1 .61 FireLock Storage Design Guide This Firelock Storage Design Guide (the "Guide") illustrates the performance characteristics of the full offering of Victaulic Storage s based upon selected design criteria such as ceiling height, class of commodity in storage, type of rack design, etc. This Guide should be used for general reference only. Consult the individual Submittal Publication for each individual sprinkler and consult Victaulic with any questions. Submittal Publications can be downloaded from the Victaulic website at. REGULATORY APPROVALS AND LISTINGS FireLock Storage V4601 FM Approved, culus Listed See Submittal Publication FireLock Storage FM Approved See Submittal Publication FireLock V4402 K14.0 ESFR culus Listed, FM Approved See Submittal Publication FireLock V4404 K16.8 ESFR culus Listed, FM Approved See Submittal Publication FireLock V3407 ELO Response UL, ULC Listed, FM Approved See Submittal Publication 40. FireLock V3408 ELO Response UL, ULC Listed, FM Approved See Submittal Publication 40. TABLE OF CONTENTS Page Design Considerations FM and NFPA 13 2 System Type Wet s for Solid Piled, Bin-Box Rack 3 Wet s for Open Frame Rack Shelving 8 Wet s for Solid Piled, Bin-Box Rack 13 Wet s for Open Frame Rack Shelving 16 Dry/Preaction s for Solid Piled, Bin-Box Rack 19 Dry/Preaction s for Open Frame Rack Shelving 22 Dry System Valve Trip Time Reference FireLock NXT Series 768 Dry Valve or Series 769P Preaction Valve with Accelerator and Four Open s ( ) 24 FireLock NXT Series 768 Dry Valve or Series 769P Preaction Valve with Accelerator and Four Open s ( s) 24 FireLock NXT Series 768 Dry Valve or Series 769P Preaction Valve with Accelerator and One Open (K8.0 Intermediate s) 24 FireLock NXT Series 768 Dry Valve or Series 769P Preaction Valve with Accelerator and One Open (K5.6 Intermediate s) 24 VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. 11 VICTAULIC COMPANY. ALL RIGHTS RESERVED _1

2 Design Considerations FM and NFPA 13 The sequence to design a storage sprinkler system is as follows: Factory Mutual (FM) For Victaulic FM Approved sprinklers Determine commodity (FM Data Sheet 8-1) Determine type of sprinkler system: wet, dry or preaction. (DS 8-9 section 2.3.2) Determine if there are any special applications for the storage area. For example: Freezer storage, or in-rack sprinklers (DS 8-9 section 2.3.6). If storage is refrigerated, see DS Follow requirements for storage area construction, like draft curtains, heat/smoke venting and panel material for refrigerated systems (DS 2-0 section and DS 1-57 for panel material). Determine maximum ceiling height of storage area. Determine how commodity is stored. (Solid-piled, palletized or open frame rack) Assess any special considerations for container style. Open top combustible containers require special consideration (DS 8-9, Section 2.2.5). Follow general guidelines for installation (DS 8-9, section and FM Bulletin 01-11). Follow requirements for ceiling-level sprinklers (DS 8-9, section and FM Bulletin 01-11). Follow requirements for flue spaces (DS 8-9, section ). Apply all data gathered to tables 7-11 of DS 8-9, section and FM Bulletin Add hose stream value (DS 8-9, section 2.3.5). Use the FireLock NXT Trip Time Data provided in this document to assist with water delivery calculations if required. NFPA 13 For Victaulic UL Listed sprinklers Determine commodity class from NFPA Chapter 5. Determine type of sprinkler system (wet/dry/preaction). Follow the parameters of wet, dry or preaction systems for the storage area. Also, note any special considerations for the protection area. For example: Freezer storage, or in-rack sprinklers. Follow Chapter 7 Follow requirements for storage area construction, like draft curtains, heat/smoke venting and panel material for refrigerated systems (Chapter ). Determine maximum ceiling height of storage area. Determine maximum storage height. Determine how commodity is stored (solid-piled, palletized or open frame rack). Assess any special considerations for container style. Open top combustible containers require special consideration and in-rack sprinklers. No exceptions. Use data for CMSA sprinklers protecting class I-IV commodities (Table ). This table will outline wet/dry capabilities and hose stream allowances. Use the FireLock NXT Trip Time Data provided in this document to assist with water delivery calculations if required. Follow general guidelines for installation. VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. VICTAULIC COMPANY. ALL RIGHTS RESERVED _2

3 FireLock Storage Design Guide Wet s for Solid Piled, Bin-Box Rack Commodity Class: I III V3407 V3408 V4402 K14.0 V4404 K16.8 Minimum Flow (gpm) Number of s Hose (gpm) Minimum Flow (gpm) Pressure (psi) Number of s Hose (gpm) Minimum Flow (gpm) Pressure (psi) Number of s Hose (gpm) Minimum Flow (gpm) Pressure (psi) Number of s Hose (gpm) Minimum Flow (gpm) Pressure (psi) Number of s Hose (gpm) Minimum Flow (gpm) Pressure (psi) Number of s Hose (gpm) 0 0 = Design data provided for ceiling heights ft. or less can also be applied to VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. 11 VICTAULIC COMPANY. ALL RIGHTS RESERVED _3

4 FireLock Storage Design Guide Wet s for Solid Piled, Bin-Box Rack Commodity Class: IV and Cartoned Unexpanded Plastics V3407 V3408 V4402 K14.0 V4404 K16.8 Minimum Flow (gpm) Number of s Hose (gpm) Minimum Flow (gpm) Pressure (psi) Number of s Hose (gpm) Minimum Flow (gpm) Number of s Hose (gpm) Minimum Flow (gpm) Number of s Hose (gpm) Minimum Flow (gpm) Pressure (psi) Number of s Hose (gpm) Minimum Flow (gpm) Pressure (psi) Number of s Hose (gpm) Minimum Flow (gpm) Pressure (psi) Number of s Hose (gpm) 0 0 = Design data provided for ceiling heights ft. or less can also be applied to VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. 11 VICTAULIC COMPANY. ALL RIGHTS RESERVED _4

5 FireLock Storage Design Guide Wet s for Solid Piled, Bin-Box Rack Commodity Class: Cartoned Expanded Plastic V3407 V3408 V4402 K14.0 V4404 K16.8 Minimum Flow (gpm) Number of s Minimum Flow (gpm) Number of s Minimum Flow (gpm) Pressure (psi) Number of s Minimum Flow (gpm) Number of s Minimum Flow (gpm) Number of s = Design data provided for ceiling heights ft. or less can also be applied to VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. 11 VICTAULIC COMPANY. ALL RIGHTS RESERVED _5

6 FireLock Storage Design Guide Wet s for Solid Piled, Bin-Box Rack Commodity Class: Uncartoned Unexpanded Plastic V3407 V3408 V4402 K14.0 V4404 K16.8 Minimum Flow (gpm) Number of s Minimum Flow (gpm) Pressure (psi) Number of s Minimum Flow (gpm) Pressure (psi) Number of s Minimum Flow (gpm) Number of s Minimum Flow (gpm) Number of s Minimum Flow (gpm) Pressure (psi) Number of s Hose (gpm) 0 0 Minimum Flow (gpm) Pressure (psi) Number of s Hose (gpm) 0 0 = Design data provided for ceiling heights ft. or less can also be applied to VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. 11 VICTAULIC COMPANY. ALL RIGHTS RESERVED _6

7 FireLock Storage Design Guide Wet s for Solid Piled, Bin-Box Rack Commodity Class: Uncartoned Expanded Plastic V3407 V3408 V4402 K14.0 V4404 K16.8 Minimum Flow (gpm) Number of s Minimum Flow (gpm) Pressure (psi) Number of s Minimum Flow (gpm) Number of s Minimum Flow (gpm) Number of s Minimum Flow (gpm) Pressure (psi) 0 70 Number of s Hose (gpm) 0 0 = Design data provided for ceiling heights ft. or less can also be applied to VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. 11 VICTAULIC COMPANY. ALL RIGHTS RESERVED _7

