1 Setting New Standards Of Excellence In The Home Inspection Industry Atlantic Blvd. #104, Jacksonville, Fl Tel: (904) (888) Inspection 11/01/2014 Address: Date: October 31, :30 PM Dear Mr. & Mrs. Public, At your request, a visual inspection was conducted at the above referenced property. As noted in the PreInspection Agreement, proper care has been taken in performing this inspection and it is not an insurance policy or warranty that items found functional will remain so for any period of time, nor that every defect will be discovered. This inspection report is effectively a snapshot of the house, recording the visual conditions of the property as they existed at the time of the inspection only. Hidden or concealed defects cannot be included in this report. Home inspectors cannot predict future behavior, and as such, we cannot be responsible for things that occur after the inspection. The inspection itself and the attached report comply with the Standards of Practice and Code of Ethics of the Florida Association of Building Inspectors (FABI). This document, which is included in your report and available at defines the scope of a home inspection. Clients sometimes assume that a home inspection will include many things that are beyond the scope. We encourage you to read the Standards of Practice so that you clearly understand what things are included in the home inspection and report. A visual inspection does not involve determining the status of illegal construction or construction modifications on and/or to this property. Work performed without proper building permits may be a problem once you take possession of the property. We recommend communicating with the building department that has jurisdiction for this property to confirm the status of any building permits as this is not part of this inspection. Any recommendation for "Further Evaluation" should be performed PRIOR to the close of this sale. This is recommended so additional information is obtained and/or a properly licensed professional can evaluate our concerns further and inspect the remainder of the systems or components that may be outside our area of expertise or the scope of our inspection. This will be indicated by the following: "RECOMMEND FURTHER EVALUATION". Items may have a rating of Functional in the main report and still show as needing attention in the summary. Please review the entire report for complete details. Items needing repair are shown in "red", and regular recommended maintenance items or upgrades are shown in "green". For your convenience, a summary is included in the report which contains only those items needing attention. The report however should be reviewed entirely. The issue of water intrusion and leaks is always a concern. While we conduct this inspection with the use of an infrared camera, it is only possible to locate moisture intrusions and leaks with this technology if the moisture is still present in the interior of the building materials, and, optimal conditions exist for proper detection. Unless the conditions causing water intrusion or leaks are present at the time of the inspection, detection is virtually impossible. The report has been prepared for the exclusive use of our client. No use by third parties is intended. We will not be responsible to any parties for the contents of the report, other than the party named herein. The report itself is Copyrighted, and may not be used in whole or in part without our express written condition. Thank you very much for your business. If you have any questions, about the report or any of the homes components, please feel free to contact my office at anytime. Sincerely, Lou Prinzi Proudly Inspecting Jacksonville & Surrounding Areas Since 1997
2 HOME INSPECTION REPORT PREPARED FOR: John Q Public October 31, :30 PM NOTICE TO THIRD PARTIES: This Report is the exclusive property of First Choice Building Inspections, Inc. and the Client(s) listed above and is not transferable to any third parties or subsequent buyers. Its use by any unauthorized persons is strictly prohibited, and agents are specifically cautioned against giving it to any unauthorized third party. Our inspection and this Report have been performed with a written contract agreement that limits its scope and usefulness. Unauthorized recipients are therefore advised not to rely upon this Report, but rather to retain the services of an appropriately qualified home inspector of their choice to provide them with their own inspection and report. FCBI, Inc Atlantic Blvd. #104, Jacksonville, Fl (904) (888) Page 1
3 Table Of Contents GENERAL INFORMATION 4 SUMMARY OF REPAIRS NEEDED 8 ETERIOR 11 STRUCTURE 17 ROOF VENTING INSULATION 18 GARAGE CARPORT OUTBUILDING 22 ELECTRICAL 23 PLUMBING 25 HVAC HEATING & COOLING 27 INTERIOR 32 BATH KITCHEN LAUNDRY 36 LAWN IRRIGATION 38 MAINTENANCE SCHEDULE & TIPS 39 FABI STANDARDS OF PRACTICE & CODE OF ETHICS 48 INSPECTION AGREEMENT FCBI, Inc Atlantic Blvd. #104, Jacksonville, Fl (904) (888) Page 2
4 GENERAL INFORMATION: Client Information: John Q Public Contact #'s mrpublic@internet.com Inspection Address: Inspection Date: October 31, :30 PM People Present: Buyer, Buyer's agent Structure Type: Single Family Occupied/Furnished: Yes Access to some items such as: electrical outlets, windows, wall/floor surfaces, and cabinet interiors was restricted by furniture and personal belongings Entry Faces Weather: North Clear Approx. Size & Yr Built: Total 3326 Heated 2661 Built in Utilities: All utilities on Your Inspector: Lou Prinzi, ACI/RPI Florida License #HI282 American Society of Home Inspectors (ASHI) certification # Florida Association of Building Inspectors (FABI) certification #0580 TET COLOR SIGNIFICANCE: "Red" text indicates items where further attention, repair or replacement is needed. These items may denote a minor defect, major damage, a safety concern or where further evaluation by a specialist is deemed necessary. These comments are also duplicated in the "Summary Section". "Green" text indicates items where repairs/improvements are more of a maintenance item or suggested upgrade and can be made at the clients discretion. Some items may be essential and require nearterm correction. Others may represent logical longterm improvements that can be addressed at your convenience. "Black" text indicates observations and information regarding the general condition of the systems and components of the home. These include comments regarding deficiencies which are less than significant, comments which further expand on a significant deficiency, or comments on recommendations, tips, and other relevant resource information. POINT OF REFERENCE: When a specific location is mentioned, it is assumed the perspective is: exterior facing toward the home, and interior facing the exterior. USE OF PHOTOS: Your report includes many photographs. Some pictures are intended as a courtesy and are added for your information. Some are to help clarify where the inspector has been, what was looked at, and the condition of the system or component at the time of the inspection. Some of the pictures may be of deficiencies or problem areas. These are to help you better understand what is documented in the report and may allow you to see areas or items that you normally would not see. Not all problem areas or conditions will be supported with photos. All photos can be supplied to you on a disc if requested. FCBI, Inc Atlantic Blvd. #104, Jacksonville, Fl (904) (888) Page 3
5 COMPONENT OBSERVATIONS: Items noted as appearing "functional" are considered to be working as designed. Please note that items may have a defect and still be rated as functional if the defect does not hinder the overall operation. If additional investigation and/or action is suggested/recommended by the inspector, it is incumbent on the client to followthru in a timely manner to receive maximum benefit from this inspection. Furthermore, the inspector assumes no responsibility for any conditions which are not acted upon as recommended. Repairs or further investigation/evaluation should be accomplished by qualified licensed professionals specializing in that type of work. When we recommend repairs to or replacement of a component, we recommend the determination of appropriate corrective action be left to the professionals retained for the detailed evaluation and repair. Lower priority conditions that are neglected may become higher priority conditions if not acted upon. Do not equate low cost with low priority cost should not be the primary motivation for performing repairs. WOOD DECAY/DAMAGE: There could be areas with wood decay/damage that were not noted because they did not appear evident or suspicious upon visual inspection. Hidden wood destroying organism structural damage cannot be determined without invasive inspection of any known affected areas. This may be done at buyer's request by a licensed pest control company. Freshly painted surfaces can conceal damaged areas. This inspection is not a wood destroying organism inspection (termite inspection). The inspector is not licensed by the state of Florida to perform a WDO inspection. A WDO inspection is required by most lenders and must be ordered independently of this inspection. FCBI, Inc Atlantic Blvd. #104, Jacksonville, Fl (904) (888) Page 4
