F05D Meeting on Damped AC Voltage Testing
|
|
- Tyler Hutchinson
- 8 years ago
- Views:
Transcription
1 October 28 th, 2008 from pm in San Antonio, TX Agenda F05D Damped AC Voltage Testing 1
2 Agenda F05D Damped AC Voltage Testing Welcome: Introduction On-site testing voltages e.g. IEC High Voltage test techniques Part 3: Definitions and requirements for on-site testing 1. Direct voltage (DC) 2. Alternating current voltage (AC) 3. Very low frequency voltage (VLF) 4. Damped alternating current voltage (DAC) Most in use for on-site testing and diagnosis of HV power cables 5. Lighting impulse voltage (LI) 6. Lighting switch voltage (LS) 2
3 Welcome: Introduction the use of damped AC voltages 1. Damped sinusoidal AC voltage (DAC) are several years applied method for onsite energizing of polymeric and paper insulated power cables and the insulation of rotating machines. 2. On-site applying of DAC voltages is mostly combined with PD measurements and dielectric losses measurements. 3. At present there are three vendors of DAC systems (one in Switzerland and two in Germany). 4. Several comparison test have been done and published in the past e.g. KEMA (1999), CESI (2002), EuroTest (2007) to demonstrate the applicability of DAC voltages for on-site testing of power cables. Welcome: Introduction principals of energizing and PD measurement at continuous AC and at damped AC voltages PD occurrence at continuous sinusoidal AC (e.g Hz) PD occurrence at damped sinusoidal AC (e.g Hz) dielectric losses PD inception voltage PDIV PD inception voltage PDIV PD extinction voltage PDEV PD extinction voltage PDEV PD level in [pc] PD level in [pc] PD pattern information < PD pattern information Test over-voltage destructiveness > Test over-voltage destructiveness 3
4 Welcome: Introduction discussion of the Ad-hoc meeting ICC Spring 2008 Different suggestions have been made to be considered in the future work: 1. The focus of the future DACV document has to be on: a) Basic principles of possible DAC test circuits, voltage generation, and measurement b) Test procedure: voltage application, test duration c) Test and measuring parameters: most important testing and diagnostic parameters 2. and not on the detection of partial discharges (see the IEEE document). 3. Literature list of relevant papers about DACV. 4. Due to the fact that in North and South America only few users are known in addition to survey also utility/service provider experiences from other users in the world are welcome. Welcome: Introduction Conclusions of the Ad-hoc meeting ICC Spring In the IEEE 400 documents all different energizing methods which are in use for on-site testing of power cables have to be discussed. 2. With regard to damped AC voltage (DACV) and based on information as given by experts and users a documentation of DACV in a separate document, according to the lines of IEEE 400 has to be done. 3. All 32 participants supported by voting the proposal to start a Discussion Group on damped AC voltages. 4
5 Agenda F05D Damped AC Voltage Testing F05D Damped AC Voltage Testing Scope and Mission Statement Scope: To collect and to evaluate information and experience as needed to propose a preparation of a Guide for Field Testing of Shielded Power Cable Systems Using Damped AC Voltages Mission: provide information concerning test procedures for shielded cable systems using damped AC voltages and performing diagnostic measurements, 5
6 Agenda F05D Damped AC Voltage Testing Agenda F05D Damped AC Voltage Testing 6
7 Agenda F05D Damped AC Voltage Testing Survey about using DAC voltages General Vendors: 4 Lemke Diagnostics, since 1997 Seitz Instruments, since 1999 Haefely Test (Hubbell HV), since 2001 SebaKMT, since 2001 Number of DAC systems: > approx. 120 Representative user response: 33% Responders type: utilities, service providers Geographic: Europe (72%), Asia (28%), US (??) DAC system application types: MV cable networks, HV cable networks 7
8 Purpose of testing using the DAC voltages voltage testing 23% partial discharge measurement 25% 52% dielectric losses measurement Relevance of combining PD test and the voltage test Yes: 50% No: 50% Voltage testing 18% Max. U test 3xU 0 82% Max. U test 2xU 0 Breakdown during voltage testing: 0%. 2% Before breakdown PD has been measured: 81% Before breakdown no PD has been measured: 47% 8
