Identifying Long-Term Latent Damages from Salt Water Flooding
|
|
- Tracey Fitzgerald
- 8 years ago
- Views:
Transcription
1 Identifying Long-Term Latent Damages from Salt Water Flooding The Port Authority of New York & New Jersey Office of Emergency Management Presented to: Society of American Military Engineers (SAME) NJ, Philadelphia and NYC Posts & The Infrastructure Security Partnership (TISP) November 12, 2013
2 Identifying Long-Term Latent Damages from Salt Water Flooding Latent Damage the damage we can t see, that we don t always detect - Mike Sweeney, P.E., Senior VP and Metro New York Area District Leader, HNTB Corporation "Post-Sandy Recovery Effort Should Be Treated As An Opportunity To Repair Latent Damage ; Times of Trenton guest opinion column, October 3, Aside from the immediately recognizable destruction and disrepair, the school is still discovering latent damage, such as pipes rusting out, and dealing with government and insurance agencies more than six years later. Xavier University of Louisiana, The story of how one performance contract is improving university facilities beyond pre-hurricane Katrina conditions ;
3 Identifying Long-Term Latent Damages from Salt Water Flooding Based upon experience and lessons learned shared by other recovery managers. Hurricanes are disasters that take multiple years and multiple phases to overcome as some damage is yet to be exposed. OEM commissioned our disaster recovery consultants, Adjusters International, to identify and document the effects of inundation and material compatibility of, our built environment in the context of salt water: Salt Water Flooding Effects Inspection, Monitoring & Advisory Services Program.
4 Identifying Long-Term Latent Damages from Salt Water Flooding Challenges for the Port Authority Identify roots and causes of component failures Yet to be realized Repetitive (repairs already completed) Drawing a clear line between deferred maintenance (pre-disaster condition) and potential disaster damage Convincing FEMA and the FTA of the imminence of asset failure For the Port Authority, component failure has critical implications on operational and life safety components (train signals, airfield lighting, tunnel pumping capacity, etc.) Need to benchmark and document conditions before too much time passes in order for claim to be viable!
5 Identifying Long-Term Latent Damages from Salt Water Flooding Goals of the Program 1. Resurvey facilities to determine full extent of flooding and damages. Tremendous political and economic pressure to restore facility operations necessitated temporary fixes and workarounds. 2. Identify conditions warranting early action and/or intervention to stabilize critical components (secondary risks). 3. Maximize recoveries through investigation and documentation of sources of component failure as a result of the long-term effects of storm surge and flooding.
6 Identifying Long-Term Latent Damages from Salt Water Flooding Methodology Conduct visual inspections using qualified inspectors to look for the typical effects of salt water flooding: Concrete soaking and corrosion Material corrosion Erosion and undermining Displacement and dislodgement Electrical short circuiting Create a comprehensive clearinghouse of component condition, benchmarked against non-effected components, documenting the evidence of: salt residue, efflorescence, staining, trapped water, infiltration points, unexpected corrosion, spalling/carbonation, cracking, erratic operation
7 Categories of Components Inspected Aviation JFK International Airport LaGuardia International Airport Newark Liberty International Airport Teterboro Commuter Airport Specific Components Included: Runway and taxiway centerline, edge, guard-bar and signage lighting Deck and high mast lighting Substations Pump houses Air & landside pavement Blast fences, dikes and outfalls Traffic signals and toll plazas General electrical and mechanical systems
8 Categories of Components Inspected Rail Ways & Structures (tunnels, tracks & buildings) Power, Signal & Communication Cars & Equipment Transportation & Fare Collection Specific Components Included: Tunnel rings, bench walls and track beds System power and signal cables, relays, switches and impedance boxes Track switches, rails and clamping clips Fire protection systems Substation switchgear Vent buildings, caissons & maintenance facility structures and equipment Station cosmetic and mechanical systems General electrical and mechanical systems
9 Categories of Components Inspected Port Commerce Brooklyn PA Marine Terminal Howland Hook Container / Port Ivory Port Elizabeth / Newark Port Jersey North & South Specific Components Included: Seawalls, headwalls and paved surfaces Buildings and building utilities Deck and high mast lighting Substations Fire protection systems Lift stations Traffic and railroad ways, structures and signals General electrical and mechanical systems
10 Categories of Components Inspected Tunnels, Bridges & Terminals Lincoln Tunnel Holland Tunnel Specific Components Included: Tunnel portals and bulkheads Tunnel rings, bench walls, road beds and tiled surfaces Fresh air and exhaust plenums Land and river vent building structures and utilities Pump room mechanical and electrical systems Fire protection systems Traffic signal and communication systems General electrical and mechanical systems
