(Master Slave Mode) 28-1. This chapter explains how to connect multiple HMIs.



Similar documents
Online simulator YES Broadcast command YES Extend address mode YES

Chapter 6 Window Operations

Chapter 6 Window Operations

Chapter 26 EasyPrinter

Panasonic FP. HMI Setting: Device Address:

KOYO DIRECT. HMI Setting: PLC Setting: Supported Series: KOYO DirectLogic series PLC DL05, DL06, DL105, DL205, DL305, and DL405 series.

CONTROLLER INFORMATION SHEET

The Answer to the 14 Most Frequently Asked Modbus Questions

SMS Alarm Messenger. Setup Software Guide. SMSPro_Setup. Revision [Version 2.2]

TECHNICAL NOTE TNOI32

Chapter 2 Utility Manager

MODBUS. Table Of Contents

4511 MODBUS RTU. Configuration Manual. HART transparent driver. No. 9107MCM100(1328)

TECHNICAL NOTE TNOI34

Chapter 3 Create an EasyBuilder Project... 2

7.7 Ethernet Communication (AFPX-COM5)

Custom Solutions Center. Users Guide. Low Cost OEM PackML Templates L02 Release. Version LC-1.0

Using these objects to view the process of the whole event from triggering waiting for processing until alarm stops. Define event content first.

APNT#1168 Modbus - Establishing Communications Hints

Using IDENT M System T with Modbus/TCP

DeviceMaster UP Modbus Controller to Controller Communication

Softstarters. Type PSTX Fieldbus communication, Built-in Modbus RTU. 1SFC132089M0201 April SFC132089M0201 1

Best gateway technologies

QuickPanel Control DeviceNet Master Communications Card (IC754DVNM01) Quick Start Guide. Thursday September 20, 2007

Connecting UniOP to Telemecanique PLC s

To perform Ethernet setup and communication verification, first perform RS232 setup and communication verification:

Bluetooth HC-06 with serial port module Easy guide

CMC-PD01 PROFIBUS DP Slave Communication Card Operation Manual

The technical aspects of V90 or V92 on two analogue telephone lines (both side PSTN) or a so called a point to point connections.

Accessing Diagnostics using a Dialup Modem

eztcp Technical Document Modbus/TCP of eztcp Caution: Specifications of this document may be changed without prior notice for improvement.

PLC Support Software at Jefferson Lab

IntesisBox. Making Building Automation go further. OPC Servers

Event Log. Chapter 7 Event Log Event Log Management Excel Editing Create a New Event Log... 9

TSX ETY 110 Module 8

Connecting to SQL server

FAQ Communication over IE

Toshiba Serial Driver Help Kepware Technologies

Modbus and ION Technology

Alcalde # 1822 Col. Miraflores C.P Guadalajara, Jal. Mexico MX 01 (33) y USA 001 (619) (San Diego, CA.

How to make a diagnostic on TeSysT to start the network?

User Manual Revision English Converter / Adapter Ethernet to RS232 / RS485 (Order Code: HD HD M HD HD M)

Tutorial: Configuring GOOSE in MiCOM S1 Studio 1. Requirements

GW-7552 PRIFIBUS/MODBUS GATEWAY

SAPIP GUI INSTALLATION. Table of Contents

Immotec Systems, Inc. SQL Server 2005 Installation Document

SSL (Secure Socket Layer)

User's Guide. Using RFDBManager. For 433 MHz / 2.4 GHz RF. Version

How To Connect A Directsofl To A Powerpoint With An Acd With An Ctel With An Dm-Tel Modem On A Pc Or Ipad Or Ipa (Powerpoint) With A Powerline 2 (Powerline

1. MOXA NPort Express TCP/IP to RS-232 server

IR-210/712A + TouchPAD

Non-ThinManager Components

Event Log. Chapter 7 Event Log Event Log Management Excel Editing Create a New Event Log... 10

Technical Information Sheet Page 1 of 8

PP8X Printer Driver Installation Instruction

rs-ba1 remote control software quick reference guide

EasyAccess User s Manual

Modbus Server SAMSUNG Air Conditioners

KCU-02 Monitor. Software Installation User Manual. For Windows XP and Windows 7

Start-up of IVI-KHD2-4HRX, IVI-KHA6-4HRX at S7-300 V1.1. Table of Contents TABLE OF CONTENTS... 1

MiraCosta College now offers two ways to access your student virtual desktop.

