1 Flammable and Combustible Liquid Storage Challenges Christopher J. Wieczorek, Ph.D., FM Global David Nugent, The Valspar Corporation Global Research Update: High Challenge Storage Protection 27 June 2012, Marriott Rive Gauche, Louis Armstrong Room, Paris, France
2 FM Global One of world s largest business property insurers Clients: 1 of every 3 FORTUNE 1000 companies 176 years in business; Mutually owned Employ 1,800 engineers; No actuaries
3 FM Global Scientifically focused. Believe losses are preventable, not inevitable. We don t manufacture or sell fire sprinklers Pioneered every major development in sprinkler technology since the 1950s
4 Overview Big Picture Liquids Containers Liquids id + Containers
5 Big Picture Liquids Small Bottles 200 L Drums IBCs Flammable Combustible Class I, II, III Inflammable Liquids + Container Container
6 Big Picture Approaching the Problem Understand the Liquids Basic hazard = large pool fire Need to understand protection for liquid pool fire Understand the Containers Impact how much liquid can be released Expected to fail in fire = all fail Expected to resist failure in fire = one container
7 Liquids
8 Liquids: What Do They Mean? Flammable Liquids Expected to burn Combustible Liquids Expected to burn less or not at all. What does it mean to burn less severely? I h t t h i th il d l l it ld I have put a torch in the oil and clearly it would take some extreme event to make it burn.
9 Liquids: Fire Testing Shows Low flash point liquids (Flammable) Ignite easily Create challenging fire High flash point liquids (Combustible) Harder to ignite with a torch Easily ignite it with a packaging fire Create challenging fire
10 Liquids: Flammable Definitions NFPA Flammable 100 F (38 C) Combustible US DOT Flammable 140 F (60 C) Combustible UN Flammable 140 F (60 C) GHS Flammable 200 F (93 C) EU Flammable 131 F (55 C) FM Global Flammable Ignitable 100 F (38 C) 200 F (93 C)
11 Ignitable Liquid = Liquid That Burns
12 Liquids: Fire Testing High Flash Point Liquid Closed cup flash point > 93 o C (200 o F) 16 mm/min (0.4 gpm/ft 2 ) for 9.1 m (30 ft) roof 33 mm/min (0.8 gpm/ft 2 ) for 14 m (45 ft) roof Very High Flash Point Liquid Closed cup flash point > 260 o C (500 o F) Local area ignition - No spreading pool fire Small Bottles = Big fire
13 Containers
14 Containers: IBC Intermediate Bulk Container Capacity 450 3,000 L ( gal.) Variety of Construction Materials Metallic Plastic Composite Corrugated
15 Containers: Failure Modes Compatibility Issues at Increased Temperatures Oil-filled Soluble with HDPE Large rips form Water-filled Pinhole leaks Average time to failure - 4 times greater
16 Containers: Approval Standard Class 6020: Intermediate Bulk Containers Small scale compatibility testing Screening Large scale testing 2x2x2 array in a 9.1 m (30 ft) roof Oil filled IBCs exposed to oil pool fire K160 / 74 o C / upright / SR / 24 mm/min No breach for at least 45 minutes
17 Liquids + Containers
18 Containers: IBC Storage Palletized Storage Rack Storage
19 Liquids + Containers Protection Needed for Non-Approved IBCs Rack Storage High flash point liquids Alcohol Palletized Storage Single IBCs Composite IBCs Empty IBCs
20 Rack Storage of Oil and Alcohol In-rack Sprinklers with Barriers Effective Stop IBC failure Control local pool fire No Way to Avoid Large Pool Fire Need ceiling sprinklers for controlling pool fire
21 Palletized: Composite IBCs Single-IBC Sufficient to Ignite a Pool Single-IBC and Pool Fire can be Protected Multiple-IBCs Require Additional Protection Suppress pool fire, not fire in the flue space Not sufficient to prevent additional IBC breaches Empty IBC fire is BAD
22 Palletized: Empty IBCs Greater Hazard than Pool or Single-IBC Plastic Pallet IBCs K200 (K14.0) and 33 mm/min (0.8 gpm/ft 2 ) Wood Pallet IBCs K200 (K14.0) and 24 mm/min (0.6 gpm/ft 2 ) Public Report will be Available FPRF/PIRG
23 New Guidance DS 7-29 Protection Options for: Oil and alcohol in composite IBCs in racks VHFP liquids in composite IBCs VHFP liquids in bag-in-box box IBCs Propylene glycol in composite IBC Silicone emulsions in IBCs Empty IBCs
24 Questions Flammable & Combustible Liquids in Non- Listed Nonmetallic IBCs, David Nugent
In accordance with NFPA 30, these containers are not to store Class I flammable liquids.
