1 Assessment of Arc Flash Detection System in Distribution Network Imran bin Hussin College of Engineering, Universiti Tenaga Nasional, Malaysia. Dr Au Mau Teng College of Engineering, Universiti Tenaga Nasional, Malaysia. Abstract The consequences from an arc flash hazard is very severe. As the temperature of an arc can reach four times the temperature of the Sun s surface and occurs very fast, one can get skin burn up to four degree and damaged inner abdominal, permanent blind, hearing impairment and other physical injuries. Arc flash inside breaker compartment can cause breaker explosive blast and destroy costly equipment. To mitigate arc flash hazard is to reduce the fault clearing time. The longer the arc fault is in the system, the more damage would take place, while the damage could be insignificant for a very fast fault clearing time. This paper is intended to utilize IEC61850 communication protocol in current arc protection relaying in which the protocol can run over TCP/IP networks or substation LANs using high speed switched Ethernet to obtain response times below four milliseconds. Unshielded fiber optic connected to a relay at outgoing panel is used to detect arc flash in the busbar, cable and breaker compartments. Trip signal issued from the relay will be transferred to a relay at incomer panel using IEC61850 which will trip its breaker and isolate the whole busbar from the fault. This method reduces transfer tripping time as compared to conventional hard wire method and minimize the material damage, increases operating personnel safety and ensure smooth power restoration. The concept of having built-in arc protection in Over Current Earth Fault (OCEF) relay gives economic value to customer where one relay can serve two functions at one time. Keywords Arc Flash Hazard, Mitigation of Arc Flash Hazard, Arc Flash Relaying, IEC61850 I. INTRODUCTION Consequences of an arcing short circuit or earth fault within a low or medium voltage switchgear can be very serious. An arc can destroy costly equipment, and cause prolonged and expensive downtime. Copper vapor expands to 67,000 times the volume of solid copper producing a considerable pressure wave and sound blast. In some cases, the pressure wave has sufficient energy to snap the heads of 3/8-inch steel bolts and to knock over construction walls [1]. A typical arc flash incident can be inconsequential but could conceivably easily produce a more severe explosion. During the arc flash, electrical energy vaporizes the metal, which changes from solid state to gas vapor, expanding it with explosive force [2]. In addition to the explosive blast, called the arc blast of such a fault, destruction also arises from the intense radiant heat produced by the arc. Surfaces of nearby objects, including people, absorb this energy and are instantly heated to vaporizing temperatures. The effects of this can be seen on adjacent walls and equipment - they are often ablated and eroded from the radiant effects [3]. To the switchgear operators and even bystanders, arc flash can cause the following injuries; firstly skin burns by direct heat exposure. Temperatures at the arc can reach four times the temperature of the Sun's surface. Secondly, the intense UV, visible, and IR light produced by the arc can temporarily and sometimes even permanently blind or cause eye damage to people [4]. II. CAUSES OF ARC Accidents caused by touching a test probe to the wrong surface or slipped tool are the most common cause of an arcing fault [5]. Arc fault can also be caused by sparks due to breakdown or gaps in insulation materials, mal-operation of a switchgear device due to use of substandard parts, improper (loose) busbar or cable joints installation, objects coming into close proximity with the energized bus assembly, overvoltage, corrosion, pollution, moisture, Ferro-resonance and even ageing under electrical stress. Besides that, dirt, dust, grease, corrosion, gas, fluid and other impurities coming into the equipment could also result in an arc short-circuit between one live part and ground or between live parts. Most of these fault reasons can be prevented by appropriate maintenance. But in spite of all precautions, human errors by personnel can also lead to arc faults such as poor service maintenance of switchgear, bridging by tools in the switchgear and forgotten tools inside the compartment. Holes or gaps presence on the panel can be the access for small animal like lizard, rat or even snake to entering the switchgear panel and cause arc flash. Besides that, poor connection inside the switchgear panel could contribute to arc fault, for instance loose connection. Figure 1 shows thermal imaging test conducted towards the switchgear assembly where the hotspot shows the loose connection which prone to cause arc flash. 90

2 avoid hazard area, increase the working distance, usage of arcresistant switchgear as well as current-limiting fuse. While the later approach would aim to reduce the clearing time of arc; in which 5 methods are identified; to reduce Co-ordination Interval (CI) of existing overcurrent (OC) relay, application of high-impedance bus diff protection scheme, or low-impedance bus differential protection, fast bus trip scheme, instantaneous trip element (during maintenance) and arc flash detection. Fig. 1. Thermal imaging of loosed connection on switchgear III. MITIGATION OF ARC FLASH HAZARDS The electrical equation for energy is volts multiplied by current and time. The transition from arc fault to arc flash takes a finite time, increasing in intensity as the pressure wave develops. Therefore, time is critical when it comes to detecting and minimizing the effects of an arc. An arc fault lasting 500ms may cause severe damage to the installation. If the arc lasts less than 100ms the damage is often smaller, but if the arc is eliminated in less than 35ms the damage is almost unnoticed. An arc is developed within a millisecond. Figure 2 shows released energy from an arc (ka 2 s) and it s proportional arc fault time (ms). Fig. 2. Damage from arc flash vs arcing current and time The basic foundation to mitigate are flash is from the incident energy equation where three most obvious mitigating strategies can be taken into consideration; to reduce the fault current (I f), to increase the working distance (D) and to reduce the clearing time (t). In order to achieve these three strategies, there are basically two approaches namely non-relaying or relaying. For the former approach, there are four methods which can be used; A. Non-Relaying Approaches There are four approaches to mitigate arc flash under nonrelaying; to avoid hazard area, increasing the work distance, use of arc resistant switchgear and current limiting use. Avoiding hazard area is the safest way to mitigate the arc flash incident. It can be performed on de-energized equipment. Technology is used to gather information and the operation can be performed without entering the hazard area. Thus, relay event reports can be gathered without exposure to arc flash. Additionally, the Circuit Breaker mechanism would also need to be remote controlled. Disadvantage is this method cannot be applied on energized equipment. Besides that, increasing the working distance has a dramatic effect on the incident energy. Examples of this strategy include remote racking devices, remote operating devices, and the use of extension tools (i.e. hot sticks). However, many tasks may not be able to be accomplished remotely and remote racking devices may not operate as desired. Alternatively, arc-resistant switchgear can be used but it requires designs and construction of current electrical switchgear to be modified in order to withstand blast of arc flash including reinforcement of door and structure, discharge path for blast pressure and material away from personnel working areas and high speed clearing times. However, this type of switchgear does not extinguish arc, plus, it is not designed to preserve the operational condition of the equipment but only to protect operating personnel located outside of the equipment [6]. Last but not least is current limiting fuse which is capable of both limiting the magnitude of fault current and duration provided the fault current is within their current limiting range (typically times the device rating) [7]. Fault currents below this range must be analyzed like non-current limiting. This is because lower level arcing currents can easily result in higher incident energy because the clearing time maybe longer. Current limiting fuse is normally installed in LV system with high speed Circuit Breaker feature, giving fast clearing times which can then reduce incident energy. This would prompt it to operate rapidly that current never reaches it s bolted short-circuit level. B. Relaying Approaches Meanwhile, there are five approaches which can be considered under relaying approach; firstly is to reduce co-ordination interval (CI) of existing over (OC) relay. The principle of this method is that if CI is more than 3s, the tripping time will be reduced. CI is less than 3s is not recommended. If distance between co-ordination devices is low, the T will continue to 91

