Wide Area Monitoring Current Continental Europe TSOs Applications Overview



Similar documents
System Protection Schemes in Eastern Denmark

Synchronized real time data: a new foundation for the Electric Power Grid.

Substation Automation Systems. We are exceptional grid stability PSGuard Wide Area Monitoring System

Allen Goldstein NIST Synchrometrology Lab Gaithersburg, MD

Evolution of Control for the Smart Transmission Grid

Hybrid processing of SCADA and synchronized phasor measurements for tracking network state

Wide Area Monitoring, Control, and Protection

CO-ORDINATION OF PARALLEL AC-DC SYSTEMS FOR OPTIMUM PERFORMANCE

Transmissão em Corrente Contínua

COMPARISON OF THE FACTS EQUIPMENT OPERATION IN TRANSMISSION AND DISTRIBUTION SYSTEMS

PHASOR MEASUREMENT UNIT (PMU) AKANKSHA PACHPINDE

FRCC Standards Handbook. FRCC Automatic Underfrequency Load Shedding Program. Revision Date: July 2003

FACTS. Solutions to optimise network performance GRID

Smart Grid: Concepts and Deployment

Modern Power Systems for Smart Energy Society

Power System review W I L L I A M V. T O R R E A P R I L 1 0,

APPLICATION CASE OF THE END-TO-END RELAY TESTING USING GPS-SYNCHRONIZED SECONDARY INJECTION IN COMMUNICATION BASED PROTECTION SCHEMES

Guidelines for Large Photovoltaic System Integration

Reactive Power and Importance to Bulk Power System OAK RIDGE NATIONAL LABORATORY ENGINEERING SCIENCE & TECHNOLOGY DIVISION

Test & Data Management Software

AORC Technical meeting 2014

Design and Implementation of SCADA System Based Power Distribution for Primary Substation ( Monitoring System)

BIGDATAANALYTICS FOR ELECTRICPOWERGRID OPERATIONS MANU PARASHAR CORPORATE POWER SYSTEMS ENGINEER JULY 29, 2015

The design and performance of Static Var Compensators for particle accelerators

Power transformers. Phase shifting transformers Reliable and efficient power flow control

White Paper. Convergence of Information and Operation Technologies (IT & OT) to Build a Successful Smart Grid

Requirements for Offshore Grid Connections. in the. Grid of TenneT TSO GmbH

DC TRANSMISSION BASED ON VOLTAGE SOURCE CONVERTERS

Nuclear Power Plant Electrical Power Supply System Requirements

AMI and DA Convergence: Enabling Energy Savings through Voltage Conservation

Electric utilities may vary in their application of end-to-end testing

Everything you need for protection scheme testing

INTELLIGENT DISTRIBUTION NETWORK ANALYSIS AND INFORMATION ARCHITECTURE DESIGN

TDMS Test & Data Management Software

SOLARCARE SERIES PRODUCT AND APPLICATION GUIDE

DDX 7000 & Digital Partial Discharge Detectors FEATURES APPLICATIONS

Monitoring Underground Power Networks

General Validation Test Program for Wind Power Plants Connected to the Hydro-Québec Transmission System

Data Mining to Characterize Signatures of Impending System Events or Performance from PMU Measurements

ABB PSPS Erich Steinmann; Generator control-2013

POWER TRANSMISSION FROM OFFSHORE WIND FARMS

For a phase-to-phase voltage between 100 V and 1000 V. The standard ratings are: 400 V V V (at 50 Hz)

PMCS. Integrated Energy Management Solution. Unlock the Full Potential of Power Networks Through Integration. Complete Solution. Informed Decisions

data integration/exchange part 2: future technical and business opportunities

Current and voltage measuring relays

UNIVERSITETET FOR MILJØ- OG BIOVITENSKAP. Smartgrid. Terje Gjengedal. The Norwegian University of Life Sciences.

Load Dispatcher (Class Code 5223) Task List

ends of transmission line are used for relay operation [70]. Another type of

PacifiCorp Original Sheet No. 476 FERC Electric Tariff, Substitute 6 th Rev Volume No. 11 APPENDIX 2 TO SGIP

Integration of Distributed Generation in the Power System. IEEE Press Series on Power Engineering

Isolated-Parallel UPS Configuration

Preparing for Distributed Energy Resources

Chapter 5. System security and ancillary services

Industrial IT for Substation Automation & Protection

Data Management Issues associated with the August 14, 2003 Blackout Investigation

HVDC-VSC: transmission technology of the future

SCADA. The Heart of an Energy Management System. Presented by: Doug Van Slyke SCADA Specialist

MINISTERIE VAN ECONOMISCHE ZAKEN GENERAL COST COMPARISON BETWEEN UNDERGROUND CABLES AND O.H. LINE SYSTEMS FOR H.V. TRANSMISSION

