Both health-care facility classification and area classification, as per CSA, determine the design requirements.

Size: px
Start display at page:

Download "Both health-care facility classification and area classification, as per CSA, determine the design requirements."

Transcription

1 HEATING, VENTILATION AND AIR-CONDITIONING SYSTEM (HVAC) Class 3 Facility: Local Anesthesia Heating, ventilation and air-conditioning system standards are a primary infection prevention and control strategy whereby contaminants are diluted and expelled through the high-frequency replacement of standing room air with clean filtered air. The Canadian Standards Association (CSA) Special requirements for heating, ventilation and airconditioning (HVAC) systems in health care facilities (CAN/CSA Z ) standard is not based on the type of room but on the functions that are expected to occur within the room. Where several functions apply in a given area of a facility, the more stringent requirements take precedence. Both health-care facility classification and area classification, as per CSA, determine the design requirements. The information contained in this document provides a general overview of the requirements. CAN/CSA Z317.2 Special requirements for heating, ventilation and air-conditioning (HVAC) systems in health care facilities shall be referenced in addition to this document. CAN/CSA Z317.2 represents the detailed requirements for HVAC in non-hospital medical/surgical facilities. ABBREVIATIONS AIA American Institute of Architects CSA Canadian Standards Association DOP Dispersed oil particulate HEPA High-efficiency particulate air HVAC Heating, ventilation and air-conditioning MDR Medical device reprocessing MERV Minimum efficiency reporting value PAR Post-anesthetic recovery PD Pressure differential RH Relative humidity T Temperature NHMSFP College of Physicians and Surgeons of British Columbia Page 1 of 8

2 DEFINITIONS CSA health-care facility classifications Class A-2 health-care facility A health-care facility in which patients are accommodated on the basis of medical need provided with continuing medical care and provided with supporting diagnostic and therapeutic services that can extend beyond 12 hours, and does not meet the other requirements of a Class A-1 health-care facility. Examples include: outpatient surgical services cosmetic surgical offices dental surgical offices laser eye clinics other office surgical facilities Class C health-care facility A health-care facility in which ambulatory patients are accommodated on the basis of medical need provided with supportive, diagnostic, non-invasive interventions and treatment services and stay for no more than 12 hours, and remain capable of self-preservation. Examples include: laser eye clinics cosmetic surgical offices CSA area classifications Type I A patient care area where the invasiveness of procedures, the level of risk of morbidity and mortality to patients and the level of risk of adverse outcomes to care providers necessitate more stringent HVAC and environmental requirements. Examples include: minor surgical procedures endoscopy cystoscopy dental minor procedures room operating rooms recovery rooms NHMSFP College of Physicians and Surgeons of British Columbia Page 2 of 8

3 Type II A patient care area of an area that is intended for the provision of services that provide direct support to patient care areas. Examples include: decontamination/soiled room preparation and packaging/clean room sterilizer room scope reprocessing room sterile storage NHMSFP Facility Classifications Class 1 Provides general anesthesia and major regional anesthesia (epidural, spinal nerve blocks) and may include use of IV sedation and/or analgesia, or local anesthesia only. Class 2 Provides use of IV sedation and/or analgesia where the patient remains responsive and breathes without assistance. Class 3 Provides local anesthesia only. May provide oral sedation but not IV sedation/analgesia or inhalants. New facilities, additions to existing facilities and/or replacement or addition of HVAC equipment in existing facilities are in compliance with CAN/CSA Z with the exception of the following clause*: air handling unit redundancy INDICATORS: Parallel air-handling units* are not required, although preferred, provided the following additional criteria are met: All procedures performed at the facility are less than or equal to 30 minutes (from start of the procedure to end of procedure) The medical director, in consultation with a certified infection prevention and control professional, is of the opinion that the absence of air-handling unit redundancy does not pose a risk to the patient population In the event of HVAC system failure, any procedure not in progress at time of failure shall be cancelled until the HVAC system is repaired and able to provide suitable control as per Z317.2 HVAC system functions in accordance with design criteria HVAC system monitoring parameters are in accordance with design criteria The position and type of supply and exhaust registers promote the movement of air within the rooms or spaces from clean to less clean areas NHMSFP College of Physicians and Surgeons of British Columbia Page 3 of 8

