Level 1 Energy Audit Report. For: Gladstone Regional Council
|
|
- Dylan Stone
- 7 years ago
- Views:
Transcription
1 Level 1 Energy Audit Report For: Gladstone Regional Council Gladstone Art Gallery & Museum Conducted by: Jamie Rogers - EcoXpert Barnes Electrical Service 1/54 Callemondah Drive Gladstone QLD 4680 Mob: sales@barneselectrical.com.au Submitted to: Heather Riches & Sonja Thomas Lyons Street Depot sonjat@gladstonerc.qld.gov.au Audit Report Date: 24/03/2016 Audit Date: 22/03/2016
2 Table of Contents SECTION 1: INTRODUCTION AND EXECUTIVE SUMMARY 2 SECTION 2: BACKGROUND AUDIT SCOPE AND LIMITATIONS METHODOLOGY SITE INFORMATION SITE VIEW 5 SECTION 3: ENERGY CONSUMPTION ANNUAL ENERGY BILL ANALYSIS 6 SECTION 4: REVIEW OF SITE ENERGY USE AND OPPORTUNITIES HVAC CONTROL to Identified HVAC opportunity Air conditioner Identified HVAC opportunity HWS 13 SECTION 5: QUICK WINS & FURTHER SCOPE 14 SECTION 6: SUMMARY OF OPPORTUNITIES 14 SECTION 7: ASSUMPTIONS 15 SECTION 8: GLOSSARY 16 1
3 SECTION 1: INTRODUCTION AND EXECUTIVE SUMMARY Barnes Electrical Service, certified EcoXpert, has been engaged by the Gladstone Regional Council to perform a simple walkthrough energy audit of the Gladstone Art Gallery & Museum and provide recommendations. This energy audit report: Evaluates overall energy consumption Illustrates current energy use Identifies and outlines potential areas of energy waste reduction and cost savings. The overall energy consumption of the site is summarised as follows: Energy Type KWh per Measured Period (9mths) GJ per year Energy Cost $ (inc. GST) GHG Emissions Tones CO2 Cost $/KWh Blended Rate (inc. GST) Electricity 541,683 1, $97, Table 1: Overall energy consumption of Gladstone Art Gallery & Museum Based on site observations, simple data analysis and meeting with Joanne Duke and Barnes Electrical Service, the following recommendations are listed at the end of this report to improve site energy efficiency and performance. Actions are related to: Operational practice Energy monitoring and tracking Lighting & Lighting control Heating, Ventilation and Air Conditioning (HVAC) control Implementation of all the identified opportunities listed at the end of this report is expected to deliver ongoing annual savings of $11, This equates to: Approximately GJ of energy savings (electricity) annually. Approximately 12% reduction of annual site energy consumption annually Approximately tco 2 emission reduction annually Total estimated implementation cost is $6,900, providing a payback period of approximately 0.58 years. In addition to these specific actions we have identified a number of low cost initiatives that may be actionable immediately that could also save energy with very little cost to implement. 2
4 SECTION 2: BACKGROUND The main objective of this walkthrough audit is to identify how energy is being used in the Art Gallery & Museum and help identify practical and cost effective energy saving measures that will reduce energy use and lower operating costs. 2.1 AUDIT SCOPE AND LIMITATIONS This audit report will: Evaluate Client site s overall energy performance. Highlight number of improvement opportunities and analyse the potential impact after the implementation. Provide an estimation of payback periods implementing the recommended actions. Demonstrate the reduction of environmental footprint. Identify quick wins and areas for further evaluation. In this walkthrough audit, the following major building-related activities were investigated: Energy supply and metering Lighting consumption and controls Climate control (Heating, Ventilation and Air Conditioning) The saving and cost calculations performed in this report are estimates only. If Gladstone Regional Council wants to implement any of the actions listed in this report, detail review will be required to get an accurate savings and implementation costs. 3
5 2.2 METHODOLOGY The following activities were performed during and after the Walkthrough Audit in Art Gallery & Museum: Short kick-off meeting the Property Team Members Analyse of existing energy bills and data Site inspection Interviews and consultation with staff Review of all major site activities, equipment s and process A written report detailing findings, recommendations, approximate costing and savings with payback times. 2.3 SITE INFORMATION The Gladstone Regional Art Gallery & Museum was established in 1985 and is a community cultural initiative funded by the Gladstone Regional Council. It is dedicated to promoting art and heritage for and by the communities of the Gladstone region and Central Queensland, acting as a focal point for the preservation and display of the region's history and cultural heritage. After talking to the Art Gallery & Museum management team, Barnes Electrical Service has collected the following information: This site is funded by Gladstone Regional Council and operates Monday to Saturday, from 10am to 5pm. The site is approximately 6,400 Square meters of covered area Electricity is the main source of energy Site has recently completed replacements of Large Air-condition Systems Air-conditioning requirements for the Touring Arts needs to maintain at fixed set points in the Main galleries and storage rooms at 21 Degrees (-1/+2) air temperature at 50% (+/-5) humidity. 4
6 2.4 SITE VIEW Figure 1: Real view of Gladstone Art Gallery & Museum Figure 2: Aerial view of Gladstone Art Gallery & Museum 5
7 SECTION 3: ENERGY CONSUMPTION The major energy consumptions at this facility are: Heating, Ventilation and Air Conditioning (HVAC) Lighting 3.1 ANNUAL ENERGY BILL ANALYSIS Electricity Consumption: Date Consumption Total Cost Consumption Blended Rate GHG Emissions KWh ($ ex GST) GJ ($/kwh) Tonnes CO2e Jul $10, $ Aug $11, $ Sep $11, $ Oct $10, $ Nov $10, $ Dec $11, $ Jan $10, $ Feb $10, $ Mar $11, $ TOTAL $97, $ Table 2: Electricity consumption for 9 months Electricity Consumption (9mths) Consumption (KWh) Jul-15 Aug-15 Sep-15 Oct-15 Nov-15 Dec-15 Jan-16 Feb-16 Mar-16 Figure 3: Electricity consumption trend 6
8 Figure 4: Gladstone Climate for 2015 Gladstone Art Gallery - Electricity Usage (Iterval Data) Summary Total 5 0 Figure 5: Gladstone Art Gallery Electricity Usage (Interval Data) for 2015 From the figure 4 and figure 5 above, it is noticeable that site reflects the outside climate. Which identifies that the air-conditioning is the main energy consumer. 7