8 FireLock Storage Design Guide Wet s for Open Frame Rack Shelving (no solid shelves) Commodity Class: I III V3407 V3408 V4402 K14.0 V4404 K16.8 Minimum Flow (gpm) Number of s Hose (gpm) Minimum Flow (gpm) Pressure (psi) Number of s Hose (gpm) Minimum Flow (gpm) Number of s Hose (gpm) Minimum Flow (gpm) Pressure (psi) Number of s Hose (gpm) Minimum Flow (gpm) Pressure (psi) Number of s Hose (gpm) = Design data provided for ceiling heights ft. or less can also be applied to VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. 11 VICTAULIC COMPANY. ALL RIGHTS RESERVED _8

9 FireLock Storage Design Guide Wet s for Open Frame Rack Shelving (no solid shelves) Commodity Class: IV and Cartoned Unexpanded Plastics V3407 V3408 V4402 K14.0 V4404 K16.8 Minimum Flow (gpm) Number of s Hose (gpm) Minimum Flow (gpm) Pressure (psi) Number of s Hose (gpm) Minimum Flow (gpm) Number of s Hose (gpm) Minimum Flow (gpm) Pressure (psi) Number of s Hose (gpm) Minimum Flow (gpm) Pressure (psi) Number of s Hose (gpm) Minimum Flow (gpm) Pressure (psi) Number of s Hose (gpm) = Design data provided for ceiling heights ft. or less can also be applied to VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. 11 VICTAULIC COMPANY. ALL RIGHTS RESERVED _9

10 FireLock Storage Design Guide Wet s for Open Frame Rack Shelving (no solid shelves) Commodity Class: Cartoned Expanded Plastic V3407 V3408 V4402 K14.0 V4404 K16.8 Minimum Flow (gpm) Number of s Minimum Flow (gpm) Pressure (psi) Number of s Minimum Flow (gpm) Number of s Minimum Flow (gpm) Pressure (psi) Number of s Hose (gpm) 0 0 = Design data provided for ceiling heights ft. or less can also be applied to VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. 11 VICTAULIC COMPANY. ALL RIGHTS RESERVED _

11 FireLock Storage Design Guide Wet s for Open Frame Rack Shelving (no solid shelves) Commodity Class: Uncartoned Unexpanded Plastic V3407 V3408 V4402 K14.0 V4404 K16.8 Minimum Flow (gpm) Number of s Minimum Flow (gpm) Pressure (psi) Number of s Minimum Flow (gpm) Number of s Minimum Flow (gpm) Number of s Minimum Flow (gpm) Number of s Minimum Flow (gpm) Pressure (psi) Number of s Hose (gpm) Minimum Flow (gpm) Pressure (psi) Number of s Hose (gpm) 0 0 Minimum Flow (gpm) Pressure (psi) Number of s Hose (gpm) 0 0 = Design data provided for ceiling heights ft. or less can also be applied to VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. 11 VICTAULIC COMPANY. ALL RIGHTS RESERVED _11

12 FireLock Storage Design Guide Wet s for Open Frame Rack Shelving (no solid shelves) Commodity Class: Uncartoned Expanded Plastic V3407 V3408 V4402 K14.0 V4404 K16.8 Minimum Flow (gpm) Number of s Minimum Flow (gpm) Pressure (psi) Number of s Minimum Flow (gpm) Pressure (psi) Number of s Minimum Flow (gpm) Number of s Minimum Flow (gpm) Number of s Minimum Flow (gpm) Pressure (psi) Number of s Hose (gpm) 0 0 Minimum Flow (gpm) Pressure (psi) Number of s Hose (gpm) 0 0 Minimum Flow (gpm) Pressure (psi) 0 70 Number of s Hose (gpm) 0 0 = Design data provided for ceiling heights ft. or less can also be applied to VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. 11 VICTAULIC COMPANY. ALL RIGHTS RESERVED _12

13 FireLock Storage Design Guide Wet s for Open Frame Rack Shelving (no solid shelves) Commodity Class: Uncartoned Expanded Plastic V3407 V3408 V4402 K14.0 V4404 K16.8 Minimum Flow (gpm) Pressure (psi) Number of s Hose (gpm) Minimum Flow (gpm) Pressure (psi) Number of s Hose (gpm) = Design data provided for ceiling heights ft. or less can also be applied to VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. 11 VICTAULIC COMPANY. ALL RIGHTS RESERVED _13

14 FireLock Storage Design Guide Commodity Class: I III Wet s for Solid Piled, Bin-Box Rack Wet s for Solid Piled, Bin-Box Rack Commodity Class: IV and Cartoned Unexpanded Plastics Minimum Flow (gpm) Minimum Flow (gpm) Pressure (psi) 7 Number of s 12 Pressure (psi) 7 Number of s 12 Hose (gpm) Hose (gpm) Minimum Flow (gpm) Minimum Flow (gpm) Pressure (psi) 7 Number of s 12 Pressure (psi) Number of s 12 Hose (gpm) Hose (gpm) Minimum Flow (gpm) Minimum Flow (gpm) Pressure (psi) 7 Number of s 12 Pressure (psi) 50 Number of s 12 Hose (gpm) Hose (gpm) Minimum Flow (gpm) Minimum Flow (gpm) Pressure (psi) 7 Number of s Pressure (psi) 50 Number of s 12 Hose (gpm) Minimum Flow (gpm) Pressure (psi) Number of s 24 Hose (gpm) 500 = Design data provided for ceiling heights ft. or less can also be applied to VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. 11 VICTAULIC COMPANY. ALL RIGHTS RESERVED _14

15 FireLock Storage Design Guide Wet s for Solid Piled, Bin-Box Rack Commodity Class: Cartoned Expanded Plastic Minimum Flow (gpm) Number of s Minimum Flow (gpm) Number of s Minimum Flow (gpm) Pressure (psi) 7 Number of s Minimum Flow (gpm) Number of s Minimum Flow (gpm) Number of s = Design data provided for ceiling heights ft. or less can also be applied to VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. 11 VICTAULIC COMPANY. ALL RIGHTS RESERVED _

16 FireLock Storage Design Guide Wet s for Solid Piled, Bin-Box Rack (no solid shelves) Commodity Class: Uncartoned Unexpanded Plastic Wet s for Solid Piled, Bin-Box Rack (no solid shelves) Commodity Class: Uncartoned Expanded Plastic Minimum Flow (gpm) Minimum Flow (gpm) Number of s Number of s Minimum Flow (gpm) Minimum Flow (gpm) Number of s Pressure (psi) 7 Number of s Minimum Flow (gpm) Minimum Flow (gpm) Pressure (psi) 7 Number of s Number of s Minimum Flow (gpm) Minimum Flow (gpm) Number of s Number of s Minimum Flow (gpm) Number of s = Design data provided for ceiling heights ft. or less can also be applied to VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. 11 VICTAULIC COMPANY. ALL RIGHTS RESERVED _16

17 FireLock Storage Design Guide Commodity Class: I III Wet s for Open Frame Rack Shelving (no solid shelves) Wet s for Open Frame Rack Shelving (no solid shelves) Commodity Class: Class IV/Cartoned Unexpanded Minimum Flow (gpm) Minimum Flow (gpm) Pressure (psi) 7 Number of s 12 Pressure (psi) 7 Number of s 12 Hose (gpm) Hose (gpm) Minimum Flow (gpm) Minimum Flow (gpm) Pressure (psi) Number of s 12 Pressure (psi) Number of s 12 Hose (gpm) Hose (gpm) Minimum Flow (gpm) Minimum Flow (gpm) Pressure (psi) 50 Number of s 12 Pressure (psi) 50 Number of s 12 Hose (gpm) Hose (gpm) Minimum Flow (gpm) 2342 Minimum Flow (gpm) Pressure (psi) Number of s 24 Pressure (psi) Number of s 12 Hose (gpm) 500 Hose (gpm) 0 Minimum Flow (gpm) Pressure (psi) Number of s 24 Hose (gpm) 500 = Design data provided for ceiling heights ft. or less can also be applied to VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. 11 VICTAULIC COMPANY. ALL RIGHTS RESERVED _17

