1 4TTM3-SF-1 Service Facts Split System Cooling 4TTM3018-4TTM3060! CAUTION UNIT CONTAINS R-410A REFRIGERANT! R-410A OPERATING PRESSURE EXCEEDS THE LIMIT OF R-22. PROPER SERVICE EQUIPMENT IS REQUIRED. FAILURE TO USE PROPER SERVICE TOOLS MAY RESULT IN EQUIPMENT DAMAGE OR PERSONAL INJURY. SERVICE USE ONLY R-410A REFRIGERANT AND APPROVED POE COMPRESSOR OIL. IMPORTANT This document contains a wiring diagram, a parts list, and service information. This is customer property and is to remain with this unit. Please return to service information pack upon completion of work. WARNING: HAZARDOUS VOLTAGE - DISCONNECT POWER and DISCHARGE CAPACITORS BEFORE SERVICING THIS INFORMATION IS INTENDED FOR USE BY INDIVIDUALS POS SES S ING ADEQUATE BACKGROUNDS OF ELECTRICAL AND MECHANICAL EXPERIENCE. ANY ATTEMPT TO REPAIR A CEN- TRAL AIR CONDITION ING PRODUCT MAY RESULT IN PERSONAL INJURY AND OR PROPERTY DAMAGE. THE MANUFACTURER OR SELLER CANT BE RESPON SIBLE FOR THE INTERPRETATION OF THIS INFORMATION, R CAN IT ASSUME ANY LIABILITY IN CONNECTION WITH ITS USE. RECONNECT ALL GROUNDING DEVICES. ALL PARTS OF THIS PRODUCT CAPABLE OF CONDUCTING ELECTRICAL CURRENT ARE GROUNDED. IF GROUNDING WIRES, SCREWS, STRAPS, CLIPS, NUTS OR WASHERS USED TO COMPLETE A PATH TO GROUND ARE REMOVED FOR SERVICE, THEY MUST BE RETURNED TO THEIR ORIGINAL POSITION AND PROPERLY FASTENED. CONTAINS REFRIGERANT!! WARNING! CAUTION! CAUTION SYSTEM CONTAINS OIL AND REFRIGERANT UNDER HIGH PRESSURE. RECOVER REFRIGERANT TO RELIEVE PRESSURE BEFORE OPENING SYSTEM. Failure to follow proper procedures can result in personal illness or injury or severe equipment damage. TICE: The manufacturer has a policy of continuous product and product data improvement and it reserves the right to change design and specifications without notice. Trane /11

2 OUTDOOR UNIT 12 POWER CONNS. V/PH/HZ 3 MIN. BRCH. CIR. AMPACITY BR. CIR. PROT. RTG. - MAX. (AMPS) COMPRESSOR. USED -. SPEEDS VOLTS/PH/HZ R.L. AMPS 7 - L.R. AMPS FACTORY INSTALLED START COMPONENTS 8 INSULATION/SOUND BLANKET COMPRESSOR HEAT OUTDOOR FAN DIA. (IN.) -. USED TYPE DRIVE -. SPEEDS 0.0 IN. W.G. 4. MOTORS - HP MOTOR SPEED R.P.M. VOLTS/PH/HZ F.L. AMPS OUTDOOR COIL FACE AREA (SQ. FT.) REFRIGERANT LBS. R-410A (O.D. UNIT) 5 FACTORY SUPPLIED LINE SIZE - IN. O.D. GAS 6 LINE SIZE - IN. O.D. LIQ. 6 3/8 CHARGING SPECIFICATION - See Charging Section DIMENSIONS CRATED (IN.) WEIGHT SHIPPING (LBS.) NET (LBS.) PRODUCT SPECIFICATIONS 4TTM3024A1000B TTM3018A1000B PROPELLER DIRECT / / LBS., 3 OZ. 5/8 H X W X D 32-3/8 x 24-3/4 x 26-3/ PROPELLER DIRECT / / LBS., 11 OZ. 5/8 3/8 H X W X D 32-3/8 x 24-3/4 x 26-3/ TTM3030A1000B -U PROPELLER DIRECT / / LBS., 2 OZ. 3/4 3/8 H X W X D 32-3/8 x 24-3/4 x 26-3/ TTM3036A1000B PROPELLER DIRECT / / LBS., 5 OZ. 3/4 3/8 H X W X D 32-3/8 x 24-3/4 x 26-3/ OUTDOOR UNIT 12 POWER CONNS. V/PH/HZ 3 MIN. BRCH. CIR. AMPACITY BR. CIR. PROT. RTG. - MAX. (AMPS) COMPRESSOR. USED -. SPEEDS VOLTS/PH/HZ R.L. AMPS 7 - L.R. AMPS FACTORY INSTALLED START COMPONENTS 8 INSULATION/SOUND BLANKET COMPRESSOR HEAT OUTDOOR FAN DIA. (IN.) -. USED TYPE DRIVE -. SPEEDS 0.0 IN. W.G. 4. MOTORS - HP MOTOR SPEED R.P.M. VOLTS/PH/HZ F.L. AMPS OUTDOOR COIL FACE AREA (SQ. FT.) REFRIGERANT LBS. R-410A (O.D. UNIT) 5 FACTORY SUPPLIED LINE SIZE - IN. O.D. GAS 6 LINE SIZE - IN. O.D. LIQ. 6 CHARGING SPECIFICATION - See Charging Section DIMENSIONS CRATED (IN.) WEIGHT SHIPPING (LBS.) NET (LBS.) 4TTM3042A1000B PROPELLER 23-1 DIRECT / / LBS., 0 OZ. 7/8 3/8 H X W X D 32-3/8 x 29-3/4 x 30-1/ TTM3048A1000B PROPELLER 23-1 DIRECT / / LBS., 13 OZ. 7/8 3/8 H X W X D 32-3/8 x 29-3/4 x 30-1/ TTM3060A1000B PROPELLER 23-1 DIRECT / / LBS., 13 OZ. 7/8 3/8 H X W X D 32-3/8 x 29-3/4 x 30-1/ Certified in accordance with the Air-Source Unitary Air-conditioner Equipment certification program, which is based on A.H.R.I. standard 210/ Rated in accordance with A.H.R.I. standard Calculated in accordance with Natl. Elec. Codes. Use only HACR circuit breakers or fuses. 4 Standard Air Dry Coil Outdoor 5 This value approximate. For more precise value see unit nameplate. 6 Max. linear length 100 ft.; Max. lift - Suction 60 ft.; Max lift - Liquid 60 ft. 7 This value shown for compressor RLA on the unit nameplate and on this specification sheet is used to compute minimum branch circuit ampacity and max. fuse size. The value shown is the branch circuit selection current. 8 No means no start components. Yes means quick start kit components. PTC means positive temperature coefficient starter. 2 4TTM3-SF-1

