1 HVAC Preventative Maintenance Basics Presented by Mike Crawley
2 Air Handlers/Package Units: Coils have to be clean! The main purpose of any coil is to absorb or reject heat If coils are dirty; air flow is restricted and minimal heat exchange is taking place Evaporator Coils Need to change filters on a quarterly basis Rule of thumb: 1.5 square foot of filter for each ton of capacity On a RTU refrigerating system poor heat exchange can lead to: freezing up, liquid flood back to compressor, and blocked air flow in which all can damage compressor 2
3 Air Handlers/Package Units: Condenser Coils Air cooled condenser units will set outside They need to be cleaned at least once a year depending on location Higher condenser temps can lead to hot gas entering metering device and evaporator. Over a long period of time, oil breakdown can occur. The lubricity becomes thinner as the oil heats up. The low viscosity can cause compressor failure Belts Belts need to be properly aligned with a straight edge or a string pulled tight on a multi-grooved variable pitch pulley Misalignment can be destructive to belts and pulleys wich can groove the pulley and wear out the belt 3
4 Air Handlers/Package Units: Belt tension is very important! Rule of thumb: Tension needs to be approximately 1/64 of an inch deflection for every inch from shaft center to shaft center Belt conversion Note 1: 4L belt to A belt = the length of the 4L belt - 2 = A belt Belt conversion Note 2: 5L belt to B belt = the length of the 5L belt 3 = B belt 4
5 Air Handlers/Package Units: Grease Motors and bearings all need grease or oil. Metal to metal contact is not good How much and what kind of grease? There is no rule of thumb for grease amount. Consulate bearing manufacturer. You can grease a ball bearing until you see a slight amount of grease around the seal Grease type: typically a NLGI2 (national lubricant grease institute) is recommended for roller bearings 5
6 Air Handlers/Package Units: Electrical All units have various forms of electricity from throw away relays and contactors to large serviceable starters Check for: corrosion, burnt wires, bubbled insulation, discoloration With electricity locked out tagged out, check for: snug (not Godzilla tight) fittings consult the manufacturer for torque values. Unlike conductors (ie:copper to aluminum) should have anti-oxidant compound Electrical also needs to be clean! Use dry nitrogen at low pressure Don t use a hose off the air compressor receiver tank. Moisture and oil may get into components Dust and grime can get in and cause over heating on starters Serviceable starter can be cleaned with contact cleaner Some pitting is okay and normal, needs to be monitored Large motors 20HP+ can be megged A megger is a hand-crank or push button DC volt generator. DC volts are used because it is easier to control 6
7 Air Handlers/Package Units: Drain Pans Cleaning will help deodorize most smells. Pan tabs and pads will help Debris can build up and block drainage Drain lines need to have correct fall P-traps need to be vented on the leaving side of the trap Pan seal can be used to coat older more rusted out pans Blow through coils - no need for trap Draw through coils - have to be trapped 7
8 Pumps Pumps are broken down into many categories. The HVAC industry generally deals with centrifugal pumps End suction pumps, close coupled pumps, and split case pumps dominate the industry Pumps have to be level Check pump coupling for wear Check for shaft seal leaks Pump alignment is important Pumps can be aligned by three methods: Feeler gauges and a straight edge A dial indicator rim and face method And laser alignment 8
9 Pumps Keep logs of pressures Head = PSI x 2.31 / specific gravity (specific gravity of water is = 1.0) You need to make sure you maintain a net positive head Exercise isolation valves Grease bearings Check starters Clean strainers on cooling tower applications 9
10 Chillers Chillers are a major investment for a facility and are costly to maintain. An in depth maintenance program can increase reliability Facilities with a thorough PM, have found for every dollar invested in maintenance they save $10 in operating cost Daily logs can help you trend pressures, temps, etc. Inspections can be set-up as three quarterly run inspections and one comprehensive e e annual inspection 10
11 Chillers Heat exchangers Air cooled chillers condensing coils should be cleaned regularly Water cooled chillers tubes should be brushed annually Note:.002 of fowling will reduce efficiency by 20% Anodes should be changed annually or depending on condition Eddy Current analysis should be performed every 3 years or as needed to both condenser bundles and evaporator bundle 11
12 Chillers Oil testing can be performed on an annual basis on large centrifugal and screw chillers Oil testing is a useful tool in determining internal conditions of a compressor Reciprocating and scroll compressors generally require a field acid test Oil filters changed manufacturers specifications Leak checking chillers All chillers should be leak checked annually Water flow must be maintained through the barrels Low/High water flow=poor heat exchange Purge Units low pressure chillers Monitor pump out minutes Check for proper operation Change filters annually 12
