Benefits of Water-Cooled Systems vs. Air-Cooled Systems for Air-Conditioning Applications



Similar documents
Benefits. Air-Cooled Systems

Tim Facius Baltimore Aircoil

Optimization of Water - Cooled Chiller Cooling Tower Combinations

Presentation Outline. Common Terms / Concepts HVAC Building Blocks. Links. Plant Level Building Blocks. Air Distribution Building Blocks

ASHRAE Boston Chapter Meeting Designing AC Refrigeration Systems Lessons Learned February 11, 2014

Agenda. Part I: Introduction to OptimumHVAC. Part II: Initial Energy Savings Analysis for MCO Main Terminal. Part III: Case Studies & Conclusion

Heating & Cooling Efficiency

GEOTHERMAL HEAT PUMP SYSTEMS ARE RED HOT BUT ARE THEY REALLY GREEN?

Wet Bulb Temperature and Its Impact on Building Performance

POLK STATE COLLEGE CHILLER PLANT EVALUATION WINTER HAVEN, FLORIDA APRIL 2, C arastro & A ssociates, C&A# 5747

OPTIMIZING CONDENSER WATER FLOW RATES. W. A. Liegois, P.E. Stanley Consultants, Inc. Muscatine, Iowa

COMMERCIAL HVAC CHILLER EQUIPMENT. Air-Cooled Chillers

Creating Efficient HVAC Systems

ENERGY EFFICIENT HVAC DESIGN FOR WARM-HUMID CLIMATE CLIMATE

EnergyPro Building Energy Analysis. Assisted Living Building

Appendix C. Minimum Equipment Efficiency Standards

DATA CENTER COOLING INNOVATIVE COOLING TECHNOLOGIES FOR YOUR DATA CENTER

How To Design A Building In New Delhi

Heating, Ventilation & Air Conditioning Equipment

CRITICAL COOLING FOR DATA CENTERS

Water cooled chiller plant (cp/vs)

ADVANCES IN SUPERMARKET REFRIGERATION SYSTEMS

Defining Quality. Building Comfort. Precision. Air Conditioning

Tips and Tricks for Estimating Energy Savings. Celeste Cizik, P.E. Project Manager E M C Engineers, Inc.

*At the AHRI Standard flow rate of 3 gpm/ton, using today s efficient chillers, the ΔT is 9.3 F rather than the 10 F often assumed.

Maximize energy savings Increase life of cooling equipment More reliable for extreme cold weather conditions There are disadvantages

HVACPowDen.xls An Easy-to-Use Tool for Recognizing Energy Efficient Buildings and HVAC Systems

Denver International Airport Total Facility Optimization. Josh Foerschler Aurom Mahobian

HVAC For Schools How to purchase an HVAC system that meets your school s unique requirements and stays within your budget

HVAC Systems: Overview

HIGH PERFORMANCE CHILLED WATER SYSTEMS. EarthWise HVAC. EarthWise HVAC High Performance CHW Plants

Heating, Ventilation & Air Conditioning Equipment

CHILLER PLANT CONTROL MULTIPLE CHILLER CONTROLS

FINAL REPORT LIFE-CYCLE COST STUDY OF A GEOTHERMAL HEAT PUMP SYSTEM BIA OFFICE BLDG., WINNEBAGO, NE

How to Build a Data Centre Cooling Budget. Ian Cathcart

85 F 80 F 50% 75 F 70 F 73.0/ F 10% Figure 1

District Cooling Plant : Refrigeration Plant Simulation

Hines Property Management, NYC

Section 2: Estimating Energy Savings and Incentives

ELECTRICAL ENERGY REDUCTION IN REFRIGERATION AND AIR CONDITIONING Ken Landymore, Director of Operations, Smartcool Systems Inc.

Energy Audits Waste Water Treatment Plants

DEEMED SAVINGS TECHNICAL ASSUMPTIONS

Calculating System Flow Requirements

Variable Refrigerant Flow Systems

The main steam enters the building in the basement mechanical room; this is where the condensate line also leaves the building.