3 REFRIGERANT CIRCUIT FIELD INSTALLED DRIER, SHIPS WITH UNIT 4TTM3-SF-1 3

4 System Charge Adjustment This system cannot be appropriately charged by subcooling. This new charging procedure helps prevent over charging. It is important to follow these instructions. You will need to measure the Outdoor Ambient temperature, the Suction Line Pressure (PSIG), The Liquid Temperature and the Liquid Pressure. You will charge to the MINIMUM Liquid Temperature or Maximum Liquid Line Pressure, whichever is reached first. STEP 1 - Check the indoor and outdoor ambient temperatures. Manual Charge Assist Hookup Leave bottle closed until ready to charge The Outdoor Ambient Temperature should be above 60ºF. If if the Outdoor Ambient temperature is below 60ºF then charge to 60ºF temperature and 115 Suction Line Pressure (PSIG) on the charging charts. The unit will be under charged and you will have to return when charging can be accurately performed. The Indoor Ambient Temperature must be kept between 70ºF to 100ºF. Raise the indoor temperature if needed, one method of increasing the indoor temperature is to run the furnace. Decrease the indoor temperature if needed, If the Indoor Ambient Temperature is above 100 ºF, operate the system to decrease the indoor temperature. 125ºF 60ºF Outdoor Temp 100ºF 70ºF Indoor Temp STEP 2 - Stabilize the system. Operate the system in cooling mode for a minimum of ten (10) minutes. Important: Whenever charge is removed or added, the system must be operated for a minimum of ten (10) minutes to stabilize before accurate measurements can be made. 10 MIN. If Suction Line Pressure is below 115 PSIG the system may experience fluctuations in pressures and temperatures due to expansion valve hunting. 4 4TTM3-SF-1

5 Example This system cannot be appropriately charged by subcooling. This new charging procedure helps prevent over charging. It is important to follow these instructions. You will need to measure the Outdoor Ambient temperature, the Suction Line Pressure (PSIG), The Liquid Temperature and the Liquid Pressure. You will charge to the MINIMUM Liquid Temperature or Maximum Liquid Line Pressure, whichever is reached first. This example demonstrates how to obtain your Target (MINIMUM) Liquid Temperature or Maximum Liquid Pressure using the instructions and tables provided on the following pages. 1. Identify the chart that applies to your outdoor unit model number. 2. Find the Measured Outdoor Ambient Temperature along the top of the chart. For this example the Measured Outdoor Ambient Temperature is 97 ºF. 4TTM3060A Locate the Measured Suction Pressure along the left side of the chart. For this example the Measured Suction Pressure is 130 PSIG. 4TTM3060A Determine the Target (MINIMUM) Liquid Temperature at the intersection of the Measured Suction Pressure and the Measured Outdoor Ambient Temperature. 4TTM3060A If intersection falls between two listed temperatures on the table you will need to estimate Find the Maximum Allowable Liquid Pressure. If intersection falls between two listed pressures on the table you will need to estimate. 4TTM3060A Target (MINIMUM) Liquid Temperature = 107ºF 414 Maximum Allowable Liquid Pressure = 414 PSIG 4TTM3-SF-1 5

6 STEP 3 - Measure Outdoor Ambient air temperature entering coil. Outdoor Ambient air temperature = F 6 STEP 4 - Measure Suction Line and Liquid line pressures Suction Line Pressure = PSIG Liquid Line Pressure = PSIG Note: If Suction Line Pressure is below 115 PSIG the system may experience fluctuations in pressures and temperatures due to expansion valve hunting. If fluctuations in Suction Line Pressure are noted then use the average PSIG. Manual Charge Assist Hookup Leave bottle closed until ready to charge STEP 5 - Determine the Liquid Line Temperature Attach a K-type temperature probe to the Liquid Line close to the Liquid Line Service Valve. The probe must be insulated. Insulation Measured Liquid Line Temp = ºF 107 F 6 4TTM3-SF-1

7 STEP 6 - Determine Target (MINIMUM) Liquid Temperature 1. Identify the table that applies to your outdoor unit model number. 2. Find the Measured Outdoor Ambient Temperature from Step 3 along the top of the table. If the Outdoor Ambient is below 60 ºF use the 60 ºF temperature on the table. 3. Locate the Measured Suction Pressure from Step 4 along the left side of the table. If system suction PSIG is below 115, use the 115 pressure on the table. 4. Determine the Target (MINIMUM) Liquid Temperature at the intersection of the Measured Suction Pressure and the Measured Outdoor Ambient Temperature. If intersection falls between two listed temperatures on the table you will need to estimate. 5. Locate the Maximum Allowable Liquid Pressure along the bottom of the table. If intersection falls between two listed pressures on the table you will need to estimate. Target (MINIMUM) Liquid Temperature = ºF Maximum Allowable Liquid Pressure = PSIG The following pages contain the charging tables needed for these steps. 4TTM3-SF-1 7

8 Charging Tables 4TTM3018A1 4TTM3024A1 4TTM3030A1 4TTM3036A1 8 4TTM3-SF-1

9 Charging Tables 4TTM3042A1 4TTM3048A1 4TTM3060A1 4TTM3-SF-1 9

10 STEP 7 - Determine Required Refrigerant Adjustment Compare the Measured Liquid Line Temperature from Step 4 against the Target (MINIMUM) Liquid Temperature from Step 6. If the Measured Liquid Line Temperature is above the Target (MINIMUM) Liquid Temperature and the Maximum Allowable Liquid Pressure has not been exceeded, you will add charge to the system. If the Measured Liquid Line Pressure is higher than the Maximum Allowable Liquid Pressure, you will remove charge. If the Measured Liquid Line Temperature is lower than the Target (MINIMUM) Liquid Temperature, you will remove charge. STEP 8 - Add or Remove System Charge Add system charge If step 7 above indicates to add charge: 1. Connect charging hose from bottle to charging port (bottle first). 2. Purge hose at bottle fitting. 3. Open bottle and turn upside down. Once the Measured Liquid Line Temperature is within 1 to 2 ºF of the Target (MINIMUM) Liquid Temperature, stop charging. As the charge level in the unit increases, Suction Pressure might increase slightly and Liquid Line temperature will decrease. Note: The manual charge assist port allows you to charge the unit using liquid. Manual Charge Assist Hookup Leave bottle closed until ready to charge Important: Charging must be performed using the manual charge assist port for accurate charging. Remove system charge If the Measured Liquid Line Pressure is higher than the Maximum Allowable Liquid Pressure or if the Measured Liquid Line Temperature is lower than the Target (MINIMUM) Liquid Temperature, recover refrigerant from the system. 10 4TTM3-SF-1

11 STEP 9 - Verify Refrigerant Adjustment Run system for ten (10) minutes. Check new Suction Pressure and Liquid Line Temperature. Measured Liquid Line Temperature = ºF Measured Suction Line Pressure = PSIG Measured Liquid Line Pressure = PSIG 10 MIN. If the current Measured Suction Pressure is different than the previous Measured Suction Pressure measured in Step 4, repeat Steps 5-8 and locate the new Target (MINIMUM) Liquid Temperature and Maximum Allowable Liquid Pressure using the table. Adjust charge if required. STEP 10 - Record System Information Record system pressures and temperatures after charging is complete. Outdoor model number = Measured Outdoor Ambient = ºF Measured Indoor Ambient = ºF Measured Liquid Line Temp = ºF Measured Suction Line Temp = ºF Liquid Gage Pressure = PSIG Suction Gage Pressure = PSIG 4TTM3-SF-1 11

12 SCHEMATIC DIAGRAM D156583P01Rev TTM3-SF-1

13 WIRING DIAGRAM D156583P01Rev01 4TTM3-SF-1 13

14 TROUBLESHOOTING Compressor fails to start Contactor check Is contactor energized? (contacts closed) Go To: Compressor won t run Check for 24 volts AC across contactor coil Is voltage present at contactor coil? Replace contactor Check control transformer and control fuse Is the control transformer and fuse good? Jumper R to Y low voltage terminals at thermostat sub base. Does the contactor energize? Replace the room thermostat Repair or replace transformer or fuse. Investigate cause for failure (possible short in field wiring) Repair or replace connecting wiring Single Pole Contactor (MS)* Double Pole Contactor (MS)* OUT T2 T1 T2 T1 OUT HIGH VOLTAGE Contactor Coil 24 VAC HIGH VOLTAGE IN L2 L1 L2 L1 IN *Refer to Wiring Diagram to determine if a single pole or double pole contactor is used. 14 4TTM3-SF-1