11 Categories of Components Inspected World Trade Center Tower 1 Transportation Hub Retail Parking / Central Chiller Plant Vehicle Security Center Specific Components Included: Monolithic concrete and reinforcing steel Power distribution systems and conduit Substations Fire protection systems Grounding and bonding systems Escalator and elevator pits General electrical and mechanical systems
12 Salt Residue Salt will consume the surface it occupies until either it, or the surface is exhausted
13 Salt Residue Areas easily contrasting where concrete exposed to floodwaters absorbed and retained salt residue, and where not exposed, stayed contamination free
14 Salt Residue Salt leaching from cracks and cold seams in the ceiling, seemingly as a result of the floor above flooding
15 Some ballast is inundated with enough salt that it has become conductive, enough so, to interrupt the signal system on the rail Salt Residue
16 Salt Residue Salt water ran from behind ceiling tiles the either rained down or migrated to the walls
17 Salt Residue There are high levels of salt concentrated at interfaces between steel components caused by the floodwaters. The small areas at the interfaces are draining slower than more open fixtures and objects
18 Salt Residue high levels of salt concentrated at interfaces between steel components caused by the floodwaters. The small areas at the interfaces are draining slower than more open fixtures and objects Salt deposits remain at the low point of drainage
19 Salt Residue
20 Salt Residue Salt deposits left on the end of this conduit suggest salt water infiltration of the entire conduit as well as others at similar elevations
21 Salt Residue Salt deposits left from leaking water in this conduit. The water entered from the vent building above. Residue at a coupling usually indicates salt water had been in the conduit
22 Salt Residue Salt residue in sign control boxes
23 Salt Residue Wire is most likely inundated with salt to approximately here Salt deposits here indicate salt water has infiltrated the wire insulation approximately 7
24 Trapped Water Has been found in components one year after the storm. It can act as a corrosive medium as well as a path to ground or between conductors
25 Trapped Water Saltwater had run through electrical conduits from the general purpose side to the explosion proof side (Class 1, Div. 1), through the poured seals, and into the associated electrical boxes. In certain cases, the seals were completely pushed into the boxes. In all cases, the code required seals were rendered useless.
26 Trapped Water
27 This conduit was filled with enough water to create a small fountain effect when opened Trapped Water
28 Trapped Water Water drained from this LB for more than 3 minutes. Standing water is being found in equipment more than 11 months after the storm.
29 Trapped Water
30 Trapped Water
31 Corrosion Premature component failure
32 Corrosion Chemical Compatibility Results 3 Chemical Selected: Sea Water 1 MATERIAL Brass Carbon Steel Cast iron Polyurethane Stainless Steel -304 Stainless Steel -316 COMPATIBILITY D-Severe Effect D-Severe Effect D-Severe Effect D-Severe Effect C-Fair C-Fair 1 Cole Parmer Corporation, Chemical Compatibility Database (09-Jan-2013)
33 Corrosion
34 Corrosion
35 Corrosion Rust filled condensate from this breaker Flood line..dripped through vent holes onto these controllers
36 This lever, corroded in place, needs to move freely to actuate this boiler overtemperature safety switch Corrosion
37 Corrosion Ground wire corrosion extends beyond insulation Components corroding for the second time despite a cleaning and rebuilding by the manufacturer
38 Corrosion Corroding motor windings and wire terminations
39 Corrosion The result of rust filled trunion wheel bearings There are four trunions on each side of the crane
40 Corrosion Brass valve stems and stem guides easily corrode in the presence of salt water
41 Corrosion A corroded valve stem and guide on this fire hose connection can make this valve inoperable
42 Corrosion Corroded valve position switch is subject to failure Brass valve stems and stem guides easily corrode in the presence of salt water
43 Corrosion induced scaling of this rebar may make it un-useable unless properly cleaned Corrosion
44 Loss of bond cables or impedance boxes result in loss of signal transmission to the Train Master Corrosion
45 Corrosion has been found several feet into conductors that were submerged Corrosion
46 Corrosion Bonding & Grounding
47 Corrosion Grounding & Bonding Accelerated corrosion will occur where salt has collected on this earth ground lug and ground wire
48 Corrosion Grounding & Bonding
49 Corrosion Grounding & Bonding Loss of bond cables or impedance boxes result in loss of signal transmission to the Train Master
50 Corrosion Grounding & Bonding The diameter of the corroded portion of this ground wire is smaller than the undamaged portion
51 Corrosion Grounding & Bonding Corrosion on grounding conductors and associated hardware
52 Summary of Observations to Date Total records 11,272 Total data 214,168 Total photos 14,090
53 Identifying Long-Term Latent Damages from Salt Water Flooding What we have learned so far There is still a lot of residual salt in, on, and around components It is having a negative effect and needs to be removed City water/ DI water is not effective in rinsing off residue Removing the visible residue is not sufficient to inhibit damage PANYNJ Engineering has begun detailed engineering assessments of the more critical component systems (structural and protection systems, power distribution, safety systems). This will determine the full extent and scope of damages as well as the recommended actions to permanently restore components to operation.
