2008 Eaton Corporation. All rights reserved.
|
|
- Bernard O’Connor’
- 8 years ago
- Views:
Transcription
1 FlashGard TM Motor Control Center Electrical Safety Hazards Design Philosophy The Product 2008 Eaton Corporation. All rights reserved. Research studies say. Five to 10 arc flash explosions occur in electrical equipment every day in the United States, according to statistics compiled by CapSchell, Inc., a Chicago-based research and consulting firm that specializes in preventing workplace injuries and deaths. Based on the incidents reported Unreported cases and near misses are estimated to be many times this number 2 2 1
2 What is an Arc Flash? An Arc Flash is a dangerous condition associated with the explosive release of energy caused by an electrical arc due to either a phase to ground or phase to phase fault. This fault can result from many factors, including dropped tools, accidental contact with electrical systems, build up of conductive dust, corrosion, and improper work procedures among others Arc Flash 3 3 What is Arc Flash Energy? It s expressed in calories per centimeter squared (cal/cm2) where Calorie (cal) Amount of thermal energy required to raise 1 gram of water s temperature 1 degree C. so Calorie/cm2 = Energy per unit of area TO GIVE YOU A PERSPECTIVE: 1 cal/cm2 = the Exposure on the tip of a finger by a Cigarette Lighter in One Second One to Two cal/cm2 will cause a 2nd Degree Burn on Human Skin 4 4 2
3 Another known fact Motor Control Centers account for the second highest frequency of electrical accidents. WHY??? MCC s 5 5 Why MCC accidents occur? MCC s are worked on more than any other electrical equipment when energized Most feel comfortable working on them live Measurements are taken daily Maintenance work is performed daily While unit is energized to avoid downtime of critical equipment or processes Or on bench but inserting and extracting the units are done live 6 6 3
4 NFPA 70E (B) Protective Clothing and Personal Protective equipment for application with a Flash Hazard Analysis Where it has been determined that work will be performed within the flash protection boundary by 130.3(A), the flash hazard analysis shall determine, and the employer shall document, the incident energy exposure of the worker (in calories per square centimeter). Flame-resistant (FR) clothing and personal protective equipment (PPE) shall be used by the employee based upon the incident energy exposure associated with the specific task. 7 7 You Have Two Options NFPA 70E, provides two methods for determining the flash hazard risk and the associated PPE to be used: 1. Generic Hazard/Risk Guideline: Defines the PPE by the specific task and exposure based on a conservative fault/energy level assessment [NFPA 70E Table 130.7(C)(9)(a)]. This Hazard/Risk Category classification table is straight forward and simple to understand
5 You Have Two Options NFPA 70E, provides two methods for determining the flash hazard risk and the associated PPE to be used: 2. Arc Flash Analysis Method: Conducting a flash hazard energy analysis to determine the actual Flash Protection Boundary and the necessary PPE. This requires data such as equipment configuration, gap between electrodes, grounding type, short circuit fault current value, system voltage on input etc. DETERMINING PPE HAZARD RISK CATEGORY Category Cal/cm2 Clothing Untreaded cotton 1 5 Flame retardant FR shirt and FR pants 2 8 Cotton underwear, FR shirt and FR pants 3 25 Cotton underwear, FR shirt, FR pants and FR coveralls 4* 40 Cotton underwear, FR shirt, FR pants and double-layer switching coat and pants * Output Categoryfor personel protective equipment (PPE) Source: NFPA 70E, Table Common Arc Flash Mythology Wearing full (CAT4) PPE for every electrical task makes electrical equipment safer Try working in PPE like this: Always shut down the Motor Control Center The best practice Sadly, this is not reality Users often find this a lengthy and costly proposition jeopardizing production
6 FlashGard Motor Control Centers Rajiv Kumar MCC Product Manager Fayetteville, NC What is Eaton s FlashGard solution? 1. Maintain a dead-front door closed while inserting or removing MCC buckets 2. Insulate and Isolate current carrying bus and components 3. With the IT. door open - limit voltages in the work area below 120 volts 4. Lower the clearing time of the upstream breaker feeding the MCC
7 What is the Eaton FlashGard? FlashGard maintains a dead-front closed door while inserting or removing MCC stabs while ALL other MCCs require the door to be OPEN!!! Standard MCC: De-energize bucket OPEN THE DOOR Disengage retention Yank bucket by hand Hope for no explosions Close door Move away hastily FlashGard MCC: De-energize bucket Insert 3/8 square drive tool or remote racking tool Withdraw MCC stabs Once visual indicators indicate lack of power and bucket shutters are closed Open the door Disengage retention walk casually away The Ultimate Design: Eaton s FlashGard MCC with RotoTract
8 What is the Eaton FlashGard? FlashGard maintains a dead-front closed door while inserting or removing MCC buckets RotoTract There is no such thing as an Arc Resistant MCC!!! Let s think about our competition s supposed Arc-Resistant offering ANSI C provides testing standards for Arc Resistant Switchgear. MCCs are NOT switchgear!!!! Switchgear must have properly latched or secured covers, doors How many MCC accidents happen with the doors and covers latched? Arc Flash with the Door Open ANSI generalizes this at CAT 3!!!