15 TROUBLESHOOTING Compressor won t run Contactor is closed Check for high voltage to contactor Is high voltage present at T1 and T2? Check for open IOL (Internal Overload) Check resistance of C to S and C to R Check power supply from disconnect and/or breaker panel. Does the resistance check show an open circuit from C to S or C to R? Allow compressor time to cool and re-test Check for open windings. Does a resistance check show an open circuit between R and S? Replace the compressor Check for locked rotor Is voltage present at C to S and C to R with locked rotor amps on C? Check Start- Capacitor and Relay (if present) and Run Capacitor Check wiring to compressor C, S and R Do the start components and run capacitor check good? Replace the compressor Replace start components and/ or run capacitor 4TTM3-SF-1 15

16 6200 Troup Highway Tyler, TX /11 The manufacturer has a policy of continuous product and product data improvement and it reserves the right to change design and specifications without notice.

Product Data. Split System Cooling 22-1904-1F-EN. March 2015

Product Data. Split System Cooling 22-1904-1F-EN. March 2015 Product Data Split System Cooling 4TTR4018L1000A 4TTR4024L1000A 4TTR4025L1000A 4TTR4030L1000A 4TTR4031L1000A 4TTR4036L1000A 4TTR4037L1000A 4TTR4042L1000A 4TTR4043L1000A 4TTR4048L1000A 4TTR4060L1000A Note:

More information

Split System Cooling Product Data

Split System Cooling Product Data Split System Cooling Product XL16i 1½ 5 Tons PUB. NO. 22-1890-01 Features and Benefits Climatuff compressor Efficiency up to 16.0 SEER and 9.0 HSPF All aluminum Spine Fin coil WeatherGuard fasteners Quick-Sess

More information

Split System Heat Pump Product & Performance Data

Split System Heat Pump Product & Performance Data Split System Heat Pump Product & Performance Data XB 13 2TWB3018-060 1½ 5 Tons PUB. NO. 22-1771-04 Features and Benefits Climatuff compressor All aluminum Spine Fin coil DuraTuff base, fast complete drain,

More information

SPLIT SYSTEM HEAT PUMP 2 5 TON HERITAGE 14 MODELS 4A6H B American Standard Heating & Air Conditioning

SPLIT SYSTEM HEAT PUMP 2 5 TON HERITAGE 14 MODELS 4A6H B American Standard Heating & Air Conditioning SPLIT SYSTEM HEAT PUMP 2 5 TON HERITAGE 14 MODELS 4A6H4018-060B 2008 American Standard Heating & Air Conditioning PUB. NO. 12-1175-03 June 2008 Features and Benefits Duration compressor Efficiency up to

More information

ALLEGIANCE 16 MODELS 4A7A6024, 036, 048, & 060C

ALLEGIANCE 16 MODELS 4A7A6024, 036, 048, & 060C SPLIT SYSTEM COOLING 2, 3, 4 & 5 ton ALLEGIANCE 16 MODELS 4A7A6024, 036, 048, & 060C with AccuLink and Charge Assist 2008 American Standard Heating & Air Conditioning PUB. NO. 12-1200-04 September 2008

More information

HERITAGE 15 MODELS 4A6H5018-60E

HERITAGE 15 MODELS 4A6H5018-60E SPLIT SYSTEM HEAT PUMP 1 1 / 2 5 ton HERITAGE 15 MODELS 4A6H5018-60E PUB. NO. 12-1256-03 July 2009 Features and Benefits DURaTION compressor Efficiency up to 17.0 SEER and 9.0 HSPF All aluminum Spine Fin

More information

Split System Cooling Product Data

Split System Cooling Product Data Split System Cooling Product Data 4TTB3018-060 1½ 5 Tons PUB. NO. 22-1843-14 Features and Benefits Efficiency up to 13.25 SEER All aluminum Spine Fin coil WeatherGuard fasteners Quick-Sess cabinet, easy

More information

Split System Heat Pump Product Data

Split System Heat Pump Product Data Split System Heat Pump Product Data XL20i 4TWZ0024, 036, 048 & 060 with ComfortLink II and Charge Assist 2, 3, 4 & 5 Tons PUB. NO. 22-1826-01 Features and Benefits Two Climatuff compressors Efficiency

More information

SPLIT SYSTEM COOLING ALLEGIANCE 20 MODELS 4A7Z0024, 036, 048, & 060A. with AccuLink and Charge Assist

SPLIT SYSTEM COOLING ALLEGIANCE 20 MODELS 4A7Z0024, 036, 048, & 060A. with AccuLink and Charge Assist SPLIT SYSTEM COOLING 2, 3, 4 & 5 ton ALLEGIANCE 20 MODELS 4A7Z0024, 036, 048, & 060A with AccuLink and Charge Assist PUB. NO. 12-1284-02 March 2009 Features and Benefits Two DURATION compressors Efficiency

More information

Split System Heat Pump Product & Performance Data

Split System Heat Pump Product & Performance Data Split System Heat Pump Product & Performance Data XB 13 4TWB3018-060 1½ 5 Tons PUB. NO. 22-1793-02 Features and Benefits Climatuff compressor All aluminum Spine Fin coil Quick-Sess cabinet, service access

More information

WCA3**2. Product Specifications. AIR CONDITIONER COMPONENT 1 1/2 THRU 5 TONS 208 / 230 Volt, 1 phase, 60 Hz ALL MODELS

WCA3**2. Product Specifications. AIR CONDITIONER COMPONENT 1 1/2 THRU 5 TONS 208 / 230 Volt, 1 phase, 60 Hz ALL MODELS AIR CONDITIONER COMPONENT 1 1/2 THRU 5 TONS 208 / 230 Volt, 1 phase, 60 Hz WCA3**2 Number Size (tons) Nominal BTU/hr Min. Circuit Ampacity Max. Fuse or Breaker WCA3182GKR 1 1/2 18,000 10.9 15 WCA3242GKR

More information

Split System Heat Pump Product Data

Split System Heat Pump Product Data Split System Heat Pump Product Silver 14 4A6H4 1 1 /2-5 Tons PUB. NO. 12-1175-07 Contents Features and Benefits 2 Model Nomenclature 3 General 4 Product Specifications 4 A-weighted Sound Power Level [db(a)]

More information

Split System Cooling Product Data

Split System Cooling Product Data Split System Cooling Product Data XR17 4TTR7 2, 3, 4 & 5 Tons PUB. NO. 22-1884-01 Features and Benefits CLIMATUFF 2-stage scroll compressor Efficiency up to 18.0 SEER All Aluminum SPINE FIN coil DURATUFF

More information

10ACB WARNING IMPORTANT

10ACB WARNING IMPORTANT Service Literature 10ACB SERIES UNITS 10ACB Corp. 435 L Revised 04 2002 The 10ACB is a residential split-system condensing unit available in sizes ranging from 1 to 5 tons. Condensing coil size, circuiting

