1 4TTM3-SF-1 Service Facts Split System Cooling 4TTM3018-4TTM3060! CAUTION UNIT CONTAINS R-410A REFRIGERANT! R-410A OPERATING PRESSURE EXCEEDS THE LIMIT OF R-22. PROPER SERVICE EQUIPMENT IS REQUIRED. FAILURE TO USE PROPER SERVICE TOOLS MAY RESULT IN EQUIPMENT DAMAGE OR PERSONAL INJURY. SERVICE USE ONLY R-410A REFRIGERANT AND APPROVED POE COMPRESSOR OIL. IMPORTANT This document contains a wiring diagram, a parts list, and service information. This is customer property and is to remain with this unit. Please return to service information pack upon completion of work. WARNING: HAZARDOUS VOLTAGE - DISCONNECT POWER and DISCHARGE CAPACITORS BEFORE SERVICING THIS INFORMATION IS INTENDED FOR USE BY INDIVIDUALS POS SES S ING ADEQUATE BACKGROUNDS OF ELECTRICAL AND MECHANICAL EXPERIENCE. ANY ATTEMPT TO REPAIR A CEN- TRAL AIR CONDITION ING PRODUCT MAY RESULT IN PERSONAL INJURY AND OR PROPERTY DAMAGE. THE MANUFACTURER OR SELLER CANT BE RESPON SIBLE FOR THE INTERPRETATION OF THIS INFORMATION, R CAN IT ASSUME ANY LIABILITY IN CONNECTION WITH ITS USE. RECONNECT ALL GROUNDING DEVICES. ALL PARTS OF THIS PRODUCT CAPABLE OF CONDUCTING ELECTRICAL CURRENT ARE GROUNDED. IF GROUNDING WIRES, SCREWS, STRAPS, CLIPS, NUTS OR WASHERS USED TO COMPLETE A PATH TO GROUND ARE REMOVED FOR SERVICE, THEY MUST BE RETURNED TO THEIR ORIGINAL POSITION AND PROPERLY FASTENED. CONTAINS REFRIGERANT!! WARNING! CAUTION! CAUTION SYSTEM CONTAINS OIL AND REFRIGERANT UNDER HIGH PRESSURE. RECOVER REFRIGERANT TO RELIEVE PRESSURE BEFORE OPENING SYSTEM. Failure to follow proper procedures can result in personal illness or injury or severe equipment damage. TICE: The manufacturer has a policy of continuous product and product data improvement and it reserves the right to change design and specifications without notice. Trane /11
2 OUTDOOR UNIT 12 POWER CONNS. V/PH/HZ 3 MIN. BRCH. CIR. AMPACITY BR. CIR. PROT. RTG. - MAX. (AMPS) COMPRESSOR. USED -. SPEEDS VOLTS/PH/HZ R.L. AMPS 7 - L.R. AMPS FACTORY INSTALLED START COMPONENTS 8 INSULATION/SOUND BLANKET COMPRESSOR HEAT OUTDOOR FAN DIA. (IN.) -. USED TYPE DRIVE -. SPEEDS 0.0 IN. W.G. 4. MOTORS - HP MOTOR SPEED R.P.M. VOLTS/PH/HZ F.L. AMPS OUTDOOR COIL FACE AREA (SQ. FT.) REFRIGERANT LBS. R-410A (O.D. UNIT) 5 FACTORY SUPPLIED LINE SIZE - IN. O.D. GAS 6 LINE SIZE - IN. O.D. LIQ. 6 3/8 CHARGING SPECIFICATION - See Charging Section DIMENSIONS CRATED (IN.) WEIGHT SHIPPING (LBS.) NET (LBS.) PRODUCT SPECIFICATIONS 4TTM3024A1000B TTM3018A1000B PROPELLER DIRECT / / LBS., 3 OZ. 5/8 H X W X D 32-3/8 x 24-3/4 x 26-3/ PROPELLER DIRECT / / LBS., 11 OZ. 5/8 3/8 H X W X D 32-3/8 x 24-3/4 x 26-3/ TTM3030A1000B -U PROPELLER DIRECT / / LBS., 2 OZ. 3/4 3/8 H X W X D 32-3/8 x 24-3/4 x 26-3/ TTM3036A1000B PROPELLER DIRECT / / LBS., 5 OZ. 3/4 3/8 H X W X D 32-3/8 x 24-3/4 x 26-3/ OUTDOOR UNIT 12 POWER CONNS. V/PH/HZ 3 MIN. BRCH. CIR. AMPACITY BR. CIR. PROT. RTG. - MAX. (AMPS) COMPRESSOR. USED -. SPEEDS VOLTS/PH/HZ R.L. AMPS 7 - L.R. AMPS FACTORY INSTALLED START COMPONENTS 8 INSULATION/SOUND BLANKET COMPRESSOR HEAT OUTDOOR FAN DIA. (IN.) -. USED TYPE DRIVE -. SPEEDS 0.0 IN. W.G. 4. MOTORS - HP MOTOR SPEED R.P.M. VOLTS/PH/HZ F.L. AMPS OUTDOOR COIL FACE AREA (SQ. FT.) REFRIGERANT LBS. R-410A (O.D. UNIT) 5 FACTORY SUPPLIED LINE SIZE - IN. O.D. GAS 6 LINE SIZE - IN. O.D. LIQ. 6 CHARGING SPECIFICATION - See Charging Section DIMENSIONS CRATED (IN.) WEIGHT SHIPPING (LBS.) NET (LBS.) 4TTM3042A1000B PROPELLER 23-1 DIRECT / / LBS., 0 OZ. 7/8 3/8 H X W X D 32-3/8 x 29-3/4 x 30-1/ TTM3048A1000B PROPELLER 23-1 DIRECT / / LBS., 13 OZ. 7/8 3/8 H X W X D 32-3/8 x 29-3/4 x 30-1/ TTM3060A1000B PROPELLER 23-1 DIRECT / / LBS., 13 OZ. 7/8 3/8 H X W X D 32-3/8 x 29-3/4 x 30-1/ Certified in accordance with the Air-Source Unitary Air-conditioner Equipment certification program, which is based on A.H.R.I. standard 210/ Rated in accordance with A.H.R.I. standard Calculated in accordance with Natl. Elec. Codes. Use only HACR circuit breakers or fuses. 4 Standard Air Dry Coil Outdoor 5 This value approximate. For more precise value see unit nameplate. 6 Max. linear length 100 ft.; Max. lift - Suction 60 ft.; Max lift - Liquid 60 ft. 7 This value shown for compressor RLA on the unit nameplate and on this specification sheet is used to compute minimum branch circuit ampacity and max. fuse size. The value shown is the branch circuit selection current. 8 No means no start components. Yes means quick start kit components. PTC means positive temperature coefficient starter. 2 4TTM3-SF-1
3 REFRIGERANT CIRCUIT FIELD INSTALLED DRIER, SHIPS WITH UNIT 4TTM3-SF-1 3