9 RotoTract Top Removed Automatic Shutters RotoTract TM Assembly EATON wins AGAIN How RotoTract works Breaker must be open to access racking tool receiver RotoTract TM prevents stripping of the mechanism or overtorquing Makes insertion of large size 4,5 buckets much safer. No more shoving buckets on to the vertical bus Internal Shutter Indicator Open Closed Bucket Position Indicator Connected Test* Withdrawn * No TEST position with Freedom
10 RotoTract TM Stab Assembly Stabs Extended Stabs Withdrawn Completely enclosed connection of the stabs to the vertical bus in combination with insulated components makes the MCC virtually Arc Free Why Keep the Door?
11 Why Keep the Door? THAT S IT!!!!! Why Keep the Door?
12 What is the Eaton FlashGard? Insulated and Isolated current carrying bus and components Labyrinth Vertical Bus Automatic Shutter RotoTract TM Stab Assembly - How it works Stabs Extended Stabs Withdrawn Completely enclosed connection of the stabs to the vertical bus in combination with insulated components makes the MCC virtually Arc Free
13 Why Shutters? Automatic Shutters provide Isolation and Insulation. Provides personal protection by isolating and insulating the live bus should a MCC unit be removed or moved to the service position, i.e., a Hazard/Risk Category reduction from Level 2* to 0 [NFPA 70E Clause 130.7(D)(1)(h), specifically Table 130.7(C)(9)(a)]. In addition, the shutters provide isolation which helps restrict an internal arc from spreading to the vertical bus [NFPA 70E Clause 130.7(D)(1)(h)] What is the Eaton FlashGard? Freedom 2100 FlashGard MCC Vertical Ground Bus CPT mounted behind device island just like any Freedom MCC bucket 120VAC Means no TEST Position in Freedom FG!
14 The Freedom FlashGard Bucket Racking Tool Receiver Power Stab Position Connected Disconnected Unit Latch Internal Shutter Position Open Closed Handle Mechanism Pilot Device Island/ Panel Start, Stop, HOA Breaker Freedom Contactor C440 SSOL Standard and Optional Features Standard RotoTract TM Assembly Labyrinth Vertical Bus Insulated Horizontal Bus Optional Bottom Plates (Stnd on NEMA 12) Vertical Bus Barrier Rodent Barrier Remote Racking Device
15 FlashGard Remote Racking Accessory Mounting Holes Remote Racking wired Accessory Accessory to perform RotoTract racking safely behind NFPA Arc Flash boundaries 120 VAC motor driven Standard Wall Plug Mounts to RotoTract Mechanism Wired pendant station for rack-in / rack-out operation. Mounting offset bracket to clear device panel FlashGard Door Accessories VoltageVision Presence or absence of voltage indicator Motor Guard Motor Guard is a patented motor testing and protection system AUTOMATICALLY monitors motor insulation breakdown
16 FlashGard Aftermarket Freedom FlashGard and IT FlashGard Freedom/ Advantage/ Five-Star MCCs - FFG Drop in to any 2100 w/ Labyrinth Vertical Bus - Non Labyrinth requires EESS Barrier retrofit
BRANDON AND CLARK INC. // SCOTT W. CLARK, P.E. ELECTRICAL CONTINUING EDUCATION ARC FLASH - NFPA 70E
BRANDON AND CLARK INC. // SCOTT W. CLARK, P.E. ELECTRICAL CONTINUING EDUCATION ARC FLASH - NFPA 70E Training is not a substitute for following corporate safety guidelines. Always refer to the latest safety
More information2013WWOA Conference Technical Conference Program
2013WWOA Conference Technical Conference Program Understanding Arc-Flash Hazards, Its Implications on Operations and Solutions that Mitigate Such Exposure Presented by Jerry Baskin Senior Product Manager
More informationWhat s up with Arc Flash?