ECE 586b Course Project Report. Auto-Reclosing

XI Seminário Técnico de Proteção e Controle 18 a 21 de novembro de 2012 Florianópolis Santa Catarina Brasil

HVDC. A firewall against disturbances in high-voltage grids. Lennart Carlsson

Engineering innovation

Advanced Distribution Grid Management for Smart Cities

HVDC Light, a tool for electric power transmission to distant loads

DIMENSIONING OF CURRENT TRANSFORMERS FOR PROTECTON APPLICATION

Network Code on Operational Security

CONSULTATION PAPER FOR PROPOSED MODIFICATIONS TO THE TRANSMISSION CODE

REAL TIME DYNAMICS MONITORING SYSTEM (RTDMS ) AND PHASOR GRID DYNAMICS ANALYZER (PGDA) USER TRAINING FOR ERCOT

Oscillation Monitoring System

PSS SINCAL - Overview -

Big Data Analytics Applications in Distribution Operations and Risk Assessment

(2) Words and expressions used and not defined in these regulations but defined in the Act shall have the meaning assigned to them in the Act.

PSS E. High-Performance Transmission Planning Application for the Power Industry. Answers for energy.

DDX 7000 & Digital Partial Discharge Detectors FEATURES APPLICATIONS

Online Transformer Insulation Monitoring System BushingGard Product Focus. Maximizing Transformer Uptime and Reliability

Topics. HVDC Fundamentals

1. Introduction Synchrophasor Technologies... 1

SCADA Controlled Multi-Step Automatic Controlled Capacitor Banks & Filter Banks

What Matters for Successful Integration of Distributed Generation

Magnus Callavik, ABB Power Systems, HVDC, Västerås, Sweden Phone: +46(0)

ENTSO-E Network Code on Emergency and Restoration

Agenda do Mini-Curso. Sérgio Yoshio Fujii. Ethan Boardman.

Study to Determine the Limit of Integrating Intermittent Renewable (wind and solar) Resources onto Pakistan's National Grid

..OR How To Protect your 3-Phase Equipment Investment with 3-Phase Monitors from Time Mark...

How To Choose A Transformer

Coordination of Telecommunications Surge Protective Devices in Countries with Unstable AC Power

T Substation Maintenance and Commissioning Test Equipment

Development of Monitoring, Protection, and Control Technologies & Impact on Modern Electric Networks. Vahid Madani

ENTSO-E Working Draft Network Code on Emergency and Restoration

Current Transformers

Big Data and Advanced Analytics Technologies for the Smart Grid

SCADA Systems Automate Electrical Distribution

Transient analysis of integrated solar/diesel hybrid power system using MATLAB Simulink

Synchrophasors Redefining SCADA Systems

Digital Energy ITI. Instrument Transformer Basic Technical Information and Application

Special Publication. Operation and Monitoring of MSCDN-Systems

FACT SHEET. BSES, Delhi - Distribution Network. Power Systems Consultancy from ABB

Generator Stator Protection, under/over voltage, under /over frequency and unbalanced loading. Ramandeep Kaur Aujla S.NO

Standards for smart grids with emphasis on their realization in remote and rural areas

Federal Wage System Job Grading Standards for Electric Power Controlling, Table of Contents

Transcription:

Wide Area Monitoring Current Continental Europe TSOs Applications Overview Version 5 System Protection & Dynamics Working Group 20th September 2015

1. Content 1. Content... 2 2. Introduction... 3 3. Main Application Examples and Tool Usage... 3 4. Conclusions and Outlook... 10 2