13 Chillers Starters Electrical must be tight and clean Contact points must be inspected and cleaned annually Change the VFD or SSS coolant on manufacturers recommendations Motor terminals must be secure in a dry environment Motors should be megged annually 13
14 Chillers Panels Safeties should be tested annually Sensors and transducers should be tested and calibrated on each visit Wiring should be neat and secure Flow switch operation should be checked annually Parameters need to be logged and maintained Refrigerant and oil circuit should be logged and maintained Predictive maintenance for chillers Vibration analysis Infra red testing Open rotor bar test Oil analysis Eddy current testing 14
15 Cooling Towers Water treatment is very important with towers To prevent scale corrosion sludge and biological growth Conductivity should be high Monitor blow down solenoid Blow down is used to re-circulate water to drain dissolved solids Make up water valve Ensure proper water level is in tower basin (3 to 4 inches below overflow pipe) Tower fans can be either belt driven or gear box driven Grease bearings Inspect belts and sheaves Inspect gear box oil level change annually Oil samples and vibration analysis can be performed on the gear boxes Keep tower inlet screens clean Inspect hot deck and spray headers 15
16 Cooling Towers Towers should be cleaned annually and inspected on a daily basis as well as a quarterly Inspect all electrical connections and disconnects Have motors tested Freeze protection Basin heaters maintained Exposed piping should be insulated with heat trace Make up water line should also be insulated with heat trace Tower by-pass must be checked in seasonal weather 16
17 Pneumatics Heart of pneumatics is the air compressor Air compressor has five components: Motors Pumps Receiver Tank PE switches Alternating Relays on duplex machine 17
18 Pneumatics Inspections: Intake filter; monthly Change filter annually or sooner depending on environment Piping Check for air leaks Relief valve Check for proper operation Oil llevell Change oil twice a year Note: any 30 weight non detergent oil will work, do not use synthetic Verify belt condition, alignment, and grease motor bearings 18
19 Pneumatics Inspect electrical Starters, PE switches, and alternating relays for proper operations and condition Blow down Important to verify moisture and oil removal from tank Inspect coalescing oil removal filter Inspect bypass Air dryer Ensure condensers are clean and compressor is operating Check the operation of the dryer every six months Maintain a main air pressure of 20 PSI 19
20 Pneumatics Thermostats and VAV boxes All Pneumatic thermostats are different Thermostats are sensitive, if adjusted to much calibration will be thrown off Fan power boxes can be inspected each season PE switches, heat strips, return fan motors should all be checked Equation for percent run time; see attachment 20
21 VFD Notations Common to most HVAC equipment Keep a copy of all start-up parameters Important to note any changes that are made Once every six months VFDs should be shut down so that the electrical can be inspected, tightened, and the drive blown out with air in a can or by dry nitrogen under low pressure Check the cooling fan for operation VFDs can damage older non-inverter rated motors Inverter rated motors can handle higher voltage spikes (from VFD) and run at lower speeds which h can overheat older motors damaging bearing etc Bearing fluting is not a myth Occurs when Eddy Currents from the drive operations take a path to ground on the bearings Some ways to counter this are to make sure drive is installed and grounded properly a grounding brush can also be installed in the motor to shield unwanted currents 21
Attachment J-C18.1. HVAC Work Instructions
. RFP: Attachment J-C18.1 HVAC Work Instructions NNC13ZFD017J SOW Item No. Title Page C18-02 Control Air Systems Annual PM 2 C18-03 Split System AC Indoor Section Annual PM 3 C18-04 Condensing Unit Semi-Annual
More informationEvaluate, Clean, and Tune Guidance
Evaluate, Clean, and Tune Guidance The Evaluate, Clean and Tune (ECT) process serves three essential purposes in the Weatherization Assistance Program (WAP). The first is to evaluate the existing system
More informationTrouble Shooting. Pump
Trouble Shooting Pump Trouble Possible Cause Remedy Oil leaking in the area of water pump crankshaft Worn crankshaft seal, bad bearing, grooved shaft, or failure of retainer o-ring. Excessive play on crankshaft
More informationAction Plan Template HVAC Page 1
Action Plan Template HVAC Page 1 Once Establish expected HVAC system efficiency - Write down the expected efficiency of HVAC systems to use as a baseline - Add this information to maintenance plan documentation
More informationSECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM
SECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Packaged rooftop air conditioning unit (5 tons and smaller). 2. Roof curb. 1.2
More informationASHRAE Boston Chapter Meeting Designing AC Refrigeration Systems Lessons Learned February 11, 2014
ASHRAE Boston Chapter Meeting Designing AC Refrigeration Systems Lessons Learned February 11, 2014 Explanation of the refrigeration cycle. Compressors. Benefits and operating characteristics. -Reciprocating
More informationTable V. Troubleshooting Checklist for Refrigeration Systems. Air or non-condensable gas in system. Inlet water warm.
