SERVICE MANUAL MUZ-GE25VA - E1 MUZ-GE25VAH - E1 MUZ-GE35VA - E1 MUZ-GE35VAH - E1 MUZ-GE42VA - E1 MUZ-GE42VAH - E1 MUZ-GE50VA - E1 MUZ-GE50VAH - E1

Size: px
Start display at page:

Download "SERVICE MANUAL MUZ-GE25VA - E1 MUZ-GE25VAH - E1 MUZ-GE35VA - E1 MUZ-GE35VAH - E1 MUZ-GE42VA - E1 MUZ-GE42VAH - E1 MUZ-GE50VA - E1 MUZ-GE50VAH - E1"

Transcription

1 SPLIT-TYPE AIR CONDITIONERS Revision A: MUZ-GE42/50VA(H) - E1 has been added. Please void OBH516. OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OBH516 REVISED EDITION-A Models MUZ-GE25VA - E1 MUZ-GE25VAH - E1 MUZ-GE35VA - E1 MUZ-GE35VAH - E1 MUZ-GE42VA - E1 MUZ-GE42VAH - E1 MUZ-GE50VA - E1 MUZ-GE50VAH - E1 Indoor unit service manual MSZ-GE VA Series (OBH515) MSZ-CGE VA Series (OBH523) MUZ-GE25/35/42VA CONTENTS 1. TECHNICAL CHANGES 3 2. PART NAMES AND FUNCTIONS 4 3. SPECIFICATION 5 4. NOISE CRITERIA CURVES 7 5. OUTLINES AND DIMENSIONS 8 6. WIRING DIAGRAM 9 7. REFRIGERANT SYSTEM DIAGRAM PERFORMANCE CURVES ACTUATOR CONTROL SERVICE FUNCTIONS TROUBLESHOOTING DISASSEMBLY INSTRUCTIONS 50 PARTS CATALOG (OBB516) NOTE: RoHS compliant products have <G> mark on the spec name plate.

2 Revision A: MUZ-GE42/50VA(H) - E1 has been added. 2

3 1 TECHNICAL CHANGES MUZ-GE25VA - E1 MUZ-GE35VA - E1 MUZ-GE42VA - E1 MUZ-GE50VA - E1 1. New model MUZ-GE25VAH - E1 MUZ-GE35VAH - E1 MUZ-GE42VAH - E1 MUZ-GE50VAH - E1 3

4 2 PART NAMES AND FUNCTIONS MUZ-GE25VA MUZ-GE25VAH MUZ-GE35VA MUZ-GE35VAH MUZ-GE42VA MUZ-GE42VAH Air inlet (back and side) Piping Drain hose Air outlet Drain outlet MUZ-GE50VA MUZ-GE50VAH Air inlet (back and side) Piping Drain hose Air outlet Drain outlet (GE50VA) ACCESSORIES MUZ-GE25/35/42VA MUZ-GE50VA Drain socket 1 1 Drain cap - 2 4

5 3 SPECIFICATION Outdoor model MUZ-GE25VA MUZ-GE25VAH MUZ-GE35VA MUZ-GE35VAH MUZ-GE42VA MUZ-GE42VAH MUZ-GE50VA MUZ-GE50VAH Power supply Single phase, 230 V, 50 Hz Capacity Cooling 2.5 ( ) 3.5 ( ) 4.2 ( ) 5.0 ( ) Rated frequency (Min.-Max.) kw Heating 3.2 ( ) 4.0 ( ) 5.4 ( ) 5.8 ( ) Breaker Capacity A Power input 1 (Total) Cooling ,215 1,515 W Heating ,460 1,565 Running current 1 Cooling (Total) A Heating Power factor 1 (Total) Cooling % Heating Starting current 1 (Total) A Coeffi cient of performance Cooling (COP) 1 (Total) Heating Model KNB073FFDHC KNB092FFAHC SNB130FGBHT Output W Compressor Cooling Current 1 A Heating Refrigeration oil (Model) cc 320 (NEO22) 450 (NEO22) Model RC0J50-DB RC0J50-EA RC0J60-AA Fan motor Cooling Current 1 A Heating Dimensions W H D mm Weight kg Dehumidifi cation Cooling /h Cooling Med. 1,806 1,872 1,872 2,940 Low 1,170 1,776 1,086 1,740 Air fl ow 1 High m 3 /h 2,106 2,016 2,016 Heating Med. 1,806 1,776 1,776 2,940 Low 1,452 1,386 1,386 2,142 Sound level 1 Cooling db(a) Heating Cooling Med Low Fan speed High rpm Heating Med Low Fan speed regulator 3 2 Refrigerant fi lling capacity (R410A) kg Electrical data Special remarks NOTE: Test conditions are based on ISO Cooling: Indoor Dry-bulb temperature 27 C Wet-bulb temperature 19 C Outdoor Dry-bulb temperature 35 C Heating: Indoor Dry-bulb temperature 20 C Outdoor Dry-bulb temperature 7 C Wet-bulb temperature 6 C Refrigerant piping length (one way): 5 m 1 Measured under rated operating frequency. 5

6 Specifications and rating conditions of main electric parts Item Current transformer Smoothing capacitor Diode module Fuse Model (CT) (CT761, CT781) (C61, C62, C63) MUZ- GE25VA MUZ- GE25VAH MUZ- GE35VA 620 μf 420 V MUZ- MUZ- GE35VAH GE42VA 20 A 15 A MUZ- GE42VAH MUZ- GE50VA MUZ- GE50VAH (DB61) 15 A 600 V 25 A 600 V (DB65) 25 A 600 V (F61) T20AL250V (F701, F801, F901) T3.15AL250V Defrost heater (H) 230 V 130 W 230 V 130 W 230 V 130 W Intelligent power module (IPM) 15 A 600 V 20 A 600 V Expansion valve coil (LEV) DC 12 V Reactor (L61) 18 mh 23 mh (R61) 45 mω 5 W (1 element) 100 mω 5 W (2 elements) Currentdetecting (R61,R62) 180 mω 5 W (2 elements) (R825) 25 mω 5 W resistor (R937, R938, R939) 430 mω 2 W (R937A,R937B) 1.1 Ω 2 W Current-limiting PTC thermistor (PTC64, PTC65) 33 Ω Terminal block (TB1, TB2) 3 P (X63) 3 A 250 V Relay (X64) 20 A 250 V 230 V 120 W (X66) 3 A 250 V 3 A 250 V 3 A 250 V 3 A 250 V R.V.coil (21S4) AC V Heater protector (26H) Open 45 C Open 45 C Open 45 C Open 45 C IGBT (TR821) 30 A 600 V 6

7 4 NOISE CRITERIA CURVES MUZ-GE25VA MUZ-GE25VAH FUNCTION SPL(dB(A)) LINE COOLING 47 HEATING 48 MUZ-GE35VA MUZ-GE35VAH FUNCTION SPL(dB(A)) LINE COOLING 47 HEATING 48 OCTAVE BAND SOUND PRESSURE LEVEL, 0dB re MICRO BAR NC-70 NC-60 NC-50 NC-40 NC-30 NC-20 NC BAND CENTER FREQUENCIES, Hz OCTAVE BAND SOUND PRESSURE LEVEL, db re MICRO BAR NC-70 NC-60 NC-50 NC-40 NC-30 NC-20 NC BAND CENTER FREQUENCIES, Hz MUZ-GE42VA MUZ-GE42VAH FUNCTION SPL(dB(A)) LINE COOLING 50 HEATING 51 MUZ-GE50VA MUZ-GE50VAH FUNCTION SPL(dB(A)) LINE COOLING 54 HEATING 56 OCTAVE BAND SOUND PRESSURE LEVEL, 0dB re MICRO BAR NC-70 NC-60 NC-50 NC-40 NC-30 NC-20 NC OCTAVE BAND SOUND PRESSURE LEVEL, db re MICRO BAR NC-70 NC-60 NC-50 NC-40 NC-30 NC-20 NC BAND CENTER FREQUENCIES, Hz BAND CENTER FREQUENCIES, Hz Test conditions Cooling : Dry-bulb temperature 35 C Heating : Dry-bulb temperature 7 C Wet-bulb temperature 6 C OUTDOOR UNIT 1 m MICROPHONE 7

8 5 OUTLINES AND DIMENSIONS MUZ-GE25VA MUZ-GE25VAH MUZ-GE35VA MUZ-GE35VAH MUZ-GE42VA MUZ-GE42VAH 400 Air in Drain hole ø42 (25/35/42VA) Drain hole ø33 (25/35/42VAH) REQUIRED SPACE 100 mm or more Unit: mm Basically open 100 mm or more without any obstruction in front and on both sides of the unit. 100 mm or more Air in Bolt pitch for installation 304~ mm or more 350 mm or more holes 10 X 21 Air out Service panel Open two sides of left, right, or rear side. Handle Liquid refrigerant pipe joint Refrigerant pipe (flared) ø Service port Gas refrigerant pipe joint Refrigerant pipe (flared) ø Bolt pitch for installation 800 MUZ-GE50VA MUZ-GE50VAH Air in Drain holes ø33(50va) 40 REQUIRED SPACE Open as a rule 500 mm or more if the front and both sides are open 100 mm or more 200 mm or more if there are obstacles to both sides 330 Air in mm or more 170 Air out holes Open as a rule 500 mm or more if the back, both sides and top are open 350 mm or more Service panel 850 Liquid refrigerant pipe joint Refrigerant pipe (flared) ø Gas refrigerant pipe joint Refrigerant pipe (flared) ø12.7 8