9 Test voltage level as used for PD measurements Max. U test 3xU 0 18% 9% Max. U test 1xU 0 73% Max. U test 2xU 0 The present standards IEEE 400 is using the name Oscillating Waves (OW). The present IEC is using the name damped alternating voltages (DAC). To avoid any confusion between oscillating voltages in the range of khz and damped AC voltage in the range of 20Hz- 500Hz as there are in use 100% of responders support the proposal to change the name to DAC. Testing procedures Duration time of applying DAC voltages: Number of DAC voltage applications/voltage level: 10 min. up to 30 min. 4x up to 50x Examples of DAC voltage application: a) x at each level: 0.3Uo, 0.5Uo, 0.7Uo, 1.0Uo, 1.3Uo, 1.5Uo, 1.7Uo, 2.0Uo c) For voltage test new cables up to 50x max 2Uo up to 3Uo (depends on safety, age and switchgear type) d) If no PD: 5x at each level: 0.8Uo, 1.0Uo, 1,5Uo, 2.0Uo If critical PD: 20x at each level 0.8Uo, 1.0Uo, 1,5Uo, 2.0Uo till PD significantly increases Two types of tests: 1. new systems 2. aged systems 9
10 Summary 1. Worldwide damped AC voltages (DAC) are in use for testing and PD measurement of new and service aged distribution and transmission power cables; 2. Diagnostic testing may consist of partial discharges and/or dielectric losses measurement and single voltage testing; 3. Regarding the test time there is no uniform testing procedure and the testing times as used till now are maximum 30min; 4. Regarding the test voltages there is no uniform testing procedure and most diagnostic application are limited to 2.0 Uo and for after-laying test are up to 3Uo; Agenda F05D Damped AC Voltage Testing 10
11 Agenda F05D Damped AC Voltage Testing Agenda F05D Damped AC Voltage Testing 11
SUITABILITY OF DIFFERENT TEST VOLTAGES FOR ON-SITE TESTING OF XLPE CABLE SYSTEMS
SUITABILITY OF DIFFERENT TEST VOLTAGES FOR ON-SITE TESTING OF XLPE CABLE SYSTEMS Michael Hensel HIGHVOLT Prüftechnik Dresden GmbH 2 3 Content 1 Introduction Test parameters and their significance Differences
More informationInvestigation of VLF Test Parameters. Joshua Perkel Jorge Altamirano Nigel Hampton
Investigation of VLF Test Parameters Joshua Perkel Jorge Altamirano Nigel Hampton 1 Introduction - why IEEE400.2 is in use with recommendations of test times and test voltages At the start of the CDFI
More informationMOBILE SYSTEM FOR DIAGNOSIS OF HIGH VOLTAGE CABLES (132KV/220KV) VLF-200 HVCD
MOBILE SYSTEM FOR DIAGNOSIS OF HIGH VOLTAGE CABLES (132KV/220KV) VLF-200 HVCD VERY LOW FREQUENCY (VLF) - PARTIAL DISCHARGES AND TANGENT DELTA HV/EHV POWER CABLES DIAGNOSTIC AND ON-SITE FIELD TESTING WITH
More informationTHE USE OF AFTER-INSTALLATION COMMISSIONING TESTS TO ASSURE MV POWER CABLE SYSTEMS MEET MANUFACTURERS STANDARDS
THE USE OF AFTER-INSTALLATION COMMISSIONING TESTS TO ASSURE MV POWER CABLE SYSTEMS MEET MANUFACTURERS STANDARDS Stefaan JESPERS (1), Massimo VANOSSI (2), Marco GREEN (3), Benjamin Lanz (4) 1 Cegelec, Brussels,
More informationD1-306. Session 2004 CIGRÉ. 50 kv. 150 kv. Condition Assessment of High Voltage Power Cables. The Netherlands. E. Gulski * F.J.
21, rue d'artois, F-75008 Paris http://www.cigre.org D1-306 Session 2004 CIGRÉ Condition Assessment of High Voltage Power Cables E. Gulski * F.J. Wester Ph. Wester E.R.S. Groot J. W. van Doeland Delft
More informationHow To Test For Safety On A Power Cable
T H E M A G A Z I N E O F 7 x 2 4 E X C H A N G E I N T E R N AT I O N A L A Green Approach to Building a Superior Data Center S P R I N G 0 9 BUILD FOR TODAY. EXPAND ON DEMAND. Modularity in the data
More informationTAN δ (DELTA) CABLE TESTING OVERVIEW AND ANSWERS TO FREQUENTLY ASKED QUESTIONS. What Is Tan δ, Or Tan Delta?
TAN δ (DELTA) CABLE TESTING OVERVIEW AND ANSWERS TO FREQUENTLY ASKED QUESTIONS What Is Tan δ, Or Tan Delta? Tan Delta, also called Loss Angle or Dissipation Factor testing, is a diagnostic method of testing
More informationWorld Leader in HV Testing Technology
World Leader in HV Testing Technology Cable Fault Locators w/tdr Oil/Fluid Dielectric Testers Very Low Frequency AC Technology W/TD & PD Diagnostics Portable AC Hipots ---------------------------------
More informationWhy Buy HVI VLF Products?
