DESIGN OF A SINGLE-ZONE HVAC SYSTEM FOR A PUBLIC LIBRARY IN DALLAS, TEXAS

Size: px
Start display at page:

Download "DESIGN OF A SINGLE-ZONE HVAC SYSTEM FOR A PUBLIC LIBRARY IN DALLAS, TEXAS"

Transcription

1 DESIGN OF A SINGLE-ZONE HVAC SYSTEM FOR A PUBLIC LIBRARY IN DALLAS, TEXAS ME Heating, Ventilation and Air Conditioning George Washington University Spring Semester 1999 Submitted to: Professor A. M. Kiper Submitted by: John F. Woodall May 4, 1999

2 TABLE OF CONTENTS Section Page Number REFERENCES... 1 INTRODUCTION... 2 DESIGN CONDITIONS... 2 BUILDING DESCRIPTION... 3 CALCULATION OF SPACE HEATING LOAD... 4 CALCULATION OF SPACE COOLING LOAD... 9 AIR-CONDITIONING EQUIPMENT SELECTION AIR-HANDLING/DISTRIBUTION SYSTEM DESIGN SUMMARY APPENDICES APPENDIX A... Circular of Requirements APPENDIX B... Drawing Sheets APPENDIX C... Calculations and Process Diagrams APPENDIX D... Selected Component Vendor Data

3 REFERENCES 1) "Heating, Ventilating, and Air Conditioning - Analysis and Design," Faye C. McQuiston and Jerald D. Parker, John Wiley & Sons, Inc., New York, ) "1993 ASHRAE Handbook - FUNDAMENTALS," American Society of Heating, Refrigerating, and Air Conditioning, Inc., Atlanta, GA, Chapter 27 - Fenestration. 1

4 INTRODUCTION: This report documents the preliminary design of a single-zone air conditioning system for a public library in Dallas, Texas. The circular-ofrequirements (COR) for the HVAC system is provided in Appendix A. When information, beyond that provided in Appendix A, was necessary for design calculations, assumptions were necessary. These assumptions are stated throughout this report, where applicable. A significant portion of the formulas, tables, and design methodology needed for the design of the subject HVAC system were taken from Reference (1). However, the data used in Reference (1) is based on current ASHRAE standards, and the ASHRAE database. Therefore, this report adheres to current ASHRAE practice and standards. Appendix B is a set of drawing sheets, which include various library arrangements, drawings, and system schematics. These drawings are referenced throughout the report where applicable. Appendix C contains system design calculations and process diagrams, and Appendix D contains vendor provided data for several selected HVAC system components. DESIGN CONDITIONS: The design indoor and outdoor conditions are prescribed in Appendix A, and are as follows: Summer Indoor: Outdoor: Winter Indoor: Outdoor: 75 o F dry bulb, 50% Relative Humidity 2.5% Design Conditions 72 o F dry bulb, 30% Relative Humidity 97.5% Design Conditions For Dallas, Texas from Ref. (1), Table C-1, the Summer 2.5% design conditions are 100 o F dry bulb and 75 o F wet bulb, and the Winter 97.5% design conditions are 22 o F and an assumed 0% Relative Humidity. Therefore, for Dallas, Texas, the library air-conditioning system design conditions become: Summer Indoor: Outdoor: Winter Indoor: Outdoor: 75 o F dry bulb, 50% Relative Humidity 100 o F dry bulb, 75 o F wet bulb 72 o F dry bulb, 30% Relative Humidity 22 o F, assumed 0% Relative Humidity 2

5 BUILDING DESCRIPTION: The library, as described in Appendix A, is a one story, slab-on-grade floor, having a total floor area of 5,000 sq. ft., with internal dimensions of 100-ft by 50-ft, and 10-ft high ceilings. Windows, as described in Appendix A, occupy 50% of the north and south side wall areas (i.e. 0.50(10-ft x 100-ft) = 500 sq. ft. of windows on both the north and south walls A nominal window size of 4-ft by 6-ft was selected from Ref. (2), Ch. 27, Table 5., which provides information on standard fenestration products. This window size best suits a library application, since they are tall - allowing sunlight in to aid in reading. A detail of the selected window is provided in Appendix B, and they have a face area of 24 square feet. Therefore, to best meet the COR window area requirements, twenty-one windows are installed on the north wall and twenty windows are installed on the south wall. This is a best fit to the COR window requirements, without resorting to using non-standard window sizes. In addition to the windows, doors are specified for the south and east walls. These doors are 6-ft by 7.5-ft solid core swinging metal doors, without a storm door. A ten-foot by fifteen-foot Utility Room was chosen and placed on the West wall of the library. This Utility Room is illustrated in Appendix B. The Utility Room is not air-conditioned, and therefore, for design purposes the temperature in the Utility Room is chosen to be the average of the inside and outside temperatures. Throughout the design process, surface areas of the building, exposed to the outside environment, are used in calculating space heating and cooling loads. Therefore, these physical dimensions of the various exposed surfaces of the library are tabulated in Table 1 and are based on the library sketches provided as Sheets 1 and 2 of Appendix B. North Wall South Wall East Wall Table 1. Surface Areas Used for Calculations Window Area: 21 x (4-ft x 6-ft) windows = 504 ft 2 Wall Area: 100-ft x 10-ft wall - (window area) = 496 ft 2 Window Area: 20 x (4-ft x 6-ft) windows = 480 ft 2 Door Area: 1 x (6-ft x 7.5-ft) door = 45 ft 2 Wall Area: 100-ft x 10-ft wall - (window & door area) = 475 ft 2 Door Area: 1 x (6-ft x 7.5-ft) door = 45 ft 2 Wall Area: 50-ft x 10-ft wall - (door area) = 455 ft 2 West Wall Wall Area (to outside): 2 x (17.5-ft x 10-ft wall = 350 ft 2 Wall Area (to Utility Rm): 15-ft x 10-ft wall = 150 ft 2 Roof Roof Area: 50-ft x 100-ft = 5000 ft 2 Floor Floor Area: 50-ft x 100-ft = 5000 ft 2 3

6 CALCULATION OF SPACE HEATING LOAD: As described in Ch. 5 of Ref. (1), the space heating load is an estimate of the maximum probable heat loss of each space or room to be heated. This does not include the heating requirements due to the outside air entering the library from the HVAC system (to meet fresh air requirements). Fresh air is considered when determining the heating system characteristics, but is not a component of the space heating load. The space heating load is composed of two major components. First, is the heating load required to handle transmission losses due to heat transfer from the air inside the library to outside, through the walls, floor, roof, and various windows and doors. Second, is the heating load required to account for outside air infiltration through doors, windows, etc. The heat gain due to the sun, as well as the heat gain from internal electrical and mechanical equipment is not considered when calculating the space-heating load. This is a good assumption, because the heating system must be able to maintain the design indoor temperature on cloudy/overcast days when minimal equipment is being used. Also, infiltration air is not considered when determining the amount of fresh air required. Although infiltration air is outdoor air entering the library, the full 20 cfm per person ventilation air requirement must be met by the system, not by infiltration. Transmission Load: Transmission losses are calculated individually for each building component from the general equation: q& = UA( t ) i to where 'U' is the Overall Heat Transfer Coefficient for the component under investigation, A is the surface area of the component, 't i ' is the inside air temperature, and 't o ' is the outside air temperature. In order to determine the heating load due to transmission losses, Overall Heat Transfer Coefficients must be found for each building component exposed to the outside environment. Sketches of various building components exposed to the outside are provided in Appendix B, Sheet 3. The calculation of the Overall Heat Transfer Coefficients for various outside surfaces is as follows: Walls - The walls, as described in Appendix A, are 4-in. face brick and 6-in concrete block with a 1-in. air gap between them. The various sub-components of the walls each have their own heat transfer coefficient, and the heat transfer coefficients for the convection losses on the outside and inside wall surfaces must also be included. Using the values found in Ref. (1), Table 8-21, the overall heat transfer coefficient for the library walls is determined. A listing of each wall sub-component, it's classification (per Table 8-21), U-value, as well as a summed overall heat transfer coefficient for the library walls is provided in Table 2. It should be noted that the transmission heat loss for the portion of the West wall 4

7 exposed to the Utility Room is calculated by using an assumed temperature in the Utility Room. Since the Utility Room is not air-conditioned, the temperature during the winter is chosen as the average of the outside and space design temperature. Table 2. Wall Overall Heat Transfer Coefficient Description Code Number From Ref. (1), Table 8-21 Thermal Resistance, R (ft 2 -hr- o F/Btu) Outside surface resistance A " face brick A Air space resistance B " concrete block *(C3+C8)/ Inside surface resistance E Total Resistance 3.27 Wall Overall Heat Transfer Coefficient (U = 1/R), Btu/ft 2 -hr- o F 0.31 * Note: 6" concrete block was not available in Ref. (1), Table Therefore, the thermal resistance values for 4" concrete block (C3) and 8" concrete block (C8) were averaged for use as a 6" concrete block thermal resistance. Windows - The windows as specified are heat absorbing out, clear in type insulating glass, with a nominal 1/4" thickness. From Ref. (1), Table 5-8a, the Overall Heat Transfer Coefficient for "Double Glass, 1/4 inch air space, aluminum frame, without thermal break" was selected as the best representative description of the specified windows. From Table 5-8a, the Window Overall Heat Transfer Coefficient is taken as 0.65 Btu/ft 2 -hr- o F. Doors - The doors, as specified, are 35-mm nominal thickness, 6-ft by 7.5-ft, solid core, swinging metal doors without storm doors. From Ref. (1) Table 5-9, the "steel door, solid urethane foam core, without thermal break" was selected to best represent the specified doors. However, Table 5-9 does not provide the Overall Heat Transfer Coefficient for a 35-mm thick door. The value available is for a 1-3/4" door. In the Table 5-9 notes, "moderate extrapolation" is allowed. Therefore, the Overall Heat Transfer Coefficient for a 35-mm steel door with solid urethane foam core, without thermal break, is extrapolated as follows: U = 1" 35mm 25.4mm " where '0.40' is the Overall Heat Transfer Coefficient for a 1-3/4" door, per Table 5-9. From this extrapolation, the door coefficient 'U' is 0.31 Btu/ft 2 -hr- o F. Roof - As specified, the roof is flat built-up roofing, roof construction code #9, dark color outside surface, without suspended ceiling below the roof deck. Ref. (1), Table 5-7b provides a breakdown of individual roof components and their thermal resistance's for a specific roof example. This example does not match with the roof specified for the library; however, the components of the specified 5