18 FireLock Storage Design Guide Wet s for Open Frame Rack Shelving (no solid shelves) Commodity Class: Cartoned Expanded Plastic Minimum Flow (gpm) Number of s Minimum Flow (gpm) Pressure (psi) 7 Number of s Minimum Flow (gpm) Pressure (psi) 7 50 Number of s = Design data provided for ceiling heights ft. or less can also be applied to VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. 11 VICTAULIC COMPANY. ALL RIGHTS RESERVED _18

19 FireLock Storage Design Guide Wet s for Open Frame Rack Shelving (no solid shelves) Commodity Class: Uncartoned Unexpanded Plastic Wet s for Open Frame Rack Shelving (no solid shelves) Commodity Class: Uncartoned Expanded Plastic Minimum Flow (gpm) Minimum Flow (gpm) Number of s 5 Number of s Minimum Flow (gpm) Minimum Flow (gpm) Pressure (psi) 7 16 Number of s 8 Pressure (psi) 7 16 Number of s Minimum Flow (gpm) Minimum Flow (gpm) Pressure (psi) 7 Number of s Pressure (psi) 7 Number of s Minimum Flow (gpm) Minimum Flow (gpm) Number of s 12 Number of s Minimum Flow (gpm) Minimum Flow (gpm) Number of s Pressure (psi) 50 Number of s = Design data provided for ceiling heights ft. or less can also be applied to VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. 11 VICTAULIC COMPANY. ALL RIGHTS RESERVED _19

20 FireLock Storage Design Guide Dry/Preaction s for Solid Piled, Bin-Box Rack Commodity Class: I III Dry/Preaction s for Solid Piled, Bin-Box Rack Commodity Class: IV and Cartoned Unexpanded Plastics Minimum Flow (gpm) Minimum Flow (gpm) Number of s Number of s Minimum Flow (gpm) Minimum Flow (gpm) Number of s Pressure (psi) 7 Number of s Minimum Flow (gpm) Minimum Flow (gpm) Number of s Number of s Minimum Flow (gpm) Minimum Flow (gpm) Pressure (psi) 7 Number of s Number of s Minimum Flow (gpm) 2342* 40 Pressure (psi) * Number of s 24* Hose (gpm) 500* Minimum Flow (gpm) 2140** Pressure (psi) 50** Number of s 12** Hose (gpm) 500** = Design data provided for ceiling heights ft. or less can also be applied to * second water delivery time required. 1 Minute Hose Stream Allowance. ** second water delivery time required. 90 Minute Hose Stream Allowance. Note: To design dry systems, water delivery times are required. See pages for Valve Trip Time Reference Data for the Victaulic FireLock NXT Series 768 Dry Valve and Series 769 Preaction Valve. VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. 11 VICTAULIC COMPANY. ALL RIGHTS RESERVED _

21 FireLock Storage Design Guide Dry/Preaction s for Solid Piled, Bin-Box Rack Commodity Class: Cartoned Expanded Plastic Dry/Preaction s for Solid Piled, Bin-Box Rack Commodity Class: Uncartoned Unexpanded Plastic Minimum Flow (gpm) Minimum Flow (gpm) Number of s Number of s Minimum Flow (gpm) Minimum Flow (gpm) Number of s Number of s Minimum Flow (gpm) Minimum Flow (gpm) Pressure (psi) 7 Number of s Pressure (psi) 7 Number of s Minimum Flow (gpm) Minimum Flow (gpm) Number of s Number of s Minimum Flow (gpm) Minimum Flow (gpm) Number of s Number of s = Design data provided for ceiling heights ft. or less can also be applied to Note: To design dry systems, water delivery times are required. See pages for Valve Trip Time Reference Data for the Victaulic FireLock NXT Series 768 Dry Valve and Series 769 Preaction Valve. VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. 11 VICTAULIC COMPANY. ALL RIGHTS RESERVED _21

22 FireLock Storage Design Guide Dry/Preaction s for Solid Piled, Bin-Box Rack Commodity Class: Uncartoned Expanded Plastic Minimum Flow (gpm) Number of s Minimum Flow (gpm) Pressure (psi) 7 Number of s Minimum Flow (gpm) Number of s Minimum Flow (gpm) Number of s = Design data provided for ceiling heights ft. or less can also be applied to Note: To design dry systems, water delivery times are required. See pages for Valve Trip Time Reference Data for the Victaulic FireLock NXT Series 768 Dry Valve and Series 769 Preaction Valve. VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. 11 VICTAULIC COMPANY. ALL RIGHTS RESERVED _22

23 FireLock Storage Design Guide Commodity Class: I III Dry/Preaction s for Open Frame Rack Shelving (no solid shelves) Dry/Preaction s for Open Frame Rack Shelving (no solid shelves) Commodity Class: IV and Cartoned Unexpanded Plastics Minimum Flow (gpm) Minimum Flow (gpm) Number of s Number of s Minimum Flow (gpm) Minimum Flow (gpm) Pressure (psi) 7 Number of s Pressure (psi) 7 Number of s Minimum Flow (gpm) Minimum Flow (gpm) Number of s Number of s Minimum Flow (gpm) 2342* Minimum Flow (gpm) Pressure (psi) * Number of s 24* Pressure (psi) Number of s 35 Hose (gpm) 500* Hose (gpm) 500 Minimum Flow (gpm) 2342* 40 Pressure (psi) * Number of s 24* Hose (gpm) 500* Minimum Flow (gpm) 2140** Pressure (psi) 50** Number of s 12** Hose (gpm) 500** = Design data provided for ceiling heights ft. or less can also be applied to * second water delivery time required. 1 Minute Hose Stream Allowance. ** second water delivery time required. 90 Minute Hose Stream Allowance. Note: To design dry systems, water delivery times are required. See pages for Valve Trip Time Reference Data for the Victaulic FireLock NXT Series 768 Dry Valve and Series 769 Preaction Valve. VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. 11 VICTAULIC COMPANY. ALL RIGHTS RESERVED _23

24 FireLock Storage Design Guide Dry/Preaction s for Open Frame Rack Shelving (no solid shelves) Commodity Class: Cartoned Expanded Plastic Dry/Preaction s for Open Frame Rack Shelving (no solid shelves) Commodity Class: Uncartoned Unexpanded Plastic Minimum Flow (gpm) Minimum Flow (gpm) Number of s 5 Number of s Minimum Flow (gpm) Minimum Flow (gpm) Pressure (psi) 7 Number of s 8 Pressure (psi) 7 16 Number of s Minimum Flow (gpm) Minimum Flow (gpm) Number of s Pressure (psi) 7 50 Number of s Minimum Flow (gpm) Number of s Minimum Flow (gpm) Number of s = Design data provided for ceiling heights ft. or less can also be applied to Note: To design dry systems, water delivery times are required. See pages for Valve Trip Time Reference Data for the Victaulic FireLock NXT Series 768 Dry Valve and Series 769 Preaction Valve. VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. 11 VICTAULIC COMPANY. ALL RIGHTS RESERVED _24

25 FireLock Storage Design Guide Dry/Preaction - s for Open Frame Rack Shelving (no solid shelves) Commodity Class: Uncartoned Expanded Plastic Minimum Flow (gpm) Number of s Minimum Flow (gpm) Pressure (psi) 7 16 Number of s Minimum Flow (gpm) Pressure (psi) 7 Number of s Minimum Flow (gpm) Number of s Minimum Flow (gpm) Number of s = Design data provided for ceiling heights ft. or less can also be applied to Note: To design dry systems, water delivery times are required. See pages for Valve Trip Time Reference Data for the Victaulic FireLock NXT Series 768 Dry Valve and Series 769 Preaction Valve. VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. 11 VICTAULIC COMPANY. ALL RIGHTS RESERVED _