9 SECTION 4: REVIEW OF SITE ENERGY USE AND OPPORTUNITIES 4.1 HVAC CONTROL Onsite meeting with Joanne Duke, it was stated that the Art Gallery is required to have the Airconditioning maintain at fixed set points in the Main galleries and storage areas to meet the requirements for the Touring Arts shows/displays. In discussions, it was found that the site has some latitude in set point adjustments in the cool months. As the result of the required set points, the running cost of the air-conditioning is high. The site has recently had the Main Gallery, Storage area, Tower and the Entry/hall ducted airconditioning systems replaced to improve the effectives of the system to maintain the set points. The systems were replaced in different stages which is hard to clarify how much the new systems has reduced energy used. But there has been some reduction in power usage. Throughout the Audit process, it was it was notice that there are different air-conditioning systems that are trying to cool the same areas. As the larger systems have been replaced or at the age of replacement, the additional smaller units may not be required. We recommend GRC to get an Aircondition Engineer or consultant to assess the whole building (new and old sections) installation to ensure all sections/systems are working together not against each other. Due to the building lay out, there are common areas shared by different sections like stair wells, Link Spans, admin offices and access points (rear personal entry points). We recommend to ensure doors that separate these areas to be closed to prevent cooling spaces that used in short periods. Examples: - Door at downstairs office to kitchen/hallway - Rear personal access exit/storage door to kitchen/hallway - Closing time, close stair well doors on exit Audit findings: Main Hall (64kw)- Temperature Adjustment in Cold Months Entry/Hallway (30kw)- Temperature Adjustment in Cold Months Tower (25kw)- Temperature Adjustment in Cold Months Store/Loading Room- Temperature Adjustment in Cold Months O Connor Gallery- Temperature Adjustment in Cold Months Split System (2.5kw)- Set Point Temperature Adjustment Split System (3kw)- Set Point Temperature Adjustment Split System (8kw)- Set Point Temperature Adjustment Link Span Cassette 10kw (Jo s Office)- Set Point Temperature Adjustment Link Span Cassette 10kw (O Conner Entry)- Set Point Temperature Adjustment Link Span Cassette 10kw (Jo s Office)- Switch off between 8pm-6am every day Link Span Cassette 10kw (O Conner Entry)- Switch off between 8pm-6am every day Down Stairs Office Entry Doors- Tint Doors to reduce heat transfer Jo s Office Windows Tint Windows to reduce heat and allow more natural light Downstairs Kitchen Room HWS Reduce time to 8hrs/day (9am-5pm) 8
10 4.1.1 Identified HVAC opportunity Main Hall (64kw)- Temperature Adjustment in Cold Months Alter Building Management System (BMS) to increase set point to 24 Degrees between 10pm- 3am during the cooler months. During the cooler months, there is less heat losses between inside and outside temperatures. Alter BMS programing to increase set point between 10pm-3am during the cooler months Every 1 degree increase from 21 degrees (up to 24), is saving of around 10% of Savings potential: Approximately 7,200 kwh, $ 1,292.65, 6.84 tco 2 p.a. Payback: Approximately 0.31 years Identified HVAC opportunity Entry/Hallway (30kw)- Temperature Adjustment in Cold Months Alter Building Management System (BMS) to increase set point to 24 Degrees between 10pm- 3am during the cooler months. During the cooler months, there is less heat losses between inside and outside temperatures. Alter BMS programing to increase set point between 10pm-3am during the cooler months Every 1 degree increase from 21 degrees (up to 24), is saving of around 10% of Savings potential: Approximately 3,375 kwh, $ , 3.21 tco 2 p.a. Payback: Approximately 0.66 years Identified HVAC opportunity Tower (25kw)- Temperature Adjustment in Cold Months Alter Building Management System (BMS) to increase set point to 24 Degrees between 10pm- 3am during the cooler months. During the cooler months, there is less heat losses between inside and outside temperatures. Alter BMS programing to increase set point between 10pm-3am during the cooler months Every 1 degree increase from 21 degrees (up to 24), is saving of around 10% of Savings potential: Approximately 2,813 kwh, $ , 2.67 tco 2 p.a. Payback: Approximately 0.79 years 9
11 4.1.4 Identified HVAC opportunity Store/Loading Room- Temperature Adjustment in Cold Months Alter Building Management System (BMS) to increase set point to 24 Degrees between 10pm- 3am during the cooler months. During the cooler months, there is less heat losses between inside and outside temperatures. Alter BMS programing to increase set point between 10pm-3am during the cooler months Every 1 degree increase from 21 degrees (up to 24), is saving of around 10% of Savings potential: Approximately 2,813 kwh, $ , 2.67 tco 2 p.a. Payback: Approximately 0.79 years Identified HVAC opportunity O Connor Gallery- Temperature Adjustment 10pm-3am in Cold Months Alter Building Management System (BMS) to increase set point to 24 Degrees between 10pm- 3am during the cooler months. During the cooler months, there is less heat losses between inside and outside temperatures. Alter BMS programing to increase set point between 10pm-3am during the cooler months Every 1 degree increase from 21 degrees (up to 24), is saving of around 10% of Savings potential: Approximately 2,250 kwh, $ , 2.14 tco 2 p.a. Payback: Approximately 0.99 years Identified HVAC opportunity Split System (2.5kw)- Set Point Temperature Adjustment Set default temperatures on split system to 24 Degrees Staff task- Set default temperature to 24 Degrees Office spaces don t require to be at 21 Degrees Every 1 degree increase from 21 degrees (up to 24), is saving of around 10% of Savings potential: Approximately 1,051 kwh, $ , 0.99 tco 2 p.a. Estimated capital cost: $0.00 (as GRC Staff can make the change) Payback: Approximately 0.00 years 10