3 add i.e. highest fault current and longest tripping time yielding towards source (personal working). Secondly is high impedance bus differential protection. The conventional MV protection schemes have traditionally been complemented by implementing busbar differential schemes. The advantages of this scheme are it is fast and secure. Voltage across the internal impedance measured is approximately However, the differential scheme implementations are typically expensive due to extra CT's needed and complicated engineering and wiring. Thirdly is low impedance bus differential protection which is also fast and secure, plus it does not require dedicated CTs like High Impedance Bus Differential Protection scheme. However, there are disadvantages of this low impedance scheme where the relay settings are more complex as each input has independent CT ratio and connection. Furthermore, similar like high impedance busbar differential, this scheme may also be too slow due to its relaying arrangements to ensure safe fault clearance times at arc faults, for instance, operation time of the overcurrent relay controlling the incoming CB may have to be delayed hundreds of milliseconds for selectivity reasons. Fourthly is fast bus trip scheme (use OC + communications). This scheme use existing over current relay with additional communications installed on it. Feeder relays and main relay communicate to signal fault location. Relay co-ordination can be maintained without long time delays. If a fault occurs on feeder, the feeder relay will send a block signal to main relay. It is such a short time delay to look for a block signal. If there is no block signal received, the main Circuit Breaker will trip and the fault will be cleared. Lastly is instantaneous trip element which can be done during maintenance. This is the best and simple solution where instantaneous setting is used within hazard zone. Workers presence indicated with a pushbutton on relay in a form of separate switch, or remote communications. While activated (when workers are in proximity of energized circuits), the change in setting will disable the time co-ordination and will allow Circuit Breaker (CB) to trip without delay. This scheme can be added to new/old installations without adding much expenses. However, this method is limited to maintenance works only [8] IV. ARC FLASH PROTECTION RELAY EVOLUTION Arc flash protection relay is now being revolutionized over the years to improvise its functionality in detecting or clearing arc fault as it has been proven that arc flash protection relaying gives the best solution to mitigate are flash problem over all other solutions. A. Proposed Enhancement of Arc Protection Scheme Using Several IEDs Figure 3 shows overall scheme proposed which utilizes several Over Current Earth Fault (OCEF) relays with built-in arc protection function that send signals to communicate between the relays via IEC61850 communication protocol. Fig. 3. Proposed Arc Protection Scheme One OCEF relay is installed on every outgoing feeder to cover the arc flash protection on that particular panel. Light sensor 1, light sensor 2 and light sensor 3 on the relay channel a fibre optics and a point sensor to locate on every compartment of the panel; cable compartment, breaker compartment and busbar compartment. In addition, a fast tripping output contact is used by the OCEF relay for tripping of the circuit breaker. The OCEF relay protecting the outgoing feeder trips the circuit breaker of the outgoing feeder when detecting an arc at the cable terminations. If the relay protecting the outgoing feeder detects an arc on the busbar or in the breaker compartment via one of the other lens sensors, it will generate a signal to the OCEF relay protecting the incoming feeder using IEC61850 protocol. Upon detecting the signal, the OCEF relay at the incoming feeder trips the circuit breaker of the incoming feeder and simultaneously generates an external trip signal via IEC61850 protocol to all OCEF relays protecting the outgoing feeders, which in turn results in tripping of all circuit breakers of the outgoing feeders. B. Software Configurations PCM600 software is used to configure the arc protection scheme. Step 1: Do IEC61850 configuration for one REM615 relay at outgoing panel as SENDER. Dataset needs to be created where the destination of the signal can be selected to receive the signal established by the relay. In GOOSE controls window, the destination REF615 relay on the incomer panel needs to be selected. There is nothing to be configured in the inputs window as this is sending relay, not receiving. 92

4 At the same time, this relay can also cater for over current and earth fault protection where PHLPTOC1 and PHIPTOC1 function blocks are used to detect over current fault while DEFLPDEF1 and EFHPTOC1 function blocks are used to detect earth fault. So this REM615 relay basically gives two protection at one time i.e. over current and earth fault function as well as arc fault function; giving economic value to the protection relay used at substation. Step 2: Do IEC61850 configuration for one REF615 relay at outgoing panel as RECEIVER. There is no configuration needs to be done on datasets and GOOSE control windows as this is receiving relay, not sending. Inputs window needs to be configured as this will receive the signals (datasets) transferred from the REM615 relay on the outgoing panel. For this case, the datasets have been automatically appear on the Inputs window of REF615 relay on incomer panel when the datasets are defined in datasets and GOOSE Controls window of the REM615 relay on outgoing panel. Similar to REM615 on the outgoing panel, this REF615 relay is also used cater for over current and earth fault protection, so PHxPTOC function blocks are used to detect over current fault while EFxPTOC function blocks are used to detect earth fault. Step 3: Define arc function block for logic configuration. The idea for REM615 relay on the outgoing panel is to detect any arc fault occur on its dedicated busbar compartment, cable compartment or breaker compartment, upon which it will trip its built-in master trip, TRPPTRC, then this tripping signal will be transferred to the REF615 relay at the incomer panel. To detect arc fault, a function block named ARCSARC is used in the logic of the REM615 relay (SENDER) to receive any arc fault input from the relay terminal upon detecting light from an arc by the lens sensors. Step 4: Define logic for REF615 as RECEIVER. For REF615 relay at the incomer panel, it will receive the signal of arc fault trip from REM615 relay on the outgoing panel. The idea is to trip the breaker on the incomer so as to isolate the electricity supply to the whole busbar should the arc fault occur on the busbar compartment. Other than receiving the arc fault trip signal from REM615 relay of the outgoing panel and OCEF function, the REF615 relay also detects arc fault on its busbar compartment, cable compartment and breaker compartment. The same configuration of arc fault function block, ARCSARC is used where upon detecting the arc fault by the lens sensor, the output of the ARCSARC function block will trigger the builtin master trip, TRPPTRC which will operate the relay output contact to trip the breaker of the incomer panel. Step 5: Completion of arc protection scheme test. As the communication protocol used is IEC61850, GOOSERV_BIN function block is used in the application configuration of the REF615 relay (RECEIVER) to receive the incoming GOOSE data (trip signal) from the REM615 relay (SENDER) on the outgoing panel to its application. There are two outputs on the GOOSERV_BIN function block; OUT and VALID. The VALID output indicates the validity of received GOOSE data, which means in case of valid, that the GOOSE communication is working and received data quality bits (if configured) indicate good process data. Invalid status is caused either by bad data quality bits or GOOSE communication failure. While the OUT output passes the received GOOSE value for the application. While the OUT output of the GOOSERCV_BIN function block is used to trigger the built-in master trip, TRPPTRC of the relay which will operate its assigned output contact to trip the breaker of the incomer panel. The output contact will reset automatically once the fault is cleared (non-latched). Step 6: The last step in the configuration is to map the GOOSE signals from REM615 relay on the outgoing panel to GOOSE receive function blocks of the REF615 relay on the incomer panel. This can be done via Signal Matrix Tools in the REF615 relay of incomer panel Step 7: Write configurations to both relays. C. Testing the Arc Protection Scheme Place one REM615 relay for outgoing panel and one REF615 relay for incomer panel. Connect a LAN cable between the two relays for IEC61850 communication medium transfer. Apply a bright light source near the light sensor of the REM615 relay. When the light intensity and current level exceeds the setting set in the relay, this will trigger the ARCSARC function block in the relay, operate the built-in master trip, TRPPTRC and the trip signal will be transferred to the REF615 relay via the IEC61850 communication. Upon receiving this trip signal, the REF615 relay will trip i.e. output contact will operate and this will trip the breaker of the incomer panel. The events should be recorded in the event record inside the relay to retrieve the signals and light channels so as to analyze and qualify the response. Fig. 4. Connection to test arc flash on REM615 and REF615 relay Arc Fault Transfer Using IEC61850 Communication Protocol Arc fault is simulated by projecting camera flashlight to the arc sensor terminal on the rear part of the REM615 relay at outgoing panel. The REM615 relay trips and instantaneously trips the REF615 relay at incomer panel. Tripping of each relay is shown on the LCD display on the relay front HMI. Disturbance recorder is extracted from the relay into the PCM600 software to get the tripping time for each relay so 93