In accordance with NFPA 30, these containers are not to store Class I flammable liquids. Zurich recommends storing these containers in dedicated liquid storage rooms, detached buildings, or in listed dispensing
Fire Protection Requirements of Empty Intermediate Bulk Containers (IBCs)
Research TECHNICAL REPORT Fire Protection Requirements of Empty Intermediate Bulk Containers (s) Fire Protection Requirements of Empty Intermediate Bulk Containers (s) by Seth E. Sienkiewicz FM Global
Denver Fire Department Idle Pallet Storage Guidelines Per NFPA 13_Chpt 12
Idle wood and plastic pallets introduce a severe fire condition. Stacking idle pallets in piles is the best arrangement of combustibles to promote rapid spread of fire, heat release, and complete combustion.
Warehouse Checklist. Warehouse Construction
PAGE 1 Warehouse Checklist Recent NFPA statistics estimate that in 1998 approximately 36,000 fires occurred in structures used for storage, accounting for $687mm of damage (over 10% of total fire damage
I.CHEM.E. SYMPOSIUM SERIES NO. 97
FIRE HAZARDS OF FLAMMABLE LIQUIDS IN SMALL CONTAINERS J. F. Siddle* Standards of fire protection for metal drums and smaller metal containers of flammable liquids have been well defined and have proved
Stored Palletized, Solid Piled, Bin Boxes, or Shelf Storage (12.2)
Stored Palletized, Solid Piled, Bin Boxes, or Shelf Storage (12.2) Formally part of NFPA 231 12.2.1 General 12.2.2 Protection of Class I - IV Commodities 12.2.3 Protection of Plastic & Rubber Commodities
FLAMMABLE AND COMBUSTIBLE LIQUIDS
GAP.8.1.0 A Publication of Global Asset Protection Services LLC FLAMMABLE AND COMBUSTIBLE LIQUIDS INTRODUCTION National Fire Protection Association (NFPA) documents describe a level of fire protection
Queen's University Environmental Health and Safety
April, 2009 1 SOP-Chem-08 1.0 Introduction This document is intended as a guide to the Queen s University requirements for handling and storing flammable and combustible material in non-laboratories areas.
Working Towards Protection Guidance for Warehouse Storage Li-ion Batteries
Working Towards Protection Guidance for Warehouse Storage Li-ion Batteries Benjamin Ditch, FM Global Tom Long, Exponent Inc. SUPDET 2016, March 1 4, San Antonio TX Experimental Knowledge Timeline Reducedcommodity
Presented by: Rich Perry Marsh Risk Consulting
Flammable and Combustible Liquids Presented by: Rich Perry Marsh Risk Consulting What s the Big Deal? Flammable and combustible liquids are easily ignited Ignite with explosive force Burn readily and give
Technical Article. Sprinkler Protection for High Bay and Automated Storage in Warehouse-Type Storage Facilities
Technical Article for High Bay and Automated Storage in Warehouse-Type Storage Facilities Scott Martorano, CFPS Senior Manager Technical Services February, 2010 Worldwide Fire Protection www.vikinggroupinc.com
FireLock LP-46 Storage Sprinkler V4601 Pendent FM Approved, culus Listed See Submittal Publication 40.95
.61 FireLock Storage Design Guide This Firelock Storage Design Guide (the "Guide") illustrates the performance characteristics of the full offering of Victaulic Storage s based upon selected design criteria
Notes. Material 1. Appropriate Flammable Liquids
29 CFR 1910.106 Flammable Materials Flammable Liquids Preparation 1. Read Applicable Background information and related Company Policy Chapter. 2. Make Copies of this Lesson Plan for Personnel 3. Make
HealthandSafetyOntario.ca. Introduction. Storage Containers. Storing Flammable Liquids
Flammable Liquids Storage Introduction This guideline is designed to help you store flammable liquids safely. It is based on the requirements of the Ontario Fire Code, Part 4, and of the Regulations for