12 4.1.7 Identified HVAC opportunity Split System (3kw)- Set Point Temperature Adjustment Set default temperatures on split system to 24 Degrees Staff task- Set default temperature to 24 Degrees Office spaces don t require to be at 21 Degrees Every 1 degree increase from 21 degrees (up to 24), is saving of around 10% of Savings potential: Approximately 1,226 kwh, $ , 1.16 tco 2 p.a. Estimated capital cost: $0.00 (as GRC Staff can make the change) Payback: Approximately 0.00 years Identified HVAC opportunity Split System (8kw)- Set Point Temperature Adjustment Set default temperatures on split system to 24 Degrees Staff task- Set default temperature to 24 Degrees Office spaces don t require to be at 21 Degrees Every 1 degree increase from 21 degrees (up to 24), is saving of around 10% of Savings potential: Approximately 2,920 kwh, $ , 2.77 tco 2 p.a. Estimated capital cost: $0.00 (as GRC Staff can make the change) Payback: Approximately 0.00 years Identified HVAC opportunity Link Span Cassette 10kw (Jo s Office)- Set Point Temperature Adjustment Alter Building Management System (BMS) to increase set point to 24 Degrees as it is walk ways. Alter BMS programing to increase set point Every 1 degree increase from 21 degrees (up to 24), is saving of around 10% of Savings potential: Approximately 3,942 kwh, $ , 3.75 tco 2 p.a. Payback: Approximately 0.57 years 11
13 Identified HVAC opportunity Link Span Cassette 10kw (O Conner Entry)- Set Point Temperature Adjustment Alter Building Management System (BMS) to increase set point to 24 Degrees as it is walk ways. Alter BMS programing to increase set point Every 1 degree increase from 21 degrees (up to 24), is saving of around 10% of Savings potential: Approximately 3,942 kwh, $ , 3.75 tco 2 p.a. Payback: Approximately 0.57 years Identified HVAC opportunity Link Span Cassette 10kw (Jo s Office)- Switch off between 8pm-6am every day Alter Building Management System (BMS) to switch off between 8pm-6am. After closing of the gallery, there is less heat losses between inside and outside temperatures due to less people traffic in the area. Alter BMS programing to shut off between 8pm-6am per day Every hour the air-conditioner is off, around 5kw electricity energy will be saved for non-occupied areas Savings potential: Approximately 9,855 kwh, $ 1,769.28, 9.36 tco 2 p.a. Payback: Approximately 0.23 years Identified HVAC opportunity Link Span Cassette 10kw (O Conner Entry)- Switch off between 8pm-6am every day Alter Building Management System (BMS) to switch off between 8pm-6am. After closing of the gallery, there is less heat losses between inside and outside temperatures due to less people traffic in the area. Alter BMS programing to shut off between 8pm-6am per day Every hour the air-conditioner is off, around 5kw electricity energy will be saved for non-occupied areas Savings potential: Approximately 9,855 kwh, $ 1,769.28, 9.36 tco 2 p.a. Payback: Approximately 0.23 years 12
14 Identified HVAC opportunity Down Stairs Office Entry Doors- Tint Doors to reduce heat transfer Tinting doors will reduce heat transfer through the glass and reduce the UV transfer into the space. Tint Sculpture Courtyard access door to Lunch room area Tint Sculpture Courtyard access door to Downstairs Office Tinting improves energy cooling efficiencies and reduces energy consumption Savings potential: Approximately 2,957 kwh, $ , 2.81 tco 2 p.a. Estimated capital cost: $ Payback: Approximately 1.53 years Identified HVAC opportunity Jo s Office Windows Tint Windows to reduce heat and allow more natural light Tinting doors will reduce heat transfer through the glass and reduce the UV transfer into the space. Currently Joanne has blinds fitted to reduce the glare and the sun light beaming into the room. If glass if fitted with darker tint, will allow more natural light through, lower glare and reduce the need to have lights on due to the blinds are fully down. Tint Windows to reduce heat and allow more natural light Tinting improves energy cooling efficiencies and reduces energy consumption Lower the need for lights to be on Savings potential: Approximately 2,957 kwh, $ , 2.81 tco 2 p.a. Estimated capital cost: $2, Payback: Approximately 4.14 years Identified HVAC opportunity Downstairs Kitchen Room HWS Reduce time to 8hrs/day (9am-5pm) Only have the hot water system on to suit site usage. Currently site only uses hot water for washing up during normal work hours. Alter Dynalite controller to suit operating hours (9am-5pm) Savings potential: Approximately 9,461 kwh, $ 1,698.55, 8.98 tco 2 p.a. Estimated capital cost: $ Payback: Approximately 0.18 years 13
15 SECTION 5: QUICK WINS & FURTHER SCOPE During the audit we have found other areas where energy efficiency can be improved. Some of them can be implemented just by doing best practice. Closing off areas that are untended to improver cooling efficiencies and cooling losses In periods where no touring arts are stored on site, shut down air-conditioning in storage areas SECTION 6: SUMMARY OF OPPORTUNITIES Based on the walkthrough audit, calculations and our assumptions, there is possibility to make a savings of approximately 12% on overall energy cost annually which equates to approximately $11, Total estimated implementation cost will be $6, with a payback period of approximately 0.58 years. Above Opportunities are listed below in table 5. 14
16 SECTION 7: ASSUMPTIONS Assumptions used in this Audit report are: The Blended electricity unit price is 18 c/kwh inc. GST. A factor of 1 kwh = GJ has been used to convert from kwh to GJ. For Electricity, GHG emission factor of 0.95 kg CO 2-e/kWh SECTION 8: GLOSSARY kw - Kilowatt: a measure of one thousand watts of electrical power GJ - Gigajoule: one thousand million joules GHG Green House Gas: a gas that contributes to the greenhouse effect by absorbing infrared radiation. Carbon dioxide and chlorofluorocarbons are examples of greenhouse gases. HVAC: Heating, Ventilating and Air-conditioning. It is the technology of indoor and vehicular environmental comfort. PF: Power Factor is the ratio of the actual electrical power dissipated by an AC circuit to the product of the r.m.s. values of current and voltage. The difference between the two is caused by reactance in the circuit and represents power that does no useful work. ROI: Return on investment is used to evaluate the efficiency of an investment or to compare the efficiency of a number of different investments. ROI measures the amount of return on an investment relative to the investment s cost. 15