8 roof can be parsed from the individual roof components in the example roof of Table 5-7b. The specified roof components for the library, their thermal resistances, and the roof Overall Heat Transfer Coefficient are provided in Table 3. Table 3. Roof Overall Heat Transfer Coefficient Description Thermal Resistance, R (ft 2 -hr- o F/Btu) Outside surface (15 mph wind) 0.17 Built-up roofing, in Concrete slab, lightweight aggregate, 2 in Inside surface (still air) 0.61 Total Resistance 3.33 Roof Overall Heat Transfer Coefficient (U = 1/R), Btu/ft 2 -hr- o F 0.30 Floor - As stated on page 177 of Ref. (1), the transmission heat loss calculation for a slab-on-grade floor uses a slightly different form of the general heat transfer equation than previously stated. The appropriate equation for a slab-on-gradefloor is: ( ) q& = U P t i t o where, U' is the overall heat transfer coefficient expressed as heat transfer per unit length of building perimeter, per degree temperature difference. The perimeter of the floor is (100-ft ft + 50-ft + 50-ft) 300 ft, assuming the Utilty Room does not have a slab-on-grade floor. Also, 'degree days' input for Dallas, Texas is needed to determine U'. From Table C-2 of Ref. (1), the yearly degree days total is 2363 for Dallas, Texas. Therefore, from Table 5-12 of Ref. (1), the U' for a 8" slab-on-grade floor, brick face, uninsulated, using the 2950 degrees day column, is 0.62 Btu/ft-hr- o F. Now that all the individual overall heat transfer coefficients have been determined, the total transmission heat loss from the building to the outside can be calculated. Table 4 tabulates the overall heat transfer coefficients, and shows the calculations used to determine the total transmission heat loss. As shown in Table 4, the total transmission heat loss is 146,411 Btu/hr. 6

9 Table 4. Total Transmission Heat Loss Uo (Btu/hr. ft 2.o F) U' (Btu/hr. ft.o F) Sur. Area (ft 2 ) Perimeter (ft) Ti To delta-t qh North Wall ,688 South Wall ,363 East Wall ,053 West Wall (to outside) ,425 West Wall (to Utility Rm) ,163 Windows ,980 Doors ,440 Roof ,000 Floor ,300 Total Transmission Heat Loss = 146,411 Infiltration Air: The amount of air that infiltrates the building during the winter conditions can be determined by several methods. These include the crack method and the air-change method. The crack method determines the infiltration rate based on pressure differences between the outside air and inside (due to wind), along with the characteristics of the windows, doors, etc. (i.e. their "cracks"). The airchange method assumes a value of air-changes per hour, and with this assumption determines the infiltration rate for a known volume. For this preliminary design, the air-change method is considered to be acceptable. Also, since the library is only a one story building, stack effects are not considered. As stated on page 227 of Ref. (1), the number of air changes per hour (ACH) can vary from 0.5 (very low) to 2.0 (very high). The ACH is assumed to be a moderate to low value. Therefore for the Library design, an ACH of 1.0 is selected. Equation 7-10 of Ref. (1), which is used to determine the infiltration, is as follows: Q & = ACH ( V )/ 60 where Q is the infiltration rate in cfm, ACH is the assumed number of air changes per hour, and V is the gross space volume in cubic feet. The gross space volume of the library is (100-ft x 50-ft x 10-ft) 50,000 ft 3. Therefore the infiltration rate of outside air is 1.0(50,000)/60 = 833 cfm. As stated on page 226 of Ref. (1), the infiltration air is considered a heating load. This load has a sensible component and a latent component. The sensible heating component due to infiltration is the sensible heat required to increase the infiltrated air to the design indoor temperature. The latent component is the latent heat required to humidify the infiltrated air to the design indoor relative humidity. Equation 7-8b of Ref. (1) is used to calculate the sensible infiltration heat load, and is as follows: 7

10 q& s Qc & = p ( t t ) v i o o where Q is the infiltration volumetric flow rate (ft 3 /hr), c p is the constant-pressure specific heat of air (taken as 0.24 Btu/lbm- o F), t i and t o are the inside and outside air temperatures respectively, and v o is the outside air specific volume (interpolated from the Ref. (1), Table A-2a as ft 3 /lbm). From this equation and our calculated infiltration air rate of 833 cfm (50,000 ft 3 /hr), the sensible heating load due to infiltration is (50,000)(0.24)(72-22)/12.14 = 49,423 Btu/hr. Equation 7-9b of Ref. (1) is used to calculate the latent infiltration heat load, and is as follows: q& l Q = & v o ( W i W o ) i fg where W i and W o are the inside and outside humidity ratios respectively (lbmv/lbma), and i fg is the enthalpy of vaporization or, the latent heat of vaporization. From the Psychometric Diagram, the inside humidity ratio W i is lbmv/lbma. The outside humidity ratio is assumed to be zero. This assumption is valid since outisde air during the heating season is very dry (low relative humidity) and therefore a conservative aproach would be to assume there is no water vapor in the outside air. The enthaply of vaporization, from Table A-1a of Ref. (1), at the indoor design temperature of 72 o F, is Btu/lbmv. From this equation and our calculated infiltration air rate of 833 cfm (50,000 ft 3 /hr), the latent heating load due to infiltration is calculated as (50,000/12.14)(0.005)(1052.8) = 21,680 Btu/hr. The space heating load due to transmission through the building roof, walls, floor, windows, and doors is combined with the space heating load due to the infiltration of outside air through windows, doors, etc. This is the total space heating load, and is tabulated in Table 5. Table 5. Total Space Heating Load Transmission ( Btu / hr) Infiltration ( Btu / hr) Total Btu / hr ( ) Sensible Heat Load q& ( s ) h Latent Heat Load q& ( l ) h 146,411 n/a 49,423 21, ,834 21,680 8

11 Supply Air for Space Heating In order to determine whether the heating season or cooling season is the driving season for the selection of the air-distribution system, the supply air requirements for space heating must be calculated. This will be compared to similiar calculations for space cooling to determine a design airflow rate. Appendix C contains a process diagram of the heating system on a Psychometric Chart, as well as detailed heating system calculations. Also, Appendix B, Sheet 4 is a detailed schematic diagram of the heating system. A pre-heater was considered necessary, to bring the temperature of the fresh air above the dewpoint temperature of the air inside the utility room. This ensures that condensation will not form on the ducting leading into the furnace. As stated previously, the utility room temperature is assumed to be the average of the outside design temperature and the desired indoor temperature, namely 47 o F. A summary of the results of the detailed calculations is provided in Table 6. It is important to note that these calculations do not take into consideration the effects of fan heat to the system. Table 6. Heating System Characteristics Required Quantity of Supply Air to Space (at 120 o F) 4,113 cfm Required Furnace Capacity 308,775 Btu/hr Required water supply to humidifier (at 47 o F) 1.0 lbm/min Required Pre-heater Capacity 40,896 Btu/hr CALCULATION OF SPACE COOLING LOAD: As stated on page 247 of Ref. (1), the heat loss calculations, during winter conditions, are based on steady-state heat transfer, and this basis is adequate for selecting heating and humidification equipment. For the cooling load, however, steady-state heat transfer would not adequately represent the heat gain, and would lead to oversized equipment. This is because the solar contributions to the space cooling load have a considerable lag effect, before the heat is actually absorbed by the inside air. There are several methods that can be used to calculate the space cooling load. These include the "Transfer Function Method," and the "Cooling Load Temperature Difference, Solar Cooling Load, and Cooling Load Factor (CLTD/SCL/CLF) Method." The CLTD/SCL/CLF Method is a hand calculation 9

12 method that uses extensive tables and charts that were derived using the Transfer Function Method. To determine the space cooling load for the Library, the CLTD/SCL/CLF Method is employed. The Circular of Requirements (Appendix A) states that the maximum cooling load occurs at 15:00 solar time, during the month of August. This statement greatly simplifies the process of determining the design space cooling load. If the time that the maximum cooling load occurs was not provided, the space cooling load would have to be determined for several times, in an iterative fashion, in order to select the maximum. Since the time of the library maximum space cooling load is known, only one iteration is necessary. Each contributing component of the space cooling load is calculated separately as follows, and is then summed to provide the total sensible and latent space cooling loads. The overall heat transfer coefficients used for conductive heat transfer are identical to those used when calculating the space heating load. Roof - For the roof, A CLTD value is required. As stated in the COR, the roof is given as roof #9, dark color outside surface, without a suspended ceiling below the roof deck. The overall heat transfer coefficient, calculated previously is For determining the CLTD value, Table 8-18 of Ref. (1) is used. The library maximum cooling load occurs during the month of August, however Table 8-18 is for July 21st. A footnote in Table 8-18 states that "for design purposes, the data will suffice for about two weeks from the 21st day of the given month (in this case July)." Therefore it is assumed that Table 8-18, and all other CLTD tables for July 21st with similar footnotes, are sufficient for the design of the library cooling system maximum load during August. Using Roof #9 and 1500 solar time (given time of maximum cooling load), the roof CLTD is selected from Table 8-18 as 46. This value, however, must be adjusted to reflect the differences in the library design temperatures and those temperatures used to derive the Table. The adjustment is as follows: 10 ( 78 t r ) + ( t 85) Corr. CLTD CLTD + = m where, t r is the inside temperature, and t m is the maximum outdoor temperature minus the (daily range/2). From Ref. (1), Table C-1, the daily range for Dallas, Texas is 20 o F. And with the design indoor and outdoor temperatures listed in the "Design Conditions" section of this report, the roof CLTD is adjusted as follows: ( 78 75) + (90 85) 54 Corr. CLTD = 46 + = To find the sensible heat gain to the library due to transmission through the roof, the following equation is used: q& c = UA( CLTD) Therefore, with U=0.30, A = 5,000 ft 2, and CLTD = 54, the library space cooling load due to the roof is calculated to be 81,000 Btu/hr.