54 Identifying Long-Term Latent Damages from Salt Water Flooding What comes next? Monitor and document changes in component condition Educate State and Federal grantee agencies on long-term challenges Continue the disaster recovery process with FEMA and FTA How can industry assist? Develop a unified position on effects of sea salt on component performance (research & literature) Review the implications on current codes and standards Provide guidance to owner/operators
55 Identifying Long-Term Latent Damages from Salt Water Flooding Chris Spillman, Senior Manager Port Authority of New York & New Jersey Office of Emergency Management
Standard Operating Procedures for Flood Preparation and Response
Standard Operating Procedures for Flood Preparation and Response General Discussion Hurricanes, tropical storms and intense thunderstorms support a conclusion that more severe flooding conditions than
More informationFlood Checklist ACTION TO BE TAKEN BEFORE THE FLOOD SEASON
Flood Checklist The following may serve as a checklist when preparing for a flood. This checklist should be tailored to processes/operations, flood protection equipment and flood potentials at your specific
More informationBuilding Foundation and Structure
Building Foundation and Structure Overview The construction of the Hall of Waters building began in 1936, and was constructed over the original site of the Siloam and Sulpho-Saline Springs. The original
More informationNational Transportation Safety Board Washington, DC 20594
National Transportation Safety Board Washington, DC 20594 Safety Recommendation Mr. Jack Requa Interim General Manager and Chief Executive Officer Washington Metropolitan Area Transit Authority 600 5th
More informationMTA UNIVERSAL STATION PEDESTRIAN BRIDGE Los Angeles, CA. Project Manual and Specification 100% PE SUBMITTAL TABLE OF CONTENTS
Los Angeles, CA Project Manual and Specification DIVISION 1 GENERAL CONDITIONS 01 01 10 STATEMENT OF WORK 01 11 00 SUMMARY OF THE WORK 01 14 05 METRO (OWNER) - DIRECTED STOPPAGES 01 20 00 PRICE AND PAYMENT
More informationMAINE DEPARTMENT OF ENVIRONMENTAL PROTECTION
Oxford Hills Bus Garage 36 Brown St, Norway, ME Oil Storage Inspection 2/20/14 CONDITIONS OBSERVED Underground Oil Storage: 12,000 gallon underground oil storage tank (split 10,000 gallon diesel/2,000
More informationQueens Midtown Tunnel Repair, Restoration, Rehabilitation Projects. Manhattan Community Board 6 Transportation Committee - June 2, 2014
Queens Midtown Tunnel Repair, Restoration, Rehabilitation Projects Manhattan Community Board 6 Transportation Committee - June 2, 2014 Opened to traffic in 1940 Two parallel tubes (North & South), each
More informationCRS Report for Congress
Order Code RS22285 Updated March 22, 2006 CRS Report for Congress Received through the CRS Web Hurricane-Damaged Drinking Water and Wastewater Facilities: Impacts, Needs, and Response Summary Claudia Copeland
More informationMay 5, 2010. Client Client Address. Re: Inspection Address, Chicago, Illinois. Dear Mr. Client,
PROPERTY INSPECTION PROFESSIONALS May 5, 2010 Client Client Address Re: Inspection Address, Chicago, Illinois Dear Mr. Client, On May 4, 2010, Tomacor completed a property inspection of the above referenced
More informationPolicy Clarifications on the Eligibility of Water and Wastewater Utility Projects for FEMA s Public Assistance and Hazard Mitigation Assistance Grants
Policy Clarifications on the Eligibility of Water and Wastewater Utility Projects for FEMA s Public Assistance and Hazard Mitigation Assistance Grants I. Introduction and Purpose This document provides
More informationInspections Standard Operating Procedure 5 Aboveground Storage Tanks
Aboveground Storage Tanks Aboveground Storage Tank Inspection This Standard Operating Procedure describes the steps that campus units that manage aboveground oil storage tanks (ASTs) or containers must
More information(4020-NY) ARCHITECTURAL BUILDING INSPECTION ASSESSMENT AND REPORT
FEMA Task Order 12-J-0001 (4020-NY) ARCHITECTURAL BUILDING INSPECTION ASSESSMENT AND REPORT Orange County Government Center 255 Main Street, Goshen NY February 15, 2012 1 INDEX and TABLE OF CONTENTS I.
