DC INVERTER SPLIT SYSTEM AIR CONDITIONER

Size: px
Start display at page:

Download "DC INVERTER SPLIT SYSTEM AIR CONDITIONER"

Transcription

1 AIR CONDITIONER TECHNICAL & SERVICE MANUAL CS-KS30NKU + CU-KS30NKUA CS-KS36NKU + CU-KS36NKUA DC INVERTER SPLIT SYSTEM AIR CONDITIONER Indoor Model No. CS-KS30NKU CS-KS36NKU Product Code No Outdoor Model No. CU-KS30NKUA CU-KS36NKUA Product Code No Indoor Unit Outdoor Unit CS-KS30NKU CS-KS36NKU CU-KS30NKUA CU-KS36NKUA IMPORTANT These air conditioners employ new refrigerant R40A. Pay special attention when servicing the unit. REFERENCE NO. SM700875

2 SAFETY PRECAUTIONS Before doing repair work, please read the " SAFETY PRECAUTIONS" carefully and fully understand them. The precautionary items here are divided into " Warning" and " Caution" items. Items in particular which may cause death or serious injury to the service personnel if the work is not performed correctly, are included in the " Warning" table. However, even precautionary items identified as " Caution" also have the potential for serious consequences if not performed correctly. Important safety precautions are described for all items in both categories. Be sure to carefully follow all of them. Symbol Indication : This symbol indicates items to which we need to pay attention. In this triangle, a definite precautionary item is described. : This symbol indicates the item to be prohibited. In or close to this circle, a prohibited item is described. : This symbol indicates the items requiring special attention or instruction. In or close to this circle, a prohibited item is described. After doing repair work, perform a test run to confirm that there are no abnormalities. At the same time, explain the precautions in use to the user. Warning Before performing an overhaul, disconnect the power plug or power cable from the unit. Performing the work with the power supplied to the unit, may cause an electric shock. When repair work or circuit inspection that requires power supply for the air conditioner, is to be performed, do not touch the charging section. Doing so may cause an electric shock. Prohibit For the step-up capacitor attached to the electric section, perform the repair work after sufficiently discharging it. Insufficient capacitor discharge may cause an electric shock. Do not perform repair work on the electric sections with wet hands. Doing so may cause an electric shock. Do not start or stop the air conditioner by means of connecting or disconnecting the power plug. Doing so may cause an electric shock or fire. When conducting repair work only use components included in the parts list for the corresponding unit and perform the work with the appropriate tools. Incorrect or poor repair work may cause an electric shock or fire. Never modify the unit. Doing so may cause an electric shock or fire. Perform all electric work according to local applicable regulations related to electrical equipment or interior wiring regulation and make sure to use the exclusive circuit. Insufficient capacity to the electric circuit or defective arrangement results may cause an electric shock or fire. Prohibit Prohibit Prohibit Make sure to replace any power cable or lead wire showing any signs of scratch or deterioration. Failure to do so may cause an electric shock, overheating or fire. Make sure that there is no dust on or slack in the power plug and insert fully into the socket. Dust or incomplete connections may cause an electric shock or fire. Do not damage or process the power cord, as it may cause an electric shock or fire. Prohibit For the wiring between the indoor unit and outdoor unit, securely fix the specified cable onto the terminal plate. Poorly fixed wiring may cause a heat or fire. After connecting the wiring between the indoor unit and outdoor unit, attach the terminal cover securely. Incomplete attachment of the terminal cover may cause overheating or fire. 2

3 Warning If refrigerant gas blows off during the work, do not touch the refrigerant gas as it may cause frostbite. Prohibit If refrigerant gas leaks during the work, ventilate the room. If refrigerant gas catches fire, harmful gas may be generated. Do not mix any gas other than the specified refrigerant gas in the refrigerating cycle. If air or other contaminants mix with the gas, pressure will become extremely high in the refrigerating cycle, which may cause a unit breakdown." When the welded section of the compressor intake or discharge pipe is to be disconnected, perform it in a well-ventilated place after sufficiently recovering the refrigerant gas. Any residue gas may jet out refrigerant or refrigerating machine oil, which may cause an injury. Prohibit When the work is to be performed in a high place (About 2 meters or more), make sure to wear a safety helmet, gloves and safety belt. Insufficient safety gear may cause a serious injury in case of a fall. When the unit is to be relocated, confirm that the new installation location has sufficient strength for the weight of the unit. Insufficient strength of the installation location and incomplete installation work may cause an injury due to the unit falling. When the remote controller batteries are replaced, dispose of the old batteries out of the reach of children. If a child swallows a battery, make sure that the child gets immediate medical attention. Caution Do not wash the air conditioner with water, as this may cause an electric shock or fire. Prohibit For the repair work in places with high humidity or moisture, make sure to ground the unit. Failure to do so may cause an electric shock. Confirm that the component attachment position, wiring condition, soldering condition and connector connection are normal. If not, it may cause overheating or fire. Confirm that the temperature around the compressor is not too high, and then perform the repair work. Failure to do so may cause a burn. Perform welding work in a place with good ventilation. If the work is performed in a poorly ventilated area, it might cause a lack of oxygen. If the installation plate or attachment frame has deteriorated due to corrosion, etc., replace it. Failure to do so may cause an injury due to the unit falling. When the cleaning is to be performed, make sure to turn off the power and pull out the plug. Touching the fan that is rotating at high speed may result in an injury. When the indoor unit is to be removed, do not place it on an incline. Doing so may cause wet furniture because water left inside may trickle down. Prohibit Do not hold the sharp end of the unit or the aluminum fins, as it may cause an injury to your hand or finger. Prohibit After repairs, make sure to measure the insulation resistance and confirm that the value is Mohm or more. Any insulation error may cause an electric shock. After repairs, make sure to check the drainage of the indoor unit. Inappropriate drainage may cause wet furniture and floors due to water leakage. 3

4 Table of Contents SAFETY PRECAUTIONS... Page 2 TABLE OF CONTENTS. OPERATING RANGE SPECIFICATIONS 2-. Unit Specifications Major Component Specifications Other Component Specifications DIMENSIONAL DATA REFRIGERANT FLOW DIAGRAM 4-. Refrigerant Flow Diagram PERFORMANCE DATA 5-. Temperature Charts Cooling Capacity Cooling Capacity (Low Ambient) Air Throw Distance Charts ELECTRICAL DATA 6-. Electrical Characteristics 6-2. Electric Wiring Diagrams 7. FUNCTIONS 7-. Operation Functions 7-2. Protective Functions TROUBLESHOOTING (BEFORE CALLING FOR SERVICE) 8-. Precautions before Performing Inspection or Repair Method of Self-Diagnostics Checking the Indoor and Outdoor Units Trouble Diagnosis of Fan Motor Noise Malfunction and Electromagnetic Interference

5 Page 9. CHECKING ELECTRICAL COMPONENTS 9-. Measurement of Insulation Resistance Checking Continuity of Fuse on PCB Ass'y REFRIGERANT R40A: SPECIAL PRECAUTIONS WHEN SERVICING UNIT 0-. Characteristics of New Refrigerant R40A Checklist before Servicing Tools Specifically for R40A Tubing Installation Procedures In Case of Compressor Malfunction In Case Refrigerant is Leaking Charging Additional Refrigerant Retro-Fitting Existing Systems APPENDIX A Operating Instructions... A- APPENDIX B INSTALLAION INSTRUCTIONS... A-2 5

6 . OPERATING RANGE Cooling Temperature Indoor Air Intake Temp. Outdoor Air Intake Temp. Maximum 95 F DB / 7 F WB 5 F DB Minimum 67 F DB / 57 F WB 0 F DB 6

7 2. SPECIFICATIONS 2-. Unit Specifications Indoor Unit Outdoor Unit Performance Electrical Rating Features Dimensions & Weight Voltage Rating CS-KS30NKU CU-KS30NKUA Total Capacity BTU/h kw 30, ( 0,900 to 30,600 ) ( 3.2 to 9.0 ) Sensible Capacity BTU/h 8,600 Latent Capacity BTU/h 2,000 Air Circulation (Hi/Me/Lo) ft 3 /min (m 3 /h) 630 (,070) / 530 (90) /42 (700) Moisture Removal (High) Pints/h 9.57 Available Voltage Range V 87 to 253 Running Amperes Power Input A W 6.5 3,290 ( 5.0 to 6.5 ) (,000 to 3,290 ) Power Factor % 87 EER BTU/h/W 9.30 SEER BTU/Wh 6.0 Compressor Locked Rotor Amperes A 3.0 Fuse or Circuit Breaker Capacity A 35 Controls / Temperature Control Microprocessor / I.C. Thermister Control Unit Wireless Remote Control Unit Timer 24-Hour ON or OFF Timer, -Hour OFF Timer Fan Speeds Indoor / Outdoor Auto and 3 steps / Auto (Hi, Me, Lo) Airflow Direction (Indoor) Horizontal Manual Air Filter Compressor Vertical Auto Washable, Anti-Mold DC Twin Rotary (Inverter) Refrigerant / Amount charged at shipment Ibs (g) R40A / 6.5 (2,950) Refrigerant Control Electric Expansion Valve Operation Sound (*Qt = Quiet mode) Indoor : Hi/Me/Lo/Qt* Outdoor : Hi db-a db-a 49 / 44 / 39 / Refrigerant Tubing Connections Flare Type Max. allowable tubing length at shipment ft (m) 64 (50) Refrigerant Narrow tube inch (mm) 3/8 (9.52) Tube Diameter Wide tube inch (mm) 5/8 (5.88) Refrigerant Tube Kit Optional Unit Dimensions Height Width Depth Package Dimensions Height Width Depth Weight Net Shipping Shipping Volume inch (mm) inch (mm) Ibs (kg) Ibs (kg) cu.ft (m 3 ) Remarks: Rating conditions are: Cooling: Indoor air temperature 80 F DB / 67 F WB Outdoor air temperature 95 F DB / 75 F WB Indoor Unit 2-7/ /8 4-3/32 (30,40 380) 32.0 (4.5) 39.7 (8.0) 4.59 (0.3) 230V Single-Phase 60Hz Cooling Outdoor Unit < 230V > -3/6 4-5/6 9-/6 35-3/6 37-/32 3-3/8 (300, ) ( ) 42-3/ /8 (,076,06 46) 83.0 (83.0) (93.0) 5.88 (0.45) DATA SUBJECT TO CHANGE WITHOUT NOTICE. 7

8 Indoor Unit Outdoor Unit Performance Electrical Rating Features Dimensions & Weight Voltage Rating CS-KS30NKU CU-KS30NKUA Total Capacity BTU/h kw Sensible Capacity BTU/h Latent Capacity BTU/h Air Circulation (Hi/Me/Lo) ft 3 /min (m 3 /h) Moisture Removal (High) Pints/h Available Voltage Range V Running Amperes A Power Input W Power Factor % EER BTU/h/W SEER BTU/Wh Compressor Locked Rotor Amperes A Fuse or Circuit Breaker Capacity A Controls / Temperature Control Control Unit Timer Fan Speeds Indoor / Outdoor Airflow Direction (Indoor) Horizontal Vertical Air Filter Compressor Refrigerant / Amount charged at shipment Ibs (g) Refrigerant Control Operation Sound (*Qt = Quiet mode) Indoor : Hi/Me/Lo/Qt* Outdoor : Hi db-a db-a Refrigerant Tubing Connections Max. allowable tubing length at shipment ft (m) Refrigerant Narrow tube inch (mm) Tube Diameter Wide tube inch (mm) Refrigerant Tube Kit Unit Dimensions Height Width Depth Package Dimensions Height Width Depth Weight Net Shipping Shipping Volume inch (mm) inch (mm) Ibs (kg) Ibs (kg) cu.ft (m 3 ) 208V Single-Phase 60Hz 30,600 ( 0,900 to 30,600 ) 9.0 ( 3.2 to 9.0 ) 8,600 2, (,070) / 530 (90) /42 (700) 8.0 3,290 Indoor Unit 2-7/ /8 4-3/32 (30,40 380) 32.0 (4.5) 39.7 (8.0) 4.59 (0.3) Cooling to 253 ( 5.0 to 8.0 ) (,000 to 3,290 ) Microprocessor / I.C. Thermister Wireless Remote Control Unit 24-Hour ON or OFF Timer, -Hour OFF Timer Auto and 3 steps / Auto (Hi, Me, Lo) Manual Auto Washable, Anti-Mold DC Twin Rotary (Inverter) R40A / 6.5 (2,950) Electric Expansion Valve 49 / 44 / 39 / Flare Type 64 (50) 3/8 (9.52) 5/8 (5.88) Optional Outdoor Unit < 208V > -3/6 4-5/6 9-/6 35-3/6 37-/32 3-3/8 (300, ) ( ) 42-3/ /8 (,076,06 46) 83.0 (83.0) (93.0) 5.88 (0.45) DATA SUBJECT TO CHANGE WITHOUT NOTICE. Remarks: Rating conditions are: Cooling: Indoor air temperature 80 F DB / 67 F WB Outdoor air temperature 95 F DB / 75 F WB 8