5 that the transfer time (IEC61850) from the outgoing panel to the incomer panel can be calculated. The tripping time of REM615 relay upon detecting arc flash fault on the busbar is recorded as 10:00: hrs while the tripping time of REF615 relay at incoming panel after receiving busbar arc fault trip signal from REM615 relay at outgoing panel is recorded as 10:00: hrs. Transfer time is achieved by calculating the difference between the tripping time of REM615 and of REF615 relay i.e. ( ) s = 0.295s. Time error of 0.102s calculated previously from item 4.1 is subtracted from this value to get the actual transfer time i.e 0.295s 0.102s = 0.193s Arc Fault Transfer Using Hard Wire In this application, the arc fault data is being transferred using hardwire which is connected from binary output of REM615 relay (programmed as Trip CB ) to the binary input of the REF615 relay (assigned as External Trip ). When the REM615 relay has tripped on arc fault, the binary output will simultaneously trip i.e. its Normally Open (NO) contact will close. This will convey the standby positive supply on the binary output to trigger the binary input of the REF615 relay. When the binary input of the REF615 relay has been triggered, the signal will be processed in the microprocessor inside the relay and will give output to trip the relay and trip its respective circuit breaker which finally isolate the system from the arc fault. Arc fault is simulated and the tripping time of both relays shown on the LCD display is taken. Similar to the IEC61850 application, the disturbance recorder for this hard wire test is extracted from the relay into the PCM600 software to get the tripping time for each relay so that the transfer time (hard wire) from the outgoing panel to the incomer panel can be calculated. The tripping time of REM615 relay upon detecting arc flash fault on the busbar is recorded as 9:49: hrs while the tripping time of REF615 relay at incoming panel after receiving busbar arc fault trip signal from REM615 relay at outgoing panel is recorded as 9:49: hrs. Transfer time is achieved by calculating the difference between the tripping time of REM615 and of REF615 relay i.e. ( ) s = 0.404s. Time error of 0.102s calculated previously from item 4.1 is subtracted from this value to get the actual transfer time i.e 0.404s 0.102s = 0.302s Table 1 shows the summary of calculation for the transfer time on both IEC61850 and hard wire application. TABLE 1: SUMMARY OF TRANSFER TIME Relay REM615 (outgoing) Busbar Arc Fault Trip REF615 (incoming) Busbar Arc Fault Trip Test Results (IEC61850) Test Results (hard wire) 10:00: hrs 9:49: hrs 10:00: hrs 9:49: hrs Transfer time 0.295s 0.404s minus time error (0.102s) (-) 0.102s (-) 0.102s Actual transfer time 0.193s 0.302s V. DISCUSSION AND CONCLUSION From the table 1, it can be seen that transfer time from outgoing panel (REM615 relay) to the incoming panel (REF615 relay) using IEC61850 as means of transfer is faster than that using hard wire i.e 0.193s for IEC61850 as compared to 0.302s for hard wire. This proves that IEC61850 communication protocol can give faster transfer time. Subsequently, faster time for the relay at incomer panel to trip its circuit breaker can be achieved in order to isolate the busbar from the arc fault. This is proven to be the fastest way to clear arc fault from the system. Aligned with figure 2, the faster the clearing time the better where damage on the switchgear installation and injury to the operating personnel is reduced to the minimum. The use of IEC61850 communication protocol has benefited a lot to the advancement of arc protection system where the arc fault clearing time has been reduced tremendously. The very fast arc fault clearing time would yield to almost nothing to the affected area, returning back the system to the normal operation without causing any cost of repair. At the end, a good technology does not only prevent arc flash to occur, but it also minimizes material damage, increases operating personnel safety and allows smooth power restoration. Besides that, it also enables redundant, instantaneous and fail-safe arc fault protection fully utilizing fiber-optic technology and flexible, fast overcurrent monitoring for secure protection. This technology will promote quick reaction and cost-effective installation. VI. RECOMMENDATION FOR FUTURE WORK Fiber optic used to detect arc fault along the busbar compartment, breaker compartment and cable compartment is generally very fragile and requires a lot of precaution during the installation as well as during its operation. Damage to any part of the fibre optic would fail the operation of the IEC61850; consequently the arc protection system as a whole would fail to function and the repair of the damaged fibre optic is quite troublesome as it involves the whole energized busbar at the substation. The relay has supervision to detect any mal-operation or cut along the fiber optic laying, but it cannot locate where exactly along the laying that the problem occur. This would require the whole busbar to be de-energized and the whole fiber optic is to be taken out for repair. 94

6 An alternative solution can be recommended where the usage of fiber optic is eliminated. The detection of arc fault is still done by a sensor located at the desired place in the switchgear compartment but the data transferred from the sensor to the arc fault protection relay will be done by using wireless communication media such as Bluetooth etc. This would give better efficiency in terms of communication transfer and the precaution of the sensor is only on the individual panel and not on the whole busbar, easy for maintenance and troubleshooting. ACKNOWLEDGMENT This paper would not have been possible without the help and assistance of several individuals, to whom the author is undeniably indebted. First and foremost, my utmost gratitude to my beloved mother and wife whom their strong support and encouragement I will never forget. My gratitude also sincerely goes to my principal supervisor, Dr Au Mau Teng, without him this thesis would have been impossible. My thanks also goes to my colleagues, Muhamad Dusin and Phang Siew Wey who always give me a bright ideas in the discussion about the topics and who have helped me a lot in the testing of the arc protection relay at lab. And my thanks also goes to the faculty of the Department of the Electrical Engineering of Universiti Tenaga Nasional, and the staff and faculty members that assisted me through writing of this thesis. REFERENCES [1] KM Kowalski-Trakofler, EA Barrett, CW Urban, GT Homce. "Arc Flash Awareness: Information and Discussion Topics for Electrical Workers". DHHS (NIOSH) Publication No D. Accessed January 10, [2] Ken s Safety Section, NEC Digest Spring 2004; Author is Ken Mastrullo, Senior Electrical Specialist, NFPA Electrical Engineering Department. [3] [4] ARC Flash Hazard Analysis and Mitigation by J. C. Das -- IEEE Press 2012 [5] How to Hamper Hazards, IEEE Industry Applications, May/June 2005 [6] Arc Flash Hazard Analysis and Mitigation, Chris Inshaw and Robert Wilson, 2006 Texas A&M Relay Conference. [7] A Total Approach to Arc Flash Compliance, Alan C. Bast, Jeffry L. Bennett, Norman E. Reifsnyder, Richard Mages, Preston Cooper, Power-Gen International 2006 Conference. [8] ABB Buyers Guide, REA 10_ Arc Protection Relay, 1MRS MBG, May

Arc Flash Energy Mitigation Techniques

Arc Flash Energy Mitigation Techniques Arc Flash Energy Mitigation Techniques When short circuits occur on an electrical distribution system, an arc flash event usually forms. These arc flash events can cause dangerous and potentially fatal

More information

Arc Flash Hazards. Electrical Hazards. Dan Neeser Field Application Engineer DanRNeeser@Eaton.com. Electrical Hazards 2/18/2015. Shock.