26 FireLock Storage Design Guide Ceiling Based Systems Dry System Valve Trip Time Reference: FireLock NXT Series 768 Dry Valve or Series 769P Preaction Valve with Accelerator and Four Open s ( ) Dry System Valve Trip Time Reference: FireLock NXT Series 768 Dry Valve or Series 769P Preaction Valve with Accelerator and Four Open s ( s) System volume (U.S. Gallons) Valve trip time (seconds) Initial Set Pressure (Trip Pressure) 13psi (psi) psi (12psi) 18psi (psi) Valve trip time (seconds) System volume Initial Set Pressure (Trip Pressure) (U.S. Gallons) 13psi (psi) psi (12psi) 18psi (psi) Intermediate Systems Dry System Valve Trip Time Reference: FireLock NXT Series 768 Dry Valve or Series 769P Preaction Valve with Accelerator and One Open (K8.0 Intermediate s) Dry System Valve Trip Time Reference: FireLock NXT Series 768 Dry Valve or Series 769P Preaction Valve with Accelerator and One Open (K5.6 Intermediate s) Valve trip time (seconds) System volume Initial Set Pressure (Trip Pressure) (U.S. Gallons) 13psi (psi) psi (12psi) 18psi (psi) Valve trip time (seconds) System volume Initial Set Pressure (Trip Pressure) (U.S. Gallons) 13psi (psi) psi (12psi) 18psi (psi) Note: To design dry systems, water delivery times are required. See pages for Valve Trip Time Reference Data for the Victaulic FireLock NXT Series 768 Dry Valve and Series 769 Preaction Valve. For complete contact information, visit REV A 09/11 VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. 11 VICTAULIC COMPANY. ALL RIGHTS RESERVED

Stored Palletized, Solid Piled, Bin Boxes, or Shelf Storage (12.2)

Stored Palletized, Solid Piled, Bin Boxes, or Shelf Storage (12.2) Stored Palletized, Solid Piled, Bin Boxes, or Shelf Storage (12.2) Formally part of NFPA 231 12.2.1 General 12.2.2 Protection of Class I - IV Commodities 12.2.3 Protection of Plastic & Rubber Commodities

More information

NFPA 13 2002 FAQs. 3. Can plastic pipe be used on a sprinkler system complying with NFPA 13?

NFPA 13 2002 FAQs. 3. Can plastic pipe be used on a sprinkler system complying with NFPA 13? NFPA 13 2002 FAQs Responses to FAQs are prepared by NFPA technical staff to assist users in reading and understanding NFPA codes and standards. The responses, however, are not Formal Interpretations issued

More information

esfr pendent sprinkler vk510 (k25.2)

esfr pendent sprinkler vk510 (k25.2) January 17, 2014 Sprinkler 124a 1. DESCRIPTION Viking Early Suppression Fast Response (ESFR) Pendent Sprinkler VK510 incorporates the capability to suppress specific high-challenge fires. The addition

More information

Denver Fire Department Idle Pallet Storage Guidelines Per NFPA 13_Chpt 12

Denver Fire Department Idle Pallet Storage Guidelines Per NFPA 13_Chpt 12 Idle wood and plastic pallets introduce a severe fire condition. Stacking idle pallets in piles is the best arrangement of combustibles to promote rapid spread of fire, heat release, and complete combustion.

More information

Automatic Fire Sprinkler Submittal Requirements

Automatic Fire Sprinkler Submittal Requirements Automatic Fire Sprinkler Submittal Requirements All commercial and industrial buildings with a total floor area of 5000 sq. ft. shall have an approved automatic sprinkler system installed. The Windsor-Severance

More information

ESFR DRY PENDENT SPRINKLER VK502 (K14.0) TECHNICAL DATA

ESFR DRY PENDENT SPRINKLER VK502 (K14.0) TECHNICAL DATA December 19, 2013 Sprinkler 122j 1. DESCRIPTION Viking Early Suppression Fast Response (ESFR) Dry Pendent Sprinkler VK502 is a fast response fusible element type sprinkler designed for use in storage areas

More information

Technical Article. Sprinkler Protection for High Bay and Automated Storage in Warehouse-Type Storage Facilities

Technical Article. Sprinkler Protection for High Bay and Automated Storage in Warehouse-Type Storage Facilities Technical Article for High Bay and Automated Storage in Warehouse-Type Storage Facilities Scott Martorano, CFPS Senior Manager Technical Services February, 2010 Worldwide Fire Protection www.vikinggroupinc.com

More information

AON SPRINKLER CERTIFICATION

AON SPRINKLER CERTIFICATION Form 1 Application for Approval of Basic Design Parameters for Automatic Sprinkler System Installations 1. Name of Protected Premises Site Name Address 2. Work to be Carried Out New System Extension or

More information

SPRINKLER RULES & STANDARDS IN EUROPE CEA 4001 & EN 12845

SPRINKLER RULES & STANDARDS IN EUROPE CEA 4001 & EN 12845 SPRINKLER RULES & STANDARDS IN EUROPE CEA 4001 & EN 12845 DAEGU: 20 th August 2010 Karim KARZAZI 1 Development of sprinkler rules & standards in Europe. Overview of past, existing and future situation

More information

Warehouse Checklist. Warehouse Construction

Warehouse Checklist. Warehouse Construction PAGE 1 Warehouse Checklist Recent NFPA statistics estimate that in 1998 approximately 36,000 fires occurred in structures used for storage, accounting for $687mm of damage (over 10% of total fire damage

More information

Flammable and Combustible Liquid

Flammable and Combustible Liquid Flammable and Combustible Liquid Storage Challenges Christopher J. Wieczorek, Ph.D., FM Global David Nugent, The Valspar Corporation Global Research Update: High Challenge Storage Protection 27 June 2012,

More information

SPRINKLER SYSTEM PLANS AND CALCULATIONS CHECK LIST

SPRINKLER SYSTEM PLANS AND CALCULATIONS CHECK LIST SPRINKLER SYSTEM PLANS AND CALCULATIONS CHECK LIST 1. Working plans shall be drawn to an indicated scale, on sheets of uniform size, with a plan of each floor, and shall show those items from the following

More information

Construction Warehouse. Culminating Experience in Fire Protection Engineering FPE 596 Prepared by Ben Johnson

Construction Warehouse. Culminating Experience in Fire Protection Engineering FPE 596 Prepared by Ben Johnson Construction Warehouse Culminating Experience in Fire Protection Engineering FPE 596 Prepared by Ben Johnson Construction Warehouse Waste Treatment and Immobilization Plant (WTP) Project U.S. Department

More information

ESFR "PRE-PRIMED SINGLE INTERLOCKED PREACTION" COLD STORAGE SYSTEM MANUAL

ESFR PRE-PRIMED SINGLE INTERLOCKED PREACTION COLD STORAGE SYSTEM MANUAL ESFR "PRE-PRIMED SINGLE INTERLOCKED PREACTION" COLD STORAGE SYSTEM MANUAL The Viking Corporation 210 N Industrial Park Road Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax:

More information

Extended Coverage Sprinklers

Extended Coverage Sprinklers Extended Coverage Sprinklers Welcome ASPE Wally Barker Sprinkler Systems 101 MATERIALS OF CONSTRUCTION The components that make up a sprinkler head are: Frame or casting Deflector Fusible element or frangible

More information

HIGH-PILED COMBUSTIBLE STORAGE

HIGH-PILED COMBUSTIBLE STORAGE CHAPTER 23 HIGH-PILED COMBUSTIBLE STORAGE SECTION 2301 GENERAL 2301.1 Scope. High-piled combustible storage shall be in accordance with this chapter. In addition to the requirements of this chapter, the

More information

HIGH-PILED COMBUSTIBLE STORAGE

HIGH-PILED COMBUSTIBLE STORAGE CHAPTER 23 HIGH-PILED COMBUSTIBLE STORAGE SECTION FC 2301 GENERAL 2301.1 Scope. This chapter shall govern high-piled combustible storage, and the design, installation, operation and maintenance of any

More information

FACILITY FIRE-SUPPRESSION WATER-SERVICE PIPING 21 11 00

FACILITY FIRE-SUPPRESSION WATER-SERVICE PIPING 21 11 00 211100_flexheadin_01_MS_0409 5/22/09 PTC 56 Lowland Street Holliston, MA 01746 Phone: (800) 829-6975 Phone: (508) 893-9596 Fax: (508) 893-6020 E-mail: sales1@flexhead.com www.flexhead.com This MANU-SPEC