4 System Charge Adjustment This system cannot be appropriately charged by subcooling. This new charging procedure helps prevent over charging. It is important to follow these instructions. You will need to measure the Outdoor Ambient temperature, the Suction Line Pressure (PSIG), The Liquid Temperature and the Liquid Pressure. You will charge to the MINIMUM Liquid Temperature or Maximum Liquid Line Pressure, whichever is reached first. STEP 1 - Check the indoor and outdoor ambient temperatures. Manual Charge Assist Hookup Leave bottle closed until ready to charge The Outdoor Ambient Temperature should be above 60ºF. If if the Outdoor Ambient temperature is below 60ºF then charge to 60ºF temperature and 115 Suction Line Pressure (PSIG) on the charging charts. The unit will be under charged and you will have to return when charging can be accurately performed. The Indoor Ambient Temperature must be kept between 70ºF to 100ºF. Raise the indoor temperature if needed, one method of increasing the indoor temperature is to run the furnace. Decrease the indoor temperature if needed, If the Indoor Ambient Temperature is above 100 ºF, operate the system to decrease the indoor temperature. 125ºF 60ºF Outdoor Temp 100ºF 70ºF Indoor Temp STEP 2 - Stabilize the system. Operate the system in cooling mode for a minimum of ten (10) minutes. Important: Whenever charge is removed or added, the system must be operated for a minimum of ten (10) minutes to stabilize before accurate measurements can be made. 10 MIN. If Suction Line Pressure is below 115 PSIG the system may experience fluctuations in pressures and temperatures due to expansion valve hunting. 4 4TTM3-SF-1
5 Example This system cannot be appropriately charged by subcooling. This new charging procedure helps prevent over charging. It is important to follow these instructions. You will need to measure the Outdoor Ambient temperature, the Suction Line Pressure (PSIG), The Liquid Temperature and the Liquid Pressure. You will charge to the MINIMUM Liquid Temperature or Maximum Liquid Line Pressure, whichever is reached first. This example demonstrates how to obtain your Target (MINIMUM) Liquid Temperature or Maximum Liquid Pressure using the instructions and tables provided on the following pages. 1. Identify the chart that applies to your outdoor unit model number. 2. Find the Measured Outdoor Ambient Temperature along the top of the chart. For this example the Measured Outdoor Ambient Temperature is 97 ºF. 4TTM3060A Locate the Measured Suction Pressure along the left side of the chart. For this example the Measured Suction Pressure is 130 PSIG. 4TTM3060A Determine the Target (MINIMUM) Liquid Temperature at the intersection of the Measured Suction Pressure and the Measured Outdoor Ambient Temperature. 4TTM3060A If intersection falls between two listed temperatures on the table you will need to estimate Find the Maximum Allowable Liquid Pressure. If intersection falls between two listed pressures on the table you will need to estimate. 4TTM3060A Target (MINIMUM) Liquid Temperature = 107ºF 414 Maximum Allowable Liquid Pressure = 414 PSIG 4TTM3-SF-1 5
6 STEP 3 - Measure Outdoor Ambient air temperature entering coil. Outdoor Ambient air temperature = F 6 STEP 4 - Measure Suction Line and Liquid line pressures Suction Line Pressure = PSIG Liquid Line Pressure = PSIG Note: If Suction Line Pressure is below 115 PSIG the system may experience fluctuations in pressures and temperatures due to expansion valve hunting. If fluctuations in Suction Line Pressure are noted then use the average PSIG. Manual Charge Assist Hookup Leave bottle closed until ready to charge STEP 5 - Determine the Liquid Line Temperature Attach a K-type temperature probe to the Liquid Line close to the Liquid Line Service Valve. The probe must be insulated. Insulation Measured Liquid Line Temp = ºF 107 F 6 4TTM3-SF-1
7 STEP 6 - Determine Target (MINIMUM) Liquid Temperature 1. Identify the table that applies to your outdoor unit model number. 2. Find the Measured Outdoor Ambient Temperature from Step 3 along the top of the table. If the Outdoor Ambient is below 60 ºF use the 60 ºF temperature on the table. 3. Locate the Measured Suction Pressure from Step 4 along the left side of the table. If system suction PSIG is below 115, use the 115 pressure on the table. 4. Determine the Target (MINIMUM) Liquid Temperature at the intersection of the Measured Suction Pressure and the Measured Outdoor Ambient Temperature. If intersection falls between two listed temperatures on the table you will need to estimate. 5. Locate the Maximum Allowable Liquid Pressure along the bottom of the table. If intersection falls between two listed pressures on the table you will need to estimate. Target (MINIMUM) Liquid Temperature = ºF Maximum Allowable Liquid Pressure = PSIG The following pages contain the charging tables needed for these steps. 4TTM3-SF-1 7
8 Charging Tables 4TTM3018A1 4TTM3024A1 4TTM3030A1 4TTM3036A1 8 4TTM3-SF-1
9 Charging Tables 4TTM3042A1 4TTM3048A1 4TTM3060A1 4TTM3-SF-1 9
10 STEP 7 - Determine Required Refrigerant Adjustment Compare the Measured Liquid Line Temperature from Step 4 against the Target (MINIMUM) Liquid Temperature from Step 6. If the Measured Liquid Line Temperature is above the Target (MINIMUM) Liquid Temperature and the Maximum Allowable Liquid Pressure has not been exceeded, you will add charge to the system. If the Measured Liquid Line Pressure is higher than the Maximum Allowable Liquid Pressure, you will remove charge. If the Measured Liquid Line Temperature is lower than the Target (MINIMUM) Liquid Temperature, you will remove charge. STEP 8 - Add or Remove System Charge Add system charge If step 7 above indicates to add charge: 1. Connect charging hose from bottle to charging port (bottle first). 2. Purge hose at bottle fitting. 3. Open bottle and turn upside down. Once the Measured Liquid Line Temperature is within 1 to 2 ºF of the Target (MINIMUM) Liquid Temperature, stop charging. As the charge level in the unit increases, Suction Pressure might increase slightly and Liquid Line temperature will decrease. Note: The manual charge assist port allows you to charge the unit using liquid. Manual Charge Assist Hookup Leave bottle closed until ready to charge Important: Charging must be performed using the manual charge assist port for accurate charging. Remove system charge If the Measured Liquid Line Pressure is higher than the Maximum Allowable Liquid Pressure or if the Measured Liquid Line Temperature is lower than the Target (MINIMUM) Liquid Temperature, recover refrigerant from the system. 10 4TTM3-SF-1