Arc Flash Hazards. Electrical Hazards. Dan Neeser Field Application Engineer DanRNeeser@Eaton.com. Electrical Hazards 2/18/2015. Shock. Arc Flash Hazards Dan Neeser Field Application Engineer DanRNeeser@Eaton.com Electrical Hazards Electrical Hazards Shock Arc Flash Arc Blast 2 1 Arcing Fault Basics 35,000 F Radiant Heat & UV Speed of

More information

New standardized approach to arc flash protection

New standardized approach to arc flash protection New standardized approach to arc flash protection Samuel Dahl Juha Arvola Tero Virtala Arcteq Relays Ltd Arcteq Relays Ltd Arcteq Relays Ltd Wolffintie 36 F 11 Wolffintie 36 F 11 Wolffintie 36 F11 65200

More information

ARC FLASH CALCULATIONS & LABELING REQUIREMENTS

ARC FLASH CALCULATIONS & LABELING REQUIREMENTS ARC FLASH CALCULATIONS & LABELING REQUIREMENTS Presented by: Edmund Elizalde EYP Mission Critical Facilities, Inc. Slides by: Lonnie Lindell SKM Systems Analysis, Inc. 1 Agenda NEC 110.16 NFPA 70E IEEE

More information

Mitigation of Arc-Flash Hazards and Reduction of Costs by Selective Arc-Flash Protection

Mitigation of Arc-Flash Hazards and Reduction of Costs by Selective Arc-Flash Protection Mitigation of Arc-Flash Hazards and Reduction of Costs by Selective Arc-Flash Protection L. Kumpulainen, S. Dahl J. Ma Vamp Ltd, Finland Vamp Ltd, China 1 ABSTRACT This paper describes causes and characteristics

More information

Arc Terminator Active Arc-Resistant Switchgear

Arc Terminator Active Arc-Resistant Switchgear Arc Terminator Active Arc-Resistant Switchgear Increasing safety and productivity by extinguishing internal arcing faults within the switchgear. The Square D Arc Terminator from Schneider Electric offers

More information

Arc Flash Mitigation. Remote Racking and Switching for Arc Flash danger mitigation in distribution class switchgear.

Arc Flash Mitigation. Remote Racking and Switching for Arc Flash danger mitigation in distribution class switchgear. Arc Flash Mitigation Remote Racking and Switching for Arc Flash danger mitigation in distribution class switchgear. Distance is Safety We will discuss through examples of actual occurrences and possible

More information

NFPA 70E 2012 Rolls Out New Electrical Safety Requirements Affecting Data Centers

NFPA 70E 2012 Rolls Out New Electrical Safety Requirements Affecting Data Centers NFPA 70E 2012 Rolls Out New Electrical Safety Requirements Affecting Data Centers A market position paper from the experts in Business-Critical Continuity TM Executive Summary Electrocutions are the fourth

More information

Part 1 System Modeling & Studies for Existing Systems

Part 1 System Modeling & Studies for Existing Systems Part 1 System Modeling & Studies for Existing Systems Operation Technology, Inc. Copyright 2009 Result of rapid release of energy due to an arcing fault between two conductors. Bus voltages > 208V Temperatures

More information

Understanding Arc Flash

Understanding Arc Flash Understanding Arc Flash Presented by Eddie F. Jones, PE 1 2 3 4 5 Five to 10 arc flash explosions occur in electric equipment every day in the United States. This number does not include cases in which

More information

FFI. Advances in Medium and Low Voltage Power Distribution ESS Metron Expo and Technical Seminars. Presented By: Greg Pelster & Robert Schmid

FFI. Advances in Medium and Low Voltage Power Distribution ESS Metron Expo and Technical Seminars. Presented By: Greg Pelster & Robert Schmid Advances in Medium and Low Voltage Power Distribution ESS Metron Expo and Technical Seminars Presented By: Greg Pelster & Robert Schmid FFI Ferrie, Franzmann Industries LOW VOLTAGE SWITCHGEAR & LOW VOLTAGE

More information

The Intelligent AX1 Switchgear for Medium Voltage

The Intelligent AX1 Switchgear for Medium Voltage The Intelligent AX1 Switchgear for Medium Voltage Leif Lundin, Manager of Research and Development, Division Medium Voltage and Compact Substations, ABB Distribution, Sweden Abstract The newly launched

More information

HAZARDS, INCLUDING SHOCK, ARC FLASH AND FIRE

HAZARDS, INCLUDING SHOCK, ARC FLASH AND FIRE Appendix B-2 - Electrical Safety In Design Final Report TECHNOLOGIES THAT REDUCE LIKELIHOOD OF INJURY FROM ELECTRICAL HAZARDS, INCLUDING SHOCK, ARC FLASH AND FIRE The following are technologies that reduce

More information

2004 TRANSMISSION SYSTEMS SEMINAR MEDIUM VOLTAGE, METAL-CLAD ARC RESISTANT SWITCHGEAR: ENHANCING WORKPLACE SAFETY

2004 TRANSMISSION SYSTEMS SEMINAR MEDIUM VOLTAGE, METAL-CLAD ARC RESISTANT SWITCHGEAR: ENHANCING WORKPLACE SAFETY 2004 TRANSMISSION SYSTEMS SEMINAR MEDIUM VOLTAGE, METAL-CLAD ARC RESISTANT SWITCHGEAR: ENHANCING WORKPLACE SAFETY Thomas P. McNamara, P.E. Manager, Development Engineering ABB Inc. Power Technologies Medium

More information

How to reduce exposure to arc flash hazards

How to reduce exposure to arc flash hazards GE Energy Industrial Solutions How to reduce exposure to arc flash hazards Multiple solutions for new and existing facilities imagination at work Multiple Issues Today s power system engineer must not

More information

ELECTRICAL SAFETY RISK ASSESSMENT

ELECTRICAL SAFETY RISK ASSESSMENT ELECTRICAL SAFETY RISK ASSESSMENT The intent of this procedure is to perform a risk assessment, which includes a review of the electrical hazards, the associated foreseeable tasks, and the protective measures

More information

BRANDON AND CLARK INC. // SCOTT W. CLARK, P.E. ELECTRICAL CONTINUING EDUCATION ARC FLASH - NFPA 70E

BRANDON AND CLARK INC. // SCOTT W. CLARK, P.E. ELECTRICAL CONTINUING EDUCATION ARC FLASH - NFPA 70E BRANDON AND CLARK INC. // SCOTT W. CLARK, P.E. ELECTRICAL CONTINUING EDUCATION ARC FLASH - NFPA 70E Training is not a substitute for following corporate safety guidelines. Always refer to the latest safety

More information

Medium Voltage Products. ZN1 12 kv arc-proof air-insulated switchgear for primary distribution

Medium Voltage Products. ZN1 12 kv arc-proof air-insulated switchgear for primary distribution Medium Voltage Products ZN1 12 kv arc-proof air-insulated switchgear for primary distribution ZN1 an innovative switchgear for power distribution requirements ABB ZN1 primary distribution switchgear is

More information

UFES Active protection for switchgear

UFES Active protection for switchgear Active protection for switchgear ABB AG Oberhausener Strasse 4047 Ratingen, Germany Phone: +49 0-0 Fax: +49 0-7 77 Note: We reserve the right to make technical changes or modify the contents of this document

More information

Low Voltage Switchgear

Low Voltage Switchgear Arc Resistant Switchgear n Insulated and isolated bus n Separation barriers and top venting n Breaker shutters 12 SWITCHGEAR Arc resistant metal-enclosed low voltage switchgear is an optional product offering