9 Indoor Unit Outdoor Unit Performance Electrical Rating Features Dimensions & Weight Voltage Rating CS-KS36NKU CU-KS36NKUA Total Capacity BTU/h kw Sensible Capacity BTU/h Latent Capacity BTU/h Air Circulation (Hi/Me/Lo) ft 3 /min (m 3 /h) Moisture Removal (High) Pints/h Available Voltage Range V Running Amperes A Power Input W Power Factor % EER BTU/h/W SEER BTU/Wh Compressor Locked Rotor Amperes A Fuse or Circuit Breaker Capacity A Controls / Temperature Control Control Unit Timer Fan Speeds Indoor / Outdoor Airflow Direction (Indoor) Horizontal Vertical Air Filter Compressor Refrigerant / Amount charged at shipment Ibs (g) Refrigerant Control Operation Sound (*Qt = Quiet mode) Indoor : Hi/Me/Lo/Qt* Outdoor : Hi db-a db-a Refrigerant Tubing Connections Max. allowable tubing length at shipment ft (m) Refrigerant Narrow tube inch (mm) Tube Diameter Wide tube inch (mm) Refrigerant Tube Kit Unit Dimensions Height Width Depth Package Dimensions Height Width Depth Weight Net Shipping Shipping Volume inch (mm) inch (mm) Ibs (kg) Ibs (kg) cu.ft (m 3 ) 230V Single-Phase 60Hz 34,000 ( 0,900 to 34,000 ) 0.0 ( 3.2 to 0.0 ) 20,700 3, (,070) / 530 (90) /42 (700) ,000 Indoor Unit 2-7/ /8 4-3/32 (30,40 380) 32.0 (4.5) 39.7 (8.0) 4.59 (0.3) Cooling to 253 ( 5.0 to 20.0 ) (,000 to 4,000 ) Microprocessor / I.C. Thermister Wireless Remote Control Unit 24-Hour ON or OFF Timer, -Hour OFF Timer Auto and 3 steps / Auto (Hi, Me, Lo) Manual Auto Washable, Anti-Mold DC Twin Rotary (Inverter) R40A / 6.5 (2,950) Electric Expansion Valve 49 / 44 / 39 / Flare Type 64 (50) 3/8 (9.52) 5/8 (5.88) Optional Outdoor Unit < 230V > -3/6 4-5/6 9-/6 35-3/6 37-/32 3-3/8 (300, ) ( ) 42-3/ /8 (,076,06 46) 83.0 (83.0) (93.0) 5.88 (0.45) DATA SUBJECT TO CHANGE WITHOUT NOTICE. Remarks: Rating conditions are: Cooling: Indoor air temperature 80 F DB / 67 F WB Outdoor air temperature 95 F DB / 75 F WB 9

10 Indoor Unit Outdoor Unit Performance Electrical Rating Features Dimensions & Weight Voltage Rating CS-KS36NKU CU-KS36NKUA Total Capacity BTU/h kw Sensible Capacity BTU/h Latent Capacity BTU/h Air Circulation (Hi/Me/Lo) ft 3 /min (m 3 /h) Moisture Removal (High) Pints/h Available Voltage Range V Running Amperes A Power Input W Power Factor % EER BTU/h/W SEER BTU/Wh Compressor Locked Rotor Amperes A Fuse or Circuit Breaker Capacity A Controls / Temperature Control Control Unit Timer Fan Speeds Indoor / Outdoor Airflow Direction (Indoor) Horizontal Vertical Air Filter Compressor Refrigerant / Amount charged at shipment Ibs (g) Refrigerant Control Operation Sound (*Qt = Quiet mode) Indoor : Hi/Me/Lo/Qt* Outdoor : Hi db-a db-a Refrigerant Tubing Connections Max. allowable tubing length at shipment ft (m) Refrigerant Narrow tube inch (mm) Tube Diameter Wide tube inch (mm) Refrigerant Tube Kit Unit Dimensions Height Width Depth Package Dimensions Height Width Depth Weight Net Shipping Shipping Volume inch (mm) inch (mm) Ibs (kg) Ibs (kg) cu.ft (m 3 ) 208V Single-Phase 60Hz 34, ,000 Indoor Unit 2-7/ /8 4-3/32 (30,40 380) 32.0 (4.5) 39.7 (8.0) 4.59 (0.3) Cooling ( 0,900 to 34,000 ) ( 3.2 to 0.0 ) 20,700 3, (,070) / 530 (90) /42 (700) to 253 ( 5.0 to 2.9 ) (,000 to 4,000 ) Microprocessor / I.C. Thermister Wireless Remote Control Unit 24-Hour ON or OFF Timer, -Hour OFF Timer Auto and 3 steps / Auto (Hi, Me, Lo) Manual Auto Washable, Anti-Mold DC Twin Rotary (Inverter) R40A / 6.5 (2,950) Electric Expansion Valve 49 / 44 / 39 / Flare Type 64 (50) 3/8 (9.52) 5/8 (5.88) Optional Outdoor Unit < 208V > -3/6 4-5/6 9-/6 35-3/6 37-/32 3-3/8 (300, ) ( ) 42-3/ /8 (,076,06 46) 83.0 (83.0) (93.0) 5.88 (0.45) DATA SUBJECT TO CHANGE WITHOUT NOTICE. Remarks: Rating conditions are: Cooling: Indoor air temperature 80 F DB / 67 F WB Outdoor air temperature 95 F DB / 75 F WB 0

11 2-2. Major Component Specifications Indoor Unit Indoor Unit CS-KS30NKU Control PCB Part No. Controls Control Circuit Fuse CB-CS-KS30NKU Microprocessor 250V 3A Fan Type Q'ty... Dia. and Length inch (mm) Cross-Flow... D3-5/6 / L32- (D00/L838) Fan Motor Type Model... Q'ty No. of Poles Rough Measure RPM (Cool) Nominal Output Coil Resistance (Ambient Temp. 68 F (20 C)) Safety Device Type Over-Current Protection Over-Heat Protection Run Capacitor Flap Motor Type Model Rating Coil Resistance (Ambient Temp. 77 F (25 C)) Heat Exchanger Coil Coil Rows Fins Per inch Face Area W Ohm Micro F VAC Ohm ft 2 (m 2 ) DC Motor SIC-4CVJ-D , Internal Controller Yes Yes - - Stepping Motor 24BYJ DC 2V Each Pair of Terminal : 200 +/- 7% Aluminum Plate Fin / Copper Tube and (0.423) DATA SUBJECT TO CHANGE WITHOUT NOTICE.

12 Indoor Unit CS-KS36NKU Control PCB Part No. Controls Control Circuit Fuse CB-CS-KS36NKU Microprocessor 250V 3A Fan Type Q'ty... Dia. and Length inch (mm) Cross-Flow... D3-5/6 / L32- (D00/L838) Fan Motor Type Model... Q'ty No. of Poles Rough Measure RPM (Cool) Nominal Output Coil Resistance (Ambient Temp. 68 F (20 C)) Safety Device Type Over-Current Protection Over-Heat Protection Run Capacitor Flap Motor Type Model Rating Coil Resistance (Ambient Temp. 77 F (25 C)) Heat Exchanger Coil Coil Rows Fins Per inch Face Area W Ohm Micro F VAC Ohm ft 2 (m 2 ) DC Motor SIC-4CVJ-D , Internal Controller Yes Yes - - Stepping Motor 24BYJ DC 2V Each Pair of Terminal : 200 +/- 7% Aluminum Plate Fin / Copper Tube and (0.423) DATA SUBJECT TO CHANGE WITHOUT NOTICE. 2

13 Outdoor Unit Outdoor Unit CU-KS30NKUA P.C.Board Part No. Controls Circuit Fuse Control P.C.B CR-C3082-F Microprocessor 400V 3.5A Noise Filer P.C.B POW-CH3082-B2-250V 25A H.I.C.Board HIC-CH3072R-C - - Compressor Type Compressor Model / Nominal Output Compressor Oil... Amount Pints (cc) Coil Resistance (Ambient Temp. 77 F (25 C)) Ohm Safety Device CT (Peak current cut-off control) Compressor Discharge Temp. Control Operation cut-off control in abnormal ambient Temp. Overload Relay Model Operation Temp. Run Capacitor Crankcase Heater Micro F VAC DC Twin Rotary (Hermetic) C-9RVN273H0H / 2,250W FV68S (,400) T - R : 0.69 T - S : 0.69 R - S : 0.69 Yes Yes Yes CS-7L0 Open : 230 F (0 C), Close : 203 F (95 C) V 30W Fan Type Q'ty... Dia. inch (mm) Propeller... D9-9/32 (D490) Fan Motor Type Model... Q'ty No. of Poles Rough Measure RPM (Cool) Nominal Output Coil Resistance (Ambient Temp. 68 F (20 C)) Safety Device Type Over- Current Protection Over- Heat Protection Run Capacitor W Ohm Micro F VAC DC Motor SIC-7FW-D820-4A Internal Controller Yes Yes - - Heat Exchanger Coil Coil Rows Fins per inch Aluminum Plate Fin / Copper Tube Face Area ft 2 (m 2 ) 8.05 (0.748) External Finish Acrylic baked-on enamel finish DATA SUBJECT TO CHANGE WITHOUT NOTICE. 3

14 Outdoor Unit CU-KS36NKUA P.C.Board Part No. Controls Circuit Fuse Control P.C.B CR-C3682-F Microprocessor 400V 3.5A Noise Filer P.C.B POW-CH3082-B2-250V 25A H.I.C.Board HIC-CH3072R-C - - Compressor Type Compressor Model / Nominal Output Compressor Oil... Amount Pints (cc) Coil Resistance (Ambient Temp. 77 F (25 C)) Ohm Safety Device CT (Peak current cut-off control) Compressor Discharge Temp. Control Operation cut-off control in abnormal ambient Temp. Overload Relay Model Operation Temp. Run Capacitor Crankcase Heater Micro F VAC DC Twin Rotary (Hermetic) C-9RVN273H0H / 2,500W FV68S (,400) T - R : 0.69 T - S : 0.69 R - S : 0.69 Yes Yes Yes CS-7L0 Open : 230 F (0 C), Close : 203 F (95 C) V 30W Fan Type Q'ty... Dia. inch (mm) Propeller... D9-9/32 (D490) Fan Motor Type Model... Q'ty No. of Poles Rough Measure RPM (Cool) Nominal Output Coil Resistance (Ambient Temp. 68 F (20 C)) Safety Device Type Over- Current Protection Over- Heat Protection Run Capacitor W Ohm Micro F VAC DC Motor SIC-7FW-D820-4A Internal Controller Yes Yes - - Heat Exchanger Coil Coil Rows Fins per inch Aluminum Plate Fin / Copper Tube Face Area ft 2 (m 2 ) 8.05 (0.748) External Finish Acrylic baked-on enamel finish DATA SUBJECT TO CHANGE WITHOUT NOTICE. 4

15 2-3. Other Component Specifications Indoor Unit CS-KS30NKU CS-KS36NKU Outdoor Unit CU-KS30NKUA CU-KS36NKUA Indoor air temp sensor (Model:KTEC ) Indoor heat exchanger sensor (Model:PTM-D5H-S6-) Compressor temp sensor (Model:TKS335B) Resistance (k ohm) (0) (5) (20) (25) (30) (35) (40) Temperature F ( C) Resistance (k ohm) (0) (0) (20) (30) (40) (50) (60) (70) (80) (90) Temperature F ( C) Outdoor air temp sensor (Model:TKS295B) Outdoor heat exchanger sensor (Model:TKS334B) Heat sink temp sensor (HIC Board) (Model:TKS36B) 40 Resistance (k ohm) (-20)(-5)(-0) (-5) (0) (5) (0) (5) (20) Temperature F ( C) 5

16 3. DIMENSIONAL DATA Indoor Unit CS-KS30NKU CS-KS36NKU 4-9/6-5/32 dia. 3-5/32 4-5/6 (065) 9-/6 (230) (3/32) 2-3/32 25/32-27/32-3/ /32 Wide tube dia. 5/8" (5.88) 5-27/32 Narrow tube dia. 3/8" (9.52) 5-/2 5-/8 7-23/32 9-3/32 3-3/4 3-3/4 7-7/8 2-/6 6-7/32 6-/32 7-5/6 9-9/6 5-3/6 6-/32 7-2/ /8 dia. 3-5/32-3/6 5/6 2-3/4-3/6 (300) -7/8 23/32 4-9/6-7/8 7-23/32 2-3/4 5-9/6-9/32 2-3/8 2-3/8 2-5/8 3-3/8 7/6 2-5/8 Unit: inch(mm) ( ) 6

17 Outdoor Unit CU-KS30NKUA CU-KS36NKUA -3/6 7/6 2-5/32 Unit: inch(mm) ( ) 3-9/32 4-/32 4-/ /32-5/6-27/32-3/6 6-23/32 9/32 4-3/4 3/32 2/32 6-/6 25-3/32 4-/32 4-/8 8-5/8 2-5/6 2-5/6 2-3/8 /2 /2 37-/32 (940) 3/4 2-3/8 2-ID:-/4 holes (holes for drain) Of the 4-ID:-/4 holes, use of 2 holes specified for drain use to install the port. Use rubber plugs to seal the remaining 3 holes. Refrigerant tubing joint (Liquid tube) Flare connection dia.3/8" (9.52) Refrigerant tubing joint (Gas tube) Flare connection dia.5/8" (5.88) 2-3/8 3-3/8 2-7/32 3/4 Wiring outlet (knock-out holes dia.-3/8, -3/32, 7/8, /2) 2-25/32-5/6 4-/32-27/32-3/6 Wiring outlet (knock-out holes dia.-3/8, -3/32, 7/8, /2) 2-5/32 2-7/32-3/32 -/ /6 (90) 23/32 3/32 3-3/8 (340) 4-3/32 6-5/32 7

18 4. REFRIGERANT FLOW DIAGRAM 4-. Refrigerant Flow Diagram Indoor Unit CS-KS30NKU CS-KS36NKU Outdoor Unit CU-KS30NKUA CU-KS36NKUA Indoor unit Outdoor unit Wide tube O.D 5/8" (5.88 mm) Wide tube service valve Muffler Sub Accumulator Main Accumulator High pressure switch H.P. Heat exchanger Heat exchanger Compressor Narrow tube Narrow tube service valve Electric expansion valve M Cooling cycle O.D. 3/8" (9.52 mm) Strainer 8