Very Low Frequency AC Hipots AC testing of cables and electrical apparatus is now easier than ever. Since the introduction of the High Voltage, Inc. line of portable and affordable VLF hipots, there is
More informationDiscussion on Class I & II Terminology. IEEE PES Transformers Committee Fall Meeting 2011 Boston, MA
Discussion on Class I & II Terminology IEEE PES Transformers Committee Fall Meeting 2011 Boston, MA What is Class I & II? C57.12.00 2010 is the only document we have that defined these terms. 5.10 Insulation
More informationCABLE DIAGNOSIS USING VARIABLE FREQUENCY AND PARTIAL DISCHARGE DIAGNOSIS WITH DEFECT LOCATION AND CHARACTERIZATION G.C. Montanari J. Rickman D.
CABLE DIAGNOSIS USING VARIABLE FREQUENCY AND PARTIAL DISCHARGE DIAGNOSIS WITH DEFECT LOCATION AND CHARACTERIZATION G.C. Montanari J. Rickman D. Kremer Abstract A new approach to cable diagnostics is discussed
More informationHigh Voltage Test Equipment. Product Catalogue
High Voltage Test Equipment Product Catalogue High Voltage Test Equipment Innovative, proven, economic HV Testing from b2 High Voltage HVA VLF-High Voltage Test Systems from page 3 TD Tan Delta Diagnostic
More informationEMTP STUDIES PERFORMED TO INSERT LONG AC CABLES IN THE FRENCH GRID
Tension (kv) Impedance (Ohms) EMTP STUDIES PERFORMED TO INSERT LONG AC CABLES IN THE FRENCH GRID frequency (Hz) Simon DESCHANVRES Yannick VERNAY RTE, CNER, Substations Department t (ms) EMTP-RV Users Group
More informationBAUR cable testing and diagnostics. Networks are sensitive. We help you protect them. USA Distributor:
BAUR cable testing and diagnostics. Networks are sensitive. We help you protect them. USA Distributor: HV TECHNOLOGIES,Inc. Tel:+1-703-365-2330 www.hvtechnologies.com hvsales@hvtechnologies.com Improved
More informationTWENTIES WORKSHOP, EWEA 2012 Unveiling the future energy system: full scale demonstrations to reach 2020 targets. 17th April 2012
TWENTIES WORKSHOP, EWEA 2012 Unveiling the future energy system: full scale demonstrations to reach 2020 targets 17th April 2012 Session 2 Technological challenges to cope with in TWENTIES field tests
More informationActuator-Sensor-Interface
Selection and ordering data Design Order No. Price Pack 3RX9 307-0AA00 3RX9 307-1AA00 4FD5 213-0AA10-1A 3RX9 305-1AA00 3RX9 306-1AA00 Single output IP 65 current 2.4 A Rated input voltage DC 24 V current
More informationEVALUATION OF ON-SITE DIELECTRIC RESPONSE METHODS FOR NON- DESTRUCTIVE TESTING OF WATER TREED MV XLPE CABLES
EVALUATION OF ON-SITE DIELECTRIC RESPONSE METHODS FOR NON- DESTRUCTIVE TESTING OF WATER TREED MV XLPE CABLES Sverre Hvidsten*, Peter Werelius**, Jørgen Christensen*** * SINTEF Energy Research (SEfAS),
More informationDDX 7000 & 8003. Digital Partial Discharge Detectors FEATURES APPLICATIONS
DDX 7000 & 8003 Digital Partial Discharge Detectors The HAEFELY HIPOTRONICS DDX Digital Partial Discharge Detector offers the high accuracy and flexibility of digital technology, plus the real-time display
More informationDDX 7000 & 8003. Digital Partial Discharge Detectors FEATURES APPLICATIONS
DDX 7000 & 8003 Digital Partial Discharge Detectors The HAEFELY HIPOTRONICS DDX Digital Partial Discharge Detector offers the high accuracy and flexibility of digital technology, plus the real-time display
More informationThree-phase monitoring relay CM-PFE
Data sheet Three-phase monitoring relay CM-PFE The CM-PFE is a three-phase monitoring relay that monitors the phase parameter phase sequence and phase failure in three-phase mains. 2CDC 251 005 S0012 Characteristics
More informationElectrical Predictive and Preventative Maintenance
Electrical Predictive and Preventative Maintenance Electrical and mechanical equipment is subject to failure at the worst possible time for no apparent reason. - Mose Ramieh III There are two types
More informationFor the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit.
Current Transducer HO-P series I PN = 6, 10, 25 A Ref: HO 6-P, HO 10-P, HO 25-P For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary
More information3. ELECTRICAL PERFORMANCE PROPERTY TEST CONDITION PERFORMANCE 3. 1 Contact Resistance 1) Center Push 100mΩ Max
1. GENERAL 1. 1 Application : This specification is applied to MULTI WAY SWITCH for electronic equipment. 1. 2 Operating Temperature Range :-25 ~ 70 1. 3 Storage Temperature Range :-0 ~ 85. However, 96
More informationBAUR Cable Testing & Diagnostics. Networks are sensitive. We help you to protect them.