2. Introduction Power system operation has become more complex within the last years. Transmission system operators are faced with increasing challenges at the interface between power plant operators, industrial consumers, distribution system operators, balance responsible parties and regulatory authorities. Highly volatile power flow changes require enhanced tools for secure operation of the meshed transmission system. The importance of monitoring dynamic phenomena is also increasing due to the geographic expansion of the power system as well as the impact of the fast and dramatic changes of the power generation mix. On the other side, Wide Area Monitoring (WAM) has become a mature and reliable technology. Measurement of voltage and currents with phasor measurement units (PMUs) and treatment of special measured values as phasor values open new opportunities in data processing and increased system insight. Therefore, one of the key components is the exact time stamping of each measurand based on GPS time signals. Secondly data concentrators are able to acquire measurements from distant substations and overlap them precisely even in real time. By doing so enhanced information about the real state of the power system with respect to steady-state as well from dynamic point of view can be derived by using related application functions. Competition between important vendors has led to a significant high number of standard products available on the market for different either local or wide area applications. Based on a questionnaire distributed within the Continental European transmission system operators, a short overview of the current WAM tools in use and approaches is given in this report. 15 TSOs have responded by completing the pre-prepared form and 8 have delivered additional information about their individual applications including man-machine interface or special data activation and data processing techniques. 3. Main Application Examples and Tool Usage As the PMU devices themselves are derived either from protection relays or from RTUs coupled with transient recorders the measurements of voltage and current are gained either from the protection or the metering VT and CT cores correspondingly. As most of the current applications in use are related to the normal system operation conditions almost all TSOs acquire their WAM data via the metering CT and VT cores in order to maximise the measurement accuracy. One key component for the application of WAM systems is a reliable and secure telecommunication network as in principle the measured data get lost if they are not immediately transmitted to the central Phasor Data Concentrator (PDC) due to the fact that for the usual sampling rate of 20 or 100 milliseconds between two subsequent measuring points related buffering capabilities are very relevant. TSOs use dedicated communication channels with related firewall protection for the data package transport (IEEE 1344 and IEEE C37.118 format) from the substation to the central located data concentrator. However, the fact that PMU maintenance is performed by almost all TSOs currently only on ad hoc basis with low priority reflects the fact that we still deal with a new technology where not all processes are yet fully included in the state-of-the art TSOs applications. The phasor technology is based on exact time synchronisation by the means of GPS receivers. Some PMUs get their time signal from own receivers, others are synchronised by central substation GPS clocks. Both approaches have their own advantages and disadvantages as we know from long experience over the last year s applications in different power systems. Depending on the application functions either all three individual single phase measurands or only the positive sequence values are processed. In principle measurements and calculated values are 3

stored for a dedicated time before they are overwritten. Special automatically triggered or manual export functionalities create the basis for subsequent detailed analysis. Within the last year special focus was also put on the creation of interfaces to the classical stateof-the-art SCADA systems in such a way that information extracted from high resolution measurements based on PMU technique is used as an additional input and decision support. As WAM recordings deliver a perfect time synchronised picture of measurements from distant substations of geographical large interconnected systems in high resolution those recordings are ideal sources for dynamic model calibration. Main CE TSOs WAM Application Tools Transient Recorder Functionality As the WAM technology offers the big advantage to have a dedicated time stamp for each individual measurement sample, the overlapping of geographically distant measurands opens new opportunities for detailed dynamic system analysis. Consequently this functionality is used in most of the CE WAM systems as priority one application either for post-mortem fault analysis or as input for several on-line awareness tools or as a basis for dynamic model calibration. A set of pre-defined triggering conditions initiate automatic storage of measurements or the creation of alarms which partially are already transmitted to the TSOs main SCADA systems, e.g. inter-area oscillation detection. Line thermal monitoring Feeder related exact measurement of voltage and currents on both sides of a transmission line creates the possibility of accurate measurement of the active power losses along of a line. By the subsequent on-line calculation of the line resistance variation the average line temperature can be determined. However by using this method the hotspots will have to be identified with other methodologies but as the operator can control only one limit per line this method is quite useful and applicable wherever lines are equipped with PMUs on both ends. However, this might be used only as an additional tool for dynamic line rating applications. In Fig. 1 the line thermal monitoring interface from one WAM system as well as the related SCADA representation is shown. 4

Fig.1: Line thermal monitoring interface, Source: Swissgrid Voltage stability monitoring By the evaluation of the voltage for critical substations the generation of the nose curve is possible which generally also includes the calculated limit or distance to voltage instability. One example of the corresponding Man-Machine-Interface is depicted in Fig. 2. 5

Fig.2: Voltage stability monitoring interface, Source: HOPS Power oscillation monitoring With respect to monitoring of system stability challenges due to inter-area oscillations WAM systems offer different approaches for detecting the most critical oscillation modes together with their main parameters as oscillation frequency or time period as well as damping factor and oscillation amplitude. By a clever combination of e.g. damping ratio and oscillation amplitude intelligent alarms are derived in such a way that only in the case of extreme oscillation activity detected operation staff receives corresponding alarms. In Fig. 3 the output of one on-line power oscillation tool can be seen, (damping blue; frequency green; oscillation amplitude black colour). Fig. 3: Power Oscillation Monitoring output, Source: Energinet.dk 6