A Code Review for Emergency Generators and Indoor Use of Portable Generators
A Code Review for Emergency Generators and Indoor Use of Portable Generators By: the Fire and Life-Safety Group (FLS) Fire Code requires that emergency generators be stationary generators. Therefore, a
Technical Requirements for Aboveground Storage Tanks (ASTs) Storing Class IIIB Liquids (other than used oil)
Technical Requirements for Aboveground Storage Tanks (ASTs) Storing Class IIIB Liquids (other than used oil) References: Comm 10 2009 EDITION / NFPA 30 2008 EDITION ITEM DESCRIPTION Comm 10 / NFPA General
Construction Warehouse. Culminating Experience in Fire Protection Engineering FPE 596 Prepared by Ben Johnson
Construction Warehouse Culminating Experience in Fire Protection Engineering FPE 596 Prepared by Ben Johnson Construction Warehouse Waste Treatment and Immobilization Plant (WTP) Project U.S. Department
Formal Interpretation NFPA 30. Flammable and Combustible Liquids Code. 2012 Edition
Reference: 1.1, Scope F.I. 84-4 Background: Tank trailers and semi-trailers are loaded with flammable or combustible liquid and moved to a storage yard. There, the tank vehicles may be kept for days, weeks,
ADMINISTRATIVE SERVICES MANUAL
Purpose Responsibilities Proper Storage and use of flammable liquids can significantly reduce the possibility of accidental fires and injuries. To minimize risk to life and properly, the requirements of
Sample Written Program. For. Flammable Liquids
Sample Written Program For Flammable Liquids 1 Flammable Liquids. (YOUR COMPANY NAME) Purpose Proper Storage and use of flammable liquids can significantly reduce the possibility of accidental fires and
Guidance for the storage of liquids in intermediate bulk containers ISSUE: 1 MARCH 2008
Guidance for the storage of liquids in intermediate bulk containers ISSUE: 1 MARCH 2008 Disclaimer The information in the Guidance is given in good faith and belief in its accuracy at the time of publication,
EFSN Training i Module 1. 90 Minutes
Introduction to Sprinklers EFSN Training i Module 1 90 Minutes Topics How sprinklers work Performance of sprinkler systems Types of Sprinkler Introduction to sprinkler systems Introduction ti to sprinkler
HOT WORK PERMIT PROGRAM TRAINING. John Braun
HOT WORK PERMIT PROGRAM TRAINING John Braun 1.0 INTRODUCTION 1.2 Purpose The Hot Work Permit Program has been developed for University employees that work on or around hot work activities. This program
LPG, Flammable Liquids, Toxic and Corrosive Substances
LPG, Flammable Liquids, Toxic and Corrosive Substances LPG, Flammable Liquids, Toxic and Corrosive Substances Safe Storage and Handling Today s focus is Dangerous substances under the Dangerous Substances
Antifreeze Solutions in Residential Fire Sprinkler Systems
Antifreeze Solutions in Residential Fire Sprinkler Systems The 2013 edition of NFPA 13D, as amended by TIA 13 1, discourages the use of antifreeze solutions within residential fire sprinkler systems unless
How To Safely Handle A Spill
WD DWGB 22 6 2010 Best Management Practices for Fueling and Maintenance of Excavation and Earthmoving Equipment Env Wq 401, Best Management Practices for Groundwater Protection, applies to a variety of
FLAMMABLE AND COMBUSTIBLE LIQUIDS
FLAMMABLE AND COMBUSTIBLE LIQUIDS These guidelines provide requirements for all University faculty, staff, and students using, handling, or storing flammable and combustible liquids. These requirements
TYPICAL FIRE SAFETY INSPECTION VIOLATIONS
TYPICAL FIRE SAFETY INSPECTION VIOLATIONS The following is a list of typical violations often found by inspectors and a generic solution. You can use this list to improve the safety of your facility, to