19 5. PERFORMANCE DATA 5-. Temperature Charts Indoor Unit CS-KS30NKU Outdoor Unit CU-KS30NKUA Cooling Characteristics (RH : 46%, Indoor fan speed : High fan) (60Hz, 230V) () Low pressure performance chart Indoor discharge air temperature F( C) Low pressure at wide tube service valve Operating current (A) psig(mpag) 74 (.2) 59 (.) 45 (.0) 3 (0.9) 7 (0.8) 04 (0.7) -4 (-20) 5 (-5) 4 (-0) 23 (-5) (2) Operating current performance chart (-20) 5 (-5) 4 (-0) 23 (-5) (3) Indoor discharge air performance chart 64.4 (8) 60.8 (6) 57.2 (4) 53.6 (2) 50.0 (0) 46.4 (8) 42.8 (6) 32 (0) 32 (0) 4 (5) 50 (0) 59 (5) Outdoor inlet air DB temp. F( C) (5) (0) (5) Outdoor inlet air DB temp. F( C) 68 (20) 68 (20) Lo fan Indoor Air Temp.86 F (30 C) Lo fan Lo fan 80 F (27 C) 75 F (24 C) 77 (25) 77 (25) 86 (30) Indoor Air Temp.86 F (30 C) 80 F (27 C) 75 F (24 C) Indoor Air Temp.86 F (30 C) 80 F (27 C) 80 F (27 C) 75 F (24 C) 75 F (24 C) 86 (30) Hi Fan Hi Fan Hi Fan 95 (35) 95 (35) 04 (40) 04 (40) -4 (-20) 5 (-5) 4 (-0) 23 (-5) 32 (0) (5) (0) (5) Outdoor inlet air DB temp. F( C) 68 (20) 77 (25) 86 (30) 95 (35) 04 (40) NOTE Check each performance value in test-run mode. Electrical performance values represent a combined indoor/outdoor value. 9

20 Indoor Unit CS-KS36NKU Outdoor Unit CU-KS36NKUA Cooling Characteristics (RH : 46%, Indoor fan speed : High fan) (60Hz, 230V) () Low pressure performance chart Indoor discharge air temperature F( C) Low pressure at wide tube service valve Operating current (A) psig(mpag) 74 (.2) 59 (.) 45 (.0) 3 (0.9) 7 (0.8) 04 (0.7) -4 (-20) 5 (-5) 4 (-0) 23 (-5) (2) Operating current performance chart (-20) 5 (-5) 4 (-0) 23 (-5) (3) Indoor discharge air performance chart 64.4 (8) 60.8 (6) 57.2 (4) 53.6 (2) 50.0 (0) 46.4 (8) 42.8 (6) 32 (0) 32 (0) 4 (5) 50 (0) 59 (5) Outdoor inlet air DB temp. F( C) (5) (0) (5) Outdoor inlet air DB temp. F( C) 68 (20) 68 (20) Lo fan Indoor Air Temp.86 F (30 C) Lo fan Lo fan 77 (25) 77 (25) 80 F (27 C) 80 F (27 C) 75 F (24 C) 80 F (27 C) Indoor Air Temp.86 F (30 C) 75 F (24 C) Indoor Air Temp.86 F (30 C) 80 F (27 C) 75 F (24 C) 86 (30) 86 (30) Hi Fan Hi Fan Hi Fan 95 (35) 95 (35) 04 (40) 04 (40) -4 (-20) 5 (-5) 4 (-0) 23 (-5) 32 (0) (5) (0) (5) Outdoor inlet air DB temp. F( C) 68 (20) 77 (25) 86 (30) 95 (35) 04 (40) NOTE Check each performance value in test-run mode. Electrical performance values represent a combined indoor/outdoor value. 20

21 5-2. Cooling Capacity Indoor Unit : CS-KS30NKU Outdoor Unit : CU-KS30NKUA Power Supply : 230V Single Phase 60Hz < Cooling Capacity > RATING CAPACITY: 30,600 BTU/h AIR FLOW RATE: 630 CFM INDOOR OUTDOOR ENT. TEMP. o F ( o C) AMBIENT TEMP. o F ( o C) WB DB (8.3) (23.9) (29.4) (35.0) (40.6) (46.) TC 26,540 27,20 27,70 27,90 24,890 7,30 CI (22.2) SHC 9,90 9,430 9,800 9,920 8,330 4, (24.4) SHC 2,50 2,880 22,20 22,250 20,660 6,990 (5.0) 80 (26.7) SHC 23,960 24,330 24,570 24,690 23,00 7,30 84 (28.9) SHC 26,280 26,650 26,890 27,020 24,890 7,30 88 (3.) SHC 26,540 27,20 27,70 27,90 24,890 7,30 TC 3,580 30,90 30,60 29,630 25,270 7,560 CI (22.2) SHC 8,330 7,970 7,600 7,360 5,50, (24.4) SHC 20,660 20,290 9,920 9,680 7,480 4,050 (7.2) 80 (26.7) SHC 23,00 22,740 22,370 22,20 20,050 6, (28.9) SHC 25,430 25,060 24,690 24,450 22,370 7, (3.) SHC 27,750 27,50 27,020 26,770 24,690 7,560 TC 32,420 3,780 3,050 # 30,600 25,550 7,760 CI (22.2) SHC 5,50 4,790 4,420 4,300 2,00 8, (24.4) SHC 7,480 7,0 6,870 6,620 4,420,240 (9.4) 80 (26.7) SHC 9,920 9,560 9,30 9,070 6,870 3, (28.9) SHC 22,250 22,000 2,640 2,390 9,90 6,00 88 (3.) SHC 24,570 24,330 23,960 23,70 2,50 7,760 TC 33,30 32,540 3,840 3,490 25,70 7,880 CI (22.2) SHC,730,480,20,000 8,670 5, (24.4) SHC 4,050 3,80 3,440 3,320,20 8,30 (2.7) 80 (26.7) SHC 6,500 6,250 5,890 5,770 3,560 0, (28.9) SHC 8,820 8,580 8,330 8,20 5,890 3, (3.) SHC 2,50 20,900 20,660 20,530 8,20 5,400 TC 33,630 33,090 32,430 32,90 25,730 7,900 CI (24.4) SHC 0,750 0,50 0,260 0,40 7,940 5,370 (23.9) 80 (26.7) SHC 3,200 2,950 2,70 2,590 0,380 7, (28.9) SHC 5,520 5,280 5,030 5,030 2,70 0,40 88 (3.) SHC 7,840 7,720 7,480 7,360 5,030 2,590 TC : Total Cooling Capacity (BTU/h) SHC : Sensible Heat Capacity (BTU/h) NOTE. Rating conditions (#) : Indoor Unit Entering Air Temp. 80 F (26.7 C) DB / 67 F (9.4 C) WB : Outdoor Ambient Temp. 95 F (35 C) DB 2. Above data does not take Freeze Prevention Protection during cooling operation into account. For this reason, the value may vary from the actual cooling characteristics. 3. Above data represents the value when the operation frequency of a compressor is fixed. 2

22 Indoor Unit : Outdoor Unit : Power supply : CS-KS36NKU CU-KS36NKUA 230V Single Phase 60Hz < Cooling Capacity > RATING CAPACITY: 34,000 BTU/h AIR FLOW RATE: 630 CFM INDOOR OUTDOOR ENT. TEMP. o F ( o C) AMBIENT TEMP. o F ( o C) WB DB (8.3) (23.9) (29.4) (35.0) (40.6) (46.) TC 27,450 28,40 28,840 29,040 24,650 6,770 CI (22.2) SHC 9,680 20,050 20,40 20,530 8,20 4, (24.4) SHC 22,000 22,370 22,740 22,860 20,530 6,740 (5.0) 80 (26.7) SHC 24,450 24,820 25,80 25,300 22,980 6, (28.9) SHC 26,770 27,40 27,50 27,630 24,650 6, (3.) SHC 27,450 28,40 28,840 29,040 24,650 6,770 TC 35,00 34,360 33,600 33,00 24,850 6,90 CI (22.2) SHC 20,70 9,800 9,30 9,070 5,030, (24.4) SHC 22,490 22,20 2,760 2,390 7,360 3,80 (7.2) 80 (26.7) SHC 24,940 24,570 24,200 23,840 9,800 6, (28.9) SHC 27,260 26,890 26,530 26,280 22,20 6,90 88 (3.) SHC 29,580 29,220 28,850 28,60 24,450 6,90 TC 35,720 35,20 34,400 # 34,000 24,930 6,970 CI (22.2) SHC 6,620 6,380 6,00 5,890,730 8, (24.4) SHC 9,070 8,700 8,330 8,20 4,80,000 (9.4) 80 (26.7) SHC 2,50 2,50 20,900 20,660 6,620 3, (28.9) SHC 23,840 23,590 23,230 22,980 8,940 5, (3.) SHC 26,60 25,920 25,550 25,300 2,270 6,970 TC 36,270 35,70 35,040 34,780 24,870 6,950 CI (22.2) SHC 3,070 2,830 2,460 2,340 8,430 5, (24.4) SHC 5,400 5,50 4,790 4,790 0,750 7,940 (2.7) 80 (26.7) SHC 7,840 7,600 7,360 7,230 3,200 0, (28.9) SHC 20,70 9,920 9,680 9,560 5,520 2,70 88 (3.) SHC 22,490 22,250 22,000 2,880 7,840 5,030 TC 36,560 36,070 35,450 34,630 24,680 6,830 CI (24.4) SHC,850,60,360,20 7,570 5,30 (23.9) 80 (26.7) SHC 4,300 4,050 3,80 3,560 0,020 7, (28.9) SHC 6,620 6,500 6,250 5,890 2,340 9, (3.) SHC 8,940 8,820 8,580 8,20 4,660 2,220 TC : Total Cooling Capacity (BTU/h) SHC : Sensible Heat Capacity (BTU/h) NOTE. Rating conditions (#) : Indoor Unit Entering Air Temp. 80 F (26.7 C) DB / 67 F (9.4 C) WB : Outdoor Ambient Temp. 95 F (35 C) DB 2. Above data does not take Freeze Prevention Protection during cooling operation into account. For this reason, the value may vary from the actual cooling characteristics. 3. Above data represents the value when the operation frequency of a compressor is fixed. 22

23 5-3. Cooling Capacity (Low Ambient) Indoor Unit : Outdoor Unit : Power supply : CS-KS30NKU CU-KS30NKUA 230V Single Phase 60Hz < Cooling Capacity (Low Ambient) > RATING CAPACITY: 30,600 BTU/h AIR FLOW RATE: 630 CFM INDOOR OUTDOOR ENT. TEMP. o F ( o C) AMBIENT TEMP. o F ( o C) WB DB (-7.8) (-5.0) (-9.4) (-3.9) (.7) (7.2) (2.8) TC 30,20 30,060 29,930 29,780 29,590 29,330 29,070 CI (22.2) SHC 2,50 2,50 2,020 23,230 20,780 20,660 20, (24.4) SHC 23,470 23,470 23,350 25,550 23,230 22,980 22,860 (5.0) 80 (26.7) SHC 25,920 25,920 25,790 27,870 25,670 25,430 25, (28.9) SHC 28,240 28,240 28,20 29,780 27,990 27,870 27, (3.) SHC 30,20 30,060 29,930 29,780 29,590 29,330 29,070 TC 30,390 30,360 30,270 30,70 30,040 29,820 29,60 CI (22.2) SHC 7,720 7,720 7,600 23,230 7,480 7,360 7, (24.4) SHC 20,050 20,050 9,920 25,550 9,800 9,800 9,680 (7.2) 80 (26.7) SHC 22,490 22,490 22,370 27,870 22,370 22,250 22,20 84 (28.9) SHC 24,820 24,820 24,820 30,70 24,690 24,570 24, (3.) SHC 27,40 27,40 27,40 30,70 27,020 26,890 26,770 TC 30,490 30,480 30,450 30,400 30,330 30,60 30,020 CI (22.2) SHC 4,80 4,80 4,80 23,230 4,80 4,050 4, (24.4) SHC 6,500 6,500 6,500 25,550 6,500 6,380 6,380 (9.4) 80 (26.7) SHC 9,070 8,940 8,940 27,870 8,940 8,820 8, (28.9) SHC 2,390 2,390 2,390 30,200 2,270 2,50 2,50 88 (3.) SHC 23,70 23,70 23,70 30,400 23,590 23,590 23,470 TC 30,370 30,380 30,40 30,430 30,420 30,30 30,250 CI (22.2) SHC 0,50 0,50 0,50 23,230 0,630 0,50 0, (24.4) SHC 2,950 2,950 2,950 25,550 2,950 2,830 2,830 (2.7) 80 (26.7) SHC 5,400 5,400 5,400 27,870 5,400 5,280 5, (28.9) SHC 7,720 7,720 7,720 30,200 7,720 7,720 7, (3.) SHC 20,050 20,050 20,050 30,430 20,050 20,050 20,050 TC 30,030 30,080 30,70 30,240 30,30 30,250 30,270 CI (24.4) SHC 9,40 9,40 9,40 25,550 9,530 9,530 9,530 (23.9) 80 (26.7) SHC,850,850,850 27,870,970,970, (28.9) SHC 4,80 4,80 4,300 30,200 4,300 4,300 4, (3.) SHC 6,500 6,620 6,620 30,240 6,620 6,620 6,620 TC : Total Cooling Capacity (BTU/h) SHC : Sensible Heat Capacity (BTU/h) NOTE. Above data does not take Freeze Prevention Protection during cooling operation into account. For this reason, the value may vary from the actual cooling characteristics. 2. Above data represents the value when the operation frequency of a compressor is fixed. 23