What s up with Arc Flash? Presented by Mark Haskins, CSP Practical Safety Solutions, LLC CONN OSHA Breakfast Roundtable February 18, 2014 2014 Practical Safety Solutions, LLC What is Arc Flash? Definition
More informationUnderstanding Arc Flash
Understanding Arc Flash Presented by Eddie F. Jones, PE 1 2 3 4 5 Five to 10 arc flash explosions occur in electric equipment every day in the United States. This number does not include cases in which
More informationArc Flash Avoidance and its Application to Overhead Traveling Cranes
Arc Flash Avoidance and its Application to Overhead Traveling Cranes Whitepaper August 2012 Jason Wellnitz, Controls Product Manager Material Handling Numerous technical papers, bulletins, magazine articles
More informationUL Validated Testing of Arc-Resistant Motor Control Centers
UL Validated Testing of Arc-Resistant Motor Control Centers Ensure Protective Features Perform as Designed Larry Sifers Account Manager Littleton, CO Siemens Industry June 1st - 3rd, 2011 Western Mining
More information2012 NFPA 70E. Ten Most Important Changes. John A. DeDad
2012 NFPA 70E Ten Most Important Changes John A. DeDad GE Energy Management 41 Woodford Avenue Plainville, CT 06062 USA 860-747-7344 John.dedad@ge.com Abstract The 2012 Edition of NFPA 70E, Standard for
More informationARC FLASH CALCULATIONS & LABELING REQUIREMENTS
ARC FLASH CALCULATIONS & LABELING REQUIREMENTS Presented by: Edmund Elizalde EYP Mission Critical Facilities, Inc. Slides by: Lonnie Lindell SKM Systems Analysis, Inc. 1 Agenda NEC 110.16 NFPA 70E IEEE
More information! WARNING Arc Flash and Shock Hazard Appropriate PPE Required
Arc Flash Hazard Labeling Do s and Don ts! WARNING Arc Flash and Shock Hazard Appropriate PPE Required 11' - 3" Flash Hazard Boundary 9 cal/cm2 Flash Hazard at 18 inches #3 PPE Level Cotton underwear plus
More informationEnhancing Personnel Safety with Arc Resistant Equipment
Enhancing Personnel Safety with Arc Resistant Equipment Carl Christian Power LV Offer Marketing Nashville, TN Sponsored by the Water Wastewater Competency Center 1 Enhancing Personnel Safety 5-10 Five
More informationArc Flash Hazards. Electrical Hazards. Dan Neeser Field Application Engineer DanRNeeser@Eaton.com. Electrical Hazards 2/18/2015. Shock.
Arc Flash Hazards Dan Neeser Field Application Engineer DanRNeeser@Eaton.com Electrical Hazards Electrical Hazards Shock Arc Flash Arc Blast 2 1 Arcing Fault Basics 35,000 F Radiant Heat & UV Speed of
More informationIntegrating SPDs in Switchgear & Switchboards Causes More Problems than it Solves
Integrating SPDs in Switchgear & Switchboards Causes More Problems than it Solves White Paper July 2010 Integrating surge protective devices (SPD) into distribution equipment (i.e. switchgear, switchboards,
More informationPower-Zone 4 Arc Resistant Low Voltage Switchgear
Power-Zone 4 Arc Resistant Low Voltage Switchgear with ArcBlok Technology Make the most of your energy SM Workplace safety 2 I Power-Zone 4 Arc Resistant Low Voltage Switchgear Five to ten arc flash explosions
More informationArc Flash Mitigation. Remote Racking and Switching for Arc Flash danger mitigation in distribution class switchgear.
Arc Flash Mitigation Remote Racking and Switching for Arc Flash danger mitigation in distribution class switchgear. Distance is Safety We will discuss through examples of actual occurrences and possible
More informationA Guide to Performing An Arc Flash Hazard Assessment Using Power Analysis Software
A Guide to Performing An Arc Flash Hazard Assessment Using Power Analysis Software Abstract: The nature of explosive equipment failures, and the rate of serious burn injuries in the electrical industry
More informationLow Voltage Switchgear
Arc Resistant Switchgear n Insulated and isolated bus n Separation barriers and top venting n Breaker shutters 12 SWITCHGEAR Arc resistant metal-enclosed low voltage switchgear is an optional product offering
More informationHow to reduce exposure to arc flash hazards
GE Energy Industrial Solutions How to reduce exposure to arc flash hazards Multiple solutions for new and existing facilities imagination at work Multiple Issues Today s power system engineer must not
More informationIntroduction to Arc Flash
Introduction to Arc Flash Worker Training of Electrical Hazards Including Arc Flash SH-16614-7 This material was produced under grant number SH-16614-7 from the Occupational Safety and Health Administration,
More informationNFPA 70E 2012 Rolls Out New Electrical Safety Requirements Affecting Data Centers
NFPA 70E 2012 Rolls Out New Electrical Safety Requirements Affecting Data Centers A market position paper from the experts in Business-Critical Continuity TM Executive Summary Electrocutions are the fourth
More informationHAZARDS, INCLUDING SHOCK, ARC FLASH AND FIRE
Appendix B-2 - Electrical Safety In Design Final Report TECHNOLOGIES THAT REDUCE LIKELIHOOD OF INJURY FROM ELECTRICAL HAZARDS, INCLUDING SHOCK, ARC FLASH AND FIRE The following are technologies that reduce
More informationProper Application of 415V Systems in North American Data Centers. A White Paper from the Experts in Business-Critical Continuity
Proper Application of 415V Systems in North American Data Centers A White Paper from the Experts in Business-Critical Continuity Introduction Increasing pressure to reduce operating expenses and be more
More informationThe following components are common to most cubicles; this example is an ABB HK cubicle.