6 We May Not Mention Some Minor Things: Some say we are inconsistent because our reports identify some minor problems, but not others. The minor problems that are identified were discovered while looking for more significant problems. We note them simply as a courtesy. The intent of the inspection is not to find the $200 problems; it is to find the $2,000 problems. These are the things that affect people s decisions to purchase. Contractor s Advice: A common source of dissatisfaction with home inspectors comes from comments made by contractors. Contractor s opinions often differ from ours. Don t be surprised when three roofers all say the roof needs replacement, when we said that the roof would last a few more years with some minor repairs. Last Man In Theory: While our advice represents the most prudent thing to do, many contractors are reluctant to undertake these repairs. This is because of the last man in theory. The contractor fears that if he is the last person to work on the roof, he will get blamed if the roof leaks, regardless of whether or not the roof leak is his fault. Consequently, he won t want to do a minor repair with high liability, when he could reroof the entire house for more money and reduce the likelihood of a callback. This is understandable. Most Recent Advice Is Best: There is more to the last man in theory. It suggests that it is human nature for homeowners to believe the last bit of expert advice they receive, even if it is contrary to previous advice. As home inspectors, we unfortunately find ourselves in the position of first man in and consequently it is our advice that is often disbelieved. Why Didn t We See It? Contractors often say, I can t believe you had this house inspected, and the inspector didn t find this problem. There are several reasons for these apparent oversights: Most Contractors Have No Clue What s Inside or Outside The Scope Of A Standard Home Inspection: All of our inspections are conducted in accordance with the Standards of Practice of The American Society of Home Inspectors. The Standards of Practice specifically state what s included and excluded from the standard home inspection. Most contractors have no clue this document exists and many of them have a tendency to blame the Home Inspector for any issue found, regardless of whether the issue is within the scope of the standard home inspection. Conditions During The Inspection: It is difficult for homeowners to remember the circumstances in the house at the time of the inspection. Homeowners seldom remember that it was snowing, there was storage everywhere or that the furnace could not be turned on because the air conditioning was operating, etc. It s impossible for contractors to know what the circumstances were when the inspection was performed. The Wisdom Of Hindsight: When the problem manifests itself, it is very easy to have 20/20 hindsight. Anybody can say that the basement is wet when there is 2 feet of water on the floor. Predicting the problem is a different story. A Long Look: If we spent half an hour under the kitchen sink or 45 minutes disassembling the furnace, we d find more problems, too. Unfortunately, the inspection would take several days and would cost considerably more. We re Generalists: We are generalists; we are not specialists. The heating contractor may indeed have more heating expertise than we do. This is because we are expected to have heating expertise and plumbing expertise, structural expertise, electrical expertise, etc. FCBI, Inc Atlantic Blvd. #104, Jacksonville, Fl (904) (888) Page 5
7 An Invasive Look: Problems often become apparent when carpets or plaster are removed, when fixtures or cabinets are pulled out, and so on. A home inspection is a visual examination. We don t perform invasive or destructive tests. Not Insurance: In conclusion, a home inspection is designed to better your odds of not purchasing a money pit. It is not designed to eliminate all risk. For that reason, a home inspection should not be considered an insurance policy. The premium that an insurance company would have to charge for a policy with no deductible, no limit and an indefinite policy period would be considerably more than the fee we charge. It would also not include the value added by the inspection. FCBI, Inc Atlantic Blvd. #104, Jacksonville, Fl (904) (888) Page 6
8 SUMMARY FURTHER EVALUATION / REPAIRS NEEDED IMPORTANT NOTE PLEASE READ: The Summary is provided to allow a brief overview of the report. This summary is not encompassing and is not a substitute for reading the entire report. The Inspection Report, including the ASHI Standards of Practice, limitations, and Inspection Agreement must be read to fully assess the findings of the inspection. If this is a property sale, this list is not intended to determine which items may need to be addressed per the contractual requirements of the sale of the property. Any areas of uncertainty regarding to the contract should be clarified by consulting an attorney or real estate agent. NOTE: Main Report Sections Contain Additional Detail And Photos For Items Listed Below Point of Reference When a specific location is mentioned, it is assumed the perspective is from standing in front of the house facing the front door with our backs to the street. ETERIOR Entry / Patios / Enclosures: (Observations pertain to all patio areas unless otherwise noted) Flagstone patio at the rear had some settled and damaged sections. Standing water was observed along the rear wall indicating improper drainage. Repair by a qualified contractor is advised Tripping hazards were noted as a result of raised edges at the front entry tiles. This is considered a safety hazard and should be repaired. Exterior Doors: (Observations pertain to all doors unless otherwise noted) Weather gasket had gaps along the threshold and at the middle joint at the front door. No daylight should be visible around the frame when the door is closed. Open areas can allow a loss of conditioned air increasing energy consumption and cost. Cladding: Upper and lower horizontal control joints on the right side of the house were heavily damaged. Both upper and lower had extensive rust damage which has swelled and allowed moisture to enter below the joints. The damage is preventing the control joints from operating as designed and should be fully replaced with proper rustresistant material. It also lends doubt as to the appropriateness of all other control joints installed on the structure. This type of repair can be extensive and expensive and should be completed by a professional stucco contractor only. Stucco wall above the garage had some cracking damage with moisture intrusion detected (moisture meter used was a Tramex Moisture Encounter Plus). Wall left of the upper window had some stress cracks with moisture intrusion detected below the cracks. Area directly above the garage had a very wide crack which has allowed moisture to leak to the header above the garage door (registered as wet along the entire header). Moisture intrusion behind the stucco can cause a myriad of damage including, but not limited to, metal lathe rusting, sheathing/framing damage, insulation damage and fungal growth. Since this is basically a nonintrusive inspection and only readily accessible areas are inspected, the extent of the damage will not become evident until a more invasive inspection is performed which should include removal of the stucco. Highly recommend further evaluation by a professional stucco contractor. Trim Elements & Flashing: Wood trim was damaged at the front door. Replacement of the damaged trim is recommended. ROOF VENTING INSULATION Roof Covering Materials: Recommend obtaining any existing warranty and installation information regarding the roof from the seller. The shingles typically have a warranty from the manufacturer which can help you should they fail. As information, the roof installation has a permit on record however it does not list any inspections by the County. Recommend obtaining any inspection records the seller may have. Moisture stains are visible on the roof decking observed from inside the attic. Locations include the rear plumbing vent. Dark moisture stains or fungal growth usually indicates some leakage, and further evaluation for repair options by a roofing contractor is advised. FCBI, Inc Atlantic Blvd. #104, Jacksonville, Fl (904) (888) Page 7
