Ventilation Standard For Health Care Facilities



Similar documents
HOSPITAL ISOLATION ROOM HVAC SYSTEM DESIGN

HEALTH CARE GUIDELINES AND STANDARDS

Essam E. Khalil

CHAPTER 4 VENTILATION

Both health-care facility classification and area classification, as per CSA, determine the design requirements.

Both health-care facility classification and area classification, as per CSA, determine the design requirements.

Flexibility, Efficiency In San Antonio Arena

HVAC Systems and Indoor Air Quality. Douglas K. Spratt, M.Sc., P.Eng.

WORKSHEET FOR RESIDENTIAL AIR SYSTEM DESIGN page 1

Methods for Effective Room Air Distribution. Dan Int-Hout Chief Engineer, Krueger Richardson, Texas

INFORMED MECHANICAL DESIGN THROUGH TESTED AIR LEAKAGE RATES. Jeff Speert, AIA MAIBC LEED AP

Innovent LASER Packaged Fresh Air Conditioning Units

Performance Rating of Room Fan- Coils

2012 Operating Room Design Manual

Answers to Your Questions from the Webinar

Presentation Outline. Common Terms / Concepts HVAC Building Blocks. Links. Plant Level Building Blocks. Air Distribution Building Blocks

Preliminary Final Proposal

Selecting the Supply Air Conditions for a Dedicated Outdoor Air System Working in Parallel with Distributed Sensible Cooling Terminal Equipment

DATA CENTER COOLING INNOVATIVE COOLING TECHNOLOGIES FOR YOUR DATA CENTER

Dr. Michael K. West, PE 1 Dr. Richard S. Combes, PE 2 Advantek Consulting / Melbourne, Florida

HVAC Air Duct Leakage. November 2013 Presented By: Mark Terzigni Project Manager Technical Services SMACNA

THERMAL LOSSES Thermal Losses Calculations

Mechanical and Natural Ventilation

VAV Laboratory Room Airflow The Lowdown on Turndown

HVAC Calculations and Duct Sizing

Element D Services Heating, Ventilating, and Air Conditioning

HVACPowDen.xls An Easy-to-Use Tool for Recognizing Energy Efficient Buildings and HVAC Systems

Residential HVAC Load Sizing Training October 14, David Kaiser Green Code Plan Reviewer

FOR CRITICAL ENVIRONMENTS

Infection Control In Hospitals

Public Review Draft. ASHRAE Standard

2004 Standard For Performance Rating Of Positive Displacement Refrigerant Compressors And Compressor Units

ANSI/AHRI Standard 880 (I-P) with Addendum Standard for Performance Rating of Air Terminals

Venice Library Humidity Study. for Williams Building Diagnostics, LLC th Street West Bradenton, FL Report April 13, 2015

AIRCONDITIONING Cooling Loads Calculations

How To Design An Hvac Design For A Stick Built Home

SPECIAL ISSUE: NATIONAL SCIENCE FOUNDATION WORKSHOP

HEPA-filtered Negative Air Machines and their Role in Creating Airborne Infection Isolation Rooms with the ECU AnteRoom. Frequently Asked Questions

Energy Recovery Ventilation Equipment

Rating Water-Source Heat Pumps Using ARI Standard 320 and ISO Standard

DEVELOPMENT OF AN OPEN SOURCE HOURLY BUILDING ENERGY MODELING SOFTWARE TOOL

09/27/2006 Centers for Disease Control and Prevention Division of Tuberculosis Elimination

Radiant Panels and Chilled Sails.

Data Center Environments

Verizon SMARTS Data Center Design Phase 1 Conceptual Study Report Ms. Leah Zabarenko Verizon Business 2606A Carsins Run Road Aberdeen, MD 21001

Causes of High Relative Humidity Inside Air Conditioned Buildings. Roger G.Morse AIA, Paul Haas CSP, CIH Morse Zehnter Associates

APPLICATION GUIDE. Comparison of Latent Cooling Performance of Various HVAC systems in a Classroom Application

APPLICATION GUIDE. Moisture Management in Waterborne Climate Systems

Subpart 1. Installation. All plumbing systems must be. installed and tested according to this chapter and chapter 4715,

Hot Air Isolation Cools High-Density Data Centers By: Ian Seaton, Technology Marketing Manager, Chatsworth Products, Inc.