More information

Split System Cooling Product Data

Split System Cooling Product Data Split System Cooling Product Data XB 13 4TTB3018-060 1½ 5 Tons PUB. NO. 22-1843-08 Features and Benefits Climatuff compressor Efficiency up to 13.25 SEER All aluminum Spine Fin coil WeatherGuard fasteners

More information

Split System Cooling Product Data

Split System Cooling Product Data Split System Cooling Product Data Three Phase 4TTA3 2½ 5 Tons PUB. NO. 22-1791-12 Features and Benefits All aluminum Spine Fin coil WeatherGuard fasteners Quick-Sess cabinet, service access and refrigerant

More information

Attachment 2 Compressor Evaluation Form

Attachment 2 Compressor Evaluation Form Warranty Tag #: Date Outdoor Unit Model: Outdoor Unit Serial: Indoor Coil Model: Indoor Coil Serial: Date Installed: Date Installed: Date Failed: Model Serial Name of Person Filling out Form Homeowner

More information

DX11S Commercial & 10-Ton, Three-Phase. Cooling Capacity: 88, ,000 BTU/h

DX11S Commercial & 10-Ton, Three-Phase. Cooling Capacity: 88, ,000 BTU/h DX11S Commercial Cooling Capacity: 88,000-112,000 BTU/h 7.5- & 10-Ton, Three-Phase Split System Air Conditioner 11.2 EER / R-410A Contents Nomenclature... 2 Product Specifications... 3 Expanded Cooling

More information

Split System Cooling Product & Performance Data

Split System Cooling Product & Performance Data Split System Cooling Product & Performance Data XB 13 2TTB3018-060 1½ 5 Tons PUB. NO. 22-1769-07 Features and Benefits Efficiency up to 13.25 SEER All aluminum Spine Fin coil Fast, complete-drain, weatherproof

More information

10ACC WARNING WARNING. Service Literature 10ACC SERIES UNITS

10ACC WARNING WARNING. Service Literature 10ACC SERIES UNITS Service Literature ACC SERIES UNITS ACC Corp. 0201 L1 Revised 08 2004 The ACC is a residential split-system condensing unit available in sizes ranging from 1 1/2 to 5 tons. Condensing coil size, circuiting

More information

Split System Heat Pump Product Data

Split System Heat Pump Product Data Split System Heat Pump Product XB 13 4TWB3018-060 1½ 5 Tons PUB. NO. 22-1793-14 Features and Benefits All aluminum Spine Fin coil Quick-Sess cabinet, service access and refrigerant connections with full

More information

Split System Heat Pump Product Data

Split System Heat Pump Product Data Split System Heat Pump Product XB 13 4TWB3018-060 1½ 5 Tons PUB. NO. 22-1793-16 Features and Benefits All aluminum Spine Fin coil Quick-Sess cabinet, service access and refrigerant connections with full

More information

Split System Heat Pump Product Data

Split System Heat Pump Product Data Split System Heat Pump Product Data XR 13 4TWR3018-060 1½ 5 Tons PUB. NO. 22-1795-12 Features and Benefits Climatuff compressor All aluminum Spine Fin coil Quick-Sess cabinet, service access and refrigerant

More information

Cooling/Heat Pump Convertible Air Handlers

Cooling/Heat Pump Convertible Air Handlers Cooling/Heat Pump Convertible Air Handlers 2/4TEC3F18-60A1000A 1½ 5 Ton PUB. NO. 22-1774-01-0905 (EN) Features and Benefits 13.0 SEER Ships horizontal converts to vertical by standing unit on end. Six-way

More information

SERVICING PROCEDURE LEAK TEST EVACUATION CHARGING

SERVICING PROCEDURE LEAK TEST EVACUATION CHARGING SERVICING PROCEDURE LEAK TEST EVACUATION CHARGING Manual No.: 2100-462 Supersedes: Date: 06-20-05 Copyright 2005 CONTENTS General Gauge Manifold... 1 Attaching Gauge Manifold... 1 Attaching Manifold Hose

More information

Installation and Startup Instructions

Installation and Startup Instructions Installation and Startup Instructions ORBIT 8 Series R410A Scroll Compressors Content Page 1 General 1 2 Safety Instructions 1 3 Installation Procedures 2 4 Accessory Items 6 5 Compressor Installation

More information

Split System Cooling Product & Performance Data

Split System Cooling Product & Performance Data Split System Cooling Product & Performance Data XR 13 4TTR3018-060 1½ 5 Tons PUB. NO. 22-1790-02-2607 (EN) Features and Benefits Climatuff compressor Efficiency up to 14.00 SEER All aluminum Spine Fin

More information

Split System Heat Pump Product Data

Split System Heat Pump Product Data Split System Heat Pump Product Three Phase 4TWA3030A3000C 4TWA3030A4000C 4TWA3036A3000C 4TWA3036A4000C 4TWA3042B3000A 2½ 5 Tons 4TWA3042B4000A 4TWA3048A3000C 4TWA3048A4000C 4TWA3060B3000A 4TWA3060B4000A

More information

Chapter 5. Components, Symbols, and Circuitry of Air-Conditioning Wiring Diagrams

Chapter 5. Components, Symbols, and Circuitry of Air-Conditioning Wiring Diagrams Chapter 5 Components, Symbols, and Circuitry of Air-Conditioning Wiring Diagrams Objectives Upon completion of this course, you will be able to: Explain what electrical loads are and their general purpose

More information

Residential Piping and Long Line Guideline

Residential Piping and Long Line Guideline R Refrigerant Systems Single --- Stage and Two --- Stage Residential Piping and Long Line Guideline TABLE OF CONTENTS A. Safety Considerations... 2 B. Definitions... 2 C. Introduction... 3 D. General Limitations...

More information

TECHNICAL GUIDE SINGLE PIECE AIR HANDLERS FOR USE WITH SPLIT-SYSTEM COOLING & HEAT PUMPS. DESCRIPTION FEATURES

TECHNICAL GUIDE SINGLE PIECE AIR HANDLERS FOR USE WITH SPLIT-SYSTEM COOLING & HEAT PUMPS.   DESCRIPTION FEATURES TECHNICAL GUIDE SINGLE PIECE AIR HANDLERS FOR USE WITH SPLIT-SYSTEM COOLING & HEAT PUMPS MODELS: AHR18 THRU 60* DESCRIPTION This fan coil line offers the ultimate in application flexibility. The AHR (non-variable

More information

Wiring Diagrams. Units Produced After January 1996 INDEX

Wiring Diagrams. Units Produced After January 1996 INDEX Wiring Diagrams Units Produced After January 1996 38AKS013-024 Air-Cooled Condensing Units 50/60 Hz UNIT 38AKS ELECTRICAL CHARACTERISTICS (V-Ph-Hz) INDEX SCHEMATIC DIAGRAM FIG. NO. COMPONENT ARRANGEMENT

More information

543-0032-00, 943-0032-00. User s Manual

543-0032-00, 943-0032-00. User s Manual 543-0032-00, 943-0032-00 User s Manual 1 Comfort Alert Diagnostics Faster Service And Improved Accuracy The Comfort Alert diagnostics module is a breakthrough innovation for troubleshooting heat pump and

More information

TECHNICAL SUPPORT MANUAL 3 Phase Air Conditioner Component R2A3**GHR

TECHNICAL SUPPORT MANUAL 3 Phase Air Conditioner Component R2A3**GHR 3 Phase Air Conditioner Component R2A3**GHR DANGER, WARNING, CAUTION, and NOTE The signal words DANGER, WARNING, CAU- TION, and NOTE are used to identify levels of hazard seriousness. The signal word DANGER