13 Walls - For the walls, a CLTD value must be determined. The wall resistance was previously determined as R = The wall # is determined from Ref. (1), Table 8-22b. With R = 3.23, and with face brick as the secondary wall material and C3 (4" heavyweight concrete block) as the principle material, the wall # is 5. And, with R = 3.23, and with face brick as the secondary wall material and C8 (8" heavyweight concrete block) as the principle material, the wall # is 10. Since the Library walls' actual secondary material is face brick, and principle material is 6" heavyweight concrete block, a wall # of 7 was interpolated. Therefore using a wall # of 7, and a solar time of 1500, the CLTD values for the North, South, East, and West walls were selected. They are also adjusted similar to the CLTD adjustment done for the roof. Table 7 contains the calculations for each wall, using the surface areas and overall heat transfer coefficients determined previously for the space heating load. The effects of the Utility Room on the West wall are considered to be negligible. Table 7. Wall Space Cooling Load Wall CLTD Corr. CLTD U A q& c = UA( CLTD) North ,690 South ,712 East ,642 West ,650 Total Space Cooling Load due to Walls = 18,694 Btu/hr Glass & Doors (Conduction) - For the conduction portion of the heat gain through glass windows and doors, a CLTD value must be determined. These CLTD values are determined from Ref. (1), Table 8-23, for a solar time of 1500 hrs. These values, and their corrected values (corrected similar to the correction to roof CLTD) are provided in Table 8, along with calculations to determine the space cooling load due to windows and doors. The surface areas and Overall Heat Transfer Coefficients were determined previously for the space heating load. Table 8. Window & Doors Conduction Space Cooling Load Item CLTD Corr. CLTD U A q& c = UA( CLTD) North Windows ,207 South Windows ,864 South Doors East Doors Total Space Cooling Load due to Glass-Door Conduction = 14,685 Btu/hr Glass (Solar) - To determine the Solar contribution to the space cooling load from windows, a Shading Coefficient (SC) and a Solar Cooling Load Factor (SCL) must be found. As stated in the COR in Appendix A, the windows are 11

14 equipped with medium venetian blinds. Also, from Ref. (1), Table 8-25a, for single-story buildings, using 4 walls, and carpet floor covering, the Zone Type is selected as 'A' for Glass Solar. Then from Ref. (1), Table 8-24, the SCL factors for the North and South windows are selected with a solar time of 1500 hrs. As stated in the notes for Table 8-24, the data is applicable to the month of August. And, from Table 6-5, for windows that are heat absorbing out, clear in-type insulating glass, a Shading Coefficient of 0.39 is selected. The contribution to the space cooling load from glass solar effects is calculated as shown in Table 9. The heat transfer areas were calculated previously when determining the space heating load. Table 9. Windows (Solar) Space Cooling Load Item A SC SCL q& c = A( SC)SCL North windows ,076 South Windows ,734 Total Space Cooling Load Due to Glass (Solar) = 16,810 Btu/hr Floor - As stated on page 177 of Ref. (1), during summer conditions the heat transfer to the floor slab is negligible. Internal Lights - To determine the contribution to the space cooling load from the internal lights, a Cooling Load Factor (CLF) must be determined and multiplied with the instantaneous heat gain of the lighting. The instantaneous heat gain can be determined from the following formula: q& = W ( ) F u Fs where, W is the total installed wattage, F u is the usage factor, and F s is an allowance factor. As stated in the COR (Appendix A) the product of W and F u is 4 Watts/ft 2 of floor area. The lights as stated in the COR are fluorescent type, and from Ref. (1), page 280, for general applications of fluorescent lights, F s is taken to be 1.2. Therefore with a floor area of 5,000 ft 2, the instantaneous heat gain is calculated as 3.41(4)(5000)(1.2) = 81,840 Btu/hr. From Table 8-25a, the Library is Zone Type 'B' for lights. As stated in the COR, the lights are on at 8AM, and off at 11 PM. Therefore they are on for 15 hrs each day. The maximum load occurs at 1500 hrs, therefore, the number of hours the lights are on up until the maximum cooling load time is 7 hours. Using these values and Zone Type 'A', from Table 8-27, the CLF is found to be Therefore the contribution to the space cooling load from internal lights is found to be (0.965)(81,840) = 78,976 Btu/hr. Equipment - To determine the contribution to the space cooling load from the equipment, a Cooling Load Factor (CLF) must be determined and multiplied with 12

15 the instantaneous heat gain of the equipment. The instantaneous heat gain from the equipment is determined in a similar fashion to the calculation for internal lighting. As stated in the COR, the Library equipment emits 0.5 Watts/ft 2 of floor area. Also stated in the COR is that the equipment is on from 8AM to 5PM. Therefore, the equipment is on for a total of 9 hrs, and is on for 7 hours at the maximum cooling load time of 1500 hrs. From Ref. (1), Table 8-25a, the Library Zone Type is 'B' for equipment and people. With these values, using Ref. (1), Table 8-26, the CLF for equipment is found to be Therefore the contribution to the space cooling load from equipment is found to be 3.41(0.5)(5,000)(0.93) = 7,928 Btu/hr. People (sensible) - The sensible portion of the instantaneous heat gain due to the Library occupants requires the determination of a Cooling Load Factor. First, from Ref. (1), Table 8-11, the instantaneous sensible heat gain for people seated doing very light work is 245 Btu/hr per person. And from Ref. (1), Table 8-25a, the Library Zone Type is 'B' for equipment and people. As stated in the COR, the people enter the space at 8AM and leave at 9PM (13 hours in space). And, at the point of maximum cooling load (1500 hrs) the people will have been in the space for 7 hours. With this data, a CLF of 0.94 is determined from Ref. (1), Table Therefore, for 75 people called out in the COR, the sensible portion of the space cooling load due to people is (75)(245)(0.94) = 17,273 Btu/hr. People (latent) - The latent portion of the instantaneous heat gain is immediately absorbed by the space air, and does not require a CLF factor for adding it to the space cooling load. From Ref. (1), Table 8-11, for people seated doing very light work, the latent heat gain is 155 Btu/hr per person. For 75 people, the latent portion of the space cooling load due to people is (75)(155) = 11,625 Btu/hr. Infiltration Air - As calculated previously for the space heating load, using the Air-Change Method, the infiltration air rate is 833 cfm. As stated in Ref. (1), page 331, "No CLF factors are necessary, since infiltration is convective in nature, and immediately becomes cooling load." As stated in the "Design Conditions" section of this report, the outside air is 100 o F dry bulb, and 75 o F wet bulb. From the Psychometric Chart in conjunction with Ref. (1), Table A-2a, the outside air conditions are: 100 o F, 32% relative humidity, and a specific volume of ft 3 /lbm. The specific heat is taken as 0.24 Btu/lbm- o F. The sensible portion of the space cooling load due to infiltration air is determined the same way as determined previously for the space heating load with the following formula: q& s Qc & = p ( t t ) v o o i Therefore, the sensible portion of the space cooling load due to infiltration air is found as (50,000)(0.24)(100-75)/ = 20,806 Btu/hr. 13

16 The latent portion of the space cooling load due to infiltration air is also determined in the same fashion as was done for the space heating load using the following formula: q& l Q = & v o ( W o W i ) i fg From Ref. (1), Table A-1a, the latent heat of vaporization (i fg ) at 100 o F is 1037 Btu/lbm. And from the Psychometric Chart, W o = lbmv/lbma, and W i = lbmv/lbma. With this data the latent portion of the space cooling load due to infiltration air is found as (50,000)( )(1037)/ = 13,665 Btu/hr. A summary of all calculated space cooling loads, and the tabulated resulting total space cooling load are provided in Table 10. Table 10. Total Space Cooling Load Roof Transmission ( Btu / hr) Walls Transmission ( Btu / hr) Glass-Doors Conduction ( Btu / hr) Glass Solar ( Btu / hr) Internal Lights ( Btu / hr) Equipment ( Btu / hr) People ( Btu / hr) Infiltration ( Btu / hr) Totals Btu / hr ( ) Sensible Cooling Load q& ( s ) c Latent Cooling Load q& ( l ) c 81,000 n/a 18,694 n/a 14,685 n/a 16,810 n/a 78,976 n/a 7,928 n/a 17,273 11,625 20,806 13, ,172 25,290 Therefore the total space cooling load is 256, ,290 = 281,462 Btu/hr. 14

17 Supply Air for Space Cooling Appendix C contains a process diagram of the cooling system on a Psychometric Chart, as well as detailed cooling system calculations. Also, Appendix B, Sheet 5 is a detailed schematic diagram of the cooling system. A summary of the results of the detailed calculations is provided in Table 11. It is important to note that these calculations do not take into consideration the effects of fan heat to the system. Table 11. Cooling System Characteristics Required Quantity of Supply Air to Space (at 55 o F) 11,026 cfm Required Cooling/Dehumidification Unit Capacity 341,775 Btu/hr Coil Sensible Heat Factor (SHF) 0.84 AIR-CONDITIONING EQUIPMENT SELECTION: As stated in the COR (Appendix A), the refrigeration cycle chosen for the Library is a Freon (R-22) cycle operating at a 30 o F evaporator temperature and with a 10 o F superheat before the refirgerant enters the compressor, and a 110 o F condensing temperature with 10 o F of subcooling before the expansion valve. Appendix B, Sheet 6, contains a detailed diagram of this system employed to provided cooling and dehumidification to the Library. As shown on Sheet 6, a cooling tower is utilized to transfer the heat from the condenser cooling water to the ambient air, and the chilled water system provides chilled water to the air/water heat exchanger which is the cooling/dehumidification coil for the Library. Appendix C contains detailed cooling system calculations for the Library Air-Conditioning system as well as a diagram showing the process on a Freon (R-22) Pressure-Enthalpy diagram. The state points shown on the Appendix C Pressure-Enthaply diagram correspond to the state points as shown on the Air- Conditioning System Schematic (Sheet 6, Appendix B). Also, on the Air- Conditioning System Schematic, it is shown that the Chilled Water enters the Cooling/Dehumdification coil at 42 o F, and leaves it at 52 o F. And, as shown, cooling water enters the condenser at 82 o F and leaves it at 92 o F. The detailed calculations in Appendix C show the process of calculating the Theoretical BHP of the Chiller Compressor, Water Chiller (R-22 Evaporator) size in terms of chilled water circulation rate, and the Water-Cooled Condenser size in terms of GPM of water flow and capacity. It is assumed, for the calculations, that the heat transfer in the chilled water piping is negligible. With 15