9 6 WIRING DIAGRAM MUZ-GE25VA MUZ-GE35VA 9

10 MUZ-GE25VAH MUZ-GE35VAH 10

11 MUZ-GE42VA 11

12 MUZ-GE42VAH 12

13 MUZ-GE50VA 13

14 MUZ-GE50VAH 14

15 7 REFRIGERANT SYSTEM DIAGRAM MUZ-GE25VA MUZ-GE25VAH Unit: mm Refrigerant pipe ø9.52 (with heat insulator) 4-way valve Flared connection Muffler Stop valve (with service port) Discharge temperature thermistor RT62 Muffler Compressor Defrost thermistor RT61 Outdoor heat exchanger Outdoor heat exchanger temperature thermistor RT68 Ambient temperature thermistor RT65 Flared connection Refrigerant pipe ø6.35 (with heat insulator) Stop valve (with strainar) Capillary tube ø3.0 ø LEV Strainer #100 R.V. coil heating ON cooling OFF Refrigerant flow in cooling Refrigerant flow in heating MUZ-GE35VA MUZ-GE35VAH MUZ-GE42VA MUZ-GE42VAH Unit: mm Refrigerant pipe ø9.52 (with heat insulator) Flared connection Muffler Stop valve (with service port) 4-way valve Discharge temperature thermistor RT62 Muffler Compressor Defrost thermistor RT61 Capillary tube ø3.0 ø ( 2) Outdoor heat exchanger Outdoor heat exchanger temperature thermistor RT68 Ambient temperature thermistor RT65 Flared connection Refrigerant pipe ø6.35 (with heat insulator) Stop valve (with strainar) Capillary tube ø3.0 ø LEV Strainer #100 R.V. coil heating ON cooling OFF Refrigerant flow in cooling Refrigerant flow in heating 15

16 MUZ-GE50VA MUZ-GE50VAH Refrigerant pipe ø12.7 (with heat insulator) 4-way valve Muffler #100 Unit: mm Flared connection Stop valve (with service port) Discharge temperature thermistor RT62 Defrost thermistor RT61 Outdoor heat exchanger Ambient temperature thermistor RT65 Flared connection Refrigerant pipe ø6.35 (with heat insulator) Receiver Stop valve (with strainar) Capillary tube ø3.6 ø Compressor LEV Strainer #100 Outdoor heat exchanger temperature thermistor RT68 R.V. coil heating ON cooling OFF Refrigerant flow in cooling Refrigerant flow in heating MAX. REFRIGERANT PIPING LENGTH and MAX. HEIGHT DIFFERENCE Refrigerant piping: m Piping size O.D: mm Max. Length Max. Height difference A B Gas Liquid MUZ-GE25/35/ MUZ-GE Indoor unit Max. Height difference B Max. Length A Outdoor unit ADDITIONAL REFRIGERANT CHARGE (R410A: g) Model Outdoor unit precharged MUZ-GE MUZ-GE35/42 1,150 Refrigerant piping length (one way) 5 m 6 m 7 m 8 m 9 m 10 m 11 m 12 m 13 m 14 m 15 m 20 m Calculation: X g = 30 g/m (Refrigerant piping length (m) - 7) Model Outdoor unit precharged Refrigerant piping length (one way) 7 m 10 m 15 m 20 m 25 m 30 m MUZ-GE50 1, Calculation: X g = 20 g/m (Refrigerant piping length (m) 7) NOTE: Refrigerant piping exceeding 7 m requires additional refrigerant charge according to the calculation. 16

17 8 PERFORMANCE CURVES MUZ-GE25VA MUZ-GE25VAH MUZ-GE35VA MUZ-GE35VAH MUZ-GE42VA MUZ-GE42VAH MUZ-GE50VA MUZ-GE50VAH The standard specifications apply only to the operation of the air conditioner under normal conditions. Since operating conditions vary according to the areas where these units are installed, the following information has been provided to clarify the operating characteristics of the air conditioner under the conditions indicated by the performance curve. (1) GUARANTEED VOLTAGE 198 ~ 264 V, 50 Hz (2) AIR FLOW Air flow should be set at MAX. (3) MAIN READINGS (1) Indoor intake air wet-bulb temperature: C [WB] } (2) Indoor outlet air wet-bulb temperature: C [WB] Cooling (3) Outdoor intake air dry-bulb temperature: C [DB] (4) Total input: W (5) Indoor intake air dry-bulb temperature: C [DB] (6) Outdoor intake air wet-bulb temperature: C [WB] } Heating (7) Total input: W Indoor air wet/dry-bulb temperature difference on the left side of the following chart shows the difference between the indoor intake air wet/dry-bulb temperature and the indoor outlet air wet/dry-bulb temperature for your reference at service. How to measure the indoor air wet-bulb / dry-bulb temperature difference 1. Attach at least 2 sets of wet and dry-bulb thermometers to the indoor air intake as shown in the figure, and at least 2 sets of wet and dry-bulb thermometers to the indoor air outlet. The thermometers must be attached to the position where air speed is high. 2. Attach at least 2 sets of wet and dry-bulb thermometers to the outdoor air intake. Cover the thermometers to prevent direct rays of the sun. 3. Check that the air filter is cleaned. 4. Open windows and doors of room. 5. Press the EMERGENCY OPERATION switch once (twice) to start the EMERGENCY COOL (HEAT) MODE. 6. When system stabilizes after more than 15 minutes, measure temperature and take an average temperature minutes later, measure temperature again and check that the temperature does not change. INDOOR UNIT OUTDOOR UNIT Wet and dry-bulb thermometers FRONT VIEW 8-1. CAPACITY AND INPUT CURVES Indoor air Wet-bulb temperature difference ( C) MUZ-GE25VA MUZ-GE25VAH MUZ-GE35VA MUZ-GE35VAH MUZ-GE42VA MUZ-GE42VAH MUZ-GE50VA MUZ-GE50VAH Capacity correction factors Wet and dry-bulb thermometers BACK VIEW Cooling capacity (at Rated frequency) Indoor intake air Wet-bulb temperature( ) Outdoor intake air Dry-bulb temperature( C)

18 Total input (Cooling : at Rated frequency) Indoor air Wet-bulb temperature difference ( C) Input correction factors Indoor intake air Wet-bulb temperature( ) MUZ-GE25VA MUZ-GE25VAH MUZ-GE35VA MUZ-GE35VAH MUZ-GE42VA MUZ-GE42VAH MUZ-GE50VA MUZ-GE50VAH Outdoor intake air Dry-bulb temperature ( C) Indoor air Dry-bulb temperature difference ( C) Capacity correction factor Heating capacity (at Rated frequency) Indoor intake air Dry-bulb temperature ( ) MUZ-GE25VA MUZ-GE25VAH MUZ-GE35VA MUZ-GE35VAH MUZ-GE42VA MUZ-GE42VAH MUZ-GE50VA MUZ-GE50VAH Outdoor intake air Wet-bulb temperature ( C) Indoor air Dry-bulb temperature difference ( C) Input correction factor Total input (Heating : at Rated frequency) Indoor intake air Dry-bulb temperature ( ) MUZ-GE25VA MUZ-GE25VAH MUZ-GE35VA MUZ-GE35VAH MUZ-GE42VA MUZ-GE42VAH MUZ-GE50VA MUZ-GE50VAH Outdoor intake air Wet-bulb temperature ( C) NOTE: The above broken lines are for the heating operation without any frost and defrost operation. 18

19 8-2. CAPACITY AND INPUT CORRECTION BY OPERATIONAL FREQUENCY OF COMPRESSOR Capacity correction factors MUZ-GE25VA MUZ-GE25VAH Correction of Cooling capacity Input correction factors The operational frequency of compressor (Hz) Correction of Cooling input The operational frequency of compressor (Hz) Capacity correction factors Correction of Heating capacity The operational frequency of compressor (Hz) Input correction factors Correction of Heating input The operational frequency of compressor (Hz) Capacity correction factors MUZ-GE35VA MUZ-GE35VAH Correction of Cooling capacity The operational frequency of compressor (Hz) Input correction factors Correction of Cooling input The operational frequency of compressor (Hz) Capacity correction factors Correction of Heating capacity The operational frequency of compressor (Hz) Input correction factors Correction of Heating input The operational frequency of compressor (Hz) MUZ-GE42VA MUZ-GE42VAH Correction of Cooling capacity Correction of Cooling input Correction of Heating capacity Correction of Heating input Capacity correction factors The operational frequency of compressor (Hz) Input correction factors The operational frequency of compressor (Hz) Capacity correction factors The operational frequency of compressor (Hz) Capacity correction factors The operational frequency of compressor (Hz) MUZ-GE50VA MUZ-GE50VAH Correction of Cooling capacity Correction of Cooling input Correction of Heating capacity Correction of Heating input Capacity correction factors Input correction factors The operational frequency of compressor (Hz) The operational frequency of compressor (Hz) Capacity correction factors The operational frequency of compressor (Hz) Capacity correction factors The operational frequency of compressor (Hz) 19

20 8-3. TEST RUN OPERATION (How to operate fixed-frequency operation) 1. Press EMERGENCY OPERATION switch to start COOL or HEAT mode (COOL: Press once, HEAT: Press twice). 2. Test run operation starts and continues to operate for 30 minutes. 3. Compressor operates at rated frequency in COOL mode or 58 Hz in HEAT mode. 4. Indoor fan operates at High speed. 5. After 30 minutes, test run operation finishes and EMERGENCY OPERATION starts (operation frequency of compressor varies). 6. To cancel test run operation (EMERGENCY OPERATION), press EMERGENCY OPERATION switch or any button on remote controller OUTDOOR LOW PRESSURE AND OUTDOOR UNIT CURRENT COOL operation Both indoor and outdoor unit are under the same temperature/ humidity condition. Operation: TEST RUN OPERATION (Refer to 8-3.) Dry-bulb temperature ( C) Relative humidity (%) Outdoor low pressure MUZ-GE25VA MUZ-GE25VAH MUZ-GE35VA MUZ-GE35VAH MUZ-GE42VA MUZ-GE42VAH MPa [Gauge] kgf/cm 2 [Gauge] MPa [Gauge] kgf/cm 2 [Gauge] MPa [Gauge] kgf/cm 2 [Gauge] Ambient temperature( C) Ambient humidity(%) Ambient temperature( C) Ambient humidity(%) Ambient temperature( C) Ambient humidity(%) MUZ-GE50VA MUZ-GE50VAH MPa [Gauge] kgf/cm 2 [Gauge] Ambient temperature( C) Ambient humidity(%) NOTE: The unit of pressure has been changed to MPa on the international system of units (SI unit system) The conversion factor is: 1 (MPa [Gauge]) = 10.2 (kgf/cm 2 [Gauge]) 20