4.0 CIRCUIT BREAKER CUBICLE Learning Objectives The circuit breaker cubicle is the component of the switchgear that holds the circuit breaker, and the controls and cabling for the distribution system.
More informationmisconceptions about arc-flash hazard assessments
misconceptions about arc-flash hazard assessments There are some common misconceptions about Arc-Flash Hazard Assessments which reduce the effectiveness of the Assessments and can increase electrical hazards.
More informationA USERS GUIDE TO ARC RESISTANT LOW VOLTAGE SWITCHGEAR & MOTOR CONTROL ANALYTICAL COMPARISON VS ARC FLASH TEST RESULTS
A USERS GUIDE TO ARC RESISTANT LOW VOLTAGE SWITCHGEAR & MOTOR CONTROL ANALYTICAL COMPARISON VS ARC FLASH TEST RESULTS By: Gabriel Arce, ABB, San Luis Potosi, Mexico Casey McCollum, ABB, Houston, TX John
More informationFFI. Advances in Medium and Low Voltage Power Distribution ESS Metron Expo and Technical Seminars. Presented By: Greg Pelster & Robert Schmid
Advances in Medium and Low Voltage Power Distribution ESS Metron Expo and Technical Seminars Presented By: Greg Pelster & Robert Schmid FFI Ferrie, Franzmann Industries LOW VOLTAGE SWITCHGEAR & LOW VOLTAGE
More informationSAFE ELECTRICAL WORK PRACTICES & 2015 NFPA 70E
SAFE ELECTRICAL WORK PRACTICES & 2015 NFPA 70E This easy-to-use Leader s Guide is provided to assist in conducting a successful presentation. Featured are: INTRODUCTION: A brief description of the program
More informationRISK MITIGATION for ELECTRICAL WORK. Feb 2013 San Diego CA
RISK MITIGATION for ELECTRICAL WORK Feb 2013 San Diego CA Agenda I. RISK Define the Risks Arc Flash Review II. MITIGATION 3 Easy Steps New Designs Vs. Existing Systems III. DUKE UNIVERSITY EXAMPLE I. Risk
More informationElectrical Wiring Methods, Components and Equipment for General Use. Approved for Public Release; Further Dissemination Unlimited
Electrical Wiring Methods, Components and Equipment for General Use Approved for Public Release; Further Dissemination Unlimited At the completion of this unit you shall be able to: 1. Utilize section
More informationPart 1 System Modeling & Studies for Existing Systems
Part 1 System Modeling & Studies for Existing Systems Operation Technology, Inc. Copyright 2009 Result of rapid release of energy due to an arcing fault between two conductors. Bus voltages > 208V Temperatures
More informationElectrical Safety in the Workplace
Electrical Safety in the Workplace NFPA 70 E Presented by Sabine Mueller What Made Sabine Choose Such a DRY Topic? Ulterior Motive Metso Mueller Engineering has been visiting many scrap yards two or more
More informationTechnical Guide. SKM Arc Flash Line Side vs. Load Side
SKM Arc Flash Line vs. Load The option of choosing the line-side or the load-side arc flash incident energy for arc flash labels is an important decision when performing an arc flash hazard analysis. When
More informationThe Other Hazard of Electricity. Larren Elliott Ph.D. Lindsay Polic, CSP, REHS
The Other Hazard of Electricity Larren Elliott Ph.D. Lindsay Polic, CSP, REHS Presenters Larren Elliott Ph.D. EORM Electrical Safety Service Partner 45 years practical and hands-on industrial experience
More informationJob Site Electrical Safety A Matter of Life and Death
Job Site Electrical Safety A Matter of Life and Death Scott Forsyth, PE Senior Engineer Johnson Controls Performing the Job Right and on Time is Top Priority!!!! Right? Wrong!!!! Performing the Job Safely
More informationIMPLEMENTING THE NEW ELECTRICAL SAFETY REQUIREMENTS
IMPLEMENTING THE NEW ELECTRICAL SAFETY REQUIREMENTS Paul A Zoubek, CSP, CIH Occupational Services, Inc. San Diego, CA 619-861 861-0612 paul@occsev.com OCCUPATIONAL SERVICES, INC. BACKGROUND Update Update
More informationSALISBURY ASSESSMENT SOLUTIONS
SALISBURY ASSESSMENT SOLUTIONS Electrical engineering services for a safe and compliant workplace Electrical Safety Program Assessments - Electrical Safety Training Arc Flash Risk Assessments - Power Systems
More informationWritten Program ELECTRICAL SAFETY. Based on OSHA Subpart S and NFPA 70E Standards
Written Program ELECTRICAL SAFETY Based on OSHA Subpart S and NFPA 70E Standards Revised November 2012 Disclaimer The presentations and program provided by Workplace Safety Solutions, Inc. are based on
More informationBypass transfer switch mechanisms
Power topic #6013 Technical information from Cummins Power Generation transfer switch mechanisms > White paper By Gary Olson, Director, Power Systems Development This paper describes the configuration
More informationInstallation Instructions for Alarm Module Kit A043F059
Instruction Sheet 07-2013 Installation Instructions for Alarm Module Kit A043F059 1 Introduction The information contained within is based on information available at the time of going to print. In line
More informationINTRODUCTION ARC FLASH PROTECTION AND SAFETY MEASURES. September 2010
ARC FLASH PROTECTION AND SAFETY MEASURES September 2010 Introduction Hazards of Electrical Energy Electrical Safety Program Safety-Related Work Practices Electrical Safety Procedures Presented By: Ken
More informationARC FLASH HAZARD OVERVIEW. Presented August 13, 2015 WWOA Lake Michigan District by Mead & Hunt, Inc.