Table V Troubleshooting Checklist for Refrigeration Systems TROUBLE POSSIBLE CAUSE CORRECTIVE MEASURE High condensing pressure. Low condensing pressure. Air or non-condensable gas in system. Inlet water
More informationREQUEST FOR BIDS 2013-12 HVAC PREVENTATIVE MAINTENANCE AND SERVICE JANUARY 18, 2013. Issued by: NH Liquor Commission. PO Box 503, Concord, NH 03302
REQUEST FOR BIDS 2013-12 HVAC PREVENTATIVE MAINTENANCE AND SERVICE JANUARY 18, 2013 Issued by: NH Liquor Commission PO Box 503, Concord, NH 03302 This Page intentional left blank TABLE OF CONTENTS EXHIBITS...
More informationOil and Coolant Circulating Heating System. Model - OCSM
Oil and Coolant Circulating Heating System Model - OCSM Installation & Operation Manual 216280-000 REV 2 Identifying Your System The HOTSTART heating system is designed to heat fluids for use in marine
More informationSECTION 15750 PACKAGED ROOFTOP AIR CONDITIONING UNITS
SECTION 15750 PART 1 - GENERAL 1.01 DESCRIPTION A. Section includes requirements for roof mounted, self-contained units, with electric cooling, and electric or reverse refrigeration cycle (heat pump) heating
More informationHow much do you know about HVAC? Try testing yourself with the following questions and then take a look at the answers on the following page.
Demystifying HVAC Test Your HVAC Knowledge By Ron Prager How much do you know about HVAC? Try testing yourself with the following questions and then take a look at the answers on the following page. 1)
More informationCDS TROUBLESHOOTING SECTION I. VACUUM. 1.0. Weak vacuum at wand. Gauge reads normal (10hg to 14hg)
CDS TROUBLESHOOTING SECTION I. VACUUM 1.0. Weak vacuum at wand. Gauge reads normal (10hg to 14hg) 1.1. Clogged hoses or wand tube. Disconnect hoses and carefully check for an obstruction. 1.2. Excessive
More informationUSF St. Petersburg Operations & Maintenance of Facilities Preventative Maintenance Guide
USF St. Petersburg Operations & Maintenance of Facilities Preventative Maintenance Guide GUIDE EQUIPMENT TYPE & TASKS FREQUENCY A-1 Air Dryer 1. Lubricate valves and replace packing, if necessary 2. Check
More informationTraining Syllabus to Instruct/Prepare for the ASE Transit Bus HVAC Test
APTA STANDARDS DEVELOPMENT PROGRAM RECOMMENDED PRACTICE American Public Transportation Association 1666 K Street, NW, Washington, DC, 20006-1215 APTA BTS-BMT-RP-001-10 Approved October, 2010 APTA Bus Maintenance
More informationPreventive Maintenance. State Energy Assessment Workshop By: DTE Energy Partnership & Services
Preventive Maintenance State Energy Assessment Workshop By: DTE Energy Partnership & Services Do you know? World wide research has shown that one of the reasons causing 80% of the accidents is deficient
More informationSWIMMING POOL HEAT PUMP
SWIMMING POOL HEAT PUMP Installation & User Manual Model HP40B HP50B HP65B Hayward Pool Products Canada, Inc. T: 1-888-238-7665 www.haywardpool.ca CONTENT I. Application 4 II. Features 4 III. Technical
More informationSPECIFICATION TECHNICAL AIR-CONDITIONING UNITS SINGLE AND SPLIT (DUCTED) (AIR COOLED PACKAGED UNIT)
SPECIFICATION TECHNICAL AIR-CONDITIONING UNITS SINGLE AND SPLIT (DUCTED) (AIR COOLED PACKAGED UNIT) MAINTENANCE TYPE: STATUTORY 1.0 SCOPE OF SERVICES The Contractor shall provide maintenance Services for
More informationCentrifugal Water Chillers. Scott Meyerkord
Centrifugal Water Chillers Scott Meyerkord Trane Account Manager Chilled Water System absorption centrifugal helical-rotary Centrifugal Water Chillers Centrifugal Water Chillers Components components of
More informationPLP - TERMS AND CONDITIONS
PLP - TERMS AND CONDITIONS 2014-2015 Philadelphia Gas Works Residential Parts & Labor Plan Contract This Residential Parts & Labor Plan Contract (this Plan ) is available to customers of the Philadelphia
More informationDESIGN STANDARDS SECTION 23 60 00
PART 1 - GENERAL 1.01 Work included: A. Piping, tubing and fittings. B. Piping specialties. C. Special duty valves. D. Refrigerants. E. Chillers. F. Refrigerant monitors. 1.02 General requirements: A.
