F.Y.I. Specifying Fire Protection Systems Using Division 13

Size: px
Start display at page:

Download "F.Y.I. Specifying Fire Protection Systems Using Division 13"

Transcription

1 F.Y.I. Specifying Fire Protection Systems Using Division 13 Automatic fire sprinkler systems and fire alarm and detection systems are increasingly installed in modern buildings. Even where building codes do not require these systems, knowledgeable and responsible professionals recognize the exceptional value of automatic on-site fire suppression. These state-of-the-art protection systems economically reduce the loss of life and property from fire. The increased demand for fire protection systems has resulted in the development of separate industries to fill these needs. These industries have responded with new products and technologies, aimed at increasing both the effectiveness of the systems and their economical installation in buildings. Traditionally, the separate identify of the fire protection industry is not well recognized. Fire sprinkler systems were often lumped with building mechanical systems, and alarm and detection systems were considered an extension of the building s electrical system. This categorization prevented the design professional from making knowledgeable up-front decisions regarding the installation of the fire protection systems, which in turn affected other basic design decisions. It also created conflicts within project specifications and lack of coordination between fire protection trades. In 1995, the Construction Specifications Institute and Construction Specifications Canada revised their MasterFormat. The new revisions place both detection and alarm systems and fire suppression systems in Division 13 for Special Construction. The use of Division 13 promises more economical and effective fire protection for today s buildings. Why Division 13? The CSI/CSD MasterFormat arranges related construction products and activities into sixteen level one titles, called divisions. In the past, fire sprinkler and other suppression systems were often located within Division 15--Mechanical. Detection and alarm systems were located within Division 16--Electrical. This relegated these important specifications to subsection status, prevented early decision-making which could utilize these systems to their maximum design potential and hampered coordination between the suppression and alarm industries. Division 13 addresses special construction, systems and features which are not common to all buildings, but which require special consideration. This list includes diverse systems such as security access and surveillance, hazardous material remediation, and lightning protection. By using Division 13 for fire protection systems specifications, design professionals can eliminate a host of problems and conflicts.

2 What Conflicts Are Avoided? In the United States and Canada, fire protection systems are installed in accordance with standards developed by the National Fire Protection Association (NFPA). The NFPA standards rely heavily upon product evaluation and listings by organizations such as Underwriters Laboratories and Factory Mutual Research Corporation. As a result of the need to comply with specialized fire protection standards, there may often be conflicts with the general requirements found in Division 15 for Mechanical systems and Division 16 for Electrical systems. Even basic specifications for piping and hangers may produce conflicts. Manufacturers of fittings for both the mechanical and fire protection industries often reference ASME standards for the mechanical systems and NFPA standards for the fire protection systems. The Underwriters Laboratories requirements for pipe hangers for fire protection piping do not match those of the Manufacturers Standardization Society for mechanical piping. Where sprinkler systems are specified as a subset of mechanical systems, contractors are often directed to adhere to certain aspects of the general mechanical specifications that are in conflict with codified fire protection standards. This can lead to misinterpretations, misunderstandings, and contractual disputes. How can the use of Division 13 improve design decisions? Modern building codes contain a number of construction alterations or "trade-off" by which the installation of fire protection systems like automatic sprinklers can reduce other fire protection requirements. Examples include larger building areas for specific construction types, reduced fire separation and fireproofing requirements for building members, longer exit travel distances, a wider range of interior finish materials, and elimination of special exit windows or devices. Making design decisions relative to fire protection systems early in the design process permits a design professional to take full advantage of these code-based construction alternatives. In many jurisdictions, the "trade-off" extend beyond the building walls. For example, installation of automatic fire sprinkler systems is permitted to reduce fire flow demands of community water systems, increase hydrant spacing, permit construction in outlaying areas, and increase zoning density. An intelligent design professional will explore these options before committing to a particular building design. Working with fire protection systems at an early point in Division 13 permits a more direct relationship between the design professional and fire protection professionals who can assist in exploring the cost and versatility of various fire protection system options. For example, the use of new technology ESFR sprinklers can eliminate the need for in-rack sprinklers in warehouses, but only if the initial design decisions permit an acceptable type of roof construction.

3 How are fire protection systems specified? Under the new Division 13 concept, Detection and Alarm Equipment is specified as Section While this section also includes gas detection and leak detection, it permits smoke detection and fire alarm systems to be directly specified outside of Division 16--Electrical. In general, specification should be in accordance with the options presented by NFPA 72--The National Fire Alarm Code. Much of the current alarm detection technology utilizes low-voltage equipment and is only interconnected with the building electrical system through a system control panel. The use of low-voltage equipment permits more economical provision of emergency power required under the standard. Automatic Fire Suppression Systems are now specified within the following subsections of Section Fire Suppression: Fire Protection Basic Materials and Methods Hangers and Supports Pipe and Fittings Piping Specialties Valves Fire Pumps Wet-Pipe Fire Suppression Sprinklers Dry-Pipe Fire Suppression Sprinklers Pre-Action Fire Suppression Sprinklers Combination Dry-Pipe and Pre-Action Deluge Fire Suppression Sprinklers Foam Fire Extinguishing Alternative Fire Extinguishing Systems Halon Alternatives Water Mist Dry Chemical Fire Extinguishing Standpipes and Hoses Most of these fire suppression systems have applicable NFPA standards which can be referenced: Wet-Pipe Sprinklers NFPA 13 - for most buildings NFPA 13R - for residential buildings up to four stories in height NFPA 13D-for one- and two- family dwellings and manufactured homes Dry-Pipe Sprinkler Systems Pre-Action Sprinkler Systems Combination Dry-Pipe/Pre-Action Systems NFPA 13