4 Airflow is directed from supply to breathing zone to exhaust outlets 1, 2 All filters are clean and sealed Air supply is from: non-aspirating ceiling outlets near the center of the work area 1, 2 ceiling outlets 3 Each operating/procedure room or area where anesthesia might be exhaled (PAR) has a minimum of two return air inlets 1, 2 Return air inlets are placed: whereby the bottom of the return air inlet is mm above the floor 1 whereby the bottom of the return air inlet is at least 75 mm above the floor 2 near the floor 3 Rooms with inhalation anesthesia and/or inhalation analgesia have a scavenging system in compliance with ISO Z , 2 or CAN/CSA Z Minimum levels of HVAC are maintained for type I areas when the space is not occupied: Minimum of six air exchanges per hour of recirculated air 1, 2 Pressure differential across separations is maintained (7.5 Pa) 1, 2 Temperature is maintained 1 Relative humidity is maintained 1 HVAC heating plant, cooling plant and controls are connected to the essential electrical system 1. CAN/CSA Z CAN/CSA Z CAN/CSA Z317.2-M91 Existing facilities are in compliance with the CAN/CSA Z317.2 at time of build INDICATORS: HVAC system functions in accordance with design criteria* 2010 present Z Z Z317.2 M91 Before 1991 American Institute of Architects *Facilities not in compliance with CAN/CSA Z317.2 standards from time of build may be required to upgrade their existing system to be in compliance with current CSA Standards. HVAC system monitoring parameters are in accordance with design criteria The position and type of supply and exhaust registers promote the movement of air within the rooms or spaces from clean to less clean areas NHMSFP College of Physicians and Surgeons of British Columbia Page 4 of 8

5 Airflow is directed from supply to breathing zone to exhaust outlets 1, 2 All filters are clean and sealed Air supply is from: non-aspirating ceiling outlets near the center of the work area 1, 2 ceiling outlets 3 Each operating/procedure room or area where anesthesia might be exhaled (PAR) has a minimum of two return air inlets 1, 2 Return air inlets are placed: whereby the bottom of the return air inlet is mm above the floor 1 whereby the bottom of the return air inlet is at least 75 mm above the floor 2 near the floor 3 Rooms with inhalation anesthesia and/or inhalation analgesia have a scavenging system in compliance with ISO Z , 2 or CAN/CSA Z Minimum levels of HVAC are maintained for type I areas when the space is not occupied minimum of six air exchanges per hour of recirculated air 1, 2 pressure differential across separations is maintained (7.5 Pa) 1, 2 temperature is maintained 1 relative humidity is maintained 1, 2 HVAC heating plant, cooling plant and controls are connected to the essential electrical system 1. CAN/CSA Z CAN/CSA Z CAN/CSA Z317.2-M91 The HVAC system is maintained in accordance with CAN/CSA Z INDICATORS: Filters and seals are visually inspected monthly to verify the presence of the filter and seal and to ensure proper physical condition Primary filters with a MERV rating less than 9 are replaced every 12 months or when loaded (based upon measurements of pressure drop across the filter bank) Primary filters with a MERV rating greater than or equal to 9 are replaced every 24 months or when loaded (based upon measurements of pressure drop across the filter bank) Secondary filters are replaced every 24 months or when loaded (based upon measurements of pressure drop across the filter bank) HEPA filters are replaced every 36 months or when loaded (based upon measurements of pressure drop across the filter bank) whichever occurs first NHMSFP College of Physicians and Surgeons of British Columbia Page 5 of 8