11 STEP 9 - Verify Refrigerant Adjustment Run system for ten (10) minutes. Check new Suction Pressure and Liquid Line Temperature. Measured Liquid Line Temperature = ºF Measured Suction Line Pressure = PSIG Measured Liquid Line Pressure = PSIG 10 MIN. If the current Measured Suction Pressure is different than the previous Measured Suction Pressure measured in Step 4, repeat Steps 5-8 and locate the new Target (MINIMUM) Liquid Temperature and Maximum Allowable Liquid Pressure using the table. Adjust charge if required. STEP 10 - Record System Information Record system pressures and temperatures after charging is complete. Outdoor model number = Measured Outdoor Ambient = ºF Measured Indoor Ambient = ºF Measured Liquid Line Temp = ºF Measured Suction Line Temp = ºF Liquid Gage Pressure = PSIG Suction Gage Pressure = PSIG 4TTM3-SF-1 11
12 SCHEMATIC DIAGRAM D156583P01Rev TTM3-SF-1
13 WIRING DIAGRAM D156583P01Rev01 4TTM3-SF-1 13
14 TROUBLESHOOTING Compressor fails to start Contactor check Is contactor energized? (contacts closed) Go To: Compressor won t run Check for 24 volts AC across contactor coil Is voltage present at contactor coil? Replace contactor Check control transformer and control fuse Is the control transformer and fuse good? Jumper R to Y low voltage terminals at thermostat sub base. Does the contactor energize? Replace the room thermostat Repair or replace transformer or fuse. Investigate cause for failure (possible short in field wiring) Repair or replace connecting wiring Single Pole Contactor (MS)* Double Pole Contactor (MS)* OUT T2 T1 T2 T1 OUT HIGH VOLTAGE Contactor Coil 24 VAC HIGH VOLTAGE IN L2 L1 L2 L1 IN *Refer to Wiring Diagram to determine if a single pole or double pole contactor is used. 14 4TTM3-SF-1
15 TROUBLESHOOTING Compressor won t run Contactor is closed Check for high voltage to contactor Is high voltage present at T1 and T2? Check for open IOL (Internal Overload) Check resistance of C to S and C to R Check power supply from disconnect and/or breaker panel. Does the resistance check show an open circuit from C to S or C to R? Allow compressor time to cool and re-test Check for open windings. Does a resistance check show an open circuit between R and S? Replace the compressor Check for locked rotor Is voltage present at C to S and C to R with locked rotor amps on C? Check Start- Capacitor and Relay (if present) and Run Capacitor Check wiring to compressor C, S and R Do the start components and run capacitor check good? Replace the compressor Replace start components and/ or run capacitor 4TTM3-SF-1 15
16 6200 Troup Highway Tyler, TX /11 The manufacturer has a policy of continuous product and product data improvement and it reserves the right to change design and specifications without notice.
Product Data. Split System Cooling 22-1904-1F-EN. March 2015
Product Data Split System Cooling 4TTR4018L1000A 4TTR4024L1000A 4TTR4025L1000A 4TTR4030L1000A 4TTR4031L1000A 4TTR4036L1000A 4TTR4037L1000A 4TTR4042L1000A 4TTR4043L1000A 4TTR4048L1000A 4TTR4060L1000A Note:
More informationSplit System Cooling Product Data
Split System Cooling Product XL16i 1½ 5 Tons PUB. NO. 22-1890-01 Features and Benefits Climatuff compressor Efficiency up to 16.0 SEER and 9.0 HSPF All aluminum Spine Fin coil WeatherGuard fasteners Quick-Sess
More informationSplit System Cooling Product Data
Split System Cooling Product Data 4TTB3018-060 1½ 5 Tons PUB. NO. 22-1843-14 Features and Benefits Efficiency up to 13.25 SEER All aluminum Spine Fin coil WeatherGuard fasteners Quick-Sess cabinet, easy
More informationSplit System Heat Pump Product Data
Split System Heat Pump Product Silver 14 4A6H4 1 1 /2-5 Tons PUB. NO. 12-1175-07 Contents Features and Benefits 2 Model Nomenclature 3 General 4 Product Specifications 4 A-weighted Sound Power Level [db(a)]
More informationSplit System Cooling Product Data
Split System Cooling Product Data XR17 4TTR7 2, 3, 4 & 5 Tons PUB. NO. 22-1884-01 Features and Benefits CLIMATUFF 2-stage scroll compressor Efficiency up to 18.0 SEER All Aluminum SPINE FIN coil DURATUFF
More informationSplit System Heat Pump Product Data
Split System Heat Pump Product Data XL20i 4TWZ0024, 036, 048 & 060 with ComfortLink II and Charge Assist 2, 3, 4 & 5 Tons PUB. NO. 22-1826-01 Features and Benefits Two Climatuff compressors Efficiency
More informationSplit System Cooling Product Data