17 Table 5: Summary of Energy Efficiency Opportunities Accuracy +/- 33% Description of Opportunity Group / Area Electricity savings (kwh) p.a. Gas savings GJ p.a. Electricity cost savings ($ p.a.) Total cost Other savings savings ($ p.a. (e.g. maint.) $ p.a. ex. GST) Capital cost $ (ex GST) Simple Payback period (years) GHG savings tonnes CO2 p.a. Energy savings as % of total site consumption Accuracy of estimate (+/-%) FORMULA FORMULA FORMULA FORMULA FORMULA 64kw A/C 10pm-3am Temp Adj in Cold Mths Main Hall % 40% 30kw A/C 10pm-3am Temp Adj in Cold Mths Entry/Hallway % 40% 25kw A/C 10pm-3am Temp Adj in Cold Mths Tower % 40% 25kw A/C 10pm-3am Temp Adj in Cold Mths Store/Loading Room % 40% 20kw A/C 10pm-3am Temp Adj in Cold Mths O'Connor Gallery % 40% 2.5kw Split AC Temp Adj as in office spaces % 20% 3kw Split AC Temp Adj as in office spaces % 20% 8kw Split AC Temp Adj as in office spaces % 20% 10kw Cassette Unit - Temp Adj Jo's Office/Hallway % 40% 10kw Cassette Unit - Temp Adj O'Connor Gallery Entry % 40% 10kw Cassette Unit - Switch off 8pm-6am Jo's Office/Hallway % 20% 10kw Cassette Unit - Switch off 8pm-6am O'Connor Gallery Entry % 20% HWS- Reduce time to 8hrs/day 9am-5pm Downstairs Kitchen % 30% Tint Entry Doors x 2 Downstairs Office Entries % 40% Tint Office Windows Jo's Office/Hallway % 40% % % % % % Sum % 33%
Unit 4: Electricity (Part 2)
Unit 4: Electricity (Part 2) Learning Outcomes Students should be able to: 1. Explain what is meant by power and state its units 2. Discuss the importance of reducing electrical energy wastage 3. State
More informationSubtropical Cities September 2006. Design for Energy Efficiency in Commercial Buildings in Queensland
Subtropical Cities September 2006 Design for Energy Efficiency in Commercial Buildings in Queensland Contents Typical Building Constraints & Requirements Understanding Energy Consumption in Buildings HVAC
More informationBirmingham City Council Author: BCCASNHL. BEST Leaders & Building User Groups
BCCÊs Sustainable Energy Project & Sustainable Schools Programme BCCÊs Sustainable Energy Project Currently, six workstreams to reduce BCCÊs energy consumption by 50% by 2018: 1. Improved Energy Management
More informationEnergy Efficiency: Integrated Design and HVAC Systems HEALTHCARE - TOP 5 GREEN BUILDING STRATEGIES
EPA Publication 909-F-07-001 What? Energy use in healthcare facilities is higher than nearly all other building types. With rising energy costs and climate change concerns energy efficiency is financially
More informationDirect Fresh Air Free Cooling of Data Centres
White Paper Introduction There have been many different cooling systems deployed in Data Centres in the past to maintain an acceptable environment for the equipment and for Data Centre operatives. The
More informationCase Studies: Infrared Heating in Industrial Applications
Case Studies: Infrared Heating in Industrial Applications Chao Chen, Puget Sound Energy ABSTRACT Puget Sound Energy (PSE) is a utility which serves more than one million electric customers and over 700,000
More informationRegatta Wharf. City of Sydney SMART GREEN APARTMENTS LEVEL 2 ENERGY AUDIT REPORT
Regatta Wharf City of Sydney SMART GREEN APARTMENTS LEVEL 2 ENERGY AUDIT REPORT Net Balance Final Report 1/03/2013 Energy Saver Regatta Wharf 1 Energy Saver participant details Name of Apartment Building
More informationA Key Component of Environmental Sustainability Efforts and a Source of Substantial Cost Savings for FCGU. Dr. Simeon Komisar
ENERGY EFFICIENCY : A Key Component of Environmental Sustainability Efforts and a Source of Substantial Cost Savings for FCGU Dr. Simeon Komisar Environmental Sustainability Committee Member Associate
More information5-Minute Primer for Commercial Building Energy Audits
5-Minute Primer for Commercial Building Energy Audits Why Energy Audits? Because an energy audit is the first step to saving energy at your facility. Putting together an energy project can be like finding
More informationEnergy Benchmarking City of New Westminster: Corporate Facilities
UBC Sustainability Scholar Project Report Energy Benchmarking City of New Westminster: Corporate Facilities August 2015 Priyanka R. Chakrabarti UBC Sustainability Scholar 2015 1 Executive Summary Introduction
More informationEnergy efficiency for small business. 19 February 2015
Energy efficiency for small business 19 February 2015 Webinar Facilitator Andrew Chamberlin ecobiz Program Associate Australian Centre for Sustainable Business and Development (ACSBD), University of Southern
More informationNatural gas heating versus split system heating and the current and future viability of the Natural gas network
Natural gas heating versus split system heating and the current and future viability of the Natural gas network Discussion Paper: Energy Consumer Reference Council meeting 7. August 2015 While ActewAGL
More informationProposal prepared for Happy Solar Owner
Happy Solar Owner 1234 Sunny Lane Portland, OR 97201 Mailing Address: Happy Solar Owner 1234 Sunny Lane Portland, OR 97201 RE: SolarWorld Sunkits System Proposal: CASSK-## Presented by: SolarWorld Authorized
More informationTHE ROOFPOINT ENERGY AND CARBON CALCULATOR A NEW MODELING TOOL FOR ROOFING PROFESSIONALS
THE ROOFPOINT ENERGY AND CARBON CALCULATOR A NEW MODELING TOOL FOR ROOFING PROFESSIONALS James L. Hoff, VP of Research Center for Environmental Innovation in Roofing Tools and Models Tools require models
More informationDATA CENTRE DESIGN AND
SPUSC 2008 SOUTH PACIFIC USER SERVICES CONFERENCE DATA CENTRE DESIGN AND ENERGY INITIATIVES Presented by Jarrad Clift Electrical Engineer Greenstar Accredited Presentation Content Data Centres General
More informationAT&T Global Network Client for Windows Product Support Matrix January 29, 2015
AT&T Global Network Client for Windows Product Support Matrix January 29, 2015 Product Support Matrix Following is the Product Support Matrix for the AT&T Global Network Client. See the AT&T Global Network
More informationSino-Italian Environment & Energy Building S I E E B
MOST Ministry of Science and Technology Republic of China Sino-Italian Environment & Energy Building S I E E B Concept The Sino-Italy Environment & Energy Building (SIEEB) is an intelligent, ecological
More informationRules of Thumb Energy Efficiency in Buildings
Energy Efficiency in Buildings Energy Savings Cost Savings Increased Productivity Economic Development Other Standard lighting retrofits: $0.90-$1.20 per square foot. High-efficiency packaged and split
More informationIt s the right time... ... for sustainable development. Paul Westbrook. www.enerjazz.com/house
It s the right time...... for sustainable development Introduction Passive Solar - Passive Solar has a slightly different priority in Texas. We want to capture free heat from the sun in the winter, but
More informationCarbon Project Annual Report
Brock University Carbon Project Annual Report 2013 July 2014 Contents Introduction... 1 Voluntary Reporting: The Carbon Project... 1 Scope of Inventory... 1 Inventory... 2 Moving Forward... 5 Measure...