4 Storage/Warehouse Sprinkler Systems NFPA for non-miscellaneous storage NFPA 231C - for storage on racks NFPA 231D - for rubber tire storage NFPA 231F - for storage of rolled paper NFPA 30 - for storage of flammable and combustible liquids NFPA 30B - for storage of aerosols Foam-Water Sprinkler Systems NFPA 16 - Foam Water Deluge Sprinkler Systems NFPA 16A - Closed-Head Foam-Water Sprinkler Systems Fire Pumps NFPA 20 Standpipe and Hose Systems NFPA 14 Private Fire Service Mains (Yard Systems and Hydrants) NFPA 24 Carbon Dioxide Systems NFPA 12 Water Spray Deluge Systems NFPA 15 Clean Agent (Halon Alternatives) NFPA 2001 Water Mist Systems NFPA 750 Dry/Wet Chemical Systems NFPA 17/17A In many cases, these standards are adopted as applicable reference standards by building codes. Where appropriate, they provide a set of reasonable minimum standards to ensure quality system design and installation. Manufacturers literature can often be used to enhance specifications by identification of specific features of equipment desirable for aesthetic or other purposes. Is professional help available? Working with the National Fire Sprinkler Association and the Automatic Fire Alarm Association, the Society of Fire Protection Engineers endorsed the move of fire protection specifications from Divisions 15 and 16 to Division 13. Fire protection engineering is now a recognized and distinct specialty licensing area in most states. Especially in unusual, complex, or high hazard occupancies, a fire protection engineer should be consulted to assist in the development of appropriate fire protection system specifications. Essential system design criteria can thereby be included in the project specifications. Utilizing the provisions of the applicable NFPA standards, fire protection engineering technicians working in the employ of fire protection contractors can then prepare detailed working plans. Most states now license fire protection contractors, and licensing laws generally specify minimum demonstrated levels of technical competency. The National Institute of Certification in Engineering Technologies (NICET) maintains a program of testing and certification which is

5 referenced by state licensing laws. NICET offers certification for technicians in the field of fire protection within three separate subfields: Automatic Sprinkler Systems Alarm and Detection Special Hazards How does the use of Division 13 improve coordination? As building codes increasingly rely upon fire protection systems, the interface between the fire suppression systems industry and the fire alarm detection industry also increases. The use of Division 13 permits easy identification of system interface issues. In general, this consists of alarm service indicating activation of a fire suppression system, as well as supervisory served indicating the ready condition of key system components. Examples include tamper switches on system control valves and temperature monitors on stored water supplies. How will the use of Division 13 affect the building owner? The building owner is the chief beneficiary of the use of Division 13 for fire protection system specifications. Every improvement in design efficiency, coordination, and elimination of conflicts translates to reduced construction costs. And the building owner will also benefit from the improvement in reliability and protection that is the inevitable result of greater attention to fire protection system specifications. How does one obtain the Master Format? The MasterFormat is available from: The Construction Specifications Institute 601 Madison Street Alexandria, Virginia Telephone: (800) Fax: (703) Construction Specifications Canada 100 Lombard Street, Suite 200 Toronto, Ontario M5C 1M3 Telephone: (416) Fax: (416) For More Information, Contact: National Fire Sprinkler Association, Inc. 40 Jon Barrett Road - Patterson, NY Telephone: (845) Fax: (845)

FOR CERTIFICATION AS PRESCRIBED BY THE STATE FIRE PREVENTION COMMISSION ON NOVEMBER 11, 2009 IN ACCORDANCE WITH THE STATE FIRE PREVENTION REGULATIONS

FOR CERTIFICATION AS PRESCRIBED BY THE STATE FIRE PREVENTION COMMISSION ON NOVEMBER 11, 2009 IN ACCORDANCE WITH THE STATE FIRE PREVENTION REGULATIONS EXAMINATION REQUIREMENTS FOR FIRE SUPPRESSION SYSTEM CERTIFICATION AS PRESCRIBED BY THE STATE FIRE PREVENTION COMMISSION ON NOVEMBER 11, 2009 IN ACCORDANCE WITH THE STATE FIRE PREVENTION REGULATIONS REGULATION

More information

ALBERTA FIRE CODE SAFETY EQUIPMENT MAINTENANCE REQUIREMENTS

ALBERTA FIRE CODE SAFETY EQUIPMENT MAINTENANCE REQUIREMENTS ALBERTA FIRE CODE SAFETY EQUIPMENT MAINTENANCE REQUIREMENTS In this document are the fire safety equipment maintenance requirements that are found in Division B of the Alberta Fire Code (AFC 2006) for

More information

DEPARTMENT OF CONSUMER AND INDUSTRY SERVICES DIRECTOR'S OFFICE

DEPARTMENT OF CONSUMER AND INDUSTRY SERVICES DIRECTOR'S OFFICE DEPARTMENT OF CONSUMER AND INDUSTRY SERVICES DIRECTOR'S OFFICE CERTIFICATION OF FIRMS FOR FIRE ALARM SYSTEMS AND FIRE SUPPRESSION SYSTEMS IN STATE-REGULATED FACILITIES (By authority conferred on the state

More information

Appendix B Forms for Inspection, Testing, and Maintenance

Appendix B Forms for Inspection, Testing, and Maintenance Appendix B Forms for Inspection, Testing, and Maintenance This appendix is not a part of the requirements of this NFPA document but is included for informational purposes only. Forms need to be complete

More information

Winnipeg Fire Department Fire Prevention Branch

Winnipeg Fire Department Fire Prevention Branch Winnipeg Fire Department Fire Prevention Branch Manitoba Fire Code Life-Safety Equipment Maintenance Requirements The Fire Prevention Branch of the Winnipeg Fire Department has prepared this document of

More information

BUILDING OWNERS - SERVICE RELATED ISSUES FOR FIRE ALARM SYSTEMS

BUILDING OWNERS - SERVICE RELATED ISSUES FOR FIRE ALARM SYSTEMS BUILDING OWNERS - SERVICE RELATED ISSUES FOR FIRE ALARM SYSTEMS Owners have numerous responsibilities as it pertains to the maintenance and operation of a building s fire safety equipment. The liabilities

More information

Fire Alarm System Standpipes Sprinkler Systems Fire Drills Commercial Cooking Hood and more

Fire Alarm System Standpipes Sprinkler Systems Fire Drills Commercial Cooking Hood and more FIRE PROTECTION SYSTEMS Fire protection systems, measures and equipment are all related to the safety of the occupants and the protection of the property. As part of a building design and its intended