24 Indoor Unit : Outdoor Unit : Power supply : CS-KS36NKU CU-KS36NKUA 230V Single Phase 60Hz < Cooling Capacity (Low Ambient) > - RATING CAPACITY: 34,000 BTU/h AIR FLOW RATE: 630 CFM INDOOR OUTDOOR ENT. TEMP. o F ( o C) AMBIENT TEMP. o F ( o C) WB DB (-7.8) (-5.0) (-9.4) (-3.9) (.7) (7.2) (2.8) TC 30,900 30,870 30,800 30,70 30,590 30,400 30,20 CI (22.2) SHC 2,50 2,50 2,50 23,230 2,390 2,270 2, (24.4) SHC 23,960 23,840 23,840 25,550 23,70 23,590 23,470 (5.0) 80 (26.7) SHC 26,400 26,400 26,280 27,870 26,60 26,040 25, (28.9) SHC 28,730 28,730 28,60 30,200 28,480 28,480 28, (3.) SHC 30,900 30,870 30,800 30,70 30,590 30,400 30,20 TC 3,00 3,00 30,990 30,950 30,890 30,750 30,620 CI (22.2) SHC 7,970 7,970 7,970 23,230 7,970 7,840 7, (24.4) SHC 20,40 20,40 20,290 25,550 20,290 20,70 20,70 (7.2) 80 (26.7) SHC 22,860 22,860 22,740 27,870 22,740 22,60 22,60 84 (28.9) SHC 25,80 25,80 25,80 30,200 25,060 25,060 24, (3.) SHC 27,50 27,50 27,50 30,950 27,380 27,380 27,260 TC 30,90 30,940 30,980 3,000 3,00 30,930 30,880 CI (22.2) SHC 4,420 4,420 4,420 23,230 4,420 4,420 4, (24.4) SHC 6,740 6,740 6,740 25,550 6,740 6,740 6,740 (9.4) 80 (26.7) SHC 9,90 9,90 9,90 27,870 9,90 9,90 9,90 84 (28.9) SHC 2,50 2,50 2,640 30,200 2,640 2,50 2,50 88 (3.) SHC 23,840 23,960 23,960 3,000 23,960 23,960 23,840 TC 30,570 30,620 30,730 30,820 30,90 30,900 30,930 CI (22.2) SHC 0,630 0,630 0,750 23,230 0,750 0,750 0, (24.4) SHC 2,950 2,950 3,070 25,550 3,070 3,070 3,070 (2.7) 80 (26.7) SHC 5,400 5,400 5,520 27,870 5,520 5,520 5, (28.9) SHC 7,720 7,840 7,840 30,200 7,970 7,970 7, (3.) SHC 20,70 20,70 20,70 30,820 20,290 20,290 20,290 TC 30,00 30,090 30,260 30,430 30,590 30,650 30,770 CI (24.4) SHC 9,40 9,40 9,530 25,550 9,650 9,650 9,650 (23.9) 80 (26.7) SHC,850,850,970 27,870 2,00 2,00 2,00 84 (28.9) SHC 4,80 4,80 4,300 30,200 4,420 4,420 4, (3.) SHC 6,500 6,620 6,620 30,430 6,740 6,740 6,870 TC : Total Cooling Capacity (BTU/h) SHC : Sensible Heat Capacity (BTU/h) CI : Compressor Input (kw) NOTE Above data does not take freeze prevention protection during cooling operation into account. For this reason, the value may vary from the actual cooling characteristics. 2 Above data represents the value when the operation frequency of a compressor is fixed. 24

25 5-4. Air Throw Distance Charts Indoor Unit CS-KS30NKU Cooling Room air temp. : 80 F (26.7 C) Fan speed : High Horizontal distance (ft.) Axis air velocity (ft./sec.) Vertical distance (ft.) : Flap angle 0, : Axis air velocity 0 : Flap angle 30, : Axis air velocity 30 25

26 Indoor Unit CS-KS36NKU Cooling Room air temp. : 80 F (26.7 C) Fan speed : High Horizontal distance (ft.) Axis air velocity (ft./sec.) Vertical distance (ft.) : Flap angle 0, : Axis air velocity 0 : Flap angle 30, : Axis air velocity 30 26

27 6. ELECTRICAL DATA 6-. Electrical Characteristics Indoor Unit CS-KS30NKU Outdoor Unit CU-KS30NKUA () Voltage:230V Cooling Indoor Fan Motor Performance at Rating conditions Running amp. A 0.4 Power input W 39 UnitOutdoor Unit Fan Motor + Compressor 230V Single-phase 60Hz 6. 3,25 < 230V > Complete Unit 6.5 3,290 Rating conditions: Indoor air temperature: 80 F (26.7 C) DB / 67 F (9.4 C) WB Outdoor air temperature: 95 F (35 C) DB (2) Voltage:208V Cooling Indoor Fan Motor Performance at Rating conditions Running amp. Power input A W Rating conditions: Indoor air temperature: 80 F (26.7 C) DB / 67 F (9.4 C) WB Outdoor air temperature: 95 F (35 C) DB UnitOutdoor Unit Fan Motor + Compressor 208V Single-phase 60Hz 7.6 3,25 < 208V > Complete Unit 8.0 3,290 27

28 Indoor Unit CS-KS36NKU Outdoor Unit CU-KS36NKUA () Voltage:230V Cooling Indoor Fan Motor Performance at Rating conditions Running amp. A 0.4 Power input W 39 UnitOutdoor Unit Fan Motor + Compressor 230V Single-phase 60Hz 9.6 3,96 < 230V > Complete Unit ,000 Rating conditions: Indoor air temperature: 80 F (26.7 C) DB / 67 F (9.4 C) WB Outdoor air temperature: 95 F (35 C) DB (2) Voltage:208V Cooling Indoor Fan Motor Performance at Rating conditions Running amp. Power input A W Rating conditions: Indoor air temperature: 80 F (26.7 C) DB / 67 F (9.4 C) WB Outdoor air temperature: 95 F (35 C) DB UnitOutdoor Unit Fan Motor + Compressor 208V Single-phase 60Hz 2.5 3,96 < 208V > Complete Unit 2.9 4,000 28

29 6-2. Electric Wiring Diagrams Indoor Unit CS-KS30NKU CS-KS36NKU EVAPORATOR M FLAP MOTOR PL ELEC J-B GRN/YEL RED ORG YEL PNK BLU GRN GND FLAP 5P (WHT) GND 2P (WHT) + + AC IN COM + BLK WHT RED SI LAMP 9P (WHT) CONTROLLER TERMINAL BASE 2 3 U U2 GND WHT BLK BLK BLK BLK BLK BLK BLK BLK TO OUTDOOR UNIT IND LAMP ASSY OPERATION SW M FAN MOTOR RED BLK WHT YEL BLU DCM 7P (WHT) S-LINK (RAC) 4P (BLU) T0 6P (BLU) COIL 2P (WHT) ROOM/UV 4P (WHT) BLK BLK BLK BLK COIL THERMISTOR ROOM THERMISTOR 8FA

30 Outdoor Unit CU-KS30NKUA CU-KS36NKUA 8FA CONTROL P.C.BOARD NOISE FILTER P.C. BOARD HIC BOARD + + HIC- W T S R V U HIC+ + L + L2 + DC- TH0 (YEL) TH + + M 3 COMPRESSOR MOTOR BLU WHT RED HIC (WHT) CN0 (WHT) WHT BLK BLK BLK BLK BLK BLK BLK BLK BLK HIC2 (WHT) CN02 (WHT) BLK BLK BLK BLK BLK BLK BLK BLK (WHT) MV (WHT) TEST/MV MAGNETIC COIL HEAT SINK (RADIATOR) BRIDGE DIODE ORG RED YEL BLK GRY 2 2 (BLK) COIL YEL YEL COIL THERMISTOR 2 2 (GRN) PRY BLK WHT (WHT) DCOUT BLK WHT (ORG) ACOUT BLK WHT (BRN) (GRN) (WHT) (ORG) (BRN) CT PRY DCIN ACIN CT WHT WHT 2 2 INDOOR UNIT POWER SUPPLY GND TERMINAL (5P) FM2 (RED) RED BLU BRN WHT ORG FM (RED) FAN MOTOR REACTOR C w E2 w E YEL YEL BLU w CH2 CRANKCASE HEATER WHT WHT WHT DC+ YEL GRY YEL + + AC2 w AC IN2 w AC IN WHT + + AC BLK M M 2 2 (WHT) COMP BLK BLK COMPRESSOR THERMISTOR 2 2 (YEL) OUTDOOR BLK BLK OUTDOOR THERMISTOR GRN/YEL 2 2 (BLK) HP-SW RED RED HIGH PRESSURE SW 2 2 (RED) OLR WHT WHT OVER LOAD RELAY BLK WHT + L3 + L4 BLK WHT + C + C2 + HIC+ + HIC- BLK WHT w w CH SI w S-COM WHT BLK WHT RED WHT BLK WHT GRN GRN 30

31 7. FUNCTIONS 7-. Operation Functions Emergency operation Emergency operation is available when the remote controller malfunctions, has been lost, or otherwise cannot be used. To operate the system, press the OPERATION button, which is also used as the receiver, below the unit display. Each time this button is pressed, the OPERATION lamp changes color to indicate the type of operation. Select the desired type of operation. SENSOR DRY During DRY operation, the system adjusts the room temperature and fan speed according to the conditions in the room, in order to maintain a comfortable room environment. SENSOR DRY operation DRY operation is as shown in the figure below. Load COOL (GREEN) STOP (Lamp Off) COOL zone A zone The set temperature is 4 F(2 C) below the detected room temperature in the case of cooling operation. B zone Conditions are monitored at all times when the room temperature is below 59 F(5 C). DRY A The compressor operation frequency varies. The indoor fan operates with /f fluctuation. DRY B The compressor operates at a low operating frequency. The indoor fan operates with /f fluctuation. Monitor Monitoring operation takes place when the room temperature is below 59 F(5 C), or more than 5 F(3 C) below the set temperature. When the monitoring range is entered, the compressor stops, and the indoor fan operates with /f fluctuation. NOTE The Sensor Dry operation during the Low Ambient Cooling Mode (outside air temperature : 59 F(5 C) or lower) is as follows. DRY A and DRY B When room temperature rises above the set temperature, the compressor turns ON. When room temperature falls below the set temperature, the compressor turns OFF. 3

32 HIGH POWER This function acts to raise the power but keeps the AC system in the same operating mode. This function is set with the HIGH POWER button on the remote controller. (It can be set regardless of the temperature and fan speed settings.) HIGH POWER operation from remote controller The unit operates at maximum output for 30 minutes, regardless of the desired temperature. The fan speed is step above "High." Frequency MAX NIGHT SETBACK When NIGHT SETBACK operation is set, the temperature and fan speed settings will be adjusted automatically to allow comfortable sleep. When NIGHT SETBACK operation is set, " mark" appears on the remote controller. The main unit display lamp also becomes dimmer. COOL and DRY modes When the night setback mode is selected, the air conditioner automatically raises the temperature setting 2 F( C) when 30 minutes have passed after the selection was made, and then another 2 F( C) after another 30 minutes have passed, regardless of the indoor temperature when night setback was selected. This enables you to save energy without sacrificing comfort. This function is convenient when gentle cooling is needed min. 5 min. Time Setting temperature 2 F( C) 2 F( C) NOTE Start End When HIGH POWER operation ends, the unit operates at low Hz for 5 minutes, regardless of the thermostat OFF conditions. When in DRY mode, operation is in the cooling zone. Press the NIGHT SETBACK button 30 min. 30 min. Time Lamp colors OPERATION lamp DRY operation COOL operation FAN operation TIMER lamp Orange Green Green Green Timer backup Operation stops if there are no operator controls for 25 hours or longer after unit operation switched from OFF to ON by use of ON timer operation. 32

33 Noise Reducing Control (Outdoor Unit) The noise reducing control is the function used for silent operation of the air conditioner by means of setting the dip switch on the outdoor unit P.C.Board to control the fan and compressor's motor speed. NOTE When this function is used, the cooling ability is slightly degraded. Therefore, when this function is to be enabled, make sure to receive the approval of the client. <Operation Sound> Noise Reducing Control Specifications (Fan's motor speed : 500rpm) Cooling Cooling 55 db-a 47 db-a Outdoor Air Temp. F( C) <In Cooling Operation> Normal Operation 9(33) 82(28) Normal Operation or Noise Reducing Operation is kept. (Initial setting is the normal operation.) Noise Reducing Operation NOTE. In the test operation, high-power operation, defrost operation or low ambient cooling operation (to be cancelled at the outside temperature of 57 F(4 C) or less, or 63 F(7 C) or more), the noise reducing control is not available. 2. In the noise reducing operation, the fan's maximum motor speed is limited to 500rpm. Also, the maximum frequency (Hz) is controlled in the cooling (30Hz) or heating operation (30Hz). <Switching Procedure to Noise Reducing Control> () Remove the 3 screws fixing the inspection panel and remove the inspection panel. (Fig. 2) (2) When the switch No. of the dip switch (SW0) on the control P.C.Board is turned ON, the noise reducing control is enabled. (Fig. 3) Power lamp Control P.C.Board ON Inspection panel 2 Dip switch (SW0) Slide downward SW0 Fig.3 Control P.C.Board Fig.2 View from front 33