Centurion PLUS CPC4 Download Guide

enervista UR Setup Software Quick Connect Instructions:

Configuring the Beckhoff BK9000 Network Parameters

[USING THE NM150 WITH ADULTICIDING] July 13, 2015

MODBUS MASTER/SLAVE Serial and Ethernet Communication Server

Programming Flash Microcontrollers through the Controller Area Network (CAN) Interface

Driver Installation and Hyperterminal Operation of iload Digital USB Sensors

Silver Series EM Operator Interface Terminals. Addendum to EZwarePlus Programming Manual

How to Setup PPTP VPN Between a Windows PPTP Client and the DIR-130.

s!nus-elektrotechnikai bt. Industrial IT & Automation

This guide will show you how to configure a Windows Mobile 6 PDA for Bluetooth connection to the KBM Systems OBDKey Bluetooth device.

Multi-Master DF1 Protocol User Guide

New OBD Smart PC Tool User Manual

SEC 4100 SYSTEM MONITOR Programmable Serial Interface Card Series 2

FBs-CM25/CM55/CBE. Ethernet Module. User s Manual

WinSCP for Windows: Using SFTP to upload files to a server

Handheld LPC Utility Software for Windows. Operation Manual

IntesisBox Modbus Server SAMSUNG Air Conditioners

Scalable PLC AC500 Communication AC500 Modbus TCP. ABB Group Version 3.1 ( ) Technical Guides

UPS Monitoring Software. User manual Borri Power Guardian

1 INTRODUCTION. This document describes the procedure to upgrade LTMR.

RcWare SoftPLC Modbus server mapping editor User manual

MT-350 SMS. Operation Manual. PORTech Communications Inc.

Applications & Tools. Master Slave Communication via a CM PtP using the Modbus RTU Protocol. S CM PtP RS422/485 HF, ET 200SP CM PtP

UPS Monitoring Software User Manual. Emily2

RTU-EN01 Modbus TCP Remote I/O Communication Module Operation Manual

You can search the event by POS and you can also add the Time Search condition to narrow the search range. By

MODBUS TCP to RTU/ASCII Gateway. User s Manual

For paid computer support call

WS_FTP Pro for Windows 95/98/NT

VM0808H HDMI Matrix Switch RS-232 Control Tool V User Manual

Operating Instruction MEW01652 Revision -

Library ModbusRTUlib Modbus RTU master communication. TXV rd Issue February 2010 All rights reserved

PLC Master / Slave Example

FINS Gateway For OMRON PLCs

ATV71 and ATV32 on Ethernet/IP with M340 and NOC0401 configured on Unity V6.0. Assemblies 20 70

ODBC Client Driver Help Kepware, Inc.

TRILOGI 5.3 PLC Ladder Diagram Programmer and Simulator. A tutorial prepared for IE 575 by Dr. T.C. Chang. Use On-Line Help

Transcription:

28-1 28.Multi-HMI Communication (Master Slave Mode) This chapter explains how to connect multiple HMIs. 28.1. Overview... 28-2 28.2. Steps to Create a Project of Master HMI... 28-2 28.3. Steps to Create a Project of Slave HMI... 28-3 28.4. Steps to Connect with MT500 Slave HMI... 28-5

28-2 28.1. Overview Multi-HMI Communication means that a HMI connects with a remote HMI via COM port, and read the data in the PLC connected to the remote HMI as shown in the following figure. The PLC is connected with HMI 1, and HMI 1 is connected with HMI 2 via COM port, so that HMI 2 can read the data in PLC through HMI 1. The following parts explain how to create the projects used in HMI 1 and HMI 2 by using EasyBuilder Pro. 28.2. Steps to Create a Project of Master HMI The following is the settings of HMI 1 in [System Parameter Settings]» [Device List]. 1. Since COM 1 of HMI 1 connects to PLC; the device list must include [Local PLC 1], and set the correct parameters. In this example the connected PLC is FATEK FB Series. 2. COM 3 of HMI 1 is used to receive commands from HMI 2; a new device must be added [Master-Slave Server] for setting communication properties of COM 3. The parameters of COM 3 in the example are set to 115200, E, 8, 1, and uses RS232. These parameters are not required to be the same as PLC settings, but the [Data bits] must be set to 8. In general, a higher baud rate is recommended for HMI 2 to efficiently read PLC data.