Increasing Energ y Efficiency In Data Centers

HVAC Checklist - Long Form

Saving Heating Costs In Warehouses

UNIVERSITY OF MISSOURI Heating Ventilating and Air-Conditioning (HVAC) March

applications laminar flow Laminar Flow Diffusers CRITICAL ENVIRONMENT LAMINAR FLOW: GENERAL

Cooling Audit for Identifying Potential Cooling Problems in Data Centers

Element D Services Heating, Ventilating, and Air Conditioning

The Data Center Dilemma - A Case Study

Building Performance Solutions HVAC Design Guide, 2007

Liabilities of Vented Crawl Spaces, Their Impacts on Indoor Air Quality in Southeastern U.S. Homes and One Intervention Strategy

Benefits of. Air Flow Management. Data Center

Glossary of Heating, Ventilation and Air Conditioning Terms

Element D Services Plumbing

Guidelines for energy efficient heating, ventilation and air conditioning (HVAC) systems

Direct Fresh Air Free Cooling of Data Centres

Residential HVAC System Sizing

Maximize energy savings Increase life of cooling equipment More reliable for extreme cold weather conditions There are disadvantages

THE APPLICATION OF OZONE FOR AIR TREATMENT: CASE STUDY OF A BINGO HALL HVAC SYSTEM

ASTACEA4 Inspect complex/central air conditioning systems

newsletter Let s take a high-level look at airside economizing: what it is, what it requires, and how it s done. How does economizer cooling work?

Controlling Condensation On CWP Insulation BY ED LIGHT, MEMBER ASHRAE; JAMES BAILEY, P.E., MEMBER ASHRAE; AND ROGER GAY

Mechanical Technical Assignment One ASHRAE Standard 62.1 and Standard 90.1 Evaluation

PERCENT OUTDOOR AIR (%OA) CALCULATION AND ITS USE

Specialty Environment Design Mission Critical Facilities

KINGDOM OF SAUDI ARABIA SAUDI ARABIAN STANDARDS ORGANIZATION SASO. SAUDI STANDARD DRAFT No. 3457/2005

AIR DISTRIBUTION FOR COMFORT AND IAQ

IEQ Management Plan. Denver Museum of Nature and Science ECF Addition

Building Energy Codes 101 October 23, Matthew Giudice Building Policy Associate Midwest Energy Efficiency Alliance

BBD 2015 Presentation HVAC, Control, and Plumbing Systems for Thermos Bottle Buildings Roy Swain, P.E. February 5, 2015

Jeff Sloan, P.E., McKinstry Co. Wednesday, April 29

ANSI/AHRI Standard 1350 (I-P) 2014 Standard for Mechanical Performance Rating of Central Station Air-handling Unit Casings

Ventilation and Air Leakage

J O U R N A L. Energy Performance for. Proper Specification of Air Terminal Units Future Climate Impacts on Building Design

Understanding Ambulatory Surgical Centers and Office Surgical Suites

Using Time-of-Day Scheduling To Save Energy

Hazardous Drug. Cleanroom. Standards

Best Practices in HVAC Design/Retrofit

SPECIAL APPLICATIONS

How Does Your Data Center Measure Up? Energy Efficiency Metrics and Benchmarks for Data Center Infrastructure Systems

Construction Indoor Air Quality Management Plans for LEED. Matt Gregg, PE, LEED AP

Sensitivity of Forced Air Distribution System Efficiency to Climate, Duct Location, Air Leakage and Insulation

SECTION TESTING, ADJUSTING, AND BALANCING FOR HVAC INTRODUCTORY INFORMATION

Data Center Design Guide featuring Water-Side Economizer Solutions. with Dynamic Economizer Cooling