More informationDEPARTMENT OF CODES AND BUILDING SAFETY FLOOD RECOVERY INFORMATION
May 2010 DEPARTMENT OF CODES AND BUILDING SAFETY FLOOD RECOVERY INFORMATION GUIDELINES FOR PERMITS ASSOCIATED WITH THE REPAIR OF FLOOD DAMAGED HOMES AND BUILDINGS The Department of Codes and Building Safety
More informationCrawford Inspection Services C.C.B. # 76914 www.crawfordinspections.com
Crawford Inspection Services C.C.B. # 76914 www.crawfordinspections.com Portland Area PO Box 665 West Linn, OR 97068 Ph: (503) 650-6957 Salem Area 5434 River Rd. N; #192 Keizer, OR 97303 Ph: (503) 362-5809
More informationReport for. Dick and Jane Homeowner. 1234 Lovers Lane, Houston, Texas 77000
Report for Dick and Jane Homeowner 1234 Lovers Lane, Houston, Texas 77000 March 17, 2004 I NI NP R Inspection Item I. STRUCTURAL SYSTEMS o o o A. Foundations (If all crawl space areas are not inspected,
More informationWilo SP Series Submersible Sump Pumps ECS. ECS19-15.25 ECS22-15.33 ECS24-15.50 Installation and operating instructions
Wilo SP Series Submersible Sump Pumps ECS ECS19-15.25 ECS22-15.33 ECS24-15.50 Installation and operating instructions PREINSTALLATION CHECK Inspect this pump before it is used. Occasionally, pumps can
More informationBOROUGH OF NATIONAL PARK APPLICATION FOR A CERTIFICATE OF OCCUPANCY FOR CHANGE OF OCCUPANCY ADDRESS OF PROPERTY FOR INSPECTION CURRENT OWNER
BOROUGH OF NATIONAL PARK APPLICATION FOR A CERTIFICATE OF OCCUPANCY FOR CHANGE OF OCCUPANCY ADDRESS OF PROPERTY FOR INSPECTION # BLOCK LOT VACANT YES NO CURRENT OWNER NAME ADDRESS TELEPHONE # PROSPECTIVE
More informationEvanston Main Street Station TOD Plan and Study. Appendix A.1: Station Area Existing Conditions
Evanston Main Street Station TOD Plan and Study Appendix A.1: Station Area Existing Conditions EvanstonMainStreetStation TODPlanandStudy A 1 AppendixA.1: ExistingConditions Table of Contents Station Locations
More informationAction to Take Before the Flood Season. Global Property Risk Consulting and Engineering
The following may serve as a checklist when preparing for a flood. This checklist should be tailored to processes/operations, flood protection equipment and flood potentials at your specific plant. The
More informationStructural Damage Due to Floods
Structural Damage Due to Floods By Craig D. Rogers, P.E. The Federal Emergency Management Agency (FEMA) reports that each year approximately 90 percent of all disaster-related property damage results from
More informationFloods and flash floods happen in all 50 states. Flash floods often bring walls of water 10 to 20 feet high. A car can easily be carried away by just
Floods and flash floods happen in all 50 states. Flash floods often bring walls of water 10 to 20 feet high. A car can easily be carried away by just two feet of flood water. Hurricanes, winter storms
More informationA GROUNDWATER PROTECTION PLAN FOR HOME HEATING OIL TANKS
A GROUNDWATER PROTECTION PLAN FOR HOME HEATING OIL TANKS What is a groundwater protection plan? A groundwater protection plan identifies the activities being conducted that can pollute groundwater and
More informationUniversity of Iowa Main Power Plant 2008 Flood Preparations, Event, & Recovery
University of Iowa Main Power Plant 2008 Flood Preparations, Event, & Recovery Yellow Alert for Mayflower Residence hall Peak at 31.5 feet Power Plant floods from steam tunnel and shuts down 1993 Flood
More informationCardok Sàrl CP37 CH-1295 Tannay Switzerland Phone: 0041 22 77 66 051 info@cardok.com
CARDOK CARLIFT Fast access to underground garages Fast, Silent, Discreet, Design, High-Tech Installation to replace an access ramp on private property Dimensions: (Built to measure, all dimensions can
More informationRegulated Waste Storage
Regulated Waste Storage Storage of both hazardous and non-hazardous waste is subject to federal and state regulations. Additionally, improper storage of wastes has the potential to contaminate soil, surface
More informationSECTION 807 PUMP STATION REHABILITATION
SECTION 807 PUMP STATION REHABILITATION 807-1 DESCRIPTION: Rehabilitation of pump stations shall be defined as the cleaning, removal, repair and/or replacement of any and/or all components including but
More informationDoes Part of My Basement Floor Have to Be Removed to Install. Where Does the Water from the Sump Pump Go?...Page 5
PROTECTIVE PLUMBING - WHAT IS IT? TABLE OF CONTENTS Protective Plumbing What is it?...page 1 What is Foundation Drainage?...Page 2 What is a Sump Pumping System?...Page 4 Does Part of My Basement Floor
More informationCATHODIC PROTECTION SYSTEM DESIGN
CATHODIC PROTECTION SYSTEM DESIGN Presented By DENIS L ROSSI P.E. CORROSION ENGINEER New England C P Inc. Corrosion Fundamentals What is corrosion? It is defined as the degradation or deterioration of
More informationEvaluate, Clean, and Tune Guidance
Evaluate, Clean, and Tune Guidance The Evaluate, Clean and Tune (ECT) process serves three essential purposes in the Weatherization Assistance Program (WAP). The first is to evaluate the existing system
More informationSafe & Sound Bridge Terminology
Safe & Sound Bridge Terminology Abutment A retaining wall supporting the ends of a bridge, and, in general, retaining or supporting the approach embankment. Approach The part of the bridge that carries
More informationH41 Electrical Stage Aft Air Conditioner Unit Installation
Aft Air Conditioner Unit Installation 1. Place Air-Cond unit in A/C shelf with air return facing fwd direction of the boat. 2. Do not secure Air-Cond Unit on shelf, install both side of air condition ABS
More informationReconstruction Support after the Great East Japan Earthquake
Advanced Maintenance, Energy Saving, Environment Reconstruction Support after the Great East Japan Earthquake Kan Kumagai Keyword Earthquake disaster reconstruction, Temporary restoration, Reuse, Diagnosis
More informationPine Creek Culvert Upgrade $ 560,000. Located at exiting hump dike, just south of Fire Training Center
To: BOS From: Joseph Michelangelo, P.E. Director of Public Works Re: CDBG-DR Pine Creek Culvert Upgrade Date: April 20, 2015 On June 19, 2014, the Town of Fairfield was awarded the above referenced project
More informationIAC 7/2/08 Agriculture and Land Stewardship[21] Ch 44, p.1
IAC 7/2/08 Agriculture and Land Stewardship[21] Ch 44, p.1 CHAPTER 44 ON-SITE CONTAINMENT OF PESTICIDES, FERTILIZERS AND SOIL CONDITIONERS [Prior to 7/27/88, see 21 Ch 9] PESTICIDES 21 44.1(206) Definitions.