9 Exposed Flashings: Drip edge flashing along the rear and sides is rusting. This is not a normal condition with a new roof installation (2006). The old flashing may have been reinstalled and/or the flashing is defective. Damaged flashing may allow leakage to the interior. Recommend full replacement of the drip edge flashing which is rusted. Attic / Insulation / Ventilation: Electric cable was running across the truss chords/framing near the attic opening. This is considered a safety hazard since walking on the wires can damage the insulation exposing live wires. Proper building practice for attics with permanent stairs, is to protect the wires with substantial guard strips that are at least as high as the cable, when the wires are across the top of floor joists within 7 feet of the opening. Attic steps had negative bends at the leg joints and the hardware was loose. This condition significantly reduces the overall structural stability when weight is applied, posing a serious safety hazard. It's possible the step assembly was not installed per the manufacturers installation instructions regarding proper trimming at the bottom legs (sometimes posted on the assembly), or the joints have become loose and damaged from age and use. Step joints should not flex when weight is applied. Recommend repair to comply with installation instructions, or full replacement if this cannot be provided. Highly advise not using the steps until repaired/replaced. Insulation in a number of areas has been compacted/disturbed with age, and complete coverage is no longer present with the true RValue somewhat less than when originally installed. Installation of additional insulation should be considered. GARAGE CARPORT OUTBUILDING Garage: Photoelectric eyes (reversing sensors) are installed more than 6 inches from the floor. A maximum of six inches is required to prevent a small child from slipping under the contact beam. Tension spring on double door needs adjustment. The door slams shut when in the manual operation mode. A properly balanced door, when operated in the manual mode, will remain open even when more than 3/4 of the way down, and can be easily opened when fully closed. This door is very heavy and will pose a safety hazard to the person operating it if they are not capable of supporting it, or lifting it open. ELECTRICAL Switches / Outlets / Fixtures/ Misc: Exterior rear outlet box was very loose and pulls easily from the wall. This is considered a safety hazard and should be repaired by an electrician. GFCI (Ground Fault Circuit Interrupter) protection was not provided at the kitchen outlet to the right of the sink. When this home was constructed, all countertop outlets within 6 feet of the kitchen sink were required to be GFCI protected. Have repaired by an electrician. HVAC HEATING & COOLING Cooling: (Details/Observations/Testing noted pertain to all units unless otherwise specified) The insulation wrap for the suction line to the condenser/compressor is damaged and needs replacement. This condition affects the efficiency of the cooling system and should be replaced. Temperature differential for the upstairs unit measured high at 27. The differential is the temperature between the air being sucked into the system (return air) versus the air coming out of the ducts (supply air). A normal temperature differential is 1422 degrees f. A temperature differential above 22 degrees indicates the system may not be operating properly which can be caused by a refrigerant imbalance and/or a dirty filter, coils, or fan. It could also mean there is some duct blockage or improperly sized ducts. Further evaluation by a professional HVAC technician is recommended. FCBI, Inc Atlantic Blvd. #104, Jacksonville, Fl (904) (888) Page 8
10 Although operational at the time of the inspection, it's recommended the heating and air system for the upstairs be fully replaced since it's operating well beyond the manufacturer's estimated lifespan of 15 years. Any component of a central cooling and heating system which is over 10 years age is categorized as being in fair condition, primarily due to its increased likelihood of breakdown and need for replacement in the future. Any service life in excess of 15 years is in the realm of good fortune only and should be viewed as such. INTERIOR Stairs & Handrails: The following conditions were observed at the interior stairway all which pose a safety hazard: Step riser heights were not consistent. Bottom riser is 1 inch higher than the rest. Also, at 8.5 inches it exceeds the maximum allowed height of 7.75 inches. Tread depth is less than the minimum allowed depth of 10 inches. In addition, the top tread is smaller than the rest by over 1 inch. Standard building practice is for treads to be of uniform depth and risers of uniform height in any stairway between two floors. There shall be no variation exceeding 3/16 inch in the depth of adjacent treads or in the height of adjacent risers and the tolerance between the largest and smallest riser or between the largest and smallest tread shall not exceed 3/8 inch in any flight. Inconsistent riser heights are considered a safety hazard since it may cause a person to stumble from the change in step heights. Handrail was missing at the upper 6 steps. Proper building practice calls for the installation of a "graspable" handrail on at least one side of every continuous flight of stairs with four or more risers. The handrail should be at least 34 inches and not more than 38 inches above the treads measured vertically from a sloped plane connecting the tread nosing or from the finished floor of a ramp. Installation by a contractor is advised. Doors & Windows: Condensation and/or fogging was visible between the glass panes of the window(s) located in the garage (all uppers), all three upper front arched over the entry, above the front door, This could mean there is damage to the window thermal seals. Additional seal failure on other windows may exist which was not visible at the time of this inspection. Further evaluation of all windows by a professional window contractor is recommended. BATH KITCHEN LAUNDRY Bathroom(s) (Observations pertain to all baths unless otherwise specified): The master bath and upstairs guest bath commode bases were loose at the floor connection and lacks sealant. Damage to the bottom connection flange may be present and should be evaluated since a damaged flange will prevent a secure connection. A loose base can sometimes cause a gap in the wax ring seal at which point it needs to be replaced. A gap can allow sewage gas to enter the home. Repair by a professional plumber is advised. Some of the wall tiles were loose located at the master bath shower, and in the upstairs guest tub surround. Loose tiles can be an indication of moisture intrusion behind them, with possible drywall/framing damage and fungal growth. The possibility of additional damage exists, the extent of which cannot be determined until the tiles are removed. At that time, a more thorough inspection can be performed and damage assessment made. Master bath right sink was damaged at the drain connection. Cracking observed which will ultimately lead to leakage. Recommend replacement of the sink. Upstairs guest bath tub was rusted at the overflow cover. The damage was partially covered with sealant which is not a proper repair. Replacement of the tub may be needed. FCBI, Inc Atlantic Blvd. #104, Jacksonville, Fl (904) (888) Page 9