Achieving ENERGY EFFICIENCY with Standard Air-Conditioning Units. Mike West, PhD, PE Advantek Consulting, Inc

Model-Based Approach for Optimizing a Data Center Centralized Cooling System

HEAT RECOVERY FROM CHILLED WATER SYSTEMS. Applications for Heat Reclaim Chillers

Cooling Efficiency Summary of 60-Day Notice - First Steps

Cooling Systems 2/18/2014. Cooling Water Systems. Jim Lukanich, CWT ChemCal, Inc. Grapevine, TX

Selection Tips For Air-Conditioning Cooling Systems

What are the Carrier ChillerVu Energy Dashboards?

HOW TO CONDUCT ENERGY SAVINGS ANALYSIS IN A FACILITY VALUE ENGINEERING STUDY

Energy Efficiency: Integrated Design and HVAC Systems HEALTHCARE - TOP 5 GREEN BUILDING STRATEGIES

CURBING THE COST OF DATA CENTER COOLING. Charles B. Kensky, PE, LEED AP BD+C, CEA Executive Vice President Bala Consulting Engineers

Typical Cooling Load Profile

ULTRA-EFFICIENT HVAC DESIGN AND CONTROL

Rittal White Paper 507: Understanding Data Center Cooling Energy Usage & Reduction Methods By: Daniel Kennedy

Condensate Free Water

In the compression-refrigeration loop (air conditioning), which is likely to be warmer? 1. Condenser coil 2. Evaporator coil

COMMERCIAL HVAC EQUIPMENT. Condensers and Cooling Towers

HVAC Basic Science - System Capacity

Data Realty Colocation Data Center Ignition Park, South Bend, IN. Owner: Data Realty Engineer: ESD Architect: BSA LifeStructures

AIR CONDITIONING EFFICIENCY F8 Energy eco-efficiency opportunities in Queensland Foundries

Sea Water Heat Pump Project

Free Cooling in Data Centers. John Speck, RCDD, DCDC JFC Solutions

Digital Realty Data Center Solutions Digital Chicago Datacampus Franklin Park, Illinois Owner: Digital Realty Trust Engineer of Record: ESD Architect

News in Data Center Cooling

Direct Fresh Air Free Cooling of Data Centres

SECTION 5 COMMERCIAL REFRIGERATION UNIT 22 CONDENSERS

HVAC Technologies for Building Energy Efficiency Improvements 2013 National Symposium on Market Transformation. Richard Lord Carrier Fellow

This presentation is posted for public use. ACEEE does not endorse any product or service.

Q Utility Rebate Report. Houston, TX

Pharmaceutical central utility plants

DEVELOPMENT OF ENERGY TRACKING SYSTEM

Geothermal Heat Pump Systems

Commissioning - Construction Documents (Page 1 of 6)

Rules of Thumb Energy Efficiency in Buildings

CONDENSER AIR PRE-COOLER RETROFITS FOR ROOFTOP UNITS

Energy Efficiency in New and Existing Data Centers-Where the Opportunities May Lie

9. ENERGY PERFORMANCE ASSESSMENT OF HVAC SYSTEMS

Preliminary Final Proposal

A Feasibility of Geothermal Cooling in Middle East

Case Study: Innovative Energy Efficiency Approaches in NOAA s Environmental Security Computing Center in Fairmont, West Virginia

STULZ Water-Side Economizer Solutions

Recommendations for Measuring and Reporting Overall Data Center Efficiency

National Grid Your Partner in Energy Solutions

Lawrence Berkeley National Laboratory Lawrence Berkeley National Laboratory

VertiCool Space Saver 2 to 15 tons Water-Cooled and Chilled Water

Q Utility Rebate Report. Fort Worth, TX

Data Center Design Guide featuring Water-Side Economizer Solutions. with Dynamic Economizer Cooling