More informationKAWERAU DISTRICT COUNCIL BUSINESS DISASTER RECOVERY PLAN 2011
KAWERAU DISTRICT COUNCIL BUSINESS DISASTER RECOVERY PLAN 2011 Kawerau District Council Private Bag 1004 Ranfurly Court KAWERAU 3169 Tel (07) 306 9009 Fax (07) 323 8072 Email kaweraudc@kaweraudc.govt.nz
More informationCapital Expenditure. The common definition of capital expenditure is
Capital Expenditure Under standard accounting practices local authorities are required to account for revenue expenditure and capital expenditure differently. Capital expenditure is defined in the Local
More informationThe total estimated PFC revenue for the application is $266,900,000. The estimated charge effective date for this application is December 1, 2016.
Public Notice of Application for Authority to Impose and Use Passenger Facility Charges (PFCs) at EWR, LGA, JFK and SWF and Amendment to Approved PFC Applications at EWR, LGA, and JFK The Port Authority
More informationEvaluating Water-Damaged Electrical Equipment
Evaluating Water-Damaged Electrical www.nema.org Evaluating Water-Damaged Electrical 1 USE OF THIS PUBLICATION This publication provides information on how to evaluate electrical equipment that has been
More informationBuilding, Plumbing, Electrical and Residential Water and Sewer Inspection Requirements
Building, Plumbing, Electrical and Residential Water and Sewer Inspection Requirements Charles County Government Planning and Growth Management P.O. Box 2150, La Plata, MD 20646 (301) 645-0692 Schedule
More informationTOWN OF HARRISBURG FIRE DEPARTMENT 6450 Morehead Road, Harrisburg North Carolina 28075 Phone: 704 455 3574 Fax 704 455 6391 www.harrisburgfd.
FLOOD FACTS AND SAFETY TIPS Floods are one of the most common hazards in the United States. Flood effects can be local, impacting a neighborhood or community, or very large, affecting entire river basins
More informationUNOPS Risk-Sensitive Planning for Resilient Infrastructure Development
UNOPS Risk-Sensitive Planning for Resilient Infrastructure Development 5 th Africa Regional Platform for Disaster Risk Reduction Abuja, Nigeria by Jeffrey Crawford, UNOPS 14 May 2014 What is Resilient
More informationWhy is my air conditioner dripping on my customers?
De-Mystifying HVAC Why is my air conditioner dripping on my customers? By Ron Prager One of the most frequent emergency service requests is a call for an air conditioner leaking water into the store. These
More informationBoiler & Pressure Vessel Inspection discrepancies and failures
Boiler & Pressure Vessel Inspection discrepancies and failures Water Heaters / Pressure Vessels Pressure Vessels are inspected once every three years. This requires a test of A: safety relief devices B:
More informationInspecting to a higher standard.
Inspecting to a higher standard. Rob Hopkin Silver Spring, MD 20902 Monday, June 2, 2014 ProTec Inspection Services Inc. 19736 Selby Ave Poolesville, MD 20837 301-972-8531 www.protec-inspections.com rob@protec-inspections.com
More informationEvaluating Water-Damaged Electrical Equipment
Evaluating Water-Damaged Electrical Equipment 1 USE OF THIS PUBLICATION This publication provides information on how to evaluate electrical equipment that has been exposed to water through flooding, fire
More informationEvaluating Water-Damaged Electrical Equipment
Evaluating Water-Damaged Electrical Equipment 1 USE OF THIS PUBLICATION This publication provides information on how to evaluate electrical equipment that has been exposed to water through flooding, fire
More informationMISCELLANEOUS ELECTRICAL JOBS REQUIRING PERMITS
MISCELLANEOUS ELECTRICAL JOBS REQUIRING PERMITS 01. SAFETY INSPECTION of service equipment at FPL Power Source 02. Construction GFI power outlets (Temp Pole for Construction) 03. 90 day temporary power
More informationGUIDELINES FOR UTILITY INSTALLATIONS Part 1 - Wire Lines and Communications Cables
Engineering Department SEPTEMBER, 2007 GUIDELINES FOR UTILITY INSTALLATIONS Part 1 - Wire Lines and Communications Cables General Requirements This section applies to all public and private utilities,
More informationSanitary Sewer Smoke Testing
Sanitary Sewer Smoke Testing Beginning March 31, 2014 The City of Brunswick will be conducting smoke testing on the City s sanitary sewer system beginning March 31, 2014. Smoke testing will occur over
More informationDuring severe flood events, such as those
Recommended Practice for Home Heating Oil Tank Flood Resistance During severe flood events, such as those occurring from Hurricane Irene and Super- Storm Sandy, many coastal and low elevation inland areas
More informationNew and Substantially Improved Buildings HVAC Systems FIGURES TABLES SECTION 3.1-1
SECTION 3.1 CONTENTS Page 3.1 Heating, Ventilating, and Air Conditioning (HVAC) Systems 3.1-2 3.1.1 Introduction 3.1-2 3.1.2 NFIP Requirements 3.1-2 3.1.3 Compressors, Heat Pumps, and Other Outdoor Equipment
More informationPort Authority of New York & New Jersey/ Port Authority Trans-Hudson (PATH) Electrician Candidate Information Bulletin
Port Authority of New York & New Jersey/ Port Authority Trans-Hudson (PATH) Electrician Candidate Information Bulletin Thank you for your interest in the Port Authority of New York & New Jersey. As one
More informationWHAT YOU DON T KNOW ABOUT ACCUMULATORS CAN KILL YOU!