Energy Efficiency: Integrated Design and HVAC Systems HEALTHCARE - TOP 5 GREEN BUILDING STRATEGIES

Transcription:

The following article was published in ASHRAE Journal, October 2008. Copyright 2008 American Society of Heating, Refrigerating and Air- Conditioning Engineers, Inc. It is presented for educational purposes only. This article may not be copied and/or distributed electronically or in paper form without permission of ASHRAE. ANSI/ASHRAE/ASHE Standard 170-2008 Ventilation Standard For Health Care Facilities By Paul Ninomura, P.E., Member ASHRAE; and Richard Hermans, P.E., Member ASHRAE Some disparity has existed in ASHRAE recommendations related to ventilation recommendations for health care facilities. ANSI/ASHRAE Standard 62.1-2007, Ventilation for Acceptable Indoor Air Quality, and the 2007 ASHRAE Handbook HVAC Applications have some differences in their recommendations. Although Standard 62.1 is an ANSI standard, the recommendations of the ASHRAE Handbook were often more used for health care applications than The standard provides minimum ventilation requirements for hospitals, nursing facilities, and outpatient facilities and is one member of a family of documents that provide guidance, regulation, and mandates to designers of health care facilities. As with other members of this family, it is foremost a mandatory minimum requirement and may not offer the latest state-of-the-art best practice for the Standard 62.1 recommendations. In recognition of this disparity, ASHRAE established a standard project committee to develop a standard for ventilation in health care facilities. Standard 170 has been in development since 2002. There have been four public review comment periods. The cognizant technical committee (TC) is TC 9.6, Healthcare Facilities. ANSI/ASHRAE/ASHE Standard 170-2008, Ventilation of Health Care Facilities was published last month. This ANSI standard is cosponsored by the American Society of Healthcare Engineers (ASHE). About the Authors Paul Ninomura, P.E., is a mechanical engineer at Indian Health Service, Seattle. He served as vicechairman, ASHRAE Standard Project Committee (SPC)170, and is a past and current revision committee member for the FGI Guidelines for Design and Construction of Healthcare Facilities. Richard Hermans, P.E., is director of applications at McQuay International in Minneapolis, Minn. He chaired SPC 170 and is an ASHRAE director at large. 52 ASHRAE Journal ashrae.org October 2008

Function of Space Pressure Relationship to Adjacent Areas (n) Minimum Air Changes of Outdoor Air Per Hour Minimum Total Air Changes Per Hour All Room Air Exhausted Directly to Outdoors (j) Air Recirculated By Means of Room Units (a) Relative Humidity (k) (%) Design Temperature (l) ( F/ C) Surgery and Critical Care Class B and C Operating Room (m), (n), (o) Positive 4 20 N/R No 30 60 68 75/20 24 Operating/Surgical Cystoscopic Rooms, (m), (n) (o) Positive 4 20 N/R No 30 60 68 75/20 24 Delivery Room (Caesarean) (m), (n), (o) Positive 4 20 N/R No 30 60 68 75/20 24 Substerile Service Area N/R 2 6 N/R No N/R N/R Recovery Room N/R 2 6 N/R No 30 60 70 75/21 24 Critical and Intensive Care Positive 2 6 N/R No 30 60 70 75/21 24 Wound Intensive Care (Burn Unit) Positive 2 6 N/R No 40 60 70 75/21 24 Newborn Intensive Care Positive 2 6 N/R No 30 60 70 75/21 24 Treatment Room (p) N/R 2 6 N/R N/R 30 60 70 75/21 24 Trauma Room (Crisis or Shock) (c) Positive 3 15 N/R No 30 60 70 75/21 24 Medical/Anesthesia Gas Storage (r) Negative N/R 8 Yes N/R N/R N/R Laser Eye Room Positive 3 15 N/R No 30 60 70 75/21 24 ER Waiting Rooms (q) Negative 2 12 Yes N/R Max. 65 70 75/21 24 Table 1: Excerpt from Table 7.1 Design Parameters from the ANSI/ASHRAE/ASHE Standard 170-2008. health care ventilation design. Other documents, like the HVAC Design Manual for Hospitals and Clinics 1 provide more depth and detail for the designer. In addition, many jurisdictions use or refer to the Guidelines for Design and Construction of Health Care Facilities, 2 which is maintained by the Facilities Guidelines Institute. The 2006 version of the Guidelines was published by the American Institute of Architects. Guidance The focal point of the standard is Table 7.1, Design Parameters. (An excerpt of the design parameters is shown in Table 1.) This table is structured similarly to a table in the Guidelines for Design and Construction of Health Care Facilities, i.e., Table 2.1-2, Ventilation Requirements for Areas Affecting Patient Care in Hospitals and Outpatient Facilities. Table 7.1, Design Parameters includes a column titled Pressure Relationship to Adjacent Areas. This reflects the HVAC design engineering approach to this parameter. The Guidelines use the criteria of airflow relationship to adjacent areas, which reflects a traditional approach that has been favored by authorities having jurisdiction (AHJ). The values in Table 7.1 are similar to those in the Guidelines. An exception is the values indicated for Class B and C operating rooms, operating/surgical cystoscopic rooms, and delivery rooms. (The standard requires 4/20 ACH in contrast to the 3/15 ACH recommended by the Guidelines.) A minor but practical enhancement is related to line items in the table where no requirements are indicated. The table shows N/R meaning that the designer has no mandatory requirement to control that particular parameter. For example, a patient room may be designed to be positive, negative, or neutral with respect to adjacent spaces. October 2008 ASHRAE Journal 53