21 Outdoor unit current MUZ-GE25VA MUZ-GE25VAH Outdoor current (A) MUZ-GE35VA MUZ-GE35VAH Outdoor current (A) MUZ-GE42VA MUZ-GE42VAH Outdoor current (A) MUZ-GE50VA MUZ-GE50VAH Ambient temperature ( C) Ambient humidity(%) Ambient temperature ( C) Ambient humidity(%) Ambient temperature( C) Ambient humidity(%) 35 Outdoor current (A) Ambient temperature ( C) Ambient humidity(%) HEAT operation Condition: Indoor Outdoor Dry bulb temperature ( C) Wet bulb temperature ( C) Operation: Test run operation (Refer to 8-3.) Outdoor unit current MUZ-GE25VA MUZ-GE25VAH Outdoor current (A) MUZ-GE35VA MUZ-GE35VAH Outdoor current (A) MUZ-GE42VA MUZ-GE42VAH (A) Ambient temperature ( C) Ambient temperature ( C) Ambient temperature( C) MUZ-GE50VA MUZ-GE50VAH 5.5 Outdoor current (A) Ambient temperature ( C) 21

22 PERFORMANCE DATA COOL operation at Rated frequency MUZ-GE25VA MUZ-GE25VAH CAPACITY: 2.5 kw SHF: 0.96 INPUT: 545 W OUTDOOR DB ( C) INDOOR INDOOR DB ( C) WB ( C) Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT NOTE Q : Total capacity (kw) SHF : Sensible heat factor DB : Dry-bulb temperature SHC : Sensible heat capacity (kw) INPUT : Total power input (W) WB : Wet-bulb temperature 22

23 PERFORMANCE DATA COOL operation at Rated frequency MUZ-GE25VA MUZ-GE25VAH CAPACITY: 2.5 kw SHF: 0.96 INPUT: 545 W OUTDOOR DB ( C) INDOOR INDOOR DB ( C) WB ( C) Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT NOTE Q : Total capacity (kw) SHF : Sensible heat factor DB : Dry-bulb temperature SHC : Sensible heat capacity (kw) INPUT : Total power input (W) WB : Wet-bulb temperature 23

24 PERFORMANCE DATA COOL operation at Rated frequency MUZ-GE35VA MUZ-GE35VAH CAPACITY: 3.5 kw SHF: 0.82 INPUT: 865 W OUTDOOR DB ( C) INDOOR INDOOR DB ( C) WB ( C) Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT NOTE Q : Total capacity (kw) SHF : Sensible heat factor DB : Dry-bulb temperature SHC : Sensible heat capacity (kw) INPUT : Total power input (W) WB : Wet-bulb temperature 24

25 PERFORMANCE DATA COOL operation at Rated frequency MUZ-GE35VA MUZ-GE35VAH CAPACITY: 3.5 kw SHF: 0.82 INPUT: 865 W OUTDOOR DB ( C) INDOOR INDOOR DB ( C) WB ( C) Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT NOTE Q : Total capacity (kw) SHF : Sensible heat factor DB : Dry-bulb temperature SHC : Sensible heat capacity (kw) INPUT : Total power input (W) WB : Wet-bulb temperature 25

26 PERFORMANCE DATA COOL operation at Rated frequency MUZ-GE42VA MUZ-GE42VAH CAPACITY: 4.2 kw SHF: 0.77 INPUT: 1215 W OUTDOOR DB ( C) INDOOR INDOOR DB ( C) WB ( C) Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT NOTE Q : Total capacity (kw) SHF : Sensible heat factor DB : Dry-bulb temperature SHC : Sensible heat capacity (kw) INPUT : Total power input (W) WB : Wet-bulb temperature 26

27 PERFORMANCE DATA COOL operation at Rated frequency MUZ-GE42VA MUZ-GE42VAH CAPACITY: 4.2 kw SHF: 0.77 INPUT: 1215 W OUTDOOR DB ( C) INDOOR INDOOR DB ( C) WB ( C) Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT NOTE Q : Total capacity (kw) SHF : Sensible heat factor DB : Dry-bulb temperature SHC : Sensible heat capacity (kw) INPUT : Total power input (W) WB : Wet-bulb temperature 27

28 PERFORMANCE DATA COOL operation at Rated frequency MUZ-GE50VA MUZ-GE50VAH CAPACITY: 5.0 kw SHF: 0.76 INPUT: 1515 W OUTDOOR DB ( C) INDOOR INDOOR DB ( C) WB ( C) Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT NOTE Q : Total capacity (kw) SHF : Sensible heat factor DB : Dry-bulb temperature SHC : Sensible heat capacity (kw) INPUT : Total power input (W) WB : Wet-bulb temperature 28

29 PERFORMANCE DATA COOL operation at Rated frequency MUZ-GE50VA MUZ-GE50VAH CAPACITY: 5.0 kw SHF: 0.76 INPUT: 1515 W OUTDOOR DB ( C) INDOOR INDOOR DB ( C) WB ( C) Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT NOTE Q : Total capacity (kw) SHF : Sensible heat factor DB : Dry-bulb temperature SHC : Sensible heat capacity (kw) INPUT : Total power input (W) WB : Wet-bulb temperature 29

SERVICE MANUAL OUTDOOR UNIT. No. OBH590 REVISED EDITION-B. Models HFC

SERVICE MANUAL OUTDOOR UNIT. No. OBH590 REVISED EDITION-B. Models HFC SPLIT-TYPE AIR CONDITIONERS Revision B: MUZ-EF25/35/42/50VE - E2 and MUZ-EF25/35VEH - E2 have been added. Please void OBH590 REVISED EDITION-A. OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OBH590 REVISED

More information

SERVICE MANUAL MUZ-FD25VABH - E1 MUZ-FD35VABH - E1 MUZ-FD50VABH - E1 OUTDOOR UNIT. No. OBH519. Models HFC SPLIT-TYPE AIR CONDITIONERS R410A

SERVICE MANUAL MUZ-FD25VABH - E1 MUZ-FD35VABH - E1 MUZ-FD50VABH - E1 OUTDOOR UNIT. No. OBH519. Models HFC SPLIT-TYPE AIR CONDITIONERS R410A SPLIT-TYPE AIR CONDITIONERS OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OBH519 Models MUZ-FD25VABH - E1 MUZ-FD35VABH - E1 MUZ-FD50VABH - E1 Indoor unit service manual MSZ-FD VA Series (OBH488) MUZ-FD25/35

More information

SERVICE MANUAL MUFZ-KJ25VE MUFZ-KJ35VE MUFZ-KJ50VE OUTDOOR UNIT. No. OBH695. Models HFC SPLIT-TYPE AIR CONDITIONERS R410A

SERVICE MANUAL MUFZ-KJ25VE MUFZ-KJ35VE MUFZ-KJ50VE OUTDOOR UNIT. No. OBH695. Models HFC SPLIT-TYPE AIR CONDITIONERS R410A SPLIT-TYPE AIR CONDITIONERS OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. Models MUFZ-KJ25VE MUFZ-KJ35VE MUFZ-KJ50VE - A1 - A1 - A1 Indoor unit service manual MFZ-KJ VE Series (OBH697) MUFZ-KJ25VE MUFZ-KJ35VE

More information

SERVICE MANUAL MUZ-DM25VA - E1, ER1, ET1 MUZ-DM35VA - E1, ER1, ET1 OUTDOOR UNIT. No. OBH751. Models HFC R410A

SERVICE MANUAL MUZ-DM25VA - E1, ER1, ET1 MUZ-DM35VA - E1, ER1, ET1 OUTDOOR UNIT. No. OBH751. Models HFC R410A OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. Models MUZ-DM25VA - E1, ER1, ET1 MUZ-DM35VA - E1, ER1, ET1 Indoor unit service manual MSZ-DM VA Series (OBH750) CONTENTS 1. TECHNICAL CHANGES 2 2. PART NAMES

More information

PARTS CATALOG OUTDOOR UNIT. No. OBB516. Models

PARTS CATALOG OUTDOOR UNIT. No. OBB516. Models SPLIT-TYPE AIR CONDITIONERS Revision D: The fan guards for MUZ-GE50VA(H) - E, MUZ -GE60VA - E and MUZ-GE7VA - E have been changed. Please void OBB56 REVISED EDITION-C. OUTDOOR UNIT PARTS CATALOG No. OBB56

More information

SERVICE MANUAL MUZ-GE09NA MUZ-GE12NA MUZ-GE15NA MUZ-GE18NA MUZ-GE24NA MUY-GE09NA MUY-GE12NA MUY-GE15NA MUY-GE18NA MUY-GE24NA OUTDOOR UNIT

SERVICE MANUAL MUZ-GE09NA MUZ-GE12NA MUZ-GE15NA MUZ-GE18NA MUZ-GE24NA MUY-GE09NA MUY-GE12NA MUY-GE15NA MUY-GE18NA MUY-GE24NA OUTDOOR UNIT SPLIT-TYPE AIR CONDITIONERS Revision B: Descriptions regarding the outdoor fan motor have been corrected. Please void OBH549 REVISED EDITION-A. OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OBH549 REVISED

More information

SERVICE MANUAL MUZ-HJ25VA MUZ-HJ35VA OUTDOOR UNIT. No. OBH648. Models HFC SPLIT-TYPE AIR CONDITIONERS R410A

SERVICE MANUAL MUZ-HJ25VA MUZ-HJ35VA OUTDOOR UNIT. No. OBH648. Models HFC SPLIT-TYPE AIR CONDITIONERS R410A SPLIT-TYPE AIR CONDITIONERS OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. Models MUZ-HJ25VA MUZ-HJ35VA - E1 - E1 Indoor unit service manual MSZ-HJ VA Series (OBH647) MUZ-HJ25VA MUZ-HJ35VA CONTENTS 1.