More information

INSPECTION, TESTING AND MAINTENANCE OF FIRE PROTECTION SYSTEMS AND EQUIPMENT

INSPECTION, TESTING AND MAINTENANCE OF FIRE PROTECTION SYSTEMS AND EQUIPMENT CITY OF SPRING LAKE PARK Code Enforcement Department 1301 81 st Avenue NE Spring Lake Park MN 55432 Business Phone 763-784-6491 Fax 763-792-7257 INSPECTION, TESTING AND MAINTENANCE OF FIRE PROTECTION SYSTEMS

More information

CHAPTER 69A-46 FIRE PROTECTION SYSTEM CONTRACTORS AND SYSTEMS

CHAPTER 69A-46 FIRE PROTECTION SYSTEM CONTRACTORS AND SYSTEMS CHAPTER 69A-46 FIRE PROTECTION SYSTEM CONTRACTORS AND SYSTEMS 69A-46.001 69A-46.010 69A-46.015 69A-46.016 69A-46.0165 69A-46.017 69A-46.025 69A-46.030 69A-46.035 69A-46.040 69A-46.041 Scope Submission

More information

REGULATIONS for INSTALLATION, MAINTENANCE, and TESTING APPLICATION PACKET

REGULATIONS for INSTALLATION, MAINTENANCE, and TESTING APPLICATION PACKET REGULATIONS for INSTALLATION, MAINTENANCE, and TESTING FIRE SUPPRESSION SYSTEMS APPLICATION PACKET CITY OF NAPERVILLE 400 S. EAGLE STREET NAPERVILLE, Il 60540 PHONE: 630.420.6070 FAX: 630.420.6657 Fire

More information

Ontario Association of Fire Chiefs Position Paper Residential Fire Sprinklers

Ontario Association of Fire Chiefs Position Paper Residential Fire Sprinklers Ontario Association of Fire Chiefs Position Paper Residential Fire Sprinklers The Ontario Association of Fire Chiefs (OAFC) supports changes to the Ontario Building Code to require that all new residential

More information

Required Certification Documentation. Contractor's installation certification for range hood fire suppression systems.

Required Certification Documentation. Contractor's installation certification for range hood fire suppression systems. OFFICE OF UNIVERSIT BUILDING OFFICIAL PROJECT/CONSTRUCTION MAGER: Sample Manager Required Aboveground only Required Certification Documentation Contractor s material and test certifications for both above

More information

EFSN Training i Module 1. 90 Minutes

EFSN Training i Module 1. 90 Minutes Introduction to Sprinklers EFSN Training i Module 1 90 Minutes Topics How sprinklers work Performance of sprinkler systems Types of Sprinkler Introduction to sprinkler systems Introduction ti to sprinkler

More information

PLAN SUBMITTAL REQUIREMENTS FOR SPRAY BOOTHS AND SPRAYING ROOMS EXTINGUISHING SYSTEMS

PLAN SUBMITTAL REQUIREMENTS FOR SPRAY BOOTHS AND SPRAYING ROOMS EXTINGUISHING SYSTEMS January 1997 PLAN SUBMITTAL REQUIREMENTS FOR SPRAY BOOTHS AND SPRAYING ROOMS EXTINGUISHING SYSTEMS 1.0 PERMIT 1.1 After receipt of a Building Permit from the City of San Jose Building Department, submit

More information

F.Y.I. Who Designs Fire Sprinkler Systems?

F.Y.I. Who Designs Fire Sprinkler Systems? F.Y.I. Who Designs Fire Sprinkler Systems? This pamphlet was prepared by the Engineering Department of the National Fire Sprinkler Association,Inc. (NFSA). Established in 1914, the NFSA is a non-profit

More information

SARATOGA FIRE DISTRICT EARLY WARNING FIRE ALARM SYSTEM STANDARDS AND REQUIRMENTS CONTENTS

SARATOGA FIRE DISTRICT EARLY WARNING FIRE ALARM SYSTEM STANDARDS AND REQUIRMENTS CONTENTS SARATOGA FIRE DISTRICT EARLY WARNING FIRE ALARM SYSTEM STANDARDS AND REQUIRMENTS CONTENTS I. APPLICATION AND DEFINITIONS 1.01 Authorization for Standards 1.02 Application of Standards 1.03 Definitions

More information

ANNUAL FIRE PROTECTION SUMMARY INFORMATION REPORTING GUIDE Revised: May 2011

ANNUAL FIRE PROTECTION SUMMARY INFORMATION REPORTING GUIDE Revised: May 2011 ANNUAL FIRE PROTECTION SUMMARY INFORMATION REPORTING GUIDE Revised: May 2011 Organizations responsible for maintaining property under stewardship of DOE and the Administrator, NNSA, will seek concurrence

More information

Automatic fire-extinguishing systems for commercial cooking

Automatic fire-extinguishing systems for commercial cooking Automatic fire-extinguishing systems for commercial cooking Leading Items First Ignited in Eating and Drinking Establishment Structure Fires, 2000-2004 Annual Averages Cooking materials, incl. food and

More information

MAINTENANCE AND SERVICE OF AUTOMATIC FIRE EXTINGUISHING SYSTEMS

MAINTENANCE AND SERVICE OF AUTOMATIC FIRE EXTINGUISHING SYSTEMS FIRE DEPARTMENT Bureau of Fire Protection and Life Safety www.cityofsanmateo.org 1900 O Farrell, Suite 140 San Mateo, CA 94403-1332 (650) 522-7940 FAX: (650) 522-7941 TDD: (650) 522-7047 MAINTENANCE AND

More information

AON SPRINKLER CERTIFICATION

AON SPRINKLER CERTIFICATION Form 1 Application for Approval of Basic Design Parameters for Automatic Sprinkler System Installations 1. Name of Protected Premises Site Name Address 2. Work to be Carried Out New System Extension or

More information

EXHIBIT A SCOPE OF WORK

EXHIBIT A SCOPE OF WORK EXHIBIT A SCOPE OF WORK 1. (Contractor) shall provide fire alarm system maintenance/repair/testing services as described herein to the California Department of Veterans Affairs (hereinafter CDVA, CalVet,

More information

Copyright 2011 S&S Sprinklers All Rights Reserved. Family Honesty Integrity Spiritual Growth Fairness Teamwork

Copyright 2011 S&S Sprinklers All Rights Reserved. Family Honesty Integrity Spiritual Growth Fairness Teamwork Copyright 2011 S&S Sprinklers All Rights Reserved Family Honesty Integrity Spiritual Growth Fairness Teamwork AUTOMATIC SPRINKLERS Wet, Dry, Pre-Action & Deluge Sprinkler Systems Foam Systems Standpipes

More information

Automatic Fire Sprinkler Submittal Requirements

Automatic Fire Sprinkler Submittal Requirements Automatic Fire Sprinkler Submittal Requirements All commercial and industrial buildings with a total floor area of 5000 sq. ft. shall have an approved automatic sprinkler system installed. The Windsor-Severance

More information

General Fire Code Requirements Within Commercial Tenant Spaces

General Fire Code Requirements Within Commercial Tenant Spaces FIRE DEPARTMENT in cooperation with Scope: General Fire Code Requirements Within Commercial Tenant Spaces This handout is designed to assist owners, architects, contractors and others in understanding

More information

NFPA 13 2002 FAQs. 3. Can plastic pipe be used on a sprinkler system complying with NFPA 13?