Hazardous Materials Packagings
Hazardous Materials Packagings I. Hazmat Basics Bulk Containers, Non-Bulk Packagings and Intermediate Bulk Containers Packagings and containers used to transport Hazardous Materials are regulated in the
Requirements for Fire Protection of Light Weight Floor Systems **Act 1 Revisited**
PHRC Webinar Series Tuesday, September 9, 2014 1:00 pm Requirements for Fire Protection of Light Weight Floor Systems **Act 1 Revisited** Presented by: Bryan Heitzmann Credit(s) earned on completion of
THERMAL BARRIERS FOR THE SPRAY POLYURETHANE FOAM INDUSTRY
THERMAL BARRIERS FOR THE SPRAY POLYURETHANE FOAM INDUSTRY Spray Polyurethane Foam Alliance Copyright 2005 To order copies of this publication, call 800-523-6154 and request SPFA Stock Number AY 126 TECHNICAL
How to Install Modular Wiring, Cabling and Air Distribution Devices beneath a Access Floor without a Fire Suppression System
How to Install Modular Wiring, Cabling and Air Distribution Devices beneath a Access Floor without a Fire Suppression System July 28, 2003 We are pleased to provide the following joint statement by CII,
ANNEX 6 EXAMPLES OF ARRANGEMENTS
ANNEX 6 EXAMPLES OF ARRANGEMENTS OF THE GHS LABEL ELEMENTS - 323 - Annex 6 EXAMPLES OF ARRANGEMENTS OF THE GHS LABEL ELEMENTS The following examples are provided for illustrative purposes and are subject
SPRINKLER RULES & STANDARDS IN EUROPE CEA 4001 & EN 12845
SPRINKLER RULES & STANDARDS IN EUROPE CEA 4001 & EN 12845 DAEGU: 20 th August 2010 Karim KARZAZI 1 Development of sprinkler rules & standards in Europe. Overview of past, existing and future situation
SPILL CONTAINMENT PRODUCTS
SPILL CONTAINMENT PRODUCTS CHEMISAFE spill containment products help you comply with environmental regulations. Keep your staff safe from accidental slips, protect your workfloor and limit high clean-up
JOINT CBA AND SIA GUIDANCE FOR THE STORAGE OF FLAMMABLE LIQUIDS IN SEALED PACKAGES IN SPECIFIED EXTERNAL STORAGE AREAS
JOINT CBA AND SIA GUIDANCE FOR THE STORAGE OF FLAMMABLE LIQUIDS IN SEALED PACKAGES IN SPECIFIED EXTERNAL STORAGE AREAS 1 JOINT CBA AND SIA GUIDANCE FOR THE STORAGE OF FLAMMABLE LIQUIDS IN SEALED PACKAGES
1.0 Purpose... 4. 2.0 Definitions...4. 3.0 Hot Work Operations. 5
HOT WORK PROGRAM Introduction The University of Kentucky recognizes a potential for fire from hot work operations. For that reason this program should be implemented in all departments at the University
Fire Life Safety ORC Review Guidelines for PPD Experimental Installations
Fire Life Safety ORC Review Guidelines for PPD Experimental Installations Fire Protection Review for the Fixed Target ES&H Review Committee September 2010 By James Priest PhD DRAFT Overview: When reviewing
Flammable Liquids Storage
A Health and Safety Guideline for Your Workplace Flammable Liquids Storage Introduction This guideline is designed to help you store flammable liquids safely. It is based on the requirements of the Ontario
February 2014 Alberta Fire Code 4.2.6.3. Page 1 of 5. Fire Safety and Hand Hygiene in Healthcare Facilities
FIRE CODE VARIANCE February 2014 Alberta Fire Code 4.2.6.3. Page 1 of 5 ISSUE: Fire Safety and Hand Hygiene in Healthcare Facilities This Variance covers alcohol based hand hygiene products used in healthcare
FLAMMABLE AND COMBUSTIBLE LIQUIDS. n OSHA Changes
FLAMMABLE AND COMBUSTIBLE LIQUIDS OSHA Changes Introduction This module covers the two primary hazards associated with flammable and combustible liquids: explosion and fire. In order to prevent these hazards,
NFPA 13 2002 FAQs. 3. Can plastic pipe be used on a sprinkler system complying with NFPA 13?