Split System Cooling Product Data Three Phase 4TTA3 2½ 5 Tons PUB. NO. 22-1791-12 Features and Benefits All aluminum Spine Fin coil WeatherGuard fasteners Quick-Sess cabinet, service access and refrigerant
More informationSplit System Heat Pump Product Data
Split System Heat Pump Product Data XR 13 4TWR3018-060 1½ 5 Tons PUB. NO. 22-1795-12 Features and Benefits Climatuff compressor All aluminum Spine Fin coil Quick-Sess cabinet, service access and refrigerant
More information10ACC WARNING WARNING. Service Literature 10ACC SERIES UNITS
Service Literature ACC SERIES UNITS ACC Corp. 0201 L1 Revised 08 2004 The ACC is a residential split-system condensing unit available in sizes ranging from 1 1/2 to 5 tons. Condensing coil size, circuiting
More informationSplit System Cooling Product & Performance Data
Split System Cooling Product & Performance Data XR 13 4TTR3018-060 1½ 5 Tons PUB. NO. 22-1790-02-2607 (EN) Features and Benefits Climatuff compressor Efficiency up to 14.00 SEER All aluminum Spine Fin
More informationSplit System Heat Pump Product Data
Split System Heat Pump Product Three Phase 4TWA3030A3000C 4TWA3030A4000C 4TWA3036A3000C 4TWA3036A4000C 4TWA3042B3000A 2½ 5 Tons 4TWA3042B4000A 4TWA3048A3000C 4TWA3048A4000C 4TWA3060B3000A 4TWA3060B4000A
More informationCooling/Heat Pump Convertible Air Handlers
Cooling/Heat Pump Convertible Air Handlers 2/4TEC3F18-60A1000A 1½ 5 Ton PUB. NO. 22-1774-01-0905 (EN) Features and Benefits 13.0 SEER Ships horizontal converts to vertical by standing unit on end. Six-way
More informationChapter 5. Components, Symbols, and Circuitry of Air-Conditioning Wiring Diagrams
Chapter 5 Components, Symbols, and Circuitry of Air-Conditioning Wiring Diagrams Objectives Upon completion of this course, you will be able to: Explain what electrical loads are and their general purpose
More informationTECHNICAL SUPPORT MANUAL 3 Phase Air Conditioner Component R2A3**GHR
3 Phase Air Conditioner Component R2A3**GHR DANGER, WARNING, CAUTION, and NOTE The signal words DANGER, WARNING, CAU- TION, and NOTE are used to identify levels of hazard seriousness. The signal word DANGER
More information543-0032-00, 943-0032-00. User s Manual
543-0032-00, 943-0032-00 User s Manual 1 Comfort Alert Diagnostics Faster Service And Improved Accuracy The Comfort Alert diagnostics module is a breakthrough innovation for troubleshooting heat pump and
More informationREFRIGERATED TYPE COMPRESSED AIR DRYERS INSTRUCTION MANUAL. For Sales & Service please contact:
7610.478.16 8/99 INSTRUCTION MANUAL Models 8005, 8010, 8015 For Sales & Service please contact: CENTRAIR Air Systems & Supplies Phone: 705-722-5747 Fax: 705-722-5458 Email: sales@centrair.ca Website: www.centrair.ca
More informationSERVICE MANUAL FOR 6535 SERIES TWO TON HIGH EFFICIENCY PACKAGED HEAT PUMPS
SERVICE MANUAL FOR 6535 SERIES TWO TON HIGH EFFICIENCY PACKAGED HEAT PUMPS TABLE OF CONTENTS 1. Warnings...2 2. Accessibility Of Appliance...3 3. Unit Dimensions And Specifications...3 4. Unit Specifications
More informationLOBOY 16 AIR CONDITIONERS
INSTRUCTION MANUAL FOR: LOBOY 16 AIR CONDITIONERS McLean Midwest Corp. dba: McLean Cooling Technology 11611 Business Park Blvd. N Champlin, MN 55316 Tel: 763-323-8200 Fax: 763-576-3200 www.mcleancoolingtech.com
More informationT-SERIES Air Conditioners. T70, 3 Ton and 5 Ton Models INSTRUCTION MANUAL. Rev. H 2013 Pentair Equipment Protection P/N 10-1008-177
T-SERIES Air Conditioners T70, 3 Ton and 5 Ton Models INSTRUCTION MANUAL Rev. H 2013 Pentair Equipment Protection P/N 10-1008-177 88043249 TABLE OF CONTENTS RECEIVING THE AIR CONDITIONER...3 HANDLING AND
More informationTWE+TTA TWE+TWA 6.25-20 T.R.
TWE+TTA TWE+TWA 6.25-20 T.R. Main features : TWE indoor unit : Convertible cabinet, vertical or horizontal. Adjustable speed pulley-belt drive centrifugal fan motor. Aluminium fin coil with copper-tubes.
More informationFLORIDA STATE COLLEGE AT JACKSONVILLE NON-COLLEGE CREDIT COURSE OUTLINE
Form 2B, Page 1 FLORIDA STATE COLLEGE AT JACKSONVILLE NON-COLLEGE CREDIT COURSE OUTLINE COURSE NUMBER: ACR 0100 COURSE TITLE: PREREQUISITE(S): COREQUISITE(S): Basic Electricity and Schematics None None
More informationOwners Manual. Refrigerated Air Dryer. HX75 thru HX2400
Owners Manual Refrigerated Air Dryer HX75 thru HX2400 IMPORTANT: READ THIS MANUAL CAREFULLY. IT CONTAINS INFORMATION ABOUT SAFETY AND THE SAFETY OF OTHERS. ALSO BECOME FAMILIAR WITH THE PROPER INSTALLATION
More informationCOMPRESSOR REPLACEMENT PROCEDURE
COMPRESSOR REPLACEMENT PROCEDURE Bard Manufacturing Company Bryan, Ohio 43506 Since 1914...Moving ahead just as planned Manual No.: 2100-003E Supersedes 2100-003D File: Volume I, Tab 1 Date: 06-25-02 Copyright
More informationSERVICE MANUAL MUZ-GE09NA MUZ-GE12NA MUZ-GE15NA MUZ-GE18NA MUZ-GE24NA MUY-GE09NA MUY-GE12NA MUY-GE15NA MUY-GE18NA MUY-GE24NA OUTDOOR UNIT
SPLIT-TYPE AIR CONDITIONERS Revision B: Descriptions regarding the outdoor fan motor have been corrected. Please void OBH549 REVISED EDITION-A. OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OBH549 REVISED
More informationUser s Information/Installation Instructions
Outdoor Heat Pump User s Information/Installation Instructions 13 SEER R-410A High Efficiency Split System These units have been designed and tested for capacity and effi ciency in accordance with A.R.I.