NFPA 13 2002 FAQs. 3. Can plastic pipe be used on a sprinkler system complying with NFPA 13? NFPA 13 2002 FAQs Responses to FAQs are prepared by NFPA technical staff to assist users in reading and understanding NFPA codes and standards. The responses, however, are not Formal Interpretations issued

More information

SPRINKLER RULES & STANDARDS IN EUROPE CEA 4001 & EN 12845

SPRINKLER RULES & STANDARDS IN EUROPE CEA 4001 & EN 12845 SPRINKLER RULES & STANDARDS IN EUROPE CEA 4001 & EN 12845 DAEGU: 20 th August 2010 Karim KARZAZI 1 Development of sprinkler rules & standards in Europe. Overview of past, existing and future situation

More information

FIVE YEAR CERTIFICATION REPORT

FIVE YEAR CERTIFICATION REPORT GARDEN GROVE FIRE DEPARTMENT FIRE PREVENTION DIVISION FIVE YEAR CERTIFICATION REPORT Service and maintenance report of automatic fire extinguishing systems, including fire sprinklers, dry, deluge, and

More information

NYC SUB-SYSTEMS INSTALLATION & SERVICE REQUIREMENTS OF THE FDNY

NYC SUB-SYSTEMS INSTALLATION & SERVICE REQUIREMENTS OF THE FDNY NYC SUB-SYSTEMS INSTALLATION & SERVICE REQUIREMENTS OF THE FDNY Presented by: James Goerl Metro Protection Systems, Inc. jgoerl@metroprotectionsystems.com Agenda Introduction & Learning Objectives History

More information

Fighting Fire in Sprinklered Buildings. Student Guide

Fighting Fire in Sprinklered Buildings. Student Guide Fighting Fire in Sprinklered Buildings Student Guide Fighting Fire in Sprinklered Buildings Student Guide Table of Contents Purpose........................................................... 3 Instruction

More information

Important Ontario Fire Code Information for Building Owners in the City of Windsor

Important Ontario Fire Code Information for Building Owners in the City of Windsor Important Ontario Fire Code Information for Building Owners in the City of Windsor This information is intended to be used a reference only. For a complete listing consult the Ontario Fire Code or contact

More information

Inspection, Testing and Preventive Maintenance

Inspection, Testing and Preventive Maintenance Fire Protection Systems and Equipment Introduction HSB Professional Loss Control Two Crossroads Drive Bedminster, NJ 07921 1-800-472-1866 www.hsbplc.com The owners and operators of industrial plants, shopping

More information

Overview of Hotel Fire Safety Requirements

Overview of Hotel Fire Safety Requirements Overview of Hotel Fire Safety Requirements in the Fire Code Susan Clarke, P.Eng. Office of the Fire Marshal - January 10, 2012 1 Agenda Regulation History - Hotels Fire Code Overview (Parts 1 to 8) Defined

More information

FIRE PROTECTION SYSTEMS

FIRE PROTECTION SYSTEMS CHAPTER 9 FIRE PROTECTION SYSTEMS SECTION 901 GENERAL 901.1 Scope. The provisions of this chapter shall specify where fire protection systems are required and shall apply to the design, installation and

More information

Chapter 19 - FIRE SPRINKLER SYSTEM INSPECTIONS

Chapter 19 - FIRE SPRINKLER SYSTEM INSPECTIONS Title 153 - NEBRASKA STATE FIRE MARSHAL Chapter 19 - FIRE SPRINKLER SYSTEM INSPECTIONS Scope. Chapter 19 of Title 153 of the Nebraska Administrative Code is concerned with the certification of contractors

More information

FIRE SPRINKLER SYSTEM SUPERVISORY SERVICE User s Guide (DamarNet RAR Service)

FIRE SPRINKLER SYSTEM SUPERVISORY SERVICE User s Guide (DamarNet RAR Service) FIRE SPRINKLER SYSTEM SUPERVISORY SERVICE User s Guide (DamarNet RAR Service) The information provided in this user guide pertains to fire suppression sprinkler system monitoring service provided over

More information

University Design Standard. Fire Alarm Systems

University Design Standard. Fire Alarm Systems University Design Standard Fire Alarm Systems 1.0 Overview This document provides Virginia Tech s standards for the design and installation of fire alarm systems and equipment in new construction, retrofit

More information

FLAMMABLE AND COMBUSTIBLE LIQUIDS. n OSHA Changes

FLAMMABLE AND COMBUSTIBLE LIQUIDS. n OSHA Changes FLAMMABLE AND COMBUSTIBLE LIQUIDS OSHA Changes Introduction This module covers the two primary hazards associated with flammable and combustible liquids: explosion and fire. In order to prevent these hazards,

More information

CHAPTER 120-3-23 TABLE OF CONTENTS

CHAPTER 120-3-23 TABLE OF CONTENTS THE RULES OF THE SAFETY FIRE COMMISSIONER ARE HEREBY FURTHER AMENDED BY ADDING A NEW CHAPTER 120-3-2 3 E N T I T L E D RULES AND REGULATIONS FOR INSTALLATION; INSPECTION; RECHARGING, REPAIRING, SERVICING

More information

FIRE PROTECTION SYSTEMS

FIRE PROTECTION SYSTEMS CHAPTER 9 FIRE PROTECTION SYSTEMS SECTION 901 GENERAL 901.1 Scope. The provisions of this chapter shall specify where fire protection systems are required and shall apply to the design, installation and