More information

GSX 16 SEER Condensing Units

GSX 16 SEER Condensing Units TEHNIAL MANUAL AL GSX 16 SEER ondensing Units Refer to Service Manual RS6200006 for installation, operation, and troubleshooting information. All safety information must be followed as provided in the

More information

Electronic Refrigerator Diagnostics

Electronic Refrigerator Diagnostics Electronic Refrigerator Diagnostics IMPORTANT SAFETY NOTICE The information in this presentation is intended for use by individuals possessing adequate backgrounds of electrical, electronic, & mechanical

More information

REFRIGERATED TYPE COMPRESSED AIR DRYERS INSTRUCTION MANUAL. For Sales & Service please contact:

REFRIGERATED TYPE COMPRESSED AIR DRYERS INSTRUCTION MANUAL. For Sales & Service please contact: 7610.478.16 8/99 INSTRUCTION MANUAL Models 8005, 8010, 8015 For Sales & Service please contact: CENTRAIR Air Systems & Supplies Phone: 705-722-5747 Fax: 705-722-5458 Email: sales@centrair.ca Website: www.centrair.ca

More information

AE8-1328 R5 March 2011. Copeland Digital Compressor Controller AE8-1328 R5. Specifications

AE8-1328 R5 March 2011. Copeland Digital Compressor Controller AE8-1328 R5. Specifications AE8-1328 R5 March 2011 Copeland Digital Compressor Controller Introduction The Digital Compressor Controller is the electronics interface between the Copeland Scroll Digital compressor or the Copeland

More information

14 SEER CONDENSING UNIT INSTALLER'S INFORMATION MANUAL

14 SEER CONDENSING UNIT INSTALLER'S INFORMATION MANUAL 14 SEER CONDENSING UNIT INSTALLER'S INFORMATION MANUAL ATTENTION, INSTALLER! After installing the system, show the user how to turn off electricity to the unit. Point out control and switch locations for

More information

SERVICE MANUAL FOR 6535 SERIES TWO TON HIGH EFFICIENCY PACKAGED HEAT PUMPS

SERVICE MANUAL FOR 6535 SERIES TWO TON HIGH EFFICIENCY PACKAGED HEAT PUMPS SERVICE MANUAL FOR 6535 SERIES TWO TON HIGH EFFICIENCY PACKAGED HEAT PUMPS TABLE OF CONTENTS 1. Warnings...2 2. Accessibility Of Appliance...3 3. Unit Dimensions And Specifications...3 4. Unit Specifications

More information

LOBOY 16 AIR CONDITIONERS

LOBOY 16 AIR CONDITIONERS INSTRUCTION MANUAL FOR: LOBOY 16 AIR CONDITIONERS McLean Midwest Corp. dba: McLean Cooling Technology 11611 Business Park Blvd. N Champlin, MN 55316 Tel: 763-323-8200 Fax: 763-576-3200 www.mcleancoolingtech.com

More information

TWE+TTA TWE+TWA 6.25-20 T.R.

TWE+TTA TWE+TWA 6.25-20 T.R. TWE+TTA TWE+TWA 6.25-20 T.R. Main features : TWE indoor unit : Convertible cabinet, vertical or horizontal. Adjustable speed pulley-belt drive centrifugal fan motor. Aluminium fin coil with copper-tubes.

More information

ACCESSORY INSTALLATION INSTRUCTION ELECTRIC HEAT ACCESSORY 10, 16, 26, 36 & 72

ACCESSORY INSTALLATION INSTRUCTION ELECTRIC HEAT ACCESSORY 10, 16, 26, 36 & 72 ACCESSORY INSTALLATION INSTRUCTION ELECTRIC HEAT ACCESSORY 10, 16, 26, 36 & 72 FOR SPLIT-SYSTEM AIR CONDITIONERS 5, 7-1/2, 10 & 15 TONS SPLIT-SYSTEM HEAT PUMPS 7-1/2 & 10 TONS GENERAL This instruction

More information

COMPRESSOR REPLACEMENT PROCEDURE

COMPRESSOR REPLACEMENT PROCEDURE COMPRESSOR REPLACEMENT PROCEDURE Bard Manufacturing Company Bryan, Ohio 43506 Since 1914...Moving ahead just as planned Manual No.: 2100-003E Supersedes 2100-003D File: Volume I, Tab 1 Date: 06-25-02 Copyright

More information

LONG LINE SET APPLICATION R-410A

LONG LINE SET APPLICATION R-410A Goodman Manufacturing Company, L.P. 1810 Wilson Parkway / Fayetteville, TN 37334 (888) 593-9988 FAX (931) 438-2273 TECHNICAL PUBLICATION TP-107 INDEX SECTION 1. General Requirements for All Long Line Set

More information

Owners Manual. Refrigerated Air Dryer. HX75 thru HX2400

Owners Manual. Refrigerated Air Dryer. HX75 thru HX2400 Owners Manual Refrigerated Air Dryer HX75 thru HX2400 IMPORTANT: READ THIS MANUAL CAREFULLY. IT CONTAINS INFORMATION ABOUT SAFETY AND THE SAFETY OF OTHERS. ALSO BECOME FAMILIAR WITH THE PROPER INSTALLATION

More information

10ACC Corp L1 WARNING IMPORTANT WARNING. Service Literature 10ACC SERIES UNITS

10ACC Corp L1 WARNING IMPORTANT WARNING. Service Literature 10ACC SERIES UNITS Service Literature 10ACC SERIES UNITS 10ACC Corp. 0201-L1 The 10ACC is a residential split-system condensing unit available in sizes ranging from 1-1/2 to 5 tons. Condensing coil size, circuiting and air

More information

SPLIT-SYSTEM CONDENSING UNITS. 10.00 SEER HRA018 thru 060 (1.5 thru 5 Nominal Tons) DESCRIPTION FEATURES

SPLIT-SYSTEM CONDENSING UNITS. 10.00 SEER HRA018 thru 060 (1.5 thru 5 Nominal Tons) DESCRIPTION FEATURES 550.46 -TG1Y (196) SPLIT-SYSTEM CONDENSING S 0 SEER HRA018 thru 060 (1.5 thru 5 Nominal Tons) DESCRIPTION The HRA Series condensing unit is the outdoor part of a versatile system of air conditioning. It

More information

User s Information/Installation Instructions

User s Information/Installation Instructions Outdoor Heat Pump User s Information/Installation Instructions 13 SEER R-410A High Efficiency Split System These units have been designed and tested for capacity and effi ciency in accordance with A.R.I.