WHAT YOU DON T KNOW ABOUT ACCUMULATORS CAN KILL YOU! Atlanta (Monroe) GA 770-267-3787 gpm@gpmhydraulic.com www.gpmhydraulic.com What You Don t Know About Hydraulic Accumulators Can Kill You TABLE OF CONTENTS
More informationProperty Condition Assessment
Property Condition Assessment Business, Wisconsin Inspection Date: 8/2009 Prepared For: Business Owner Report Number: TD999909 Prepared By: Shamrock Building Inspection Consultants LLC N29 W29951 Shel-Mar
More informationCOMPREHENSIVE PROPERTY INSPECTIONS
COMPREHENSIVE PROPERTY INSPECTIONS Thank you for selecting CPI for your Deficiency Observation. A full home inspection was not performed on this property at the buyers request. This inspection is a limited
More informationCertificate of Registration
Certificate of Registration This is to certify that Clancy Docwra Limited Supplier Number: 061973 are now fully registered as a supplier on UVDB for the following products/services 1.4.25 Communication
More informationELECTRICAL GUIDELINES FOR SINGLE-FAMILY HOME OWNERS:
ELECTRICAL GUIDELINES FOR SINGLE-FAMILY HOME OWNERS: Chapter 12 of the Burlington Code of ordinances allows owner occupants of single family homes to do their own wiring if they choose. If you choose to
More informationSEWER BACKUPS & BASEMENT FLOODING PREVENTATIVE SOLUTIONS FOR THE BUILDING OWNER
Village of Shorewood, Wisconsin SEWER BACKUPS & BASEMENT FLOODING PREVENTATIVE SOLUTIONS FOR THE BUILDING OWNER Prepared By: Thomas A. Zoulek, P.E., LEED A.P. Vice President Mid City Plumbing & Heating
More informationHistoric Flood Impact on the Nashville Drinking Water System. Scott Potter, Director Metro Water Services, Nashville, TN
Historic Flood Impact on the Nashville Drinking Water System Scott Potter, Director Metro Water Services, Nashville, TN Historic Event = 13.53 /48 Hours May 1 6.32 of Rain = 3rd greatest one-day rainfall
More informationWATER DAMAGE RECOVERY G U I D E
WATER DAMAGE RECOVERY GUIDE YOU CAN TRUST T TEAM RAPID 14 TH YEAR IN BUSINESS 5 YEAR WARRANTY! CERTIFIED TECHNICIANS INSURANCE COMPANY RECOMMENDED A + RATING PAYMENT PLANS! Thank You for choosing Team
More informationBASEMENT FLOODING. Prevention Guide for. Homeowners
BASEMENT FLOODING Prevention Guide for Homeowners 1 Did You Know? Floods are the most common hazards in Canada. Water damage is a common cause of loss for homeowner insurance. A heavy rainfall can result
More informationNOTICE OF BOARD OF DIRECTORS SPECIAL TELEPHONE MEETINGS
NOTICE OF BOARD OF DIRECTORS SPECIAL TELEPHONE MEETINGS CALL TO ORDER NEW JERSEY TRANSIT CORPORATION NJ TRANSIT BUS OPERATIONS, INC. NJ TRANSIT RAIL OPERATIONS, INC. NJ TRANSIT MERCER, INC. NJ TRANSIT
More informationAIR RELEASE, CLEANOUT, AND SEWER MANHOLES
AIR RELEASE, CLEANOUT, AND SEWER MANHOLES **From Hartford IM BLDG(10) DESCRIPTION. This work shall consist of the construction of air release, cleanout, and sanitary sewer manholes; and the furnishing
More informationSevere Weather Safety Resources to help weather the storm
Severe Weather Safety Resources to help weather the storm Hurricanes: By the Basics What: A Hurricane is a severe weather system that brings high winds, torrential rain, storm surges, and flooding. Hurricanes
More informationFirst in Service First in Safety
7840 Nagle Avenue Morton Grove, Illinois 60053 847-470-5235 Fax - 847-965-9511 Wind Damage; Frequently Asked Questions: What can I do with branches that fall in my yard? Bring them out to the parkway;
More informationPlumbing Identification and Damage Assessment Guide
Plumbing Identification and Damage Assessment Guide *Please note that not all systems will be represented exactly by these diagrams and photos. As a vendor, it is required that you familiar yourself with
More informationRoof Inspection. Summary Report
Phone: (561) 866 9956 www.real-estate-inspections.com Roof Inspection Summary Report Subject Property File Number: 05-15-RF-002 Inspector: Craig Milliken, PE CPM Real Estate Inspections, Inc. Date of Inspection:
More informationWalking and Working Surface Checklist:
Walking and Working Surfaces Purpose: This information is presented to improve the level of safety in our operations, and to inform you that we will comply with the OSHA Standard 29 CFR 1910.23. Responsibility:
More informationMAP KEYS GLOSSARY FOR THE DRAINAGE AND WATER REPORT