ARC FLASH HAZARD OVERVIEW Presented August 13, 2015 WWOA Lake Michigan District by Mead & Hunt, Inc. ARC FLASH EXPERIENCE Christopher J. DeWaal, MS, MEM, PE, LEED AP, HACCP How did I get involved? A client
More informationNFPA 70E Updates Affect Your Most Valuable Assets
NFPA 70E Updates Affect Your Most Valuable Assets EXECUTIVE SUMMARY Electrocution is a well-known hazard associated with direct contact with electrical energy. According to the U.S. Department of Labor,
More informationPROCEDURES FOR SAFE WORKING AND TESTING OF ENERGIZED ELECTRICAL EQUIPMENT
Human Resources Support Services Health, Wellness and Safety PROCEDURES FOR SAFE WORKING AND TESTING OF ENERGIZED ELECTRICAL EQUIPMENT 1 SCOPE The electrical safety procedure shall be part of the Peel
More informationEaton Safety & Reliability Solutions in the Oil & Gas Industry Electrical
Eaton Safety & Reliability Solutions in the Oil & Gas Industry Electrical Victor Lee Commercial Marketing Manager SEA Eaton Oil & Gas Solution Tech Day 2013 Eaton. All Rights Reserved. Eaton is a leading
More informationAutomation & Power World Improving safety Through arc resistant switchgear and arc reducing components. ABB Wednesday, 23 March 2011 Slide 1
Automation & Power World Improving safety Through arc resistant switchgear and arc reducing components Wednesday, 23 March 2011 Slide 1 Automation & Power World 2011 April 18-21, 2011 in Orlando, Florida
More informationUnderstanding Emergency Power Off (EPO)
Understanding Emergency Power Off (EPO) White Paper #22 Executive Summary Emergency Power Off (EPO) is the capability to power down a piece of electronic equipment or an entire installation from a single
More informationAnalyzing Electrical Hazards in the Workplace
Analyzing Electrical Hazards in the Workplace By Dennis K. Neitzel, CPE AVO Training Institute, Inc. The need for analyzing electrical hazards in the workplace has been recognized by a small segment of
More informationArc Flash Mitigation & Selective Co-ordination
Arc Flash Mitigation & Selective Co-ordination Michael Hodder March 2015 Overview This seminar will provide information on: Mitigating arc flash hazards Selective Coordination What can we do to make these
More informationSiemens tiastar TM Motor Control Center (MCC) Siemens 2011. All rights reserved.
Siemens tiastar TM Motor Control Center (MCC) Siemens 2011. All rights reserved. tiastar Arc Resistant MCCs UL Validated Testing of Arc-Resistant Motor Control Centers page 2 tiastar Arc Resistant MCCs
More informationArc Flash Overview. Arc-Flash Hazard. Who is Eaton. Engineering Studies ABSTRACT. Eaton PSE s
Arc-Flash Hazard Arc Flash Overview Tom Studer Eaton Electrical Power Systems Engineering Tempe, AZ Who is Eaton?: Company Overview Electrical Engineering Services What is Arc-Flash?: Definitions / Examples
More informationInstruction Bulletin. MCS025 Sync-Check Module Installation Sheet
Instruction Bulletin 63230-216-244B1 LaVergne, TN, USA MCS025 Sync-Check Module Installation Sheet Retain for future use. DANGER HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH Only qualified electrical
More informationArc Flash Energy Mitigation Techniques
Arc Flash Energy Mitigation Techniques When short circuits occur on an electrical distribution system, an arc flash event usually forms. These arc flash events can cause dangerous and potentially fatal
More informationChoosing the Best Solution for Reducing Arc Energy
CONVENTION SESSION HANDOUT Choosing the Best Solution for Reducing Arc Energy Terry L. Schiazza, Business Development Manager Square D / Schneider Electric SESSION #11 Independent Electrical Contractors
More informationMedium voltage VCP-W MR2 (integral racking)
Supersedes March 2013 Contents Description Page Notices and warnings...................... 2 Introduction.............................. 3 Breaker pan configurations.................. 3 Inspection/maintenance.....................