Building Energy Systems. - HVAC: Heating, Distribution -

THE ROOFPOINT ENERGY AND CARBON CALCULATOR A NEW MODELING TOOL FOR ROOFING PROFESSIONALS

Data Center Planning. PUE Overview

The next generation of geothermal systems for school buildings

10 Strategic Steps to Reducing Your Energy Costs AEE Regional Chapter Meeting February 2, 2005

Transcription:

Benefits of Water-Cooled Systems vs. Air-Cooled Systems for Air-Conditioning Applications Kavita A. Vallabhaneni

U. S. Government commitment to reduce greenhouse gas emissions can have a significant impact on HVAC system consideration

Kyoto Conference on Global Warming International effort to control greenhouse gas emissions Greenhouse gasses include: Carbon Dioxide (CO 2 ) Methane (CH 4 ) Nitrous Acid (N 2 0) Hydrofluorocarbons (HFC s) Perflurocarbons (PFC s) Sulfur Hexafluorides (SF 4 )

U. S. Commitment to Kyoto Conference Kyoto Protocol signed by President Bill Clinton in October, 1997 Committed U. S. to reduce greenhouse gas emissions to 7% below 1990 levels by 2012 President Bush rejected the Kyoto Protocol and has argued that the treaty was wrong to exempt developing nations like China and India, and would hurt the U.S. economically. U.S. has chosen another policy. But we have the same targets, and we have to meet the same problems.

U. S. Greenhouse Gas Emissions by Component, 2001

U. S. Greenhouse Gas Emissions Carbon Dioxide (CO 2 ) emissions account for approximately 85% of the U. S. greenhouse gas emissions.

Major CO 2 Emissions Sources Transportation Industry Heavy Industry Utility Industry

Major CO 2 Emission Sources Utility Industry Fossil Fuel Burning Power Plants Produce 55% of U. S. electricity Addition of exhaust gas scrubbers not economically viable for most plants Only 16% of Power Plants have exhaust scrubbers.

US Gov t Plan to Reduce CO 2 Emissions from Power Plants Convert to less carbon intensive fuels or non-carbon fuels Taxation of carbon fuels Regulation of emissions for new plants Reduce energy demand New energy-saving technologies Improve efficiency of equipment and systems

Fossil Fuel Burning Power Plants Air-conditioning systems drive many power plant peak loads and have been identified as an energy reduction opportunity.

U. S. Actions Impacting HVAC Systems and Equipment Energy Policy Act of 1992 ASHRAE Standard 90.1 as basis for energy efficiency for commercial buildings.

Energy Saving System Designs our Environmental Responsibility

Basic Air-Conditioning System Large Buildings (> 400 tons) Water cooled systems provide clear-cut economic and environmental justification. Mid-size Buildings (200-400 tons) Air cooled systems may offer first cost incentive to sacrifice energy efficiencies of water cooled systems.

Theoretical Building Profile Building load 400 tons Building Configuration Square with five (5) floors One (1) air handling fan/ floor Air Volume 350 CFM/ton 3 ½ w. g. T. S. P.

400 Ton System Comparisons Chiller systems: Air-Cooled Chiller Centrifugal Chiller Packaged systems: Roof-Top Units Self-Contained Units

400 Ton System Comparisons Compare five components System energy requirements Installed cost Annual energy cost Annual water usage & cost Payback analysis

System Energy Requirements 400 Ton Air-Cooled System Compressor Condenser Fans Air Handling Units Chilled H 2 0 pump Total KW KW/Unit 406.00 62.50 22.37 14.92 Total KW 406.00 62.50 111.85 14.92 595.27 KW/Ton = 595.27/400 = 1.49 KW/ton

System Energy Requirements 400 Ton Centrifugal Chiller System Compressor Air Handling Units Chilled H 2 0 pump Condenser H 2 0 pump Cooling tower fan Total KW KW/Unit 220.0 22.37 14.92 11.19 18.65 Total KW 220.00 111.85 14.92 11.19 18.65 376.61 KW/Ton = 376.61/400 = 0.94 KW/ton