More information

SERVICE MANUAL MUZ-HE09NA MUZ-HE12NA MUZ-HE15NA MUZ-HE18NA MUZ-HE24NA OUTDOOR UNIT. No. OBH686. Models HFC SPLIT-TYPE AIR CONDITIONERS R410A

SERVICE MANUAL MUZ-HE09NA MUZ-HE12NA MUZ-HE15NA MUZ-HE18NA MUZ-HE24NA OUTDOOR UNIT. No. OBH686. Models HFC SPLIT-TYPE AIR CONDITIONERS R410A SPLIT-TYPE AIR CONDITIONERS OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. Models MUZ-HE09NA MUZ-HE12NA MUZ-HE15NA MUZ-HE18NA MUZ-HE24NA Indoor unit service manual MSZ-HE NA Series (OBH685) MUZ-HE09NA

More information

SERVICE MANUAL MUZ-GA60VA - E1 MUZ-GA60VA - MUZ-GA71VA - E1. Wireless type Models HFC SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS R410A. No.

SERVICE MANUAL MUZ-GA60VA - E1 MUZ-GA60VA - MUZ-GA71VA - E1. Wireless type Models HFC SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS R410A. No. SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS SERVICE MANUAL Wireless type Models E MUZ-GA50VA - E MUZ-GA60VA - MUZ-GA7VA - E HFC utilized R40A. OB389 Indication of model name MUZ-GA50VA - E MUZ-GA60VA - E MUZ-GA7VA

More information

SERVICE MANUAL MUZ-FE09NA MUZ-FE12NA MUZ-FE18NA OUTDOOR UNIT. No. OBH543 REVISED EDITION-A. Models HFC

SERVICE MANUAL MUZ-FE09NA MUZ-FE12NA MUZ-FE18NA OUTDOOR UNIT. No. OBH543 REVISED EDITION-A. Models HFC SPLIT-TYPE AIR CONDITIONERS Revision A: MUZ-FE18NA has been added. Please void OBH543. OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OBH543 REVISED EDITION-A Models MUZ-FE09NA MUZ-FE12NA MUZ-FE18NA Indoor

More information

SERVICE MANUAL MUZ-GC25VA - MUZ-GC25VAH - MUZ-GC35VA - MUZ-GC35VAH - E1 OUTDOOR UNIT. No. OBH469. Wireless type Models HFC

SERVICE MANUAL MUZ-GC25VA - MUZ-GC25VAH - MUZ-GC35VA - MUZ-GC35VAH - E1 OUTDOOR UNIT. No. OBH469. Wireless type Models HFC SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS OUTDOOR UNIT SERVICE MANUAL Wireless type Models E1 - E1 H - E1 - - E1 HFC utilized R410A. OBH469 Indoor unit service manual MSZ-GC VA Series (OBH468) H CONTENTS

More information

SERVICE MANUAL OUTDOOR UNIT MUZ-A09NA,- 1,- U1,- U2 MUZ-A12NA,- U1 MUZ-A15NA,- U1 MUZ-A17NA,- U1 MUY-A15NA MUY-A17NA MUY-A24NA,- 1,- U1,- U2

SERVICE MANUAL OUTDOOR UNIT MUZ-A09NA,- 1,- U1,- U2 MUZ-A12NA,- U1 MUZ-A15NA,- U1 MUZ-A17NA,- U1 MUY-A15NA MUY-A17NA MUY-A24NA,- 1,- U1,- U2 SPLIT-TYPE AIR CONDITIONERS Revision E: MUZ-GA24NA and MUY-GA24NA have been added. Please void OB451 REVISED EDITION-D. OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OB451 REVISED EDITION-E Models MUZ-A09NA,-

More information

PARTS CATALOG MUZ-HJ25VA - E1, ER1, ET1 MUZ-HJ35VA - E1, ER1, ET1 MUZ-HJ50VA - E1, ER1, ET1 OUTDOOR UNIT. No. OBB648 REVISED EDITION-C.

PARTS CATALOG MUZ-HJ25VA - E1, ER1, ET1 MUZ-HJ35VA - E1, ER1, ET1 MUZ-HJ50VA - E1, ER1, ET1 OUTDOOR UNIT. No. OBB648 REVISED EDITION-C. SPLIT-TYPE AIR CONDITIONERS Revision C: MUZ-HJ25VA-, MUZ-HJ35VA- and MUZ-HJ50VA- have been added. The defrost heater for MUZ-HJ25VA and MUZ- HJ35VA has been added to the optional parts. Please void OBB648

More information

SERVICE MANUAL MUZ-FH09NAH MUZ-FH12NAH MUZ-FH15NAH MUZ-FH09NA MUZ-FH12NA MUZ-FH15NA OUTDOOR UNIT. No. OBH684 REVISED EDITION-A.

SERVICE MANUAL MUZ-FH09NAH MUZ-FH12NAH MUZ-FH15NAH MUZ-FH09NA MUZ-FH12NA MUZ-FH15NA OUTDOOR UNIT. No. OBH684 REVISED EDITION-A. SPLIT-TYPE AIR CONDITIONERS Revision A: 3. SPECIFICATION has been modified. 10. TROUBLESHOOTING has been modified. Please void OBH684. OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OBH684 REVISED EDITION-A

More information

technical data air conditioning systems RXS20-25-35E (single phase) FBQ-B8V1-B8V3B Split Heat Pump Condensing Units Split Sky Air

technical data air conditioning systems RXS20-25-35E (single phase) FBQ-B8V1-B8V3B Split Heat Pump Condensing Units Split Sky Air technical data RXS20-25-35E FBQ-B8V-B8V3B (single phase) Split Heat Pump Condensing Units air conditioning systems Split Sky Air Outdoor Units R-40A RXS-E2VB Split Sky Air Outdoor Units Features O u t

More information

PARTS CATALOG OUTDOOR UNIT. No. OBB560. Models MXZ-2B20NA, - 1 MXZ-3B24NA MXZ-3B30NA MXZ-4B36NA HFC

PARTS CATALOG OUTDOOR UNIT. No. OBB560. Models MXZ-2B20NA, - 1 MXZ-3B24NA MXZ-3B30NA MXZ-4B36NA HFC SPLIT-TYPE AIR CONDITIONERS Revision C: MXZ-3B30NA has been added. Please void OBB560 REVISED EDITION-B. OUTDOOR UNIT PARTS CATALOG HFC utilized R410A No. OBB560 REVISED EDITION-C Models, - 1 MXZ-3B24NA

More information

SERVICE MANUAL MUZ-GA50VA - MUZ-GA60VA- MUZ-GA60VA - MUZ-GA60VA - MUZ-GA71VA - MUZ-GA71VA - E2 OUTDOOR UNIT. No. OB389 REVISED EDITION-F

SERVICE MANUAL MUZ-GA50VA - MUZ-GA60VA- MUZ-GA60VA - MUZ-GA60VA - MUZ-GA71VA - MUZ-GA71VA - E2 OUTDOOR UNIT. No. OB389 REVISED EDITION-F SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS Revision F: MUZ-A60VA- E3 has been added. Please void OB389 REVISED EDITION-E. OUTDOOR UNIT SERVICE MANUAL Wireless type Models E MUZ-A50VA - E MUZ-A60VA - E2 MUZ-A60VA

More information

High Wall Type (3 series)

High Wall Type (3 series) High Wall Type (3 series) MMK-AP0073H MMK-AP0093H MMK-AP0123H MMK-AP0153H MMK-AP0183H MMK-AP0243H Contents 1. Specifications 2. Dimensions 3. Center of gravity 4. Piping diagram 5. Wiring diagram 6. Electrical

More information

Content. Part 1 General Information Part 2 Indoor Units Part 3 Outdoor Units Part 4 Installation Part 5 Control...

Content. Part 1 General Information Part 2 Indoor Units Part 3 Outdoor Units Part 4 Installation Part 5 Control... Content Part 1 General Information... 2 Part 2 Indoor Units... 6 Part 3 Outdoor Units... 91 Part 4 Installation... 119 Part 5 Control... 151 1 Part 1 General Information 1. Model Names of Indoor/Outdoor

More information

SERVICE MANUAL INDOOR UNIT

SERVICE MANUAL INDOOR UNIT SPLIT-TYPE AIR CONDITIONERS Revision E: MSZ-GE22VAD- A1 has been added. Please void OBH531 REVISED EDITION-D. INDOOR UNIT SERVICE MANUAL. OBH531 REVISED EDITION-E Models MSZ-GE22VA - A1 MSZ-GE50VA - A1

More information

Content. Part 1 General Information Part 2 Indoor Units Part 3 Outdoor Units Part 4 Installation Part 5 Control...

Content. Part 1 General Information Part 2 Indoor Units Part 3 Outdoor Units Part 4 Installation Part 5 Control... R410A Tropical Split Type AC Technical Manual Content Content Part 1 General Information... 2 Part 2 Indoor Units... 6 Part 3 Outdoor Units... 88 Part 4 Installation... 120 Part 5 Control... 154 Indoor

More information

Mitsubishi Electric ilmalämpöpumput korjaa ja huoltaa pääkaupunkiseudulla: Jäähdytinpalvelu RefGroup Oy MUZ-A09YV - MUZ-A12YVH - E1

Mitsubishi Electric ilmalämpöpumput korjaa ja huoltaa pääkaupunkiseudulla: Jäähdytinpalvelu RefGroup Oy MUZ-A09YV - MUZ-A12YVH - E1 SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS Revision A: MUZ-AYV- E and MUZ-AYVHcan be connected to MCFZ-AWV- E. E Some mistakes were corrected. Please void OB8. SERVICE MANUAL Wireless type Models E MUZ-A09YV

More information

Air Conditioners Technical Data

Air Conditioners Technical Data Air Conditioners Technical Data O u t d o o r U n i t E E D E N 2-0 0 RX-JV Outdoor Unit RX-JV TABLE OF CONTENTS RX-JV Features............................................................. 2 2 Specifications.......................................................

More information

Air to Air Heat exchanger with DX-coil type

Air to Air Heat exchanger with DX-coil type Air to Air Heat exchanger with DX-coil type MMD-VN2HEX1E MMD-VN82HEX1E MMD-VN12HEX1E MMD-VN12HEX1E2 Contents 1. Specifications 2. Dimensions 3. Center of gravity 4. Piping diagram 5. Wiring diagram 6.