18 this assumption, the design cooling/dehumidification unit capacity can be equated to the Water Chiller (R-22 Evaporator) capacity. From this known Water Chiller capacity, along with the known refrigeration cycle state points, the mass flow rate of Freon in the theoretical refrigeration cycle was determined. Then, using the calculated mass flow rate of Freon, the Theoretical BHP of the Compressor was determined. And, using an energy balance on the refrigeration cycle (Q condenser = Q evaporator + W compressor, see Sheet 6, Appendix B) the Theoretical capacity of the Condenser was determined. To meet the cooling and dehumidification needs of the Library, a York, Model LCHWC 35, Reciprocating, Packaged Liquid Chiller was selected with a cooling capacity of 33.8 tons. This Chiller meets the Library cooling requirements with a 10% margin. Details of this Chiller Unit are provided in Appendix D. The selection methodology is provided in the Appendix C calculations, and any assumptions not stated here are stated in Appendix C. Table 12 summarizes the characteristics of the Air-Conditioning System components. Table 12. Air-Conditioning System Characteristics Cooling/Dehumidification Capacity Cooling/Dehumidification Capacity (With 10% margin) Theoretical BHP of Compressor Theoretical Capacity of Condenser Selected Chiller Capacity (at 90 o F Cond. Lvg wtr temp, 42 o F Cooler lvg wtr temp) Compressor Power for Selected Chiller 28.5 tons (341,775 Btu/hr) 31.4 tons 21.5 kw (for 28.5 ton system cooling capacity) 415,012 Btu/hr (for 28.5 ton system cooling capacity) 33.8 tons 28.0 kw Chilled Water Circulation Rate 81.0 gpm Condenser Cooling Water Flow Rate gpm 16

19 AIR-HANDLING/DISTRIBUTION SYSTEM DESIGN: For the Library, a low-velocity air distribution system was selected. A high-velocity system would likely not meet the noise requirements for a library application, and are normally selected for more industrial-type applications. As stated in the COR (Appendix A), the recommended air velocities for the library air distribution system are: Duct Sections (max) Air Supply Diffusers Return Air Registers Cooling Coil 1,000 fpm 400 fpm 200 fpm 500 fpm Also, the combined supply and return air pressure drop should not exceed 4.0 in w.g. This requirement is likely based on an independent cost analysis which compared costs due to duct size (non-recurring costs) and costs due to fan power consumption (recurring costs). From this analysis, a maximum system pressure drop of 4.0 in w.g. may have been selected. The air distribution system should be designed for the maximum volumetric flow rate that the system will operate with. In heating mode, the supply air required was previously determined to be 4,113 cfm. And, in cooling mode, the supply air required was previously determined to be 11,026 cfm. Obviously, the cooling season supply air requirements will drive the air distribution system design, since the required volumetric flow rate is much larger. The process followed in developing the air distribution system is as follows. First, the design airflow is selected. Based on the cooling season required cfm, a design airflow rate of 11,000 cfm is selected. The velocity limitations on the system were provided in the COR, and are listed above. Next, the diffuser and return grills are selected, and their corresponding pressure losses are determined. Then the layout of the supply and return air-ducting network is accomplished. With the duct layout decided upon, the ducts are sized to ensure that the system behaves as desired, and the supply and return system pressure losses are determined. Finally, with the total system losses tabulated, a fan is selected. More detailed discussion for each of these steps in provided in the following sections. Diffuser Selection After several iterations of diffuser number and size, 10 diffusers were selected to supply air to the Library. The diffuser type was selected as Circular Ceiling Diffusers. Sheet 7 of Appendix B shows the location of these 10 diffusers. They are each located in the Library overhead, in the center of a 20 ft by 25 ft section of the building. Since there are 10 diffusers, the cfm per each diffuser is 11,000 cfm / 10 diffusers = 1,100 cfm per diffuser. The Room load is the system cooling load divided by the room floor area. This is determined to be (341,775 Btu/hr) / (100 ft X 50 ft) = 68.4 Btu/hr-ft 2. The characteristic room length (L), per Ref. (1), Table 11-7, for Circular Ceiling 17

20 Diffusers is the distance to the closest wall or intersecting jet. Therefore, since each diffuser is serving a 20 ft by 25 ft section, the characteristic room length is taken to be between ft. From Ref. (1), Table 11-8, knowing the Room load, the x 50 /L = 0.8 for maximum ADPI, and the x 50 /L can range from 0.7 to 1.3. The x 50 value is the length from the diffuser where the air velocity is 50 ft/min. And, the ADPI value is a value which when met by a particular diffuser selected for an application, ensures that the occupants of the building do not feel discomfort. A point where occupants feel discomfort can be defined by an effective draft temperature. And, per Ref. (1), page 439, the ADPI is defined as the percentage of measurements taken at many locations in the occupied zone of a space that meet the effective draft criteria. By selecting a diffuser so that the x 50 /L value falls in the defined range for the known Room load, it can be ensured that the occupants do not feel uncomfortable. Since maximum ADPI occurs at a value of x 50 /L = 0.8, x 50 = 0.8(L), the x 50 value is 0.8(12.5 ft) = 10. Also, a recommeded diffuser velocity of 400 ft/min was stated in the COR. Therefore, from Ref. (1), Table 11-3, a 24" diffuser was selected, with ft/min. This airflow rate is close to the design rate of 1100 cfm. From Table 11-3, the Radius of Diffusion for 50 ft/min is 15 ft. Therefore our actual x 50 /L = 15 ft / 12.5 ft = 1.2. This x 50 /L value falls in the range provided in Table 11-8, and is acceptable. Therefore, 24" Circular Ceiling Diffiusers are selected for the Library. Also, the Noise Criteria Index (NC) is lower than the recommended noise level in a Library of NC = 35-40, as stated in Ref. (1), Table Per Table 11-3, the P o for these diffusers is 0.024" w.g. Return Grill Selection As stated in the COR, the recommended return air register velocity is 200 ft/min. After several iterations, ten return grills, each sized for 1,100 cfm were chosen. From Table 11-6, each is chosen to be a 24" by 24" grill, with characteristics: 1080 cfm, NC =20, and 300 ft/min. The return grill velocity is above the recommended velocity in the COR, however this is considered to be acceptable since the Noise Criteria value (NC = 20) is well below the levels specified for Library applications. The P s for this grill is " w.g., and the velocity pressure is Therefore the P o value determined for this grill is found to be = " w.g. This value is stated as negative because it is on the suction side of the supply fan, and therefore the pressure is below atmospheric pressure. Supply Air Ducting Layout/Sizing Appendix B, Sheets 7 & 8, show the layout of the supply air duct system. To determine the sizes of these ducts, in order to properly deliver 1,100 cfm to each of the ten diffusers, the Balance Method was employed. For this method, first the pressure drop through the longest run is determined (main duct run). Then, the additional branches are sized so that their pressure drop is equivalent to the pressure drop from the start of the particular branch to the end of the main duct run. This ensures that the pressure drop is equal for every path the air can 18

21 travel through the system, which ensures the proper amount of air is delivered to each diffuser. To determine the pressure drops through each section, the Equivalent Length Method was employed. This method determined the pressure drop through selected duct sections, by calculating equivalent lengths for components other than straight duct, to add to the length of straight duct. This allows a single equivalent length (L e ) value to be multiplied by P o per 100 ft of duct value to determine the branch pressure loss. Table 13 shows the Equivalent Length calculations for the supply system braches. Equivalent lengths for components other than straight duct are determined using Ref. (1), Figures and It is not necessary to include the diffuser pressure losses in each branch for sizing purposes, since each branch has a diffuser of the same size and airflow rate. The section designations in Table 13 correspond to the duct section labels as shown in Appendix B, Sheet 8. Table 13. Supply System Equivalent Length Calculations Section Individual Lengths L e Main Run A-B 35' (plenum) + 5' (duct) + 10' (90 o elbow) + 15' (duct) + 10' (90 o elbow) 83' + 3' (duct) + 5' (Main Branch) B-C 3' (duct) + 5' (Main Branch) 8' C-D 17' (duct) + 5' (Main Branch) 23' D-E 3' (duct) + 5' (Main Branch) 8' E-F 17' (duct) + 5' (Main Branch) 23' F-G 3' (duct) + 5' (Main Branch) 8' G-H 17' (duct) + 5' (Main Branch) 23' H-I 3' (duct) + 5' (Main Branch) 8' I-J 17' (duct) + 5' (Main Branch) 23' J-T 3' (duct) + 5' (45 o elbow) + 3' (duct) + 5' (45 o elbow) + 10' (duct) 26' Branches B-K 35' (Take-off branch) + 3' (duct) + 5' (45 o elbow) + 10' (duct) 53' C-P 35' (Take-off branch) + 3' (duct) + 5' (45 o elbow) + 10' (duct) 53' D-L 35' (Take-off branch) + 3' (duct) + 5' (45 o elbow) + 10' (duct) 53' E-Q 35' (Take-off branch) + 3' (duct) + 5' (45 o elbow) + 10' (duct) 53' F-M 35' (Take-off branch) + 3' (duct) + 5' (45 o elbow) + 10' (duct) 53' G-R 35' (Take-off branch) + 3' (duct) + 5' (45 o elbow) + 10' (duct) 53' H-N 35' (Take-off branch) + 3' (duct) + 5' (45 o elbow) + 10' (duct) 53' I-S 35' (Take-off branch) + 3' (duct) + 5' (45 o elbow) + 10' (duct) 53' J-O 35' (Take-off branch) + 3' (duct) + 5' (45 o elbow) + 10' (duct) 53' The ducts were sized using these equivalent lengths for each branch. Using a Figure similiar to Ref. (1), Figure 12-29, an iterative process was used to determine the Pressure Drop per 100 ft, for each section. Iteration was necessary to ensure that the duct velocities remain below the recommended velocities. As stated in the COR, the recommeded maximum duct velocity is 1,000 ft/min. For the large ducts needed for the 11,000 cfm supply system, the 19

22 1,000 ft/min velocity limit kept the duct velocities well below velocities that are characteristic of a low-velocity duct system. However, since the recommended maximum duct velocity was considered to be important to avoid any noise problems in the Library, it was adhered to. This resulted in low pressure drops throughout the supply system. Table 14 shows the resulting supply system duct sizes for the main run, and Table 15 shows the resulting supply system duct sizes for the corresponding branches. These values were determined after much iteration, and as shown in Tables 14 & 15, the system is balanced and the duct velocities remain under the prescribed limit. Also, these Tables show the supply system pressure drop calculated as " w.g. Table 14. Supply System Main Branch Pressure Drop Balance Method (Main Duct Run A-T) Section CFM Le (ft) De (in) V (ft/min) Delta-P o /100 ft Section Delta-P o A-B 11, B-C 9, C-D 8, D-E 7, E-F 6, F-G 5, G-H 4, H-I 3, I-J 2, J-T 1, Total Branch Ducts Section Loss Equivalent to Section: Table 15. Supply System Branch Sizing Required Delta-P o Le (ft) Delta- P o /100 ft CFM De (in) V (ft/min) B-K B-T , ,029 C-P C-T , ,029 D-L D-T , ,029 E-Q E-T , ,029 F-M F-T , G-R G-T , H-N H-T , I-S I-T , J-O J-T ,