More informationProcedure Number 1022. Arc Flash Hazard Calculation and Required Protection Revision 5. TVA Safety Procedure Page 1 of 25. 1.
TVA Safety Procedure Page 1 of 25 Arc Flash Hazard Calculation and 1. Purpose April 30, 2007 1.1. This procedure defines TVA s method for calculating the electric arc flash incident energy at various distances,
More informationCampus Safety Procedure Electrical Safety
Campus Safety Procedure Electrical Safety Electrical Safety Procedures 1.0 Purpose The purpose of this procedure is to provide guidance in the performance of work on electrical systems, wiring, and equipment
More informationUsing Infrared Sightglasses to Protect Against Arc-Flash Exposure
Using Infrared Sightglasses to Protect Against Arc-Flash Exposure Antony J. Holliday IEEE Member Hawk IR International, Ltd. 117 High Street, Marske-by-Sea Redcar, Cleveland TS116JX, United Kingdom Ph:
More informationRoadmap to Compliance with NFPA 70E Arc Flash Requirements
Roadmap to Compliance with NFPA 70E Arc Flash Requirements TAHFM Interlink 2015 March 30, 2015 Antony Parsons, Ph.D., P.E. Schneider Electric Engineering Services 1 2 How do we get to Reliable Power? >
More informationUnderstanding the Standards Surrounding Arc Flash Hazards and Arc Resistant Equipment
Understanding the Standards Surrounding Arc Flash Hazards and Arc Resistant Equipment 1 Rev 5058-CO900E This presentation contains many hidden slides that are provided for the presenters information and/or
More informationSafety By Design. Strategies for Electrical Contractors
Safety By Design Strategies for Electrical Contractors Introduction Engineering and system design significantly impact worker safety System design provides opportunity to eliminate/minimize workers exposure
More informationRisk Mitigation of Aging Electrical Infrastructure
Risk Mitigation of Aging Electrical Infrastructure 2015 MWEA Annual Conference 2pm Monday June 22 nd, 2015 Presented by Tim Murphy Authored by Jeff M. Miller, PE, ENV SP About the Presenter 5 Jeff M. Miller,
More informationMCC Ratings. Voltage Rating
MCC Ratings In addition to the various ratings of individual components used in motor control centers, the overall ratings of the motor control center must also be considered. Voltage Rating Motor control
More informationUnion County Public Schools. Facilities Department. Electrical. Safe Work Practices
1 Union County Public Schools Facilities Department Electrical Safe Work Practices 2 Purpose In accordance with OSHA Standards 1910.331-335, safety-related work practices shall be used by Union County
More information100% Rule Alternate Method Arc Blast Arc Flash Approved Approved Equipment Authority Having Jurisdiction (AHJ) Authorized Work Bare Hand Work
Definitions 100% Rule Work on or near energized parts must be performed only after all participating qualified electrical workers are in 100% agreement on the work to be completed, on the sequence in which
More informationOSHA and NFPA 70 Understanding NFPA 70 and its Implications in Electrical Inspections 2010
OSHA and NFPA 70 Understanding NFPA 70 and its Implications in Electrical Inspections 2010 By: Martin Robinson, Level III Thermographer 18-1030-0005 Rev. A The National Fire Protection Association (NFPA)
More informationVilter motor starter solutions The NEW industry standard in motor starter packages
Vilter motor starter solutions The NEW industry standard in motor starter packages Electrical safety by design Built to Underwriters Laboratory (UL) 508A UL Standard for Safety for Industrial Control Panels.
More informationUnderstanding 2015 Changes to NFPA 70E Safety-related work practices and maintenance requirements mandate more robust electrical safety programs for
Understanding 2015 Changes to NFPA 70E Safety-related work practices and maintenance requirements mandate more robust electrical safety programs for commercial and industrial facilities Executive Summary
More informationCommon Electrical Hazards in the Workplace Including Arc Flash. Presented by Ken Cohen, PhD, PE & CIH (Ret.)