More information

T-SERIES Air Conditioners. T70, 3 Ton and 5 Ton Models INSTRUCTION MANUAL. Rev. H 2013 Pentair Equipment Protection P/N 10-1008-177

T-SERIES Air Conditioners. T70, 3 Ton and 5 Ton Models INSTRUCTION MANUAL. Rev. H 2013 Pentair Equipment Protection P/N 10-1008-177 T-SERIES Air Conditioners T70, 3 Ton and 5 Ton Models INSTRUCTION MANUAL Rev. H 2013 Pentair Equipment Protection P/N 10-1008-177 88043249 TABLE OF CONTENTS RECEIVING THE AIR CONDITIONER...3 HANDLING AND

More information

Customized Assessment Blueprint

Customized Assessment Blueprint Customized Assessment Blueprint HVAC Installer Basic - Test Codes: 7906 and 7796 Measuring What Matters Competencies and Skills Tested in this Assessment: HVAC Theory Heat Theory and Refrigeration HVAC

More information

FLORIDA STATE COLLEGE AT JACKSONVILLE NON-COLLEGE CREDIT COURSE OUTLINE

FLORIDA STATE COLLEGE AT JACKSONVILLE NON-COLLEGE CREDIT COURSE OUTLINE Form 2B, Page 1 FLORIDA STATE COLLEGE AT JACKSONVILLE NON-COLLEGE CREDIT COURSE OUTLINE COURSE NUMBER: ACR 0100 COURSE TITLE: PREREQUISITE(S): COREQUISITE(S): Basic Electricity and Schematics None None

More information

Mark IV/AC Controller for Legacy Console Water Source Heat Pumps

Mark IV/AC Controller for Legacy Console Water Source Heat Pumps Operation & Maintenance Data OM 120-4 Group: WSHP Part Number: 910146916 Date: October 2013 Mark IV/AC Controller for Legacy Console Water Source Heat Pumps Specific to Mark IV Boards with Part No. 056792402

More information

INSTALLATION MANUAL AFFINITY SERIES SINGLE PACKAGE HEAT PUMPS. MODEL: B*HP024 thru thru 5 Ton (13 SEER) NOTES, CAUTIONS AND WARNINGS

INSTALLATION MANUAL AFFINITY SERIES SINGLE PACKAGE HEAT PUMPS. MODEL: B*HP024 thru thru 5 Ton (13 SEER) NOTES, CAUTIONS AND WARNINGS INSTALLATI MANUAL CTENTS GENERAL....................................3 INSPECTI..................................3 REFERENCE..................................3 REPLACEMENT PARTS.........................3

More information

NXA6. Product Specifications HIGH EFFICIENCY 16 SEER AIR CONDITIONER

NXA6. Product Specifications HIGH EFFICIENCY 16 SEER AIR CONDITIONER ENVIRONMENTALLY SOUND REFRIGERANT NXA6 Performance Series Product Specifications HIGH EFFICIENCY 16 AIR CONDITIONER ENVIRONMENTALLY SOUND R 410A REFRIGERANT 1½ THRU 5 TONS SPLIT SYSTEM 208 / 230 Volt,

More information

TECHNICAL DATA & SERVICE MANUAL SPLIT SYSTEM AIR CONDITIONER INDOOR UNIT: AW52AL AW64AL AW52AL 387030095 AW64AL 0.8180.463.0 07/05

TECHNICAL DATA & SERVICE MANUAL SPLIT SYSTEM AIR CONDITIONER INDOOR UNIT: AW52AL AW64AL AW52AL 387030095 AW64AL 0.8180.463.0 07/05 TECHNICAL DATA & SERVICE MANUAL INDOOR UNIT: AW52AL AW64AL SPLIT SYSTEM AIR CONDITIONER Model No. Product Code No. AW52AL 387030095 AW64AL 387030096 0.8180.463.0 07/05 IMPORTANT! Please read before installation

More information

Commercial Microwave-Technical Information

Commercial Microwave-Technical Information Commercial Microwave-Technical Information, 60 Hz model RCS10TS MCS10TS P2002401M P2002403M Due to possibility of personal injury or property damage, always contact an authorized technician for servicing

More information

Liebert Fin/Tube Condenser Warranty Inspection Check Sheet

Liebert Fin/Tube Condenser Warranty Inspection Check Sheet The following information must be fully completed and forwarded to your local Liebert sales office to establish your equipment warranty. Installer Address Owner Address Owner e-mail address Installation

More information

Compressor Will Not Run

Compressor Will Not Run Compressor Will Not Run Contactor Open The contactor should be energized or "closed" on a call for cooling. If the contactors contacts do not pull in or close (completing the high voltage circuit) voltage

More information

AC Electrical System Tests Sign-Off Sheet. STEP Initials Date

AC Electrical System Tests Sign-Off Sheet. STEP Initials Date AC Electrical System Tests Hot Skin Test Prepare Documentation? Make sure shore line is plugged into 120VAC source? Set VOM to AC voltage scale? Place one probe on a bare metal surface of the RV (i.e.,

More information

SERVICE MANUAL MUZ-GE09NA MUZ-GE12NA MUZ-GE15NA MUZ-GE18NA MUZ-GE24NA MUY-GE09NA MUY-GE12NA MUY-GE15NA MUY-GE18NA MUY-GE24NA OUTDOOR UNIT

SERVICE MANUAL MUZ-GE09NA MUZ-GE12NA MUZ-GE15NA MUZ-GE18NA MUZ-GE24NA MUY-GE09NA MUY-GE12NA MUY-GE15NA MUY-GE18NA MUY-GE24NA OUTDOOR UNIT SPLIT-TYPE AIR CONDITIONERS Revision B: Descriptions regarding the outdoor fan motor have been corrected. Please void OBH549 REVISED EDITION-A. OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OBH549 REVISED

More information

INSTALLATION INSTRUCTIONS Fan Coil Replacement Coil Kit EBX & EBXX

INSTALLATION INSTRUCTIONS Fan Coil Replacement Coil Kit EBX & EBXX Fan Coil Replacement Coil Kit EBX & EBXX These instructions must be read and understood completely before attempting installation. These instructions covers the installation of replacement coil kit into

More information

Panasonic Industrial Company Air Conditioning Department 5PS102FAD21 208/230V, 60Hz R-410a 5PS102FAD21 Application Cooling (C) / Heating (H) Ref. Charge Limit (C/H) 24.0 oz. 680 g (C) 28.2 oz. 800 g Evaporating

More information

120 Series Refrigeration Systems. Water Cooled Condensing Units Hermetic / Scroll / Semi-Hermetic ½ Thru 6 Hp Models

120 Series Refrigeration Systems. Water Cooled Condensing Units Hermetic / Scroll / Semi-Hermetic ½ Thru 6 Hp Models 120 Series Refrigeration Systems Water Cooled Condensing Units Hermetic / Scroll / Semi-Hermetic ½ Thru 6 Hp Models RDI PC Water Cooled Refrigeration Systems The RDI PC Water Cooled Refrigeration system

More information

technical data air conditioning systems RXS20-25-35E (single phase) FBQ-B8V1-B8V3B Split Heat Pump Condensing Units Split Sky Air

technical data air conditioning systems RXS20-25-35E (single phase) FBQ-B8V1-B8V3B Split Heat Pump Condensing Units Split Sky Air technical data RXS20-25-35E FBQ-B8V-B8V3B (single phase) Split Heat Pump Condensing Units air conditioning systems Split Sky Air Outdoor Units R-40A RXS-E2VB Split Sky Air Outdoor Units Features O u t

More information

E2 Series Electric Furnaces

E2 Series Electric Furnaces E2 Series Electric Furnaces Service Manual Table of Contents Electrical Requirements... 10 Codes, Specifications Requirements... 10 Connection Supply Service Wires... 10 Furnace Sequence of Operation...

