

Methane emissions trading 24 Chapter 3: Methane emissions trading Methane emissions trading One of the key issues in this report is whether methane trading is a viable option for the UK. Market based trading schemes are currently

More information

CSA Group Safety Standards for Oil and Gas Pipeline Systems: A Life-Cycle Approach

CSA Group Safety Standards for Oil and Gas Pipeline Systems: A Life-Cycle Approach CSA Group Safety Standards for Oil and Gas Pipeline Systems: A Life-Cycle Approach Greg Orloff, MBA Government Relations Officer North America and Europe CSA Group Z662 Technical Committee (TC) Over 250

More information

EMISSIONS OF AIR POLLUTANTS IN THE UK, 1970 TO 2014

EMISSIONS OF AIR POLLUTANTS IN THE UK, 1970 TO 2014 STATISTICAL RELEASE: 17 DECEMBER 2015 EMISSIONS OF AIR POLLUTANTS IN THE UK, 1970 TO 2014 There has been a long term decrease in the emissions of all of the air pollutants covered by this statistical release

More information

Shipping, World Trade and the Reduction of

Shipping, World Trade and the Reduction of Shipping, World Trade and the Reduction of United Nations Framework Convention on Climate Change International Maritime Organization Marine Environment Protection Committee International Chamber of Shipping

More information

ENVIRONMENTAL STANDARDS FOR PETROLEUM OIL REFINERIES EMISSIONS. Standards for emissions from furnaces, boilers and Power Plant

ENVIRONMENTAL STANDARDS FOR PETROLEUM OIL REFINERIES EMISSIONS. Standards for emissions from furnaces, boilers and Power Plant ENVIRONMENTAL STANDARDS FOR PETROLEUM OIL REFINERIES EMISSIONS Standards for emissions from furnaces, boilers and Power Plant S. Parameter Limiting concentration in mg/nm 3, unless stated Existing refineries

More information

The Greenhouse Gas Protocol

The Greenhouse Gas Protocol The Greenhouse Gas Protocol Introduction to the Greenhouse Gas Protocol Corporate Accounting and Reporting Standard The Greenhouse Gas (GHG) Protocol Corporate Accounting and Reporting Standard provides

More information

CALDON LEFM 380Ci Gas Ultrasonic Flow Meter. Integrating experience, proven technology and innovation

CALDON LEFM 380Ci Gas Ultrasonic Flow Meter. Integrating experience, proven technology and innovation CALDON LEFM 380Ci Gas Ultrasonic Flow Meter Integrating experience, proven technology and innovation VALVES & MEASUREMENT Cameron s CALDON LEFM 380Ci gas ultrasonic flow meter combines world-leading flow

More information

EPA Requirements for Diesel Standby Engines In Data Centers. Bob Stelzer / CTO / Safety Power Inc. For 7x24 Fall 2014 Conference. 1.

EPA Requirements for Diesel Standby Engines In Data Centers. Bob Stelzer / CTO / Safety Power Inc. For 7x24 Fall 2014 Conference. 1. EPA Requirements for Diesel Standby Engines In Data Centers Bob Stelzer / CTO / Safety Power Inc For 7x24 Fall 2014 Conference 1.0 Introduction In order to get the Air Emissions Permit for facilities that

More information

Select the Right Relief Valve - Part 1 Saeid Rahimi

Select the Right Relief Valve - Part 1 Saeid Rahimi Select the Right Relief Valve - Part 1 Saeid Rahimi 8-Apr-01 Introduction Selecting a proper type of relief valve is an essential part of an overpressure protection system design. The selection process

More information

EOR/CCS 360-DEGREE LEGAL REVIEW

EOR/CCS 360-DEGREE LEGAL REVIEW November 2012 EOR/CCS 360-DEGREE LEGAL REVIEW INDEX 1 Introduction 1 2 Executive Summary 1 3 Project description and stakeholders 3 3.1 Overview of the combined EOR and CCS project 3 3.2 Stakeholders 4