More information

R410A INDOOR UNIT 1. WALL MOUNTED TYPE : AS A07LCC AS A09LCC AS A12LCC AS A14LCC AS A18LCC D1D_AS007E/

R410A INDOOR UNIT 1. WALL MOUNTED TYPE : AS A07LCC AS A09LCC AS A12LCC AS A14LCC AS A18LCC D1D_AS007E/ RA INDOOR UNIT. : AS A7LCC AS A9LCC AS ALCC AS ALCC AS A8LCC DD_AS7E/ 7..6 AS A7-8LC AS A7-8LC. FEATURE MODEL : AS A7LCC AS A9LCC AS ALCC AS ALCC AS A8LCC (AO R7/9LC) (AO RLC) (AO R/8LC) FEATURES Energy

More information

HP switch LP switch Discharge thermo Comp. Surface thermo

HP switch LP switch Discharge thermo Comp. Surface thermo 1 Specifications Zubadan Model Name PUHZ-SHW80VHA PUHZ-SHW11VHA PUHZ-SHW11YHA Power supply (phase, cycle, voltage) 1φ, V, Hz 1φ, V, Hz 3φ, 0V, Hz Max. current A 9.5 35.0 13.0 Breaker size A 3 16 Outer

More information

TECHNICAL & SERVICE MANUAL SPLIT SYSTEM AIR CONDITIONER + SAP C181MA + SAP C181GA + SAP C181BA + SAP C241MA + SAP C241BA FILE NO.

TECHNICAL & SERVICE MANUAL SPLIT SYSTEM AIR CONDITIONER + SAP C181MA + SAP C181GA + SAP C181BA + SAP C241MA + SAP C241BA FILE NO. TECHNICAL & SERVICE MANUAL SAP K161GJA SAP K181GJA SAP K181MBA SAP K241GJA SAP K241MBA + SAP C161GA + SAP C161JA + SAP C181GA + SAP C181JA + SAP C181MA + SAP C181BA + SAP C241GA + SAP C241JA + SAP C241MA

More information

R410A INDOOR UNIT 1. CASSETTE TYPE : AU A12LAL AU F12LAL AU A14LAL AU F14LAL D2D_AU029E/

R410A INDOOR UNIT 1. CASSETTE TYPE : AU A12LAL AU F12LAL AU A14LAL AU F14LAL D2D_AU029E/ R4A INDOOR UNIT. : AU ALAL AU FLAL AU A4LAL AU F4LAL DD_AU9E/4 9.8. MODEL : INDOOR UNIT AU ALAL AU FLAL AO ALACL AO ALALL AO BLACL AO BLALL AU A4LAL AU F4LAL AO A4LACL AO A4LALL AO B4LACL AO B4LALL FEATURES

More information

SERVICE MANUAL MUZ-GA25VA - MUZ-GA35VA - MUZ-GA25VAH - MUZ-GA25VAH - E1. Wireless type Models HFC SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS. No.

SERVICE MANUAL MUZ-GA25VA - MUZ-GA35VA - MUZ-GA25VAH - MUZ-GA25VAH - E1. Wireless type Models HFC SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS. No. SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS SERVICE MANUAL Wireless type Models E MUZ-GA5VA - E MUZ-GA35VA - E MUZ-GA5VAH - MUZ-GA35VAH - E HFC utilized R40A. OB379 Indication of model name MUZ-GA5VA - E MUZ-GA35VA

More information

Appendix - Controllers 179

Appendix - Controllers 179 Version: 200703 Appendix - Controllers 179 -3- -4- -5- -6- -7- -8- 2. Specifications 2.1 Specifications for inverter units item Model AB182ACERA Function cooling heating Capacity kw 5.01.8--5.8 5.22.0---6.2

More information

Air Conditioners. Technical Data. Wall Mounted Unit. www.daikin.eu RX-JV/GV

Air Conditioners. Technical Data. Wall Mounted Unit. www.daikin.eu RX-JV/GV Air Conditioners Technical Data Wall Mounted Unit www.daikin.eu RX-JV/GV Air Conditioners Technical Data Wall Mounted Unit www.daikin.eu RX-JV/GV TABLE OF CONTENTS RX-JV/GV 1 Features.............................................................

More information

SERVICE MANUAL MXZ-2A20NA MXZ-2A20NA - MXZ-3A30NA MXZ-3A30NA - MXZ-4A36NA OUTDOOR UNIT. No. OB444. Models HFC. Inverter-controlled multi system type

SERVICE MANUAL MXZ-2A20NA MXZ-2A20NA - MXZ-3A30NA MXZ-3A30NA - MXZ-4A36NA OUTDOOR UNIT. No. OB444. Models HFC. Inverter-controlled multi system type Revision C: MXZ-4A36NA have been added. SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS Please void OB444 REVISED EDITION-B. OUTDOOR UNIT SERVICE MANUAL HFC utilized R40A No. OB444 REVISED EDITION-C Inverter-controlled

More information

ROOFTOP - HEAT PUMP UNIT. This document applies when installing into an air handler or as part of an air handling system.

ROOFTOP - HEAT PUMP UNIT. This document applies when installing into an air handler or as part of an air handling system. ROOFTOP - HEAT PUMP UNIT Technical data Applies to Model YNRA R410A This document applies when installing into an air handler or as part of an air handling system. CONTENTS 1. General description... 2

More information

PARTS CATALOG MSZ-FH25VE MSZ-FH35VE MSZ-FH50VE INDOOR UNIT. No. OBB623. Models

PARTS CATALOG MSZ-FH25VE MSZ-FH35VE MSZ-FH50VE INDOOR UNIT. No. OBB623. Models SPLIT-TYPE AIR CONDITIONERS Revision B: MSZ-FH25VE-, MSZ-FH35VE- and MSZ-FH50VE- have been added. Please void OBB623 REVISED EDITION-A. INDOOR UNIT PARTS CATALOG No. OBB623 REVISED EDITION-B Models MSZ-FH25VE

More information

SERVICE MANUAL SPLIT SYSTEM ROOM AIR CONDITIONER SHARP CORPORATION SHARP CORPORATION CONTENTS

SERVICE MANUAL SPLIT SYSTEM ROOM AIR CONDITIONER SHARP CORPORATION SHARP CORPORATION CONTENTS SERVICE MANUAL SPLIT SYSTEM ROOM AIR CONDITIONER INDOOR UNIT AH-129 AH-MP14 OUTDOOR UNIT AU-129 AU-MP14 CONTENTS SPECIFICATIONS...2 EXTERNAL DIMENSIONS...4 WIRING DIAGRAMS...5 ELECTRICAL PARTS...6 MICROCOMPUTER

More information

SERVICE MANUAL INDOOR UNIT

SERVICE MANUAL INDOOR UNIT SPLIT-TYPE AIR CONDITIONERS Revision B: "How to check miswiring and serial signal error" for MUZ type has been added. The description about "Low standby power control" has been added to "TECHNICAL CHANGES".

More information

INVERTER MULTI-SPLIT SYSTEM ROOM AIR-CONDITIONER (Air to air heat pump type) Manual No. '06 SCM-T-052

INVERTER MULTI-SPLIT SYSTEM ROOM AIR-CONDITIONER (Air to air heat pump type) Manual No. '06 SCM-T-052 INVERTER MULTI-SPLIT SYSTEM ROOM AIR-CONDITIONER (Air to air heat pump type) Manual No. '06 SCM-T-052 CONTENTS 1 GENERAL INFORMATION... 1 1.1 Specific features... 1 1.2 How to read the model name... 1

More information

XeNeA. Indoor packaged air-to-water heat pump. Plug & Heat ready to use heat pump Quick and easy to install equipped with HomeConnect control USE

XeNeA. Indoor packaged air-to-water heat pump. Plug & Heat ready to use heat pump Quick and easy to install equipped with HomeConnect control USE Indoor packaged air-to-water heat pump Plug & Heat ready to use heat pump Quick and easy to install equipped with HomeConnect control XeNeA 0 HFC R410A option CERTIFIÉ PAR CERTITA HEATING 30/35-40/45 Heating

More information

3. OUTDOOR UNITS DTV_V2E011E_21--CHAPTER03 2013.04.01

3. OUTDOOR UNITS DTV_V2E011E_21--CHAPTER03 2013.04.01 3. DTV_V2E011E_21--CHAPTER03 2013.04.01 CONTENTS 3. 1. SPECIFICATIONS... 03-01 1-1. SPACE SAVING COMBINATION... 03-01 1-2. ENERGY EFFICIENCY COMBINATION... 03-07 2. DIMENSIONS... 03-11 2-1. SINGLE UNIT...

More information

SPLIT TYPE ROOM AIR CONDITIONER WALL MOUNTED TYPE

SPLIT TYPE ROOM AIR CONDITIONER WALL MOUNTED TYPE SPLIT TYPE ROOM AIR CONDITIONER WALL MOUNTED TYPE Indoor unit ASYG14LMCB Outdoor unit AOYG14LMCBN CONTENTS SPECIFICATIONS...................1 DIMENSIONS...................... 2 REFRIGERANT SYSTEM DIAGRAM....3

More information

SERVICE MANUAL MU-A09WA MU-A12WA MU-A12WA- 1 OUTDOOR UNIT. No. OB449. Wireless type Models HFC. Revision : A SPLIT-TYPE AIR CONDITIONERS

SERVICE MANUAL MU-A09WA MU-A12WA MU-A12WA- 1 OUTDOOR UNIT. No. OB449. Wireless type Models HFC. Revision : A SPLIT-TYPE AIR CONDITIONERS SPLIT-TYPE AIR CONDITIONERS Revision : A MU-AWA- Please void OB449. has been added. OUTDOOR UNIT SERVICE MANUAL Wireless type Models MU-AWA MU-AWA- HFC utilized R40A No. OB449 REVISED EDITION-A Indoor

More information

AIR-CONDITIONER SPLIT TYPE

AIR-CONDITIONER SPLIT TYPE TCTC 13-006 AIR-CONDITIONER SPLIT TYPE Indoor Unit Outdoor Unit RAS-B10UFV-E RAS-B13UFV-E RAS-B18UFV-E RAS-10N3AV-E RAS-13N3AV-E RAS-18N3AV-E May, 2013 Contents

More information

Troubleshooting. Basic Troubleshooting Procedures

Troubleshooting. Basic Troubleshooting Procedures Basic Procedures 1. Is there any noise from a loose drive belt? Loose or worn drive belt, various squeaking and slapping noises. If such noises are heard, check and adjust the drive belt tension. 2. Is

More information

Medium Static Ducted type

Medium Static Ducted type Medium Static Ducted type MMD-AP0074BH2UL- / MMD-AP0094BH2UL- MMD-AP024BH2UL- / MMD-AP054BH2UL- MMD-AP084BH2UL- / MMD-AP024BH2UL- MMD-AP0244BH2UL- / MMD-AP0304BH2UL- MMD-AP0364BH2UL- / MMD-AP0424BH2UL-

More information

SERVICE MANUAL MSZ-HJ25VA MSZ-HJ35VA MSZ-HJ50VA INDOOR UNIT. No. OBH647. Models. Revision A: MSZ-HJ50VA- E1 has been added.