More information

Series ELO-231B 11.2 K-factor Upright and Pendent Sprinklers. Standard Response, Standard Coverage, General Description

Series ELO-231B 11.2 K-factor Upright and Pendent Sprinklers. Standard Response, Standard Coverage, General Description Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500 Series ELO-231B 11.2 K-factor Upright and Pendent Sprinklers Standard Response, Standard Coverage General Description IMPORTANT Always refer

More information

Model KFR56 Series Quick Response Standard Spray

Model KFR56 Series Quick Response Standard Spray Bulletin 036 Model KFR56 Series Quick Response Standard Spray Bulletin 036 Model KFR56 Sprinkler Types Standard Upright Standard Pendent Horizontal Sidewall Model KFR56 Sprinkler Types Pendent F1/F2/FP

More information

Cost Evaluation of Black Steel Pipe and Galvanized Pipe When Using a Nitrogen Generator

Cost Evaluation of Black Steel Pipe and Galvanized Pipe When Using a Nitrogen Generator Cost Evaluation of Black Steel Pipe and Galvanized Pipe When Using a Nitrogen Generator Andy L. Kaempfer Business Development Manager Potter Electric Signal Company, LLC 1609 Park 370 Place St. Louis,

More information

Fire Protection System Requirements Bulletin

Fire Protection System Requirements Bulletin Fire Protection System Requirements Bulletin FIRE PROTECTION DESIGN REQUIREMENTS FOR TENANTS (Revised 5-20-16) Simon requires all tenants to use a property specific pre-approved fire sprinkler contractor

More information

Tyco Fire & Building Products is a leading manufacturer and distributor of water-based fire suppression systems and components, offering one of the

Tyco Fire & Building Products is a leading manufacturer and distributor of water-based fire suppression systems and components, offering one of the Tyco Fire & Building Products is a leading manufacturer and distributor of water-based fire suppression systems and components, offering one of the broadest lines of fire protection system equipment worldwide.

More information

Model F156 Sprinkler Types. Model F156 Recessed Sprinkler Types. Model F142, F1XLH & F128 Sprinkler Types

Model F156 Sprinkler Types. Model F156 Recessed Sprinkler Types. Model F142, F1XLH & F128 Sprinkler Types Bulletin 013 Rev. M Models F1 Series Standard Response s Bulletin 013 Rev. M Model F156 Types Standard Upright Standard Pendent Conventional Vertical Sidewall Model F156 Recessed Types Pendent/F1/F2/FP

More information

F.Y.I. Specifying Fire Protection Systems Using Division 13

F.Y.I. Specifying Fire Protection Systems Using Division 13 F.Y.I. Specifying Fire Protection Systems Using Division 13 Automatic fire sprinkler systems and fire alarm and detection systems are increasingly installed in modern buildings. Even where building codes

More information

Amerex CPS FM-200 Waterless Pre-engineered Fire Suppression System

Amerex CPS FM-200 Waterless Pre-engineered Fire Suppression System Amerex CPS FM-200 Waterless Pre-engineered Fire Suppression System A Simple Solution An Affordable Approach An Industry Innovation I N T R O D U C T I O N A SIMPLE SOLUTION. AN AFFORDABLE How many days

More information

WAREHOUSE PROPERTY PROTECTION

WAREHOUSE PROPERTY PROTECTION STRATEGIC OUTCOMES PRACTICE TECHNICAL ADVISORY BULLETIN October 2011 WAREHOUSE PROPERTY PROTECTION Among the most challenging occupancies from a property loss control viewpoint are warehouses, distribution

More information

RESIDENTIAL SPRINKLER INSTALLATION GUIDE

RESIDENTIAL SPRINKLER INSTALLATION GUIDE RESIDENTIAL SPRINKLER INSTALLATION GUIDE 4077 AIR PARK DRIVE STANDISH, MICHIGAN 48658 PHONE 989-846-4583 800-248-0278 FAX 989-846-9231 www.globesprinkler.com A-15 GLOBE RESIDENTIAL SPRINKLER GUIDE DESCR.,

More information

Fire Protection Requirements of Empty Intermediate Bulk Containers (IBCs)

Fire Protection Requirements of Empty Intermediate Bulk Containers (IBCs) Research TECHNICAL REPORT Fire Protection Requirements of Empty Intermediate Bulk Containers (s) Fire Protection Requirements of Empty Intermediate Bulk Containers (s) by Seth E. Sienkiewicz FM Global

More information

Model WS Specific Application Window Sprinklers Horizontal and Pendent Vertical Sidewall 5.6 K-factor General Description

Model WS Specific Application Window Sprinklers Horizontal and Pendent Vertical Sidewall 5.6 K-factor General Description Worldwide Contacts www.tyco-fire.com Model WS Specific Application Window Sprinklers Horizontal and Pendent Vertical Sidewall 5.6 K-factor General Description The TYCO Model WS Specific Application Window

More information

FIVE YEAR CERTIFICATION REPORT

FIVE YEAR CERTIFICATION REPORT GARDEN GROVE FIRE DEPARTMENT FIRE PREVENTION DIVISION FIVE YEAR CERTIFICATION REPORT Service and maintenance report of automatic fire extinguishing systems, including fire sprinklers, dry, deluge, and

More information

FIRE SPRINKLER SYSTEM DESIGN, ENGINEERING EXEMPTION POLICY FOR (Effective April 1, 2006)

FIRE SPRINKLER SYSTEM DESIGN, ENGINEERING EXEMPTION POLICY FOR (Effective April 1, 2006) State of Tennessee Department of Commerce and Insurance Board of Architectural and Engineering Examiners 500 James Robertson Parkway Nashville, TN 37243 1142 800 256 5758 615 741 3221 (Nashville Area)

More information

Features. Model EX Low Pressure Dry Pipe Valve System 2 (DN50), 2½ (DN65), 3 (DN80), 76 mm, 4 (DN100 ), 6 (DN150), 165 mm & 8 (DN200)

Features. Model EX Low Pressure Dry Pipe Valve System 2 (DN50), 2½ (DN65), 3 (DN80), 76 mm, 4 (DN100 ), 6 (DN150), 165 mm & 8 (DN200) Features 1. Differential latching clapper-type, lightweight, dependable construction. 2. Low Air Pressurized System, psi -to- 2 psi (0.6 bar -to- 1.9 bar) Max 3. Reset externally. Cover removal is not

More information

FLAMMABLE AND COMBUSTIBLE LIQUIDS

FLAMMABLE AND COMBUSTIBLE LIQUIDS GAP.8.1.0 A Publication of Global Asset Protection Services LLC FLAMMABLE AND COMBUSTIBLE LIQUIDS INTRODUCTION National Fire Protection Association (NFPA) documents describe a level of fire protection

More information

Firefighter Review. Instructor Guide

Firefighter Review. Instructor Guide Firefighter Review Instructor Guide Session Reference: 3 Topic: Attack Line Handling Level of Instruction: Time Required: Three Hours Materials: Two Fully Equipped Pumpers Structure for Use in Advancing

More information

Automatic Fire Sprinkler System Checklist

Automatic Fire Sprinkler System Checklist Fire Prevention rd Location: 701 E. 3 Avenue Mail to: P.O. Box 1579 Moses Lake, WA 98837 (509) 765-2204 www.ci.moses-lake.wa.us Automatic Fire Sprinkler System Checklist Please print in Black or Blue ink

More information

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST RESIDENTIAL FIRE SPRINKLERS NFPA 13D

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST RESIDENTIAL FIRE SPRINKLERS NFPA 13D July 1, 2010 SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST RESIDENTIAL FIRE SPRINKLERS NFPA 13D Address: Permit #: Inspector: Date: Status: Inspector: Date: Status: A-Approved;

More information

Design & Construction Standards, Revised January 2013 5.21.30-1

Design & Construction Standards, Revised January 2013 5.21.30-1 PART 1 GENERAL 1.01 Scope of Standard A. This standard provides general requirements of The University of Texas at Austin for fire pumps. This document is not intended to serve as a guide specification.