More informationTable Z. Troubleshooting Chart for Air Conditioners. Cause
Troubleshooting Chart for Air Conditioners Type of Unit Complaint Cause With open-type compressor Electric motor will not start Power failure Check circuit for power source Compressor stuck Locate cause
More informationMedical Air Systems: Scroll
GENERAL The Chemetron skid mount scroll medical air system is designed to provide medical breathing air for hospital and medical institutions. This system meets NFPA 99 requirements for Level 1 breathing
More informationHEAT PUMP FREQUENTLY ASKED QUESTIONS HEAT PUMP OUTDOOR UNIT ICED-UP DURING COLD WEATHER:
HEAT PUMP FREQUENTLY ASKED QUESTIONS HEAT PUMP OUTDOOR UNIT ICED-UP DURING COLD WEATHER: It is normal for a heat pump to have a build up of white frost on the outside coil during cold damp weather. The
More informationFederal Wage System Job Grading Standards for Air Conditioning Equipment Operating, 5415. Table of Contents
Federal Wage System Job Grading Standards for Air Conditioning Equipment Operating, 5415 Table of Contents WORK COVERED... 2 WORK NOT COVERED...2 TITLES... 2 GRADE LEVELS... 2 HELPER AND INTERMEDIATE JOBS...
More informationHVAC Checklist - Long Form
HVAC Checklist - Long Form Page 1 of 14 Appendix B discusses HVAC system components in relation to indoor air quality. utside Air Intake Location pen during occupied hours? Unobstructed? Standing water,
More information3620 W 11th Streetб Houston, TX 77008 Telephone: 713-635-6291 Email: sales@kellogg-american.com Website: www.kellogg-american.com
Unpackaging & Handling Be sure to carefully inspect the unit before accepting the shipment. If any damage has occurred document it with the trucking company immediately. Contact your Kellogg Distributor
More informationA Guide to Trouble-Free Cooling Towers
A Guide to Trouble-Free Cooling Towers A basic understanding of cooling tower operation and maintenance will help keep a cooling water system running in top condition, year after year By David M. Suptic
More informationHow To Design A Refrigeration System
AIRAH Refrigeration (in HVAC) Back to Basics For the First Time Terms of Reference What this session is NOT about Detailed Refrigeration Design Detailed analysis of various Refrigants properties Comparison
More informationConsortiwm Awdurdodau Lleol Cymru Consortium Local Authorities Wales
Consortiwm Awdurdodau Lleol Cymru Consortium Local Authorities Wales SPECIFICATION FOR LAUNDRY EQUIPMENT MAINTENANCE Maintenance Module 32 March 2011 issue This document has been compiled by the Engineering
More informationHydraulic Trouble Shooting
Hydraulic Trouble Shooting Hydraulic systems can be very simple, such as a hand pump pumping up a small hydraulic jack, or very complex, with several pumps, complex valving, accumulators, and many cylinders
More informationGLYCOL CHILLER SYSTEM TROUBLESHOOTING 101
GLYCOL CHILLER SYSTEM TROUBLESHOOTING 101 By Jim VanderGiessen Jr, Pro Refrigeration Inc. There is a good chance your glycol chiller system is often completely forgotten about, until that dreaded day you
More informationENGINE COOLING SYSTEM
ENGINE COOLING SYSTEM 1988 Toyota Celica 1987-88 TOYOTA Engine Cooling Systems Celica DESCRIPTION The basic liquid cooling system consists of a radiator, water pump, thermostat, cooling fan, pressure cap,
More informationLife Cycle Costing Analysis of Water-cooled Chillers. Chillventa Nuremburg, Germany
Life Cycle Costing Analysis of Water-cooled Chillers Chillventa Nuremburg, Germany Spring 2012 Description Life Cycle Cost Analysis is a method of determining and comparing the total costs of investment
More information1.2 Refrigerant Equipment. General
Part 1 General 1.1 Summary.1 Unless otherwise indicated, follow the standards below when specifying heating, ventilation and air conditioning (HVAC) work. These standards are not intended to restrict or
More informationAir Conditioner Water Heater - A Product of HotSpot Energy LLC
Air Conditioner Water Heater - A Product of HotSpot Energy LLC PLEASE READ THIS BEFORE YOU INSTALL THE UNIT 1. This air conditioner must be installed and/or repaired by a qualified technician. If you perform
More informationHeating, Ventilation, Air Conditioning and Refrigeration (HVACR)
Heating, Ventilation, Air Conditioning and Refrigeration (HVACR) I. Demonstrate safety skills in typical HVACR work situations to NATE Core Installer Knowledge Areas for Technician Excellence for Safety
More informationNational Competency Based Skill Training Refrigeration and Air-conditioning Mechanic Logbook
National Competency Based Skill Training Refrigeration and Air-conditioning Mechanic Logbook Trainee:... Training Provider:... Year:... Trainee Contact no:... Competency Based Skill Training Logbook Introduction
More informationWhy is my air conditioner dripping on my customers?