SERVICE MANUAL MSZ-HJ25VA MSZ-HJ35VA MSZ-HJ50VA INDOOR UNIT. No. OBH647. Models. Revision A: MSZ-HJ50VA- E1 has been added. SPLIT-TYPE AIR CONDITIONERS Revision A: MSZ-HJ50VA- E1 has been added. Please void OBH647. INDOOR UNIT SERVICE MANUAL. OBH647 REVISED EDITION-A Models MSZ-HJ25VA MSZ-HJ35VA MSZ-HJ50VA - E1 - E1 - E1 CONTENTS

More information

MUZ-G09SV - MSZ-G12SV -

MUZ-G09SV - MSZ-G12SV - 000 SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS SERVICE MANUAL. OB45 Wireless type Models E MSZ-G09SV - (WH) E MUZ-G09SV - MSZ-GSV - (WH) MUZ-GSV - E E CONTENTS. PART NAMES AND FUNCTIONS. SPECIFICATION 4 3.

More information

TECHNICAL DATA. Gas Heat Pump Air Conditioner 2-WAY Multi 2-WAY W Multi 3-WAY Multi

TECHNICAL DATA. Gas Heat Pump Air Conditioner 2-WAY Multi 2-WAY W Multi 3-WAY Multi TECHNICAL DATA Gas Heat Pump Air Conditioner 2-WAY Multi 2-WAY W Multi 3-WAY Multi OUTDOOR MODEL No. U-16GE2E5 U-20GE2E5 U-25GE2E5 U-16GEP2E5 U-20GEP2E5 U-25GEP2E5 U-30GE2E5 U-16GF2E5 U-20GF2E5 U-25GF2E5

More information

ASU9RLS3 ASU12RLS3 AOU9RLS3H AOU12RLS3H SPLIT TYPE ROOM AIR CONDITIONER WALL MOUNTED TYPE CONTENTS

ASU9RLS3 ASU12RLS3 AOU9RLS3H AOU12RLS3H SPLIT TYPE ROOM AIR CONDITIONER WALL MOUNTED TYPE CONTENTS SPLIT TYPE ROOM AIR CONDITIONER WALL MOUNTED TYPE Indoor unit ASU9RLS ASURLS Outdoor unit AOU9RLSH AOURLSH CONTENTS SPECIFICATIONS................... DIMENSIONS...................... REFRIGERANT SYSTEM

More information

Air Conditioners. Technical Data RKS-J

Air Conditioners. Technical Data RKS-J Air Conditioners Technical Data P a i r a p p l i c a t i o n E E D E N 1 1-1 0 0 RKS-J Air Conditioners Technical Data P a i r a p p l i c a t i o n E E D E N 1 1-1 0 0 RKS-J TABLE OF CONTENTS RKS-J 1

More information

2. DUCT TYPE AR 7-9FUAB, AR 12-18FUAD AR 7-9UUAB, AR 12-18UUAD

2. DUCT TYPE AR 7-9FUAB, AR 12-18FUAD AR 7-9UUAB, AR 12-18UUAD R410A 2. AR 7-9FUAB, AR 12-18FUAD AR 7-9UUAB, AR 12-18UUAD D2D_AR006E/03 2006.03.15 - (02-01) - 2-1. FEATURE MODELS : AR 7FUAB / AO 7FSAJ AR 9FUAB / AO 9FSAJ AR 12FUAD / AO 12FSAJ AR 14FUAD / AO 14FSDJ

More information

INSTALLATION AND USER GUIDE

INSTALLATION AND USER GUIDE EN POOL EQUIPMENT KLIN GOTHIC ITC DEMI-13,3 b zlatá černá PANTONE 871 U Swimming Pool Heat Pump XHP PANTONE 426 U INSTALLATION AND USER GUIDE i Read the instructions Illustrative photo Contents 1. Specification...3

More information

SERVICE MANUAL MSZ-GE22VA - E1 MSZ-GE25VA - E1 MSZ-GE35VA - E1 MSZ-GE42VA - E1 MSZ-GE50VA - E1 INDOOR UNIT. No. OBH515. Models

SERVICE MANUAL MSZ-GE22VA - E1 MSZ-GE25VA - E1 MSZ-GE35VA - E1 MSZ-GE42VA - E1 MSZ-GE50VA - E1 INDOOR UNIT. No. OBH515. Models Revision B: MSZ-GE42/50VA - E1 has been added. SPLIT-TYPE AIR CONDITIONERS Please void OBH515 REVISED EDITION-A. INDOOR UNIT SERVICE MANUAL. OBH515 REVISED EDITION-B Models MSZ-GE22VA - E1 MSZ-GE25VA -

More information

Technical Specifications

Technical Specifications Technical Specifications Indoor Indoor Units Combination Outdoor Units Nominal Power Input Nominal Running Current without Electric Heater A Operation Range Cooling(Fan coil unit) C (Min.~Max.) Cooling(Under

More information

Replacement Parts Catalog

Replacement Parts Catalog GA Ductfree Series Mini-Split Systems Packaged 18,000-42,000 Terminal BTUH Air Conditioner / Heat Pump 7,000 --- 15,000 BTUH Replacement Parts Catalog 1 Table of Contents Model Number Description Page

More information

Service manual. MIV V4+ Mini

Service manual. MIV V4+ Mini Service manual MIV V4+ Mini DC INVERTER R410A ~220V, 1Ph, 50Hz MVUH120A-VA1 MVUH140A-VA1 MVUH160A-VA1 Contents Part 1 General Information... 1 Part 2 Outdoor Units... 9 Part 3 Installation... 55 Part 1

More information

Indoor coil is too warm in cooling mode or too cold in heating mode. Reversing valve or coil thermistor is faulty

Indoor coil is too warm in cooling mode or too cold in heating mode. Reversing valve or coil thermistor is faulty Codes Room Air Conditioner range: Indoor unit alarm s If timer lamp flashes for 1 second on, 1 second off, this indicates pre heating on the coil during heating mode and is not an error. If timer lamp

More information

SERVICE MANUAL MSZ-FH25VE MSZ-FH35VE MSZ-FH50VE INDOOR UNIT. No. OBH623. Models. Revision A: MSZ-FH50VE- E1 has been added. Please void OBH623.

SERVICE MANUAL MSZ-FH25VE MSZ-FH35VE MSZ-FH50VE INDOOR UNIT. No. OBH623. Models. Revision A: MSZ-FH50VE- E1 has been added. Please void OBH623. SPLIT-TYPE AIR CONDITIONERS Revision A: MSZ-FH50VE- E1 has been added. Please void OBH623. INDOOR UNIT SERVICE MANUAL. OBH623 REVISED EDITION-A Models MSZ-FH25VE MSZ-FH35VE MSZ-FH50VE - E1 - E1 - E1 Outdoor

More information

Split System Cooling Units

Split System Cooling Units Split System Cooling Units Split System Cooling Units TTA075A-TTA200B Air Handlers TWE050A-TWE200B 50 Hz December 2000 Introduction Split System Heat Pump Units Designed With Your Needs In Mind. The Trane

More information

SERVICE MANUAL INDOOR UNIT MSZ-EF35VEW MSZ-EF22VEB - - E1 MSZ-EF25VEB E1 MSZ-EF35VEB - - E1 MSZ-EF35VEB E1 MSZ-EF35VES - E1 - E1 MSZ-EF22VEW -

SERVICE MANUAL INDOOR UNIT MSZ-EF35VEW MSZ-EF22VEB - - E1 MSZ-EF25VEB E1 MSZ-EF35VEB - - E1 MSZ-EF35VEB E1 MSZ-EF35VES - E1 - E1 MSZ-EF22VEW - SPLIT-TYPE AIR CONDITIONERS Revision A: Airflow in the Silent mode in the cooling operation has been changed. "TROUBLESHOOTING" has been corrected. Please void OBH589. INDOOR UNIT SERVICE MANUAL. OBH589

More information

*ATTENTION* ACAC12. Double Windpipe Portable Air Conditioner

*ATTENTION* ACAC12. Double Windpipe Portable Air Conditioner ACAC12 Double Windpipe Portable Air Conditioner *ATTENTION* THIS AIR CONDITIONER UNIT IS RECOMMENDED FOR GARDENING APPLICATIONS NOT EXCEEDING A 10 X 10 X 8 ROOM AND (2) AIR COOLED 1000 WATT HID LIGHTING

More information

Кондиционеры Mitsubishi Heavy

Кондиционеры Mitsubishi Heavy Кондиционеры Mitsubishi Heavy Техническое руководство Кондиционеры настенного типа SRK20HD-S, SRK28HD-S, SRK40HD-S, SRK20CD-S, SRK28CD-S, SRK40CD-S CTENTS 1. GENERAL INFORMATI... 1 1.1 Specific features...