More information

Ontario Fire Code SECTION 5.13 DIP TANKS. Illustrated Commentary. Office of the Ontario Fire Marshal

Ontario Fire Code SECTION 5.13 DIP TANKS. Illustrated Commentary. Office of the Ontario Fire Marshal Ontario Fire Code SECTION 5.13 DIP TANKS Illustrated Commentary Office of the Ontario Fire Marshal Dip Tanks Illustrated Commentary 1 5.13.1. Location 5.13.1.1. Dip tank operations involving flammable

More information

Aerosol Fire Suppression. Your Choice for Special Hazard Fire Protection

Aerosol Fire Suppression. Your Choice for Special Hazard Fire Protection Aerosol Fire Suppression Your Choice for Special Hazard Fire Protection Traditional Special Hazard Fire Protection Centers Around Two Technologies Water deluge and chemical agent fixed systems protect

More information

Inspection and Testing of Water-Based Systems

Inspection and Testing of Water-Based Systems Inspection and Testing of Water-Based Systems Standard Model/Computer-Based Testing Level III Content Outline The candidate for NICET certification at Level III in the Inspection and Testing of Water-Based

More information

Fire Alarm and Protection Impairment Policy and Procedures

Fire Alarm and Protection Impairment Policy and Procedures 1.0 Policy Statement The University of New Haven has developed a Fire Alarm and Protection Impairment Plan in accordance with the National Fire Protection Associations (NFPA) codes. Specific codes referenced

More information

FIRE PROTECTION SYSTEMS

FIRE PROTECTION SYSTEMS CHAPTER 9 FIRE PROTECTION SYSTEMS SECTION 901 GENERAL 901.1 Scope. The provisions of this chapter shall specify where fire protection systems are required and shall apply to the design, installation and

More information

1.0 General. Inspection, Testing, and Maintenance 1 of 8

1.0 General. Inspection, Testing, and Maintenance 1 of 8 1.0 General 1.1 Scope This specifications covers the minimum requirements for the inspection, testing, and maintenance of the existing Notifier fire alarm systems at Bergen Community College (BCC) campus

More information

FIRE PROTECTION SYSTEMS

FIRE PROTECTION SYSTEMS CHAPTER 9 FIRE PROTECTION SYSTEMS SECTION 901 GENERAL 901.1 Scope. The provisions of this chapter shall specify where fire protection systems are required and shall apply to the design, installation and

More information

Inspection, Testing and Maintenance

Inspection, Testing and Maintenance Page 18 ABOUT CODE CORNER CCFS would like to remind you to check with your local Authority Having Jurisdiction (AHJ) for questions and opinions concerning your local Fire and Building Codes. The information

More information

2014 Limited Plan Submittal Checklist

2014 Limited Plan Submittal Checklist City of Aurora Public Works Department WET AND DRY CHEMICAL HOOD SUPPRESSION SYSTEM 2014 Limited Plan Submittal Checklist Building Division 15151 E. Alameda Parkway, Ste 2400 Aurora, CO 80012 303-739-7420

More information

Health Chapter 420-5-22 ALABAMA STATE BOARD OF HEALTH ALABAMA DEPARTMENT OF PUBLIC HEALTH ADMINISTRATIVE CODE

Health Chapter 420-5-22 ALABAMA STATE BOARD OF HEALTH ALABAMA DEPARTMENT OF PUBLIC HEALTH ADMINISTRATIVE CODE Health Chapter 420-5-22 ALABAMA STATE BOARD OF HEALTH ALABAMA DEPARTMENT OF PUBLIC HEALTH ADMINISTRATIVE CODE CHAPTER 420-5-22 SUBMISSION OF PLANS AND SPECIFICATIONS FOR HEALTH CARE FACILITIES TABLE OF

More information

FIRE PROTECTION SYSTEMS

FIRE PROTECTION SYSTEMS CHAPTER 9 FIRE PROTECTION SYSTEMS SECTION 901 GENERAL 901.1 Scope. The provisions of this chapter shall specify where fire protection systems are required and shall apply to the design, installation, inspection,

More information

UNIFIED FACILITIES CRITERIA (UFC) OPERATION AND MAINTENANCE: INSPECTION, TESTING, AND MAINTENANCE OF FIRE PROTECTION SYSTEMS

UNIFIED FACILITIES CRITERIA (UFC) OPERATION AND MAINTENANCE: INSPECTION, TESTING, AND MAINTENANCE OF FIRE PROTECTION SYSTEMS UNIFIED FACILITIES CRITERIA (UFC) OPERATION AND MAINTENANCE: INSPECTION, TESTING, AND MAINTENANCE OF FIRE PROTECTION SYSTEMS APPROVED FOR PUBLIC RELEASE; DISTRIBUTION UNLIMITED UNIFIED FACILITIES CRITERIA

More information

Fire Detection, Protection, and Suppression Systems. Objectives (1 of 5) Objectives (2 of 5) Chapter 36

Fire Detection, Protection, and Suppression Systems. Objectives (1 of 5) Objectives (2 of 5) Chapter 36 Fire Detection, Protection, and Suppression Systems Chapter 36 Objectives (1 of 5) Explain why all firefighters should have a basic understanding of fire protection systems. Describe the basic components

More information

FIRE AND LIFE SAFETY REQUIREMENTS FOR CONVENTIONS, TRADE SHOWS AND EXHIBITS November 2011

FIRE AND LIFE SAFETY REQUIREMENTS FOR CONVENTIONS, TRADE SHOWS AND EXHIBITS November 2011 FIRE AND LIFE SAFETY REQUIREMENTS FOR CONVENTIONS, TRADE SHOWS AND EXHIBITS November 2011 COLORADO SPRINGS FIRE DEPARTMENT Division of the Fire Marshal If you have any questions or comments regarding the

More information

Fire Alarm System Monitoring - CAN/ULC-S561-03

Fire Alarm System Monitoring - CAN/ULC-S561-03 Fire Alarm System Monitoring - CAN/ULC-S561-03 Brian McBain ULC Regulatory Services May 4, 2011 Copyright 1995-2007 Underwriters' Laboratories of Canada. All rights reserved. No portion of this material