BAUR Cable Testing & Diagnostics. Networks are sensitive. We help you to protect them. Improved security and cost-effectiveness of cable networks High voltage testing and diagnostics with BAUR Underground
More informationInvestigation of the Residual-charge Technique for Diagnosis of Water-tree Deteriorated Cross-linked Polyethylene Cable
Investigation of the Residual-charge Technique for Diagnosis of Water-tree Deteriorated Cross-linked Polyethylene Cable Dr. Uchida Katsumi*, Youichi Katou*, Dr. Hiroyuki Kon, Dr. Kazuo Watanabe and Takenori
More informationThe Impact of Transmission Cable System Construction and Design on Commissioning Test Options & Results
The Impact of Transmission Cable System Construction and Design on Commissioning Test Options & Results Steve Campbell General Cable Benjamin Lanz IMCORP Subcommittee A ICC Meeting in Fountain Hills, AZ
More informationGUIDE FOR TESTING POWER TRANSFORMERS
GUIDE FOR TESTING POWER TRANSFORMERS Routine test 11/11/02 Pagina 1 di 10 INDEX Introduction... 3 1 Dielectric tests Separate-source voltage withstand test... 4 2 Induced voltage test... 5 3 Voltage ratio
More informationRM17TE 183...528 V AC. Main. Product or component type. Product specific application. Relay monitored parameters 250 V DC 5 A DC
Characteristics multifunction control relay RM17-TE - range 183..528 V AC Complementary Reset time Maximum switching voltage Minimum switching current Maximum switching current [Us] rated supply voltage
More informationCase Studies in On-Line Measurement of PD in Motors Fed by Voltage Source PWM Drives
Case Studies in On-Line Measurement of PD in Motors Fed by Voltage Source PWM Drives G.C. Stone, I. Culbert, H.G. Sedding Qualitrol-Iris Power Mississauga, Ontario, Canada Abstract On-line partial discharge
More informationSURGE PROTECTIVE DEVICES
SURGE PROTECTIVE DEVICES 1. INTRODUCTION In order to ensure safety of people, protection of equipment and, to a certain extent, continuity of supply, insulation co-ordination aims at reducing the likelihood
More informationIEEE802.3poep Study Group Revision of isolation requirements in IEEE802.3 clause 33.
IEEE802.3poep Study Group Revision of isolation requirements in IEEE802.3 clause 33. San Francisco, July 2005 Arkadiy Peker Powerdsine Arkadiyp@powerdsineusa.com Yair Darshan Powerdsine Yaird@powerdsine.com
More informationTRACTION NETWORK MONITORING AND PROTECTION SYSTEM SMTN-3 CITY ELECTRIC TRANSPORT RAILWAYS METRO INDUSTRY
TRACTION NETWORK MONITORING AND PROTECTION SYSTEM SMTN-3 CITY ELECTRIC TRANSPORT RAILWAYS METRO INDUSTRY 2 TRACTION NETWORK MONITORING AND PROTECTION SYSTEM Traction network monitoring and protection system,
More informationMiCAFIL. 1 RIP Technology. Bushings. Z. Zic 09/2003
MiCAFIL 1 RIP Technology Z. Zic 09/2003 )XQFWLRQRI+LJK9ROWDJH%XVKLQJ Uncontrolled (natural) electrical field Capacity-controlled electrical field %XVKLQJV0DLQ,QVXODWLRQ6\VWHPV 7\SH 0DLQ,QVXODWLRQ +RXVLQJFRYHU
More informationSINEAX U553 Transducer for AC Voltage
With power supply RMS value measurement Carrying rail housing P/0 Application he transducer SINEAX U55 (Fig. ) converts a sinusoidal or a distorted AC voltage into a load independent DC current or a load
More informationHSP GmbH Zum Handwerkerhof 2 90530 Wendelstein Tel. 09129 / 2852-0 Fax: 09129 / 2852-11 Web: www.hsshsp.de EMAIL: HSP@hsshsp.de NTG-3000.