11 ETERIOR The Exterior Components in this section include the building perimeter, land grade and water drainage directly adjacent to the foundation, trees and vegetation that adversely affect the structure, cladding material, trim, walks, steps, driveways, patios, and retaining walls contiguous with the structure, attached porches, decks, steps, balconies, handrails, guardrails and carports. These items were examined for proper function, excessive or unusual wear and general state of repair. Components may not be visible because of soil, vegetation, storage and/or the nature of construction. In such cases these items are considered inaccessible and are not inspected. Limitations: This exterior inspection does not include screening, shutters, awnings(and similar accessories), fences, remotely controlled components, water testing (unless agreed upon) subterranean drainage systems, geological and/or soil conditions, recreational facilities, outbuildings or detached structures (other than garages and carports) such as storage sheds and stables, seawalls, breakwalls and docks, erosion control or earth stabilization measures. In addition, we do not comment on coatings or cosmetic deficiencies and the wear and tear associated with the passage of time. Driveway: Concrete. Appears functional overall. Minor cracking/damage may be present which does not pose any structural concerns and repairs can be made at your discretion. Walkways: Concrete. Appears functional overall. Some minor cracking/ damage may be present which does not pose any structural concerns and repair can be made at your discretion. Entry / Patios / Enclosures: (Observations pertain to all patio areas unless otherwise noted) Tile. Appears functional. No evidence was visible of a standing water problem and the runoff slope appears adequate. Some minor cracking may be present which does not pose any structural concerns and repair can be made at your discretion. Observations: Flagstones patio at the rear had some settled and damaged sections. Standing water was observed along the rear wall indicating improper drainage. Repair by a qualified contractor is advised Tripping hazards were noted as a result of raised edges at the front entry tiles. This is considered a safety hazard and should be repaired. FCBI, Inc Atlantic Blvd. #104, Jacksonville, Fl (904) (888) Page 10
12 Exterior Doors: (Observations pertain to all doors unless otherwise noted) Front, side/rear, and standard door form the interior to the garage. Appears functional overall. Observations: Weather gasket had gaps along the threshold and at the middle joint at the front door. No daylight should be visible around the frame when the door is closed. Open areas can allow a loss of conditioned air increasing energy consumption and cost. Grading / Drainage: Flat site overall. Grade at foundation appears functional with proper drainage away from the foundation perimeter. Landscaping: Landscaping appeared to be maintained overall and is only inspected for conditions that adversely affect the structure. We do not evaluate landscape components, such as trees, shrubs, fountains, ponds, statuary, pottery, fire pits, patio fans, heat lamps, and decorative or lowvoltage lighting. FCBI, Inc Atlantic Blvd. #104, Jacksonville, Fl (904) (888) Page 11
13 Cladding: Stucco was installed on all sides of the home. The most common stucco types are OneCoat, TwoCoat and ThreeCoat. The two most common types of installation in this part of the Country are TwoCoat and ThreeCoat. In order to properly identify the exact type of stucco installed, it's necessary to identify some of the key installation components. However, this can be very difficult considering that these components are installed behind the finish coat and cannot be observed with a visual inspection. An effort to properly identify the stucco installed on this home has been made utilizing the visual identifiers present at the time of the inspection. Stucco on this home appears to be a TwoCoat System. These systems merge a fiber reinforced cementicous scratch and brown coats into one coat that is between 3/8 and 1/2 inch thick. A 1/8 inch thick colored finish coat is applied after the first coat has cured according to the manufacturer's instructions. Installation of TwoCoat Systems begins with a vaporpermeable waterresistant barrier (WRB). Expanded polystyrene foam (EPS) is installed over the WRB and attached to the framing. Corrosionresistant lathe is installed and the stucco is applied over the lathe. Finish coat is premixed, and textured decorative coating. Identifying factors include the finish coat, thickness, accessories and expansion joints. The stucco appeared functional overall with no visible major damage at the time of the inspection. Maintenance Tip: Because stucco is a rigid material, cracks can develop as a result of slight movement of the house and should be repaired as soon as possible. Movement occurs from foundation settlement and from wind forces. Once a crack develops, water can penetrate into the wall during a driving rain and cause problems. In time, the portion of the metal lath around the crack rusts and deteriorates, and, depending on the condition of the backing paper, the wood framing might rot. Make certain to seal any stucco cracks, no matter how small, as soon as they are detected. Observations: Upper and lower horizontal control joints on the right side of the house are heavily damaged. Both upper and lower had extensive rust damage which has swelled and allowed moisture to enter below the joints. The damage is preventing the control joints from operating as designed and should be fully replaced with proper rustresistant material. It also lends doubt as to the appropriateness of all other control joints installed on the structure. This type of repair can be extensive and expensive and should be completed by a professional stucco contractor only. Stucco wall above the garage had some cracking damage with moisture intrusion detected (moisture meter used was a Tramex Moisture Encounter Plus). Wall left of the upper window had some stress cracks with moisture intrusion detected below the cracks. Area directly above the garage had a very wide crack which has allowed moisture to leak to the header above the garage door (registered as wet along the entire header). Moisture intrusion behind the stucco can cause a myriad of damage including, but not limited to, metal lathe rusting, sheathing/framing damage, insulation damage and fungal growth. Since this is basically a nonintrusive inspection and only readily accessible areas are inspected, the extent of the damage will not become evident until a more invasive inspection is performed which should include removal of the stucco. Highly recommend further evaluation by a professional stucco contractor. FCBI, Inc Atlantic Blvd. #104, Jacksonville, Fl (904) (888) Page 12
Vision Home Inspection
Vision Home Inspection 324 Rams Run Shepherdsville KY 40165-7877 Inspector: James McFadden Property Inspection Report Client(s): Property address: Inspection date: View report summary This report is the
More informationHome Inspection Report
4949 Brownsboro Rd Suite 293 Louisville, KY 40223 (502) 414-1440 tripleainspections@gmail.com Inspected By: William Carter, HI-1956 Home Inspection Report Prepared For: Edward Cullen Property Address:
More informationInspection Report. Dream Home Inspections. www.timinspects.com. 415 Second Ave. Frisco CO 80443-1789 (970) 368-2668
Inspection Report Property Address: 123 Dream Home Way Frisco, CO 80443 Prepared for: Inspector: Tim Nixon Tim Nixon Inspection date: 3/28/2014 1 of 9 General Information Property Information Address:
More informationPROPERTY INSPECTION REPORT
(850) 297-1998 1716 Monticello Dr Tallahassee, Florida 32303 PROPERTY INSPECTION REPORT THIS INSPECTION IS A DETAILED LISTING OF AREAS VISUALLY INSPECTED AT:, Tallahassee FL Client Tallahassee, FL 32304
More informationCOMPREHENSIVE PROPERTY INSPECTIONS
COMPREHENSIVE PROPERTY INSPECTIONS Thank you for selecting CPI for your Deficiency Observation. A full home inspection was not performed on this property at the buyers request. This inspection is a limited
More informationReport for. Dick and Jane Homeowner. 1234 Lovers Lane, Houston, Texas 77000
Report for Dick and Jane Homeowner 1234 Lovers Lane, Houston, Texas 77000 March 17, 2004 I NI NP R Inspection Item I. STRUCTURAL SYSTEMS o o o A. Foundations (If all crawl space areas are not inspected,
More informationSTATE OF FLORIDA HOME INSPECTION STANDARDS OF PRACTICE:
STATE OF FLORIDA HOME INSPECTION STANDARDS OF PRACTICE: 61-30.801 Standards of Practice, General. (1) Home inspections performed to these Standards of Practice are intended to provide the client with information
More informationInspecton Report. Property Address:
Inspecton Report Provided by: National Home Inspections Inspector: Bob Smith 456 S Main Denver, CO 46312 (645) 423-3242 bob@nationalhomeinspections.com www.nationalhomeservices.com Property Address: 873
More informationwww.citiesinspection.com October 5, 2015 Dear Client,
www.citiesinspection.com October 5, 2015 Dear Client, On 9/14/2015, Cities Inspection Service, Inc. completed a building inspection of the property located at 123 Oak Street, Someplace, Minnesota for you.
More informationINSPECTION PROPERTY ADDRESS: Fort Bend County, Texas
5006 Cherry Ridge Road Richmond, Texas 77406 281-342-9944 harris31@sbcglobal.net INSPECTION PROPERTY ADDRESS: INSPECTION PERFORMED FOR: XXXX Drive Fort Bend County, Texas Mr. and Mrs. New Construction
More informationSelf-Home Inspection Checklist
To be used as a first home visit for note taking. Visit www.homeinspectiondirect.com for more tips and information about buying a home and hiring a home inspector. This form in no way replaces a professional
More informationCLIENT. Inspection Report. 271 Front St. Alert Bay, B.C. Island Building Inspections V ANCOUVER I SLAND B. C.