More information

IEC 61850 in ZX Gas-insulated medium voltage switchgear

IEC 61850 in ZX Gas-insulated medium voltage switchgear IEC 61850 in ZX Gas-insulated medium voltage switchgear IEC 61850 in ZX Just as the supply of electrical power is becoming more and more important in a networked world, demands for the integration of electrical

More information

Automation & Power World Improving safety Through arc resistant switchgear and arc reducing components. ABB Wednesday, 23 March 2011 Slide 1

Automation & Power World Improving safety Through arc resistant switchgear and arc reducing components. ABB Wednesday, 23 March 2011 Slide 1 Automation & Power World Improving safety Through arc resistant switchgear and arc reducing components Wednesday, 23 March 2011 Slide 1 Automation & Power World 2011 April 18-21, 2011 in Orlando, Florida

More information

Safety By Design. Strategies for Electrical Contractors

Safety By Design. Strategies for Electrical Contractors Safety By Design Strategies for Electrical Contractors Introduction Engineering and system design significantly impact worker safety System design provides opportunity to eliminate/minimize workers exposure

More information

What s up with Arc Flash?

What s up with Arc Flash? What s up with Arc Flash? Presented by Mark Haskins, CSP Practical Safety Solutions, LLC CONN OSHA Breakfast Roundtable February 18, 2014 2014 Practical Safety Solutions, LLC What is Arc Flash? Definition

More information

Fault Characteristics in Electrical Equipment

Fault Characteristics in Electrical Equipment 1. Introduction Proper design and installation of electrical equipment minimizes the chance of electrical faults. Faults occur when the insulation system is compromised and current is allowed to flow through

More information

EVALUATION OF ALTERNATIVE BACKUP PROTECTION SCHEMES ON A 66KV DISTRIBUTION NETWORK

EVALUATION OF ALTERNATIVE BACKUP PROTECTION SCHEMES ON A 66KV DISTRIBUTION NETWORK EVALUATION OF ALTERNATIVE BACKUP PROTECTION SCHEMES ON A 66KV DISTRIBUTION NETWORK F. Malone*, P.D. Doyle *ESB International, Ireland fergus.malone@esbi.ie ESB International, Ireland paul.d.doyle@esbi.ie

More information

ARC FLASH HAZARD MITIGATION. Industrial Tests, Inc. [indtests.com]

ARC FLASH HAZARD MITIGATION. Industrial Tests, Inc. [indtests.com] ARC FLASH HAZARD MITIGATION ARC FLASH HAZARD MITIGATION NWHA TECHNICAL SEMINAR May 17, 2012 Richard D Reese Power Systems Manager Industrial Tests, Inc. Rocklin, California [Dick@indtests.com; 916-660-2837]

More information

PRESENTED AT THE 2011 IEEE IAS PULP & PAPER INDUSTRY TECHNICAL CONFERENCE, NASHVILLE, TN: IEEE 2011 - PERSONAL USE OF THIS MATERIAL IS PERMITTED.

PRESENTED AT THE 2011 IEEE IAS PULP & PAPER INDUSTRY TECHNICAL CONFERENCE, NASHVILLE, TN: IEEE 2011 - PERSONAL USE OF THIS MATERIAL IS PERMITTED. Arc Flash Energy Reduction Techniques Zone Selective Interlocking & Energy-Reducing Maintenance Switching Christopher G. Walker Senior Member, IEEE Eaton Corporation Moon Township, PA 15108 chrisgwalker@eaton.com

More information

Demystifying arc flash hazard management

Demystifying arc flash hazard management Demystifying arc flash hazard management Presented by Matt Brazier Senior Electrical Engineer Gove Operations November 2013 Standard NFPA 70E IEEE 1584 AS/NZS 4836 TERMINOLOGY Arc arc flash hazard analysis

More information

Siemens tiastar TM Motor Control Center (MCC) Siemens 2011. All rights reserved.

Siemens tiastar TM Motor Control Center (MCC) Siemens 2011. All rights reserved. Siemens tiastar TM Motor Control Center (MCC) Siemens 2011. All rights reserved. tiastar Arc Resistant MCCs UL Validated Testing of Arc-Resistant Motor Control Centers page 2 tiastar Arc Resistant MCCs

More information

What Are the Qualifications to Conduct Arc Flash Studies? Where Do You Begin?

What Are the Qualifications to Conduct Arc Flash Studies? Where Do You Begin? What Are the Qualifications to Conduct Arc Flash Studies? Where Do You Begin? Comparing apples-to-apples bids Plant Services Special Report A shock hazard analysis should be included as part of an arc

More information

UL Validated Testing of Arc-Resistant Motor Control Centers

UL Validated Testing of Arc-Resistant Motor Control Centers UL Validated Testing of Arc-Resistant Motor Control Centers Ensure Protective Features Perform as Designed Larry Sifers Account Manager Littleton, CO Siemens Industry June 1st - 3rd, 2011 Western Mining

More information

ALTERNATIVE METHODS FOR INTERNAL ARC TESTS ON 12 KV AND 24 KV METAL-ENCLOSED SWITCHGEARS WITH COMPACT RMU

ALTERNATIVE METHODS FOR INTERNAL ARC TESTS ON 12 KV AND 24 KV METAL-ENCLOSED SWITCHGEARS WITH COMPACT RMU ALTERNATIVE METHODS FOR INTERNAL ARC TESTS ON 12 KV AND 24 KV METAL-ENCLOSED SWITCHGEARS WITH COMPACT RMU George CURCANU, Constantin ILINCA, Ilie SBORA ICMET Craiova, Romania, Calea Bucuresti 144, phone:

More information

Relion. Power system protection and automation reference Extending substation life cycle with IEC 61850

Relion. Power system protection and automation reference Extending substation life cycle with IEC 61850 Relion Power system protection and automation reference Extending substation life cycle with IEC 61850 Extending substation life cycle with IEC 61850 A step-by-step power system retrofit approach for optimizing

More information

Choosing the Best Solution for Reducing Arc Energy

Choosing the Best Solution for Reducing Arc Energy CONVENTION SESSION HANDOUT Choosing the Best Solution for Reducing Arc Energy Terry L. Schiazza, Business Development Manager Square D / Schneider Electric SESSION #11 Independent Electrical Contractors

More information

TRACTION NETWORK MONITORING AND PROTECTION SYSTEM SMTN-3 CITY ELECTRIC TRANSPORT RAILWAYS METRO INDUSTRY

TRACTION NETWORK MONITORING AND PROTECTION SYSTEM SMTN-3 CITY ELECTRIC TRANSPORT RAILWAYS METRO INDUSTRY TRACTION NETWORK MONITORING AND PROTECTION SYSTEM SMTN-3 CITY ELECTRIC TRANSPORT RAILWAYS METRO INDUSTRY 2 TRACTION NETWORK MONITORING AND PROTECTION SYSTEM Traction network monitoring and protection system,

More information

Protection Considerations to Mitigate Arc-Flash Hazards

Protection Considerations to Mitigate Arc-Flash Hazards 1 Protection Considerations to Mitigate Arc-Flash Hazards echnical Report to the Substation Subcommittee of the Power Systems Relaying Committee Working Group: Chair: K. Zimmerman, Vice Chair: R.A. Hedding,

More information

Catalog. Arc Guard System TM TVOC-2

Catalog. Arc Guard System TM TVOC-2 Catalog Arc Guard System TM TVOC-2 Introduction An even better Arc Guard System TVOC-2, ABB s latest Arc Monitor, builds on the well known TVOC design. Its new functions and features improve an already