34 Maximum Current Value Change Function The maximum current value is changed to 4A (for CU-KS30NKUA) or 7A (for CU-KS36NKUA) to prevent power breaker tripping. (It is set to 24A when the unit is delivered from the factory.) NOTE. When the high load is given (Outside temperature is high in the cooling operation), the capacity is reduced. When the maximum current value change function is to be enabled, make sure to receive the approval of the client. 2. The maximum capacity for cooling operation is about as much as the rated capacity. Description of function Frequency Current Target frequency Example of operation Frequency Stops operation Approx.3 minutes Power Point C Point B Point A Operates at the target frequency at Point A and below. Stops increases to the frequency between Points A and B. Reduces the frequency by Hz per 0.5 seconds when Point B is exceeded. Stops operation, and restarts it appoximately 5 minutes later, if Point C is exceeded. (May operate when sudden voltage fluctuations occur. Indicates trouble.) < CU-KS30NKUA > Current Value on the Point C Current Value on the Point B Current Value on the Point A < CU-KS36NKUA > Current Value on the Point C Current Value on the Point B Current Value on the Point A In cooling operation (25.0) In cooling operation (25.0) <Maximum Current Value Change Procedure> () Remove the inspection panel. Refer to Fig. 2 in " Noise Reducing Control" for details. (2) When the switch No.2 of the dip switch (SW0) on the control P.C.Board is turned ON, the maximum current value change. (Fig. 4) Power lamp Dip Switch (SW0) Switch No.2 ON OFF Max. Current Value CU-KS30NKUA CU-KS36NKUA 4.0A 7.0A 22.0A 24.0A ON 2 Dip switch (SW0) SW0 Fig.4 Control P.C.Board 34

35 7-2. Protective Functions Freeze prevention During COOL or DRY operation, freezing is detected and operation is stopped when the temperature of the indoor heat exchanger matches the conditions below.. Freeze-prevention operation is engaged when the temperature of the indoor heat exchanger is below 4 F(5 C). 2. Restart after freeze-prevention operation occurs when the temperature of the indoor heat exchanger reaches 46 F(8 C) or above. Indoor heat exchanger temperature F( C) 46 (8) 4 (5) 36 (2) * A a b c d a. Area: Automatic capacity control b. When the temperature drops below Point A, the operation frequency is reduced by a certain proportion. c. Area: Frequency increase is prohibited. d. When the temperature reaches Point C or above, freezing prevention is ended and control is the same as in the a area. * When the temperature drops to below 36 F(2 C) (continuously for 2 minutes or longer), the compressor stops. Once the freeze condition is detected, the air conditioner will work less than the maximum frequency until it is turned off. B C Compressor discharge temperature control This function controls the operation frequency to prevent the compressor discharge temperature from rising more than a specified temperature. Compressor discharge temperature F( C) Approx. 24 (0) Approx. 20 (94) A a b c d a. Area: Automatic capacity control. b. When the temperature rises above Point A, the operation frequency is reduced at a specified rate. c. Area: Further frequency increase is prohibited. d. When the temperature falls below Point B, prevention of a rise in frequency is released and the air conditioner operates as in a area. * The compressor will stop if the temperature of the compressor discharge exceeds 248 F(20 C) due to shortage of gas or other reason. CT (Peak current cut-off control) This function prevents the circuit breaker or fuse from operating to open the circuit. This function works when electrical current has increased due to an increase in the cooling load, or to a decrease in the power supply voltage. In these cases, operation frequency is reduced or operation is interrupted automatically to control the electrical current for operation. When the cause of the increase in electrical current is rectified, the system will resume operation in the original mode. < CS-KS30NKU > (A) Cooling Dry Peak current cut-off trips 25.0 Hz down 22.0 B < CS-KS36NKU> Cooling Dry Peak current cut-off trips 25.0 Hz down 24.0 (A) 35

36 8. TROUBLESHOOTING (BEFORE CALLING FOR SERVICE) 8-. Precautions before Performing Inspection or Repair After checking the self-diagnostics monitor, turn the power OFF before starting inspection or repair. High-capacity electrolytic capacitors are used inside the outdoor unit controller (inverter). They retain an electrical charge (charging voltage DC 30V) even after the power is turned OFF, and some time is required for the charge to dissipate. Be careful not to touch any electrified parts before the controller LED (red) turns OFF. If the outdoor controller is normal, approximately 30 seconds will be required for the charge to dissipate. However, allow at least 5 minutes for the charge to dissipate if there is thought to be any trouble with the outdoor controller Method of Self-Diagnostics Follow the procedure below to perform detailed trouble diagnostics. NOTE < Clock display > Test run mode Deletion of self-diagnostics report mode Self-diagnostics mode : If the operation lamp blinks every 0.5 seconds immediately when the power is turned ON, there is an external ROM (OTP data) failure on the indoor circuit board, or a ROM socket insertion problem, or the ROM has not been installed. 2: The failure mode is stored in memory even when the power is not ON. Follow the procedure below to perform diagnostics. PROCEDURE After turning on power to the air conditioner, use the remote controller and follow the steps below to execute self-diagnostics. Step : Press and hold the remote controller QUIET button and HR TIMER button. Then, press and hold the ACL (reset) button with a pointed object such as the tip of a pen. After 5 seconds, release ACL button first, then release QUIET and HR TIMER buttons, "op-" (test run) appears, blinking in the remote controller clock display area. Step 2: Next, press the HR TIMER button twice to change the display from "op-" to "op-2" and "op-3" (self-diagnostics). (The display continues to blink.) Step 3: Finally press the ON/OFF button to engage self-diagnostics mode. The self-diagnostics function utilizes the 3 indicator lamps on the main unit, in combinations of ON lamps, blinking lamps, and OFF lamps, to report the existence of sensor trouble or a protective operation. (The lamps blink or remain ON for 5 seconds, then turn OFF for 2 seconds.) Self-diagnostics is completed when the buzzer sounds 3 short beeps. A maximum of 3 self-diagnostics reports are displayed, for 5 seconds each, beginning with the most recent report. Following this display the lamps turn OFF. In order to view the self-diagnostics results again, press the ON/OFF button again. The 3 lamps remain OFF if no trouble has occurred. <IMPORTANT> After self-diagnostics is completed, be sure to press the ACL (reset) button to return to normal mode. The air conditioner will not operate if this is not done. QUIET button ON/OFF operation button HR. TIMER button ACL (Reset) button 36

DC INVERTER SPLIT SYSTEM AIR CONDITIONER

DC INVERTER SPLIT SYSTEM AIR CONDITIONER TECHNICAL & SERVICE MANUAL CSKE1NB41 & CZ18BT1U + CUKE1NK1 CSKE18NB4UW & CZ18BT1U + CUKE18NKU DC INVERTER SPLIT SYSTEM AIR CONDITIONER Indoor Model No. Body (Panel) CSKE1NB41 (CZ18BT1U) CSKE18NB4UW (CZ18BT1U)

More information

DC INVERTER SPLIT SYSTEM AIR CONDITIONER

DC INVERTER SPLIT SYSTEM AIR CONDITIONER TECHNICAL & SERVICE MANUAL CSKS12NB41 & CZ18BT1U + CUKS12NK1A CSKS18NB4UW & CZ18BT1U + CUKS18NKU CSKS18NB4UW & CZ18BT1U + CUKS18NKUA DC INVERTER SPLIT SYSTEM AIR CONDITIONER Indoor Model No. Body (Panel)

More information

DC INVERTER MULTI-SYSTEM AIR CONDITIONER

DC INVERTER MULTI-SYSTEM AIR CONDITIONER AIR CONDITIONER AIR CONDITIONER TECHNICAL & SERVICE MANUAL INDOOR UNIT : CS-MKE7NKU CS-MKE9NKU CS-MKE12NKU CS-MKE18NKU CS-MKE24NKU DC INVERTER MULTI-SYSTEM AIR CONDITIONER Capacity 7,500BTU / h 9,000BTU

More information

DC INVERTER MULTI-SYSTEM AIR CONDITIONER

DC INVERTER MULTI-SYSTEM AIR CONDITIONER TECHNICAL & SERVICE MANUAL OUTDOOR UNIT : CM97 CM7 CM7 FILE NO. Destination: North America DC INVERTER MULTI-SYSTEM AIR CONDITIONER Capacity at 0V 9,700 BTU/h,00 BTU/h 0,600 BTU/h Outdoor Model No. CM97

More information

DC INVERTER MULTI-SYSTEM AIR CONDITIONER

DC INVERTER MULTI-SYSTEM AIR CONDITIONER TECHNICAL & SERVICE MANUAL OUTDOOR UNIT : AEMI0AH AEMIAHB AEMIAH AEMI0AH FILE NO. Destination: Europe DC INVERTER MULTI-SYSTEM AIR CONDITIONER Capacity.0k.k.k.0k Outdoor Model No. AEMI0AH AEMIAHB AEMIAH

More information

DC INVERTER SPLIT SYSTEM AIR CONDITIONER

DC INVERTER SPLIT SYSTEM AIR CONDITIONER TECHNICAL & SERVICE MANUAL CSKS1NB41 & CZ18BT1U + CUKS1NK1A CSKS18NB4UW & CZ18BT1U + CUKS18NKU CSKS18NB4UW & CZ18BT1U + CUKS18NKUA DC INVERTER SPLIT SYSTEM AIR CONDITIONER Indoor Model No. Body (Panel)

More information

TECHNICAL & SERVICE MANUAL SPLIT SYSTEM AIR CONDITIONER + SAP C181MA + SAP C181GA + SAP C181BA + SAP C241MA + SAP C241BA FILE NO.

TECHNICAL & SERVICE MANUAL SPLIT SYSTEM AIR CONDITIONER + SAP C181MA + SAP C181GA + SAP C181BA + SAP C241MA + SAP C241BA FILE NO. TECHNICAL & SERVICE MANUAL SAP K161GJA SAP K181GJA SAP K181MBA SAP K241GJA SAP K241MBA + SAP C161GA + SAP C161JA + SAP C181GA + SAP C181JA + SAP C181MA + SAP C181BA + SAP C241GA + SAP C241JA + SAP C241MA

More information

TECHNICAL DATA & SERVICE MANUAL SPLIT SYSTEM AIR CONDITIONER INDOOR UNIT: AW52AL AW64AL AW52AL 387030095 AW64AL 0.8180.463.0 07/05

TECHNICAL DATA & SERVICE MANUAL SPLIT SYSTEM AIR CONDITIONER INDOOR UNIT: AW52AL AW64AL AW52AL 387030095 AW64AL 0.8180.463.0 07/05 TECHNICAL DATA & SERVICE MANUAL INDOOR UNIT: AW52AL AW64AL SPLIT SYSTEM AIR CONDITIONER Model No. Product Code No. AW52AL 387030095 AW64AL 387030096 0.8180.463.0 07/05 IMPORTANT! Please read before installation

More information

DC INVERTER SPLIT SYSTEM AIR CONDITIONER

DC INVERTER SPLIT SYSTEM AIR CONDITIONER AIR CONDITIONER TECHNICAL & SERVICE MANUAL SAP-KRV96EHDS + SAP-CRV96EHDS SAP-KRV126EHDS + SAP-CRV126EHDS FILE NO. Destination: Europe DC INVERTER SPLIT SYSTEM AIR CONDITIONER Indoor Model No. SAP-KRV96EHDS

More information

SERVICE MANUAL SPLIT SYSTEM ROOM AIR CONDITIONER SHARP CORPORATION SHARP CORPORATION CONTENTS

SERVICE MANUAL SPLIT SYSTEM ROOM AIR CONDITIONER SHARP CORPORATION SHARP CORPORATION CONTENTS SERVICE MANUAL SPLIT SYSTEM ROOM AIR CONDITIONER INDOOR UNIT AH-129 AH-MP14 OUTDOOR UNIT AU-129 AU-MP14 CONTENTS SPECIFICATIONS...2 EXTERNAL DIMENSIONS...4 WIRING DIAGRAMS...5 ELECTRICAL PARTS...6 MICROCOMPUTER

More information

DC INVERTER SPLIT SYSTEM AIR CONDITIONER

DC INVERTER SPLIT SYSTEM AIR CONDITIONER TECHNICAL & SERVICE MANUAL SAP-KRV9AEH + SAP-CRV9AEH SAP-KRV12AEH + SAP-CRV12AEH FILE NO. Destination: Europe DC INVERTER SPLIT SYSTEM AIR CONDITIONER Indoor Model No. SAP-KRV9AEH SAP-KRV12AEH Product

More information

TECHNICAL & SERVICE MANUAL WINDOW TYPE AIR CONDITIONER SA 79G SA 99G FILE NO. SA 79G SA 99G REFERENCE NO. SM700402

TECHNICAL & SERVICE MANUAL WINDOW TYPE AIR CONDITIONER SA 79G SA 99G FILE NO. SA 79G SA 99G REFERENCE NO. SM700402 TECHNICAL & SERVICE MANUAL SA 79G SA 99G FILE NO. WINDOW TYPE AIR CONDITIONER Model No. Product Code No. Destination SA-79G-A 1 851 005 18 General (50Hz) & Europe SA-99G-A 1 851 005 19 SA 79G SA 99G REFERENCE

More information

SERVICE INSTRUCTION R410A. WALL MOUNTEDtype INVERTER SPLIT TYPE ROOM AIR CONDITIONER. Models Indoor unit Outdoor unit

SERVICE INSTRUCTION R410A. WALL MOUNTEDtype INVERTER SPLIT TYPE ROOM AIR CONDITIONER. Models Indoor unit Outdoor unit SERVICE INSTRUCTION SPLIT TYPE ROOM AIR CONDITIONER WALL MOUNTEDtype INVERTER Models Indoor unit Outdoor unit ASYG07LECA ASYG09LECA ASYG12LECA ASYG14LECA AOYG07LEC AOYG09LEC AOYG12LEC AOYG14LEC R410A CONTENTS

More information

14. Troubleshooting Guide

14. Troubleshooting Guide 14. Guide 14.1 Refrigeration Cycle System In order to diagnose malfunctions, ensure the air conditioner is free from electrical problems before inspecting the refrigeration cycle. Such problems include