CLIENT Inspection Report 271 Front St. Alert Bay, B.C. Island Building Inspections 2013 V ANCOUVER I SLAND B. C. Elevation Photos For the Property at 271 Front Street Alert Bay, BC ELEVATION PICTURES Front
More informationInspecting to a higher standard.
Inspecting to a higher standard. Rob Hopkin Silver Spring, MD 20902 Monday, June 2, 2014 ProTec Inspection Services Inc. 19736 Selby Ave Poolesville, MD 20837 301-972-8531 www.protec-inspections.com rob@protec-inspections.com
More informationHome Inspection Report
Report# 21009 Page 1 of 24 Home Inspection Report Property Address: 123 Maple Lane, St. Augustine, FL 32092 Prepared For: Mr. Smith Prepared By: EDGE Inspections www.edgeinspections.com PO Box 601055 Jacksonville,
More information2. What building projects are exempted? (permit not required)
BUILDING AND SAFETY DEPARTMENT 1. What building projects require a permit? Following is a list of projects that require building permits based on Appendix chapter 1 of the California Building Code and
More informationA.C.E. Home Inspection Service www.acehomeweb.com St. Peters, MO 63376 (636) 978-9111
A.C.E. Home Inspection Service www.acehomeweb.com St. Peters, MO 63376 (636) 978-9111 Inspector Name: Tim Knight, ASHI Member 202490 Inspection No: 12121212 Inspection Date: 1/1/2012 Client: Address: John
More informationInspection Item COMMENTS
APPENDIX 9 AFFORDABLE HOUSING PROGRAM INSPECTION CHECKLIST Participating Jurisdiction: Homeowner Name: Assisted Property Address: Date of Physical Inspection of Property: Total Square Footage of Property:
More informationI NI NP R Inspected Items
6/ /07 The Inspection of the property listed above must be performed in compliance with the rules of TREC. The inspection is of conditions which are present and visible at the time of the inspection, and
More informationPropery Inspection Report
Propery Inspection Report Cover Page,, Ok Inspection prepared for: Date of Inspection: 9/28/2014 Time: 8:30 AM Age of Home: 2011 MOL Weather: Clear 62 degrees Inspector: License #130 5400 Hwy 177, Marland,
More informationSouth Carolina Home Inspector Standards of Practice
South Carolina Home Inspector Standards of Practice The following Standards provide guidelines for the Residential Home Inspector and outline what the Residential Home Inspector should observe, identify,
More informationVari Inspection Services
Cover Page Vari Inspection Services Property Inspection Report Inspection prepared for: Sample Real Estate Agent: None - Date of Inspection: 5/13/2015 Inspector: Tony Vari License # HI8047 23110 STRD 54
More informationGeorgia Home Inspection Services
Cover Page Property Inspection Report My street, Anytown GA, 30000 Inspection prepared for: John Doe Inspection Date: 7/18/2011 Time: 5pm Age: 25+ Size: >1500 Weather: Clear This ranch style home is in
More informationInspection Report Atlanta Strip Mall Commercial Building Property Address:
Page 1 of 25 Inspection Report Atlanta Strip Mall Property Address: Smyrna GA 30082 Page 2 of 25 South East Building Consultants Ray Thoroman Serving the entire State of Georgia 6 678-410-3005 Page 3 of
More informationPre-Drywall Inspection Report
SM MEDALLION INSPECTIONS helping people make informed decisions Pre-Drywall Inspection Report 5657 Garden Valley Place Milton, Georgia 30024 Prepared for Betsy and Paul Dougherty January12, 2015 Medallion
More informationA TO Z HOME INSPECTIONS PROFESSIONAL HOME INSPECTION SERVICES FOR HOME BUYERS AND SELLERS
A TO Z HOME INSPECTIONS PROFESSIONAL HOME INSPECTION SERVICES FOR HOME BUYERS AND SELLERS Insurance Inspection Report 1234 Main Street Tallahassee, Florida Report Prepared For: Charles Smith Report Prepared
More informationHOME INSPECTION CHECKLIST
CLOSING.COM LEARNING CENTER HOME INSPECTION CHECKLIST CONTENTS Attic 1 Balconies 1 Basement 1 Bathroom 2 Ceiling, Floors and Walls 2 Crawlspace 3 Decks and Porches 3 Doors and Windows 4 Drainage 4 Driveways
More informationSAMPLE INSPECTION REPORT PREPARED FOR: John Q Public
925 W. Baseline Road Suite 105-Y1 Tempe AZ 85283 Tel: 480-456-8809 Fax: 480-456-6139 Mobile: 602-790-0976 www.accuproinspect.com AccuPro@AccuProINSPECT.com SAMPLE INSPECTION REPORT PREPARED FOR: John Q
More informationHome Inspection Report
Home Inspection Report Report Number: 144 For The Property Located On: 123 Any Street 27587 Prepared For Exclusive Use By: Mr. Sample N/A,,, Report Prepared By: Edward Carapezza; License No.: 3447 Inspector
More informationInspection Tech. (330) 310-6559 http://www.inspectiontech.us a_westerburg@inspectiontech.us Inspected By: Aaron Westerburg
Inspection Tech (330) 310-6559 http://www.inspectiontech.us a_westerburg@inspectiontech.us Inspected By: Aaron Westerburg Inspection Tech Home Inspection Report Prepared For: Mr. & Mrs. Homebuyer Property
More informationTotal Home Inspection Checklist
Total Home Inspection Checklist Use a checklist like this to make sure that you are looking at all parts of the house. Check off those items that are in good condition and make notes about those that are
More informationHomeSpec REPORT SUMMARY
HomeSpec 04/25/2007 Ms. Rachel Trujeque Re: 13038 West Plum Road Lot #1225 - Peoria, AZ. 85383 - Pre Drywall Inspection Dear Ms. Trujeque, At your request, a visual pre drywall inspection of the above
More information159 Morningside Avenue, Toronto
159 Morningside Avenue, Toronto Inspection Report February 6, 2013 159 Morningside Avenue, Toronto Inspection Report Overall Condition: This 60±-year-old home was extensively renovated and extended in
More informationBUILDING PERMIT SPECIFICATIONS
BUILDING PERMIT SPECIFICATIONS The below noted requirements are based upon La Plata County Building Code. These specifications are not intended as a complete set of requirements, but are intended to provide
More informationHEDDERMAN ENGINEERING, INC. www.heddermanengineering.com Office 281-355-9911, Fax 281-355-9903 office@heddermanengineering.com
HEDDERMAN ENGINEERING, INC. www.heddermanengineering.com Office 281-355-9911, Fax 281-355-9903 office@heddermanengineering.com, 2011 TO: Mr. REF: CONDITION OF PROPERTY SURVEY Dear Mr. : At your request,
More informationHOME INSPECTION REPORT
Edgewood Home Inspections, Inc. 407 W. Smith Valley Rd. #1032 Greenwood, IN 46142 (317) 833-6048 HOME INSPECTION REPORT Indianapolis IN 46000 Inspector's Name: License Number: Scott Kissel HI00800073 TABLE
More informationStructure Survey Findings:
Structure Survey Findings: Visible portions of the following were observed: foundations; structure to walls, columns, floors, roofs, overhang posts, and columns; attached or firmly abutting decks, balconies,
More informationCHRIS CURLES and ASSOCIATES INSPECTION SERVICES
CHRIS CURLES and ASSOCIATES INSPECTION SERVICES Inc. Chris Curles, President www.homeinspectionsatlanta.com chriscurl@comcast.net Office: 770-493-0227 Professional Member Of: GAHI # 93006 ASHI # 211725
More informationBuilding Condition Assessment Report
Building Condition Assessment Report Asset C3c - Oak Terrace Cottage 121 Address Riverview Lands, 2601 Lougheed Highway, Coquitlam, BC. V5C 4J2 Construction Year Size (Gross Floor Area) 1920. 2,553 Sq.Ft.