More information

ISIO 200. Binary Input/Output (I/O) Terminal with IEC 61850 Interface

ISIO 200. Binary Input/Output (I/O) Terminal with IEC 61850 Interface ISIO 200 Binary Input/Output (I/O) Terminal with IEC 61850 Interface Compact and Easy ISIO 200 Put your Binary I/Os where you need them ISIO 200 is a simple and versatile binary I/O terminal with IEC 61850

More information

OPTIMIZING POWER SYSTEM PROTECTION FOR MODERN DATA CENTERS

OPTIMIZING POWER SYSTEM PROTECTION FOR MODERN DATA CENTERS OPTIMIZING POWER SYSTEM PROTECTION FOR MODERN DATA CENTERS Data center power systems are constructed with a premium on reliability at a significant cost. The return on this investment is realized if it

More information

2008 Eaton Corporation. All rights reserved.

2008 Eaton Corporation. All rights reserved. FlashGard TM Motor Control Center Electrical Safety Hazards Design Philosophy The Product 2008 Eaton Corporation. All rights reserved. Research studies say. Five to 10 arc flash explosions occur in electrical

More information

3053 Electrical Safety Training Program Course Outline

3053 Electrical Safety Training Program Course Outline 3053 Electrical Safety Training Program Course Outline The following outline summarizes the major points of information presented in the program. The outline can be used to review the program before conducting

More information

Power-Zone 4 Arc Resistant Low Voltage Switchgear

Power-Zone 4 Arc Resistant Low Voltage Switchgear Power-Zone 4 Arc Resistant Low Voltage Switchgear with ArcBlok Technology Make the most of your energy SM Workplace safety 2 I Power-Zone 4 Arc Resistant Low Voltage Switchgear Five to ten arc flash explosions

More information

A USERS GUIDE TO ARC RESISTANT LOW VOLTAGE SWITCHGEAR & MOTOR CONTROL ANALYTICAL COMPARISON VS ARC FLASH TEST RESULTS

A USERS GUIDE TO ARC RESISTANT LOW VOLTAGE SWITCHGEAR & MOTOR CONTROL ANALYTICAL COMPARISON VS ARC FLASH TEST RESULTS A USERS GUIDE TO ARC RESISTANT LOW VOLTAGE SWITCHGEAR & MOTOR CONTROL ANALYTICAL COMPARISON VS ARC FLASH TEST RESULTS By: Gabriel Arce, ABB, San Luis Potosi, Mexico Casey McCollum, ABB, Houston, TX John

More information

Enhancing Personnel Safety with Arc Resistant Equipment

Enhancing Personnel Safety with Arc Resistant Equipment Enhancing Personnel Safety with Arc Resistant Equipment Carl Christian Power LV Offer Marketing Nashville, TN Sponsored by the Water Wastewater Competency Center 1 Enhancing Personnel Safety 5-10 Five

More information

Secure your electrical network. PACiS The Safety Solution for Healthcare Institutions

Secure your electrical network. PACiS The Safety Solution for Healthcare Institutions Secure your electrical network The Safety Solution for Healthcare Institutions Fast Secure : the solution for fault isolation and electrical network restoration in less than 500 ms 03 A Real Time System

More information

ECE 586b Course Project Report. Auto-Reclosing

ECE 586b Course Project Report. Auto-Reclosing ECE 586b Course Project Report Auto-Reclosing Srichand Injeti May 5, 2008 Department Of Electrical and computer Engineering University Of Western Ontario, London Ontario Table of contents 1. Introduction...1

More information

Arc Flash Mitigation & Selective Co-ordination

Arc Flash Mitigation & Selective Co-ordination Arc Flash Mitigation & Selective Co-ordination Michael Hodder March 2015 Overview This seminar will provide information on: Mitigating arc flash hazards Selective Coordination What can we do to make these

More information

NATUS NES / NES-H Draw-out Type Medium Voltage Switchgear Systems. Safe energy distribution that meets the highest industrial requirements

NATUS NES / NES-H Draw-out Type Medium Voltage Switchgear Systems. Safe energy distribution that meets the highest industrial requirements NATUS NES / NES-H Draw-out Type Medium Voltage Switchgear Systems Safe energy distribution that meets the highest industrial requirements NATUS switchgear systems your advantages minimal use of insulant

More information

The Application of Circuit Breakers to Reduce Downtime in Datacentres

The Application of Circuit Breakers to Reduce Downtime in Datacentres The Application of Circuit Breakers to Reduce Downtime in Datacentres Tim Campbell BEng MIET. Marketing Manager, Terasaki Electric (Europe) Ltd. Abstract Circuit breakers fulfil several functions in the

More information

A Comparison of Contemporary Electrical Distribution Equipment Standards. San Francisco IEEE Industry Applications Society May 26, 2009

A Comparison of Contemporary Electrical Distribution Equipment Standards. San Francisco IEEE Industry Applications Society May 26, 2009 A Comparison of Contemporary Electrical Distribution Equipment Standards San Francisco IEEE Industry Applications Society May 26, 2009 What are Standards? Clearly defined performance characteristics Based

More information

What are the basic electrical safety issues and remedies in solar photovoltaic installations?

What are the basic electrical safety issues and remedies in solar photovoltaic installations? What are the basic electrical safety issues and remedies in solar photovoltaic installations? Presented by: Behzad Eghtesady City of Los Angeles Department of Building and Safety Topics Covered Photovoltaic

More information

Relion. Power system protection and automation reference Fast substation busbar protection with IEC 61850 and GOOSE

Relion. Power system protection and automation reference Fast substation busbar protection with IEC 61850 and GOOSE Relion Power system protection and automation reference Fast substation busbar protection with IEC 61850 and GOOSE Fast substation busbar protection with IEC 61850 and GOOSE Falu Elnät AB applies new power

More information

OSHA and NFPA 70 Understanding NFPA 70 and its Implications in Electrical Inspections 2010

OSHA and NFPA 70 Understanding NFPA 70 and its Implications in Electrical Inspections 2010 OSHA and NFPA 70 Understanding NFPA 70 and its Implications in Electrical Inspections 2010 By: Martin Robinson, Level III Thermographer 18-1030-0005 Rev. A The National Fire Protection Association (NFPA)

More information

Nothing s BetterThan the Original MODAN Power Distribution Systems

Nothing s BetterThan the Original MODAN Power Distribution Systems MODAN www.eaton.com Nothing s BetterThan the Original MODAN Power Distribution Systems Modan Modular switchboard system Controlling and Distributing Power Safely Thinking further. Questioning the well-established

More information

Arc Flash Avoidance and its Application to Overhead Traveling Cranes

Arc Flash Avoidance and its Application to Overhead Traveling Cranes Arc Flash Avoidance and its Application to Overhead Traveling Cranes Whitepaper August 2012 Jason Wellnitz, Controls Product Manager Material Handling Numerous technical papers, bulletins, magazine articles

More information

MV, HV AND EHV SWITCHGEAR TESTING & COMMISSIONING

MV, HV AND EHV SWITCHGEAR TESTING & COMMISSIONING Training Title MV, HV AND EHV SWITCHGEAR TESTING & COMMISSIONING Training Duration 5 days Training Date MV, HV and EHV Switchgear Testing & Commissioning 5 20 24 Apr $3,750 Dubai, UAE In any of the 5 star