More informationSPLIT-SYSTEM CONDENSING UNITS. 10.00 SEER HRA018 thru 060 (1.5 thru 5 Nominal Tons) DESCRIPTION FEATURES
550.46 -TG1Y (196) SPLIT-SYSTEM CONDENSING S 0 SEER HRA018 thru 060 (1.5 thru 5 Nominal Tons) DESCRIPTION The HRA Series condensing unit is the outdoor part of a versatile system of air conditioning. It
More informationCustomized Assessment Blueprint
Customized Assessment Blueprint HVAC Installer Basic - Test Codes: 7906 and 7796 Measuring What Matters Competencies and Skills Tested in this Assessment: HVAC Theory Heat Theory and Refrigeration HVAC
More informationModel No. XP13 018 XP13 024 XP13 030 XP13 036 XP13 037 XP13 042 XP13 048 XP13 060 Data Nominal Tonnage 1.5 2 2.5 3 3+ 3.5 4 5 Connections (sweat)
Service Literature Corp. 0528 L10 Revised 05 2008 XP13 SERIES UNITS XP13 The XP13 is a high efficiency residential split system heat pump unit, which features a scroll compressor and R 410A refrigerant.
More informationINSTALLATION INSTRUCTIONS Fan Coil Replacement Coil Kit EBX & EBXX
Fan Coil Replacement Coil Kit EBX & EBXX These instructions must be read and understood completely before attempting installation. These instructions covers the installation of replacement coil kit into
More informationSUBJECT: How to wire a motor starter Number: AN-MC-004 Date Issued: 2/08/2005 Revision: Original
SUBJECT: How to wire a motor starter Number: AN-MC-004 Date Issued: 2/08/2005 Revision: Original A motor starter is a combination of devices to allow an induction motor to start, run and stop according
More informationTECHNICAL DATA & SERVICE MANUAL SPLIT SYSTEM AIR CONDITIONER INDOOR UNIT: AW52AL AW64AL AW52AL 387030095 AW64AL 0.8180.463.0 07/05
TECHNICAL DATA & SERVICE MANUAL INDOOR UNIT: AW52AL AW64AL SPLIT SYSTEM AIR CONDITIONER Model No. Product Code No. AW52AL 387030095 AW64AL 387030096 0.8180.463.0 07/05 IMPORTANT! Please read before installation
More informationtechnical data air conditioning systems RXS20-25-35E (single phase) FBQ-B8V1-B8V3B Split Heat Pump Condensing Units Split Sky Air
technical data RXS20-25-35E FBQ-B8V-B8V3B (single phase) Split Heat Pump Condensing Units air conditioning systems Split Sky Air Outdoor Units R-40A RXS-E2VB Split Sky Air Outdoor Units Features O u t
More informationE2 Series Electric Furnaces
E2 Series Electric Furnaces Service Manual Table of Contents Electrical Requirements... 10 Codes, Specifications Requirements... 10 Connection Supply Service Wires... 10 Furnace Sequence of Operation...
More informationTEST REPORT #44. System Drop-in Tests of Refrigerant R-32 in Single Packaged Vertical Heat Pump (SPVH)
Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP) TEST REPORT #44 System Drop-in Tests of Refrigerant R-32 in Single Packaged
More informationMAC-120HE-01 Air-Cooled Chiller
MAC-120HE-01 Air-Cooled Chiller 10 Ton / 120,000 BTUH Air-Cooled Chiller 208/230-1-50/60 1 HVAC Guide Specifications Air-Cooled Liquid Chiller Nominal Size: 10 Tons Multiaqua Model Number: MAC-120HE-01
More informationSECTION 15750 PACKAGED ROOFTOP AIR CONDITIONING UNITS
SECTION 15750 PART 1 - GENERAL 1.01 DESCRIPTION A. Section includes requirements for roof mounted, self-contained units, with electric cooling, and electric or reverse refrigeration cycle (heat pump) heating
More informationTECHNICAL & SERVICE MANUAL WINDOW TYPE AIR CONDITIONER SA 79G SA 99G FILE NO. SA 79G SA 99G REFERENCE NO. SM700402
TECHNICAL & SERVICE MANUAL SA 79G SA 99G FILE NO. WINDOW TYPE AIR CONDITIONER Model No. Product Code No. Destination SA-79G-A 1 851 005 18 General (50Hz) & Europe SA-99G-A 1 851 005 19 SA 79G SA 99G REFERENCE
More informationSERVICE MANUAL OUTDOOR UNIT MUZ-A09NA,- 1,- U1,- U2 MUZ-A12NA,- U1 MUZ-A15NA,- U1 MUZ-A17NA,- U1 MUY-A15NA MUY-A17NA MUY-A24NA,- 1,- U1,- U2
SPLIT-TYPE AIR CONDITIONERS Revision E: MUZ-GA24NA and MUY-GA24NA have been added. Please void OB451 REVISED EDITION-D. OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OB451 REVISED EDITION-E Models MUZ-A09NA,-
More informationSplit Systems Cooling Condensers
Installation Operation Maintenance Split Systems Cooling Condensers 7½ - 20 Tons Model Numbers: TTA090A***F (60 Hz) TTA075AD**F (50 Hz) TTA155BD**F (50 Hz) TTA120A***F (60 Hz) TTA085AD**F (50 Hz) TTA155CD**G
More informationService manual. Website: www.andico.com.au CAUTION - BEFORE SERVICING THE UNIT, READ THE SAFETY - PRECAUTIONS IN THIS MANUAL.