More informationThe City of Basehor, Kansas
The City of Basehor, Kansas Residential and Miscellaneous Permits This list provides general information regarding permit requirements for various residential construction and maintenance activities. The
More informationBOROUGH OF NATIONAL PARK APPLICATION FOR A CERTIFICATE OF OCCUPANCY FOR CHANGE OF OCCUPANCY ADDRESS OF PROPERTY FOR INSPECTION CURRENT OWNER
BOROUGH OF NATIONAL PARK APPLICATION FOR A CERTIFICATE OF OCCUPANCY FOR CHANGE OF OCCUPANCY ADDRESS OF PROPERTY FOR INSPECTION # BLOCK LOT VACANT YES NO CURRENT OWNER NAME ADDRESS TELEPHONE # PROSPECTIVE
More informationPROPERTY INSPECTION OR ASSESSMENT OF DAMAGES
PROPERTY INSPECTION OR ASSESSMENT OF DAMAGES ADDRESS: Somewhere, FL CLIENT: GAIA GC ID No: 2015000 DATE: 12/31/2015 INSPECTION OR ASSESSMENT BY: GAIA CONSTRUCTION INC. CGC 1516136 FLORIDA HI-2792 FLORIDA
More informationPROPERTY INSPECTION OR ASSESSMENT OF DAMAGES
PROPERTY INSPECTION OR ASSESSMENT OF DAMAGES ADDRESS: 123 MAIN ST MIAMI, FL CLIENT: BUYER ID No: 2014193 DATE: 5/13/2014 INSPECTION OR ASSESSMENT BY: GAIA CONSTRUCTION INC. CGC 1516136 FLORIDA HI-2792
More informationPROPERTY INSPECTION REPORT Property Address:
Scott Certified Member P. O. Box 9007 Indianapolis, IN 690-007 (7)-750-60 Fax: 7-876-8 PROPERTY INSPECTION REPORT Property Address: Prepared for: Inspection Inspector: Lou Buehler Inspection #: BUYERS
More informationELIGIBLE REPAIR PROJECT PARAMETERS
THE DISTRICT MUNICIPALITY OF MUSKOKA ONTARIO RENOVATES PROGRAM FOR HOMEOWNERS ELIGIBLE REPAIR PROJECT PARAMETERS 1. To have your project considered and payment processed, all projects requiring a Building
More informationLicense Requirements for Persons Engaging in the Business of Inspection Practice:
SC Standards of Practice SOUTH CAROLINA RESIDENTIAL BUILDERS COMMISSION HOME INSPECTOR STANDARDS OF PRACTICE Adopted by the Residential Builders Commission May 13, 1998 PURPOSE: The purpose of a residential
More informationCrawford Inspection Services C.C.B. # 76914 www.crawfordinspections.com
Crawford Inspection Services C.C.B. # 76914 www.crawfordinspections.com Portland Area PO Box 665 West Linn, OR 97068 Ph: (503) 650-6957 Salem Area 5434 River Rd. N; #192 Keizer, OR 97303 Ph: (503) 362-5809
More informationHEDDERMAN ENGINEERING, INC. 3011 Carrie Cove Ct., Spring, TX 77386 281-355-9911, fax 281-355-9903 Tim@heddermanengineering.com
HEDDERMAN ENGINEERING, INC. 3011 Carrie Cove Ct., Spring, TX 77386 281-355-9911, fax 281-355-9903 Tim@heddermanengineering.com 2007 TO: Mr. REF: CONDITION OF PROPERTY SURVEY Dear Mr. : At your request,
More informationInspection Report. Jacksonville Krystals Inspection. Property Address: Downtown. Jacksonville FL 32204. South East Building Consultants
Page 1 of 53 Inspection Report Jacksonville Property Address: Jacksonville FL 32204 South East Building Consultants Ray Thoroman Inspecting Jacksonville FL and entire South East Page 2 of 53 Table of Contents
More informationOrlando Home Inspection Services
PLEASE NOTE: Orlando Home Inspection Services Serving Central Florida since 1999 P O Box 915451, Longwood, Florida, 32791-5451 Phone: (321) 228-2493 Fax: (407) 374-8505 Web: http://www.orlando-home-inspections.com
More informationBUILDING DEPARTMENT 8748 W. 82 nd Place - Justice, IL 60458 Phone: (708) 458-2130 Fax: (708) 458-3207
BUILDING DEPARTMENT 8748 W. 82 nd Place - Justice, IL 60458 Phone: (708) 458-2130 Fax: (708) 458-3207 SELF EVALUATION CHECKLIST FOR RESIDENTIAL AND MULTI-FAMILY DWELLING INSPECTIONS The attached checklist
More informationInspection Report. Mr. Sample Sample. Property Address: 1234 USA Drive Indianapolis IN 12345. 1234 USA Drive. Morris Home Inspection Group, LLC
Inspection Report Mr. Sample Sample Property Address: 1234 USA Drive Indianapolis IN 12345 1234 USA Drive Morris Home Inspection Group, LLC Cedric Morris HI01200039 Fishers, IN 46037 317-550-6281 Table
More informationThe Uniform Building Inspection Report Condensed
The Uniform Building Inspection Report Condensed Single Family Residence:, Scottsdale, AZ Condensed Report Version Prepared for: John Doe Inspection Date: 9/19/2005, 1:00:00 AM Report Number: 091805s Inspection
More informationBurns Home Services SUMMARY REPORT. 7/18/2006 Start: 9:00 am End: 12:30 pm
Burns Home Services Service Makes the Difference 2620 W Grovers Ave, Phoenix, AZ 85053 Tel: 602-889-6970 Fax: 602-870-4563 Mobile: 602-291-7138 Garryh@burnshomeservices.com SUMMARY REPORT Client: John
More informationLIMITED ONE-YEAR WARRANTY SELLER S RESPONSIBILITY
LIMITED ONE-YEAR WARRANTY SELLER S RESPONSIBILITY Except as covered by a manufacturers limited warranty, the Seller hereby provides a Limited Warranty for the dwelling against defects in the original material
More informationInspection Report. provided by: Delaware Property Inspection. Inspector: Richard Hiddemen (302)355-1748
Inspection Report provided by: Delaware Property Inspection Inspector: Richard Hiddemen (302)355-1748 ASHI # 243377 DPR #H4-0000018 DDA #06-444 Delaware 1992105842 Wilmington #03857 New Castle #2010-845
More informationExterior Elevated Elements Inspection Guidelines
Exterior Elevated Elements Inspection Guidelines Planning and Development 1. Guideline Purpose These guidelines are intended to assist practicing professionals in complying with Berkeley Municipal Code
More informationINSPECTION REPORT. LOCATION OF PROPERTY 1234 Sample Street Tucson, AZ 85701. CLIENT Mr. & Mrs. John Q. Sample c/o Agent DATE OF INSPECTION 1/30/2008
INSPECTION REPORT LOCATION OF PROPERTY 1234 Sample Street CLIENT Mr. & Mrs. John Q. Sample c/o Agent DATE OF INSPECTION 1/30/2008 INSPECTOR Dave Woityra FILE CODE: 0100114.SAM AGENT Sample Q. Jones A.B.C.