6 Fan coils, drain pans and induction and finned units are inspected and cleaned at minimum semi-annually (usually spring and fall) Ducts are inspected at minimum annually Supply ducts are cleaned when deemed necessary by annual inspection Return ducts are cleaned every 10 years or when deemed necessary by annual inspection, whichever occurs first Exhaust ducts are cleaned every 10 years or when deemed necessary by annual inspection, whichever occurs first Diffusers (supply, return or exhaust) are cleaned every six months HVAC Design Criteria The information contained in this document provides a general overview of the requirements. CAN/CSA Z317.2 Special requirements for heating, ventilation and air-conditioning (HVAC) systems in health care facilities shall be referenced in addition to this document. CAN/CSA Z317.2 represents the detailed requirements for HVAC in non-hospital medical/surgical facilities. Minimum filter efficiency Operating room Filter # 1 MERV 1 8 Filter # 1 50% 3 Filter # 1 30% Filter # 2 MERV 14 Filter # 2 90% Filter # 2 95% Procedure room Filter # 1 MERV 8 Filter # 1 50% Filter # 1 30% Filter # 2 MERV 14 Filter # 2 90% Filter # 2 95% Specialized operating Filter # 1 MERV 8 Filter # 1 50% Filter # 1 30% room* Filter # 2 MERV 14 Filter # % 4 Filter # 2 95% Endoscopy / bronchoscopy *Specialized operating room, e.g. transplants, orthopedics 1. Minimum efficiency reporting value (MERV) 2. High-efficiency particulate air (HEPA) 3. Dust spot efficiency 4. Dispersed oil particulate (DOP) Filter # 3 HEPA 2 Filter # 3 N/A Filter # 3 N/A Filter # 1 MERV 8 Filter # 1 50% Filter # 1 30% Filter # 2 MERV 14 Filter # 2 90% Filter # 2 95% Minimum outdoor air changes/total air changes per hour Operating room 6/20 6/20 6/20 Procedure room 5/15 6/20 6/20 Recovery room 6/20 6/20 6/20 Endoscopy / bronchoscopy 5/(15/20) 6/20 6/20 Dirty room (MDR) 2/10 2/8 3/12 Clean room (MDR) 3/10 3/10 3/12 Sterile storage 0/4 0/4 3/12 NHMSFP College of Physicians and Surgeons of British Columbia Page 6 of 8

7 Relative pressurization Operating room Positive Positive Positive Procedure room Positive Positive Positive Recovery room Positive Positive Positive Endoscopy / bronchoscopy Negative Positive/Negative Positive/Negative Clean room (MDR) Positive Positive Positive Sterile storage Positive Positive Positive Dirty room (MDR) Negative Negative Negative Pressure-critical spaces: minimum pressure differential Operating room Pa mm + Procedure room Pa mm + Recovery room Pa mm + Endoscopy / bronchoscopy Pa / mm + / - Clean room (MDR) Pa mm + Sterile storage Pa mm + Dirty room (MDR) Pa mm Pa = 0.03wc = mm of water pressure Temperature Operating room o C o C o C Procedure room o C o C o C Recovery room o C 24 o C o C Endoscopy / bronchoscopy o C o C o C Clean room (MDR) o C o C o C Sterile storage o C o C o C Dirty room (MDR) o C o C o C Relative humidity Operating room 40 60% 45 55% 50 60% Procedure room 30 60% 45 55% 50 60% Recovery room 30 60% 50 60% 50 60% Endoscopy / bronchoscopy 30 60% 30 60% 50 60% Clean room (MDR) 30 60%* 30 60% 40 50% Sterile storage 30 60%* 30 60% 40 50% Dirty room (MDR) 30 60%* 30 60% 40 50% *As per the Ministry of Health Best Practice Guidelines for Cleaning, Disinfection and Sterilization of Critical and Semi-Critical Medical Devices relative humidity of 40 50% is preferred NHMSFP College of Physicians and Surgeons of British Columbia Page 7 of 8

8 Parameter monitoring: monitored, alarmed central readout Pressure differential (PD) Temperature (T) Relative humidity (RH) Parameter monitoring: local readout OR/procedure room PD, T, RH T, RH T, RH Dirty room T, RH T, RH - Clean room T, RH T, RH - Sterile supply T, RH T, RH - Parameter monitoring: calibration OR/procedure room (PD, T, RH) Monthly - - Dirty room (T, RH) Annually - - Clean room (T, RH) Annually - - Sterile supply (T, RH) Annually - - REFERENCES Canadian Standards Association. Special requirements for heating, ventilation, and air conditioning (HVAC) systems in health care facilities. Mississauga, ON: Canadian Standards Association; p. CSA Standard No.: Z NHMSFP College of Physicians and Surgeons of British Columbia Page 8 of 8

Both health-care facility classification and area classification, as per CSA, determine the design requirements.