More information

technical data air conditioning systems Concealed Ceiling Unit FXMQ-PVE

technical data air conditioning systems Concealed Ceiling Unit FXMQ-PVE technical data Concealed Ceiling Unit FXMQ-PVE air conditioning systems technical data Concealed Ceiling Unit FXMQ-PVE air conditioning systems Indoor Units Conceiled ceiling unit FXMQ-PVE TABLE OF CONTENTS

More information

Air Exchanger (JX5, JX4, D-EXR, D-EX)

Air Exchanger (JX5, JX4, D-EXR, D-EX) Air Exchanger (JX5, JX4, D-EXR, D-EX) Technical Catalogue DC Inverter Air exchanger RAS/RAC HITACHI Specifications in this catalogue are subject to change without prior notice in order for HITACHI to

More information

1 Features. Heat pump HEAT PUMP CONTROL BOX. Air Handling Unit Connection Heat pump

1 Features. Heat pump HEAT PUMP CONTROL BOX. Air Handling Unit Connection Heat pump i l l r t r i Features nx o b p dm nu ap o H an oe AC H Wide range of Daikin units offers maximum application potential plus flexible control options. The system provides optimized air conditions such

More information

Commercial Split-type Air-conditioner

Commercial Split-type Air-conditioner Commercial Split-type Air-conditioner R-22 60 Hz Cassette Type:22,400 ~ 50,000 BTU/hr Ceiling / Flooring Type:22,400 ~ 50,000 BTU/hr Wall-mounted Type:32,000 ~ 40,000 BTU/hr Duct Type:22,400 ~ 50,000 BTU/hr

More information

1. INDOOR UNITS... MFZ-2 2. OUTDOOR UNITS... MFZ-3 3. SYSTEM... MFZ SPECIFICATIONS... MFZ EXTERNAL DIMENSIONS...

1. INDOOR UNITS... MFZ-2 2. OUTDOOR UNITS... MFZ-3 3. SYSTEM... MFZ SPECIFICATIONS... MFZ EXTERNAL DIMENSIONS... M-SERIES SINGLE ZONE SYSTEMS MFZ FLOOR-MOUNT HEAT PUMP SYSTEMS 1. INDOOR UNITS... MFZ-2 2. OUTDOOR UNITS... MFZ-3 3. SYSTEM... MFZ-4 3-1. SPECIFICATIONS... MFZ-5 3-2. EXTERNAL DIMENSIONS... MFZ-6 3-3.

More information

Split units TH with hermetic compressors

Split units TH with hermetic compressors Split units TH with compressors Refrigeration units in split variant. Available with screw or solder terminal. Condensing unit with sound insulated weatherproof housing for outdoor installation. Split

More information

TABLE OF CONTENTS. Air Conditioner CS-CE7GKEW CU-CE7GKE CS-CE9GKEW CU-CE9GKE CS-CE12GKEW CU-CE12GKE

TABLE OF CONTENTS. Air Conditioner CS-CE7GKEW CU-CE7GKE CS-CE9GKEW CU-CE9GKE CS-CE12GKEW CU-CE12GKE Order No. MAC0706002A2 Air Conditioner CS-CE7GKEW CU-CE7GKE CS-CE9GKEW CU-CE9GKE CS-CE12GKEW CU-CE12GKE Please file and use this manual together with the service manual for Model No. CS-E9GKEW-5 / CU-

More information

Packaged Air Conditioner - Water Cooled Vertical Type Model 25

Packaged Air Conditioner - Water Cooled Vertical Type Model 25 Refrigerant R407C CX Packaged Air Conditioner - Water Cooled Vertical Type Model 25 8.0kW CX 25 1 Product Code Model Power supply Product code CX 25 230V / 1 ~ / 50 Hz 7XU012153 CX 25 CX 25 2 CX 25 General

More information

SERVICE MANUAL MSC-GE20VB - E1 MSC-GE25VB - E1 MSC-GE35VB - E1 MS-GE50VB - E1 MSH-GE50VB - E1 INDOOR UNIT. No. OBH529. Models

SERVICE MANUAL MSC-GE20VB - E1 MSC-GE25VB - E1 MSC-GE35VB - E1 MS-GE50VB - E1 MSH-GE50VB - E1 INDOOR UNIT. No. OBH529. Models SPLIT-TYPE AIR CONDITIONERS Revision A: Another type of the electronic control P.C. board (TYPE 2) has been added to the original one (TYPE 1). They are both compatible with MS/MSH-GE50VB- E1. Please void

More information

NewAir AC-10000E, AC-10000H Portable Air Conditioner Owner s Manual PLEASE READ AND SAVE THESE INSTRUCTIONS

NewAir AC-10000E, AC-10000H Portable Air Conditioner Owner s Manual PLEASE READ AND SAVE THESE INSTRUCTIONS NewAir AC-10000E, AC-10000H Portable Air Conditioner Owner s Manual PLEASE READ AND SAVE THESE INSTRUCTIONS BEFORE USE GENERAL SAFETY INSTRUCTIONS: ALWAYS OPERATE THE UNIT IN AN UPRIGHT POSITION AND PLACE

More information

Inverter Ducted Air Conditioners

Inverter Ducted Air Conditioners Inverter Ducted Air Conditioners Advantages of Carrier s DC Inverter Ducted system Quiet operation Reverse cycle system (heating and cooling) 5 year warranty for consumer confidence Easy and flexible installation

More information

DC INVERTER MULTI-SYSTEM AIR CONDITIONER

DC INVERTER MULTI-SYSTEM AIR CONDITIONER TECHNICAL & SERVICE MANUAL OUTDOOR UNIT : AEMI0AH AEMIAHB AEMIAH AEMI0AH FILE NO. Destination: Europe DC INVERTER MULTI-SYSTEM AIR CONDITIONER Capacity.0k.k.k.0k Outdoor Model No. AEMI0AH AEMIAHB AEMIAH

More information

REPAIR - TROUBLESHOOTING

REPAIR - TROUBLESHOOTING REPAIR - TROUBLESHOOTING Before troubleshooting this system, the following inspection should be performed. 1-1. Inspection of Power Source Voltage Check the voltage of the power source. 24HFU & 24HFU-1:

More information

Ceiling Cassette Split Systems

Ceiling Cassette Split Systems MCK - 2005 Ceiling Cassette Split Systems Models: MCK 020A/AR MCK 025A/AR MCK 030A/AR MCK 040A/AR MCK 050A/AR MCK 015B/BR MCK 020B/BR MCK 025B/BR MCK/M5CK 010C/CR MCK/M5CK 015C/CR MCK 020C/CR Contents

More information

ECOCIAT. Domestic hot water heat recovery unit

ECOCIAT. Domestic hot water heat recovery unit Heat recovery unit Domestic hot water High energy efficiency with R410A Compact and quiet Scroll compressors Brazed-plate heat exchangers Heating Heat recovery ENVIRONMENTALLY HFC R410A PROTECTION DE FRIENDLY

More information

PARTS CATALOG INDOOR UNIT

PARTS CATALOG INDOOR UNIT SPLIT-TYPE AIR CONDITIONERS Revision A: Part numbers of the electronic control P.C. boards have been changed. Please void OBB589. INDOOR UNIT PARTS CATALOG No. OBB589 REVISED EDITION-A Models MSZ-EF22VEW

More information

PARTS CATALOG MS-GF20VA MS-GF25VA MS-GF35VA MS-GF50VA MS-GF60VA MS-GF80VA INDOOR UNIT. No. OBB621 REVISED EDITION-A. Models

PARTS CATALOG MS-GF20VA MS-GF25VA MS-GF35VA MS-GF50VA MS-GF60VA MS-GF80VA INDOOR UNIT. No. OBB621 REVISED EDITION-A. Models SPLIT-TYPE AIR CONDITIONERS Revision A: 50VA- E, 60VA- E and 0VA- E have been added. Please void OBB6. INDOOR UNIT PARTS CATALOG No. OBB6 REVISED EDITION-A Models 0VA 5VA 5VA 50VA 60VA 0VA - E - E - E

More information

Split-type Air-Conditioner INSTALLATION MANUAL CONTENTS FOR INSTALLER MXZ-3A30NA MXZ-4A36NA ATTENTION. English. Français. Español

Split-type Air-Conditioner INSTALLATION MANUAL CONTENTS FOR INSTALLER MXZ-3A30NA MXZ-4A36NA ATTENTION. English. Français. Español Split-type Air-Conditioner MXZ-3A30NA MXZ-4A36NA INSTALLATION MANUAL Refer to the installation manual of each indoor unit for indoor unit installation. English Français Español ATTENTION This manual mentions

More information

SUZ-KA25VA4.TH SUZ-KA35VA4.TH SUZ-KA50VA4.TH SUZ-KA60VA4.TH SUZ-KA71VA4.TH

SUZ-KA25VA4.TH SUZ-KA35VA4.TH SUZ-KA50VA4.TH SUZ-KA60VA4.TH SUZ-KA71VA4.TH SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS August 2013. TECHNICAL & SERVICE MANUAL R410A Outdoor unit [Model Name] SUZ-KA25VA4 SUZ-KA35VA4 SUZ-KA50VA4 SUZ-KA60VA4 SUZ-KA71VA4 [Service Ref.] SUZ-KA25VA4.TH

More information

Air Conditioners. Technical Data. Multi model application EEDEN MXS-H

Air Conditioners. Technical Data. Multi model application EEDEN MXS-H Air Conditioners Technical Data Multi model application EEDEN11-100 2MXS-H Air Conditioners Technical Data Multi model application EEDEN11-100 2MXS-H TABLE OF CONTENTS MXS-H 1 Features.............................................................

More information

AquaFREE System. Technical Catalogue. Outdoor units: RAS-(3~5)HVRNE RAS-(4/5)HRNE. Indoor units: RWM-(3~5)FSN1E RWM-(3~5)FSN1E-(4.