More information

NELSON VOLTAGE MONITOR INSTALLATION & PROGRAMMING MANUAL

NELSON VOLTAGE MONITOR INSTALLATION & PROGRAMMING MANUAL NELSON VOLTAGE MONITOR INSTALLATION & PROGRAMMING MANUAL CONTENTS GENERAL INFORMATION...3 INSTALLATION...3 FIELD WIRING...4 PROGRAMMING...4 Circuit Monitor Options...5 Power Frequency...5 Alarm Silence

More information

MEDIUM VOLTAGE CE-BF SWITCHBOARDS. UP TO 40.5 kv. CE - BF - C - en - REV.00 2012.4

MEDIUM VOLTAGE CE-BF SWITCHBOARDS. UP TO 40.5 kv. CE - BF - C - en - REV.00 2012.4 CE - BF - C - en - REV.00 2012.4 APPLICATION CE-BF Switchbords up to 40.5 kv are designed for use in public and industrial distribution system up to 40,5KV for the operation and protection of lines, transformers,

More information

Arc Flash Safety in 400V Data Centers

Arc Flash Safety in 400V Data Centers Arc Flash Safety in 400V Data Centers Strategies for protecting employees from underappreciated yet potentially deadly hazards By Dave G. Loucks PCM Solution Manager Eaton Corporation Executive summary

More information

1SFC170011M0201 EN, Rev C. Arc Guard System, TVOC-2 Installation and maintenance guide

1SFC170011M0201 EN, Rev C. Arc Guard System, TVOC-2 Installation and maintenance guide EN, Rev C Arc Guard System, TVOC-2 Installation and maintenance guide Original instruction This is the Installation and maintenance guide for Arc Guard System Type TVOC-2. Document number: Revision: B

More information

Electrical Predictive and Preventative Maintenance

Electrical Predictive and Preventative Maintenance Electrical Predictive and Preventative Maintenance Electrical and mechanical equipment is subject to failure at the worst possible time for no apparent reason. - Mose Ramieh III There are two types

More information

Switchgear and Metal-Enclosed Bus

Switchgear and Metal-Enclosed Bus Section 18 Switchgear and Metal-Enclosed Bus 180. SWITCHGEAR ASSEMBLIES 180A. General Requirements for All Switchgear. This rule covers general requirements for all switchgear. Examples of switchgear found

More information

Common Electrical Hazards in the Workplace Including Arc Flash. Presented by Ken Cohen, PhD, PE & CIH (Ret.)

Common Electrical Hazards in the Workplace Including Arc Flash. Presented by Ken Cohen, PhD, PE & CIH (Ret.) Common Electrical Hazards in the Workplace Including Arc Flash Presented by Ken Cohen, PhD, PE & CIH (Ret.) 1 What s New In February 1972, OSHA incorporated the 1971 edition of the National Fire Protection

More information

Bypass transfer switch mechanisms

Bypass transfer switch mechanisms Power topic #6013 Technical information from Cummins Power Generation transfer switch mechanisms > White paper By Gary Olson, Director, Power Systems Development This paper describes the configuration

More information

Roadmap to Compliance with NFPA 70E Arc Flash Requirements

Roadmap to Compliance with NFPA 70E Arc Flash Requirements Roadmap to Compliance with NFPA 70E Arc Flash Requirements TAHFM Interlink 2015 March 30, 2015 Antony Parsons, Ph.D., P.E. Schneider Electric Engineering Services 1 2 How do we get to Reliable Power? >

More information

How To Choose A Transformer

How To Choose A Transformer Consider open loop MV network as an example source 1 source 2 NC NC NC or NO main MV switchboard A B Detail design of substation NC NC NC NO NC NC switchboard 1 switchboard 2 switchboard 3 MV MV MV LV

More information

Medium Voltage (MV) & High Voltage (HV) Training Module 6. Date of the presentation

Medium Voltage (MV) & High Voltage (HV) Training Module 6. Date of the presentation Medium Voltage (MV) & High Voltage (HV) Training Module 6 Date of the presentation Electrical System Basics MV vs. HV - Definitions Differences between USA and the rest of the world IEC define a high voltage

More information

2013WWOA Conference Technical Conference Program

2013WWOA Conference Technical Conference Program 2013WWOA Conference Technical Conference Program Understanding Arc-Flash Hazards, Its Implications on Operations and Solutions that Mitigate Such Exposure Presented by Jerry Baskin Senior Product Manager

More information

RISK MITIGATION for ELECTRICAL WORK. Feb 2013 San Diego CA

RISK MITIGATION for ELECTRICAL WORK. Feb 2013 San Diego CA RISK MITIGATION for ELECTRICAL WORK Feb 2013 San Diego CA Agenda I. RISK Define the Risks Arc Flash Review II. MITIGATION 3 Easy Steps New Designs Vs. Existing Systems III. DUKE UNIVERSITY EXAMPLE I. Risk

More information

Analyzing Electrical Hazards in the Workplace

Analyzing Electrical Hazards in the Workplace Analyzing Electrical Hazards in the Workplace By Dennis K. Neitzel, CPE AVO Training Institute, Inc. The need for analyzing electrical hazards in the workplace has been recognized by a small segment of

More information

Installation Instructions for Alarm Module Kit A043F059

Installation Instructions for Alarm Module Kit A043F059 Instruction Sheet 07-2013 Installation Instructions for Alarm Module Kit A043F059 1 Introduction The information contained within is based on information available at the time of going to print. In line

More information

The Three A s of Arc Flash

The Three A s of Arc Flash The Three A s of Arc Flash Gary H. Fox, PE Senior Specification Engineer In 2007 GE conducted a survey of industry professionals working in facilities related to the oil and gas industry, pulp and paper

More information

Introduction to Arc Flash

Introduction to Arc Flash Introduction to Arc Flash Worker Training of Electrical Hazards Including Arc Flash SH-16614-7 This material was produced under grant number SH-16614-7 from the Occupational Safety and Health Administration,

More information

Electrical Grounding. Appendix C

Electrical Grounding. Appendix C Appendix C Electrical Grounding Low-Voltage Equipment Grounding The most frequently cited Office of Safety and Health Administration (OSHA) electrical violation is improper occupational grounding of equipment

More information

Electrical Resistance Resistance (R)

Electrical Resistance Resistance (R) Electrical Resistance Resistance (R) Any device in a circuit which converts electrical energy into some other form impedes the current. The device which converts electrical energy to heat energy is termed

More information

New Supervisory Control and Data Acquisition (SCADA) Based Fault Isolation System for Low Voltage Distribution Systems

New Supervisory Control and Data Acquisition (SCADA) Based Fault Isolation System for Low Voltage Distribution Systems International Conference on Computer and Communication Engineering (ICCCE 2010), 11-13 May 2010, Kuala Lumpur, Malaysia New Supervisory Control and Data Acquisition (SCADA) Based Fault Isolation System

More information

Session Eleven: Development of Standards for MV Switchgear Rated for Arc Protection

Session Eleven: Development of Standards for MV Switchgear Rated for Arc Protection Session Eleven: Development of Standards for MV Switchgear Rated for Arc Protection Bryan Johnson Product Group Manager, MV Switchgear ABB South Africa Contents Introduction... 3 What is an internal arc

More information

Circuit Breakers and Switchgear. Thomas Greer Director of Engineering TLG Services

Circuit Breakers and Switchgear. Thomas Greer Director of Engineering TLG Services Circuit Breakers and Switchgear Thomas Greer Director of Engineering TLG Services Presentation Outline Switchgear Definition Overcurrent Protection Devices Circuit Breaker Trip Curves and Coordination

More information

Installation and safety instructions for AC/DC built-in devices

Installation and safety instructions for AC/DC built-in devices The device type and date of manufacture (week/year) can be found on the device rating plate. In the event of any queries about the device, please quote all the details given on the rating plate. For further