NFPA 13 2002 FAQs Responses to FAQs are prepared by NFPA technical staff to assist users in reading and understanding NFPA codes and standards. The responses, however, are not Formal Interpretations issued
How to prepare a DG Declaration according to IMDG (Amendment 31)
How to prepare a DG Declaration according to IMDG (Amendment 31) 1. (NEW) Continuation Page: Chapter 5.4.1.2.3 requires multiple pages of the DG Declaration be numbered consecutively. PAGE 1 of 2; PAGE
Extended Coverage Sprinklers
Extended Coverage Sprinklers Welcome ASPE Wally Barker Sprinkler Systems 101 MATERIALS OF CONSTRUCTION The components that make up a sprinkler head are: Frame or casting Deflector Fusible element or frangible
POLY DRUMS. LAB PACK - OVERPACK - SALVAGE DRUMS The Best Drums in the Field CONTENTS: What s the difference?
POLY DRUMS America s All Star Poly Drum Lineup LAB PACK - OVERPACK - SALVAGE DRUMS The Best Drums in the Field What s the difference? These tough drum products handle all of your hazardous material needs.
Flammable and Combustible Liquids. Slide 1 (of 23)
Flammable and Combustible Liquids Slide 1 (of 23) Introduction The two primary hazards associated with flammable and combustible liquids are explosion and fire Safe handling and storage of flammable liquids
Lithium Ion Batteries Hazard and Use Assessment
Lithium Ion Batteries Hazard and Use Assessment Phase IIB Flammability Characterization of Li-ion Batteries for Storage Protection Prepared by: R. Thomas Long Jr. Jason A. Sutula Michael J. Kahn Exponent,
ALVERNIA UNIVERSITY OSHA REGULATION: 29 CFR 1910.252 WELDING, CUTTING, AND BRAZING ( HOT WORK ) SECTION: 3600
OSHA REGULATION: 9 CFR 90.5 WELDING, CUTTING, AND BRAZING ( HOT WORK ) A. POLICY. This procedure follows requirements set forth in 9 CFR 90.5.. This policy applies to all Hot Work operations being done
FIRE PREVENTION PLAN
FIRE PREVENTION PLAN 1 FIRE PREVENTION PLAN OSHA s Fire Prevention Plan regulation, found at 29 CFR 1910.38(b) and 29 CFR 1926.24, requires Northern Clearing, Inc. to have a written fire prevention plan
STORAGE AND HANDLING OF FLAMMABLE AND COMBUSTIBLE LIQUIDS
Page 1 of 10 STORAGE AND HANDLING OF These guidelines provide requirements for all University faculty, staff, and students using, handling, or storing flammable and combustible liquids. These requirements
esfr pendent sprinkler vk510 (k25.2)
January 17, 2014 Sprinkler 124a 1. DESCRIPTION Viking Early Suppression Fast Response (ESFR) Pendent Sprinkler VK510 incorporates the capability to suppress specific high-challenge fires. The addition
FIRE SPRINKLER SYSTEM DESIGN, ENGINEERING EXEMPTION POLICY FOR (Effective April 1, 2006)
State of Tennessee Department of Commerce and Insurance Board of Architectural and Engineering Examiners 500 James Robertson Parkway Nashville, TN 37243 1142 800 256 5758 615 741 3221 (Nashville Area)
MATERIAL SAFETY DATA SHEET
MATERIAL SAFETY DATA SHEET SECTION 1 -- CHEMICAL PRODUCT AND COMPANY IDENTIFICATION PRODUCT NAME Sav-A-Hoof Protectant PRODUCT CODE 309 ISSUE DATE 11/15/14 EMERGENCY TELEPHONE NUMBERS DISTRIBUTOR SBS EQUINE
Flammable liquid classes: Combustible Liquid Classes. Class IC. Class II. Class IB F.P. below 22.8 C (73 F), boiling point at or above 37.
BCFC Part 4 Flammable and Combustible Liquids Application: BCFC Part 4 Part 4 provides for the storage, handling, use and processing of flammable liquids and combustible liquids in buildings,, structures
Flammable Liquids Storage
A Health and Safety Guideline for Your Workplace Flammable Liquids Storage Introduction This guideline is designed to help you store flammable liquids safely. It is based on the requirements of the Ontario
OFF! DEEP WOODS SPORTSMEN INSECT REPELLENT I (PUMP SPRAY)
1. PRODUCT AND COMPANY IDENTIFICATION Product information Trade name : OFF! DEEP WOODS SPORTSMEN INSECT REPELLENT I (PUMP Use of the : Insect Repellent Substance/Preparation Company : S.C. Johnson and
PEROXIDE SAFETY DATA SHEET (60% H2O2) Safety Data Sheet
SAYFA : 1/6 1. Identification of the substance Identification of the product Product name : Hydrogen peroxide solution 60% Manufacturer / supplier identification Company : A.Ş. 600Evler Mahallesi Atatürk
Combustible Dust - Things that go Boom. W. Jon Wallace, CSP, MBA Workplace Group, LLC O: 919.933.5548 E: jwallace@workplacegroup.