Both health-care facility classification and area classification, as per CSA, determine the design requirements. HEATING, VENTILATION AND AIR-CONDITIONING SYSTEM (HVAC) Class 1 Facility: General Anesthesia Heating, ventilation and air-conditioning system standards are a primary infection prevention and control strategy

More information

HEALTH CARE GUIDELINES AND STANDARDS

HEALTH CARE GUIDELINES AND STANDARDS HEALTH CARE GUIDELINES AND STANDARDS APPLICATION NOTE LC-126 INTRODUCTION This publication provides excerpts from some of the many guidelines and standards that pertain to the construction and operation

More information

Ventilation Standard For Health Care Facilities

Ventilation Standard For Health Care Facilities The following article was published in ASHRAE Journal, October 2008. Copyright 2008 American Society of Heating, Refrigerating and Air- Conditioning Engineers, Inc. It is presented for educational purposes

More information

Essam E. Khalil khalile1@asme.org

Essam E. Khalil khalile1@asme.org AIR-CONDITIONING SYSTEMS DEVELOPMENTS IN HOSPITALS: COMFORT, AIR QUALITY, AND ENERGY UTILIZATION Essam E. Khalil khalile1@asme.org PROFESSOR OF MECHANICAL ENGINEERING, CAIRO UNIVERSITY, EGYPT Abstract

More information

2012 Operating Room Design Manual

2012 Operating Room Design Manual CHAPTER 9 ROOM VENTILATION SYSTEMS Lead Author: Kamal Maheshwari, MD, Staff Anesthesiologist, Cleveland Clinic Foundation Checklist 1. Does the ventilation system in your operating room (OR) meet the standards

More information

SECTION 23 01 30.51 HVAC AIR-DISTRIBUTION SYSTEM CLEANING

SECTION 23 01 30.51 HVAC AIR-DISTRIBUTION SYSTEM CLEANING SECTION 23 01 30.51 HVAC AIR-DISTRIBUTION PART 1 - GENERAL 1.1 SUMMARY A. Section includes cleaning of interior surfaces of HVAC equipment. The HVAC equipment cleaning work includes the following: 1. Air

More information

1. Certification: Employ an ASCS certified by NADCA on a full-time basis. 2. Supervisor Qualifications: Certified as an ASCS by NADCA.

1. Certification: Employ an ASCS certified by NADCA on a full-time basis. 2. Supervisor Qualifications: Certified as an ASCS by NADCA. PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section.

More information

The facility must have methods in place to ensure staff are managed effectively to support the care, treatment and services it provides.

The facility must have methods in place to ensure staff are managed effectively to support the care, treatment and services it provides. HUMAN RESOURCES The facility must have methods in place to ensure staff are managed effectively to support the care, treatment and services it provides. This standard addresses human resource planning,

More information

SPECIAL APPLICATIONS

SPECIAL APPLICATIONS Page 1 SPECIAL APPLICATIONS The protection of microelectronics clean rooms using aspirating smoke detection systems requires special consideration. The physical configuration of the room(s) and the direction

More information

AORN Position Statement on Allied Health Care Providers and Support Personnel in the Perioperative Practice Setting

AORN Position Statement on Allied Health Care Providers and Support Personnel in the Perioperative Practice Setting AORN Position Statement on Allied Health Care Providers and Support Personnel in the Perioperative Practice Setting POSITION STATEMENT The perioperative RN is accountable for patient outcomes resulting

More information

www.inspection-for-industry.com

www.inspection-for-industry.com Quality Control Form (TEST RUNNING RECORD FOR AIR HANDLING UNIT) SUB POWER SUPPLY: MAIN POWER V, Hz, CONTROL V, Blower 1 kw, Blower 2 kw, Compressor: (1) kw (2) kw (3) kw (4) kw Heating Element: kw 1.

More information

Element D Services Heating, Ventilating, and Air Conditioning

Element D Services Heating, Ventilating, and Air Conditioning PART 1 - GENERAL 1.01 OVERVIEW A. This section supplements Design Guideline Element D3041 on air handling distribution with specific criteria for projects involving design of a Data Center spaces B. Refer

More information

There are several types of air cleaning devices available, each designed to remove certain types of pollutants.