More information

Houston Service Center Medium Voltage Service and Aftermarket Solutions

Houston Service Center Medium Voltage Service and Aftermarket Solutions Houston Service Center Medium Voltage Service and Aftermarket Solutions Table of contents Introduction...3 Breaker refurbishment...4 Protective relay & control service and support...5 Power Service and

More information

Integrating SPDs in Switchgear & Switchboards Causes More Problems than it Solves

Integrating SPDs in Switchgear & Switchboards Causes More Problems than it Solves Integrating SPDs in Switchgear & Switchboards Causes More Problems than it Solves White Paper July 2010 Integrating surge protective devices (SPD) into distribution equipment (i.e. switchgear, switchboards,

More information

INTERNATIONAL POWER DISTRIBUTION CONGRESS CIDEL ARGENTINA 2002

INTERNATIONAL POWER DISTRIBUTION CONGRESS CIDEL ARGENTINA 2002 INTERNATIONAL POWER DISTRIBUTION CONGRESS CIDEL ARGENTINA 2002 NEW GAS INSULATED SWITCHGEAR (GIS) FOR ALL MEDIUM VOLTAGE APPLICATIONS H. Fink, ABB Calor Emag Mittelspannungs GmbH; M. Hyrenbach, ABB Calor

More information

Eaton Safety & Reliability Solutions in the Oil & Gas Industry Electrical

Eaton Safety & Reliability Solutions in the Oil & Gas Industry Electrical Eaton Safety & Reliability Solutions in the Oil & Gas Industry Electrical Victor Lee Commercial Marketing Manager SEA Eaton Oil & Gas Solution Tech Day 2013 Eaton. All Rights Reserved. Eaton is a leading

More information

Medium voltage products UniSec for Smart Grid Air-insulated medium-voltage secondary distribution switchgear

Medium voltage products UniSec for Smart Grid Air-insulated medium-voltage secondary distribution switchgear Medium voltage products UniSec for Smart Grid Air-insulated medium-voltage secondary distribution switchgear Index 3 Overview 4 Standard Levels 6 Monitoring & Control 7 Measurements 8 Protection & Logic

More information

Video Camera Installation Guide

Video Camera Installation Guide Video Camera Installation Guide The intent of this guide is to provide the information needed to complete or modify a video camera installation to avoid lightning and induced power surge damage. This guide

More information

Fuses. Introduction. Measuring is knowing. Who chooses?

Fuses. Introduction. Measuring is knowing. Who chooses? Fuses Introduction. There are many theories going around about the necessity for protecting PDUs (Power Distribution Unit / multiple socket / socket, etc.). A fuse is by definition a Single Point of Failure

More information

LOXONE 12 Channel Amplifier

LOXONE 12 Channel Amplifier LOXONE 12 Channel Amplifier Item no.: 200110 Thank you for purchasing the Loxone Twelve Channel Amplifier. The versatility of the Amplifier makes it the perfect choice for almost every type of custom multi-room

More information

For a phase-to-phase voltage between 100 V and 1000 V. The standard ratings are: 400 V - 690 V - 1000 V (at 50 Hz)

For a phase-to-phase voltage between 100 V and 1000 V. The standard ratings are: 400 V - 690 V - 1000 V (at 50 Hz) 24 1. NETWORK CONFIGURATIONS definition Standard IEC 38 defines voltage ratings as follows: - Low voltage () For a phase-to-phase voltage between 100 V and 1000 V. The standard ratings are: 400 V - 690

More information

Paralleling Switchgear

Paralleling Switchgear Paralleling Switchgear By Maurice D Mello, P.Eng. Systems Engineer, GE Consumer & Industrial, Canada What is Paralleling? Paralleling is the operation in which multiple power sources, usually two or more

More information

3.1.1 Full Type Tests & Routine Tests according to Clause 8 2 & 8 3. 4.0 Instructions For Installation, Operation & Maintenance

3.1.1 Full Type Tests & Routine Tests according to Clause 8 2 & 8 3. 4.0 Instructions For Installation, Operation & Maintenance SPECIFICATION FOR LOW VOLTAGE SWITCHBOARD SEN I N D E X Description 10 STANDARD TECHNICAL REQUIREMENTS 11 Standards 12 General Operating Conditions 13 General Description Of Switchboard 131 Structure 132

More information

METAL-CLAD AND METAL-ENCLOSED SWITCHGEAR 3.6KV~40.5KV. tgood.com. Energy. Fast.

METAL-CLAD AND METAL-ENCLOSED SWITCHGEAR 3.6KV~40.5KV. tgood.com. Energy. Fast. METAL-CLAD AND METAL-ENCLOSED SWITCHGEAR 3.6KV~40.5KV tgood.com Energy. Fast. TGOOD produces over 5000 switchgear units annually for projects around the globe PRODUCT OVERVIEW Integral substation component

More information

30 ms High Speed Transfer System (HSTS) Product Description

30 ms High Speed Transfer System (HSTS) Product Description 30 ms High Speed Transfer System (HSTS) Product Description 2 30 ms High Speed Transfer System (HSTS) Product Description Content Page 1 General 5 1.1 Description of the 30 ms high speed transfer system

More information

Enhance Power Equipment Reliability with Predictive Maintenance Technologies

Enhance Power Equipment Reliability with Predictive Maintenance Technologies Enhance Power Equipment Reliability with Predictive Maintenance Technologies November 2012/1910DB1208 by S. Frank Waterer, Electrical Engineerinig, Fellow Schneider Electric USA, Inc. Make the most of

More information

Fortune Oregon Data Center Increases Reliability with a High Resistance Grounding System

Fortune Oregon Data Center Increases Reliability with a High Resistance Grounding System Fortune Oregon Data Center Increases Reliability with a High Resistance Grounding System Cory David Smith, Project Manager, ECOM Engineering Inc., and David Lawrence Smith, Principal, ECOM Engineering

More information

Electrical Safety in the Marine Environment

Electrical Safety in the Marine Environment January 3, 2001 TEHNIAL BULLETIN 010 Electrical Safety in the Marine Environment Approach Boundaries Electrical Safety in the Marine Environment presented by adick orporation 1 Overview Electrical power

More information

A series of technology briefs spanning Tyco Electronics product portfolio

A series of technology briefs spanning Tyco Electronics product portfolio A series of technology briefs spanning Tyco Electronics product portfolio Coordinated Circuit Protection Schemes Help Prevent Overvoltage and Overcurrent Damage Through advances in materials science and

More information

LIMITING SHORT-CIRCUIT CURRENTS IN MEDIUM-VOLTAGE APPLICATIONS

LIMITING SHORT-CIRCUIT CURRENTS IN MEDIUM-VOLTAGE APPLICATIONS LIMITING SHORT-CIRCUIT CURRENTS IN MEDIUM-VOLTAGE APPLICATIONS Terence Hazel Senior Member IEEE Schneider Electric 38050 Grenoble France Abstract The power requirements for large industrial sites is increasing.

More information

21 st Century Facilities

21 st Century Facilities Electrical Testing 21 st Century Facilities Facility Owners face tough challenges 24 X 7 reliability needed Non linear loads cause harmonics VFD Computers Switching transients disrupt operations Less customer

More information

Table of Contents. TransformerIQ FAQs 1

Table of Contents. TransformerIQ FAQs 1 [12/12] FAQs Table of Contents FAQ 1. What size transformer will TransformerIQ monitor?... 2 FAQ 2. Are there different TransformerIQ versions?... 2 FAQ 3. How are the units powered?... 2 FAQ 4. What is

More information