More informationAIR CONDITIONING EFFICIENCY F8 Energy eco-efficiency opportunities in Queensland Foundries
AIR CONDITIONING EFFICIENCY F8 Energy eco-efficiency opportunities in Queensland Foundries Hot tips and cool ideas to save energy and money! Air conditioning units or systems are often used by foundries
More informationModule 2.2. Heat transfer mechanisms
Module 2.2 Heat transfer mechanisms Learning Outcomes On successful completion of this module learners will be able to - Describe the 1 st and 2 nd laws of thermodynamics. - Describe heat transfer mechanisms.
More informationENERGY MANAGEMENT. for INDUSTRY AND BUSINESS
ENERGY MANAGEMENT for INDUSTRY AND BUSINESS [Principles of Energy Management] Denis Cooke Denis Cooke & Associates Pty Limited Phone + 61 2 9871 6641 Fax +61 2 9614 1723 Email: denis@decoa.com.au Web Site
More informationDraft UCL Heating, Cooling and Ventilation Policy
Draft UCL Heating, Cooling and Ventilation Policy Page 1 of 7 UCL Estates UCL Heating, Cooling & UCL Heating, Cooling and Document Owner UCL Estates Leadership Team is the Owner of this document. Distribution
More informationTHE EUROPEAN GREEN BUILDING PROGRAMME. Technical Module on Combined Heat and Power
THE EUROPEAN GREEN BUILDING PROGRAMME Technical Module on Combined Heat and Power Contents Foreword...1 1. Introduction...2 2. Inventory of the CHP system...3 3. Assessment of technical energy saving measures...5
More informationSTRATEGIC ENERGY MANAGEMENT PLAN FOR NORFOLK GENERAL HOSPITAL 2014
STRATEGIC ENERGY MANAGEMENT PLAN FOR NORFOLK GENERAL HOSPITAL 2014 1 TABLE OF CONTENTS Introduction Energy Management Vision Guiding Principles for Energy Management Business Case for Strategic Energy
More informationUniversity Of Wollongong Main Campus Site Report
ENERGY AUDIT REPORT University Of Wollongong Main Campus Site Report Prepared by Version 5.6 August 2007 Disclaimer: EMET Consultants and its personnel have no financial interests in any equipment or supplier
More informationENERGY SAVINGS FROM SOLAR HEATED WATER IN BULGARIA
ENERGY SAVINGS FROM SOLAR HEATED WATER IN BULGARIA R. Todorova National Institute of Meteorology and Hydrology Blvd.Tzarigradsko shousee 66 Email: Radostina.Todorova@meteo.bg Abstract At the present work
More informationInternational Telecommunication Union SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES IN PUBLIC NETWORKS
International Telecommunication Union ITU-T TELECOMMUNICATION STANDARDIZATION SECTOR OF ITU Technical Paper (13 December 2013) SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES
More informationschool energy consumption assessment
school energy consumption assessment understanding our school s energy use Adapted from EcoSpark s Wattwize: Teacher Guide, Handout #1, available at ecospark.ca. The energy consumption assessment offers
More informationFurther electricity cost increases with the introduction of the Carbon Pollution Reduction Scheme
Responding to electricity cost increases Dr Darren Oemcke, CEO Provisor Karl Forsyth, Principal Provisor Electricity costs have been on the rise with increases this year of between 16% and 36% for Provisor
More informationENERGY AUDITS (OR SURVEYS) & ENERGY MANAGEMENT PROGRAMS SECTION B
ENERGY AUDITS (OR SURVEYS) & ENERGY MANAGEMENT PROGRAMS SECTION B GOALS OF THE ENERGY AUDIT Clearly identify types and costs of energy use Understand how energy is being used--and possibly wasted Identify
More informationCase Study Family Room Renovation 3br family home, Melbourne
Family Room Renovation 3br family home, Melbourne In a Nutshell With time and budget constraints we often renovate just one room at a time. This case study looks at a family room renovation where the key
More informationFuture Megacities in Balance Low Carbon Cities in Making: Masdar City Tobias Fiedler, TRANSSOLAR Energietechnik, Stuttgart
Future Megacities in Balance Low Carbon Cities in Making: Masdar City Tobias Fiedler, TRANSSOLAR Energietechnik, Stuttgart Zeche Zollverein, Essen 11 th of October 2010 TRANSSOLAR Climate Engineering sustainable
More informationDATA CENTER COOLING INNOVATIVE COOLING TECHNOLOGIES FOR YOUR DATA CENTER
DATA CENTER COOLING INNOVATIVE COOLING TECHNOLOGIES FOR YOUR DATA CENTER DATA CENTERS 2009 IT Emissions = Aviation Industry Emissions Nations Largest Commercial Consumers of Electric Power Greenpeace estimates
More informationMailing Address 4650 Adohr Ln. Camarillo, CA 93012. 25 Year Financial Analysis. $1,051 / mo (avg) Cost Breakdown. System Description
Summary Customer Dan Glaser - CASSK-13-00932 SolarWorld USA Site Address 4650 Adohr Ln. Camarillo, CA 93012 Mailing Address 4650 Adohr Ln. Camarillo, CA 93012 Company Contact We turn sunlight into power
More informationEnergy Saving Tips. Adjust set point temperature up a few degrees... Window contact. Occupancy sensor. A Programmable Thermostat
Energy Saving Tips Nowadays when Energy costs are skyrocketing and the awareness to environmental issues is increasing, we all want to reduce energy consumption and have a greener lifestyle. Heating &
More informationUNDERSTANDING YOUR UTILITY BILL A GUIDE FOR BUSINESSES IN INDIANA
UNDERSTANDING YOUR UTILITY BILL A GUIDE FOR BUSINESSES IN INDIANA TABLE OF CONTENTS Introduction... 5 Basic Billing Concepts... 6 Electric Energy and Demand... 6 Electric Consumption and Charges... 7
More informationAir Conditioning. The opportunity for energy efficiency. Low cost actions to reduce energy usage now
Fact Sheet #6 Air Conditioning In this fact sheet you will discover: The opportunity for energy efficiency How air conditioning works Low cost actions to reduce energy usage now Investments to reduce costs
More informationCouncil s energy efficiency upgrades benefit community
Council s energy efficiency upgrades benefit community Project Snapshot Objective: reduce energy, save money & improve comfort in public buildings Where: Meander Valley Council, Northern Tasmania Total
More informationHot Water. Heat pump water heaters. Residential and Commercial R410a
Hot Water Heat pump water heaters Residential and Commercial R410a Heat pump technology Heat Pump Water Heating is a new idea using existing technology and is viewed as the latest generation of water heating