Operating Rooms In Class B and C operating rooms, the airflow needs to be unidirectional, downwards, and the average velocity of the diffusers shall be 25 to 35 cfm/ft 2 (127 L/s m 2 to 178 L/s m 2 ). (Average velocity is specified as cfm/ft 2 so it is clear that the critical parameter is the average airflow velocity that is measured at the face of the supply diffuser.) The diffusers need to be concentrated to provide an airflow pattern over the patient and surgical team. This aligns with the results of research that studied particulate concentration as a function of air-distribution patterns and air exchange rates for operating rooms. 3 A minimum positive pressure differential of 0.01 in. w.c. (+2.5 Pa) with respect to all adjoining spaces is required. Reserve Cooling Sources Reserve capacity is required for certain large cooling systems with some exceptions. The standard states that The number and arrangement of cooling sources and related essential accessories shall be sufficient to support the owner s facility operation plan upon breakdown or routine maintenance of any one of the cooling sources. Reserve capacity is required by this standard if 1) the total central cooling plant capacity is greater than 400 ton (1407 kw); and 2) the building is located in geographic parts of the country where the 1% cooling dry-bulb temperature is more than 85 F (29 C) (2005 ASHRAE Handbook Fundamentals). Considerable latitude is afforded by the owner s facility operation plan, e.g., the plan can allow for specific duration of time that the facility can operate without cooling, the plan can allow load shedding to maintain service to critical spaces, etc. Filters The standard specifies a minor difference from the recommendations in the Guidelines. The first filter banks are indicated to be MERV 7 filters in the standard. The Guidelines recommend a MERV 8 filter. Investigation by the ASHRAE project committee concluded that MERV 7 filters are more readily available and the filtration efficiency is equally satisfactory. Radiant Cooling and Heating Systems Although radiant panels have been used in health care applications for some time, application guidance had not been previously addressed (neither in the Guidelines nor Chapter 7, Health Care Facilities, of the ASHRAE Handbook. Minimum criteria are provided in this standard. The dew-point criteria are intended to control the agglomeration of condensation. The minimum criteria are: 6.5.2 Radiant Cooling Systems If radiant cooling panels are utilized, the chilled water temperature shall always remain above the dew-point temperature of the space. 6.5.3 Radiant Heating Systems If radiant heating is provided for an airborne infection isolation room, a protective environment room, a wound intensive care unit (burn unit), or a room for any class of surgery, either flat and smooth radiant ceiling panels with exposed cleanable surfaces or radiant floor heating shall be used. Isolation Rooms The standard provides some clarifying guidance for the airborne infection isolation room. The exhaust from the room should include the exhaust from the toilet and the anteroom (where provided). The location of the exhaust grille is specified to be in the vicinity of the head of the bed in alignment with CDC guidelines. 4 The allowable air leakage can be quantified during the design because of the differential pressure control requirement, i.e., 0.01 in. w.c. (2.5 Pa). The Standard s guidance for airborne infection isolation rooms: c) All exhaust air from the Airborne Infection Isolation (AII) rooms, associated anterooms and associated toilet rooms shall be discharged October 2008 ASHRAE Journal 55