There are several types of air cleaning devices available, each designed to remove certain types of pollutants. Please Note: EPA neither certifies nor recommends particular brands of home air cleaning devices. While some home air cleaning devices may be useful in some circumstances, EPA makes no broad endorsement

More information

Why Measure Carbon Dioxide Inside Buildings? By Rich Prill, Washington State University Extension Energy Program

Why Measure Carbon Dioxide Inside Buildings? By Rich Prill, Washington State University Extension Energy Program Why Measure Carbon Dioxide Inside Buildings? By Rich Prill, Indoor air quality Workers and students spend about half their waking hours at work or school. Therefore, maintaining adequate indoor air quality

More information

UNIVERSITY OF MISSOURI 23 0000 - Heating Ventilating and Air-Conditioning (HVAC) March 2015.01

UNIVERSITY OF MISSOURI 23 0000 - Heating Ventilating and Air-Conditioning (HVAC) March 2015.01 GENERAL: This section provides general standards for overall sizing and design of Heating, Ventilating, and Air Conditioning (HVAC) systems. Other sections contain specific standards for each system per

More information

CHAPTER 4 VENTILATION

CHAPTER 4 VENTILATION CHAPTER 4 VENTILATION SECTION 401 GENERAL 401.1 Scope. This chapter, in conjunction with the building code, shall govern the ventilation of spaces within a building intended to be occupied. Mechanical

More information

In-Room HEPA Cleaners: Guidance Document

In-Room HEPA Cleaners: Guidance Document In-Room HEPA Cleaners: Guidance Document Healthcare Human Factors Group Centre for Global ehealth Innovation University Health Network Toronto, ON, Canada Oct, 2007 Table of Contents 1 Introduction...4

More information

HVAC Design Requirements

HVAC Design Requirements Maintenance of HVAC HVAC Design Requirements Air Flow Diagram แบบ Recirculation Air Flow Diagram แบบ Once Through Definition Of Conditions As built At rest In operation air air air Maintenance GMP Requirements

More information

Environmental Monitoring

Environmental Monitoring Chapter 10 Environmental Monitoring By the end of this chapter, you will be able to: l List the types of environmental testing l Name three types of checks that are carried out to ensure the isolator is

More information

ASTACEA4 Inspect complex/central air conditioning systems

ASTACEA4 Inspect complex/central air conditioning systems Overview This Unit covers the competences required to inspect complex/central air conditioning systems as defined by the CIBSE TM 44 Figure 1.1: Summary of system types and their component parts. The air

More information

Construction Indoor Air Quality Management Plans for LEED. Matt Gregg, PE, LEED AP

Construction Indoor Air Quality Management Plans for LEED. Matt Gregg, PE, LEED AP Construction Indoor Air Quality Management Plans for LEED Matt Gregg, PE, LEED AP Agenda What is a Construction IAQ Management Plan? What are the LEED Requirements? What is the Mechanical Contractor s

More information

HVAC Checklist - Long Form

HVAC Checklist - Long Form HVAC Checklist - Long Form Page 1 of 14 Appendix B discusses HVAC system components in relation to indoor air quality. utside Air Intake Location pen during occupied hours? Unobstructed? Standing water,

More information

HOSPITAL ISOLATION ROOM HVAC SYSTEM DESIGN

HOSPITAL ISOLATION ROOM HVAC SYSTEM DESIGN HOSPITAL ISOLATION ROOM HVAC SYSTEM DESIGN Presented to: ASHRAE YEA Illinois Chapter Specialty Environment Design Conference March 24, 2014 Jean O. Gibbons, PE, LEED AP Senior Vice President Grumman/Butkus

More information

Understanding Ambulatory Surgical Centers and Office Surgical Suites

Understanding Ambulatory Surgical Centers and Office Surgical Suites Understanding Ambulatory Surgical Centers and Office Surgical Suites The Issues of Code, Licensing, and Reimbursement Daniel Roark, Assoc. AIA Skip Gregory, NCARB Who is Studio+? People Passion Process

More information

HEPA-filtered Negative Air Machines and their Role in Creating Airborne Infection Isolation Rooms with the ECU AnteRoom. Frequently Asked Questions

HEPA-filtered Negative Air Machines and their Role in Creating Airborne Infection Isolation Rooms with the ECU AnteRoom. Frequently Asked Questions HEPA-filtered Negative Air Machines and their Role in Creating Airborne Infection Isolation Rooms with the ECU AnteRoom Frequently Asked Questions What is a negative air machine and why do I need one?