More informationBERRI BARMERA COUNCIL LEVEL 1 ENERGY AUDITS OF SELECTED COUNCIL FACILITIES January 2013
BERRI BARMERA COUNCIL LEVEL 1 ENERGY AUDITS OF SELECTED COUNCIL FACILITIES January 2013 ENVIRONARC PO BOX 56 NORTH ADELAIDE 5006 Telephone: 1300 738 611 Facsimile: (08) 8537 0657 Email: environarc@environarc.com.au
More informationCOMPARISON OF FIXED & VARIABLE RATES (25 YEARS) CHARTERED BANK ADMINISTERED INTEREST RATES - PRIME BUSINESS*
COMPARISON OF FIXED & VARIABLE RATES (25 YEARS) 2 Fixed Rates Variable Rates FIXED RATES OF THE PAST 25 YEARS AVERAGE RESIDENTIAL MORTGAGE LENDING RATE - 5 YEAR* (Per cent) Year Jan Feb Mar Apr May Jun
More informationCOMPARISON OF FIXED & VARIABLE RATES (25 YEARS) CHARTERED BANK ADMINISTERED INTEREST RATES - PRIME BUSINESS*
COMPARISON OF FIXED & VARIABLE RATES (25 YEARS) 2 Fixed Rates Variable Rates FIXED RATES OF THE PAST 25 YEARS AVERAGE RESIDENTIAL MORTGAGE LENDING RATE - 5 YEAR* (Per cent) Year Jan Feb Mar Apr May Jun
More informationEconomic Evaluation of Residential Air Conditioner Designs for Hot and Dry Climates
Economic Evaluation of Residential Air Conditioner Designs for Hot and Dry Climates Arthur Rosenfeld, California Energy Commission Gregory Rosenquist, Lawrence Berkeley National Laboratory C. Keith Rice,
More information1. INTRODUCTION 2. MEASUREMENTS AND METHODS F O R U M
Energy consumption of 1 Australian residential air conditioners Seasonal operating and stand-by energy consumption of air conditioners across Melbourne, Adelaide and Brisbane Andrew Law*, Peter Osman**,
More information8ah: 2xBlue-B ST300L 2.919MW SF56.5% 225L/D. 2,391.9 kwh
Solar Colwood 2013 8ah: 2xBlue-B ST300L 2.919MW SF56.5% 225L/D Location of the system Canada Victoria Longitude: -123.37 Latitude: 48.42 Elevation: 40 m This report has been created by: MD Miroslav Danielka
More informationRe Engineering to a "Green" Data Center, with Measurable ROI
Re Engineering to a "Green" Data Center, with Measurable ROI Alan Mamane CEO and Founder Agenda Data Center Energy Trends Benchmarking Efficiency Systematic Approach to Improve Energy Efficiency Best Practices
More informationRosevilleProject. LoE _ 2 Glass Products. You can reduce your cooling energy usage by 25% or more. Here is the proof.
RosevilleProject Glass Products You can reduce your cooling energy usage by 25% or more. Here is the proof. Hot-Button Issues Residents of California, Arizona, and Nevada don t need a weather forecast
More informationWinter heating This winter heating guide includes ways to reduce heating costs and provides advice on choosing the right heater to suit your needs.
Winter heating This winter heating guide includes ways to reduce heating costs and provides advice on choosing the right heater to suit your needs. Fuel for thought Choosing the right heating system for
More informationOffice of the Government Chief Information Officer. Green Data Centre Practices
Office of the Government Chief Information Officer Green Data Centre Practices Version : 2.0 April 2013 The Government of the Hong Kong Special Administrative Region The contents of this document remain
More informationCorporate Carbon Neutral Plan
This Carbon Neutral Plan will guide the District of 100 Mile House decision making process in terms of reducing corporate energy consumption and greenhouse gas emissions and in achieving carbon neutrality.
More informationProfessional Report. Map section. Location of the system. Valkkinen Longitude: 23.667 Latitude: 61.267 Elevation: 89 m
Puulämmitys 6 x SF3 Location of the system Map section Valkkinen Longitude: 23.667 Latitude: 61.267 Elevation: 89 m This report has been created by: Samppa Takala Samppa Takala Nyrhintie 14 28760 Pori
More informationGreenhouse Gas Implications of HVAC Upgrades in Multi-Unit Residential Buildings
Greenhouse Gas Implications of HVAC Upgrades in Multi-Unit Residential Buildings J A NUARY 2015 INTRODUCTION This Research Report explores best practices and approaches for reducing greenhouse gas (GHG)
More informationCO2 Emissions. Indirect CO 2. Emissions Electricity and Heat Production 25 % Direct Emissions AFOLU 24 % Energy 1,4% Buildings 6,4 % Industry 11 %
CO2 Emissions Direct Emissions AFOLU 24 % Buildings 6,4 % Transport 14 % 49 Gt CO2 eq (2010) Indirect CO 2 Emissions Electricity and Heat Production 25 % Energy 1,4% Industry 11 % Transport 0,3 % Industry
More informationThe main steam enters the building in the basement mechanical room; this is where the condensate line also leaves the building.
MSV: Square Footage: 24,844 No. of Floors: 1 Year Built: 1963 Type of Use: Lounge and dining area open all night for snacks Steam Water-cooled condenser, 50-Ton York unit with a 6 cylinder-reciprocating
More informationCCX Forestry Carbon Offset Programs
CCX Forestry Carbon Offset Programs Status of the U.S. Carbon Market A developing, voluntary market No national, regulatory greenhouse gas reduction scheme YET! Many local, state, and regional systems
More informationEnhanced Vessel Traffic Management System Booking Slots Available and Vessels Booked per Day From 12-JAN-2016 To 30-JUN-2017
From -JAN- To -JUN- -JAN- VIRP Page Period Period Period -JAN- 8 -JAN- 8 9 -JAN- 8 8 -JAN- -JAN- -JAN- 8-JAN- 9-JAN- -JAN- -JAN- -JAN- -JAN- -JAN- -JAN- -JAN- -JAN- 8-JAN- 9-JAN- -JAN- -JAN- -FEB- : days
More informationUBC Social Ecological Economic Development Studies (SEEDS) Student Report. Project on server room management. Yu Chen Wang, Auburn Leung
UBC Social Ecological Economic Development Studies (SEEDS) Student Report Project on server room management Yu Chen Wang, Auburn Leung University of British Columbia EECE 496 April 7, 2013 Disclaimer:
More informationTransmission System Total Cost of Ownership
Transmission System Total Cost of Ownership February 2013 Featuring GatesAir s Geoff Mendenhall Technology Advisor Copyright 2015 GatesAir, Inc. All rights reserved. Transmission System - Total Cost of
More informationAPES Math Review. For each problem show every step of your work, and indicate the cancellation of all units No Calculators!!