AquaFREE System. Technical Catalogue. Outdoor units: RAS-(3~5)HVRNE RAS-(4/5)HRNE. Indoor units: RWM-(3~5)FSN1E RWM-(3~5)FSN1E-(4. AquaFREE System Technical Catalogue Outdoor units: RAS-(3~5)HVRNE RAS-(4/5)HRNE Indoor units: RWM-(3~5)FSN1E RWM-(3~5)FSN1E-(4.5/6)H(1/3) Specifications in this manual are subject to change without notice

More information

1999 Toyota RAV MANUAL A/C-HEATER SYSTEMS RAV MANUAL A/C-HEATER SYSTEMS

1999 Toyota RAV MANUAL A/C-HEATER SYSTEMS RAV MANUAL A/C-HEATER SYSTEMS 1999 MANUAL A/C-HEATER SYSTEMS RAV4 SPECIFICATIONS SPECIFICATIONS Application Compressor Type Compressor Clutch Clearance Compressor Belt Tension (1) Specification Nippondenso 10PA15 10-Cyl..014-.026"

More information

CONTENTS 1. IMPORTANT NOTICE 2 2. TECHNICAL SPECIFICATION 3 3. OPERATION DETAILS 4 4. ELECTRICAL SCHEMATIC DIAGRAM 13 5. EXPLOSION VIEW 16 6

CONTENTS 1. IMPORTANT NOTICE 2 2. TECHNICAL SPECIFICATION 3 3. OPERATION DETAILS 4 4. ELECTRICAL SCHEMATIC DIAGRAM 13 5. EXPLOSION VIEW 16 6 TCL WALL MOUNTED SPLIT-TYPE AIR CONDITIONERS SERVICE MANUAL No.TE080528 Models KFTHP-12 KFTHP-18 KFTHP-24 CONTENTS 1. IMPORTANT NOTICE 2 2. TECHNICAL SPECIFICATION 3 3. OPERATION DETAILS 4 4. ELECTRICAL

More information

york air-conditioning products Residential & VRF News 2015

york air-conditioning products Residential & VRF News 2015 york air-conditioning products Residential & VRF News 2015 york air-conditioning products Catalogue Content Split Systems Pag. High wall High Efficiency Inverter YWHJZH 09 to 24 K 6 High wall Inverter

More information

DC INVERTER SPLIT SYSTEM AIR CONDITIONER

DC INVERTER SPLIT SYSTEM AIR CONDITIONER TECHNICAL & SERVICE MANUAL CSKE1NB41 & CZ18BT1U + CUKE1NK1 CSKE18NB4UW & CZ18BT1U + CUKE18NKU DC INVERTER SPLIT SYSTEM AIR CONDITIONER Indoor Model No. Body (Panel) CSKE1NB41 (CZ18BT1U) CSKE18NB4UW (CZ18BT1U)

More information

Operating Instructions Split System Air Conditioner

Operating Instructions Split System Air Conditioner Operating Instructions Split System Air Conditioner Model No. Indoor Unit Type Indoor Unit Type Nominal Capacity 26 36 F2 Low Silhouette Ducted S-26PF2U6 S-36PF2U6 Connectable outdoor unit lineup This

More information

Inspect A/C control lever adjustment. Inspect engine coolant volume. Inspect volume of refrigerant Inspect drive belt tension

Inspect A/C control lever adjustment. Inspect engine coolant volume. Inspect volume of refrigerant Inspect drive belt tension AC15 Use the table below to help you find the cause of the problem. The numbers indicate the priority of the likely cause of the problem. Check each part in order. If necessary, replace these parts. See

More information

INVERTER WALL MOUNTED TYPE ROOM AIR-CONDITIONER ( Split system, air to air heat pump type )

INVERTER WALL MOUNTED TYPE ROOM AIR-CONDITIONER ( Split system, air to air heat pump type ) Manual No. 06. SRK-T. 050 updated September 29, 2009 INVERTER WALL MOUNTED TYPE ROOM AIR-CDITIER ( Split system, air to air heat pump type ) SRK20ZD-S1, SRK25ZD-S1, SRK35ZD-S1, SRK50ZD-S1 SRK63ZE-S1, SRK71ZE-S1

More information

USER INSTRUCTIONS FOR GET PORTABLE 12k BTU AIR CONDITIONER MODEL No. GPACU12HR

USER INSTRUCTIONS FOR GET PORTABLE 12k BTU AIR CONDITIONER MODEL No. GPACU12HR USER INSTRUCTIONS FOR GET PORTABLE 12k BTU AIR CONDITIONER MODEL No. GPACU12HR CONTENTS Introduction Safety Notes Identification of parts Installation instructions Operation instructions Maintenance Troubleshooting

More information

AquaFREE system. Technical Catalogue. Outdoor units: RAS-(3~5)HVRNE RAS-(4/5)HRNE

AquaFREE system. Technical Catalogue. Outdoor units: RAS-(3~5)HVRNE RAS-(4/5)HRNE AquaFREE system Technical Catalogue Outdoor units: RAS(3~5)HVRNE RAS(4/5)HRNE Indoor units: RWM(3~5)FSN1E RWM(3~5)FSN1E(4.5/6)H(1/3) RWM(3~5)FSN1ES1 RWM(3~5)FSN1E(4.5/6)SH(1/3) Specifications in this

More information

NewAir AC-10000E, AC-10000H Portable Air Conditioner Owner s Manual PLEASE READ AND SAVE THESE INSTRUCTIONS

NewAir AC-10000E, AC-10000H Portable Air Conditioner Owner s Manual PLEASE READ AND SAVE THESE INSTRUCTIONS NewAir AC-10000E, AC-10000H Portable Air Conditioner Owner s Manual PLEASE READ AND SAVE THESE INSTRUCTIONS BEFORE USE GENERAL SAFETY INSTRUCTIONS: ALWAYS OPERATE THE UNIT IN AN UPRIGHT POSITION AND PLACE

More information

DESIGN & TECHNICAL MANUAL

DESIGN & TECHNICAL MANUAL AIR CONDITIONER Wall Mounted type DESIGN & TECHNICAL MANUAL INDOOR AS G07LECA AS G09LECA AS G12LECA AS G14LECA OUTDOOR AO G07LEC AO G09LEC AO G12LEC AO G14LEC 1. INDOOR UNIT : AS G07LECA AS G09LECA AS

More information

WATER CASSETTES HCV4S. 90x90cm 5,1 15,0 3,7 8,2. kw kw. kw kw. m 3 /h 1290

WATER CASSETTES HCV4S. 90x90cm 5,1 15,0 3,7 8,2. kw kw. kw kw. m 3 /h 1290 WATER CASSETTES HCV4S 90x90cm 3,7 8,2 kw kw 5,1 15,0 kw kw 850 m 3 /h 1290 m 3 /h HCV4S QUALITY DESIGN HIGH QUALITY CONSTRUCTION 4 SIZES90X90QUALITYDESIGN INFRARED REMOTE CONTROL DESIGN HCV4S 4 SIZE 90X90

More information

technical data air conditioning systems RZQ-B7 Twin/Triple/ Double Twin Application Split Sky Air

technical data air conditioning systems RZQ-B7 Twin/Triple/ Double Twin Application Split Sky Air technical data RZQ-B7 /Triple/ Double Application air conditioning systems Split Sky Air Split - Sky Air ISO400 assures an effective environmental management system in order to help protect human health

More information

SUBMITTAL DATA: MSZ-FH06NA & MUZ-FH06NA 6,000 BTU/H WALL-MOUNTED HEAT PUMP SYSTEM. Electrical Power Requirements. Indoor / Outdoor A 1 / 11

SUBMITTAL DATA: MSZ-FH06NA & MUZ-FH06NA 6,000 BTU/H WALL-MOUNTED HEAT PUMP SYSTEM. Electrical Power Requirements. Indoor / Outdoor A 1 / 11 M-SERIES SUBMITTAL DATA: MSZ-FH06NA & MUZ-FH06NA 6,000 BTU/H WALL-MOUNTED HEAT PUMP SYSTEM Job Name: System Reference: Date: Electrical Power Requirements 08 / 30V, 1-Phase, 60 Hz ACCESSORIES: Unit Unit:

More information

Multi-Room Ductless heat-pump systems Submittal Data: MULTI18HP230V1BO 18,000 BTU/H Wall Mounted Heat- Pump System Job Name Location Date

Multi-Room Ductless heat-pump systems Submittal Data: MULTI18HP230V1BO 18,000 BTU/H Wall Mounted Heat- Pump System Job Name Location Date Multi-Room Ductless heat-pump systems Submittal Data: 18,000 BTU/H Wall Mounted Heat- Pump System Job Name Location Date Purchaser Engineer Submitted To For Reference Approval Construction Unit Designation

More information

CONTENTS 1. IMPORTANT NOTICE 2 2. TECHNICAL SPECIFICATION 3 3. OPERATION DETAILS 4 4. WIRING DIAGRAM 11 5. EXPLOSION VIEW 12 6.

CONTENTS 1. IMPORTANT NOTICE 2 2. TECHNICAL SPECIFICATION 3 3. OPERATION DETAILS 4 4. WIRING DIAGRAM 11 5. EXPLOSION VIEW 12 6. TCL WALL MOUNTED SPLIT-TYPE AIR CONDITIONERS SERVICE MANUAL No.TE051220 Models TAC-09CHSA/GI TAC-12CHSA/GI CONTENTS 1. IMPORTANT NOTICE 2 2. TECHNICAL SPECIFICATION 3 3. OPERATION DETAILS 4 4. WIRING DIAGRAM

More information

SERVICE MANUAL MSH-24NV - MUH-24NV - Wireless type Models MSH-09NV - MUH-09NV - SPLIT-TYPE,HEAT PUMP AIR CONDITIONERS. No.

SERVICE MANUAL MSH-24NV - MUH-24NV - Wireless type Models MSH-09NV - MUH-09NV - SPLIT-TYPE,HEAT PUMP AIR CONDITIONERS. No. This Servise Manual OB07 deals with MSH-07/09//8/NV-E, MUH-07/09//8/NV-E, MSH-8NV-E, and MUH-8NV-E in OB76 REVISED EDITION-A issued in July in997. Therefore, please refer to OB07, not to OB76 REVISED EDITION-A,

More information

A/C-HEATER SYSTEM - MANUAL

A/C-HEATER SYSTEM - MANUAL A/C-HEATER SYSTEM - MANUAL 1993 Toyota Celica 1993 Manual A/C-Heater Systems Celica A/C SYSTEM SPECIFICATIONS SPECIFICATIONS TABLE Application Specification Compressor Type 4A-FE Engine... Nippondenso

More information