De-Mystifying HVAC Why is my air conditioner dripping on my customers? By Ron Prager One of the most frequent emergency service requests is a call for an air conditioner leaking water into the store. These
More informationPresented By: WALTER E. JOHNSTON, PE CEM, CEA, CLEP, CDSM, CPE <walterjohnston@bellsouth.net
Presented By: WALTER E. JOHNSTON, PE CEM, CEA, CLEP, CDSM, CPE
More informationFirst irst Co. Products
First irst Co. Products Recommended Maintenance Program PM1193 FIRST OPERATIONS,LP - P.O. Box 270969 - Dallas, Texas 75227 - www.firstco.com Table of Contents Introduction... 3 General Precautions... 3
More informationIt will be available soon as an 8.5 X 11 paperback. For easier navigation through the e book, use the table of contents.
The System Evaluation Manual and Chiller Evaluation Manual have been revised and combined into this new book; the Air Conditioning and Refrigeration System Evaluation Guide. It will be available soon as
More informationHVAC Claims: Repair vs. Replacement
HVAC Claims: Repair vs. Replacement Curtis M. VanNess Field Operations Manager Outline Brief history of HVAC How do HVAC systems work? Types of systems and equipment Causes of failure Repair vs. Replace
More informationCompressor Service & Maintenance Manual
Compressor Service & Maintenance Manual C Series COMPRESSOR (D)C1103 (D)C1203 (D)C2106 (D)C2206 (D)C3210 Copyright 2006 DCI. All Rights Reserved. 92311, Rev. C, 08/13 1 C1000 Series Service & Maintenance
More informationPANASONIC TROUBLE SHOOTING GUIDE
A General Guide To Room Style Products Pipework Pipe sizes and lengths should be as the relevant Technical Guide Both lines should be insulated No line accessories or oil traps should be fitted In cooling
More informationMAC-120HE-01 Air-Cooled Chiller
MAC-120HE-01 Air-Cooled Chiller 10 Ton / 120,000 BTUH Air-Cooled Chiller 208/230-1-50/60 1 HVAC Guide Specifications Air-Cooled Liquid Chiller Nominal Size: 10 Tons Multiaqua Model Number: MAC-120HE-01
More informationChilled Water HVAC Systems
Chilled Water HVAC Systems By Ron Prager, Brinco Mechanical Services, Inc. Types of water based systems: There are three types of HVAC systems that utilize water as a heat transfer medium. The first system,
More informationADDENDUM NO. 1 TO THE BIDDING DOCUMENTS. HVAC SERVICE AND MAINTENANCE Saint Clair County MidAmerica Saint Louis Airport.
ADDENDUM NO. 1 TO THE BIDDING DOCUMENTS DATE: May 6, 2016 HVAC SERVICE AND MAINTENANCE Saint Clair County MidAmerica Saint Louis Airport BIDS CLOSE: May 12, 2016, at 2:30 p.m., Local Time TO ALL BIDDERS
More informationCOMPRESSED AIR DRYER
COMPRESSED AIR DRYER Model 40211 ASSEMBLY and OPERATING INSTRUCTIONS 3491 Mission Oaks Blvd., Camarillo, CA 93011 Visit our Web site at http://www.harborfreight.com Copyright 2002 by Harbor Freight Tools.
More informationA. Section includes air conditioning units, controls and control panels.
SECTION 23 81 23 - COMPUTER-ROOM AIR-CONDITIONERS PART 1 - GENERAL 1.1 SUMMARY A. Section includes air conditioning units, controls and control panels. 1.2 REFERENCES A. Air-Conditioning, Heating, and
More informationFlushing and Cleaning the A/C System
Flushing and Cleaning the A/C System Once an AC system has been contaminated or has suffered a failure, the most important part of the AC service to restore the cooling performance to the system = FLUSHING
More informationPreventive Maintenance. Learning Objectives: Howdy! Learning Objectives Cont:
Preventive Maintenance Fountain of Youth for HVAC Successful Learning Environment Bonus Strategies James D. McClure, P.E. Action Planning Guide As you listen to this presentation, use the chart in your
More informationB.C. Buildings Corporation. Mandatory Preventive Maintenance Standard. To Meet Section 4.78 of the WCB OH & S Regulation
B.C. Buildings Corporation Mandatory Preventive To Meet Section 4.78 of the WCB OH & S Regulation Prepared by: BCBC WCB-IAQ Steering Committee Mandatory Preventive TABLE OF CONTENTS Page no. INTRODUCTION...1
More informationPreventative Maintenance Plan. Guide. The Simple, Smart Way To Properly Care For Home Systems And Appliances.