APES Math Review For each problem show every step of your work, and indicate the cancellation of all units No Calculators!! Scientific Notation All APES students should be able to work comfortably with
More informationGlossary of Heating, Ventilation and Air Conditioning Terms
Glossary of Heating, Ventilation and Air Conditioning Terms Air Change: Unlike re-circulated air, this is the total air required to completely replace the air in a room or building. Air Conditioner: Equipment
More informationCarbon Footprint Calculator for Royal Society of Arts
Carbon Footprint Calculator for Royal Society of Arts This Carbon Calculator has been produced for Royal Society of Arts to enable the company to better understand its environmental performance in terms
More informationConserve Insight Energy Use Monitor. User Guide
Conserve Insight Energy Use Monitor User Guide Find out how much energy your devices really use including watts, the cost of operation, and the amount of carbon dioxide (CO 2 ) produced in generating the
More informationHeat Recovery from Data Centres Conference Designing Energy Efficient Data Centres
What factors determine the energy efficiency of a data centre? Where is the energy used? Local Climate Data Hall Temperatures Chiller / DX Energy Condenser / Dry Cooler / Cooling Tower Energy Pump Energy
More informationBuilding Performance Optimization Services in the city of Boras, Sweden.
Building Performance Optimization Services in the city of Boras, Sweden. Siemens Building Technologies Johny Hjerpe +46317276103 Johny.hjerpe@siemens.com Summary In 2002 the Siemens branch office of Gothenburg
More informationUNDERSTANDING YOUR UTILITY BILL A GUIDE FOR BUSINESSES IN OHIO
UNDERSTANDING YOUR UTILITY BILL A GUIDE FOR BUSINESSES IN OHIO TABLE OF CONTENTS INTRODUCTION Introduction... 3 Basic Billing Concepts... 4 Customer Choice Programs... 4 Gas Consumption and Charges...
More informationEnergy Efficiency Opportunities in Federal High Performance Computing Data Centers
Energy Efficiency Opportunities in Federal High Performance Computing Data Centers Prepared for the U.S. Department of Energy Federal Energy Management Program By Lawrence Berkeley National Laboratory
More informationRetrofit HVAC. Heating, Ventilation, and Air Conditioning Services
Retrofit HVAC Heating, Ventilation, and Air Conditioning Services Mission Reach home owners seeking low cost HVAC repair and maintenance. Provide low cost, quality HVAC services to home owners within the
More informationEnergy Efficiency, Clean Power as Engine for Sustainable Growth
Energy Efficiency, Clean Power as Engine for Sustainable Growth Rakesh Kumar Bhatnagar, Advisor (Technology), & P K Panigrahi, Sr. DDG, Department of Telecommunications, Government of India. 1 Agenda 2
More informationAnalysis One Code Desc. Transaction Amount. Fiscal Period
Analysis One Code Desc Transaction Amount Fiscal Period 57.63 Oct-12 12.13 Oct-12-38.90 Oct-12-773.00 Oct-12-800.00 Oct-12-187.00 Oct-12-82.00 Oct-12-82.00 Oct-12-110.00 Oct-12-1115.25 Oct-12-71.00 Oct-12-41.00
More informationENERGY SAVINGS ACTION PLAN 2014 2018
Environment Unit ENERGY SAVINGS ACTION PLAN 2014 2018 LISA MILLER ENVIRONMENT MANAGER JOHN HAZELTON ENERGY & WATER SUSTAINABILITY PROJECTS ENGINEER FACILITIES MANAGEMENT DIVISION MAY 2014 APPROVED BY:
More informationTranslating the need for energy, water and food dynamics in security analysis as well as in operational and tactical implementation
Translating the need for energy, water and food dynamics in security analysis as well as in operational and tactical implementation Senior Analyst Annica Waleij annica.waleij@foi.se Swedish Defence Research
More informationCommunicating Your Commitment: Your Guide to Clean Energy Messaging
Communicating Your Commitment: Your Guide to Clean Energy Messaging Congratulations on your recent purchase of clean energy from Renewable Choice! Whether you ve purchased green power in the form of renewable
More informationInfrastructure & Cities Sector
Technical Article Infrastructure & Cities Sector Building Technologies Division Zug (Switzerland), October 18, 2011 Saving Energy in a Data Center A Leap of Faith? New guidelines from ASHRAE (American
More informationDataCenter 2020: first results for energy-optimization at existing data centers
DataCenter : first results for energy-optimization at existing data centers July Powered by WHITE PAPER: DataCenter DataCenter : first results for energy-optimization at existing data centers Introduction
More informationHVAC. Kitchen Exhaust. rooftop equipment! let s drop on a few exhaust fans! it doesn t get easier!