More information

Risk Guidance Note 03. Management of In-Rack Automatic Sprinklers (IRAS)

Risk Guidance Note 03. Management of In-Rack Automatic Sprinklers (IRAS) Risk Guidance Note 03 Management of In-Rack Automatic Sprinklers (IRAS) Overview In-rack automatic sprinklers (IRAS) are often a fundamental part of the fire protection solution for racked storage areas.

More information

Antifreeze Solutions in Residential Fire Sprinkler Systems

Antifreeze Solutions in Residential Fire Sprinkler Systems Antifreeze Solutions in Residential Fire Sprinkler Systems The 2013 edition of NFPA 13D, as amended by TIA 13 1, discourages the use of antifreeze solutions within residential fire sprinkler systems unless

More information

INTERACTION OF SPRINKLERS WITH SMOKE AND HEAT VENTS

INTERACTION OF SPRINKLERS WITH SMOKE AND HEAT VENTS INTERACTION OF SPRINKLERS WITH SMOKE AND HEAT VENTS Craig L. Beyler and Leonard Y. Cooper Fire Science and Engineering Baltimore, Maryland EXECUTIVE SUMMARY There has been an ongoing controversy about

More information

In accordance with NFPA 30, these containers are not to store Class I flammable liquids.

In accordance with NFPA 30, these containers are not to store Class I flammable liquids. In accordance with NFPA 30, these containers are not to store Class I flammable liquids. Zurich recommends storing these containers in dedicated liquid storage rooms, detached buildings, or in listed dispensing

More information

PRE APPLICATION CONFERENCE - INTRODUCTION

PRE APPLICATION CONFERENCE - INTRODUCTION CITY OF AUBURN Planning & Development Department Auburn City Hall Annex, 2 nd Floor 1 East Main Street Auburn, WA 98001 Tel: 253.931.3090 Fax: 253.804.3114 permitcenter@auburnwa.gov www.auburnwa.gov PRE-APPLICATION

More information

TECHNICAL DATA 2. LISTINGS AND APPROVALS. Spray Nozzle 11. December 20, 2013

TECHNICAL DATA 2. LISTINGS AND APPROVALS. Spray Nozzle 11. December 20, 2013 Spray Nozzle 11 1. DESCRIPTION Viking Model C-1 Window Sprinklers are non-automatic, open, outside intended for protection of windows, walls, and roofs against exposure fires. The directional discharge

More information

CONSULTING from DESIGN to PROJECT MANAGEMENT We Transform your Vision into Productive Force

CONSULTING from DESIGN to PROJECT MANAGEMENT We Transform your Vision into Productive Force 2012 CONSULTING from DESIGN to PROJECT MANAGEMENT We Transform your Vision into Productive Force Consulting : from Design to Project IBLS can provide complete solutions in the Design, Procurement and Project

More information

LHD LINEAR HEAT D ETECTIONN

LHD LINEAR HEAT D ETECTIONN Tri-Metallic Core: Steel provides tensile strength Copper increase conductivity Tin for corrosion resistance LHD LINEAR HEAT D ETECTIONN TECHNICAL DATA Temperature Rating: 155 F (68 C) (typical temperature)

More information

Willis Technical Advisory Bulletin

Willis Technical Advisory Bulletin Willis Technical Advisory Bulletin Warehouse Property Protection February 2007 Among the most challenging occupancies from a property loss control viewpoint are warehouses, distribution centers and large

More information

EFSN Training i Module 1. 90 Minutes

EFSN Training i Module 1. 90 Minutes Introduction to Sprinklers EFSN Training i Module 1 90 Minutes Topics How sprinklers work Performance of sprinkler systems Types of Sprinkler Introduction to sprinkler systems Introduction ti to sprinkler

More information

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST RESIDENTIAL FIRE SPRINKLERS NFPA 13R

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST RESIDENTIAL FIRE SPRINKLERS NFPA 13R July 1, 2010 SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST RESIDENTIAL FIRE SPRINKLERS NFPA 13R Address: Permit #: Inspector: Date: Status: Inspector: Date: Status: A-Approved;

More information

LogisticsCentre IV Distribution Center

LogisticsCentre IV Distribution Center KCI Intermodal BusinessCentre LogisticsCentre IV LogisticsCentre IV Distribution Center Modern Warehouse/Distribution Space Ranging From 108,000± SF to 432,000± SF 10221 NW Transcon Drive 112th Street

More information

SPP Pumps Inc. Atlanta

SPP Pumps Inc. Atlanta SPP Pumps Inc. Atlanta UL Listed, FM Approved Fire Pump Sets Horizontal Split Case Pumps Flows from 200-5000 US GPM Vertical Turbine Flows to 5000 US GPM In-Line Pumps Flows to 750 US GPM End Suction Flows

More information

TAMARAC FIRE RESCUE INSTRUCTIONS FOR FIRE ALARM PRE-SUBMITTAL CHECKLIST

TAMARAC FIRE RESCUE INSTRUCTIONS FOR FIRE ALARM PRE-SUBMITTAL CHECKLIST TAMARAC FIRE RESCUE INSTRUCTIONS FOR FIRE ALARM PRE-SUBMITTAL CHECKLIST In order to provide a comprehensive plan review in a timely manner, and to insure the design and installation of fire alarm systems

More information

Pr o d u c t In f o r m at i o n V008.0

Pr o d u c t In f o r m at i o n V008.0 AGF Manufacturing Inc. Pr o d u c t In f o r m at i o n V008.0 Reliability, Versatility, Code Compatibility BK002 COLLECTa ndrain The COLLECTa ndrain family of products are anti-trip drum drips that prevent

More information

4077 AIRPARK DRIVE STANDISH, MICHIGAN 48658 PHONE 989-846-4583 800-248-0278 FAX

4077 AIRPARK DRIVE STANDISH, MICHIGAN 48658 PHONE 989-846-4583 800-248-0278 FAX Butterfly Valves 4077 AIRPARK DRIVE STANDISH, MICHIGAN 48658 PHONE 989-846-4583 800-248-0278 FAX 989-846-9231 www.globesprinkler.com MAY 2013 L-1 BULLETIN BUTTERFLY REV. #5 GLOBE BUTTERFLY VALVE INSTALLATION

More information

Viking Residential Sprinkler Installation Guide

Viking Residential Sprinkler Installation Guide Viking Residential Sprinkler Installation Guide January, 2009 Trusted Above AllT M www.flowbusiness.cl Sprinkler RES1 January 9, 2009 1. DESCRIPTION Viking residential automatic sprinklers are equipped

More information

Fire Pump Plan Review March 2010

Fire Pump Plan Review March 2010 Fire Pump Plan Review March 2010 Date of Review: / / Permit Number: Business/Building Name: Address of Project: Designer Name: Designer s Phone: Contractor: Contractor s Phone: Occupancy Classification:

More information

SARATOGA FIRE DISTRICT EARLY WARNING FIRE ALARM SYSTEM STANDARDS AND REQUIRMENTS CONTENTS

SARATOGA FIRE DISTRICT EARLY WARNING FIRE ALARM SYSTEM STANDARDS AND REQUIRMENTS CONTENTS SARATOGA FIRE DISTRICT EARLY WARNING FIRE ALARM SYSTEM STANDARDS AND REQUIRMENTS CONTENTS I. APPLICATION AND DEFINITIONS 1.01 Authorization for Standards 1.02 Application of Standards 1.03 Definitions

More information

Sprinkler Guards Model C Model D

Sprinkler Guards Model C Model D Bulletin 208 Rev. M Sprinkler Guards Model C Model D Bulletin 208 Rev. M Model C Sprinkler Guards Model C Series sprinkler guards are designed to be assembled onto installed sprinklers. They are constructed