More information

technical data air conditioning systems RXS20-25-35E (single phase) FBQ-B8V1-B8V3B Split Heat Pump Condensing Units Split Sky Air

technical data air conditioning systems RXS20-25-35E (single phase) FBQ-B8V1-B8V3B Split Heat Pump Condensing Units Split Sky Air technical data RXS20-25-35E FBQ-B8V-B8V3B (single phase) Split Heat Pump Condensing Units air conditioning systems Split Sky Air Outdoor Units R-40A RXS-E2VB Split Sky Air Outdoor Units Features O u t

More information

USER S MANUAL HSC-24A

USER S MANUAL HSC-24A AIRREX AIR CONDITIONER USER S MANUAL HSC-24A Thank you for purchasing an AIRREX AIR CONDITIONER. BEFORE operation please read this user s manual carefully. Keep this manual readily available. It is ESSENTIAL

More information

DC INVERTER SPLIT SYSTEM AIR CONDITIONER

DC INVERTER SPLIT SYSTEM AIR CONDITIONER AIR CONDITIONER TECHNICAL & SERVICE MANUAL SAP-KRV96EH + SAP-CRV96EH SAP-KRV126EH + SAP-CRV126EH FILE NO. Destination: Europe DC INVERTER SPLIT SYSTEM AIR CONDITIONER Indoor Model No. SAP-KRV96EH SAP-KRV126EH

More information

Si10-417_C. Pocket Manual. Service Diagnosis SPLIT & MULTI

Si10-417_C. Pocket Manual. Service Diagnosis SPLIT & MULTI Pocket Manual Service Diagnosis SPLIT & MULTI Service Diagnosis SPLIT & MULTI 1. Troubleshooting with LED...5 1.1 Indoor Unit... 5 1.2 Outdoor Unit... 10 2. Troubleshooting by Symptoms...11 2.1 Air conditioner

More information

SERVICE MANUAL OUTDOOR UNIT. No. OBH590 REVISED EDITION-B. Models HFC

SERVICE MANUAL OUTDOOR UNIT. No. OBH590 REVISED EDITION-B. Models HFC SPLIT-TYPE AIR CONDITIONERS Revision B: MUZ-EF25/35/42/50VE - E2 and MUZ-EF25/35VEH - E2 have been added. Please void OBH590 REVISED EDITION-A. OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OBH590 REVISED

More information

SERVICE INSTRUCTION R410A. WALL MOUNTEDtype SPLIT TYPE ROOM AIR CONDITIONER INVERTER. Models Indoor unit Outdoor unit AOU 9RLFW AOU12RLFW AOU15RLS

SERVICE INSTRUCTION R410A. WALL MOUNTEDtype SPLIT TYPE ROOM AIR CONDITIONER INVERTER. Models Indoor unit Outdoor unit AOU 9RLFW AOU12RLFW AOU15RLS SERVICE INSTRUCTION SPLIT TYPE ROOM AIR CONDITIONER WALL MOUNTEDtype INVERTER Models Indoor unit Outdoor unit ASU 9RLF ASURLF ASU5RLS AOU 9RLFW AOURLFW AOU5RLS R40A CONTENTS. DESCRIPTION OF EACH CONTROL

More information

New Deluxe Wall Mounted Heat Pump Series EXTERIOS

New Deluxe Wall Mounted Heat Pump Series EXTERIOS New Deluxe Wall Mounted Heat Pump Series EXTERIOS May 2013 New Deluxe Wall Mounted Heat Pump Series Panasonic Adding New Air Conditioner Lineup Setting Another Mile Stone in the US Ductless Split History

More information

Service manual. Website: www.andico.com.au CAUTION - BEFORE SERVICING THE UNIT, READ THE SAFETY - PRECAUTIONS IN THIS MANUAL.

Service manual. Website: www.andico.com.au CAUTION - BEFORE SERVICING THE UNIT, READ THE SAFETY - PRECAUTIONS IN THIS MANUAL. Website: www.andico.com.au Service manual CAUTION - BEFORE SERVICING THE UNIT, READ THE SAFETY - PRECAUTIONS IN THIS MANUAL. - ONLY FOR AUTHORISED SERVICE PERSONNEL. MODELS: MPK1-09CR-QB8 MPK1-12ER-QB6

More information

DC INVERTER SPLIT SYSTEM AIR CONDITIONER

DC INVERTER SPLIT SYSTEM AIR CONDITIONER AIR CONDITIONER TECHNICAL & SERVICE MANUAL SAP-KRV93EH + SAP-CRV93EH SAP-KRV123EH + SAP-CRV123EH FILE NO. Destination: Europe DC INVERTER SPLIT SYSTEM AIR CONDITIONER Indoor Model No. Product Code No.

More information

SiUS041111. Service Manual. Inverter Pair Wall Mounted Type K-Series. [Applied Models] Inverter Pair : Cooling Only Inverter Pair : Heat Pump

SiUS041111. Service Manual. Inverter Pair Wall Mounted Type K-Series. [Applied Models] Inverter Pair : Cooling Only Inverter Pair : Heat Pump Service Manual Inverter Pair Wall Mounted Type K-Series [Applied Models] Inverter Pair : Cooling Only Inverter Pair : Heat Pump Inverter Pair Wall Mounted Type K-Series Cooling Only Indoor Unit FTXN09KEVJU

More information

SERVICE INSTRUCTION R410A. SPLIT TYPE ROOM AIR CONDITIONER Universal Floor / Ceiling Duct / Cassette Wall Mounted / Floor type INVERTER MULTI

SERVICE INSTRUCTION R410A. SPLIT TYPE ROOM AIR CONDITIONER Universal Floor / Ceiling Duct / Cassette Wall Mounted / Floor type INVERTER MULTI SERVICE INSTRUCTION SPLIT TYPE ROOM AIR CONDITIONER Universal Floor / Ceiling Duct / Cassette Wall Mounted / Floor type INVERTER MULTI R410A Models Indoor unit Outdoor unit AB*14LBAJ AB*18LBAJ AB*F14LAT

More information

HP switch LP switch Discharge thermo Comp. Surface thermo

HP switch LP switch Discharge thermo Comp. Surface thermo 1 Specifications Zubadan Model Name PUHZ-SHW80VHA PUHZ-SHW11VHA PUHZ-SHW11YHA Power supply (phase, cycle, voltage) 1φ, V, Hz 1φ, V, Hz 3φ, 0V, Hz Max. current A 9.5 35.0 13.0 Breaker size A 3 16 Outer

More information

SERVICE MANUAL MUZ-GE09NA MUZ-GE12NA MUZ-GE15NA MUZ-GE18NA MUZ-GE24NA MUY-GE09NA MUY-GE12NA MUY-GE15NA MUY-GE18NA MUY-GE24NA OUTDOOR UNIT

SERVICE MANUAL MUZ-GE09NA MUZ-GE12NA MUZ-GE15NA MUZ-GE18NA MUZ-GE24NA MUY-GE09NA MUY-GE12NA MUY-GE15NA MUY-GE18NA MUY-GE24NA OUTDOOR UNIT SPLIT-TYPE AIR CONDITIONERS Revision B: Descriptions regarding the outdoor fan motor have been corrected. Please void OBH549 REVISED EDITION-A. OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OBH549 REVISED

More information

york air-conditioning products Residential & VRF News 2015

york air-conditioning products Residential & VRF News 2015 york air-conditioning products Residential & VRF News 2015 york air-conditioning products Catalogue Content Split Systems Pag. High wall High Efficiency Inverter YWHJZH 09 to 24 K 6 High wall Inverter

More information

AIR CONDITIONER INSTALLATION MANUAL

AIR CONDITIONER INSTALLATION MANUAL INSTALLATION MANUAL AIR CONDITIONER Please read this installation manual completely before installing the product. Installation work must be performed in accordance with the national wiring standards by

More information

CONTENTS 1. IMPORTANT NOTICE 2 2. TECHNICAL SPECIFICATION 3 3. OPERATION DETAILS 4 4. ELECTRICAL SCHEMATIC DIAGRAM 13 5. EXPLOSION VIEW 16 6

CONTENTS 1. IMPORTANT NOTICE 2 2. TECHNICAL SPECIFICATION 3 3. OPERATION DETAILS 4 4. ELECTRICAL SCHEMATIC DIAGRAM 13 5. EXPLOSION VIEW 16 6 TCL WALL MOUNTED SPLIT-TYPE AIR CONDITIONERS SERVICE MANUAL No.TE080528 Models KFTHP-12 KFTHP-18 KFTHP-24 CONTENTS 1. IMPORTANT NOTICE 2 2. TECHNICAL SPECIFICATION 3 3. OPERATION DETAILS 4 4. ELECTRICAL

More information

SERVICE MANUAL MUZ-FE09NA MUZ-FE12NA MUZ-FE18NA OUTDOOR UNIT. No. OBH543 REVISED EDITION-A. Models HFC

SERVICE MANUAL MUZ-FE09NA MUZ-FE12NA MUZ-FE18NA OUTDOOR UNIT. No. OBH543 REVISED EDITION-A. Models HFC SPLIT-TYPE AIR CONDITIONERS Revision A: MUZ-FE18NA has been added. Please void OBH543. OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OBH543 REVISED EDITION-A Models MUZ-FE09NA MUZ-FE12NA MUZ-FE18NA Indoor

More information

SERVICE MANUAL. Room Air Conditioner Multi Split Wall-Mounted Type Indoor. FSAI-Pro-91AE2 FSAI-Pro-121AE2 FSAIF-Pro-181AE2

SERVICE MANUAL. Room Air Conditioner Multi Split Wall-Mounted Type Indoor. FSAI-Pro-91AE2 FSAI-Pro-121AE2 FSAIF-Pro-181AE2 SERVICE MANUAL Room Air Conditioner Multi Split Wall-Mounted Type Indoor FSAI-Pro-91AE2 FSAI-Pro-121AE2 FSAIF-Pro-181AE2 NOTE: Before servicing the unit, please read this at first. Always contact with

More information

Air Conditioners Technical Data

Air Conditioners Technical Data Air Conditioners Technical Data O u t d o o r U n i t E E D E N 2-0 0 RX-JV Outdoor Unit RX-JV TABLE OF CONTENTS RX-JV Features............................................................. 2 2 Specifications.......................................................

More information

AIR-CONDITIONER SPLIT TYPE

AIR-CONDITIONER SPLIT TYPE FILE NO. A08-016 SERVICE MANUAL AIR-CONDITIONER SPLIT TYPE RAS-M10PKVP-E, RAS-M13PKVP-E, RAS-M16PKVP-E, RAS-M18PKVP-E / RAS-M10PKVP-ND, RAS-M13PKVP-ND, RAS-M16PKVP-ND, RAS-M18PKVP-ND / RAS-3M26GAV-E1,

More information

CONTENTS 1. IMPORTANT NOTICE 2 2. TECHNICAL SPECIFICATION 3 3. OPERATION DETAILS 4 4. WIRING DIAGRAM 11 5. EXPLOSION VIEW 12 6.

CONTENTS 1. IMPORTANT NOTICE 2 2. TECHNICAL SPECIFICATION 3 3. OPERATION DETAILS 4 4. WIRING DIAGRAM 11 5. EXPLOSION VIEW 12 6. TCL WALL MOUNTED SPLIT-TYPE AIR CONDITIONERS SERVICE MANUAL No.TE051220 Models TAC-09CHSA/GI TAC-12CHSA/GI CONTENTS 1. IMPORTANT NOTICE 2 2. TECHNICAL SPECIFICATION 3 3. OPERATION DETAILS 4 4. WIRING DIAGRAM

More information

SERVICE MANUAL MUZ-GE25VA - E1 MUZ-GE25VAH - E1 MUZ-GE35VA - E1 MUZ-GE35VAH - E1 MUZ-GE42VA - E1 MUZ-GE42VAH - E1 MUZ-GE50VA - E1 MUZ-GE50VAH - E1

SERVICE MANUAL MUZ-GE25VA - E1 MUZ-GE25VAH - E1 MUZ-GE35VA - E1 MUZ-GE35VAH - E1 MUZ-GE42VA - E1 MUZ-GE42VAH - E1 MUZ-GE50VA - E1 MUZ-GE50VAH - E1 SPLIT-TYPE AIR CONDITIONERS Revision A: MUZ-GE42/50VA(H) - E1 has been added. Please void OBH516. OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OBH516 REVISED EDITION-A Models MUZ-GE25VA - E1 MUZ-GE25VAH

More information

LG Air Conditioning - Universal Split Fault Codes Sheet. Universal Split Systems

LG Air Conditioning - Universal Split Fault Codes Sheet. Universal Split Systems Universal Split Systems If there is a fault on any LG Universal unit, a two digit number will appear on the remote controllers led display. If the unit does not have a remote controller the fault will

More information

Indoor coil is too warm in cooling mode or too cold in heating mode. Reversing valve or coil thermistor is faulty

Indoor coil is too warm in cooling mode or too cold in heating mode. Reversing valve or coil thermistor is faulty Codes Room Air Conditioner range: Indoor unit alarm s If timer lamp flashes for 1 second on, 1 second off, this indicates pre heating on the coil during heating mode and is not an error. If timer lamp

More information

SiUS091133. Service Manual. Inverter Pair FTXS-L Series FDXS-L Series. [Applied Models] Inverter Pair : Cooling Only Inverter Pair : Heat Pump

SiUS091133. Service Manual. Inverter Pair FTXS-L Series FDXS-L Series. [Applied Models] Inverter Pair : Cooling Only Inverter Pair : Heat Pump Service Manual Inverter Pair FTXS-L Series FDXS-L Series [Applied Models] Inverter Pair : Cooling Only Inverter Pair : Heat Pump Inverter Pair FTXS-L Series FDXS-L Series Cooling Only Indoor Unit FTXS30LVJU