Record MAP KEYS GLOSSARY FOR THE DRAINAGE AND WATER REPORT Abandoned Gravity Private Combined Gravity Private Foul Gravity Private Surface Water Gravity Public Combined Gravity Public Foul Gravity Public
More informationCommercial Roof Inspection Form
Inspection Date: Inspector: Building Information Building ID: No.: Used For: Year Roof Applied: Building Description: Permanent Temporary Building Type: Retail Industrial Residential Building Name: Building
More informationMunchkin Heat Exchanger Maintenance
Munchkin Heat Exchanger Maintenance By: Mike Granahan *Refer to the appropriate boiler manual for your specific model number. Adjustment procedures will vary. Boiler shown below is an HTP Munchkin 80M
More informationCITY OF WASHINGTON SPILL PREVENTION, CONTROL AND COUNTERMEASURE PLAN
CITY OF WASHINGTON SPILL PREVENTION, CONTROL AND COUNTERMEASURE PLAN Adopted October 5, 2009 Table of Contents Chapter Description Page 1 Facility Descriptions... 3 1.1 Municipal Power Plant, 1001 Park
More informationwww.citiesinspection.com October 5, 2015 Dear Client,
www.citiesinspection.com October 5, 2015 Dear Client, On 9/14/2015, Cities Inspection Service, Inc. completed a building inspection of the property located at 123 Oak Street, Someplace, Minnesota for you.
More informationMUNICIPALITY OF THAMES CENTRE COMMUNITY SERVICES AND DEVELOPMENT RECREATION
REPORT NO. PR-019-15 MUNICIPALITY OF THAMES CENTRE COMMUNITY SERVICES AND DEVELOPMENT RECREATION TO: Mayor and Members of Council FROM: Liz Murray Recreation and Facilities Manager DATE: July 13, 2015
More informationVision Home Inspection
Vision Home Inspection 324 Rams Run Shepherdsville KY 40165-7877 Inspector: James McFadden Property Inspection Report Client(s): Property address: Inspection date: View report summary This report is the
More informationbout your HOUSE before you start Renovating Your Basement Moisture Problems
A bout your HOUSE before you start Renovating Your Basement Moisture Problems CE 28 c Condensation of cold surfaces, efflorescence Water leak in corner on floor Mold and decay on floor joists and sill
More informationGUIDELINES FOR WATER-DAMAGED ELECTRICAL EQUIPMENT
GUIDELINES FOR HANDLING WATER-DAMAGED ELECTRICAL EQUIPMENT NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION 1300 NORTH 17 TH STREET, SUITE 1752 ROSSLYN, VIRGINIA 22209 703 841-3200 703 841-5900 FAX WWW.NEMA.ORG
More informationUnderstanding the Risk
Understanding the Risk Flood is defined as a temporary condition of partial or complete inundation of normally dry land areas from: Overflow of inland or tidal waters Unusual or rapid accumulation of run-off
More informationWaste Handling & Disposal
Objectives Cover Contain Educate Reduce/Minimize Product Substitution Description Improper storage and handling of solid wastes can allow toxic compounds, oils and greases, heavy metals, nutrients, suspended
More informationRoof Inspection. Summary Report
www.real-estate-inspections.com Roof Inspection Summary Report Subject Property Prepared for: File Number: Client in Detroit 05-15-RF-004 Inspector: Craig Milliken, PE # 32779 CPM Real Estate Inspections,
More informationPRE-PURCHASE INSPECTION REPORT
PRE-PURCHASE INSPECTION REPORT PREPARED FOR: PROPERTY ADDRESS: Waiheke Island DATE: 21 November 2012 Page 1 of 13 (a) This is a report of a visual only, non-invasive inspection of the areas of the building
More informationSection 402. STORM SEWERS
402.02 Section 402. STORM SEWERS 402.01. Description. This work consists of constructing storm sewers of the size and class required, including excavation, bedding, and backfill. 402.02. Materials. Provide
More informationSANITARY SEWER BACKUP. Causes & Prevention
SANITARY SEWER BACKUP Causes & Prevention A. PURPOSE The purpose of this publication is twofold: 1. It provides homeowners with basic information on the causes of sanitary sewer backups. 2. It provides
More information6.7L Diesel Fuel System Contamination Diagnosis and Service Procedure Job Aid (Revised March, 2012)
6.7L Diesel Fuel System Contamination Diagnosis and Service Procedure Job Aid (Revised March, 2012) Fuel contamination on 6.7L diesel engines can damage fuel system components including the High Pressure
More informationSECTION 22 LIGHTNING PROTECTION SYSTEM
SECTION 22 LIGHTNING PROTECTION SYSTEM 22.01 SCOPE: A. These Specifications shall form a part of the Contract Documents and shall govern construction work for all buildings to be built or modified for