23 Return Air Ducting Layout/Sizing The layout of the return air system is shown in Appendix B, Sheets 7 & 9. The balance method was employed to determine the pressure drop through the longest run (Section A-O, per Appendix B, Sheet 9), in similar fashion as the supply air ducting. However, in this case, there is more than one "main run." As can be seen on Sheet 9, sections A-O and A-J both have branches (i.e. the short ducts leading to the return grills). Therefore in addition to the braches being sized to match the pressure drop from their branch point to the end of the longest run, both "main runs," A-O and A-J, must have equal pressure drop. This is true because both sections originate from the same plenum. The pressure drop through section A-O was calculated first, then section A-J was sized to match the pressure drop through A-O. Once this was accomplished, the branches to the other return grills were sized using the balance method, for their corresponding "main run." Table 16 provides the equivalent lengths of all runs in the return ducting, used in sizing calculations, determined in a similar fashion as the supply ducting. The return grill pressure drops are not included in the equivalent length calculations because each run has an identical grill and airflow rate, and therefore, an identical pressure loss. The section designations in Table 16 correspond to the duct section labels as shown in Appendix B, Sheet 9. Table 16. Return System Equivalent Length Calculations Section Individual Lengths L e Main Run (A-O) A-P 35' (plenum) + 50' (duct) +10' (90 o elbow) +8' (duct) + 5' (Branch Main) 108' P-Q 15' (duct) + 5' (Branch Main) 20' Q-R 20' (duct) + 5' (Branch Main) 25' R-S 20' (duct) + 5' (Branch Main) 25' S-O 20' (duct) +10' (90 o elbow) +1' (duct) 31' Main Run (A-J) A-B 35' (plenum) + 8' (duct) + 5' (Branch Main) 48' B-C 15' (duct) + 5' (Branch Main) 20' C-D 20' (duct) + 5' (Branch Main) 25' D-E 20' (duct) + 5' (Branch Main) 25' E-J 20' (duct) +10' (90 o elbow) +1' (duct) 31' Branch K-P 50' (Branch Main) + 1' (duct) 51' L-Q 50' (Branch Main) + 1' (duct) 51' M-R 50' (Branch Main) + 1' (duct) 51' N-S 50' (Branch Main) + 1' (duct) 51' B-F 50' (Branch Main) + 1' (duct) 51' C-G 50' (Branch Main) + 1' (duct) 51' D-H 50' (Branch Main) + 1' (duct) 51' E-I 50' (Branch Main) + 1' (duct) 51' 21

24 Using the Equivalent Length Method to calculate the pressure drop through each path that the return air can travel, with the equivalent lenghts provided in Table 17, the pressure drop through section A-O was calculated after iteration, and is provided in Table 17. Also Table 17 provides the pressure drop calculations for the other "main run," section A-J. And, as can be seen, the pressure drop through both runs is the same. Therefore, since they are both connected to the same plenum, on the suction side of the fan, equal quantities of air should travel through them, namely 5,500 cfm in each run. As depicted in Table 17, slightly smaller duct sizes were used in section A-J, to provide additional pressure drop to equalize with section A-O (section A-O has an additional sizty feet of equivalent duct length). Table 17. Return System Main Duct Pressure Drop Balance Method (Main Duct Run A-O) Section CFM Le (ft) De (in) V (ft/min) Delta-P o /100 ft Section Delta-P o A-P 5, P-Q 4, Q-R 3, R-S 2, S-O 1, Total Balance Method (Main Duct Run A-J) Section CFM Le (ft) De (in) V (ft/min) Delta-P o /100 ft Section Delta-P o A-B 5, , B-C 4, , C-D 3, , D-E 2, , E-J 1, , Total Once the two "main runs" were sized, the respective braches were sized, using the Balance Method, to ensure that approximately 1,100 cfm enters each return grill. As shown in Table 18, the branches from section A-O, and the branches from section A-J are sized so that their pressure drop matches the pressure drop of the duct run that begins at the respective branch point to the end to the respective longest run. The duct sizes, selected for each branch, provide the necessary pressure drop, so that the return system is balanced. Based on the calculations in Tables 17 and 18, after much iteration, the return 22

25 system is considered balanced. The pressure drop, through the return system, not including the pressure drop through the grill, was calculated as " w.g. Table 18. Return System Remaining Branch Duct Sizing Branches From Section A-O Section Required Delta-P o Le (ft) Delta- P o /100 ft CFM De (in) V (ft/min) K-P , L-Q , M-R , N-S , Branches from Section A-J Section Required Delta- Le (ft) Delta-P o P o /100 ft CFM De (in) V (ft/min) B-F , ,029 C-G , ,029 D-H , E-I , Fan Selection To select a fan for the Library HVAC system, the total system pressure drop must be determined. This is done by summing absolute value of all the individual pressure drops calculated previously. Also, assumed pressure drops for the cooling coil and filters are neccessary. As stated in previous sections and Tables, the supply system pressure drop is " w.g., the diffuser pressure drop is " w.g., the return system pressure drop is " w.g., and the return grill pressure drop is " w.g. The cooling coil pressure drop is assumed to be " w.g., and the pressure drop due to various filters in the system is assumed to be " w.g. Plenum losses before and after the fan are included in the supply and return system pressure drop calculations. In order to ensure the fan is capable of delivering air through the duct system, a margin of 15% in pressure drop is added to account for any additional losses overlooked, as well as degradation of the duct system over time from fouling. Table 19 shows a tabulation of system pressure losses, and a total P o for fan selection purposes. As can be seen in Table 19, the total pressure drop does not exceed 23

HVAC Calculations and Duct Sizing

HVAC Calculations and Duct Sizing PDH Course M199 HVAC Calculations and Duct Sizing Gary D. Beckfeld, M.S.E., P.E. 2007 PDH Center 2410 Dakota Lakes Drive Herndon, VA 20171-2995 Phone: 703-478-6833 Fax: 703-481-9535 www.pdhcenter.com An

More information

Heating Load Calculation

Heating Load Calculation Heating Load Calculation ME 425 Air Conditioning System Design Keith E. Elder, P.E. Heating Load Calculation The heating load calculation begins with the determination of heat loss through a variety of

More information

Cooling Load Calculations and Principles

Cooling Load Calculations and Principles Cooling Load Calculations and Principles Course No: M06-004 Credit: 6 PDH A. Bhatia Continuing Education and Development, Inc. 9 Greyridge Farm Court Stony Point, NY 10980 P: (877) 322-5800 F: (877) 322-4774

More information

Software Development for Cooling Load Estimation by CLTD Method

Software Development for Cooling Load Estimation by CLTD Method IOSR Journal of Mechanical and Civil Engineering (IOSR-JMCE) ISSN: 2278-1684Volume 3, Issue 6 (Nov. - Dec. 2012), PP 01-06 Software Development for Cooling Load Estimation by CLTD Method Tousif Ahmed Department

More information

UNIVERSITY OF MISSOURI 23 0000 - Heating Ventilating and Air-Conditioning (HVAC) March 2015.01

UNIVERSITY OF MISSOURI 23 0000 - Heating Ventilating and Air-Conditioning (HVAC) March 2015.01 GENERAL: This section provides general standards for overall sizing and design of Heating, Ventilating, and Air Conditioning (HVAC) systems. Other sections contain specific standards for each system per

More information

HVAC Systems: Overview

HVAC Systems: Overview HVAC Systems: Overview Michael J. Brandemuehl, Ph.D, P.E. University of Colorado Boulder, CO, USA Overview System Description Secondary HVAC Systems Air distribution Room diffusers and air terminals Duct

More information

AIRCONDITIONING Cooling Loads Calculations

AIRCONDITIONING Cooling Loads Calculations Calculations -1- AIRCONDITIONING Cooling s Calculations Employer : 4M SA Project Location : ASHRAE Office Room : Example from ASHRAE 2013 Handbook - Fundamentals : Chapter 18, Single Room Example (p. 18.37)

More information

Refrigeration Manual. Part 3 - The Refrigeration Load

Refrigeration Manual. Part 3 - The Refrigeration Load Refrigeration Manual Part 3 - The Refrigeration Load FOREWORD The practice of refrigeration undoubtedly goes back as far as the history of mankind, but for thousands of years the only cooling mediums were

More information

Characteristics of Evaporators

Characteristics of Evaporators Characteristics of Evaporators Roger D. Holder, CM, MSME 10-28-2003 Heat or Energy In this paper, we will discuss the characteristics of an evaporator coil. The variance of the operational condenses of

More information

CHAPTER 3. BUILDING THERMAL LOAD ESTIMATION

CHAPTER 3. BUILDING THERMAL LOAD ESTIMATION CHAPTER 3. BUILDING THERMAL LOAD ESTIMATION 3.1 Purpose of Thermal Load Estimation 3.2 Heating Load versus Cooling Load 3.3 Critical Conditions for Design 3.4 Manual versus Computer Calculations 3.5 Heating

More information

Glossary of Heating, Ventilation and Air Conditioning Terms

Glossary of Heating, Ventilation and Air Conditioning Terms Glossary of Heating, Ventilation and Air Conditioning Terms Air Change: Unlike re-circulated air, this is the total air required to completely replace the air in a room or building. Air Conditioner: Equipment

More information

Air Conditioning Contractors of America

Air Conditioning Contractors of America Air Conditioning Contractors of America WHO IS ACCA???? Industry Manuals Residential D, J, S, H, RS, T, P A manual J load calculation is a measurement of how much heating and cooling capacity a home will

More information

Comparing Air Cooler Ratings Part 1: Not All Rating Methods are Created Equal

Comparing Air Cooler Ratings Part 1: Not All Rating Methods are Created Equal Technical Bulletin By Bruce I. Nelson, P.E., President, Colmac Coil Manufacturing, Inc. Comparing Air Cooler Ratings Part 1: Not All Rating Methods are Created Equal SUMMARY Refrigeration air coolers (evaporators)

More information

Energy Efficient Building Design College of Architecture Illinois Institute of Technology, Chicago. Relative Humidities RH% 49.4. 0.