NTG-3000 Transducer Data Sheet Document Version 2.8 Page 1 of 10 Versions / Revisions: Document Creation Author Description version date 2.0 2012-07-25 P. Compensis First official version 2.1 2012-08-24
More informationHOW GOOD ARE ELECTRICAL DIAGNOSTIC TESTS TO PREDICT WATER TREES IN HV CABLES AN EVALUATION USING OPTICAL MICROSCOPY
Journal of ELECTRICAL ENGINEERING, VOL. 56, NO. 1-2, 25, 31 35 HOW GOOD ARE ELECTRICAL DIAGNOSTIC TESTS TO PREDICT WATER TREES IN HV CABLES AN EVALUATION USING OPTICAL MICROSCOPY Motaheruddin Ahmed Mohammad
More informationElectronic timer CT-VBS.17+18 OFF-delayed without auxiliary voltage, for DC contactors Data sheet
Characteristics Single-function OFF-delay timer for DC contactors, without auxiliary voltage Width.5 mm CDC 5 6 F3 Approvals A culus E CCC CT-VBS a Circuit diagram b Marker label Marks a CE b C-Tick Order
More informationThermistor motor protection
Thermistor motor protection CM-E Range Thermistor motor protection Thermistor motor protection relays Benefits and advantages Selection table Operating principle and fields of application for thermistor
More informationRISH CON - Hz. Salient Features : Application : Product Features: FREQUENCY TRANSDUCER
Application : The RISH CON - Hz transducer is used for frequency measurement. The output signal is proportional to measured frequency and is either load independent DC Current or load independent DC Voltage.
More informationPower over Ethernet plus Isolation requirements. David Law 3Com David_Law@3Com.com
Power over Ethernet plus Isolation requirements David Law 3Com David_Law@3Com.com Agenda History 10BASE2 and 10BASE5 10BASE-T DTE Power via MDI Analyses of Differences in DTE Power via MDI Recommendation
More informationA Practical Guide to Dielectric Testing
Chroma Systems Solutions, Inc. A Practical Guide to Dielectric Testing 19032 Series Electrical Safety Analyzer & 19050 Series Hipot Tester AC/DC/IR/SCAN Keywords: Dielectric tests, insulation resistance
More informationEMOSAFE EN-100. Network Isolators for PCB assembly 1 GENERAL DESCRIPTION. Product Data Sheet ENGLISH
ENGLISH EMOSAFE EN-100 Product Data Sheet Network Isolators for PCB assembly November 2013 1 GENERAL DESCRIPTION The EMOSAFE EN-100 Network Isolator interrupts all galvanically conducting connections (conductors
More informationOn-Line Partial Discharge Testing. Skip Hicks Director - New Business Development
On-Line Partial Discharge Testing Skip Hicks Director - New Business Development What Is Partial Discharge? According the the International Electrotechnical Commission (IEC) International Standard 60270,
More informationRack mounted telephone- and leased line modem for industrial applications
Rack mounted telephone- and leased line modem for industrial applications TR-6 Rack modem for industrial PSTNand /-wire leased line applications The TR-6 is an analogue V. 9 -rack PSTN modem as well as
More information7.2KV SL400 Withdrawable Vacuum Contactor-Fuse Combination Units
Automotive Powering business worldwide Aerospace Eaton delivers the hundreds of power distribution products that are answering the demands of today s fast changing world. We help our customers worldwide
More informationInductive Proximity Sensors
M12 Inductive Proximity Sensors Standard Length Mini's Extended Sensing 3 Wire DC 2 Wire DC 2 Wire AC (Wiring Schematic) 3 Wire DC PNP Normally Open (1) IMM32122C IMM35124C IMN32122C IMN35124C IMN32122M12
More informationWIRE AND CABLE ENGINEERING GUIDE
Excerpt From Prysmian s WIRE AND CABLE ENGINEERING GUIDE Page 1 of 8 CABLE TESTING Testing represents an integral part in the life of a cable. A cable will be subjected to multiple tests in its lifetime
More information(PREVIEW) Indian Standard COMMON SPECIFICATION FOR HIGH-VOLTAGE SWITCHGEAR AND CONTROLGEAR STANDARDS
(PREVIEW) Indian Standard COMMON SPECIFICATION FOR HIGH-VOLTAGE SWITCHGEAR AND CONTROLGEAR STANDARDS IS 12729:2004 IEC 60694(2002) 1.1 Scope This International Standard applies to a.c. switchgear and controlgear,
More informationOMICRON Monitoring Solutions
OMICRON Monitoring Solutions Partial discharge monitoring of high voltage assets M/G Extending the service life of high-voltage assets Why monitoring? Insulation degradation in critical high-voltage (HV)
More informationAMP CO Plus Insert for Cat. 6 A Applications
Product Specification 108-93039 10/Mar/2011 Rev F AMP CO Plus Insert for Cat. 6 A Applications 1. SCOPE 1.1 Content This specification covers performance, tests and quality requirements for AMP* CO Plus
More informationABB 1. Three-phase monitoring relay CM-PFS. Data sheet. Features. Approvals. Marks. Order data. Order data - Accessories. Application.