More information

METHANE EMISSIONS MITIGATION OPTIONS IN THE GLOBAL OIL AND NATURAL GAS INDUSTRIES

METHANE EMISSIONS MITIGATION OPTIONS IN THE GLOBAL OIL AND NATURAL GAS INDUSTRIES METHANE EMISSIONS MITIGATION OPTIONS IN THE GLOBAL OIL AND TURAL GAS INDUSTRIES Robinson, D.R., ICF Consulting, Inc. Fernandez, R., U.S. Environmental Protection Agency Kantamaneni, R. K., ICF Consulting,

More information

The World Market for Thermal Flowmeters

The World Market for Thermal Flowmeters Overview Published: October 2009 www.flowthermal.com 2 27 Water Street Wakefield, MA 01880 United States [1] 781-245-3200 [1] 781-224-7552 (fax) www.flowresearch.com Flow Research has completed a new market

More information

GAS HEATING IN COMMERCIAL PREMISES

GAS HEATING IN COMMERCIAL PREMISES ENERGY EFFICIENCY OFFICES GAS HEATING IN COMMERCIAL PREMISES www.energia.ie www.energia.ie Typically, energy reductions of 10% or more can be made easily through maintenance and low cost improvements.

More information

BP Texas City Refinery

BP Texas City Refinery BP Texas City Refinery ENVIRONMENTAL STATEMENT FOR YEAR 2010 (Review of Y2009 Performance) Introduction Recognizing the complex nature of petroleum refining operations and to ensure that we meet our stated

More information

Description of Thermal Oxidizers

Description of Thermal Oxidizers Description of Thermal Oxidizers NESTEC, Inc. is a full service equipment supplier specializing in solutions for plant emission problems. The benefit in working with NESTEC, Inc. is we bring 25+ years

More information

Birmingham City University / Students Union Aspects and Impacts Register. Waste. Impacts description

Birmingham City University / Students Union Aspects and Impacts Register. Waste. Impacts description Birmingham City University / Students Union and Impacts Register Waste Production of non - hazardous waste Production of hazardous waste Storage of non - hazardous waste Potential for waste to be disposed

More information

World s Best Oil in Water Analyzers

World s Best Oil in Water Analyzers World s Best Oil in Water Analyzers Advanced Water Measurement and Analysis Advanced Sensors Ltd is the leading global supplier of Oil in Water analyzers to the Oil and Gas Industries. We provide innovative

More information

Technical Guidance. Application of Portable Gas Detectors in the Petrochemical Industry. Made simple. Introduction

Technical Guidance. Application of Portable Gas Detectors in the Petrochemical Industry. Made simple. Introduction Introduction Technical Guidance Application of Portable Gas Detectors in the Petrochemical Industry Made simple For more than 20 years CoGDEM members have been at the forefront in the development of the

More information

COLORADO REGULATION 7

COLORADO REGULATION 7 COLORADO REGULATION 7 Author: Jay Christopher, Business Unit Manager, Air & Process Services, Trihydro Corporation Jane Steere, QAQC Coordinator, Air & Process Services, Trihydro Corporation ABSTRACT The

More information

The German Emissions Trading Scheme Could Effect emission Reductions After 2012

The German Emissions Trading Scheme Could Effect emission Reductions After 2012 The EU Emissions Trading Scheme post 2012 Executive summary The full report, in Swedish, is available at; - Swedish Energy Agency, www.stem.se, report ER 2006:45 - Swedish Environmental Protection Agency,

More information

Shipping, World Trade and the Reduction of

Shipping, World Trade and the Reduction of Shipping, World Trade and the Reduction of United Nations Framework Convention on Climate Change International Maritime Organization International Chamber of Shipping COP 19 WARSAW UNFCCC Must Support

More information

Energy Saving Fact Sheet Boilers

Energy Saving Fact Sheet Boilers Energy Saving Fact Sheet Boilers Turn a burning issue into real energy savings You need a boiler to heat your premises and provide hot water or to generate steam for use in industrial processes. Unfortunately,

More information

FLAMMABLE LIQUIDS COMPLIANCE NOTE

FLAMMABLE LIQUIDS COMPLIANCE NOTE Issued by: Heather Rice Page: 1 of 7 COMPLIANCE NOTE INTRODUCTION This document provides additional guidance to support the Arrangement on Flammable Liquids (Ref No. CYC/HS/A27) CONTENTS Section Topic