More information

HVAC Systems and Indoor Air Quality. Douglas K. Spratt, M.Sc., P.Eng.

HVAC Systems and Indoor Air Quality. Douglas K. Spratt, M.Sc., P.Eng. HVAC Systems and Indoor Air Quality Douglas K. Spratt, M.Sc., P.Eng. The 5 Senses Architecture Electrical Structural Mechanical Hearing Seeing Smelling Feeling Tasting HVAC Systems are Dynamic Heat Gains

More information

CLEAN ROOM MONITORING REGULATORY STANDARDS

CLEAN ROOM MONITORING REGULATORY STANDARDS CLEAN ROOM MONITORING REGULATORY STANDARDS Air Classification as per Schedule M Maximum permitted number of particles / m3 equal or above at rest in operation 0.5µm 5.0µm 0.5µm 5.0µm A 3,520 29 3,500 29

More information

Infection Control Risk Assessment Matrix of Precautions for Construction & Renovation

Infection Control Risk Assessment Matrix of Precautions for Construction & Renovation Infection Control Risk Assessment Matrix of Precautions for Construction & Renovation Step One: Using the following table, identify the Type of Construction Project Activity (Type A-D) TYPE A TYPE B TYPE

More information

CSA Z317-13-12 Infection Control during Construction, Renovation and Maintenance of Health Care Facilities Overview and Case Studies

CSA Z317-13-12 Infection Control during Construction, Renovation and Maintenance of Health Care Facilities Overview and Case Studies CSA Z317-13-12 Infection Control during Construction, Renovation and Maintenance of Health Care Facilities Overview and Case Studies Grant Rogers, BSc. Principal 1 North West Environmental Group Industrial

More information

NADCA GENERAL SPECIFICATIONS FOR THE CLEANING OF COMMERCIAL HEATING, VENTILATING AND AIR CONDITIONING SYSTEMS

NADCA GENERAL SPECIFICATIONS FOR THE CLEANING OF COMMERCIAL HEATING, VENTILATING AND AIR CONDITIONING SYSTEMS NADCA GENERAL SPECIFICATIONS FOR THE CLEANING OF COMMERCIAL HEATING, VENTILATING AND AIR CONDITIONING SYSTEMS National Air Duct Cleaners Association 1518 K Street, N.W. Suite 503 Washington, DC 20005 (202)

More information

THREE. Heating and Cooling

THREE. Heating and Cooling THREE Heating and Cooling 17 Condensation Drain Line The line that drains condensed moisture away from your heating and/or cooling unit needs periodic maintenance. If your unit is located in the attic,

More information

heating 3 & cooling heating and cooling 2010 PulteGroup, Inc. All Rights Reserved.

heating 3 & cooling heating and cooling 2010 PulteGroup, Inc. All Rights Reserved. 3 & cooling 17 heating 2010 PulteGroup, Inc. All Rights Reserved. condensation The line that drains condensed moisture away from your heating and/or cooling unit needs periodic maintenance. Air conditioning

More information

Guidelines for energy efficient heating, ventilation and air conditioning (HVAC) systems

Guidelines for energy efficient heating, ventilation and air conditioning (HVAC) systems Guidelines for energy efficient heating, ventilation and air conditioning (HVAC) systems If you're a designer or a BCA, this guidance on the energy efficiency of HVAC systems in commercial buildings may

More information

Radford University. Indoor Air Quality Management Plan

Radford University. Indoor Air Quality Management Plan Radford University Indoor Air Quality Management Plan Spring 2015 Introduction Concerns with Indoor Air Quality (IAQ) have increased since energy conservation measures were instituted in office buildings

More information

MANAGING A STERILE PROCESSING DEPARTMENT IN CRISIS: HOW TO STAY COOL WHEN YOUR SPD GETS TOO HOT

MANAGING A STERILE PROCESSING DEPARTMENT IN CRISIS: HOW TO STAY COOL WHEN YOUR SPD GETS TOO HOT MANAGING A STERILE PROCESSING DEPARTMENT IN CRISIS: HOW TO STAY COOL WHEN YOUR SPD GETS TOO HOT FRANK MYERS, MA, CIC INFECTION PREVENTIONIST III UC SAN DIEGO HEALTH SYSTEM POTENTIAL CONFLICT: MR. MYERS