1SR 430 824 F9300 Features Monitoring of three-phase mains for phase sequence and failure Powered by the measuring circuit 2 c/o (SPDT) contacts 1 LED for status indication Approvals R: yellow LED - relay
More informationHigh Voltage Electrical Equipment Failure Diagnosis. Presented by: Spencer Tang & Terence Ng T&T Inspection & Engineering Sdn Bhd
High Voltage Electrical Equipment Failure Diagnosis Presented by: Spencer Tang & Terence Ng T&T Inspection & Engineering Sdn Bhd High Voltage Electrical Equipment Failure Diagnosis Definition of High Voltage
More informationCirculating Current Relay. Type IRXm
Circulating Current Relay Type IRXm ABB a global technology leader ABB is a global leader in Power and Automation technologies that enable utility and industry customers to improve performance while lowering
More informationSANS 10142-1 : 2008 CODE OF PRACTICE THE WIRING OF PREMISES Part 1 : Low Voltage Installation
SANS 10142-1 : 2008 CODE OF PRACTICE THE WIRING OF PREMISES Part 1 : Low Voltage Installation 4 Compliance Proof of Compliance (Sub clause 4.1.1) The SABS safety mark The SABS approved performance mark
More informationTelephone- and leased line modem for industrial applications TD-36
Telephone- and leased line modem for industrial applications TD-36 Modem for industrial PSTN- and leased line applications The TD-36 is an analogue V.34 PSTN modem as well as an industrial 2-wire leased
More informationType: DILM32 10(24V50HZ) Article No.: 277247
Type: DILM32 10(24V50HZ) Article No.: 277247 Ordering information Rated operational current AC 3 400 V I e A 32 Max. rating for three phase motors, 50 60 Hz AC 3 230 V Max. rating for three phase motors,
More informationIDEAL INDUSTRIES, INC. TECHNICAL MANUAL MODELS: 61-763 61-765
IDEAL INDUSTRIES, INC. TECHNICAL MANUAL MODELS: 61-763 61-765 The Service Information provides the following information: Precautions and safety information Specifications Performance test procedure Calibration
More informationCIGRE 2012 A brief report regarding B1 and D1 activities (related to cables)
CIGRE 2012 A brief report regarding B1 and D1 activities (related to cables) Pierre ARGAUT CIGRÉ Study Committees Rotating Electrical Machines SC A1 Transformers SC A2 High-Voltage Equipment SC A3 Insulated
More informationLAUBE TECHNOLOGY DRY REED RELAYS
LAUBE TECHNOLOGY DRY REED RELAYS CONTACT FORM CURRENT PART SERIES PAGE #'S (1A) SPST-NO 1 AMP D41A...0L 147~148 (Link) (1A) SPST-NO 1 AMP D71A.1.0 149~150 (Link) (1A) SPST-NO 1 AMP F51A.100 151~152 (Link)
More informationHOW TO SELECT VARISTORS
HOW TO SELECT VARISTORS We have three alternatives: - selection of the varistors suitable for the operating voltage of the application - calculating the surge current, energy absorption and average power
More informationUnified requirements for systems with voltages above 1 kv up to 15 kv
(1991) (Rev.1 May 2001) (Rev.2 July 2003) (Rev.3 Feb 2015) Unified requirements for systems with voltages above 1 kv up to 15 kv 1. General 1.1 Field of application The following requirements apply to
More informationCondition Monitoring of equipment to improve quality of supply to customers by averting failures
Condition Monitoring of equipment to improve quality of supply to customers by averting failures Author & presenter: Patrick O Halloran BTECH Manager Technology Services at City Power Johannesburg Abstract
More informationSingle-phase (220...240 V) voltage monitoring: Undervoltage Overvoltage Window mode (overvoltage + undervoltage) Voltage fault memory selectable
Features 70.11 70.31 70.41 Electronic voltage monitoring relays for single and three-phase applications Multifunctional types, providing the flexibility of monitoring Undervoltage, Overvoltage, Window
More information48.12. 2 pole, 8 A Safety relay. Screw terminal. 35 mm rail (EN 60715) mounting. 2 CO (DPDT) 8/15 250/400 2,000 500 0.37 8/0.65/0.
48 Series - Relay interface modules 8 A Features 48.12 2 Pole Safety relay interface modules, 15.8 mm wide 48.12-2 Pole 8 A (screw terminal) DC sensitive coils Relay with forcibly guided contacts according
More information40 Years of experience in EMC testing
40 Years of experience in EMC testing Your reference laboratory for tests of generation, propagation and reception of electromagnetic energy in civil, military and industrial applications. CESI has been
More informationInsulation resistance
The insulation resistance is particularly important for the prevention of damage and injury, and for the reliability of electrical systems and equipment. On the one hand it is basis for the protection
More informationJUMPFLEX 857 Series. 0...20 ma 2...10 V. 4...20 ma. Transducers / Relay and Optocoupler Modules
0888-0172/0002-3601 JUMPFLEX 857 Series 2.0 E 12/08 Printed in Germany Subject to design changes 2...10 V 0...20 ma 4...20 ma WAGO Kontakttechnik GmbH & Co. KG Postfach 2880 32385 Minden Hansastraße 27
More informationAssessment ASSET MANAGEMENT SERVICES. Benefits: > Optimal Exploitation > Increased Reliability > Reduced Unplanned Outages Time.