More informationProperty Inspection Report
Property Inspection Report 1234 Bear St., Denver, CO 80223 Prepared For: John Smith Inspection Date: 12/11/2015 Prepared By: Bill Heine, Certified Professional Inspector ResInspect, LLC 303-359-7573 Email:
More informationHome. Safe. Home. home inspection report
home inspection report Home. Safe. Home. Each office is independently owned and operated. 2013 The HomeTeam Inspection Service, Inc. All rights reserved. What is a home inspection? The purpose of a home
More informationBuilding Inspection Report
Building Inspection Report 14100 W. Cleveland Avenue, Phoenix, AZ 55555 Inspection Date: 03/18/2002 Prepared For: Mark Newcomer Prepared By: ABC Home Inspections 212 Wisconsin Avenue Scottsdale, AZ 55555
More informationDoes Wall Township require an inspection by the building department on resale of a home?
Selling your home Does Wall Township require an inspection by the building department on resale of a home? No. We do not require a Certificate of Continued Occupancy on the resale of home. A Smoke Detector,
More informationGROWTH MANAGEMENT DEPARTMENT 201 SE 3 rd ST, (Second Floor), Ocala, FL 34471 (352) 629-8421; FAX: (352) 629-8264
BUILDING CODE GUIDELINES FOR ELECTRICAL INSPECTIONS Building Code compliance is the obligation of design professionals and/or contractors. Plan Review and Inspection Guidelines are intended to be used
More informationWhen is a Permit Required? What Types of Permits are Required? The most common types of projects that require permits are:
When is a Permit Required? The most common types of projects that require permits are: -New Houses or buildings -Room Additions or Expansions -Structural repairs, remodeling and alterations -Accessory
More informationPROPERTY INSPECTION REPORT
Whisper Computer Solutions, Inc. P.O. Box 690502 San Antonio, TX 78269-0502 Phone: (210)681-6325 Fax: (210)681-6325 Email: support@whispersolutions.com PROPERTY INSPECTION REPORT Prepared For: Concerning:,
More informationCITY OF WHITE BEAR LAKE BUILDING INSPECTION DEPARTMENT 4701 Highway 61 White Bear Lake, MN 55110 Fax: 651-429-8503. Re-Roofing: Asphalt Shingles
CITY OF WHITE BEAR LAKE BUILDING INSPECTION DEPARTMENT 4701 Highway 61 White Bear Lake, MN 55110 Fax: 651-429-8503 Re-Roofing: Asphalt Shingles This is a summary of the standard requirements based on the
More informationSAMPLE INSPECTION REPORT
SAMPLE INSPECTION REPORT Inspection Report # 070707 ~ TURNER Client: Mr. Jim Turner Property Address: 305 N. Second Ave. ~ Upland, CA. 91786 Property Description: Single Story ~ Detached Single Family
More informationInspection Report. Prepared For: Sampath Sample. Property Address: 12712 Waterside Drive. Alpharetta, GA 30004. Atlanta Home Inspections
Page 1 of 37 Inspection Report Prepared For: Sampath Sample Property Address: Alpharetta, GA 30004 Atlanta Home Inspections Matthew A Thoroman 6625 Hwy. 53 E. Ste. 410-151 Dawsonville Ga 30534 (678)-410-8062
More informationHome Inspection Report
Home Inspection Report 555 Wind Way, Fake City, OR 54645 Inspection Date: Monday May 12, 2014 Prepared For: John Doe Prepared By: House to Home 3468 N. Bartlett Ave Milwaukee, WI 53211 262-754-5973 christopher@ahit.com
More informationAccurate Home Inspection of Illinois. Property Inspection Report For Steve & Jenny Hynek 210 W.Chicago Ave., Westmont, Illinois
Accurate Home Inspection of Illinois 815-260-1727 1213 Norley st. Joliet, illinois 60435 aaccurate1@yahoo.com We Inspect to Protect!!! Property Inspection Report For Steve & Jenny Hynek 210 W.Chicago Ave.,
More informationHow To Make A House Safe
1 RESIDENTIAL Screen Enclosures Orange County Residential Code Compliance Alternative design method for screen enclosures R301.2.1.1.3 PLAN REVIEW Engineered plans must state that the Alternative Design
More informationINVOICE. DATE: May 11, 2005. DESCRIPTION Inspection and report on a property located at OF SERVICES: Perfect Street, Sarasota, Fl.
INVOICE DATE: May 11, 2005 CLIENT: The Buyer DESCRIPTION Inspection and report on a property located at OF SERVICES: Perfect Street, Sarasota, Fl. TOTAL FEE: $ See Schedule Tom Villani Hallmark Inspection
More informationInspection Report. Prepared For: Atlanta Commercial Customer. Property Address: xxx Sandy Plains Road. Building 5 Marietta, GA 30066
Page 1 of 58 Inspection Report Prepared For: Atlanta Commercial Customer Property Address: Building 5 Marietta, GA 30066 Superior Home Inspections Ray Thoroman 8070 Ivy Shaw Dr. Gainesville,GA 30506 678-410-3005
More informationSouth Carolina Home Inspector Standards of Practice
South Carolina Home Inspector Standards of Practice The following Standards provide guidelines for the Residential Home Inspector and outline what the Residential Home Inspector should observe, identify,
More informationEstimating Database Checklist
Estimating Database Checklist If you are creating a new estimating database for projects, the following list offers a thorough listing of Main and Sub Categories. You can also use it as a checklist to
More informationGeorgiaHomePros.com. 6858 Yellow Creek Road Ball Ground, GA 30107 770-893-2271 www.georgiahomepros.com inspections@tds.net Inspected By: Scott Webb
GeorgiaHomePros.com 6858 Yellow Creek Road Ball Ground, GA 30107 770-893-2271 www.georgiahomepros.com inspections@tds.net Inspected By: Scott Webb Home Inspection Report Prepared For: Jack & Diane Samples
More informationInspection Report. Mr. Happy 2 flat owner. Property Address: Focal Point Home Inspection Ltd.