More information

FIRE PROTECTION SYSTEMS

FIRE PROTECTION SYSTEMS CHAPTER 9 FIRE PROTECTION SYSTEMS SECTION 901 GENERAL 901.1 Scope. The provisions of this chapter shall specify where fire protection systems are required and shall apply to the design, installation, inspection,

More information

Ethanol Vehicle and Infrastructure Codes and Standards Citations

Ethanol Vehicle and Infrastructure Codes and Standards Citations Ethanol Vehicle and Infrastructure Codes and Standards Citations This document lists codes and standards typically used for U.S. ethanol vehicle and infrastructure projects. To determine which codes and

More information

Environment of Care Fire Safety Management Plan 2014

Environment of Care Fire Safety Management Plan 2014 Environment of Care Fire Safety Management Plan 2014 Updated 4.29.2014 PURPOSE The purpose of the Fire Safety Management Plan is to ensure that all facilities are designed, constructed, maintained, and

More information

Risk Control Bulletin Inspection, Testing & Maintenance (ITM) of Water-Based Fire Protection Systems

Risk Control Bulletin Inspection, Testing & Maintenance (ITM) of Water-Based Fire Protection Systems Risk Control Bulletin Inspection, Testing & Maintenance (ITM) of Water-Based Fire Protection Systems Introduction Fire protection systems are provided in or at a building to safeguard the lives of building

More information

FLORIDA ATLANTIC UNIVERSITY FIRE ALARM SYSTEM INSTALLATION MANUAL

FLORIDA ATLANTIC UNIVERSITY FIRE ALARM SYSTEM INSTALLATION MANUAL FLORIDA ATLANTIC UNIVERSITY FIRE ALARM SYSTEM INSTALLATION MANUAL January, 2003 Environmental Health and Safety Florida Atlantic University 777 Glades Rd. Boca Raton, FL 33431 Phone: 561-297-3129 Fax:

More information

Program No. 1.6.1. Section Heading

Program No. 1.6.1. Section Heading ENVIRONMENTAL HEALTH AND SAFETY EHS PROGRAM MANUAL Program Title 1.0 INTRODUCTION The New York City Fire Department (FDNY) is responsible for approving and/or inspecting fire alarm systems, buildings,

More information

FIRE-FIGHTING DESIGN BRIEF REPORT

FIRE-FIGHTING DESIGN BRIEF REPORT P a g e 1 SECTION 04 (Doc.No.A/DBR 001) FIRE-FIGHTING DESIGN BRIEF REPORT P a g e 2 1.0 SCOPE 2.0 STANDARDS AND CODES 3.0 TYPES OF SYSTEM PROPOSED 4.0 FIRE HYDRANT SYSTEM 5.0 AUTOMATIC SPRINKLER SYSTEM

More information

FIRE SAFETY SELF-INSPECTION FORM FOR CULTURAL INSTITUTIONS. 1. All Floors (inspect from top floor to basement): Yes No

FIRE SAFETY SELF-INSPECTION FORM FOR CULTURAL INSTITUTIONS. 1. All Floors (inspect from top floor to basement): Yes No General Inspection FIRE SAFETY SELF-INSPECTION FORM FOR CULTURAL INSTITUTIONS 1. All Floors (inspect from top floor to basement): Yes are fire exits and directional signs properly illuminated? is the emergency

More information

FIRE PROTECTION SYSTEMS ACCEPTANCE INSPECTION AND TESTING PROCEDURE

FIRE PROTECTION SYSTEMS ACCEPTANCE INSPECTION AND TESTING PROCEDURE ACCEPTANCE INSPECTION AND TESTING PROCEDURE Wet Pipe Sprinkler Systems...2 Dry Pipe Sprinkler Systems...2 Clean Agent Fire Extinguishing System...4 Total Flooding Systems...4 Fire Dampers...5 Smoke Dampers...5

More information

INSTRUCTIONS FOR BUILDINGS WITH FIRE PROTECTION EQUIPMENT

INSTRUCTIONS FOR BUILDINGS WITH FIRE PROTECTION EQUIPMENT INSTRUCTIONS FOR BUILDINGS WITH FIRE PROTECTION EQUIPMENT FIRE EXTINGUISHERS,SPRINKLER SYSTEMS AND FIRE ALARMS Attachment #1 Inspection of Fire Extinguishers Fire Extinguishers must be tested according

More information

2012 Ontario Building Code Changes Affecting Fire Alarm Systems

2012 Ontario Building Code Changes Affecting Fire Alarm Systems 2012 Ontario Building Code Changes Affecting Fire Alarm Systems CFAA Annual Technical Seminar May 31, 2013 Ken Baird VP Systems www.lrifire.com LRI 2010 Developments in Life Safety Introduction Code Development

More information

FIRE AND LIFE SAFETY REQUIREMENTS FOR CONVENTIONS, TRADE SHOWS AND EXHIBITS

FIRE AND LIFE SAFETY REQUIREMENTS FOR CONVENTIONS, TRADE SHOWS AND EXHIBITS FIRE AND LIFE SAFETY REQUIREMENTS FOR CONVENTIONS, TRADE SHOWS AND EXHIBITS November 2011, Updated March 2012 COLORADO SPRINGS FIRE DEPARTMENT Division of the Fire Marshal If you have any questions or

More information

FIRE PROTECTION SYSTEMS

FIRE PROTECTION SYSTEMS CHAPTER 9 FIRE PROTECTION SYSTEMS SECTION 901 GENERAL 901.1 Scope. The provisions of this chapter shall specify where fire protection systems are required and shall apply to the design, installation and

More information

NEW YORK CITY FIRE DEPARTMENT

NEW YORK CITY FIRE DEPARTMENT NEW YORK CITY FIRE DEPARTMENT AIA NYC CODE COMMITTEE OVERVIEW OF NEW YORK CITY FIRE CODE OCTOBER 22, 2009 JULIAN BAZEL Counsel to the Department JAMES HANSEN Director of Code Revision NYC MODEL CODE INITIATIVE

More information

UNIVERSITY OF TOLEDO

UNIVERSITY OF TOLEDO UNIVERSITY OF TOLEDO SUBJECT: INTERIM LIFE SAFETY MEASURES AND INFECTION Procedure No: LS-08-008 CONTROL PROCEDURE STATEMENT Interim life safety and infection control measures will be implemented to protect