Theoretical 400 Ton System Comparisons Chiller systems Air-cooled chiller system 1.49 KW/ton Centrifugal chiller system 0.94 KW/ton

System Energy Requirements 400 Ton Roof-Top System : (5) 80 Ton Units Compressor Air handling fan Condenser fan Total KW KW/Unit 74.65 29.84 8.60 Total KW 373.25 149.20 43.00 565.45 KW/Ton = 565.45/400 = 1.42 KW/ton

System Energy Requirements 400 Ton Self-Contained System : (5) 80 Ton Units Compressor Air handling fan Condenser H 2 0 pump Cooling tower fan Total KW KW/Unit 63.12 22.37 11.19 18.75 Total KW 315.60 111.85 11.19 18.75 457.39 KW/Ton = 457.39/400 = 1.14 KW/ton

System Energy Comparison Chiller systems Air-cooled chiller system 1.49 KW/ton Centrifugal chiller system 0.94 KW/ton Packaged systems Roof-top units 1.42 KW/ton Self-Contained units 1.14 KW/ton

Basic HVAC System Options Water-cooled systems More energy-efficient than air-cooled systems Support environmental efforts to control greenhouse gas emissions

Installed Cost Estimate Sources Air Cooled Chiller.. $350/Tr x 1.50 Centrifugal Chiller..$250/Tr x 1.50 Roof Top Units.. $550/Tr x 1.25 Self Contained Units.$400/Tr x 1.50 Air Handling Units.$1.00/CFM x 1.25 Cooling Towers.$45/Tr x 1.50 Pump/Piping..Means Mech. Est.

Installed Cost Estimate Air Cooled Chiller System 400 ton air cooled chiller $210,000 (5) 28,000 CFM air handlers.$175,000 1000 LF chilled water piping..$ 67,000 Chilled water pump $ 3,600 Total installed cost.$455,600

Installed Cost Estimate Centrifugal Chiller System 400 ton centrifugal chiller. $150,000 400 ton cooling tower...$ 27,000 (5) 28,000 CFM air handlers...$175,000 1000 LF chilled H 2 0 piping. $ 67,000 400 LF condenser H 2 0 piping. $ 26,800 Chilled water pump..$ 3,600 Condenser water pump.. $ 4,000 Mechanical equipment room... $ 45,000 Total Installed Cost...$498,400

Installed Cost Estimate Roof-Top Unit System (5) 80 ton roof top units. Installed cost $275,000

Installed Cost Estimate Self-Contained Unit System (5) 80 ton self-contained units.. $240,000 Closed Circuit Cooling Tower $ 54,000 Condenser water pump..$ 4,000 Condenser water piping..$ 26,800 Installed cost $324,800

Installed Cost Summary Chiller Systems Air-Cooled Chiller Centrifugal Chiller Installed Cost $455,600 $498,400 Packaged Systems Roof-Top Self-Contained $275,000 $324,800

System Energy Cost Assumptions 1800 Equivalent Full Load Hours per Year $0.06 per KW-Hour $12 per KW Demand Charge for 6 Months

Annual Energy Cost Comparison Total KW Annual Energy Cost Annual Demand Cost Total Annual Cost Chiller System Air-Cooled Chiller 595.27 $64,289 $42,860 $101,149 Centrifugal Chiller 376.61 $40,674 $27,116 $ 67,790 Packaged Systems Roof-Top 565.45 $61,069 $40,712 $101,781 Self-Contained 457.39 $49,398 $32,932 $ 82,330

System Cost Summary Chiller System Air-Cooled Chiller Centrifugal Chiller Packaged System Roof-top Self-contained Installed Cost $455,600 $498,400 $275,000 $324,800 Annual Energy Cost $107,149 $ 67,790 $101,781 $ 82,330