More information

I.CHEM.E. SYMPOSIUM SERIES NO. 97

I.CHEM.E. SYMPOSIUM SERIES NO. 97 FIRE HAZARDS OF FLAMMABLE LIQUIDS IN SMALL CONTAINERS J. F. Siddle* Standards of fire protection for metal drums and smaller metal containers of flammable liquids have been well defined and have proved

More information

Appendix B Forms for Inspection, Testing, and Maintenance

Appendix B Forms for Inspection, Testing, and Maintenance Appendix B Forms for Inspection, Testing, and Maintenance This appendix is not a part of the requirements of this NFPA document but is included for informational purposes only. Forms need to be complete

More information

2014 Limited Plan Submittal Checklist

2014 Limited Plan Submittal Checklist City of Aurora Public Works Department WET AND DRY CHEMICAL HOOD SUPPRESSION SYSTEM 2014 Limited Plan Submittal Checklist Building Division 15151 E. Alameda Parkway, Ste 2400 Aurora, CO 80012 303-739-7420

More information

Rental Services Temporary Cooling - Flexible Water Hose

Rental Services Temporary Cooling - Flexible Water Hose Engineering Bulletin Rental Services Temporary Cooling - Flexible Water Hose September 2006 CHS-PRB007-EN Warnings and Cautions Warnings and Cautions. Notice that warnings and cautions appear at appropriate

More information

I-768 FireLock NXT Dry Valve

I-768 FireLock NXT Dry Valve HANG THESE INSTRUCTIONS ON THE INSTALLED VALVE FOR EASY FUTURE REFERENCE WARNING WARNING Failure to follow instructions and warnings can cause product failure, resulting in serious personal injury and

More information

Fire Sprinkler System Maintenance and Testing Page 1 MAINTENANCE AND TESTING OF FIRE SPRINKLER SYSTEMS

Fire Sprinkler System Maintenance and Testing Page 1 MAINTENANCE AND TESTING OF FIRE SPRINKLER SYSTEMS Page 1 MAINTENANCE AND TESTING OF FIRE SPRINKLER SYSTEMS Introduction When properly installed and maintained, automatic fire sprinkler systems have proven to be the most effective means for protecting

More information

Clark County Fire Prevention

Clark County Fire Prevention Clark County Fire Prevention Mission Statement: To provide the highest level of fire protection and related services TITLE: REQUIREMENTS FOR A NEW SPRINKLER SYSTEM IN ACCORDANCE WITH THE 2002 EDITION OF

More information

TECHNICAL DATA. 30a. September 18, 2009 1-1/4-8 (DN32 - DN200)

TECHNICAL DATA. 30a. September 18, 2009 1-1/4-8 (DN32 - DN200) September 18, 2009 30a 1. DESCRIPTION Viking EasyPac Commercial Riser Manifold Assemblies are available in sizes 1-1/4, 1-1/2, 2, 2-1/2, 3, 4, 6 and 8 for commercial systems. They are available with an

More information

FAIRBANKS NIJHUIS PACKAGED FIRE PUMP SYSTEMS. www.fairbanksnijhuis.com

FAIRBANKS NIJHUIS PACKAGED FIRE PUMP SYSTEMS. www.fairbanksnijhuis.com FAIRBANKS NIJHUIS PACKAGED FIRE PUMP SYSTEMS FAIRBANKS NIJHUIS Packaged Fire Pump Systems At the heart of our systems you ll find the Fairbanks Nijhuis pumps you ve relied on for over 90 years. Fairbanks

More information

TECHNICAL DATA. 2. LISTINGS AND APPROVALS See Tables 1 & 2.

TECHNICAL DATA. 2. LISTINGS AND APPROVALS See Tables 1 & 2. May 3, 2013 Foam 138a 1. DESCRIPTION Chemguard Water Powered Oscillating Monitors are designed to automatically discharge over a specific design area upon system activation. These are suitable for use

More information

Insight. Storage Fires. Balanced Risk Engineering Solutions. Understanding the Risk. Commodity Classification. Storage Configuration

Insight. Storage Fires. Balanced Risk Engineering Solutions. Understanding the Risk. Commodity Classification. Storage Configuration Balanced Risk Engineering Solutions Storage Fires Understanding the Risk Many of the most costly fires occur in warehouses and storage areas, where often a high fire risk is combined with high values and/or

More information

Roland Garcia Pearland Fire Department

Roland Garcia Pearland Fire Department Roland Garcia Pearland Fire Department NFPA13D Texas Legislation Conflicting Views - Fire Service and Home Builders Incentives offered in the ICC Detect and control residential fires Prevent injury and

More information

Fighting Fire in Sprinklered Buildings. Student Guide

Fighting Fire in Sprinklered Buildings. Student Guide Fighting Fire in Sprinklered Buildings Student Guide Fighting Fire in Sprinklered Buildings Student Guide Table of Contents Purpose........................................................... 3 Instruction

More information

Series TY-FRB 2.8, 4.2, 5.6, and 8.0 K-Factor Upright, Pendent, and Recessed Pendent Sprinklers Quick Response, Standard Coverage General Description

Series TY-FRB 2.8, 4.2, 5.6, and 8.0 K-Factor Upright, Pendent, and Recessed Pendent Sprinklers Quick Response, Standard Coverage General Description Worldwide Contacts www.tyco-fire.com Series 2.8,.2,.6, 8.0 K-Factor Upright, Pendent, Recessed Pendent Sprinklers Quick Response, Stard Coverage General Description The TYCO Series, 2.8,.2,.6, 8.0 K-factor,

More information

MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION

MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION Fire Pump Plan Review 2009 International Fire Code and NFPA 20 Date of Review / / BLD201 - Project Address: Project Name: Contractor s Business

More information

Approved Products for Fire Protection Piping Systems

Approved Products for Fire Protection Piping Systems R FIRE PROTECTION PRODUCTS 10.01 Approved Products for Fire Protection Piping Systems This product submittal contains approvals of the following piping products for the below-listed projects: products

More information

FIRE ALARM SYSTEMS PERMIT APPLICATION, PLAN SUBMITTAL, DESIGN, INSTALLATION AND INSPECTION REQUIREMENTS Effective Date: January, 2011

FIRE ALARM SYSTEMS PERMIT APPLICATION, PLAN SUBMITTAL, DESIGN, INSTALLATION AND INSPECTION REQUIREMENTS Effective Date: January, 2011 Office of the Fire Marshal 1.0 PERMITS FIRE ALARM SYSTEMS PERMIT APPLICATION, PLAN SUBMITTAL, DESIGN, INSTALLATION AND INSPECTION REQUIREMENTS Effective Date: January, 2011 1.1 To acquire an installation

More information

Inspection and Testing of Water-Based Systems

Inspection and Testing of Water-Based Systems Inspection and Testing of Water-Based Systems Standard Model/Computer-Based Testing Level III Content Outline The candidate for NICET certification at Level III in the Inspection and Testing of Water-Based

More information

DuPont FM-200 COMPARISON TESTING IN A SIMULATED DATA PROCESSING/TELECOMMUNICATIONS FACILITY

DuPont FM-200 COMPARISON TESTING IN A SIMULATED DATA PROCESSING/TELECOMMUNICATIONS FACILITY DuPont FM-200 COMPARISON TESTING IN A SIMULATED DATA PROCESSING/TELECOMMUNICATIONS FACILITY DuPont FM-200 and Automatic Sprinkler Systems Mark L. Robin and Eric W. Forssell, DuPont Fluoroproducts Data

More information

Series TY-FRB 5.6 and 8.0 K-factor Extended Coverage Horizontal Sidewall Sprinklers Quick and Standard Response (Light Hazard) General Description

Series TY-FRB 5.6 and 8.0 K-factor Extended Coverage Horizontal Sidewall Sprinklers Quick and Standard Response (Light Hazard) General Description Worldwide Contacts www.tyco-fire.com Series TY-FRB 5.6 and 8.0 K-factor Extended Coverage Horizontal Sidewall s Quick and Standard Response (Light Hazard) General Description TYCO Series TY-FRB 5.6 and