More information

Portable Air Conditioner

Portable Air Conditioner Portable Air Conditioner Owner's Manual Model:3 in 1 12,000 Btu/h Series 3 Please read this owner s manual carefully before operation and retain it for future reference. CONTENTS 1. SUMMARY...1 2. PORTABLE

More information

SERVICE MANUAL. Room Air Conditioner Multi Split type Outdoor unit /R410A DC Inverter/

SERVICE MANUAL. Room Air Conditioner Multi Split type Outdoor unit /R410A DC Inverter/ SERVICE MANUAL Room Air Conditioner Multi Split type Outdoor unit /R410A DC Inverter/ FS2MI-147HFD FS2MI-187HFD FS3MI-217HFD FS3MI-277HFD FS4MI-277HFD FS4MI-367HFD FS5MI-367HFD NOTE: Before servicing the

More information

SiBE12-625. D-Series / E-Series. [Applied Models] Inverter Multi : Cooling Only Inverter Multi : Heat Pump

SiBE12-625. D-Series / E-Series. [Applied Models] Inverter Multi : Cooling Only Inverter Multi : Heat Pump SiBE12-625 D-Series / E-Series [Applied Models] Inverter Multi : Cooling Only Inverter Multi : Heat Pump SUPER MULTI NX D-Series / E-Series Cooling Only Indoor Unit FTKS20D3VMW FTKS20CAVMB FDKS25CAVMB

More information

Operating Instructions Split System Air Conditioner

Operating Instructions Split System Air Conditioner Operating Instructions Split System Air Conditioner Model No. Indoor Unit Type Indoor Unit Type Nominal Capacity 26 36 F2 Low Silhouette Ducted S-26PF2U6 S-36PF2U6 Connectable outdoor unit lineup This

More information

PANASONIC TROUBLE SHOOTING GUIDE

PANASONIC TROUBLE SHOOTING GUIDE A General Guide To Room Style Products Pipework Pipe sizes and lengths should be as the relevant Technical Guide Both lines should be insulated No line accessories or oil traps should be fitted In cooling

More information

DC INVERTER MULTI-SYSTEM AIR CONDITIONER

DC INVERTER MULTI-SYSTEM AIR CONDITIONER TECHNICAL & SERVICE MANUAL OUTDOOR UNIT : SAP-CMRVEH SAP-CMRV9EH SAP-CMRV9EH SAP-CMRVEH SAP-CMRVEH FILE NO. Destination: Europe Northern Europe DC INVERTER MULTI-SYSTEM AIR CONDITIONER Capacity.0k.6k.6k

More information

OPTIONAL SLENDER REMOTE CONTROL

OPTIONAL SLENDER REMOTE CONTROL DAIKIN ROOM AIR CONDITIONER Operation Manual OPTIONAL SLENDER REMOTE CONTROL BRC944A2B READ BEFORE OPERATION Safety Precautions...2 Names of Functions of Parts...4 Preparation before Operation...5 OPERATION

More information

How To Use A Power Supply Unit (Upu)

How To Use A Power Supply Unit (Upu) BRAVER UPS (Uninterruptible Power System) User s Manual Safety CAUTION! This UPS utilizes voltages that may be hazardous. Do not attempt to disassemble the unit. The unit contains no user replaceable parts.

More information

Failure code manual. content

Failure code manual. content Failure code manual content 一 wall split AC series 2 二 floor standing AC series. 4 三 portable AC series.. 5 四 dehumidifer 6 五 DC inverter single split series...7 六 DC inverter multi-split series 10 1 一

More information

SERVICE MANUAL OUTDOOR UNIT MUZ-A09NA,- 1,- U1,- U2 MUZ-A12NA,- U1 MUZ-A15NA,- U1 MUZ-A17NA,- U1 MUY-A15NA MUY-A17NA MUY-A24NA,- 1,- U1,- U2

SERVICE MANUAL OUTDOOR UNIT MUZ-A09NA,- 1,- U1,- U2 MUZ-A12NA,- U1 MUZ-A15NA,- U1 MUZ-A17NA,- U1 MUY-A15NA MUY-A17NA MUY-A24NA,- 1,- U1,- U2 SPLIT-TYPE AIR CONDITIONERS Revision E: MUZ-GA24NA and MUY-GA24NA have been added. Please void OB451 REVISED EDITION-D. OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OB451 REVISED EDITION-E Models MUZ-A09NA,-

More information

Air Conditioner Water Heater - A Product of HotSpot Energy LLC

Air Conditioner Water Heater - A Product of HotSpot Energy LLC Air Conditioner Water Heater - A Product of HotSpot Energy LLC PLEASE READ THIS BEFORE YOU INSTALL THE UNIT 1. This air conditioner must be installed and/or repaired by a qualified technician. If you perform

More information

NewAir AC-10100E / AC-10100H Portable Air Conditioner Owner s Manual PLEASE READ AND SAVE THESE INSTRUCTIONS

NewAir AC-10100E / AC-10100H Portable Air Conditioner Owner s Manual PLEASE READ AND SAVE THESE INSTRUCTIONS NewAir AC-10100E / AC-10100H Portable Air Conditioner Owner s Manual PLEASE READ AND SAVE THESE INSTRUCTIONS ELECTRICAL SAFETY This appliance is for indoor use only. Always turn off the unit and unplug

More information

SERVICE MANUAL FOR 6535 SERIES TWO TON HIGH EFFICIENCY PACKAGED HEAT PUMPS

SERVICE MANUAL FOR 6535 SERIES TWO TON HIGH EFFICIENCY PACKAGED HEAT PUMPS SERVICE MANUAL FOR 6535 SERIES TWO TON HIGH EFFICIENCY PACKAGED HEAT PUMPS TABLE OF CONTENTS 1. Warnings...2 2. Accessibility Of Appliance...3 3. Unit Dimensions And Specifications...3 4. Unit Specifications

More information

Technical service manual 2009

Technical service manual 2009 MULTI SPLIT TYPE, HEAT PUMP AIR CONDITIONERS Technical service manual 2009 KSIM MULTI ZONE SERIES R410A DC Inverter multi Series Models KSIM20912-H216 KSIM30912-H216 KSIM40912-H216 CONTENT 1. Product features

More information

Appendix - Controllers 179

Appendix - Controllers 179 Version: 200703 Appendix - Controllers 179 -3- -4- -5- -6- -7- -8- 2. Specifications 2.1 Specifications for inverter units item Model AB182ACERA Function cooling heating Capacity kw 5.01.8--5.8 5.22.0---6.2

More information

LG Air Conditioning Multi F(DX) Fault Codes Sheet. Multi Split Units

LG Air Conditioning Multi F(DX) Fault Codes Sheet. Multi Split Units Multi Split Units If there is a fault on any LG Multi unit, an Error mark is indicated on the display window of the indoor unit, wired-remote controller, and LED s of outdoor unit control board. A two

More information

Split-type Air-Conditioner INSTALLATION MANUAL CONTENTS FOR INSTALLER MXZ-3A30NA MXZ-4A36NA ATTENTION. English. Français. Español

Split-type Air-Conditioner INSTALLATION MANUAL CONTENTS FOR INSTALLER MXZ-3A30NA MXZ-4A36NA ATTENTION. English. Français. Español Split-type Air-Conditioner MXZ-3A30NA MXZ-4A36NA INSTALLATION MANUAL Refer to the installation manual of each indoor unit for indoor unit installation. English Français Español ATTENTION This manual mentions

More information

CS-XE9EKE CU-XE9EKE CS-XE12EKE CU-XE12EKE

CS-XE9EKE CU-XE9EKE CS-XE12EKE CU-XE12EKE Order No. MAC0512111C8 Air Conditioner CS-XE9EKE CU-XE9EKE CS-XE12EKE CU-XE12EKE TABLE OF CONTENTS PAGE 1 Safety Precautions----------------------------------------------- 3 2 Specifications -----------------------------------------------------

More information

Instruction manual for Firstline FCS12000CH

Instruction manual for Firstline FCS12000CH Instruction manual for Firstline FCS12000CH Contents Introduction... 2 Safety Awareness... 3 Safety Awareness... 4 Name of Parts... 5 Name of Parts... 6 Remote Controller Preparation... 7 Operation of

More information

How To Power A Car With A Fan And A Fan (Power)

How To Power A Car With A Fan And A Fan (Power) SPLIT TYPE ROO AIR CONDITIONER CEILING WALL TYPE INVERTER Indoor unit AWYZLBC AWYZLBC AWYZLBC AWYZLBC Outdoor unit AOYZLBC AOYZLBL AOYZLBC AOYZLBL CONTENTS SPECIFICATIONS................... OUTLINE AND

More information

User s Manual AURORA 1.2K/2.2K

User s Manual AURORA 1.2K/2.2K User s Manual AURORA 1.2K/2.2K Uninterruptible Power System Safety CAUTION This UPS utilizes voltages that may be hazardous. Do not attempt to disassemble the unit. The unit contains no user serviceable

More information

Model: AC-S13CG x 2. Model No: AC-S13CGx2.doc Version 1.0

Model: AC-S13CG x 2. Model No: AC-S13CGx2.doc Version 1.0 Air Conditioner Service Manual 2 3 Model: AC-S13CG x 2 3 Content Technical specification.. 4 Performance curve.5 Outline & dimension of indoor unit..10 Outline & dimension of outdoor unit 11 Exploded view

More information

CU-2E15LBE CU-2E18LBE CU-3E18LBE CU-4E23LBE

CU-2E15LBE CU-2E18LBE CU-3E18LBE CU-4E23LBE Order No. PHAAM1003090C3 Outdoor Unit CU-2E15LBE CU-2E18LBE CU-3E18LBE CU-4E23LBE Air Conditioner Please file and use this manual together with the service manual for Model No. CS-E7LKEW CU-E7LKE CS-E7LKEW

More information

OWNER S MANUAL VMH 09/12/18/27/36 InverterFlex

OWNER S MANUAL VMH 09/12/18/27/36 InverterFlex OWNER S MANUAL VMH 09/12/18/27/36 InverterFlex Version C Single, Dual, Tri or Quad Zone Ductless Mini-Split System Heat Controller, Inc. 1900 Wellworth Ave. Jackson, MI 49203 (517)787-2100 www.heatcontroller.com

More information

REGULINE 600VA / 1000VA REGULATOR USER MANUAL

REGULINE 600VA / 1000VA REGULATOR USER MANUAL REGULINE 600VA / 1000VA REGULATOR USER MANUAL TUNÇMATİK REGULINE SERIES AUTOMATIC VOLTAGE REGULATOR Models: REGULINE 600VA / REGULINE 1000VA Principle of Operation Automatic Voltage Regulators regulate

More information

Operating Instructions Air Conditioner

Operating Instructions Air Conditioner F566272 Operating Instructions Air Conditioner CS-C18FFH CS-C28FFH CU-C18FFH CU-C28FFH ENGLISH Before operating the unit, read these operating instructions thoroughly and keep them for future reference.

More information

DESIGN & TECHNICAL MANUAL

DESIGN & TECHNICAL MANUAL AIR CONDITIONER Wall Mounted type DESIGN & TECHNICAL MANUAL INDOOR AS G07LECA AS G09LECA AS G12LECA AS G14LECA OUTDOOR AO G07LEC AO G09LEC AO G12LEC AO G14LEC 1. INDOOR UNIT : AS G07LECA AS G09LECA AS

More information

DC INVERTER (WALL TYPE) INDOOR UNIT OUTDOOR UNIT INDOOR UNIT OUTDOOR UNIT RAS-18FH6 RAC-18YH6. 1 PHASE, 50 Hz, 220-230V

DC INVERTER (WALL TYPE) INDOOR UNIT OUTDOOR UNIT INDOOR UNIT OUTDOOR UNIT RAS-18FH6 RAC-18YH6. 1 PHASE, 50 Hz, 220-230V SERVICE MANUAL TECHNICAL INFORMATION AW NO. 0024E RAS-18FH6 RAC-18YH6 RAS-25FH6 RAC-25YH6 REFER TO THE FOUNDATION MANUAL FOR SERVICE PERSONNEL ONLY CONTENTS SPECIFICATIONS -------------------------------------------------------------------

More information

USER INSTRUCTIONS FOR GET PORTABLE 12k BTU AIR CONDITIONER MODEL No. GPACU12HR

USER INSTRUCTIONS FOR GET PORTABLE 12k BTU AIR CONDITIONER MODEL No. GPACU12HR USER INSTRUCTIONS FOR GET PORTABLE 12k BTU AIR CONDITIONER MODEL No. GPACU12HR CONTENTS Introduction Safety Notes Identification of parts Installation instructions Operation instructions Maintenance Troubleshooting

More information

Split Type Room Air Conditioner. KSWM units

Split Type Room Air Conditioner. KSWM units OWNER S MANUAL Split Type Room Air Conditioner KSWM units Please read the operating instructions and safety precautions carefully and thoroughly before installing and operating your room air conditioner.