Combustible Dust - Things that go Boom W. Jon Wallace, CSP, MBA Workplace Group, LLC O: 919.933.5548 E: [email protected] Presentation Objectives After attending this presentation you will: Learn
SECTION 1: GENERAL INFORMATION
Part 1B: Physical Chemical Properties of Selected Fuels SECTION 1: GENERAL INFORMATION DOT Number UN 1049 UN 1966 CH 4 8399%; C 2H 6 113% UN 1971 UN 1075 UN 1978 C 4C 12 C 8C 25 UN 1230 UN 1170 UN 1203
Newson Gale. Is it ever Safe to use Plastic Drums and Containers in Hazardous areas? White Paper. Author Details:
White Paper Is it ever Safe to use Plastic Drums Author Details: Mike O Brien, Head of Product Marketing for If you have any questions relating to the topics discussed in this article, you can contact
527 CMR: BOARD OF FIRE PREVENTION REGULATIONS 527 CMR 14.00: FLAMMABLE AND COMBUSTIBLE LIQUIDS, FLAMMABLE SOLIDS OR FLAMMABLE GASES
527 CMR 14.00: FLAMMABLE AND COMBUSTIBLE LIQUIDS, FLAMMABLE SOLIDS OR FLAMMABLE GASES Section 14.01: Scope 14.02: Definitions 14.03: Storage 14.04: Handling of Flammable Fluids 14.05: Handling of Flammable
LIFE SAFETY UPDATE. FULL SPRINKLERING OF ALL NURSING FACILITIES ADDITIONAL CLARIFICATIONS Prepared by Eric Rosenbaum, P.E. Hughes Associates, Inc.
LIFE SAFETY UPDATE FULL SPRINKLERING OF ALL NURSING FACILITIES ADDITIONAL CLARIFICATIONS Prepared by Eric Rosenbaum, P.E. Hughes Associates, Inc. The purpose of this update is as follows: Remind all state
SAFE TRANSFER OF POWDERS INTO FLAMMABLE LIQUIDS David E. Kaelin Sr., Senior Process Safety Specialist
Hazards Control & Assess- SAFE TRANSFER OF POWDERS INTO FLAMMABLE LIQUIDS SAFE TRANSFER OF POWDERS INTO FLAMMABLE LIQUIDS David E. Kaelin Sr., Senior Process Safety Specialist A major consideration in
F.Y.I. Specifying Fire Protection Systems Using Division 13
F.Y.I. Specifying Fire Protection Systems Using Division 13 Automatic fire sprinkler systems and fire alarm and detection systems are increasingly installed in modern buildings. Even where building codes
BP WIND ENERGY POLICIES AND PROCEDURES
BP WIND ENERGY POLICIES AND PROCEDURES Document Control Details 1.0 Purpose/Scope 1.1 This procedure provides the minimum requirements to be followed for the storage of flammable or combustible materials
Compressed Gases The Dangers
Compressed Gases COMPRESSED Compressed gases are any gases or mixture of gases exerting a gauge pressure of 6 pounds per square inch at 68 F. Federal regulations specify how these gases must be stored
TECHNICAL DATA 2. LISTINGS AND APPROVALS. Spray Nozzle 11. December 20, 2013
Spray Nozzle 11 1. DESCRIPTION Viking Model C-1 Window Sprinklers are non-automatic, open, outside intended for protection of windows, walls, and roofs against exposure fires. The directional discharge
HIGH-PILED COMBUSTIBLE STORAGE
CHAPTER 23 HIGH-PILED COMBUSTIBLE STORAGE SECTION 2301 GENERAL 2301.1 Scope. High-piled combustible storage shall be in accordance with this chapter. In addition to the requirements of this chapter, the
Plan Review and Construction Project Guidelines for Columbia University & CUMC NYC
Plan Review and Construction Project Guidelines for Columbia University & CUMC NYC Prepared by Factory Mutual Insurance Company 400 Interpace Parkway Building C Third Floor Parsippany, NJ 07054-1196 2013
HIGH-PILED COMBUSTIBLE STORAGE
CHAPTER 23 HIGH-PILED COMBUSTIBLE STORAGE SECTION FC 2301 GENERAL 2301.1 Scope. This chapter shall govern high-piled combustible storage, and the design, installation, operation and maintenance of any
Boiler & Pressure Vessel Inspection discrepancies and failures