Common Electrical Hazards in the Workplace Including Arc Flash Presented by Ken Cohen, PhD, PE & CIH (Ret.) 1 What s New In February 1972, OSHA incorporated the 1971 edition of the National Fire Protection
More informationElectrical Safety in the Marine Environment
January 3, 2001 TEHNIAL BULLETIN 010 Electrical Safety in the Marine Environment Approach Boundaries Electrical Safety in the Marine Environment presented by adick orporation 1 Overview Electrical power
More information2004 TRANSMISSION SYSTEMS SEMINAR MEDIUM VOLTAGE, METAL-CLAD ARC RESISTANT SWITCHGEAR: ENHANCING WORKPLACE SAFETY
2004 TRANSMISSION SYSTEMS SEMINAR MEDIUM VOLTAGE, METAL-CLAD ARC RESISTANT SWITCHGEAR: ENHANCING WORKPLACE SAFETY Thomas P. McNamara, P.E. Manager, Development Engineering ABB Inc. Power Technologies Medium
More informationArc Flash Mitigation. Executive summary. by Antony Parsons, Ph.D., P.E.
by Antony Parsons, Ph.D., P.E. Executive summary Arc flash events can result in significant injury to workers, including severe burn injuries. The most effective arc flash safety programs are not those
More informationELECTRICAL SAFETY RISK ASSESSMENT
ELECTRICAL SAFETY RISK ASSESSMENT The intent of this procedure is to perform a risk assessment, which includes a review of the electrical hazards, the associated foreseeable tasks, and the protective measures
More informationProgress in Impacting Policy in Workplace Electrical Safety
Progress in Impacting Policy in Workplace Electrical Safety H. Landis Lanny Floyd II, PE, CSP, CMRP, Fellow IEEE Principal Consultant Electrical Safety & Technology The miracles of science TM NIOSH PtD
More informationElectrical Safety Program
California State University-Fullerton 800 N. State College Blvd. Fullerton, CA 92831 Prepared by: Paul A Zoubek, CSP, CIH President/Principal Consultant Zoubek Consulting, LLC 3737 Granada Ave. San Diego,
More informationUnderstanding 2015 Changes to NFPA 70E Safety-related work practices and maintenance requirements mandate more robust electrical safety programs for
Understanding 2015 Changes to NFPA 70E Safety-related work practices and maintenance requirements mandate more robust electrical safety programs for data centers Executive Summary Every three years, the
More informationWhat are the basic electrical safety issues and remedies in solar photovoltaic installations?
What are the basic electrical safety issues and remedies in solar photovoltaic installations? Presented by: Behzad Eghtesady City of Los Angeles Department of Building and Safety Topics Covered Photovoltaic
More informationHow to Build a Safe and Effective Electrical Maintenance Program
How to Build a Safe and Effective Electrical Maintenance Program The Business Case Ask Yourself the Following Questions: What is your dependence on electrical energy and control systems? What are the consequences
More informationSample - No Commercial Use
COMPLETE REVISION October 2010 Electrical PIP ELSSG01 Design and Fabrication of Low-Voltage Metal-Enclosed AC Power Circuit Breaker Switchgear PURPOSE AND USE OF PROCESS INDUSTRY PRACTICES In an effort
More information3053 Electrical Safety Training Program Course Outline
3053 Electrical Safety Training Program Course Outline The following outline summarizes the major points of information presented in the program. The outline can be used to review the program before conducting
More informationApplication Technique. Safety Function: Magnetic Door Switch Monitoring
Application Technique Safety Function: Magnetic Door Switch Monitoring Products: MC1 Magnetically-coded Door Switch, Guardmaster Dual-input Safety Relay Safety Rating: CAT. 3, PLd to EN ISO 13849-1: 2008
More informationMidwest Healthcare Engineering Conference and Trade Show 2012 Indianapolis, Indiana
Midwest Healthcare Engineering Conference and Trade Show 2012 Indianapolis, Indiana Arc Flash Overview An engineering solutions company November 7, 2012 Agenda Introductions Arc Flash defined History and
More informationOSHA Published First-Ever Arc Flash Protection Requirements for the Electric Power Industry Significant changes and unprecedented compliance
OSHA Published First-Ever Arc Flash Protection Requirements for the Electric Power Industry Significant changes and unprecedented compliance deadlines require high-voltage facilities to take immediate
More informationWiser Panel Meter, Model Number WISERCTPM200 Installer s Guide
Instruction Bulletin EAV85226 08/2014 Wiser Panel Meter, Model Number WISERCTPM200 Installer s Guide Retain for future use. Product Description Kit Contents The Wiser Panel Meter is for use in energy management
More information01.4IB.51200B PowlVac-AR Arc Resistant Switchgear. 5kV & 15kV 1200A, 2000A, 3000A, & 4000A Forced Cooled. Powered by Safety
PowlVac-AR Arc Resistant Switchgear 1200A, 2000A, 3000A, & 4000A Forced Cooled Powered by Safety PowlVac-AR Arc Resistant Switchgear 01.4IB.51200B Contact Information Powell Electrical Systems, Inc. www.powellind.com
More informationDemystifying arc flash hazard management
Demystifying arc flash hazard management Presented by Matt Brazier Senior Electrical Engineer Gove Operations November 2013 Standard NFPA 70E IEEE 1584 AS/NZS 4836 TERMINOLOGY Arc arc flash hazard analysis
More informationARC FLASH HAZARD MITIGATION. Industrial Tests, Inc. [indtests.com]
ARC FLASH HAZARD MITIGATION ARC FLASH HAZARD MITIGATION NWHA TECHNICAL SEMINAR May 17, 2012 Richard D Reese Power Systems Manager Industrial Tests, Inc. Rocklin, California [Dick@indtests.com; 916-660-2837]
More informationCommon Sense and Knowledge Approach to Electrical Safety
Common Sense and Knowledge Approach to Electrical Safety L. Bruce McClung Distinguished Lecturer on Electrical Safety Issues for IEEE-IAS/PES 2002-03 3/30/2004 1 For IEEE-Brazil Section in Guararema -
More informationLow Voltage Circuit Breakers. Arc flash hazards
Low Voltage Circuit Breakers Arc flash hazards Index Low voltage selectivity with ABB circuit breakers Introduction... 2 Definitions, acronyms and terms used... 3 Electrical arcs and their dangerous effects
More informationPRESENTED AT THE 2011 IEEE IAS PULP & PAPER INDUSTRY TECHNICAL CONFERENCE, NASHVILLE, TN: IEEE 2011 - PERSONAL USE OF THIS MATERIAL IS PERMITTED.