Benefits: > Optimal Exploitation > Increased Reliability Applications The Condition services include all of those activities aimed at defining the conditions of all the components of a link before it is
More informationType: DILM9 10(24VDC) Article No.: 276705
Type: DILM9 10(24VDC) Article No.: 276705 Ordering information Rated operational current AC 3 400 V I e A 9 Max. rating for three phase motors, 50 60 Hz AC 3 230 V Max. rating for three phase motors, 50
More informationQuick Connect. quick - simple - efficient. www.g-mw.de
Quick Connect quick - simple - efficient www.g-mw.de Phone: +49 9103 7129-0 Fax: +49 9103 7129-207 Innovative connection technology to plug three single-phase current transformers to multifunctional power
More informationElectronic timer CT-AHD.12 OFF-delayed with 1 c/o (SPDT) contact
Data sheet Electronic timer CT-AHD.12 OFF-delayed with 1 c/o (SPDT) contact The CT-AHD.12 is an electronic time relay with OFF-delay. It is from the CT-D range. With their MDRC profile and a width of only
More informationType: EASY719 DC RC Article No.: 274119. Ordering information Relay outputs Quantity 6 Power supply V DC 24 V DC. Description
Type: EASY719 DC RC Article.: 274119 Ordering information Relay outputs Quantity 6 Power supply V DC 24 V DC Description 12 digital inputs (4 inputs available as analog inputs) 6 relay outputs LCD display
More informationOn-line PD Monitoring Makes Good Business Sense
On-line PD Monitoring Makes Good Business Sense An essential tool for asset managers to ensure reliable operation, improve maintenance efficiency and to extend the life of their electrical assets. Executive
More informationCapacitor Bank Switching with Vacuum Circuit Breakers
Technical collection Capacitor Bank Switching with Vacuum Circuit Breakers 2008 - Conferences publications H. Schellekens 2008 China International Conference on Electricity Distribution (CICED 2008) 1
More informationPARTIAL DISCHARGE INCEPTION TESTING ON LOW VOLTAGE MOTORS
PARTIAL DISCHARGE INCEPTION TESTING ON LOW VOLTAGE MOTORS Copyright Material IEEE Paper No. PCIC-2004-27 Dennis Bogh Senior Member, IEEE GE - Motors 18628 182nd Ave NE Woodinville, WA 98077 USA Jeff Coffee
More informationELECTRICAL INSULATION TESTING OF HV EQUIPMENT UP TO 33kV
1. SCOPE This document details PowerSystems requirements for electrical testing of HV Equipment up to and including 33kV. 2. ISSUE RECORD This is a Reference document. The current version of Controlled
More informationRM35UA13MW. range 15..600 V. Main. Product or component type. Relay monitored parameters
Characteristics multifunction voltage control relay RM35-U - range 15..600 V Complementary Reset time Maximum switching voltage [Us] rated supply voltage Supply voltage limits Power consumption in W Main
More informationHV Submarine Cable Systems Design, Testing and Installation
HV Submarine Cable Systems Design, Testing and Installation CIGRE Ireland Technical Seminar 6 th October 2010 Robert Donaghy Senior Consultant Engineer, ESB International Presentation Overview Applications
More informationType: DILM50(230V50HZ,240V60HZ) Article No.: 277830
Type: DILM50(230V50HZ,240V60HZ) Article No.: 277830 Ordering information Rated operational current AC 3 400 V I e A 50 Max. rating for three phase motors, 50 60 Hz AC 3 230 V Max. rating for three phase
More informationPCS0100en 02.2008. Persy Control Services B.V. Netherlands
P-Bus Gateway PBGW2.128 Universal gateway between the P-bus protocol and open standard protocols. The variety of available electrical interfaces on the gateway offers a wide range of possibilities for
More informationCable Solutions for Servo and Variable Frequency Drives (VFD)
Cable Solutions for Servo and Variable Frequency Drives (VFD) Electric drive systems with continuous torque and speed control are widespread today. They allow an optimal adjustment of the drive with respect
More information5SV Residual Current Protective Devices
s Siemens AG 2013 SENTRON 5SV Residual Current Protective Devices New portfolio for reliable personnel, material and fire protection Safe protection against residual currents Residual current protective
More informationHigh-Voltage Insulated DC/DC Power Supply ISO3116I for gate drivers for 4.5kV and 6.5kV IGBTs
High-Voltage Insulated DC/DC Power Supply ISO3116I for gate drivers for 4.5kV and 6.5kV IGBTs The ISO3116I is a single-channel insulated DC/DC converter suitable as a power supply for IGBT drivers up to
More informationI-PEX MHF4 Micro Coaxial Connector