More information

TECHNICAL GUIDE MODELS: H4CE090 & H2CE120 & H1CE /2, 10, & 12-1/2 NOMINAL TONS EER

TECHNICAL GUIDE MODELS: H4CE090 & H2CE120 & H1CE /2, 10, & 12-1/2 NOMINAL TONS EER 036-21083-003 Rev. B (0301) DESCRIPTION These Sunline 2000 units are completely assembled, piped and wired at the factory to provide one-piece shipment and rigging. Each unit is pressurized with a holding

More information

/ Marley Electric Basin Heater / User Manual C

/ Marley Electric Basin Heater / User Manual C / Marley Electric Basin Heater / User Manual 92-1322C / Receiving and Inspection / The heater package is shipped directly from the vendor. 1. Check all parts for any damage in transit. The carrier is

More information

SUBJECT: How to wire a motor starter Number: AN-MC-004 Date Issued: 2/08/2005 Revision: Original

SUBJECT: How to wire a motor starter Number: AN-MC-004 Date Issued: 2/08/2005 Revision: Original SUBJECT: How to wire a motor starter Number: AN-MC-004 Date Issued: 2/08/2005 Revision: Original A motor starter is a combination of devices to allow an induction motor to start, run and stop according

More information

TEST REPORT #44. System Drop-in Tests of Refrigerant R-32 in Single Packaged Vertical Heat Pump (SPVH)

TEST REPORT #44. System Drop-in Tests of Refrigerant R-32 in Single Packaged Vertical Heat Pump (SPVH) Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP) TEST REPORT #44 System Drop-in Tests of Refrigerant R-32 in Single Packaged

More information

NE1130BZ COMPRESSOR TECHNICAL SPECIFICATION INDEX

NE1130BZ COMPRESSOR TECHNICAL SPECIFICATION INDEX NE1130BZ COMPRESSOR TECHNICAL SPECIFICATION 2010.6 INDEX page 1 Compressor Type..2 2 Performance Data.2 3 Running Condition 2 4 Compressor Mechanical Information 3 5 Compressor Shape.3 6 Wiring Diagram

More information

TECHNICAL & SERVICE MANUAL WINDOW TYPE AIR CONDITIONER SA 79G SA 99G FILE NO. SA 79G SA 99G REFERENCE NO. SM700402

TECHNICAL & SERVICE MANUAL WINDOW TYPE AIR CONDITIONER SA 79G SA 99G FILE NO. SA 79G SA 99G REFERENCE NO. SM700402 TECHNICAL & SERVICE MANUAL SA 79G SA 99G FILE NO. WINDOW TYPE AIR CONDITIONER Model No. Product Code No. Destination SA-79G-A 1 851 005 18 General (50Hz) & Europe SA-99G-A 1 851 005 19 SA 79G SA 99G REFERENCE

More information

Model No. XP13 018 XP13 024 XP13 030 XP13 036 XP13 037 XP13 042 XP13 048 XP13 060 Data Nominal Tonnage 1.5 2 2.5 3 3+ 3.5 4 5 Connections (sweat)

Model No. XP13 018 XP13 024 XP13 030 XP13 036 XP13 037 XP13 042 XP13 048 XP13 060 Data Nominal Tonnage 1.5 2 2.5 3 3+ 3.5 4 5 Connections (sweat) Service Literature Corp. 0528 L10 Revised 05 2008 XP13 SERIES UNITS XP13 The XP13 is a high efficiency residential split system heat pump unit, which features a scroll compressor and R 410A refrigerant.

More information

VSX13 13 SEER. Split System Air Conditioner. 1½ to 5 Tons. Cooling Capacity: 18,000-60,000 BTU/h

VSX13 13 SEER. Split System Air Conditioner. 1½ to 5 Tons. Cooling Capacity: 18,000-60,000 BTU/h Split System Air onditioner 1½ to 5 Tons 13 SEER ooling apacity: 18,000-60,000 BTU/h Standard Features Energy-efficient compressor Quiet condenser fan system Factory-installed liquid line filter drier

More information

A319 Electronic Temperature Control

A319 Electronic Temperature Control FANs 216, 125, 195 Product/Technical Bulletin A319 Issue Date 0396 A319 Electronic Temperature Control The A319 Series is a line voltage, single-stage electronic temperature control with Single-Pole, Double-Throw

More information

Water Source Heat Pumps Field Installed Loop Pump Module

Water Source Heat Pumps Field Installed Loop Pump Module Installation & Maintenance Data IM 1189 Group: WSHP Part Number: 910144616 Date: October 2013 Water Source Heat Pumps Field Installed Loop Pump Module Single pump module Dual pump module Contents Receiving

More information

Installation, Operation & Troubleshooting for Texas Instruments 41AA Motor Protection Modules

Installation, Operation & Troubleshooting for Texas Instruments 41AA Motor Protection Modules Installation, Operation & Troubleshooting for Texas Instruments 41AA Motor Protection Modules SUBJECT: Installation Operation & Troubleshooting Texas Instruments (TI) KLIXON 41AA Motor Winding Protectors

More information

SECTION 4 ELECTRIC MOTORS UNIT 17: TYPES OF ELECTRIC MOTORS

SECTION 4 ELECTRIC MOTORS UNIT 17: TYPES OF ELECTRIC MOTORS SECTION 4 ELECTRIC MOTORS UNIT 17: TYPES OF ELECTRIC MOTORS UNIT OBJECTIVES After studying this unit, the reader should be able to Describe the different types of open single-phase motors used to drive

More information

INSTALLATION INSTRUCTIONS High-Pressure Switch Kit NASA204PS, NASA404PS

INSTALLATION INSTRUCTIONS High-Pressure Switch Kit NASA204PS, NASA404PS NASA204PS, NASA404PS These instructions must be read and understood completely before attempting installation. Safety onsiderations: Installing and servicing of air conditioning equipment can be hazardous

More information

Service manual. Website: www.andico.com.au CAUTION - BEFORE SERVICING THE UNIT, READ THE SAFETY - PRECAUTIONS IN THIS MANUAL.

Service manual. Website: www.andico.com.au CAUTION - BEFORE SERVICING THE UNIT, READ THE SAFETY - PRECAUTIONS IN THIS MANUAL. Website: www.andico.com.au Service manual CAUTION - BEFORE SERVICING THE UNIT, READ THE SAFETY - PRECAUTIONS IN THIS MANUAL. - ONLY FOR AUTHORISED SERVICE PERSONNEL. MODELS: MPK1-09CR-QB8 MPK1-12ER-QB6

More information

SUNLINE 2000 SINGLE PACKAGE AIR-TO-AIR HEAT PUMPS DESCRIPTION FEATURES

SUNLINE 2000 SINGLE PACKAGE AIR-TO-AIR HEAT PUMPS DESCRIPTION FEATURES 511.06TGY (600) SINGLE PACKAGE AIRTOAIR HEAT PUMPS B3CH090, 10 (08/30, 460V) B5CH090, 10 (575V) 71/ & 10 NOMINAL TONS (9 EER) SUNLINE 000 DESCRIPTION YORK Sunline 000 Heat Pumps are convertible single

More information

AAON HA SERIES HORIZONTAL DISCHARGE COOLING UNITS USERS INFORMATION MANUAL MANUFACTURED IN THE U.S.A

AAON HA SERIES HORIZONTAL DISCHARGE COOLING UNITS USERS INFORMATION MANUAL MANUFACTURED IN THE U.S.A AAON HA SERIES HORIZONTAL DISCHARGE COOLING UNITS USERS INFORMATION MANUAL MANUFACTURED IN THE U.S.A 1 2 TABLE OF CONTENTS AAON SECTION PAGE NUMBER OWNER'S INFORMATION 04 Unpacking Setting the Unit Electrical