Preventative Maintenance Plan Guide The Simple, Smart Way To Properly Care For Home Systems And Appliances. Protect. Prevent. Preserve. Prolong. What AHS Preventative Maintenance Plans Can Do For Your
More informationCC145. Air Conditioning System. Operation Manual. CC145 Compact Cooler 4/2013 P.N. 10000034A
Air Conditioning System Operation Manual CC145 Compact Cooler 4/2013 P.N. 10000034A To receive the best performance from the air conditioning system, we suggest carefully reading this manual before operating
More informationHeating Ventilation and Air Conditioning Diagnostics for Single Family Homes
Heating Ventilation and Air Conditioning Diagnostics for Single Family Homes Vincent Pedalino FSL Home Improvements Phoenix, AZ 1 HVAC Basics Ways to improve the performance of existing air conditioning
More informationChapter 7 Hydraulic System Troubleshooting
Chapter 7 Hydraulic System Troubleshooting General The following troubleshooting information is provided as a general guide to identify, locate and correct problems that may be experienced with the hydraulic
More informationTHE CASE FOR A REFRIGERATION PREVENTATIVE MAINTENACE PROGRAM
THE CASE FOR A REFRIGERATION PREVENTATIVE MAINTENACE PROGRAM Prepared and Presented By: Don Langston President & CEO, Aire Rite Air Conditioning & Refrigeration Inc Setting the Foundation The Refrigeration
More information1. What percent of a commercial business s energy usage comes from their HVAC system? A. 13% B. 23% C. 33% D. 43% E. 53%
1 1. What percent of a commercial business s energy usage comes from their HVAC system? A. 13% B. 23% C. 33% D. 43% E. 53% 2. How much money do commercial facilities spend per square foot on energy costs
More informationSECTION 5 COMMERCIAL REFRIGERATION UNIT 22 CONDENSERS
SECTION 5 COMMERCIAL REFRIGERATION UNIT 22 CONDENSERS UNIT OBJECTIVES After studying this unit, the reader should be able to explain the purpose of the condenser in a refrigeration system. describe differences
More informationPump Maintenance - Repair
Pump Maintenance - Repair Brian Trombly Mo Droppers Cummins Bridgeway, Gaylord, Mi The basic centrifugal pump consists of two main elements: 1. The rotating element which includes an impeller and a shaft.
More informationHeat Pump Water Heater IOM Manual
Heat Pump Water Heater IOM Manual Installation Operation & Maintenance This manual is intended as an aid to qualified service personnel for proper installation, operation and maintenance of the heat pump
More informationSUGGESTED GUIDELINES FOR REFRIGERATION PLANT MAINTENANCE
SUGGESTED GUIDELINES FOR REFRIGERATION PLANT MAINTENANCE SEPTEMBER, 2003 ONTARIO RECREATION FACILITIES ASSOCIATION INC. 1185 EGLINTON AVENUE EAST, SUITE 402 NORTH YORK, ONTARIO CANADA M3C 3C6 T.416.426.7062
More informationHow To Clean Water From An Ammonia Refrigeration System
Water Contamination and Water Removal in Industrial Ammonia Refrigeration Systems By Ray Ficker, PE Effects of Water Contamination Water contamination in an industrial ammonia refrigeration system can
More informationHVAC Scheduled Maintenance Program
(DATE) HVAC Scheduled Maintenance Program Designed Especially for: Company Name: Address: Nick Savio Commercial Sales Manager ADVANTAGE AIR LLC. What Advantage Air can do for you? 1) PROVIDE 28 YEARS OF
More informationMaintenance for Energy Efficiency
Maintenance for Energy Efficiency Institute of Hospital Engineering, Australia (IHEA) Seminar Asset Management & Energy Efficiency Exclusive Trane distributor Australia/New Zealand. The TRANE trade mark
More informationMechanical Engineering Technician- Plant Technician
Mechanical Engineering Technician- Plant Technician A competent Mechanical Engineering Technician- Plant Maintenance is expected to: 1. Ability to plan and execute work in a safe and responsible manner
More informationSYLLABUS For BASIC TRADE COURSE (360 Hours) On REFRIGERATION AND AIR CONDITIONING
SYLLABUS For BASIC TRADE COURSE (360 Hours) On REFRIGERATION AND AIR CONDITIONING INDEX 1. Introduction 3 2. Objectives 3 3. Employment Opportunity 4 4. Course Structure 4 5. Entry Qualification 4 6. List
More informationRefrigeration Basics 101. By: Eric Nelson
Refrigeration Basics 101 By: Eric Nelson Basics Refrigeration is the removal of heat from a material or space, so that it s temperature is lower than that of it s surroundings. When refrigerant absorbs
More informationLow Profile Unit Cooler
Super-Flo Now available with EC Motors High Efficiency / High Reliability Low Profile Unit Cooler Publication No. 411.4 November, 2008 S A N I T A T I O N F O U N D A T I O N A L N A T I O N Air Defrost
More informationCOMPETENCY ANALYSIS PROFILE Refrigeration and Air Conditioning Systems Mechanic - Branch 1 313A
COMPETENCY ANALYSIS PROFILE Refrigeration and Air Conditioning Systems Mechanic - Branch 1 313A (All unshaded skill sets must be demonstrated/completed) PROTECT SELF AND OTHERS Identify, interpret, and
More informationINVOICE. DATE: May 11, 2005. DESCRIPTION Inspection and report on a property located at OF SERVICES: Perfect Street, Sarasota, Fl.