More information

White Paper. Chemical dosing and blending - the role of precision actuators

White Paper. Chemical dosing and blending - the role of precision actuators White Paper Chemical dosing and blending - the role of precision actuators Chemical dosing and blending - the role of precision actuators White Paper 16 th August 2014 Chemical dosing and blending - the

More information

Head Loss in Pipe Flow ME 123: Mechanical Engineering Laboratory II: Fluids

Head Loss in Pipe Flow ME 123: Mechanical Engineering Laboratory II: Fluids Head Loss in Pipe Flow ME 123: Mechanical Engineering Laboratory II: Fluids Dr. J. M. Meyers Dr. D. G. Fletcher Dr. Y. Dubief 1. Introduction Last lab you investigated flow loss in a pipe due to the roughness

More information

The Use of Exhaust Gas Recirculation (EGR) Systems in Stationary Natural Gas Engines. The Engine Manufacturers Association August 2004

The Use of Exhaust Gas Recirculation (EGR) Systems in Stationary Natural Gas Engines. The Engine Manufacturers Association August 2004 www.enginemanufacturers.org Two North LaSalle Street Suite 2200 Chicago, Illinois 60602 Tel: 312/827-8700 Fax: 312/827-8737 The Use of Exhaust Gas Recirculation (EGR) Systems in Stationary Natural Gas

More information

Top Technology for Industry, Agriculture, Business and Communities

Top Technology for Industry, Agriculture, Business and Communities Top Technology for Industry, Agriculture, Business and Communities CHP The Technology with a Potential for Saving Energy Combined Heat and Power (CHP) is a highly efficient technology for the conversion

More information

Optimization Design for Sulfur Dioxide Flow Monitoring Apparatus in Thermal Power Plants Hao-wei Hu 1, a, Xue Yang 1, b and Xiao-wei Song 1, c

Optimization Design for Sulfur Dioxide Flow Monitoring Apparatus in Thermal Power Plants Hao-wei Hu 1, a, Xue Yang 1, b and Xiao-wei Song 1, c International Conference on Information Sciences, Machinery, Materials and Energy (ICISMME 2015) Optimization Design for Sulfur Dioxide Flow Monitoring Apparatus in Thermal Power Plants Hao-wei Hu 1, a,

More information

OFFSHORE OIL & GAS SECTOR STRATEGY 2014 TO 2017

OFFSHORE OIL & GAS SECTOR STRATEGY 2014 TO 2017 STRATEGIC CONTEXT OFFSHORE OIL & GAS SECTOR STRATEGY 2014 TO 2017 1 This strategy sets out how HSE s Energy Division will regulate health and safety of the offshore oil and gas industry operating on the

More information

Proposal for a RECOMMENDATION OF THE EUROPEAN COMMISSION

Proposal for a RECOMMENDATION OF THE EUROPEAN COMMISSION EUROPEAN COMMISSION Brussels, XXX [ ] (2013) XXX draft Proposal for a RECOMMENDATION OF THE EUROPEAN COMMISSION Providing minimum principles for the exploration and production of hydrocarbons (especially

More information

Specific Volume of Liquid (Column 7). The volume per unit of mass in cubic feet per pound.

Specific Volume of Liquid (Column 7). The volume per unit of mass in cubic feet per pound. Steam Tables What They Are How to Use Them The heat quantities and temperature/ pressure relationships referred to in this Handbook are taken from the Properties of Saturated Steam table. Definitions of

More information

Laminar and Turbulent flow. Flow Sensors. Reynolds Number. Thermal flow Sensor. Flow and Flow rate. R = Mass Flow controllers

Laminar and Turbulent flow. Flow Sensors. Reynolds Number. Thermal flow Sensor. Flow and Flow rate. R = Mass Flow controllers Flow and Flow rate. Laminar and Turbulent flow Laminar flow: smooth, orderly and regular Mechanical sensors have inertia, which can integrate out small variations due to turbulence Turbulent flow: chaotic

More information

The oil fields in the NCS are located in the North Sea, Norwegian Sea, and Barents Sea.