More information

air conditioners how to choose a cooling system

air conditioners how to choose a cooling system air conditioners how to choose a cooling system taking responsibility As an individual, your efficient use of energy brings benefits such as lower bills, improved comfort levels in your home and a reduced

More information

SECTION 15950 - TESTING, ADJUSTING, AND BALANCING

SECTION 15950 - TESTING, ADJUSTING, AND BALANCING SECTION 15950 - TESTING, ADJUSTING, AND BALANCING PART 1 - GENERAL 1.1 RELATED DOCUMENTS Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification

More information

Glossary of Heating, Ventilation and Air Conditioning Terms

Glossary of Heating, Ventilation and Air Conditioning Terms Glossary of Heating, Ventilation and Air Conditioning Terms Air Change: Unlike re-circulated air, this is the total air required to completely replace the air in a room or building. Air Conditioner: Equipment

More information

Infection Control In Hospitals

Infection Control In Hospitals 2006 American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). Published in ASHRAE Journal (Vol. 48, June 2006). For personal use only. Additional distribution in

More information

QUESTIONS TO ASK WHEN REPLACING YOUR HVAC TOGETHERWESAVE.COM

QUESTIONS TO ASK WHEN REPLACING YOUR HVAC TOGETHERWESAVE.COM QUESTIONS TO ASK WHEN REPLACING YOUR HVAC TOGETHERWESAVE.COM TOGETHERWESAVE.COM IS IT TIME TO REPLACE YOUR HVAC SYSTEM? If your heating and cooling system is 15 to 20 years old and is experiencing problems,

More information

Australian/New Zealand Standard

Australian/New Zealand Standard AS/NZS 4187:2003 AS/NZS 4187 Australian/New Zealand Standard Cleaning, disinfecting and sterilizing reusable medical and surgical instruments and equipment, and maintenance of associated environments in

More information

Infection Control Risk Assessment Matrix of Precautions for Construction & Renovation

Infection Control Risk Assessment Matrix of Precautions for Construction & Renovation Infection Control Risk Assessment Matrix of Precautions for Construction & Renovation Step One: Using the following table, identify the Type of Construction Project Activity (Type A-D) TYPE A TYPE B TYPE

More information

Preliminary Final Proposal

Preliminary Final Proposal 1 Butler Memorial Hospital New Inpatient Tower Senior Capstone Project Mechanical Option Preliminary Final Proposal Mechanical System Re-design and Breadth Topics Butler Memorial Hospital New Inpatient

More information

DESERT RESEARCH INSTITUTE MOLD ASSESSMENT AND REMEDIATEION PROCEDURE

DESERT RESEARCH INSTITUTE MOLD ASSESSMENT AND REMEDIATEION PROCEDURE 1.0 Introduction DESERT RESEARCH INSTITUTE This Desert Research Institute (DRI) Mold Assessment and Remediation Procedure was established to assure that consistent and uniform information is provided to

More information

Diagnostics for Mobile Homes: HVAC

Diagnostics for Mobile Homes: HVAC Diagnostics for Mobile Homes: HVAC Adam Harris NYSWDA Wade Thompson - IWTC Objectives Identify different types of HVAC used in mobile homes Provide an overview of duct systems Demonstrate various tests

More information

SECTION 23 05 93 TESTING, ADJUSTING, AND BALANCING FOR HVAC INTRODUCTORY INFORMATION

SECTION 23 05 93 TESTING, ADJUSTING, AND BALANCING FOR HVAC INTRODUCTORY INFORMATION SECTION 23 05 93 TESTING, ADJUSTING, AND BALANCING FOR HVAC INTRODUCTORY INFORMATION The purpose of this guide specification is to assist the specifier in correctly specifying Mechanical System Testing

More information

IEQ Management Plan. Denver Museum of Nature and Science ECF Addition

IEQ Management Plan. Denver Museum of Nature and Science ECF Addition IEQ Management Plan GH Phipps Construction Companies 5995 Greenwood Plaza Blvd., Suite 100 Greenwood Village, Colorado 80111-4710 303.571.5377 PHONE www.ghphipps.com Denver Museum of Nature and Science