More information

Daker DK 1, 2, 3 kva. Manuel d installation Installation manual. Part. LE05334AC-07/13-01 GF

Daker DK 1, 2, 3 kva. Manuel d installation Installation manual. Part. LE05334AC-07/13-01 GF Daker DK 1, 2, 3 kva Manuel d installation Installation manual Part. LE05334AC-07/13-01 GF Daker DK 1, 2, 3 kva Index 1 Introduction 24 2 Conditions of use 24 3 LCD Panel 25 4 Installation 28 5 UPS communicator

More information

CS-CE9NKE CS-CE12NKE CU-CE9NKE CU-CE12NKE TABLE OF CONTENTS WARNING

CS-CE9NKE CS-CE12NKE CU-CE9NKE CU-CE12NKE TABLE OF CONTENTS WARNING Order No: PAPAMY1207094CE Indoor Unit CS-CE9NKE CS-CE12NKE Outdoor Unit CU-CE9NKE CU-CE12NKE WARNING This service information is designed for experienced repair technicians only and is not designed for

More information

SPLIT WALL MOUNTED TYPE AIR CONDITIONERS OWNER'S MANUAL

SPLIT WALL MOUNTED TYPE AIR CONDITIONERS OWNER'S MANUAL SPLIT WALL MOUNTED TYPE AIR CONDITIONERS OWNER'S MANUAL Thank you for choosing our Air Conditioner. Please read this OWNER'S MANUAL carefully prior to use and keep it for further reference. CONTENTS Contents

More information

USER S MANUAL FH052EAV1 FH070EAV1. System Air Conditioner (Cooling and Heating) ENGLISH ESPAÑOL FRANÇAIS ITALIANO PORTUGUÊS DEUTSCH E HNIKA

USER S MANUAL FH052EAV1 FH070EAV1. System Air Conditioner (Cooling and Heating) ENGLISH ESPAÑOL FRANÇAIS ITALIANO PORTUGUÊS DEUTSCH E HNIKA USER S MANUAL FH052EAV1 FH070EAV1 E HNIKA PORTUGUÊS ENGLISH ESPAÑOL ITALIANO DEUTSCH FRANÇAIS System Air Conditioner (Cooling and Heating) E S F I P D G DB98-29263A(1) Safety Precautions Register your

More information

Portable Air Conditioner. OWNER S MANUAL Read these instructions before use. Model: MM14CHCSCS

Portable Air Conditioner. OWNER S MANUAL Read these instructions before use. Model: MM14CHCSCS Portable Air Conditioner OWNER S MANUAL Read these instructions before use Model: MM14CHCSCS Voltage rating: 120V~60Hz Power rating : 1400W(Cooling) Power rating : 1350W(Heating) Customer Support : 1-800-474-21477

More information

CLOSE CONTROL SYSTEM. PFD series provide you with highly reliable computer room cooling system. High Reliability

CLOSE CONTROL SYSTEM. PFD series provide you with highly reliable computer room cooling system. High Reliability PFD-P250VM-E PUHY-P250YJM-A(-BS) PUHY-P500YSJM-A(-BS) PQHY-P250YHM-A CLOSE CONTROL SYSTEM MITSUBISHI ELECTRIC s Close Control System (PFD series) is specifically designed for computer rooms, laboratories

More information

Air Conditioners. Technical Data. Wall Mounted Unit. www.daikin.eu RX-JV/GV

Air Conditioners. Technical Data. Wall Mounted Unit. www.daikin.eu RX-JV/GV Air Conditioners Technical Data Wall Mounted Unit www.daikin.eu RX-JV/GV Air Conditioners Technical Data Wall Mounted Unit www.daikin.eu RX-JV/GV TABLE OF CONTENTS RX-JV/GV 1 Features.............................................................

More information

SERVICE MANUAL INDOOR UNIT

SERVICE MANUAL INDOOR UNIT SPLIT-TYPE AIR CONDITIONERS Revision B: "How to check miswiring and serial signal error" for MUZ type has been added. The description about "Low standby power control" has been added to "TECHNICAL CHANGES".

More information

NewAir AC-10000E, AC-10000H Portable Air Conditioner Owner s Manual PLEASE READ AND SAVE THESE INSTRUCTIONS

NewAir AC-10000E, AC-10000H Portable Air Conditioner Owner s Manual PLEASE READ AND SAVE THESE INSTRUCTIONS NewAir AC-10000E, AC-10000H Portable Air Conditioner Owner s Manual PLEASE READ AND SAVE THESE INSTRUCTIONS BEFORE USE GENERAL SAFETY INSTRUCTIONS: ALWAYS OPERATE THE UNIT IN AN UPRIGHT POSITION AND PLACE

More information

SERVICE Manual AIR CONDITIONER AWH090ZE0K. 1. Precautions. 2. Product Specifications. 3. Installation and Operating Instructions

SERVICE Manual AIR CONDITIONER AWH090ZE0K. 1. Precautions. 2. Product Specifications. 3. Installation and Operating Instructions ROOM AIR CONDITIONER AWH090ZE0K SERVICE Manual AIR CONDITIONER CONTENTS 1. Precautions 2. Product Specifications 3. Installation and Operating Instructions 4. Disassembly and Reassembly 5. Troubleshooting

More information

SERVICE MANUAL INDOOR UNIT

SERVICE MANUAL INDOOR UNIT SPLIT-TYPE AIR CONDITIONERS Revision E: MSZ-GE22VAD- A1 has been added. Please void OBH531 REVISED EDITION-D. INDOOR UNIT SERVICE MANUAL. OBH531 REVISED EDITION-E Models MSZ-GE22VA - A1 MSZ-GE50VA - A1

More information

Please read this owner s Manual carefully before operating the unit. - Cooling - Heating - Dehumidifying - Fan

Please read this owner s Manual carefully before operating the unit. - Cooling - Heating - Dehumidifying - Fan Please read this owner s Manual carefully before operating the unit. - Cooling - Heating - Dehumidifying - Fan TABLE OF CONTENTS INTRODUCTION 2 IMPORTANT SAFEGUARDS...2 PACKAGE CONTAINS..2 NAMES OF PARTS.3

More information

DUCTLESS MINI-SPLITS SINGLE & MULTI-ZONE HORIZONTAL AIR CONDITIONERS PORTABLE UNITS FREE MATCH COMPONENTS

DUCTLESS MINI-SPLITS SINGLE & MULTI-ZONE HORIZONTAL AIR CONDITIONERS PORTABLE UNITS FREE MATCH COMPONENTS DUCTLESS MINI-SPLITS SINGLE & MULTI-ZONE HORIZONTAL AIR CONDITIONERS PORTABLE UNITS FREE MATCH COMPONENTS AN EXCELLENT CHOICE IN COOLING, COMFORT AND CONVENIENCE Why choose a Mini-Split system? Installing

More information

DUCT TYPE AIR CONDITIONER

DUCT TYPE AIR CONDITIONER OPERATING MANUAL OPERATING MANUAL BEDIENUNGSANLEITUNG MODE D EMPLOI MANUAL DE FUNCIONAMIENTO MANUALE DI ISTRUZIONI ΕΓΧΕΙΡΙ ΙΟ ΛΕΙΤΟΥΡΓΙΑΣ MANUAL DE INSTRUÇÕES AIR CONDITIONER DUCT TYPE English Deutsch

More information

Use and Care Manual. Model CPA12KH AIR CONDITIONER

Use and Care Manual. Model CPA12KH AIR CONDITIONER Use and Care Manual Model CPA12KH AIR CONDITIONER Introduction Thank you for choosing this air conditioner to provide you and your family with all of the "Home Comfort" requirements for your home, cottage

More information

USER S MANUAL. MaxPower 400-600 UPS. Uninterruptible Power System 28-2MAXPO0018

USER S MANUAL. MaxPower 400-600 UPS. Uninterruptible Power System 28-2MAXPO0018 USER S MANUAL MaxPower 400-600 UPS Uninterruptible Power System 28-2MAXPO0018 IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS This manual contains important instructions for models MaxPower 400 and

More information

MAC-120HE-01 Air-Cooled Chiller

MAC-120HE-01 Air-Cooled Chiller MAC-120HE-01 Air-Cooled Chiller 10 Ton / 120,000 BTUH Air-Cooled Chiller 208/230-1-50/60 1 HVAC Guide Specifications Air-Cooled Liquid Chiller Nominal Size: 10 Tons Multiaqua Model Number: MAC-120HE-01

More information

Operating Instructions Air Conditioner

Operating Instructions Air Conditioner P07-T10130 Operating Instructions Air Conditioner Indoor Unit CS-F24DD1E5 CS-F28DD1E5 CS-F34DD1E5 CS-F43DD1E5 CS-F50DD1E5 Outdoor Unit Inverter Model (HBE5 Series) CU-YL24HBE5 CU-YL28HBE5 CU-YL34HBE5 CU-YL43HBE5

More information

Dehumidifier Users manual. For Models: DH45S DH65S

Dehumidifier Users manual. For Models: DH45S DH65S Dehumidifier Users manual For Models: DH45S DH65S 950-0062-revD Jan. 9 2007 FORWARD The appearance of the units that you purchase might be slightly different from the ones described in the Manual, but

More information

OWNER'S MANUAL R-410A Duct Free Split System Air Conditioner and Heat Pump

OWNER'S MANUAL R-410A Duct Free Split System Air Conditioner and Heat Pump R-410A Duct Free Split System Air Conditioner and Heat Pump Product Family: DFS4(A/H)-System, DFC4(A/H)3-Outdoor, DFF4(A/H)H-Indoor Please read the operating instructions and safety precautions carefully

More information

Portable Air Conditioner. OWNER S MANUAL Read these instructions before use. Model: MF08CESWW. Voltage rating: 115V~60Hz Power rating : 800W

Portable Air Conditioner. OWNER S MANUAL Read these instructions before use. Model: MF08CESWW. Voltage rating: 115V~60Hz Power rating : 800W MODE ALARM Portable Air Conditioner OWNER S MANUAL Read these instructions before use 8 Model: MF08CESWW Voltage rating: 115V~60Hz Power rating : 800W Customer Support : 1-800-474-2147 For product inquiries

More information

Portable Air Conditioner. OWNER S MANUAL Read these instructions before use. Model: MM14CCS. Voltage rating: 115V~60Hz Power rating : 1400W

Portable Air Conditioner. OWNER S MANUAL Read these instructions before use. Model: MM14CCS. Voltage rating: 115V~60Hz Power rating : 1400W Portable Air Conditioner OWNER S MANUAL Read these instructions before use Model: MM14CCS Customer Support : 1-800-474-2147 Voltage rating: 115V~60Hz Power rating : 1400W For product inquiries or support

More information

How To Measure Temperature On A Thermostat

How To Measure Temperature On A Thermostat Кондиционеры Mitsubishi Heavy Техническое руководство Кондиционеры настенного типа SRK20HD-S, SRK28HD-S, SRK40HD-S, SRK20CD-S, SRK28CD-S, SRK40CD-S CTENTS 1. GENERAL INFORMATI... 1 1.1 Specific features...

More information

R22. K Control. Indoor Unit. Nomenclature. Compatibility PL H 3 G K H B. Unit style Heat Pump Horse Power

R22. K Control. Indoor Unit. Nomenclature. Compatibility PL H 3 G K H B. Unit style Heat Pump Horse Power R22. K Control. Indoor Unit. Nomenclature. PL H 3 G K H B Compatibility Unit style Heat Pump Horse Power Control Boost Heaters R22. K Control. Outdoor Unit. Nomenclature. PU H 3 Y K A Compatibility Outdoor

More information

DESIGN & TECHNICAL MANUAL

DESIGN & TECHNICAL MANUAL AIR CONDITIONER Wall Mounted type DESIGN & TECHNICAL MANUAL INDOOR AS A09LKC AS A12LKC OUTDOOR AO R09LKC AO R12LKC 1.INDOOR UNIT : AS A09LKC AS A12LKC DTR_AS039E_01 2010.02.24 1. INDOOR UNIT CONTENTS 1.

More information

Portable Air Conditioner. OWNER S MANUAL Read these instructions before use. Model: MN12CES / MN10CESWW

Portable Air Conditioner. OWNER S MANUAL Read these instructions before use. Model: MN12CES / MN10CESWW Portable Air Conditioner OWNER S MANUAL Read these instructions before use 8 Model: MN12CES / MN10CESWW Voltage rating: 120V~60Hz Power rating : 1100W (MN12CES) Power rating : 900W (MN10CESWW) Customer

More information

FAN SPEED AIR SWING SET CANCEL FAN AIR SWING SET CANCEL WARNING

FAN SPEED AIR SWING SET CANCEL FAN AIR SWING SET CANCEL WARNING AUT O HE AT COOL DRY AUT O HE AT COOL DRY FAN SP E ED FAN SPEED AC AC AIR SWING SE T CHE CK CLOCK RE SE T AIR SWING SE T CHE CK CLOCK RE SE T FAN SPEED AIR SWING RC RC Order No: PAPAMY32039CE (YE9/2QKE)

More information

COLOR VIDEO DOOR PHONE CDV-71BE/D

COLOR VIDEO DOOR PHONE CDV-71BE/D COLOR VIDEO DOOR PHONE CDV-71BE/D 513-11, Sangdaewon-dong, Jungwon-gu, Seongnam-si, Gyeonggi-do, Korea Int l Business Dept. : Tel.; +82-31-7393-540~550 Fax.; +82-31-745-2133 Web site : www.commax.com Printed

More information

1 4. 3 4-2 ABNORMAL OPERATION. 4-2-1 Error code Display. Specifics Error Code. Subsection Error Code. Subsection and Specifics Error code target

1 4. 3 4-2 ABNORMAL OPERATION. 4-2-1 Error code Display. Specifics Error Code. Subsection Error Code. Subsection and Specifics Error code target 4-2 ABNORMAL OPERATI 4-2-1 An is represented by 3 digit characters. The first 2 digit means the subsection, and the last 1 digit means the specifics. Ex.) Indoor unit Network communication Error Subsection

More information

Meaco 30L and Meaco 40L dehumidifier instruction manual

Meaco 30L and Meaco 40L dehumidifier instruction manual Meaco 30L and Meaco 40L dehumidifier instruction manual Please read this instruction manual before using the dehumidifier and keep safe for future reference SAFETY INSTRUCTIONS PLEASE READ ALL INSTRUCTIONS

More information

Technical Service Manual. Version One

Technical Service Manual. Version One [Gree Central Air Conditioner] Technical Service Manual Ducted type unit 2.3KW-16KW Version One GREE ELECTRIC APPLIANCES.INC.OF ZHUHAI - 1 - FG Series wind pipe blowing air-conditioning unit Section One:

More information