More information

EXETER TOWNSHIP DRY OR WET CHEMICAL FIRE SUPPRESSION SYSTEMS

EXETER TOWNSHIP DRY OR WET CHEMICAL FIRE SUPPRESSION SYSTEMS DRY OR WET CHEMICAL FIRE SUPPRESSION SYSTEMS POLICY STATEMENT This policy applies to NEW Dry or Wet chemical fire suppression systems. The Authority Having Jurisdiction will not waive major criteria in

More information

FIRE PROTECTION SYSTEMS

FIRE PROTECTION SYSTEMS CHAPTER 9 FIRE PROTECTION SYSTEMS SECTION BC 901 GENERAL 901.1 Scope. The provisions of this chapter shall specify where fire protection systems are required and shall apply to the design, installation

More information

FIRE PROTECTION SYSTEMS/EQUIPMENT MAINTENANCE & INSPECTION SEMINAR

FIRE PROTECTION SYSTEMS/EQUIPMENT MAINTENANCE & INSPECTION SEMINAR FIRE PROTECTION SYSTEMS/EQUIPMENT MAINTENANCE & INSPECTION SEMINAR August 18-21, 2015 Conducted at the FM Global Emergency Response Consultants Training Center in Rome, Georgia (Formerly known as TSB Loss

More information

FIRE SAFETY PLAN FOR KITCHENER, ONTARIO

FIRE SAFETY PLAN FOR KITCHENER, ONTARIO FIRE SAFETY PLAN FOR KITCHENER, ONTARIO Additional information of fire safety plans may be found at our website at www.kitchener.ca/fire.htm. Before submission, please read and change all sections to address

More information

Flammable Liquids 29 CFR 1910.106

Flammable Liquids 29 CFR 1910.106 Flammable Liquids 29 CFR 1910.106 OSHA s Directorate of Training and Education These materials were developed by OSHA s Directorate of Training and Education and are intended to assist employers, workers,

More information

Rhode Island State Fire Marshal Fire Protection Systems Narrative Reports. What is a Narrative Report?

Rhode Island State Fire Marshal Fire Protection Systems Narrative Reports. What is a Narrative Report? RHODE ISLAND DIVISION OF STATE FIRE MARSHAL 1951 Smith Street, North Providence, RI 02911 Telephone: (401) 383-7717 Fax: (401) 383-8879 John E. Chartier, EFO, CFI State Fire Marshal Rhode Island State

More information

SPRINKLER SYSTEM PLANS AND CALCULATIONS CHECK LIST

SPRINKLER SYSTEM PLANS AND CALCULATIONS CHECK LIST SPRINKLER SYSTEM PLANS AND CALCULATIONS CHECK LIST 1. Working plans shall be drawn to an indicated scale, on sheets of uniform size, with a plan of each floor, and shall show those items from the following

More information

How To Protect Yourself In Seattle

How To Protect Yourself In Seattle CHAPTER 9 FIRE PROTECTION SYSTEMS SECTION 901 GENERAL 901.1 Scope. The provisions of this chapter shall specify where fire protection systems are required and shall apply to the design, installation, inspection,

More information

City of Columbus Department of Building and Zoning Services

City of Columbus Department of Building and Zoning Services City of Columbus Department of Building and Zoning Services Introduction This manual is designed to provide you, the contractor, owner or design professional with a step-by-step guide to our process, beginning

More information

FIRE SAFETY SELF-INSPECTION FORM FOR CULTURAL INSTITUTIONS

FIRE SAFETY SELF-INSPECTION FORM FOR CULTURAL INSTITUTIONS FIRE SAFETY SELF-INSPECTION FORM FOR CULTURAL INSTITUTIONS The attached self-inspection form is intended for staff use at regular, frequent intervals. It should not take the place of two other vital measures

More information

FIRE PROTECTION SYSTEMS

FIRE PROTECTION SYSTEMS CHAPTER 9 FIRE PROTECTION SYSTEMS SECTION 901 GENERAL 901.1 Scope. The provisions of this chapter shall apply to the inspection, operation, testing and maintenance of all fire protection systems. 901.2.

More information

Division 21. Fire Suppression

Division 21. Fire Suppression 21 00 00. Fire Suppression For campus projects that require a fire suppression system shut down in a campus facility, a Shut Down Procedure of Fire Safety System Sheet must be completed and filed seven

More information

TYPICAL FIRE SAFETY INSPECTION VIOLATIONS

TYPICAL FIRE SAFETY INSPECTION VIOLATIONS TYPICAL FIRE SAFETY INSPECTION VIOLATIONS The following is a list of typical violations often found by inspectors and a generic solution. You can use this list to improve the safety of your facility, to

More information

IFE Level 4 Certificate in Fire Science and Fire Safety (HL)

IFE Level 4 Certificate in Fire Science and Fire Safety (HL) IFE Level 4 Certificate in Fire Science and Fire Safety (HL) Unit 2: Fire Safety Unit Reference Number: D/505/5932 Introduction This unit focuses on the prevention and detection of fire in premises and

More information

POSITION STATEMENT THE ENGINEER AND THE ENGINEERING TECHNICIAN DESIGNING FIRE PROTECTION SYSTEMS. July 28, 2008

POSITION STATEMENT THE ENGINEER AND THE ENGINEERING TECHNICIAN DESIGNING FIRE PROTECTION SYSTEMS. July 28, 2008 SOCIETY OF FIRE PROTECTION ENGINEERS (SFPE) NATIONAL SOCIETY OF PROFESSIONAL ENGINEERS (NSPE) NATIONAL INSTITUTE FOR CERTIFICATION IN ENGINEERING TECHNOLOGIES (NICET) POSITION STATEMENT THE ENGINEER AND

More information

RESIDENTIAL COURSE OF CONSTRUCTION QUESTIONNAIRE

RESIDENTIAL COURSE OF CONSTRUCTION QUESTIONNAIRE RESIDENTIAL COURSE OF CONSTRUCTION QUESTIONNAIRE Residential Course of Construction policies, also known as Builder s Risk, are designed to cover the property owner for potential loss while the property

More information

Maintaining Fire Protection Systems

Maintaining Fire Protection Systems Maintaining Fire Protection Systems Fire continues to be a major threat to your business and your personal safety. Each year several thousand people are injured or killed by fires and billions of dollars

More information

FIRE PREVENTION & INVESTIGATION DIVISION 125 Idylwyld Drive South Saskatoon, SK S7M 1L4 Phone: (306) 975-2578 Fax: (306) 975-2589.