INVOICE DATE: May 11, 2005 CLIENT: The Buyer DESCRIPTION Inspection and report on a property located at OF SERVICES: Perfect Street, Sarasota, Fl. TOTAL FEE: $ See Schedule Tom Villani Hallmark Inspection
More information123 street Salt Lake City, Utah 84092
Salt Lake City, Utah 84092 Prepared for: Sample AC inspection Prepared by: Page 1 of 8 Table of Contents Definitions 2 General Information 2 Air Conditioning 3 Heating System 6 Summary 8 Page 2 of 8 Definitions
More informationBACK TO PAGE ONE ANALYSIS OF SURVEY DATA
TABLE OF CONTENTS TO-98-7-4 MAIN PAGE Maintenance and Service s of Commercial Building Ground-Source Heat Pump Systems Douglas Cane, P.E. Andrew Morrison, P.E. Christopher J. Ireland Member ASHRAE Associate
More informationA.Y. McDonald Mfg. Co. Troubleshooting Submersible and Jet Pumps
A.Y. McDonald Mfg. Co. Troubleshooting Submersible and Jet Pumps Troubleshooting Submersible Pumps Fuse overload or circuit breaker trips when motor is started 1. Incorrect line voltage. Check the line
More informationGeyser-R Heat pump water heater Installation manual
Geyser-R Heat pump water heater Installation manual 1 Version 2.9 SAFETY INFORMATION Please read carefully to prevent serious accidents or injury. The Geyser-R Heat Pump Water Heater must be installed
More informationCustomized Assessment Blueprint
Customized Assessment Blueprint HVAC Installer Basic - Test Codes: 7906 and 7796 Measuring What Matters Competencies and Skills Tested in this Assessment: HVAC Theory Heat Theory and Refrigeration HVAC
More informationThis chapter is devided into two sections:
This chapter is devided into two sections: Page Installation requirements........................................................................ 127 The installation process..........................................................................
More informationHow To Fix A Car With A Carbide Engine
Section 12 Adjustment, Repair, and Replacement Page 12-1 Section 12 Adjustment, Repair and Replacement Section Contents Page Overview...12-5 Belts Belt Guard Removal/Installation...12-7 Belt Removal/Installation...12-11
More informationService manual. Website: www.andico.com.au CAUTION - BEFORE SERVICING THE UNIT, READ THE SAFETY - PRECAUTIONS IN THIS MANUAL.
Website: www.andico.com.au Service manual CAUTION - BEFORE SERVICING THE UNIT, READ THE SAFETY - PRECAUTIONS IN THIS MANUAL. - ONLY FOR AUTHORISED SERVICE PERSONNEL. MODELS: MPK1-09CR-QB8 MPK1-12ER-QB6
More informationUSER S, MAINTENANCE and SERVICE INFORMATION MANUAL
CONTENTS SAFETY INFORMATION................ 2 FOR YOUR SAFETY....................... 2 SYSTEM OPERATION.................. 2 THERMOSTATS........................... 2 INTERMITTENT IGNITION DEVICE...........
More informationREQUEST FOR PROPOSALS
REQUEST FOR PROPOSALS COURT OF APPEAL, 4TH APPELLATE DISTRICT, DIVISION 2 REGARDING: RFP TITLE: RFP NUMBER: PROPOSALS Due: MECHANICAL AND HVAC INSPECTION AND PREVENTIVE MAINTENANCE Inspection and preventive
More informationCO-10 COOLING SYSTEM. Page DESCRIPTION TROUBLESHOOTING CHECK AND REPLACEMENT OF ENGINE COOLANT
CO-1 COOLING SYSTEM DESCRIPTION TROUBLESHOOTING CHECK AND REPLACEMENT OF ENGINE COOLANT WATER PUMP THERMOSTAT RADIATOR Page CO-2 CO-4 CO-4 CO-6 CO-10 CO-12 CO-2 COOLING SYSTEM - Description DESCRIPTION
More informationUniversity of Houston Master Construction Specifications Insert Project Name
SECTION 23 62 13 - AIR-COOLED SPLIT SYSTEM AIR CONDITIONING UNITS PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Division 1, "General Requirements",
More information3. SEISCO PARTS & SERVICE REMOVAL AND REPAIR GUIDE
4 3. SEISCO PARTS & SERVICE REMOVAL AND REPAIR GUIDE A. Changing the Control Board B. Replacing a Heating Element C. Thermistor Replacement D. High Limit Switch Replacement E. Level Detector Replacement
More informationWhy and How we Use Capacity Control
Why and How we Use Capacity Control On refrigeration and air conditioning applications where the load may vary over a wide range, due to lighting, occupancy, product loading, ambient weather variations,
More informationTroubleshooting Your Refrigerator
Troubleshooting Your Refrigerator With conscientious care, a refrigerator will perform for years with little or no repairs. Refrigerators are categorized according to the way frost is removed from them.