directly to the outdoors without mixing with exhaust air from any other non-airborne Infection Isolation room or exhaust system. d) Exhaust air grilles or registers in the patient room shall be located directly above the patient bed on the ceiling or on the wall near the head of the bed. e) The room envelope shall be sealed to limit leakage air flow at 0.01 in. w.c. (2.5 Pa) differential pressure across the envelope. f) Differential pressure between AII rooms and adjacent spaces that have a different function shall be a minimum of 0.01 in. w.c. ( 2.5 Pa). The standard does not require any particular air volume flow rate differential to an AII room. To do so would then establish a mandatory effective leakage area in the room envelope. This is manifest from the following equation (Equation 28) found in the 2005 ASHRAE Handbook Fundamentals in Chapter 27, Ventilation and Infiltration. (1) where Q = Airflow rate, cfm C D = Discharge coefficient for opening, dimensionless A = Cross-sectional area of opening, ft 2 ρ = Air density, lb m /ft 3 D p = Pressure difference across opening, in. of w.c. C 3 = Unit of conversion factor = 776 Air Distribution Devices Table 6.2 Supply Air Outlets (Table 2) prescribes supply air diffusers in accordance with the classification systems in Chapter 33, Space Air Diffusion, of the 2005 ASHRAE Handbook Fundamentals. This provides implicit guidance regarding acceptable air distribution patterns. (This is an example where the standard acknowledges that the ventila- 56 ASHRAE Journal October 2008

tion for health care occupancies must address more than simply the air exchange rates.) Space Designation (According to Function) Supply Air Outlet Classification Ventilation Upon Loss of Electrical Power The standard addresses that ventilation and pressure requirements for Airborne Isolation, Protective Environment and Class B and C Operating Rooms, and Delivery Rooms shall be maintained in the event of loss of normal electrical power. This conforms with the provisions of NFPA 99, Standard for Health Care Facilities. 5 (Refer to Section 4.4 of NFPA 99 for a specific list of equipment that should be on the essential electrical system.). Summary This new standard provides clear and concise language that describes the required minimum ventilation design parameters for health care facilities. It is intended that this standard will eventually supplant Normative Appendix E, Ventilation Rates for Health Care Facilities, in Standard 62.1. References 1. ASHRAE. 2003. HVAC Design Manual for Hospitals and Clinics. 2. AIA. 2006. Guidelines for Design and Construction of Health Care Facilities. Washington, D.C.: American Institute of Architects. Class A, B and C Surgeries Protective Environment (PE) Rooms Wound Intensive Care Units (Burn Units) Trauma Rooms (Crisis or Shock) Airborne Infection Isolation (AII) All other areas Group A Group A or Group E Table 2: Excerpt from Table 6.2 Supply Air Outlets from ANSI/ASHRAE/ASHE Standard 170-2008. 3. Memarzadeh, F. and A. Manning. 2002. Comparison of operating room ventilating systems in the protection of the surgical site. ASHRAE Transactions 108(2):3 15. 4. CDC. 2003. Guidelines for Environmental Infection Control in Health-Care Facilities. Atlanta: Centers for Disease Control. 5. NFPA. 2005. NFPA 99, Health Care Facilities. Massachusetts: National Fire Protection Association. 58 ASHRAE Journal October 2008