Water Usage Water cooled systems recycle 95% of the total water The remaining 5% is lost to evaporation & bleed. A small portion of the water is bled from the system to control the build-up of impurities Bleed Rate = Evaporation Rate Cycles of Concentration -1

Water Usage and Cost (400 ton sample system) Evaporation Rate = 3.0 GPM/100 ton = 12.0 GPM/400 ton system

Water Usage and Cost (400 ton sample system) Evaporation Rate = 3.0 GPM/100 ton = 12.0 GPM/400 ton system Bleed Rate = 12.0 GPM 4 cycles 1 Bleed Rate = 4.0 GPM

Water Usage and Cost (400 ton sample system) Evaporation Rate = 3.0 GPM/100 ton = 12.0 GPM/400 ton system Bleed Rate = 12.0 GPM 4 cycles 1 Bleed Rate = 4.0 GPM Consumption = Evaporation + Bleed = 12.0 GPM + 4.0 GPM = 16.0 GPM

Water Usage and Cost (400 ton sample system) Annual Water Consumption 16.0 GPM x 60 min/hr x 1800 eq FLH 1,728,000 gallons/year Annual Water and Sewer Cost 1,728,000 gallons x $3.00/1000 gal $5,184

Water Quality and Control Cost Considerations Water-cooled systems require chemical treatment to control scale/corrosion and biological growths These costs must be included in a cost analysis of water-cooled and air-cooled systems

Annual Water Treatment Costs (400 ton sample system) Full Service Water Treatment Average annual program costs - $1.00/ton/month 400 Tr x $1.00/ton/month x 6 month = $2400/year

Annual Water Cost Estimate (400 ton sample system) Water Consumption Water Treatment Annual Water Cost $5,184 $2,400 $7,584

System Cost Summary Installed Cost Annual Energy Cost Annual Water Cost Chiller Systems Air Cooled Chiller $455,600 $107,149 N/A Centrifugal Chiller $498,400 $67,790 $7,584 Packaged System Roof-Top Units $275,000 $101,781 N/A Self-Contained $324,800 $82,330 $7,584

System Cost Summary Installed Cost Annual Energy Cost Annual Water Cost Payback Yrs Chiller Systems Air-Cooled Chiller $455,600 $107,149 N/A Base Centrifugal Chiller $498,400 $67,790 $7,584 1.3 Packaged system Roof-Top Units $275,000 $101,781 N/A Base Self-Contained $324,800 $82,330 $7,584 4.2

HVAC System Considerations Cost analysis must consider the economic impact that environmental and electric power generation issues will have on energy prices in the near future.

Projected Energy Prices for Commercial Market* Projected Energy Price Increase (P V ) 2025Projected Increase..+ 32.05% * per 2005 Energy Information Administration (EIA) report

2025 Simple Payback Analysis Installed Cost Annual Energy Cost Annual Water Cost Chiller System Air-Cooled Chiller $455,600 $141.490 N/A Centrifugal Chiller $498,400 $89,517 $7,584 Packaged System Roof-Top Units $275,000 $134,402 N/A Self-Contained $324,800 $108,717 $7,584

2025 Simple Payback Analysis Installed Cost Annual Energy Cost Annual Water Cost Payback Yrs Chiller System Air-Cooled Chiller $455,600 $141,490 N/A Base Centrifugal Chiller $498,400 $89,517 $7,584 0.75 Packaged System Roof-Top Units $275,000 $134,402 N/A Base Self-Contained $324,800 $108,717 $7,584 1.1

Deregulation of Electric Power Generation Industry

Electric Power Industry Generation Transmission Distribution

Deregulation Changed since 2001 Consolidation efforts are taking place Con Edison merging with Excelon Fewer number of companies = higher prices for the customer Some utilities are modeling Demand Response models

Energy Saving System Designs. our Environmental Responsibility

Energy Saving System Designs. our Fiscal Responsibility

EPA Climate Wise Program Wise Rules to Energy Efficiency Process Cooling Wise Rule 1. Installing energy efficient chillers and refrigeration systems can save 1.2% of a facility s total energy use with an average simple payback of 23 months. Process Cooling Wise Rule 2. Free cooling with cooling tower water can reduce a facility's total energy use by about 1% with an average simple pay back of 14 months.