Website: www.andico.com.au Service manual CAUTION - BEFORE SERVICING THE UNIT, READ THE SAFETY - PRECAUTIONS IN THIS MANUAL. - ONLY FOR AUTHORISED SERVICE PERSONNEL. MODELS: MPK1-09CR-QB8 MPK1-12ER-QB6
More informationSECTION 4 ELECTRIC MOTORS UNIT 17: TYPES OF ELECTRIC MOTORS
SECTION 4 ELECTRIC MOTORS UNIT 17: TYPES OF ELECTRIC MOTORS UNIT OBJECTIVES After studying this unit, the reader should be able to Describe the different types of open single-phase motors used to drive
More informationSkills Canada National Competition Instructions and Competition Details 38 Refrigeration and Air Conditioning / Post - Secondary May 27-30, 2015 -
Skills Canada National Competition Instructions and Competition Details / Post - Secondary May 27-30, 2015 - Saskatoon 1. Test Project Details This project is designed to test the range of skills used
More informationSERVICE MANUAL OUTDOOR UNIT. No. OBH590 REVISED EDITION-B. Models HFC
SPLIT-TYPE AIR CONDITIONERS Revision B: MUZ-EF25/35/42/50VE - E2 and MUZ-EF25/35VEH - E2 have been added. Please void OBH590 REVISED EDITION-A. OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OBH590 REVISED
More informationESPD8-301R MODEL ESP-D FAN COIL UNIT TROUBLESHOOTING GUIDE
ESPD8-301R MODEL ESP-D FAN COIL UNIT TROUBLESHOOTING GUIDE Protected by one or more of the following U.S. Patents (3,507,354; 3,575,234; 3,596,936; 3,605,797; 3,685,329; 4,045,977; 4,698,982; 926,673 and
More informationAir Conditioning Sign-Off Sheet
Air Conditioning Sign-Off Sheet Printed Technician Name Address Social Security Number Telephone Number City State Zip Code Install Or Verify The Accuracy Of An Air Conditioner s Installation The candidate
More informationSSB*H4. Service Literature. SSB*H4 Commercial Air Conditioner
Service Literature Corp. 0628 L5 Revised 07 2010 SSB*H4 Commercial Air Conditioner SSB*H4 The SSB*H4 is a high efficiency commercial split system condensing unit, which features a two stage scroll compressor
More informationLG Air Conditioning - Universal Split Fault Codes Sheet. Universal Split Systems
Universal Split Systems If there is a fault on any LG Universal unit, a two digit number will appear on the remote controllers led display. If the unit does not have a remote controller the fault will
More informationFailure code manual. content
Failure code manual content 一 wall split AC series 2 二 floor standing AC series. 4 三 portable AC series.. 5 四 dehumidifer 6 五 DC inverter single split series...7 六 DC inverter multi-split series 10 1 一
More informationMDT5N25 & MTD5N40 SERVICE PARTS
MDTN & MTDN0 SERVICE PARTS This parts list contains the service parts and wiring diagrams for this model. Check the model number of the machine requiring the parts to be sure that this is the correct parts
More informationDC INVERTER MULTI-SYSTEM AIR CONDITIONER
TECHNICAL & SERVICE MANUAL OUTDOOR UNIT : CM97 CM7 CM7 FILE NO. Destination: North America DC INVERTER MULTI-SYSTEM AIR CONDITIONER Capacity at 0V 9,700 BTU/h,00 BTU/h 0,600 BTU/h Outdoor Model No. CM97
More informationEngineering Specifications
Engineering Specifications NORDIC W-85-H-B-*S-PD Water to Water Heat Pump Single-Stage R134a Nominal 7.5 Ton With Double Wall Condenser for Domestic Hot Water Production Maritime Geothermal Ltd. P.O. Box
More informationCircuit breaker panel. Power supply for condensing unit. Power supply for furnace. Air handler (Furnace)
UNIT OBJECTIVES Describe the concept of year-round air conditioning List three typical year-round air conditioning system types List the five ways to condition the air Determine airflow for a cooling system
More informationInstallation Manual. Rental Services. Air Handling Units CHS-SVN01A-EN. July 2008
Installation Manual Rental Services Air Handling Units July 2008 CHS-SVN01A-EN Copyright 2008 Trane All rights reserved This document and the information in it are the property of Trane and may not be
More informationINSTALLATION AND MAINTENANCE INSTRUCTIONS 4AC16LT SERIES. Split System Air Conditioner. Save these instructions for future reference WARNING
INSTALLATION AND MAINTENANCE INSTRUCTIONS 4AC16LT SERIES Split System Air Conditioner Save these instructions for future reference WARNING The equipment covered in this manual is to be installed by trained
More informationINSTALLATION INSTRUCTIONS
2008 Lennox Industries Inc. Dallas, Texas, USA WARNING Improper installation, adjustment, alteration, service or maintenance can cause property damage, personal injury or loss of life. Installation and
More informationWhy and How we Use Capacity Control
Why and How we Use Capacity Control On refrigeration and air conditioning applications where the load may vary over a wide range, due to lighting, occupancy, product loading, ambient weather variations,
More informationPump Specifications 250 Series Submersible Sump / Effluent Pump 2 Solids handling
Pump Specifications 250 Series Submersible Sump / Effluent Pump 2 Solids handling 250_P1 R10/7/2015 Copyright 2015 Liberty Pumps Inc. All rights reserved. Specifications subject to change without notice.
More informationOil and Coolant Circulating Heating System. Model - OCSM
Oil and Coolant Circulating Heating System Model - OCSM Installation & Operation Manual 216280-000 REV 2 Identifying Your System The HOTSTART heating system is designed to heat fluids for use in marine
More informationT-Series Air Conditioner T62 Model
INSTRUCTION MANUAL T-Series Air Conditioner T62 Model Protecting Electronics. Exceeding Expectations. McLean Cooling Technology 11611 Business Park Blvd N Champlin, MN 55316 USA Tel 763-323-8200 Fax 763-576-3200
More informationAir Conditioners Technical Data
Air Conditioners Technical Data O u t d o o r U n i t E E D E N 2-0 0 RX-JV Outdoor Unit RX-JV TABLE OF CONTENTS RX-JV Features............................................................. 2 2 Specifications.......................................................
More informationSERVICE MANUAL MUZ-FE09NA MUZ-FE12NA MUZ-FE18NA OUTDOOR UNIT. No. OBH543 REVISED EDITION-A. Models HFC
SPLIT-TYPE AIR CONDITIONERS Revision A: MUZ-FE18NA has been added. Please void OBH543. OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OBH543 REVISED EDITION-A Models MUZ-FE09NA MUZ-FE12NA MUZ-FE18NA Indoor
More informationAFE424 SERVICE PARTS
This is the parts list for the AFE. When looking up part numbers, always check the complete model and serial numbers to be certain of ordering the correct parts. The Air Cooled model has also been manufactured
More informationTable V. Troubleshooting Checklist for Refrigeration Systems. Air or non-condensable gas in system. Inlet water warm.