Energy Efficient Building Design College of Architecture Illinois Institute of Technology, Chicago. Relative Humidities RH% 49.4. 0. Psychrometrics Psychrometric Chart Relative Humidities RH% 49.4 100% 80% 0.030 Enthalpies 70% H btu/lb 46.5 0.028 85 Not to Scale 0.026 Humidity Numbers and Values 43.7 60% Ratios are approximate 0.024

More information

Residential HVAC System Sizing

Residential HVAC System Sizing Residential HVAC System Sizing William P. Goss University of Massachusetts, Amherst, Massachusetts, USA Corresponding email: goss@acad.umass.edu SUMMARY Heating, ventilating and air-conditioning (HVAC)

More information

Presentation Outline. Common Terms / Concepts HVAC Building Blocks. Links. Plant Level Building Blocks. Air Distribution Building Blocks

Presentation Outline. Common Terms / Concepts HVAC Building Blocks. Links. Plant Level Building Blocks. Air Distribution Building Blocks Presentation Outline Common Terms / Concepts HVAC Building Blocks Plant Level Building Blocks Description / Application Data Green opportunities Selection Criteria Air Distribution Building Blocks same

More information

UNDERSTANDING AND USING THE HVAC DESIGN REVIEW FORM

UNDERSTANDING AND USING THE HVAC DESIGN REVIEW FORM Page 1 UNDERSTANDING AND USING THE HVAC DESIGN REVIEW FORM Each of the 38 points of requested information is discussed, and references to the supporting manual are given to substantiate the requirement.

More information

COMMERCIAL HVAC EQUIPMENT. Condensers and Cooling Towers

COMMERCIAL HVAC EQUIPMENT. Condensers and Cooling Towers COMMERCIAL HVAC EQUIPMENT Condensers and Cooling Towers Technical Development Programs (TDP) are modules of technical training on HVAC theory, system design, equipment selection and application topics.

More information

DEVELOPMENT OF AN OPEN SOURCE HOURLY BUILDING ENERGY MODELING SOFTWARE TOOL

DEVELOPMENT OF AN OPEN SOURCE HOURLY BUILDING ENERGY MODELING SOFTWARE TOOL DEVELOPMENT OF AN OPEN SOURCE HOURLY BUILDING ENERGY MODELING SOFTWARE TOOL Brittany Hanam, MASc, EIT RDH Building Engineering Ltd. Vancouver, BC John Straube, PhD, P.Eng. Building Engineering Group, Civil

More information

Creating Efficient HVAC Systems

Creating Efficient HVAC Systems Creating Efficient HVAC Systems Heating and Cooling Fundamentals for Commercial Buildings Heating, ventilating, and air conditioning (HVAC) systems account for nearly half of the energy used in a typical

More information

Comparing Energy Savings of Different VAV Systems

Comparing Energy Savings of Different VAV Systems Comparing Energy Savings of Different VAV Systems Prepared By: Martyn Dodd mart@energysoft.com EnergySoft LLC 1025 5th Street, Suite A Novato, CA 94945 415-897-6400 www.energysoft.com Last Modified: March

More information

Radiant Heating and Cooling Systems BY KWANG WOO KIM, ARCH.D., MEMBER ASHRAE; BJARNE W. OLESEN, PH.D., FELLOW ASHRAE

Radiant Heating and Cooling Systems BY KWANG WOO KIM, ARCH.D., MEMBER ASHRAE; BJARNE W. OLESEN, PH.D., FELLOW ASHRAE TECHNICAL FEATURE Fundamentals at Work This article was published in ASHRAE Journal, February 2015. Copyright 2015 ASHRAE. Posted at www.ashrae.org. This article may not be copied and/or distributed electronically

More information

Methods for Effective Room Air Distribution. Dan Int-Hout Chief Engineer, Krueger Richardson, Texas

Methods for Effective Room Air Distribution. Dan Int-Hout Chief Engineer, Krueger Richardson, Texas Methods for Effective Room Air Distribution Dan Int-Hout Chief Engineer, Krueger Richardson, Texas Agenda Overview LEED issues and Update Perimeter Acoustics Thermal Comfort IAQ / Standard 62.1 Update

More information

Residential HVAC Load Sizing Training October 14, 2015. David Kaiser Green Code Plan Reviewer

Residential HVAC Load Sizing Training October 14, 2015. David Kaiser Green Code Plan Reviewer Residential HVAC Load Sizing Training October 14, 2015 David Kaiser Green Code Plan Reviewer DCRA - Green Building Division Regulations of green codes including: Green Building Act Green Construction Code

More information

Energy Use in Residential Housing: A Comparison of Insulating Concrete Form and Wood Frame Walls

Energy Use in Residential Housing: A Comparison of Insulating Concrete Form and Wood Frame Walls PCA R&D Serial No. 415 Energy Use in Residential Housing: A Comparison of Insulating Concrete Form and Wood Frame Walls by John Gajda and Martha VanGeem 000 Portland Cement Association KEYWORDS Concrete,

More information

EFFECTS OF INDOOR RELATIVE HUMIDITY ON REFRIGERATED DISPLAY CASE PERFORMANCE

EFFECTS OF INDOOR RELATIVE HUMIDITY ON REFRIGERATED DISPLAY CASE PERFORMANCE P (5, EFFECTS OF INDOOR RELATIVE HUMIDITY ON REFRIGERATED DISPLAY CASE PERFORMANCE Ronald H. Howell, Professor Luis Rosario, Graduate Student Antonio Bula, Graduate Student Department of Mechanical Engineering

More information

CODE NOTES. Insulation Requirements in Commercial Buildings for Mechanical and Service Hot-Water Piping

CODE NOTES. Insulation Requirements in Commercial Buildings for Mechanical and Service Hot-Water Piping BUILDING TECHNOLOGIES PROGRAM Insulation Requirements in Commercial Buildings for Mechanical and Service Hot-Water Piping The intent of the pipe insulation requirements is to reduce temperature changes

More information

THERMAL LOSSES Thermal Losses Calculations

THERMAL LOSSES Thermal Losses Calculations Calculations -1- THERMAL LOSSES Thermal Losses Calculations Employer : 4M SA Project Location : ASHRAE Office Room : Example from ASHRAE 2013 Handbook - Fundamentals : Chapter 18, Single Room Example Peak

More information

Cooling Audit for Identifying Potential Cooling Problems in Data Centers

Cooling Audit for Identifying Potential Cooling Problems in Data Centers Cooling Audit for Identifying Potential Cooling Problems in Data Centers By Kevin Dunlap White Paper #40 Revision 2 Executive Summary The compaction of information technology equipment and simultaneous

More information

THE PSYCHROMETRIC CHART AND ITS USE

THE PSYCHROMETRIC CHART AND ITS USE Service Application Manual SAM Chapter 630-16 Section 3A THE PSYCHROMETRIC CHART AND ITS USE Psychrometry is an impressive word which is defined as the measurement of the moisture content of air. In broader

More information

Verizon SMARTS Data Center Design Phase 1 Conceptual Study Report Ms. Leah Zabarenko Verizon Business 2606A Carsins Run Road Aberdeen, MD 21001

Verizon SMARTS Data Center Design Phase 1 Conceptual Study Report Ms. Leah Zabarenko Verizon Business 2606A Carsins Run Road Aberdeen, MD 21001 Verizon SMARTS Data Center Design Phase 1 Conceptual Study Report Ms. Leah Zabarenko Verizon Business 2606A Carsins Run Road Aberdeen, MD 21001 Presented by: Liberty Engineering, LLP 1609 Connecticut Avenue

More information

EnergyPro Building Energy Analysis. Assisted Living Building

EnergyPro Building Energy Analysis. Assisted Living Building EnergyPro Building Energy Analysis Assisted Living Building EnergyPro Building Energy Analysis for an assisted living building Project Scope The purpose of the EnergyPro energy model was to evaluate the

More information

Energy Efficient Building Design College of Architecture Illinois Institute of Technology, Chicago. Ceiling/Airspace

Energy Efficient Building Design College of Architecture Illinois Institute of Technology, Chicago. Ceiling/Airspace HEAT GAINS and LOSSES : ROOFS and WALLS Wall Roof Ts To Ts To Ti Ceiling/Airspace Ti Roof and wall are analyzed in the same way. In winter the heat loss is simple transmission based on the inside and outside

More information

Lesson 36 Selection Of Air Conditioning Systems

Lesson 36 Selection Of Air Conditioning Systems Lesson 36 Selection Of Air Conditioning Systems Version 1 ME, IIT Kharagpur 1 The specific objectives of this chapter are to: 1. Introduction to thermal distribution systems and their functions (Section

More information

Yijun Gao, Wei Wu, Zongwei Han, Xianting Li *

Yijun Gao, Wei Wu, Zongwei Han, Xianting Li * Study on the performance of air conditioning system combining heat pipe and vapor compression based on ground source energy-bus for commercial buildings in north China Yijun Gao, Wei Wu, Zongwei Han, Xianting

More information

Below are detailed instructions for using the EMS load calculator.

Below are detailed instructions for using the EMS load calculator. Introduction The EMS load calculator is designed to make load calculating as painless as possible. For sizing the equipment, only the first three tabs (Steps 1, 2 & 3) need to be completed. This process

More information

Preliminary Final Proposal

Preliminary Final Proposal 1 Butler Memorial Hospital New Inpatient Tower Senior Capstone Project Mechanical Option Preliminary Final Proposal Mechanical System Re-design and Breadth Topics Butler Memorial Hospital New Inpatient

More information

Pool Dehumidification Basics

Pool Dehumidification Basics Copyright 2009 Wescor. All rights reserved. Permission granted to reproduce for personal and educational use only. When energy costs were low, many pool owners considered only first cost when choosing

More information

HVAC and REFRIGERATION

HVAC and REFRIGERATION This is a preview. Some pages have been omitted. PE principles and practice prracticce of engineering mechanical: HVAC and REFRIGERATION sample questions + solutions Copyright 2011 by NCEES. All rights

More information

Innovent LASER Packaged Fresh Air Conditioning Units

Innovent LASER Packaged Fresh Air Conditioning Units LASER Latent And Sensible Energy Reduction Latent And Sensible Energy Reduction For Outside Air Innovent LASER Packaged Fresh Air Conditioning Units Innovent LASER units provide both sensible and latent

More information

Components HVAC General Standards HVAC Guidelines HVAC System Selection Life Cycle Cost Analysis

Components HVAC General Standards HVAC Guidelines HVAC System Selection Life Cycle Cost Analysis Components HVAC General System Selection Life Cycle Cost Analysis Outdoor Air Design Values Indoor Air Design Values Outdoor Air Ventilation Welding Ventilation Temperature Control Systems Ductwork HVAC