More information

NYC SUB-SYSTEMS INSTALLATION & SERVICE REQUIREMENTS OF THE FDNY

NYC SUB-SYSTEMS INSTALLATION & SERVICE REQUIREMENTS OF THE FDNY NYC SUB-SYSTEMS INSTALLATION & SERVICE REQUIREMENTS OF THE FDNY Presented by: James Goerl Metro Protection Systems, Inc. jgoerl@metroprotectionsystems.com Agenda Introduction & Learning Objectives History

More information

Recommended Product Specifications Fuel Day Tank System Tramont UTRS Fuel Day Tank

Recommended Product Specifications Fuel Day Tank System Tramont UTRS Fuel Day Tank Recommended Product Specifications Fuel Day Tank System Tramont UTRS Fuel Day Tank This specification describes requirements for a Diesel Fuel Day Tank System consisting of one or more fuel tanks, an Electronic

More information

TECHNICAL DATA. Dry 122a. November 12, 2013

TECHNICAL DATA. Dry 122a. November 12, 2013 Dry 122a 1. PRODUCT DESCRIPTION The Viking is a quick-opening device. When installed with the required external Anti-flood Device, the assembly is designed to increase the operating speed of Viking Model

More information

For Data Center and Control Room Applications

For Data Center and Control Room Applications For Data Center and Control Room Applications Nearly zero wetting No costly clean up or equipment replacement Sustainable design Quick system recharge, minimal downtime No need for assurance of tight room

More information

C I T Y O F S E L M A F I R E D E P A R T M E N T

C I T Y O F S E L M A F I R E D E P A R T M E N T C I T Y O F S E L M A F I R E D E P A R T M E N T Informational Bulletin Regarding Residential Fire Sprinkler Systems for One and Two Family Homes: Frequently Asked Questions ADMINISTRATIVE PROVISIONS:

More information

SECTION 15300 - FIRE PROTECTION PIPING SYSTEMS STANDARD CONSTRUCTION STANDARD PART 1: GENERAL

SECTION 15300 - FIRE PROTECTION PIPING SYSTEMS STANDARD CONSTRUCTION STANDARD PART 1: GENERAL PART 1: GENERAL 1.01 Scope of Standard A. This standard provides general guidance concerning the specific preferences of The University of Texas at Austin for automatic fire sprinkler and standpipe systems.

More information

MERCER ISLAND FIRE DEPARTMENT FIRE COMMERCIAL SPRINKLER STANDARDS

MERCER ISLAND FIRE DEPARTMENT FIRE COMMERCIAL SPRINKLER STANDARDS MERCER ISLAND FIRE DEPARTMENT FIRE COMMERCIAL SPRINKLER STANDARDS COMMERCIAL FIRE SPRINKLER SYSTEMS Page 1-5 SCOPE: Fire sprinkler systems in the City of Mercer Island shall meet the criteria as set forth

More information

1-1/2 Inch (DN40) 9 lbs. (4,1 Kg) 8 lbs. (3,6 Kg) Flange Groove* N/A N/A. Flange Flange N/A N/A

1-1/2 Inch (DN40) 9 lbs. (4,1 Kg) 8 lbs. (3,6 Kg) Flange Groove* N/A N/A. Flange Flange N/A N/A Worldwide Contacts www.tyco-fire.com DV-5 Deluge Valve Diaphragm Style General Description The TYCO 1-1/2 thru inch (DN40 thru DN200), DV-5 Deluge Valves are diaphragm type valves designed for vertical

More information

REGULATIONS for INSTALLATION, MAINTENANCE, and TESTING APPLICATION PACKET

REGULATIONS for INSTALLATION, MAINTENANCE, and TESTING APPLICATION PACKET REGULATIONS for INSTALLATION, MAINTENANCE, and TESTING FIRE SUPPRESSION SYSTEMS APPLICATION PACKET CITY OF NAPERVILLE 400 S. EAGLE STREET NAPERVILLE, Il 60540 PHONE: 630.420.6070 FAX: 630.420.6657 Fire

More information

The Station House A News Letter for AHJ s,

The Station House A News Letter for AHJ s, May, 2004 Volume 4, Issue 2 The Station House A News Letter for AHJ s, Fire Sprinkler Contractors & Underwriters New European Legislation Mandates Tunnel Protection In This Issue Vehicle & Train Tunnel

More information

STANDARD CONTAINER DETAILS 20' GENERAL PURPOSE / DRY VAN. Door Opening. Weight 40' GENERAL PURPOSE / DRY VAN. Internal Dimensions.

STANDARD CONTAINER DETAILS 20' GENERAL PURPOSE / DRY VAN. Door Opening. Weight 40' GENERAL PURPOSE / DRY VAN. Internal Dimensions. STANDARD CONTAINER DETAILS 20' GENERAL PURPOSE / DRY VAN Millimeters Length 5'900 19'4'' Height 2'390 7'10'' Height 2'280 7'6'' 21'800 48'060 2'200 4'850 Gross 24'000 52'910 Capacity 33,2 1173 40' GENERAL

More information

Series DS-1 Dry-Type Sprinklers 5.6K Horizontal Sidewall Standard and Quick Response, Extended Coverage General Description

Series DS-1 Dry-Type Sprinklers 5.6K Horizontal Sidewall Standard and Quick Response, Extended Coverage General Description Worldwide Contacts www.tyco-fire.com Series DS-1 Dry-Type Sprinklers 5.6K Horizontal Sidewall Standard and Quick Response, Extended Coverage General Description TYCO Series DS-1 Dry-Type Sprinklers, 5.6

More information

INSTRUCTIONS FOR BUILDINGS WITH FIRE PROTECTION EQUIPMENT

INSTRUCTIONS FOR BUILDINGS WITH FIRE PROTECTION EQUIPMENT INSTRUCTIONS FOR BUILDINGS WITH FIRE PROTECTION EQUIPMENT FIRE EXTINGUISHERS,SPRINKLER SYSTEMS AND FIRE ALARMS Attachment #1 Inspection of Fire Extinguishers Fire Extinguishers must be tested according

More information

The Jockey Pump, an Important Part of a Fire Pump System.

The Jockey Pump, an Important Part of a Fire Pump System. The Jockey Pump, an Important Part of a Fire Pump System. May 18, 2008 A Jockey Pump is an important component of a fire pump system. The Jockey Pump is not as mundane, as many engineers, contractors and

More information

Fire Protection Systems

Fire Protection Systems VICTAULIC FIRE PROTECTION SYSTEMS G-05 UPDATED 6/2009 Fire Protection Systems G-05 UPDATED 6/2009 Innovation More than 80 years of piping systems solutions uilt into every FireLock system are innovative

More information

TRAINING BULLETIN Fire Apparatus Pump Test

TRAINING BULLETIN Fire Apparatus Pump Test TOPIC: TRAINING BULLETIN Fire Apparatus Pump Test EFFECTIVE DATE: 05/06 DOC NO: TB081 CROSS REF: INTRODUCTION District Fire Apparatus Pump Testing is completed on an annual basis. Currently, pump testing

More information

SELF-INSPECTION PROGRAM FOR FIRE PROTECTION EQUIPMENT

SELF-INSPECTION PROGRAM FOR FIRE PROTECTION EQUIPMENT SELF-INSPECTION PROGRAM FOR FIRE PROTECTION EQUIPMENT INTRODUCTION No matter how reliable fire protection equipment may seem, periodic maintenance is needed to ensure proper operation. Fire protection

More information

CHAPTER 9 FIRE PROTECTION SYSTEMS

CHAPTER 9 FIRE PROTECTION SYSTEMS CHAPTER 9 FIRE PROTECTION SYSTEMS SECTION 901 GENERAL 901.1 Scope. Provisions of this chapter shall govern the application, design, installation, testing and maintenance of automatic sprinklers, standpipes

More information

Plan Review and Construction Project Guidelines for Columbia University & CUMC NYC

Plan Review and Construction Project Guidelines for Columbia University & CUMC NYC Plan Review and Construction Project Guidelines for Columbia University & CUMC NYC Prepared by Factory Mutual Insurance Company 400 Interpace Parkway Building C Third Floor Parsippany, NJ 07054-1196 2013

More information