Arc Flash Energy Reduction Techniques Zone Selective Interlocking & Energy-Reducing Maintenance Switching Christopher G. Walker Senior Member, IEEE Eaton Corporation Moon Township, PA 15108 chrisgwalker@eaton.com
More informationWorldwide Thermography Headquarters
Arc-flash brochure B 18/9/07 09:22 Page 1 Copyright 2007, Hawk IR International Ltd. All other brand and product names are trademarks of Hawk IR International Ltd.. Hawk IR International Ltd. reserve the
More informationMODEL 5010 DUAL CHANNEL SMOKE/FIRE DETECTION MODULE
DESCRIPTION MODEL 5010 DUAL CHANNEL SMOKE/FIRE DETECTION MODULE DESCRIPTION The SST Model 5010 Two Channel Smoke/Fire Detection Module provides two independent detection input channels for the NOVA-5000
More informationEnvironmental Health & Safety Electrical Safety Program
**Printed copies of this document are uncontrolled, visit the EHS website at http://www.wright.edu/admin/ehs/ for the latest revision** I. Purpose Ensure the safety of employees who may work on or near
More informationThe Performance of Voltage Rated Gloves in Arc Flash Exposures
The Performance of Voltage Rated Gloves in Arc Flash Exposures Background. Ever since NFPA 70E -2000 was published many customers came to us with a question How will your gloves perform in arc flash? From
More informationTAMPA ELECTRIC COMPANY ENERGY SUPPLY ELECTRICAL SAFETY PROGRAM
TABLE OF CONTENTS TITLE PAGE # PURPOSE / INTRODUCTION 1 SCOPE 2 RESPONSIBILITY 3 EMPLOYEE TRAINING INCLUDING DOCUMENTATION 4 ELECTRICAL EQUIPMENT LABELING 5 APPROACH DISTANCES AND BOUNDARIES 5-8 GENERAL
More informationElectrical Safety Program. Electrical Safety Program Audit (Appendix: X) Performed By: Date:
Performed By: Date: The following sets of audit questions can be used to validate and verify that the is understood and being properly applied. Any non-compliant issues will be identified and prioritized
More information90.2(A) Covered & 90.2(B) Not Covered 6/23/2015. Learning Objectives. 90.2(A) Covered & 90.2(B) Not Covered. Change Summary
Learning Objectives After reviewing this material, the student will be able to: 1. Identify the installations that fall under the scope of the 2015 edition of NFPA 70E. 2. Identify the assessments required
More informationAdvantium 2 Plus Alarm
ADI 9510-B Advantium 2 Plus Alarm INSTALLATION AND OPERATING INSTRUCTIONS Carefully Read These Instructions Before Operating Carefully Read These Controls Corporation of America 1501 Harpers Road Virginia
More informationSURGE PROTECTIVE DEVICES (SPDs) LOW VOLTAGE AC INTEGRATED SURGE PROTECTION FOR ELECTRICAL DISTRIBUTION SYSTEMS SECTION 16671A SECTION 16671A
SURGE PROTECTIVE DEVICES (SPDs) INTEGRATED UNITS LOW VOLTAGE AC SURGE PROTECTION FOR ELECTRICAL DISTRIBUTION SYSTEMS PART 1 GENERAL 01 02 03 SCOPE The Contractor shall furnish and install the Surge Protective
More informationSwitchgear and Metal-Enclosed Bus
Section 18 Switchgear and Metal-Enclosed Bus 180. SWITCHGEAR ASSEMBLIES 180A. General Requirements for All Switchgear. This rule covers general requirements for all switchgear. Examples of switchgear found
More information