More information

How To Design A Building In New Delhi

How To Design A Building In New Delhi ENERGY EFFICIENT HVAC DESIGN FOR COMPOSITE CLIMATE Overview of Design Conditions: Air conditioning system consumes most of the energy that a building needs in its operation. In order to reduce energy consumption

More information

HOT & COLD. Basic Thermodynamics and Large Building Heating and Cooling

HOT & COLD. Basic Thermodynamics and Large Building Heating and Cooling HOT & COLD Basic Thermodynamics and Large Building Heating and Cooling What is Thermodynamics? It s the study of energy conversion using heat and other forms of energy based on temperature, volume, and

More information

ENERGY EFFICIENT HVAC DESIGN FOR WARM-HUMID CLIMATE CLIMATE

ENERGY EFFICIENT HVAC DESIGN FOR WARM-HUMID CLIMATE CLIMATE ENERGY EFFICIENT HVAC DESIGN FOR WARM-HUMID CLIMATE CLIMATE Overview of Design Conditions: Air conditioning system consumes most of the energy that a building needs in its operation. In order to reduce

More information

Heating, Ventilation & Air Conditioning Equipment

Heating, Ventilation & Air Conditioning Equipment FinAnswer Express Wyoming Incentive Catalog Effective as of October 1, 2011 Heating, Ventilation & Air Conditioning Equipment Rocky Mountain Power provides incentives for many types of energy efficient

More information

1932 Lexington Houston, Texas 77098-4220 (713) 524-4877. Recommendations for installation of cooling systems

1932 Lexington Houston, Texas 77098-4220 (713) 524-4877. Recommendations for installation of cooling systems 1932 Lexington Houston, Texas 77098-4220 (713) 524-4877 The purpose for this information is to provide a better understanding of the HVAC equipment, components, designs, and installations, of HVAC system

More information

Thermal Mass Availability for Cooling Data Centers during Power Shutdown

Thermal Mass Availability for Cooling Data Centers during Power Shutdown 2010 American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). Published in ASHRAE Transactions (2010, vol 116, part 2). For personal use only. Additional reproduction,

More information

Home Energy Evaluation Report

Home Energy Evaluation Report Home Energy Evaluation Report Nate Begeman, 1550 Saint Francis Dr San Jose, CA 95125 Air Infiltration Current Air Leakage 2,852 Current Air Changes Per Hour 0.91 Recommended Air Changes Per Hour 0.35 Percent

More information

HVAC Made Easy: A Guide to Heating & Cooling Load Estimation

HVAC Made Easy: A Guide to Heating & Cooling Load Estimation PDHonline Course M196 (4 PDH) HVAC Made Easy: A Guide to Heating & Cooling Load Estimation Instructor: A. Bhatia, B.E. 2012 PDH Online PDH Center 5272 Meadow Estates Drive Fairfax, VA 22030-6658 Phone

More information

Answers to Your Questions from the Webinar

Answers to Your Questions from the Webinar 2008 Desert Aire and USA Swimming. Used by permission. Desert Aire & USA Swimming - Aquatics Webinar - Answers to Your Questions Answers to Your Questions from the Webinar Thank you for your interest in

More information

Energy Efficiency. Energy Efficient Home Cooling:

Energy Efficiency. Energy Efficient Home Cooling: Energy Efficiency Energy Efficient Home Cooling: Choosing an air conditioning system is an important decision. A poor choice may be costly to purchase and operate and yet fail to provide the desired cooling

More information

Water Fired Chiller/Chiller-Heater. WFC-S Series: 10, 20 and 30 RT Cooling

Water Fired Chiller/Chiller-Heater. WFC-S Series: 10, 20 and 30 RT Cooling Water Fired Chiller/Chiller-Heater WFC-S Series: 1, 2 and 3 RT Cooling W E A R E F R I E N D L Y T O T H E E A R T H Water Fired SINGLE-EFFECT Chiller or Chiller-Heater Absorption Principle Cooling Cycle

More information

Element D Services Heating, Ventilating, and Air Conditioning

Element D Services Heating, Ventilating, and Air Conditioning Load Calculation Criteria PART 1 - GENERAL 1.01 OVERVIEW A. This section includes requirements for calculating HVAC cooling and heating loads. B. Load calculations must be performed in accordance with

More information

Data Bulletin. Mounting Variable Frequency Drives in Electrical Enclosures Thermal Concerns OVERVIEW WHY VARIABLE FREQUENCY DRIVES THERMAL MANAGEMENT?

Data Bulletin. Mounting Variable Frequency Drives in Electrical Enclosures Thermal Concerns OVERVIEW WHY VARIABLE FREQUENCY DRIVES THERMAL MANAGEMENT? Data Bulletin April 2001 Raleigh, NC, USA Mounting Variable Frequency Drives in Electrical Enclosures Thermal Concerns OVERVIEW Variable frequency drives are available from manufacturers as enclosed engineered

More information

VAV Laboratory Room Airflow The Lowdown on Turndown

VAV Laboratory Room Airflow The Lowdown on Turndown Technology Report March, 2003 VAV Laboratory The Lowdown on Turndown Turndown comparison of these two turndown ratios. Note the small actual airflow difference between them. control ranges are normally

More information

Cooling Load Estimation and Air Conditioning Unit Selection for Hibir Boat

Cooling Load Estimation and Air Conditioning Unit Selection for Hibir Boat The International Journal Of Engineering And Science (IJES) Volume 3 Issue 5 Pages 63-72 2014 ISSN (e): 2319 1813 ISSN (p): 2319 1805 Cooling Load Estimation and Air Conditioning Unit Selection for Hibir

More information

SECTION 11 78 13 MORTUARY REFRIGERATORS

SECTION 11 78 13 MORTUARY REFRIGERATORS PART 1 - GENERAL 1.1 DESCRIPTION SECTION 11 78 13 MORTUARY REFRIGERATORS SPEC WRITER NOTE: Delete between //---// if not applicable to project. Also delete any other item or paragraph not applicable in

More information

CAE 331/513 Building Science Fall 2013

CAE 331/513 Building Science Fall 2013 CAE 331/513 Building Science Fall 2013 Lecture 10: November 11, 2013 Finish cooling loads HVAC systems Energy estimation methods Advancing energy, environmental, and sustainability research within the

More information

Impacts of Refrigerant Charge on Air Conditioner and Heat Pump Performance

Impacts of Refrigerant Charge on Air Conditioner and Heat Pump Performance Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2010 Impacts of Refrigerant Charge on Air Conditioner and Heat Pump Performance

More information

Chapter 3.4: HVAC & Refrigeration System

Chapter 3.4: HVAC & Refrigeration System Chapter 3.4: HVAC & Refrigeration System Part I: Objective type questions and answers 1. One ton of refrigeration (TR) is equal to. a) Kcal/h b) 3.51 kw c) 120oo BTU/h d) all 2. The driving force for refrigeration

More information

Heating, Ventilation & Air Conditioning Equipment

Heating, Ventilation & Air Conditioning Equipment FinAnswer Express Utah Incentive Catalog Effective as of May 19, 2012 Heating, Ventilation & Air Conditioning Equipment Rocky Mountain Power provides incentives for many types of energy-efficient technologies.

More information

Fan Applications & System Guide

Fan Applications & System Guide Fan Applications & System Guide Airflow for general ventilation can be calculated by; Area Method Air Change Method Occupancy Method Ventilation Calculation Methods Area Method Derives the ventilation

More information

Impacts of Static Pressure Set Level on the HVAC Energy Consumption and Indoor Conditions

Impacts of Static Pressure Set Level on the HVAC Energy Consumption and Indoor Conditions Impacts of Static Pressure Set Level on the HVAC Energy Consumption and Indoor Conditions M. Liu, Y. Zhu, D. E. Claridge Energy Systems Laboratory Texas A&M University Ed. White Energy Management Operation

More information

Building Energy Systems. - HVAC: Heating, Distribution -

Building Energy Systems. - HVAC: Heating, Distribution - * Some of the images used in these slides are taken from the internet for instructional purposes only Building Energy Systems - HVAC: Heating, Distribution - Bryan Eisenhower Associate Director Center

More information

CONDENSATION IN REFRIDGERATED BUILDINGS

CONDENSATION IN REFRIDGERATED BUILDINGS CONDENSATION IN REFRIDGERATED BUILDINGS By: Steve Salisbury Nov. 10, 2010 (revised Nov. 14, 2013) Introduction The following discussion reviews the basic causes of condensation in refrigerated buildings

More information

Mechanical Systems Proposal revised

Mechanical Systems Proposal revised Mechanical Systems Proposal revised Prepared for: Dr. William Bahnfleth, Professor The Pennsylvania State University, Department of Architectural Engineering Prepared by: Chris Nicolais Mechanical Option

More information

Moisture Control. It s The Dew Point. Stupid! Its not the humidity.

Moisture Control. It s The Dew Point. Stupid! Its not the humidity. Moisture Control Its not the humidity. It s The Dew Point Stupid! Mike Schell EpiphanyTec Inc. Santa Barbara, CA mschell@epiphanytec.com 805 687-3175 Matching great technology to market need! Topics SHR

More information

Department of Mechanical and Materials Engineering Florida International University, Miami, FL. EML 4905 Senior Design Project

Department of Mechanical and Materials Engineering Florida International University, Miami, FL. EML 4905 Senior Design Project Department of Mechanical and Materials Engineering Florida International University, Miami, FL EML 4905 Senior Design Project HVAC Design for Green Building Miami Green Final Report Submitted By: James

More information

Chilled Water HVAC Systems

Chilled Water HVAC Systems Chilled Water HVAC Systems By Ron Prager, Brinco Mechanical Services, Inc. Types of water based systems: There are three types of HVAC systems that utilize water as a heat transfer medium. The first system,

More information

Equivalents & Conversion Factors 406 Capacity Formulas for Steam Loads 407 Formulas for Control Valve Sizing 408-409

Equivalents & Conversion Factors 406 Capacity Formulas for Steam Loads 407 Formulas for Control Valve Sizing 408-409 Engineering Data Table of Contents Page No. I II Formulas, Conversions & Guidelines Equivalents & Conversion Factors 406 Capacity Formulas for Steam Loads 407 Formulas for Control Sizing 408-409 Steam

More information

By Tom Brooke PE, CEM

By Tom Brooke PE, CEM Air conditioning applications can be broadly categorized as either standard or critical. The former, often called comfort cooling, traditionally just controlled to maintain a zone setpoint dry bulb temperature