28-3 28.3. Steps to Create a Project of Slave HMI The following is the settings of HMI 2 in [System Parameter Settings]» [Device List]. Since the PLC that HMI 2 reads is connected with HMI 1, thus for HMI 2, PLC is a remote device. Therefore, it is necessary to add a [Remote PLC] into the device list. In this example the connected PLC is FATEK FB Series. The way to create [*Remote PLC 1] is described in the following steps. 1. Add a new device. Set [PLC type] to [FATEK FB Series] and [PLC default station no.] must be set in accordance with the connected PLC. 2. Correctly set the parameters. Since COM 1 of HMI 2 connects with COM 3 of HMI 1 instead of directly connect with PLC, the settings of PLC will be ignored. HMI 2 COM 1 and HMI 1 COM 3 must set to the same communication parameters and interfaces. As shown in the following figure, use RS232, and set parameters to [115200, E, 8, 1].

28-4 3. For HMI 2, PLC is a remote device, change [Location] to [Remote], and select [COM port] to connect remote HMI (HMI 1). 4. When finished, a new device [Remote PLC] can be found in the [Device List]. This device has a * symbol, which means, even if it contains Remote in the name, it actually gives commands and gets replies through a local COM port, and therefore the connection with PLC can be checked from a local system register. [*Remote PLC 1], [*Remote PLC 2], [*Remote PLC 3] and [Local PLC 1], [Local PLC 2], [Local PLC 3] use the same system registers from the listed below.

28-5 Register LB-9150 LB-9151 LB-9152 LB-9200~ LB-9455 LB-9500~ LB-9755 LB-9800~ LB-10055 Description When ON, automatically connects with PLC (COM 1) when disconnected. When OFF, ignores disconnection with PLC. When ON, automatically connects with PLC (COM 2) when disconnected. When OFF, ignores disconnection with PLC. When ON, automatically connects with PLC (COM 3) when disconnected. When OFF, ignores disconnection with PLC. These local registers indicate the connection states with PLC (through COM1). LB9200 indicates the connection state with PLC (station no. 0), and LB9201 indicates the connection state with PLC (station no. 1) and so on. When ON, indicates the connection state is normal. When OFF, indicates disconnection with PLC. Set ON again, the system will then try to connect with PLC. These local registers indicate the connection states with PLC (through COM2). LB9500 indicates the connection state with PLC (station no. 0), and LB9501 indicates the connection state with PLC (station no. 1) and so on. When ON, indicates the connection state is normal. When OFF, indicates disconnection with PLC. Set ON again, the system will then try to connect with PLC. These local registers indicate the connection states with PLC (through COM3). LB9800 indicates the connection state with PLC (station no. 0), and LB9801 indicates the connection state with PLC (station no. 1) and so on. When ON, indicates the connection state is normal. When OFF, indicates disconnection with PLC. Set ON again, the system will then try to connect with PLC. 28.4. Steps to Connect with MT500 Slave HMI EasyBuilder Master-Slave Protocol enables MT500 to exchange data with emt3000 local data via the connected PLC. 28.4.1. Settings in EasyBuilder Pro 1. Select [Master-Slave Server] and click [Settings]. If a PLC is connected, follow the original settings.

28-6 2. Select [RS-232], click [Settings]. 3. Fill in MT500 PLC ID No. in [Parameter 1] (Refer to MT500 settings). 28.4.2. Settings in EasyBuilder500 1. In [System Parameter Settings], set [Multiple HMI] to Slave, set [HMI-HMI link speed] to 115200. Note [Baud rate] must be identical in EasyBuilder500 and EasyBuilder Pro.

28-7 2. Double click PLC Address View.exe to check PLC ID No. and fill in [Parameter 1] of EasyBuilder. 3. Connect HMIs via Com Port RS-232, the communication is then enabled.

28-8 Note There will always be a PLC selected in MT500 system parameter settings, in this case, even to read/write emt3000 local data, the ID of the selected PLC of MT500 system parameters must also be filled in EasyBuilder [Parameter 1]. When using S7-200, S7-300 drivers, since MT500 reverses the high bytes and the low bytes, this will cause MT500 to misread emt3000 local data, therefore this way is not available in Master-Slave Mode. The Comparison between MT500 and emt3000: Bit/Word MT500 emt3000 Range B Ms_RB RW_Bit dddd: 0~4095 (h): 0~f B Ms_LB LB dddd: 0~9999 W Ms_RW RW ddddd: 0~65535 W Ms_LW LW dddd: 0~9999