Table V Troubleshooting Checklist for Refrigeration Systems TROUBLE POSSIBLE CAUSE CORRECTIVE MEASURE High condensing pressure. Low condensing pressure. Air or non-condensable gas in system. Inlet water
More informationREMOTE AIR-COOLED CONDENSERS. Installation and Maintenance Data. Models 1-26. Bulletin H-IM-73A June 2000 Part Number 90800801.
Bulletin H-IM-73A June 2000 Part Number 90800801 Replaces H-IM-73 and H-IM-74 REMOTE AIR-COOLED CONDENSERS Models 1-26 Installation and Maintenance Data Table of Contents Inspection Installation... 3-4
More informationSERVICE MANUAL MUZ-GE25VA - E1 MUZ-GE25VAH - E1 MUZ-GE35VA - E1 MUZ-GE35VAH - E1 MUZ-GE42VA - E1 MUZ-GE42VAH - E1 MUZ-GE50VA - E1 MUZ-GE50VAH - E1
SPLIT-TYPE AIR CONDITIONERS Revision A: MUZ-GE42/50VA(H) - E1 has been added. Please void OBH516. OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OBH516 REVISED EDITION-A Models MUZ-GE25VA - E1 MUZ-GE25VAH
More informationLG Air Conditioning Multi F(DX) Fault Codes Sheet. Multi Split Units
Multi Split Units If there is a fault on any LG Multi unit, an Error mark is indicated on the display window of the indoor unit, wired-remote controller, and LED s of outdoor unit control board. A two
More informationUHIR Series. Horizontal or Vertical Mounting Industrial / Commercial Electric Unit Heater. Owner s Manual
UHIR Series Horizontal or Vertical Mounting Industrial / Commercial Electric Unit Heater Owner s Manual This manual covers installation, maintenance and repair parts. Read carefully before attempting to
More informationHeating, Ventilation, Air Conditioning and Refrigeration (HVACR)
Heating, Ventilation, Air Conditioning and Refrigeration (HVACR) I. Demonstrate safety skills in typical HVACR work situations to NATE Core Installer Knowledge Areas for Technician Excellence for Safety
More informationINSTALLATION INSTRUCTION
INSTALLATION INSTRUCTION OUTDOOR SPLIT-SYSTEM AIR CONDITIONER MODELS: 10, 12, 13 AND 14 SEER 1 PHASE - 1.5 TO 5 TONS TABLE OF CONTENTS GENERAL INFORMATION.................... 2 INSPECTION..............................
More informationXV 95. Upflow/ Horizontal Left, Downflow/ Horizontal Right Variable Speed Two Stage Condensing Gas-Fired Furnace PUB. NO.
Upflow/ Horizontal Left, Downflow/ Horizontal Right Speed Two Stage Condensing Gas-Fired Furnace XV 95 TUH2B060A9V3VB TUH2B080A9V3VB TUH2B080A9V4VB TUH2C100A9V4VB TUH2C100A9V5VB TUH2D120A9V5VB Direct Vent
More informationNO-FROST CUSTOMER SUPPORT INFORMATION INFORMATION ON THE NO-FROST TECHNOLOGY WHITE GOODS
INFORMATION INFORMATION ON THE TECHNOLOGY The -Frost refrigerators are different from the other static refrigerators in terms of their operational system. In normal refrigerators, in the freezing section,the
More informationSERVICE MANUAL SPLIT SYSTEM ROOM AIR CONDITIONER SHARP CORPORATION SHARP CORPORATION CONTENTS
SERVICE MANUAL SPLIT SYSTEM ROOM AIR CONDITIONER INDOOR UNIT AH-129 AH-MP14 OUTDOOR UNIT AU-129 AU-MP14 CONTENTS SPECIFICATIONS...2 EXTERNAL DIMENSIONS...4 WIRING DIAGRAMS...5 ELECTRICAL PARTS...6 MICROCOMPUTER
More informationTECHNICAL & SERVICE MANUAL SPLIT SYSTEM AIR CONDITIONER + SAP C181MA + SAP C181GA + SAP C181BA + SAP C241MA + SAP C241BA FILE NO.
TECHNICAL & SERVICE MANUAL SAP K161GJA SAP K181GJA SAP K181MBA SAP K241GJA SAP K241MBA + SAP C161GA + SAP C161JA + SAP C181GA + SAP C181JA + SAP C181MA + SAP C181BA + SAP C241GA + SAP C241JA + SAP C241MA
More informationARMSTRONG AIR HEAT PUMPS www.armstrongair.com
INDEX ELECTRIC FURNACE MODULAR AIR SYSTEM EFC/EFV... 5-10 electric Heat Kits... 5-11 evaporator coils EC1P / EM1P UPFLOW / COUNTERFLOW APPLICATIONS and upflow / horizontal applications (CASED)... 5-6 5-7
More informationAluminum Cased Cooling Coils 2-5 Ton 4CXC PUB. NO. 22-1839-03
Aluminum Cased Cooling Coils 2-5 Ton 4CXC PUB. NO. 22-1839-03 Aluminum Cooling Coil Nomenclature 4 C X C B 0 3 6 C C 3 C U A A Refrigerant Type 4 - R410A Product Family T-Premium (Heat Pump or Convertible
More informationWON0502-B INSTALLATION INSTRUCTIONS FOR ELECTRIC FURNACES. Bulletin 30-34 / March 2013
Bulletin 30-34 / March 2013 INSTALLATION INSTRUCTIONS FOR ELECTRIC FURNACES General The information on the following pages is to provide the installer the necessary information to properly install the
More informationInstallation and Troubleshooting Instructions for Electric Tankless Residential Water Heaters.