The oil fields in the NCS are located in the North Sea, Norwegian Sea, and Barents Sea. A.2 Norway Volumes of Associated Gas Flared on Norwegian Continental Shelf Norway is a major oil producer, and its oil fields are located offshore in the Norwegian Continental Shelf (NCS). 81 In 2002,

More information

CONTENTS. ZVU Engineering a.s., Member of ZVU Group, WASTE HEAT BOILERS Page 2

CONTENTS. ZVU Engineering a.s., Member of ZVU Group, WASTE HEAT BOILERS Page 2 WASTE HEAT BOILERS CONTENTS 1 INTRODUCTION... 3 2 CONCEPTION OF WASTE HEAT BOILERS... 4 2.1 Complex Solution...4 2.2 Kind of Heat Exchange...5 2.3 Heat Recovery Units and Their Usage...5 2.4 Materials

More information

VALIDATION, MODELING, AND SCALE-UP OF CHEMICAL LOOPING COMBUSTION WITH OXYGEN UNCOUPLING

VALIDATION, MODELING, AND SCALE-UP OF CHEMICAL LOOPING COMBUSTION WITH OXYGEN UNCOUPLING VALIDATION, MODELING, AND SCALE-UP OF CHEMICAL LOOPING COMBUSTION WITH OXYGEN UNCOUPLING A research program funded by the University of Wyoming School of Energy Resources Executive Summary Principal Investigator:

More information

CCS Roadmap. The regulatory framework

CCS Roadmap. The regulatory framework The regulatory framework April 2012 The regulatory framework We are: Ensuring that the CCS Commercialisation Programme provides practical experience with the regulatory framework and that the framework

More information

MICROPACK Visual Flame Detection Application Note

MICROPACK Visual Flame Detection Application Note MICROPACK Visual Flame Detection Application Note ABSTRACT Optical flame detection has evolved over the last 30 years with improved sensors, processing power, and high electronics reliability, which has

More information

ATMOSPHERIC EMISSIONS FROM GAS FIRED HOME HEATING APPLIANCES

ATMOSPHERIC EMISSIONS FROM GAS FIRED HOME HEATING APPLIANCES ATMOSPHERIC EMISSIONS FROM GAS FIRED HOME HEATING APPLIANCES Stefano Cernuschi, Stefano Consonni, Giovanni Lonati, Michele Giugliano, Senem Ozgen DIIAR Environmental Sect., Politecnico di Milano, P.za

More information

Application Note 12: TrendView Recorders Continuous Emissions Monitoring

Application Note 12: TrendView Recorders Continuous Emissions Monitoring Application Note 12: TrendView Recorders Continuous Emissions Monitoring Continuous Emissions Monitoring (often abbreviated to CEM) is the term commonly used to describe instantaneous or real-time environmental

More information

Air quality and biomass installations. A briefing for local authorities

Air quality and biomass installations. A briefing for local authorities Air quality and biomass installations A briefing for local authorities March 2011 Published by BioRegional Development Group BedZED Centre, 24 Helios Road, Wallington, Surrey SM6 7BZ. www.bioregional.com

More information

Shipping, World Trade and the Reduction of

Shipping, World Trade and the Reduction of Shipping, World Trade and the Reduction of International Chamber of Shipping CO DO P HA 18 United Nations Framework Convention on Climate Change International Maritime Organization UNFCCC Must Support

More information

Techniques to Improve Measurement Accuracy in Power Plant Reported Emissions

Techniques to Improve Measurement Accuracy in Power Plant Reported Emissions Techniques to Improve Measurement Accuracy in Power Plant Reported Emissions Carlos E. Romero Nenad Sarunac Senior Research Engineer Principal Research Engineer Energy Research Center Energy Research Center

More information

Sentinel LCT. Panametrics Ultrasonic Flowmeter for Liquid Custody Transfer Measurement. GE Measurement & Control Solutions. Benefits.