EPA Climate Wise Program Wise Rules to Energy Efficiency Process Cooling Wise Rule 3. Free cooling can reduce cooling system energy use by as much as 40% depending on location and load profile. Process Cooling Wise Rule 4. Increasing chilled water temperature by 1 F reduces chiller energy use by 0.6% to 2.5%.

EPA Climate Wise Program Wise Rules to Energy Efficiency Process Cooling Wise Rule 5. Reducing condenser pressure by 10 psi can decrease refrigeration system energy use per ton of refrigeration by about 6%. Process Cooling Wise Rule 6. For each degree decrease in condenser cooling water temperature, until optimal water temperature is reached, there is a decrease in chiller energy use by up to 3.5%.

There s simply no substitute for raw (chiller) efficiency

Equipment Cost Comparison* Centrifugal Chiller First Cost $250/ton Means Mechanical Cost Data

Equipment Cost Comparison* Centrifugal Chiller First Cost Cooling Tower First Cost $45/ton $250/ton Means Mechanical Cost Data

Energy Saving Tip Lower the design condenser water temperature

ARI Nominal Condenser Water Rating Condition 3 GPM/Ton 10 F Temperature Rise 85 F Condenser Water

Cooling Towers can be economically selected to provide condenser water temperatures within 4 F or less of the ambient wet bulb temperature

Effect of Condenser Water Temperature on Chiller Energy CW Temp 85 F 83 F 80 F 75 F 70 F Typ Chiller Energy 0.570 kw/ton 0.542 kw/ton 0.524 kw/ton 0.484 kw/ton 0.450 kw/ton Energy Savings Base 5% 8% 15% 21%

Rule of Thumb for Saving Chiller Energy Chiller energy is reduced 2% for every 1 F of reduced condenser water temperature.

Typical Office Building 500 Ton System Operating Season 8 Months/Year 2,500 Equiv. Full Load Hours $0.08/kWH Energy Rate $10/kW Demand Charge

System Economics with Energy Saving Cooling Tower Nominal Cooling Tower Selection 1500 gpm 95/85/78 F 30 HP Fan Motor

System Economics with Energy Saving Cooling Tower Nominal Cooling Tower Selection 1500 gpm 95/85/78 F 30 HP Fan Motor Energy Saving Cooling Tower Selection 1500 GPM 93/83/78 F 30 HP Fan Motor

System Economics with Energy Saving Cooling Tower Nominal Cooling Tower Selection 1500 gpm 95/85/78 F 30 HP Fan Motor Energy Saving Cooling Tower Selection 1500 GPM 93/83/78 F 30 HP Fan Motor First Cost Premium........$7800

Chiller Energy Savings with 2 F Colder Condenser Water Typical Chiller Energy Based on 85 F Condenser Water: 0.570 kw/ton

Chiller Energy Savings with 2 F Colder Condenser Water Typical Chiller Energy Based on 85 F Condenser Water: Typical Chiller Energy Based on 83 F Condenser Water: 0.570 kw/ton 0.542 kw/ton

Chiller Energy Savings with 2 F Colder Condenser Water Typical Chiller Energy Based on 85 F Condenser Water: Typical Chiller Energy Based on 83 F Condenser Water: 0.570 kw/ton 0.542 kw/ton Saves 0.028 kw/ton

Annual Energy Savings with 2 F Colder Condenser Water Chiller Peak Energy Reduction..0.028 kw/ton 500 Ton System..500 Tons Equivalent Full Load Hours/Year...2,500 Hours Energy Cost..x 0.08 $/kwh Energy Savings.. $2,800 Demand Savings (0.028kW/ton x 500 tons x $10/kW x 8 months) $1,120 Total Annual Energy Savings $3,920