FIRE PREVENTION & INVESTIGATION DIVISION 125 Idylwyld Drive South Saskatoon, SK S7M 1L4 Phone: (306) 975-2578 Fax: (306) 975-2589. FIRE PREVENTION & INVESTIGATION DIVISION 125 Idylwyld Drive South Saskatoon, SK S7M 1L4 Phone: (306) 975-2578 Fax: (306) 975-2589 Bulletin 17-12 Fire Safety Plan The purpose of this bulletin is to assist

More information

KODAK VERSAMARK, INC.

KODAK VERSAMARK, INC. KODAK VERSAMARK, INC. PREPARED BY : Gary Rowland 6/6/06 Kodak Versamark, Inc. 3000 Research Blvd. Dayton, Ohio 45420 APPROVED BY : Fire Suppression System Inspection, Testing and Maintenance SHEET 1 OF

More information

OVERVIEW SCOPE DEFINITIONS

OVERVIEW SCOPE DEFINITIONS Procedure No 400.10 Subject: Fire Protection Impairment Program Reference: NFPA (see bottom of page 5) Effective Date: March 2008 Distribution All Employees Review Date: April 2008 Purpose: To establish

More information

City of Bettendorf Fire Alarm System Requirements

City of Bettendorf Fire Alarm System Requirements City of Bettendorf Fire Alarm System Requirements Section 907 of the 2009 Edition of the International Fire Code (IFC) and Section 10-7-3 of the Municipal Code provide fire alarm requirements. IFC Section

More information

General Safety & Health Standards Published by the Division of Building Safety In Cooperation with the Idaho Industrial Commission

General Safety & Health Standards Published by the Division of Building Safety In Cooperation with the Idaho Industrial Commission General Safety & Health Standards Published by the Division of Building Safety In Cooperation with the Idaho Industrial Commission Local Fire Alarm 064. FIRE ALARM SYSTEMS 01. Scope 02. Definitions 03.

More information

TORONTO MUNICIPAL CODE CHAPTER 470, FIRE SAFETY BOXES. Chapter 470 FIRE SAFETY BOXES

TORONTO MUNICIPAL CODE CHAPTER 470, FIRE SAFETY BOXES. Chapter 470 FIRE SAFETY BOXES Chapter 470 FIRE SAFETY BOXES 470-1. Interpretation. 470-2. Administration. 470-3. Fire safety box and lock box. 470-4. One fire safety box and one lock box. 470-5. Location. 470-6. Contents. 470-7. Service

More information

Amerex CPS FM-200 Waterless Pre-engineered Fire Suppression System

Amerex CPS FM-200 Waterless Pre-engineered Fire Suppression System Amerex CPS FM-200 Waterless Pre-engineered Fire Suppression System A Simple Solution An Affordable Approach An Industry Innovation I N T R O D U C T I O N A SIMPLE SOLUTION. AN AFFORDABLE How many days

More information

FIRE DETECTION AND ALARM

FIRE DETECTION AND ALARM Scope Provide a fire alarm system, or expand the existing system, as required by Code, the requirements in the Special Instructions to Designers (SID) of the Design Guidelines, and/or as noted in the Program

More information

Design Options (Tradeoffs) Allowed by the 2012 Building Codes for Properties with Sprinkler Systems. April 2013

Design Options (Tradeoffs) Allowed by the 2012 Building Codes for Properties with Sprinkler Systems. April 2013 Design Options (Tradeoffs) Allowed by the 2012 Building Codes for Properties with Sprinkler Systems April 2013 The National Multi Housing Council and the National Apartment Association (NMHC/NAA) have

More information

STATE OF WISCONSIN Department of Safety and Professional Services

STATE OF WISCONSIN Department of Safety and Professional Services STATE OF WISCONSIN Department of Safety and Professional Services IN THE MATTER OF RULE-MAKING : ORDER OF THE PROCEEDINGS BEFORE THE : DEPARTMENT OF SAFETY AND DEPARTMENT OF SAFETY AND : PROFESSIONAL SERVICES,

More information

Department & Fee or Service Unit Charge. Incident Reports 1 st Page 25.00 Additional Page 0.10

Department & Fee or Service Unit Charge. Incident Reports 1 st Page 25.00 Additional Page 0.10 SECTION 5 - FIRE DEPARTMENT Incident Reports 1 st Page 25.00 Additional Page 0.10 Arson Report w/ Digital Photos Each 52.00 First Aid Training Each 36.40 CPR Training Each 36.40 CPR/First Aid Combined

More information

DEPARTMENT OF LICENSING AND REGULATORY AFFAIRS DIRECTOR'S OFFICE GENERAL INDUSTRY SAFETY STANDARDS

DEPARTMENT OF LICENSING AND REGULATORY AFFAIRS DIRECTOR'S OFFICE GENERAL INDUSTRY SAFETY STANDARDS MIOSHA-STD-1110 (10/15) 10 Pages For further information Ph: 517-284-7740 www.michigan.gov/mioshastandards DEPARTMENT OF LICENSING AND REGULATORY AFFAIRS DIRECTOR'S OFFICE GENERAL INDUSTRY SAFETY STANDARDS

More information

CHAPTER 9 FIRE PROTECTION SYSTEMS

CHAPTER 9 FIRE PROTECTION SYSTEMS CHAPTER 9 FIRE PROTECTION SYSTEMS SECTION 901 GENERAL 901.1 Scope. Provisions of this chapter shall govern the application, design, installation, testing and maintenance of automatic sprinklers, standpipes

More information

We hope these Frequently Asked Questions will be of use both to municipal officials and fire inspectors.

We hope these Frequently Asked Questions will be of use both to municipal officials and fire inspectors. September 14, 2012 Dear AMM Member: Please see the attached Fire Code Frequently Asked Questions. This document was compiled by the Office of the Fire Commissioner at the AMM s request to help clarify

More information