Boiler & Pressure Vessel Inspection discrepancies and failures Water Heaters / Pressure Vessels Pressure Vessels are inspected once every three years. This requires a test of A: safety relief devices B:
Flammable Storage in a Biotech Facility
Deputy Chief Gerard Mahoney; Chairman 100 Smith Place Cambridge, MA, 02138 (617) 349-4944 Fax: (617) 349-4905 Mailing Address: 491 Broadway Cambridge, MA 02138 Flammable Storage - Intro Date: 12/09/2009
Section III Hazardous Materials Management
Section III Hazardous Materials Management This section of the Everyday Hazmat User s Training Guide covers various types of hazardous materials commonly found in the USDA Forest Service. Federal regulations
SAFETY DATA SHEET INSTANT HAND SANITIZER GEL / SANTI-GEL
SECTION 1 PRODUCT AND COMPANY IDENTIFICATION Product Name : Product Codes : 5607, 5612, 5619, 5630, 5634, 5635, 5647, 5666, 5679, 5682, 5693, 65636, 6667 Recommended use : Hand sanitizer Product dilution
FACILITY FIRE PREVENTION AND EMERGENCY PREPAREDNESS INSPECTION CHECKLIST
FACILITY FIRE PREVENTION AND EMERGENCY PREPAREDNESS INSPECTION CHECKLIST Date of Inspection: Conducted by: Location: Reviewed by: Date of Review: Comments or additional corrective action taken as a result
Ontario Fire Code SECTION 5.13 DIP TANKS. Illustrated Commentary. Office of the Ontario Fire Marshal
Ontario Fire Code SECTION 5.13 DIP TANKS Illustrated Commentary Office of the Ontario Fire Marshal Dip Tanks Illustrated Commentary 1 5.13.1. Location 5.13.1.1. Dip tank operations involving flammable
Grounding and Bonding Against Static Electricity. Jon Koppari, CSP, MS Occupational Safety and Health Instructor OSHA Training Institute
Grounding and Bonding Against Static Electricity Jon Koppari, CSP, MS Occupational Safety and Health Instructor OSHA Training Institute Objectives Identify Sources of Ignition. Identify Hazards associated
WINDEX ORIGINAL GLASS CLEANER
1. PRODUCT AND COMPANY IDENTIFICATION Product information Trade name : Use of the : Hard Surface Cleaner Substance/Mixture Company : S.C. Johnson & Son, Inc. 1525 Howe Street Racine WI 53403-2236 Emergency
Casey C. Grant, P.E., FSFPE Research Director Fire Protection Research Foundation
RESEARCH FOUNDATION ACTIVITIES AND OUTCOMES IN DETECTION AND SUPPRESSION SYSTEMS Casey C. Grant, P.E., FSFPE Research Director Fire Protection Research Foundation Madrid, del 23 al 25 de febrero de 2010
EACH CLASS of fire A, B, C, or D has a different source. Some
Classes of Fires and Types of Extinguishers EACH CLASS of fire A, B, C, or D has a different source. Some principles apply to putting out all fires. However, certain procedures and products are used only
FDNY C14 Certificate of Fitness Quiz
FDNY C14 Certificate of Fitness Quiz Name: Date: 1. Who issues a New York City laboratory permit? a) Department of Environmental Protection (DEP) b) Department of Environmental Conservation (DEC) c) Occupational
Installation Instructions for Alarm Module Kit A043F059
Instruction Sheet 07-2013 Installation Instructions for Alarm Module Kit A043F059 1 Introduction The information contained within is based on information available at the time of going to print. In line
Static Spark Ignites Flammable Liquid during Portable Tank Filling Operation
Static Spark Ignites Flammable Liquid during Portable Tank Filling Operation No. 2008-02-I-IA (September 2008) Key Lessons for Safe Handling and Storage of Flammables Ensure that equipment, such as fill
OSHA Office of Training and Education 1