PRODUCT SPECIFICATION I-PEX MHF4 Micro Coaxial Connector Plug P/N 20448-001R-81 Receptacle P/N 20449-001E RF Connector, RF Cable & Antenna Manufacturer E-mail: sales@wellshow.com.tw Tel: +886-2-24239376
More informationMV, HV AND EHV SWITCHGEAR TESTING & COMMISSIONING
Training Title MV, HV AND EHV SWITCHGEAR TESTING & COMMISSIONING Training Duration 5 days Training Date MV, HV and EHV Switchgear Testing & Commissioning 5 20 24 Apr $3,750 Dubai, UAE In any of the 5 star
More informationPreset Counter signo 721
Most simple handling Impressive, clearly readable display in 48x48 mm Input frequency up to 60 khz Easy installation due to pluggable terminals TECHNICAL DATA GENERAL Display Height of digits Supply voltage
More informationHigh-Voltage GIS yesterday - today - tomorrow
High-Voltage GIS yesterday - today - tomorrow Peter Glaubitz, Siemens AG, Principal Expert GIS-Technology siemens.at/future-of-energy Table of content GIS yesterday beginning and establishment of Gas-
More information48 SERIES Relay interface modules 10 A
48 Relay interface modules 10 A 1 CO relay interface modules, mm wide Ideal interface for PLC and electronic systems Type 48.P3 1 CO 10 A s Type 48.31 1 CO 10 A s AC coils or DC sensitive coils Supply
More informationUser's Guide. True RMS Industrial Multimeter
User's Guide 97650 True RMS Industrial Multimeter Ω C ã F ã 10A V µ 10A V ã ã ma A Introduction This meter measures AC/DC Voltage, AC/DC Current, Resistance, Capacitance, Frequency (electrical & electronic),
More information6 ELECTRICAL PARAMETERS
6 ELECTRICAL PARAMETERS For power, low voltage and medium voltage cables, cross section nominal areas are calculated in taking into account several parameters as: permissible current carrying capacities
More informationTechnical Description. Transistor D.C. Chopper Controller Type GS 24 S
Technical Description Transistor D.C. Chopper Controller Type GS 24 S Table of contents 1. Getting started guide 2. General information 2.1. Characteristics 2.2. Accessories 3. Information about the Machine
More informationSTRATO LED Drivers 70W, Single output
Features STRATO switch mode driver technology is designed to generate one constant current output from a wide range AC input. The size and performance of these products make them the ideal choice for LED
More information1587/1577. Insulation Multimeters. Technical Data. Two powerful tools in one.
1587/1577 Insulation Multimeters Technical Data Two powerful tools in one. The Fluke 1587 and 1577 Insulation Multimeters combine a digital insulation tester with a full-featured, true-rms digital multimeter
More informationOrdering Information. Cylindrical Proximity Sensor E2E/E2E2
Cylindrical Sensor E2E/E2E2 A New Series of Easy-to-use and Tough E2E/E2E2 Models Long-size E2E2 Sensor Conforms to CENELEC Ideal for a variety of applications. With a metal connector that can be tightened
More informationPower Meter Series 700
PowerLogic power-monitoring units Power Meter Series 700 Technical data sheet 2007 Functions and characteristics E90463 The PowerLogic Power Meter Series 700 offers all the measurement capabilities required
More informationMIT510/2, MIT520/2 and MIT1020/2
99 Washington Street Melrose, MA 02176 Phone 781-665-1400 Toll Free 1-800-517-8431 Visit us at www.testequipmentdepot.com MIT510/2, MIT520/2 and MIT1020/2 Line supply or battery operated Digital/analog
More informationDS 600. A contact free flux gate based current measurement sensor 600A rms
DS 600 A contact free flux gate based current measurement sensor 600A rms DS 600 is member of the small housing sensor family. The family includes a 200A and a 600A version. 600A rms - 900A peak Maximum
More information80 Series - Modular timers 16 A. Features 80.01 80.11
80 Series - Modular timers 16 A Features 80.11 Multi-function and mono-function timer range - Multi-function & multi-voltage 80.11 - On-delay, multi-voltage 17.5 mm wide Six time scales from 0.1s to 24h
More informationPOWER SYSTEM CONSULTANTS POWER-LINKER
GROUP POWER SYSTEM CONSULTANTS POWER-LINKER REFERENCE LIST : VERY LOW FREQUENCY (VLF) Given below is a list of Very Low Frequency (VLF) job executed by us: SR. 40.0 Cairn India Ltd., MPT Barmer Cable 6.6
More information49 Series - Relay interface modules 8-10 - 16 A. Features
Features 1 & 2 Pole relay interface modules 5 µm Gold plate contacts for low level switching capability 49.31-50x0-1 Pole 10 A (screw terminal) 49.52-50x0-2 Pole 8 A (screw terminal) 49.72-50x0-2 Pole
More information