More information

SERVICE MANUAL OUTDOOR UNIT. No. OBH590 REVISED EDITION-B. Models HFC

SERVICE MANUAL OUTDOOR UNIT. No. OBH590 REVISED EDITION-B. Models HFC SPLIT-TYPE AIR CONDITIONERS Revision B: MUZ-EF25/35/42/50VE - E2 and MUZ-EF25/35VEH - E2 have been added. Please void OBH590 REVISED EDITION-A. OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OBH590 REVISED

More information

Failure code manual. content

Failure code manual. content Failure code manual content 一 wall split AC series 2 二 floor standing AC series. 4 三 portable AC series.. 5 四 dehumidifer 6 五 DC inverter single split series...7 六 DC inverter multi-split series 10 1 一

More information

2 THRU 5 TONS SPLIT SYSTEM FCP / FCX Series

2 THRU 5 TONS SPLIT SYSTEM FCP / FCX Series 2 THRU 5 TONS SPLIT SYSTEM FCP / FCX Series FEATURES Air Conditioning or Heat Pump ready Prepainted galvanized steel cabinet Internally lined with R3.2, 3/4 Tuf--Skin II insulation Electronic control board

More information

SECTION 15750 PACKAGED ROOFTOP AIR CONDITIONING UNITS

SECTION 15750 PACKAGED ROOFTOP AIR CONDITIONING UNITS SECTION 15750 PART 1 - GENERAL 1.01 DESCRIPTION A. Section includes requirements for roof mounted, self-contained units, with electric cooling, and electric or reverse refrigeration cycle (heat pump) heating

More information

Air Conditioning Sign-Off Sheet

Air Conditioning Sign-Off Sheet Air Conditioning Sign-Off Sheet Printed Technician Name Address Social Security Number Telephone Number City State Zip Code Install Or Verify The Accuracy Of An Air Conditioner s Installation The candidate

More information

Split Systems Cooling Condensers

Split Systems Cooling Condensers Installation Operation Maintenance Split Systems Cooling Condensers 7½ - 20 Tons Model Numbers: TTA090A***F (60 Hz) TTA075AD**F (50 Hz) TTA155BD**F (50 Hz) TTA120A***F (60 Hz) TTA085AD**F (50 Hz) TTA155CD**G

More information

ESPD8-301R MODEL ESP-D FAN COIL UNIT TROUBLESHOOTING GUIDE

ESPD8-301R MODEL ESP-D FAN COIL UNIT TROUBLESHOOTING GUIDE ESPD8-301R MODEL ESP-D FAN COIL UNIT TROUBLESHOOTING GUIDE Protected by one or more of the following U.S. Patents (3,507,354; 3,575,234; 3,596,936; 3,605,797; 3,685,329; 4,045,977; 4,698,982; 926,673 and

More information

LG Air Conditioning - Universal Split Fault Codes Sheet. Universal Split Systems

LG Air Conditioning - Universal Split Fault Codes Sheet. Universal Split Systems Universal Split Systems If there is a fault on any LG Universal unit, a two digit number will appear on the remote controllers led display. If the unit does not have a remote controller the fault will

More information

MDT5N25 & MTD5N40 SERVICE PARTS

MDT5N25 & MTD5N40 SERVICE PARTS MDTN & MTDN0 SERVICE PARTS This parts list contains the service parts and wiring diagrams for this model. Check the model number of the machine requiring the parts to be sure that this is the correct parts

More information

LOAD BANK PART NUMBER / OPERATIONS AND MAINTENANCE MANUAL

LOAD BANK PART NUMBER / OPERATIONS AND MAINTENANCE MANUAL LOAD BANK PART NUMBER 2004297/2004298 OPERATIONS AND MAINTENANCE MANUAL Prepared by: 5455 N River RD W Geneva, OH 44041 Phone: 1-800-969-8527 TechSupport@get-psi.com HDT 1 TM-2004297/2004298 TABLE OF CONTENTS

More information

DC INVERTER MULTI-SYSTEM AIR CONDITIONER

DC INVERTER MULTI-SYSTEM AIR CONDITIONER TECHNICAL & SERVICE MANUAL OUTDOOR UNIT : CM97 CM7 CM7 FILE NO. Destination: North America DC INVERTER MULTI-SYSTEM AIR CONDITIONER Capacity at 0V 9,700 BTU/h,00 BTU/h 0,600 BTU/h Outdoor Model No. CM97

More information

Fast Track Troubleshooting

Fast Track Troubleshooting Model: FX510BGS/XAA FX710BGS/XAA WARNING Fast Track Troubleshooting IMPORTANT SAFETY NOTICE For Technicians Only This service data sheet is intended for use by persons having electrical, electronic, and

More information

MAC-120HE-01 Air-Cooled Chiller

MAC-120HE-01 Air-Cooled Chiller MAC-120HE-01 Air-Cooled Chiller 10 Ton / 120,000 BTUH Air-Cooled Chiller 208/230-1-50/60 1 HVAC Guide Specifications Air-Cooled Liquid Chiller Nominal Size: 10 Tons Multiaqua Model Number: MAC-120HE-01

More information

REFRIGERATION COMPRESSED AIR DRYER GRF SERIES NON-CYCLING OWNER / OPERATOR MANUAL

REFRIGERATION COMPRESSED AIR DRYER GRF SERIES NON-CYCLING OWNER / OPERATOR MANUAL Great Lakes Air Products Inc. 5861 Commerce Drive Westland, MI 48185 PH: 734-326-7080 FX 734-326-5910 www.glair.com REFRIGERATION COMPRESSED AIR DRYER GRF SERIES NON-CYCLING OWNER / OPERATOR MANUAL Introduction

More information

Engineering Specifications

Engineering Specifications Engineering Specifications NORDIC W-85-H-B-*S-PD Water to Water Heat Pump Single-Stage R134a Nominal 7.5 Ton With Double Wall Condenser for Domestic Hot Water Production Maritime Geothermal Ltd. P.O. Box

More information

Application Guide. Refrigerant Piping Manual for Small Split Cooling and Heat Pump Systems SS-APG006-EN

Application Guide. Refrigerant Piping Manual for Small Split Cooling and Heat Pump Systems SS-APG006-EN Refrigerant Piping Manual for Small Split Cooling and Heat Pump Systems I Refrigerant Piping II Microchannel Units III High Rise Systems Trane and American Standard Heating & Air Conditioning Split Systems

More information

Coolant Circulating Heating System TCR Controlled Installation & Operation Manual

Coolant Circulating Heating System TCR Controlled Installation & Operation Manual Coolant Circulating Heating System TCR Controlled Installation & Operation Manual 216261-000 REV 5 Identifying Your System The HOTSTART heating system is designed for use in marine propulsion, diesel-powered

More information

SERVICE MANUAL OUTDOOR UNIT MUZ-A09NA,- 1,- U1,- U2 MUZ-A12NA,- U1 MUZ-A15NA,- U1 MUZ-A17NA,- U1 MUY-A15NA MUY-A17NA MUY-A24NA,- 1,- U1,- U2

SERVICE MANUAL OUTDOOR UNIT MUZ-A09NA,- 1,- U1,- U2 MUZ-A12NA,- U1 MUZ-A15NA,- U1 MUZ-A17NA,- U1 MUY-A15NA MUY-A17NA MUY-A24NA,- 1,- U1,- U2 SPLIT-TYPE AIR CONDITIONERS Revision E: MUZ-GA24NA and MUY-GA24NA have been added. Please void OB451 REVISED EDITION-D. OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OB451 REVISED EDITION-E Models MUZ-A09NA,-

More information