Flammable and Combustible Liquids OSHA Office of Training and Education 1 Introduction The two primary hazards associated with flammable and combustible liquids are explosion and fire Safe handling and
WINDEX ORIGINAL GLASS CLEANER
1. PRODUCT AND COMPANY IDENTIFICATION Product information Trade name : Use of the : Hard Surface Cleaner Substance/Mixture Company : S.C. Johnson and Son, Limited 1 Webster Street Brantford ON N3T 5R1
Material Safety Data Sheet
Material Safety Data Sheet OASIS 259 GLASS FORCE 1. Product and company identification Trade name of product Product use Product dilution information : OASIS 259 GLASS FORCE : Glass Cleaner : Up to 12.5
Department of Transportation Hazardous Material Regulations General Awareness, Safety & Security Training. For: University of Dayton Hazmat Employees
Department of Transportation Hazardous Material Regulations General Awareness, Safety & Security Training For: University of Dayton Hazmat Employees February, 2014 Overview Hazardous materials are substances
ASME B31.3 Process Piping. Scope of B31.3 Course
ASME B31.3 Process Piping Charles Becht IV, PhD, PE Don Frikken, PE Instructors BECHT ENGINEERING COMPANY, INC. Introduction -1 Scope of B31.3 Course This course covers piping as typically used in process
**** MATERIAL SAFETY DATA SHEET **** 22204 - STABIL Fuel Stabilizer **** SECTION 1 - CHEMICAL PRODUCT AND MANUFACTURER IDENTIFICATION ****
**** MATERIAL SAFETY DATA SHEET **** 22204 - STABIL Fuel Stabilizer SEC 1 - PRODUCT AND MANUFACTURER INFO SEC 2 - COMPOSITION INFORMATION SEC 3 - HAZARDS IDENTIFICATION SEC 4 - FIRST AID MEASURES SEC 5
NFPA 30-2008: Basic Requirements for Storage Tanks
NFPA 30-2008: Basic Requirements for Storage Tanks New York City Metro Chapter Society of Fire Protection Engineers New York, NY February 22, 2011 NFPA 30, Flammable and Combustible Liquids Code Storage
PLEDGE WITH FUTURE SHINE PREMIUM FLOOR FINISH
1. PRODUCT AND COMPANY IDENTIFICATION Product information Trade name : Use of the : Floor Polish/Cleaner Substance/Preparation Company : S.C. Johnson & Son, Inc. 1525 Howe Street Racine WI 53403-2236 Emergency
Fire testing for BCA compliance
Fire testing for BCA compliance SFS NSW Chapter December 2010 Vince Dowling Fire Science and Technology Australia Standards and Specifications Type Purpose Examples Test method How to do the test and what
Safe Operating Procedure
Safe Operating Procedure (Revised 07/09) HOT WORK PERMIT OPERATIONS (For assistance, please contact EHS at (402) 472-4925, or visit our web site at http://ehs.unl.edu/) Authority In recognition of the
Safety Data Sheet. EPSON INK CARTRIDGE T220XL220 Ink for Epson Printers. Proprietary organic materials - 10-15 none. Glycerols 56-81-5 5-10 none
Safety Data Sheet Section 1 : Identification of substance and company undertaking 1.1 1.2 1.3 Product identifier: Relevant substance use: Supplier details Distributor : Address : Telephone : FAX : EPSON
Trade Name of this Product Isopropyl Rubbing Alcohol 91% USP. Corporate Compliance Team 1666 East Touhy Avenue
Page 1 of 5 MSDS Document Product 1. Chemical Product and Company Identification Trade Name of this Product Manufacturer Contact Name Lawson Products, Inc. Corporate Compliance Team 1666 East Touhy Avenue
Static Electricity. A Health and Safety Guideline for Your Workplace. What Are Some Sources of Static Electricity? What is Static Electricity?
A Health and Safety Guideline for Your Workplace What is static electricity? What causes it? How is it hazardous? And, most importantly, how can it be controlled? All of these questions will be answered