More informationOverview. Introduction Cooling Tower Basics Principles of Operation Types of Cooling Towers Common Applications Design Considerations
Stephen Lowe ASHRAE Hampton Roads Chapter Past President AECOM Design Mechanical Engineering Discipline Manager, Virginia Beach Division Professional Engineer Commonwealth of Virginia, NCEES BSME University
More informationA brief explanation on how air conditioning works and what terms mean
A brief explanation on how air conditioning works and what terms mean -presented by- Before we begin, let s explain the air conditioning process. In the most basic of terms, air conditioning simply takes
More informationSENTRA SERIES WATER UNITS. 30 to 300 F Process Temperatures. 1/2 to 7.5 HP Centrifugal Pumps (20-100 GPM) 10 to 34 KW Stainless Steel Heaters
Temperature Control Units Water & Oil - 00 F Portable Chillers Air & Water-Cooled 0-70 F Central Chillers Air & Water-Cooled Packages & Modules 0-70 F Pump Tank Stations Chilled or Tower Water 00-00 gallons
More informationWINDOW ROOM AIR CONDITIONER
WINDOW ROOM AIR CONDITIONER Installation and Operation Manual Electromechanical Remote Control CAPACITIES 220V - 60 HZ. 12,000; 18,000; 24000 BTU/HR 220V-240V - 50 HZ. 12,000; 18,000; 24000 BTU/HR Please
More informationSECTION 23 00 01 HEATING, VENTILATION AND AIR CONDITIONING EQUIPMENT
SECTION 23 00 01 HEATING, VENTILATION AND AIR CONDITIONING EQUIPMENT PART 1 - GENERAL 1.1 DESCRIPTION A. The Work specified in this Section consists of designing, furnishing and installing factory-assembled
More information3/29/2012 INTRODUCTION HVAC BASICS
INTRODUCTION HVAC BASICS AND HVAC SYSTEM EFFICIENCY IMPROVEMENT SECTION O HVAC systems or Heating, Ventilating and Air-Conditioning systems control the environment for people and equipment in our facilities.
More informationWynn s Extended Care
Wynn s Extended Care Every car deserves to receive the very best care... especially yours. How Do You Keep Your Reliable Transportation Reliable? Count on Wynn s Because Wynn s has been caring for cars
More informationSERVICE BULLETIN AIR CONDITIONER COMPRESSOR FAILURES ALSO SEE BULLETIN #SB3-304AS (SYSTEM CONTAMINATION)
Form #SB4-304AS AirSourceR SERVICE BULLETIN AIR CONDITIONER COMPRESSOR FAILURES ALSO SEE BULLETIN #SB3-304AS (SYSTEM CONTAMINATION) Second only to refrigerant hose leaks, compressors have the highest rate
More informationTechnical Guide 08/15/14
Technical Guide 08/15/14 1 Table of Contents Contact information.3 Identifying your system..4-8 Model Number Serial number location Parts of your fuel system..9-14 Fuel pump diagram Wire harness schematics
More informationNo grinding or welding operations should be done in the area where hydraulic components are being installed.
1 Warnings Never force a hydraulic connection that doesn t seem to fit. Use only fasteners of the proper size. Beware of corroded, loose or missing fasteners. Do not operate hydraulics below minimum rated
More informationTRAINING, EXAMINATION AND CERTIFICATION
TECHNICAL STANDARDS & SAFETY AUTHORITY TRAINING, EXAMINATION AND CERTIFICATION REFRIGERATION OPERATOR CLASS B CERTIFICATION & EXAMINATION GUIDE REVISED EDITION 2 CERTIFICATIONS PERSUANT TO THE OPERATING
More informationDealer Sales & Service Guide
Analog Models w/thermostat or Timerstat Heat Siphon Not Starting 1 BREAKER TRIPPED - Check Breaker Box for correct size breaker Breakers: EX; Domestic model 2.25hp (20amp) 3.25hp (40amp) 5hp (50amp) check
More informationSYLLABUS FOR SIX MONTHS - FULL TIME CERTIFICATE COURSE IN REFRIGERATION AND AIR-CONDITIONING. Effective From :- UNDER DEVELOPMENT.
SYLLABUS FOR SIX MONTHS - FULL TIME CERTIFICATE COURSE IN REFRIGERATION AND AIR-CONDITIONING Effective From :- UNDER DEVELOPMENT Prepared by: Curriculum development cell Institute of Research Development
More informationLOBOY 16 AIR CONDITIONERS
INSTRUCTION MANUAL FOR: LOBOY 16 AIR CONDITIONERS McLean Midwest Corp. dba: McLean Cooling Technology 11611 Business Park Blvd. N Champlin, MN 55316 Tel: 763-323-8200 Fax: 763-576-3200 www.mcleancoolingtech.com
More information