Model Number: Serial Number: Information Manual Installation and Troubleshooting Instructions for Electric Tankless Residential Water Heaters. ATTENTION: IF YOU ARE NOT A LICENSED PLUMBER OR A LICENSED
More informationINSTALLATION INSTRUCTIONS
2012 Lennox Industries Inc. Dallas, Texas, USA THIS MANUAL MUST BE LEFT WITH THE HOMEOWNER FOR FUTURE REFERENCE The State of California has determined that this product may contain or produce a chemical
More informationECOCIAT. Domestic hot water heat recovery unit
Heat recovery unit Domestic hot water High energy efficiency with R410A Compact and quiet Scroll compressors Brazed-plate heat exchangers Heating Heat recovery ENVIRONMENTALLY HFC R410A PROTECTION DE FRIENDLY
More informationAir-Cooled Condensers
Air-Cooled Condensers 20 to 120 Tons April 2001 Introduction Air-Cooled Condensers Built for Every Need Trane has the right condenser...if you are designing a new system or replacing an existing air-cooled
More informationPROAIR Water-Cooled Air Conditioner. CR43WC Model INSTRUCTION MANUAL. Rev. E 2013 Pentair Technical Products P/N 10-1008-167
PROAIR Water-Cooled Air Conditioner CR43WC Model INSTRUCTION MANUAL Rev. E 2013 Pentair Technical Products P/N 10-1008-167 87976466 TABLE OF CONTENTS HANDLING & TESTING THE AIR CONDITIONER...3 INSTALLATION
More informationHP switch LP switch Discharge thermo Comp. Surface thermo
1 Specifications Zubadan Model Name PUHZ-SHW80VHA PUHZ-SHW11VHA PUHZ-SHW11YHA Power supply (phase, cycle, voltage) 1φ, V, Hz 1φ, V, Hz 3φ, 0V, Hz Max. current A 9.5 35.0 13.0 Breaker size A 3 16 Outer
More informationINSTALLATION INSTRUCTIONS
2008 Lennox Industries Inc. Dallas, Texas, USA WARNING Improper installation, adjustment, alteration, service or maintenance can cause personal injury, loss of life, or damage to property. Installation
More informationPRE-ASSEMBLED REMOTE REFRIGERATION SYSTEMS
NOR-LAKE, INCORPORATED 727 Second Street P.O. Box 248 Hudson, Wisconsin 54016 800-955-5253 715-386-2323 866-961-5253 Parts 800-388-5253 Service 715-386-4291 FAX www.norlake.com Split-Pak Pre-Assembled
More informationARCO Electric Products Installation and Maintenance Manual Low Voltage Automatic Power Factor Correction Capacitor Systems 2013
ARCO Electric Products Installation and Maintenance Manual Low Voltage Automatic Power Factor Correction Capacitor Systems 2013 READ CAREFULLY These instructions are intended to cover good practices in
More informationFan Coil EC Motor Control
Fan Coil EC Motor Control G3 PWM BARD The Enviro-Tec Generation 3 PWM (G3 PWM) board provides a pulse-width modulated (PWM) signal to the EC motor to control fan speed. The board is factory programmed
More informationTest Code: 8297 / Version 1
Blueprint HVAC Maintenance Technology PA Test Code: 8297 / Version 1 Copyright 2014. All Rights Reserved. General Assessment Information HVAC Maintenance Technology PA Blueprint Contents General Assessment
More information3.0 CHARACTERISTICS. AR Auxiliary Relay High Speed, High Threshold 41-759.3C
41-759.3C the magnetic core upon energizing of the switch. When the switch closes, the moving contacts bridge two stationary contacts, completing the trip circuit. Also during this operation two fingers
More informationRecharge Procedure for Telemark TVP-2000 and TVP-3500
Recharge Procedure for Telemark TVP-2000 and TVP-3500 Required items: 1.) Refrigeration service manifold. 2.) Charge recovery system. 3.) Dry nitrogen gas. If a high pressure cylinder is used, a pressure
More informationInstalling the Tracer ZN517 Unitary Controller Ordering number: 4950 0496, 4950 0596
Installing the Tracer ZN517 Unitary Controller Ordering number: 4950 0496, 4950 0596 Product overview The Tracer ZN517 controller is a field-installed, application-specific controller that provides directdigital
More informationTechnical Information
Date of last update: Oct-11 Ref: D7.8.4/1011/E Application Engineering Europe CORESENSE DIAGNOSTICS FOR STREAM REFRIGERATION COMPRESSORS CoreSense Diagnostics for Stream Refrigeration Compressors... 1
More information0150506194 C Limited 2nd through 5th Year Functional Parts Warranty During the 2nd through 5th year,haier will provide functional parts which prove to be defective due to workmanship
More informationIndoor coil is too warm in cooling mode or too cold in heating mode. Reversing valve or coil thermistor is faulty
Codes Room Air Conditioner range: Indoor unit alarm s If timer lamp flashes for 1 second on, 1 second off, this indicates pre heating on the coil during heating mode and is not an error. If timer lamp
More informationIt will be available soon as an 8.5 X 11 paperback. For easier navigation through the e book, use the table of contents.
The System Evaluation Manual and Chiller Evaluation Manual have been revised and combined into this new book; the Air Conditioning and Refrigeration System Evaluation Guide. It will be available soon as
More informationFTQ. Daikin Inverter Ducted Heat Pump
FTQ Daikin Inverter Ducted Heat Pump A TRADITIONAL CENTRAL AIR SYSTEM MADE BETTER WITH DAIKIN CONSTANT COMFORT INVERTER TECHNOLOGY. The Daikin Inverter Ducted Heat Pump line is a cost effective alternative
More informationExplosion-Proof Electric Unit Heaters
Type FX4 FX4 Explosion-Proof Electric Air Heaters FX4 heaters are UL listed and/or CSA certified for use in hazardous locations. They are designed for dry indoor industrial applications such as oil refineries,
More informationAIR CONDITIONER INSTALLATION MANUAL
INSTALLATION MANUAL AIR CONDITIONER Please read this installation manual completely before installing the product. Installation work must be performed in accordance with the national wiring standards by
More informationA.Y. McDonald Mfg. Co. Troubleshooting Submersible and Jet Pumps
A.Y. McDonald Mfg. Co. Troubleshooting Submersible and Jet Pumps Troubleshooting Submersible Pumps Fuse overload or circuit breaker trips when motor is started 1. Incorrect line voltage. Check the line
More informationMiami Heat Pump HP Series Installation Guide
CAUTION- THIS UNIT IS FOR INDOOR USE ONLY!! WARNING BEFORE ANY INSTALLATION OR MAINTANCE IS STARTED PLEASE READ COMPLETE INSTLLATION GUIDE. INSTALLATION START-UP AND SERVICE INSTRUCTION- The HP Water Source
More informationSECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM
SECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Packaged rooftop air conditioning unit (5 tons and smaller). 2. Roof curb. 1.2
More information