Power system restoration tool Taking advantage of the WAM high-resolution measurement principles with respect to accuracy as well as time resolution, this tools have demonstrated to be an useful tool for the power system restoration process as for system operation where monitoring of system dynamics is of crucial importance. In Fig. 4 measurements of a joint Italian-Swiss power system restoration test with voltage support from Switzerland are represented. All the related measurements were acquired with the help of WAM systems. 242 241 10:25 a.m.: CIRCUIT BREAKER LACCHIARELLA-CHIGNOLO LINE CLOSED 240 239 10:27 a.m.: CIRCUIT BREAKER MARTIGNONE-BARGI LINE CLOSED 10:47 a.m.: OUTAGE OF PRESENZANO GROUP 238 237 236 10:57-10: 59: REMESHING ACTIONS 235 234 233 232 10:41 a.m.: 231 230 229 228 227 226 225 10:31-10:32: VARIATION OF TAP CHANGER LAVORGO TRANSFORMER SYNCHRONIZATION OF PRESENZANO GROUP END OF THE TEST 10:34 a.m.: CIRCUIT BREAKER SUVERETOMONTALTO LINE CLOSED 10:51 a.m.: CIRCUIT BREAKER SUVERETOMONTALTO LINE OPENED 10:22 a.m.: CIRCUIT BREAKER MUSIGNANO-LAVORGO LINE CLOSED STARING POINT OF THE TEST 224 Phase-to-ground Voltage Phase-to-ground Voltage Phase-to-ground Voltage Fig. 4: Phase to ground voltages in Musignano substation during restoration test, Source: Terna Monitoring tools, awareness tools Of course, the man-machine interface for WAM systems offers a large variety of possibilities for power system state visualisation. Geographic system colouring base on voltage phase angle difference is used in order to show system corridor loading as the voltage phase angle difference is a good measure for enhanced representation of system loading. Secondly, either direct time domain curves or information extracted from fast system changes creates a mirror of system state in steady-state as well as in the dynamic dimension. For oscillation patterns even common used polar representation visualises on-line the current system stage. Single line graphics enriched with phasor information complete the picture and creates a first bridge between classical steady-state information and simplified dynamic information. Two examples of alarming and awareness interfaces are shown in Fig. 5, coloured map with angle differences and Fig. 6, voltage and voltage phase angle. 7

Fig. 5: Single Lin Graphic Online awareness Interface example, Source: TenneT DE 8

Fig. 6: Substation awareness, voltage magnitude and voltage phase angle, Source: REN On-line short-circuit power calculation By installing dedicated PMUs for monitoring eq. switchable shunt reactors, capacitors or filter batteries on the AC-side of HVDC interconnectors it is possible to on-line calculate the instantaneous available short-circuit power of that substation. This has proven especially useful for monitoring the available SC power at the LCC-type HVDC interconnectors in Denmark in operational situations with high wind power productions and thus few base-load power stations online. The challenge is to avoid commutation failures on the HVDC converters due to critical low SC power available while still running the system with a minimum number of base-load power stations in forced operation only to provide SC power. Basically the method works on sets of PMU measurements of voltage and current phasors immediately before and after switching on or off of e.g. a shunt reactor. The most challenging part has been to identify the most optimal sets of voltage and current phasors. At the corresponding PDC workbench the SC-calculation functionality has been automated in such a way that the SC-power is automatically calculated whenever a switching occurs on any of the monitored shunt devices. This gives the operator the possibility to perform a switching operation whenever he needs to check the (low) level of available SC-power in one of the monitored substations. The resulting SC-power is presented to the operator as depicted in Fig. 7. 9

Fig. 7: Automatic calculation of SC power following switching incident in Energinet.dk 400 kv substation BJS, Source: Energinet.dk. 4. Conclusions and Outlook Link to other systems, exchanges with other TSOs As Wide Area Monitoring only becomes really effective by exchanging data between distant substations of a meshed interconnected system, the Continental European TSOs have started in an early stage to interconnect their WAM systems too by creating corresponding links between their data concentrators. However, in order to avoid an overload of the common dedicated telecommunication backbone only the information of a few strategic PMUs is currently exchanged. In principle the purpose of using WAM systems is for each TSO divided into two main categories: a) Internal applications as e.g. corridor loading monitoring b) External applications such as inter-area oscillation monitoring This means that TSO-TSO WAM data exchange only requires exchange of a carefully selected subset of the TSOs measurands. 10

Open loop operation As shown above several commercially available systems provide decision support by online visualisation and early warning signals. These applications are constantly improving and extended with new functionalities Closed loop operation Even if currently in the CE power system all WAM applications are still open-loop applications that mean only for monitoring, reporting or alarming in the future this might change and be extended in different directions: 1) Use WAM measurements or information as input for special protection schemes (SPS) for complex protection applications which include dynamic information for different interfaces, or 2) Wide Area Control by closing the loop by using power electronics as actuators (HVDCcontrol, STATCOM, SVCs, PSS etc.) 3) SCADA improvement, introducing hybrid state estimation application, more feasible and fast by combining current state of the art state estimation with WAM based state measurements 4) Use of WAM system enhanced awareness information for subsequent dispatcher decisions/actions as e.g. inter-area oscillation detection and LFC blocking 11