Sentinel LCT. Panametrics Ultrasonic Flowmeter for Liquid Custody Transfer Measurement. GE Measurement & Control Solutions. Benefits. GE Measurement & Control Solutions Sentinel LCT Panametrics Ultrasonic Flowmeter for Liquid Custody Transfer Measurement Benefits Extremely reliable and highly accurate flowmeter, designed specifically

More information

How To Make A High Co 2 Gas Blend

How To Make A High Co 2 Gas Blend ECONOMICAL OPTION FOR CO 2 / METHANE SEPARATION IN PRODUCED GAS CONTAINING A HIGH CO 2 FRACTION F. Patrick Ross, P.E. TPR Consulting 9907 Sagecourt Drive Houston, Texas 77089 (713) 870-9208 pat.ross@att.net

More information

Thermal Dispersion Mass Flow

Thermal Dispersion Mass Flow Thermatel Thermal Dispersion Mass Flow Measurement Handbook Table of Contents Introduction...1 What is Mass Flow Measurement?...1 Types of Flow Transmitters...4 Differential Pressure...4 Orifice...4 Venturi...6

More information

Testing Protocol for Differential Pressure Measurement Devices API MPMS Chapter 22.2

Testing Protocol for Differential Pressure Measurement Devices API MPMS Chapter 22.2 Testing Protocol for Differential Pressure Measurement Devices API MPMS Chapter 22.2 Steve Baldwin Chevron Energy Technology Company Houston, Texas USA Casey Hodges CEESI Measurement Solutions. Nunn, Colorado

More information

PIPELINE INSPECTION UTILIZING ULTRASOUND TECHNOLOGY: ON THE ISSUE OF RESOLUTION By, M. Beller, NDT Systems & Services AG, Stutensee, Germany

PIPELINE INSPECTION UTILIZING ULTRASOUND TECHNOLOGY: ON THE ISSUE OF RESOLUTION By, M. Beller, NDT Systems & Services AG, Stutensee, Germany ABSTRACT: PIPELINE INSPECTION UTILIZING ULTRASOUND TECHNOLOGY: ON THE ISSUE OF RESOLUTION By, M. Beller, NDT Systems & Services AG, Stutensee, Germany Today, in-line inspection tools are used routinely

More information

Source: EIA Natural Gas Issues and Trends 1998

Source: EIA Natural Gas Issues and Trends 1998 7.0 System Redesign Analysis 7.1 Emissions Natural gas is a clean burning fossil fuel. It consists of a mixture of hydrocarbon gases, primarily Methane (CH 4 ). In analyzing the combustion process, it

More information

THE BASICS Q: What is VOC? Q: What are flashing losses/voc emissions from hydrocarbon storage tanks? - 1 -

THE BASICS Q: What is VOC? Q: What are flashing losses/voc emissions from hydrocarbon storage tanks? - 1 - Calculation of Flashing Losses/VOC Emissions from Hydrocarbon Storage Tanks THE BASICS Q: What is VOC? A: VOC is an acronym that stands for Volatile Organic Compounds. VOC are components of hydrocarbon

More information

97 MW of Cat coal seam methane power in New South Wales, Australia

97 MW of Cat coal seam methane power in New South Wales, Australia CAT GAS SOLUTIONS 97 MW of Cat coal seam methane power in New South Wales, Australia SMARTER ENERGY SOLUTIONS From natural gas combined heat and power (CHP) for facilities to alternative biogas electric

More information

Nitrogen Blanketing for Methanol Storage and Transportation

Nitrogen Blanketing for Methanol Storage and Transportation Nitrogen Blanketing for Methanol Storage and Transportation Overview Air is the enemy of many materials. Not only can oxygen cause safety concerns and product degradation, but moisture, dirt, hydrocarbons

More information

This article provides a basic primer on an

This article provides a basic primer on an Everything You Need to Know About NOx Controlling and minimizing pollutant emissions is critical for meeting air quality regulations. By Charles Baukal, Director of R&D, John Zinc Co. LLC, Tulsa, Okla.

More information

Boiler Tune-up Guide

Boiler Tune-up Guide Boiler Tune-up Guide National Emission Standards for Hazardous Air Pollutants for Area Sources: Industrial, Commercial, and Institutional Boilers What is a boiler tune-up? 40 CFR Part 63 Subpart JJJJJJ

More information