More informationHEDDERMAN ENGINEERING, INC. www.heddermanengineering.com Office 281-355-9911, Fax 281-355-9903 office@heddermanengineering.com
HEDDERMAN ENGINEERING, INC. www.heddermanengineering.com Office 281-355-9911, Fax 281-355-9903 office@heddermanengineering.com, 2011 TO: Mr. REF: CONDITION OF PROPERTY SURVEY Dear Mr. : At your request,
More informationTownship of Enniskillen. Asset Management Plan
Township of Enniskillen Asset Management Plan 2014 1 TABLE OF CONTENTS Page A. Introduction 3 B. State of Local Infrastructure 4 C. Desired Levels of Service 7 D. Asset Management Strategy 8 E. Financing
More informationContainer Management for Hazardous Waste Generators Technical Guidance Document HW-2005-G1
Kansas Department of Health and Environment Bureau of Waste Management 1000 SW Jackson, Suite 320, Topeka, Kansas 66612-1366 Container Management for Hazardous Waste Generators Technical Guidance Document
More informationTable of Contents. Division 2 Site Work Site Preparation Site Demolition Tree Protection Excavation, Trenching, and Backfilling for Utilities
Division 1 Requirements Design and Construction Quality Campus Master Plans Texas Tech University System Operating and Building Maintenance Project Administration Historically Underutilized Business (HUB)
More informationClimate Change and Infrastructure Planning Ahead
Climate Change and Infrastructure Planning Ahead Climate Change and Infrastructure Planning Ahead Infrastructure the physical facilities that support our society, such as buildings, roads, railways, ports
More informationFailing Culverts Structural Problems & Economic Considerations
Failing Culverts Structural Problems & Economic Considerations Al Tenbusch, President, Tenbusch, Inc. Brian Dorwart, Senior Associate, Brierley Associates Albert F. Tenbusch, Engineer, Tenbusch, Inc. June
More informationSECTION 00 0110 TABLE OF CONTENTS. H. 00 2115.01 - Proposed Material, Product or Equipment Substitution Request
SECTION 00 0110 PROCUREMENT AND CONTRACTING REQUIREMENTS 1.1 DIVISION 00 -- PROCUREMENT AND CONTRACTING REQUIREMENTS A. 00 0101 - Project Title Page B. 00 0105 - Certifications Page C. 00 0110 - Table
More information48. AQUARIUM. Aquarium. Classification: Cluster: Location: Close to junction of Inselrhue and Loiter Way, Belle Isle. Total Area: No.
Classification: Cluster: Location: Total Area: No. of Stories Aquarium Acreage Owned: Acquired: 1904 Most Recent Improvements: THE AQUARIUM Close to junction of Inselrhue and Loiter Way, Belle Isle Two
More informationSECTION 15076 CEMENT-MORTAR LINED AND COATED STEEL PIPE
SECTION 15076 CEMENT-MORTAR LINED AND COATED (CML&C) STEEL PIPE PART 1 GENERAL 1.01 DESCRIPTION This section designates the requirements for steel pipe fabrication, test in shop, installation of steel
More informationElectrical Safety Tips. Help us keep you safe
Electrical Safety Tips Help us keep you safe To help you stay safe when using electricity, ActewAGL has compiled these electrical safety tips. For natural gas safety tips please see ActewAGL s natural
More informationSPILL PREVENTION, CONTROL AND COUNTERMEASURE PLAN
SPILL PREVENTION, CONTROL AND COUNTERMEASURE PLAN XXXX FARM (CITY OR COUNTY), MICHIGAN CONTACT (NAME), OWNER CERTIFICATION: I hereby certify that I have examined the facility, and being familiar with the
More informationSolving Persistent Moisture Problems and Moisture Damage
B etter buildings Solving Persistent Moisture Problems and Moisture Damage Summary This three-storey, 15-unit, 1,300 square metre (13,993 sq. ft) walk-up was built in 1958. In the 1980s, the building started
More informationCommercial Roof Management
Disclaimer: This material is designed and intended for general informational purposes only, and is not intended, nor shall it be construed or relied upon, as specific legal advice. Roof damage is a leading
More informationTown of Amherst Flood Plan Annex
Town of Amherst Flood Plan Annex The following document is an annex to the Town of Amherst Disaster Plan and is specifically used as a guideline for Flooding events Flood Plans can enable a flexible response
More informationMechanical, Plumbing, and Fire Protection Conditions
Mechanical, Plumbing, and Fire Protection Conditions Mechanical Conditions The mechanical systems within the building consist of a combination of the original 1926 systems and renovations that occurred
More information