Page 1 of 35 Inspection Report Mr. Happy Property Address: Joseph Poelsterl 450.010220 6334 W. Grace st Chicago Illinois 60634 1-773-454-6700 Page 2 of 35 Table of Contents Cover Page Table of Contents
More informationTerry Jenkins, Owner Member, American Society of Home Inspectors Virginia Certified Home Inspector Certificate # 3380 000373, expires 1/2010
Terry Jenkins, Owner Member, American Society of Home Inspectors Virginia Certified Home Inspector Certificate # 3380 000373, expires 1/2010 Tel: (804) 378-0861 terry@prospectpropertiesva.com Inspection
More informationHome Inspection Report
Home Inspection Report Cincinnati, Ohio 45000 Prepared for: Dean Murphy Prepared by: BEDROCK ENTERPRISES, INC. 4060 Simca Lane Cincinnati, OH 45211 20:13 July 07, 2008 Page 1 of 18 Definitions NOTE: All
More informationEAST STROUDSBURG BOROUGH RESIDENTIAL RENTAL INSPECTION CHECK LIST
DATE TIME EAST STROUDSBURG BOROUGH RESIDENTIAL RENTAL INSPECTION CHECK LIST INSPECTOR: LICENSE # ADDRESS: PROPERTY OWNER: SINGLE: DOUBLE: MULTI-UNIT # OF UNITS POINT OF INSPECTION Sanitation IPMC 302.1
More informationInspection Report. Mr. John Doe. Property Address: 123 Somewhere Jacksonville FL 32224. Tabor Hill & Associates LLC
Inspection Report Mr. John Property Address: 123 Somewhere Jacksonville FL 32224 Tabor Hill & Associates LLC James Cox HI4634 P.O. Box 65699 Orange Park FL 32065 Table of Contents Cover Page...1 Table
More informationCode Enforcement Inspection Manual. City of Virginia Beach Department of Housing and Neighborhood Preservation Code Enforcement Division
Code Enforcement Inspection Manual City of Virginia Beach Department of Housing and Neighborhood Preservation Code Enforcement Division LIVING ROOM 304.15 EXTERIOR DOOR(S) Check door(s) and trim for condition,
More informationPEPPER VINER HOMES WARRANTY GUIDELINES
PEPPER VINER HOMES WARRANTY GUIDELINES All non-emergency warranty and customer service requests MUST be made in writing. This provides you with documentation and allows Pepper Viner to operate efficiently.
More informationWHEN IS A PERMIT REQUIRED?
WHEN IS A PERMIT REQUIRED? Any owner, builder, contractor, or other authorized agent who intends to construct, enlarge, alter, repair, move, demolish, or change the occupancy of a building or structure,
More informationProperty Condition Assessment
Property Condition Assessment Business, Wisconsin Inspection Date: 8/2009 Prepared For: Business Owner Report Number: TD999909 Prepared By: Shamrock Building Inspection Consultants LLC N29 W29951 Shel-Mar
More informationHow To Get A Building Permit In Florida
MIAMI-DADE COUNTY BUILDING DEPARTMENT PERMIT EXEMPTIONS Please note that the exemptions listed in this section are from Florida Building Code requirements only. Other State and County regulatory departments
More informationMark Cramer Inspection Services, Inc.
Mark Cramer Inspection Services, Inc. 492 Twentieth Avenue, Indian Rocks Beach, FL 34635-2970 (727) 595-4211 Fax (727) 596-7583 Certified Member #12085 American Society of Home Inspectors Construction
More informationBuilding Permits: When are they required?
Building Permits: When are they required? Generally, you need to obtain a building permit from the City whenever you construct, enlarge, alter, repair, move, remove, improve, convert, or demolish a building
More informationBuilding Condition Assessment Report
C2 - Nurses Resident (aka Administration) Building Condition Assessment Report Asset Address Address Construction Year Size (Gross Floor Area) Asset Type Floors Above Ground Inspection Date C2 - Nurses
More informationINSPECTION REPORT. Client Name Address From the inspection on: August XX, 2011 805-256-5519 CHRIS LOWE
08XX11aa 805-256-5519 CHRIS LOWE President, Inspector INSPECTION REPORT Client Name Address From the inspection on: August XX, 2011 This report is solely for the use of client personnel. No part of it
More informationFoundation Evaluation Report for PROPERTY ADDRESS Houston, Texas 77089. August 30, 2012. Prepared for:
A Full Service Real Estate Inspection & Engineering Firm for Houston, Texas 77089 August 30, 2012 Prepared for: CLIENT S NAME MAILING ADDRESS Houston, Texas 77089 Prepared by: Charles J. Jenkins, P.E.
More informationHOME INSPECTOR STANDARDS OF PRACTICE
HOME INSPECTOR STANDARDS OF PRACTICE Adopted by the Residential Builders Commission May 13, 1998, South Carolina Home Inspector Standards of Practice The following Standards provide guidelines for the
More informationRoof Inspection. Summary Report
www.real-estate-inspections.com Roof Inspection Summary Report Subject Property Prepared for: File Number: Client in Detroit 05-15-RF-004 Inspector: Craig Milliken, PE # 32779 CPM Real Estate Inspections,
More informationASHI STANDARD OF PROFESSIONAL PRACTICE FOR HOME INSPECTIONS
ASHI STANDARD OF PROFESSIONAL PRACTICE FOR HOME INSPECTIONS 1. INTRODUCTION 1.1 This ASHI Standard of Professional Practice for Home Inspections (Standard) defines the scope of home inspections performed
More informationAsphalt Shingle Application Requirements
Alberta Allied Roofing Association Asphalt Shingle Application Requirements Section 1 Roof Decks 1.1 General Asphalt Shingles are not permitted to be installed directly over rigid insulation. When Asphalt
More informationReport Index PROPERTY DESCRIPTION 1 ELECTRICAL SYSTEM 2 COMMON INTERIOR AREAS 3 INTERIOR ROOMS 6 KITCHEN 8 BATHROOMS 10
Report Index PROPERTY DESCRIPTION 1 ELECTRICAL SYSTEM 2 COMMON INTERIOR AREAS 3 INTERIOR ROOMS 6 KITCHEN 8 BATHROOMS 10 PROPERTY DESCRIPTION PROPERTY INSPECTED: INSPECTION ADDRESS: 4722 Baltimore Avenue
More informationSTATE OF SOUTH CAROLINA RESIDENTIAL PROPERTY CONDITION DISCLOSURE STATEMENT
STATE OF SOUTH CAROLINA RESIDENTIAL PROPERTY CONDITION DISCLOSURE STATEMENT The South Carolina Code of Laws (Title 27, Chapter 50, Article 1) requires that an owner of residential real property (single
More informationAztec Property Inspections 2719 Mission Blvd San Diego, CA 92109 (858) 245-9329. 6352 Some Road San Diego, CA 92114
2719 Mission Blvd San Diego, CA 92109 (858) 245-9329 Client: Could Be You 6352 Some Road San Diego, CA 92114 Page 1 of 14 Defective Summary This summary is not the entire report. The complete report may
More informationPRE-PURCHASE INSPECTION REPORT
PRE-PURCHASE INSPECTION REPORT PREPARED FOR: PROPERTY ADDRESS: Waiheke Island DATE: 21 November 2012 Page 1 of 13 (a) This is a report of a visual only, non-invasive inspection of the areas of the building
More information2012 Ontario Building Code Requirements for New Construction. Bradford West Gwillimbury Building Division March 5, 2012
2012 Ontario Building Code Requirements for New Construction Bradford West Gwillimbury Building Division March 5, 2012 1 Ontario Building Code changes Applicable to permits applied for after December 31,
More informationExterior Condition Report
Scope of Work for Property Located at: 3918-20 West Cherry Street Date: 3/10/2014 Property is: Single Family Duplex Below is the minimum requirement to meet health and safety issues. The City of Milwaukee,
More information