HVAC & Kitchen Exhaust The Heart of Restaurant HVAC rooftop equipment! let s drop on a few exhaust fans! it doesn t get easier! 1 CKV Design: Just not that easy! There is no piece of equipment in the commercial
More informationcarbon neutral update April 2008
carbon neutral update April 2008 With almost 25,000 employees and around 1,000 buildings within Australia, NAB s carbon footprint is substantial. Most of our direct environmental impacts result from the
More informationCommercial Building Energy Initiative Tenant Business Case
Commercial Building Energy Initiative Tenant Business Case April 2010 An initiative of the Greater Toronto CivicAction Alliance The business case for GTA tenants Why to invest in energy efficiency programs
More informationNewfoundland and Labrador Hydro Electricity Rates
Newfoundland and Hydro Electricity Rates The following charts and descriptions outline: 1) residential rates by area 2) general service rates information including basic customer charges, energy charges,
More informationResources for School Energy Managers
Resources for School Energy Managers Cooling can present a substantial energy cost to schools. Temperatures of 24 to 27 C with less than 60% relative humidity give acceptable comfort in summer. Higher
More informationImproving comfort and energy efficiency in a nursery school design process S. Ferrari, G. Masera, D. Dell Oro
Improving comfort and energy efficiency in a nursery school design process S. Ferrari, G. Masera, D. Dell Oro Dept. Building Environment Science &Technologies Politecnico di Milano Italy Research funded
More informationDallas/Fort Worth International Airport District Energy Plant Upgrades Project Making More with Less Sustainable Communities Conference Dallas, TX
Dallas/Fort Worth International Airport District Energy Plant Upgrades Project Making More with Less Sustainable Communities Conference Dallas, TX March 10, 2009 Agenda DFW Capital Development Program
More informationNorth American Centre 5650 & 5700 Yonge Street, Toronto Greenhouse Gas Inventory Report
5650 & 5700 Yonge Street, Toronto Greenhouse Gas Inventory Report June 19, 2013 Page 1 TABLE OF CONTENTS 1 SUMMARY 2 2 PURPOSE 3 3 ORGANIZATION PROFILE 3 4 GHG INVENTORY BOUNDARIES 5 4.1 Organizational
More informationCase Study. Commercial Building Energy Efficiency Retrofit 4 Mort Street, Canberra. Results. Background PEOPLE PRACTICES SYSTEMS
Case Study PEOPLE PRACTICES SYSTEMS Commercial Building Energy Efficiency Retrofit 4 Mort Street, Canberra In 2010, 4 Mort St, Canberra (Figure 1) was upgraded to significantly improve its energy performance.
More informationHIGH LEVEL BUSINESS CASE FOR AN EEMS SYSTEM
HIGH LEVEL BUSINESS CASE FOR AN EEMS SYSTEM Christine Dennehy, Project Manager Todd Isherwood, Energy Manager Joseph LaRusso, Finance Manager City of Boston Bill Kosik Munther Salim Hewlett-Packard August
More informationHEATING, VENTILATION & AIR CONDITIONING
HEATING, VENTILATION & AIR CONDITIONING as part of the Energy Efficiency Information Grants Program Heating and cooling can account for approximately 23 % of energy use in pubs and hotels 1. Reducing heating
More informationMetering for today s systems
Metering for today s systems The sub-meter gathers data on the building side of the utility company meter. This allows us to break out usage so data can be collected from individual circuits, a single
More informationENERGY SAVING BY COOPERATIVE OPERATION BETWEEN DISTRICT HEATING AND COOLING PLANT AND BUILDING HVAC SYSTEM
Proceedings of Building Simulation 211: ENERGY SAVING BY COOPERATIVE OPERATION BETWEEN DISTRICT HEATING AND COOLING PLANT AND BUILDING HVAC SYSTEM Yoshitaka Uno 1, Shinya Nagae 1, Yoshiyuki Shimoda 1 1
More informationDesign Guide. Managing Peak Energy Demand In Live Performance Venues
Design Guide Managing Peak Energy Demand In Live Performance Venues Peak demand; the highest amount of electricity consumed at any one time, has a major impact on network charges and has a considerable
More informationGeorgian Bay General Hospital Strategic Energy Management Plan 2014
Georgian Bay General Hospital Strategic Energy Management Plan 2014 TABLE OF CONTENTS TABLE OF CONTENTS... 2 INTRODUCTION... 3 ENERGY MANAGEMENT VISION... 4 GUIDING PRINCIPLES FOR STRATEGIC ENERGY MANAGEMENT...
More informationTAV Tunisie FIFTH INTERNATIONAL FORUM ON ENERGY FOR SUSTAINABLE DEVELOPMENT. International Airport Enfidha-Hammamet 4-7 November 2014
TAV Tunisie FIFTH INTERNATIONAL FORUM ON ENERGY FOR SUSTAINABLE DEVELOPMENT International Airport Enfidha-Hammamet 4-7 November 2014 PRESENTATION OF THE INTERNATIONAL AIRPORT ENFIDHA-HAMMAMET CO2 EMISSIONS
More informationEnergy Awareness for Success
Insert logo here Energy Awareness for Success Presented by Leeanne Timony MSc Environmental Engineer Nypro Healthcare Ireland COMMUNICATION ENCOURAGEMENT ENGAGEMENT LISTENING SUPPORT Effective Awareness
More informationDaikin Altherma Hybrid Heat Pump
your comfort. our world. Daikin Altherma Hybrid Heat Pump The natural combination Heating Integrated Solutions Ventilation Air Conditioning Refrigeration About Daikin Forward thinking... Daikin has a worldwide
More informationSea Water Heat Pump Project
Sea Water Heat Pump Project Alaska SeaLife Center, Seward, AK Presenter: Andy Baker, PE, YourCleanEnergy LLC Also Present is ASLC Operations Manager: Darryl Schaefermeyer ACEP Rural Energy Conference Forum
More informationGet Ready For The One Tonne Action Challenge!
Get Ready For The One Tonne Action Challenge! Read through the four elements of the one-tonne challenge - making a difference is easier than you think!! Watt's It All About? As our demand for electricity
More informationQuestions to be responded to by the firm submitting the application. Why do you think this project should receive an award? How does it demonstrate:
Questions to be responded to by the firm submitting the application Why do you think this project should receive an award? How does it demonstrate: innovation, quality, and professional excellence transparency
More informationEnergy at Home ENERGY USE AND DELIVERY LESSON PLAN 3.6. Public School System Teaching Standards Covered
ENERGY USE AND DELIVERY LESSON PLAN 3.6 Energy at Home This lesson is designed for 3rd 5th grade students in a variety of school settings (public, private, STEM schools, and home schools) in the seven
More informationAshley Institute of Training Schedule of VET Tuition Fees 2015
Ashley Institute of Training Schedule of VET Fees Year of Study Group ID:DECE15G1 Total Course Fees $ 12,000 29-Aug- 17-Oct- 50 14-Sep- 0.167 blended various $2,000 CHC02 Best practice 24-Oct- 12-Dec-
More informationCase 2:08-cv-02463-ABC-E Document 1-4 Filed 04/15/2008 Page 1 of 138. Exhibit 8
Case 2:08-cv-02463-ABC-E Document 1-4 Filed 04/15/2008 Page 1 of 138 Exhibit 8 Case 2:08-cv-02463-ABC-E Document 1-4 Filed 04/15/2008 Page 2 of 138 Domain Name: CELLULARVERISON.COM Updated Date: 12-dec-2007
More information