Payback Period for 2 F Colder Condenser Water Cooling Tower First Cost Premium Annual Energy Cost Savings = $7800 $3920 = 2.0 Year Payback

Total Energy Savings 20 Year System Life 700, 000 kwh saved $ 78,400 Saved

Energy Saving Tip Evaluate the additional free cooling hours with low design water temperatures

Additional Free Cooling Energy Savings 250 Ton Winter Load 55 F Building Loop Water 52 F Condenser Water

System Economics with Energy Saving Cooling Tower Nominal Cooling Tower Selection 1500 gpm 95 /85 /78 F 30 HP Fan Motor Winter WB = 46.5 F 4007 Hours

System Economics with Energy Saving Cooling Tower Nominal Cooling Tower Selection 1500 gpm 95 /85 /78 F 30 HP Fan Motor Winter WB = 46.5 F 4007 Hours Energy Saving Cooling Tower Selection 1500 gpm 93/83/78 F 30 Hp Fan Motor Winter WB = 48.41 4438 Hours

System Economics with Energy Saving Cooling Tower Nominal Cooling Tower Selection 1500 gpm 95 /85 /78 F 30 HP Fan Motor Winter WB = 46.5 F 4007 Hours Energy Saving Cooling Tower Selection 1500 gpm 93/83/78 F 30 Hp Fan Motor Winter WB = 48.41 4438 Hours Additional Energy Savings..$ 4265

Payback Period for 2 F Colder Condenser Water Cooling Tower First Cost Premium Annual Energy Cost Savings = $7800 $3920 +$4265 < 1.0 Year Payback

Total Energy Savings 20 Year System Life 1,766,700 kwh Saved $163,700 Saved

Energy Saving Tip Take advantage of ambient wet bulb temperatures

ASHRAE 0.4% Wet Bulb Temperatures Location Baltimore, MD New York, NY Boston, MA Los Angeles, CA Seattle, WA Denver, CO Wet Bulb 78 F 76 F 75 F 70 F 66 F 65 F

ASHRAE 0.4% Wet Bulb Temperatures Location Baltimore, MD New York, NY Boston, MA Los Angeles, CA Seattle, WA Denver, CO Wet Bulb 78 F 76 F 75 F 70 F 66 F 65 F CWT 85 F 83.5 F 82.7 F 80.5 F 76.0 F 75.0 F

ASHRAE 0.4% Wet Bulb Temperatures Location Wet Bulb CWT Energy Baltimore, MD 78 F 85 F 0.57 kw/t New York, NY 76 F 83.5 F 0.55 kw/t Boston, MA 75 F 82.7 F 0.54 kw/t Los Angeles, CA 70 F 80.5 F 0.53 kw/t Seattle, WA 66 F 76.0 F 0.49 kw/t Denver, CO 65 F 75.0 F 0.48 kw/t

ASHRAE 0.4% Wet Bulb Temperatures Location Wet Bulb CWT Energy Save Baltimore, MD 78 F 85 F 0.57 kw/t Base New York, NY 76 F 83.5 F 0.55 kw/t $2K Boston, MA 75 F 82.7 F 0.54 kw/t $3K Los Angeles, CA 70 F 80.5 F 0.53 kw/t $4K Seattle, WA 66 F 76.0 F 0.49 kw/t $6K Denver, CO 65 F 75.0 F 0.48 kw/t $9K

Energy Saving Tips Tip #1 Lower the Design Condenser Water Temperature. Tip #2 Evaluate Additional Free Cooling Hours. Tip #3 Take Advantage of Low Ambient Wet Bulb Temperatures.

Conclusion Air-conditioning system evaluations should take the pending impact of environmental issues into consideration Water cooled systems provide the most energy efficient systems and can help protect building owners and operators from uncertainties in electricity pricing.

Benefits of Water-Cooled Systems vs. Air-Cooled Systems for Air-Conditioning Applications Kavita A. Vallabhaneni