More information

DUCT SYSTEM DESIGN CONSIDERATIONS Part 1

DUCT SYSTEM DESIGN CONSIDERATIONS Part 1 Refrigeration Service Engineers Society 1666 Rand Road Des Plaines, Illinois 60016 DUCT SYSTEM DESIGN CONSIDERATIONS Part 1 by Roger M Hensley, CMS TYPES OF SUPPLY DUCT SYSTEMS There are several basic

More information

UNIT 2 REFRIGERATION CYCLE

UNIT 2 REFRIGERATION CYCLE UNIT 2 REFRIGERATION CYCLE Refrigeration Cycle Structure 2. Introduction Objectives 2.2 Vapour Compression Cycle 2.2. Simple Vapour Compression Refrigeration Cycle 2.2.2 Theoretical Vapour Compression

More information

HVAC Basic Science - System Capacity

HVAC Basic Science - System Capacity HVAC Basic Science - System Capacity Btu/hour, btu/h, b/h, btuh. btu?? 1 MBH = 1000 btu/hour 1 KBH = 1000 btu/hour 1 ton of cooling= 12,000 btu/hour 1 watt = 3.414 btu/hour 1 kilowatt = 1000 watts = 3,414

More information

EFA PSBP. Natural Ventilation Strategy. Introduction. 1.1 Relevant legislation. 1.1.1 The Building Regulations 2010

EFA PSBP. Natural Ventilation Strategy. Introduction. 1.1 Relevant legislation. 1.1.1 The Building Regulations 2010 EFA PSBP Natural Ventilation Strategy Introduction The Baseline Designs Project will provide scheme design details for a number of Primary and Secondary School Exemplars. For the purposes of setting a

More information

Theoretical Study on Separate Sensible and Latent Cooling Air-Conditioning System

Theoretical Study on Separate Sensible and Latent Cooling Air-Conditioning System Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2008 Theoretical Study on Separate Sensible and Latent Cooling Air-Conditioning

More information

Total Heat Versus Sensible Heat Evaporator Selection Methods & Application

Total Heat Versus Sensible Heat Evaporator Selection Methods & Application Total Heat Versus Sensible Heat Evaporator Selection Methods & Application Scope The purpose of this paper is to provide specifying engineers, purchasers and users of evaporators in industrial refrigeration

More information

Performance Rating of Room Fan- Coils

Performance Rating of Room Fan- Coils ANSI/AHRI Standard 440 with Addendum 1 (Formerly ARI Standard 440) 2008 Standard for Performance Rating of Room Fan- Coils ANSI/AHRI STANDARD 440-2008 WITH ADDENDUM 1, PERFORMANCE RATING OF ROOM FAN-COILS

More information

DOE FEMP First Thursday Seminar. Learner Guide. Core Competency Areas Addressed in the Training. Energy/Sustainability Managers and Facility Managers

DOE FEMP First Thursday Seminar. Learner Guide. Core Competency Areas Addressed in the Training. Energy/Sustainability Managers and Facility Managers DOE FEMP First Thursday Seminar Achieving Energy Efficient Data Centers with New ASHRAE Thermal Guidelines Learner Guide Core Competency Areas Addressed in the Training Energy/Sustainability Managers and

More information

Glossary of HVAC Terms

Glossary of HVAC Terms Glossary of HVAC Terms Heating, Ventilation and Air Conditioning (HVAC) is a major sub- discipline of mechanical engineering. The goal of HVAC design is to balance indoor environmental comfort with other

More information

Whole House Dehumidification for Occupant Comfort and Energy Savings

Whole House Dehumidification for Occupant Comfort and Energy Savings Downloaded from www.rsrews.com. Since 1968, RS Andrews has proudly served Atlanta's Heating, Air Conditioning & Plumbing Needs. Whole House Dehumidification for Occupant Comfort Energy Savings June 2009

More information

Molds and mildew are fungi that grow

Molds and mildew are fungi that grow Appendix C: Moisture, Mold and Mildew Molds and mildew are fungi that grow on the surfaces of objects, within pores, and in deteriorated materials. They can cause discoloration and odor problems, deteriorate

More information

Green Building Handbook for South Africa Chapter: Heating, Ventilation and Cooling Luke Osburn CSIR Built Environment

Green Building Handbook for South Africa Chapter: Heating, Ventilation and Cooling Luke Osburn CSIR Built Environment Green Building Handbook for South Africa Chapter: Heating, Ventilation and Cooling Luke Osburn CSIR Built Environment The heating, ventilation and cooling loads of typical commercial office space can range

More information

HOW TO CONDUCT ENERGY SAVINGS ANALYSIS IN A FACILITY VALUE ENGINEERING STUDY

HOW TO CONDUCT ENERGY SAVINGS ANALYSIS IN A FACILITY VALUE ENGINEERING STUDY HOW TO CONDUCT ENERGY SAVINGS ANALYSIS IN A FACILITY VALUE ENGINEERING STUDY Benson Kwong, CVS, PE, CEM, LEED AP, CCE envergie consulting, LLC Biography Benson Kwong is an independent consultant providing

More information

Calculating Total Cooling Requirements for Data Centers

Calculating Total Cooling Requirements for Data Centers Calculating Total Cooling Requirements for Data Centers By Neil Rasmussen White Paper #25 Revision 2 Executive Summary This document describes how to estimate heat output from Information Technology equipment

More information

Energy Recovery Ventilation Equipment

Energy Recovery Ventilation Equipment AHRI Standard 1060 (I-P) 2013 Standard for Performance Rating of Airto-Air Exchangers for Energy Recovery Ventilation Equipment IMPORTANT SAFETY DISCLAIMER AHRI does not set safety standards and does not

More information

Maximize energy savings Increase life of cooling equipment More reliable for extreme cold weather conditions There are disadvantages

Maximize energy savings Increase life of cooling equipment More reliable for extreme cold weather conditions There are disadvantages Objectives Increase awareness of the types of economizers currently used for data centers Provide designers/owners with an overview of the benefits and challenges associated with each type Outline some

More information

Flexibility, Efficiency In San Antonio Arena

Flexibility, Efficiency In San Antonio Arena 2005, American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). Reprinted by permission from ASHRAE Journal, (Vol. 47, No. 9, September 2005). This article may not

More information

Defining Quality. Building Comfort. Precision. Air Conditioning

Defining Quality. Building Comfort. Precision. Air Conditioning Defining Quality. Building Comfort. Precision Air Conditioning Today s technology rooms require precise, stable environments in order for sensitive electronics to operate optimally. Standard comfort air

More information

Why Do I Need Precision Air Conditioning?

Why Do I Need Precision Air Conditioning? Why Do I Need Precision Air Conditioning? Executive Summary Today's technology rooms require precise, stable environments in order for sensitive electronics to operate optimally. Standard comfort air

More information

AIR CONDITIONING EFFICIENCY F8 Energy eco-efficiency opportunities in Queensland Foundries

AIR CONDITIONING EFFICIENCY F8 Energy eco-efficiency opportunities in Queensland Foundries AIR CONDITIONING EFFICIENCY F8 Energy eco-efficiency opportunities in Queensland Foundries Hot tips and cool ideas to save energy and money! Air conditioning units or systems are often used by foundries

More information

> Executive summary. Explanation of Cooling and Air Conditioning Terminology for IT Professionals. White Paper 11 Revision 2. Contents.

> Executive summary. Explanation of Cooling and Air Conditioning Terminology for IT Professionals. White Paper 11 Revision 2. Contents. Explanation of Cooling and Air Conditioning Terminology for IT Professionals White Paper 11 Revision 2 by Tony Evans Click on a section to jump to it > Executive summary As power densities continue to

More information

A Glossary of HVAC Terms:

A Glossary of HVAC Terms: Since 1979 TACL A537C Doctor COOL & P rofessor HEA T The Team For All Seasons TM A Glossary of HVAC Terms: Confused by the many terms and acronyms surrounding your indoor comfort system? Don t be! This

More information

Code of Practice for Building Energy Audit

Code of Practice for Building Energy Audit Code of Practice for Building Energy Audit 2012 Code of Practice for Building Energy Audit Table of Contents Page No. 1. Introduction 1 2. Interpretations 1 3. Application 4 4. Technical Compliance with

More information

Carnegie Mellon University School of Architecture, Department of Mechanical Engineering Center for Building Performance and Diagnostics

Carnegie Mellon University School of Architecture, Department of Mechanical Engineering Center for Building Performance and Diagnostics Carnegie Mellon University School of Architecture, Department of Mechanical Engineering Center for Building Performance and Diagnostics A Presentation of Work in Progress 4 October 2006 in the Intelligent

More information

BILL OF QUANTITY FOR THE HVAC WORKS OF The Institute of space technology, near Toll Plaza (G.T. Road,) Islamabad

BILL OF QUANTITY FOR THE HVAC WORKS OF The Institute of space technology, near Toll Plaza (G.T. Road,) Islamabad BILL OF QUANTITY FOR THE HVAC WORKS OF The Institute of space technology, near Toll Plaza (G.T. Road,) Islamabad PLEASE MARK TICK ON LEFT BOX WHICH EQUIPMENT YOU HAVE QUOTED PROPOSAL BASED ON CHINESE EQUIPMENT

More information

STAYFLEX CORROSION CONTROL AND THERMAL INSULATION SYSTEM

STAYFLEX CORROSION CONTROL AND THERMAL INSULATION SYSTEM STAYFLEX CORROSION CONTROL AND THERMAL INSULATION SYSTEM Installed in Pre-engineered Steel Buildings Provides Lowest Cost Construction Method for CORROSIVE AND WET Environments PREFERRED SOLUTIONS, INC.

More information

Air Conditioning. The opportunity for energy efficiency. Low cost actions to reduce energy usage now

Air Conditioning. The opportunity for energy efficiency. Low cost actions to reduce energy usage now Fact Sheet #6 Air Conditioning In this fact sheet you will discover: The opportunity for energy efficiency How air conditioning works Low cost actions to reduce energy usage now Investments to reduce costs

More information

Case Study: Innovative Energy Efficiency Approaches in NOAA s Environmental Security Computing Center in Fairmont, West Virginia

Case Study: Innovative Energy Efficiency Approaches in NOAA s Environmental Security Computing Center in Fairmont, West Virginia Case Study: Innovative Energy Efficiency Approaches in NOAA s Environmental Security Computing Center in Fairmont, West Virginia Prepared for the U.S. Department of Energy s Federal Energy Management Program

More information