More information

Innovent LASER Packaged Fresh Air Conditioning Units

Innovent LASER Packaged Fresh Air Conditioning Units LASER Latent And Sensible Energy Reduction Latent And Sensible Energy Reduction For Outside Air Innovent LASER Packaged Fresh Air Conditioning Units Innovent LASER units provide both sensible and latent

More information

WORKSHEET FOR RESIDENTIAL AIR SYSTEM DESIGN page 1

WORKSHEET FOR RESIDENTIAL AIR SYSTEM DESIGN page 1 WORKSHEET FOR RESIDENTIAL AIR SYSTEM DESIGN page 1 Wallet card photocopy Inspection Authority: Signature: Date: / / Submitted For: ( Owner ) Name Address City Prov Postal code Phone ( ) Fax ( ) Designer/Signature:

More information

Dehumidification Frequently Asked Questions

Dehumidification Frequently Asked Questions Dehumidification Basics Why do you want to keep indoor Rh between 30-60%? ASHRAE recommends keeping the relative humidity in a home between 30-60% to limit the effects of many unwanted conditions and harmful

More information

MINNESOTA WEST COMMUNITY & TECHNICAL COLLEGE COURSE OUTLINE

MINNESOTA WEST COMMUNITY & TECHNICAL COLLEGE COURSE OUTLINE MINNESOTA WEST COMMUNITY & TECHNICAL COLLEGE COURSE OUTLINE Faculty are required to have the outline submitted to the Academic Affairs Office. The course outline is the form used for approval of new courses

More information

Mold Response and Remediation Plan

Mold Response and Remediation Plan 1.0 Policy Statement The University of New Haven has developed a mold response and remediation plan in accordance with best practices set forth by the Environmental Protection Agency (EPA), Occupational

More information

1.2 Refrigerant Equipment. General

1.2 Refrigerant Equipment. General Part 1 General 1.1 Summary.1 Unless otherwise indicated, follow the standards below when specifying heating, ventilation and air conditioning (HVAC) work. These standards are not intended to restrict or

More information

Contractors State License Board

Contractors State License Board Your New Heating, Ventilating and Air-Conditioning (HVAC) System Dear Customer: We want you to feel assured that your new HVAC system is safe for you and your home, and meets the legal requirements in

More information

SUPPLEMENTARY GUIDELINES ON

SUPPLEMENTARY GUIDELINES ON August 2015 Draft document for comment 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 SUPPLEMENTARY GUIDELINES ON GOOD MANUFACTURING PRACTICES

More information

MOLD RESPONSE AND REMEDIATION PLAN

MOLD RESPONSE AND REMEDIATION PLAN MOLD RESPONSE AND REMEDIATION PLAN Prepared By: Triumvirate Environmental Developed: April 2011 Last Revised: March 2015 Program Approval Associate Vice President of Public Safety & Administrative Services

More information

RFI Response RFP: HSCG88-16-R-PQQ015 Replace HVAC Bldg A & C San Diego, CA.

RFI Response RFP: HSCG88-16-R-PQQ015 Replace HVAC Bldg A & C San Diego, CA. 1. There is verbiage in the hazardous material report referring to a state licensed abatement contractor. Within the recommendations part of the report (page 64 of 111 of the specification pdf) is the

More information

Venice Library Humidity Study. for Williams Building Diagnostics, LLC 305 15 th Street West Bradenton, FL 34205. Report April 13, 2015

Venice Library Humidity Study. for Williams Building Diagnostics, LLC 305 15 th Street West Bradenton, FL 34205. Report April 13, 2015 for Williams Building Diagnostics, LLC 305 15 th Street West Bradenton, FL 34205 Report April 13, 2015 Moses & Associates, Inc. 2209 NW 40 th Terrace, Suite A Gainesville, FL 32605 FL License EB-0003097

More information

PANDA SPRAY BOOTH FILTER INFORMATION

PANDA SPRAY BOOTH FILTER INFORMATION PANDA SPRAY BOOTH FILTER INFORMATION Our Spray Booth has been designed to reduce the risk of potential hazardous situations occurring. You must adhere to the specifications chart listed below when replacing

More information

International Telecommunication Union SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES IN PUBLIC NETWORKS

International Telecommunication Union SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES IN PUBLIC NETWORKS International Telecommunication Union ITU-T TELECOMMUNICATION STANDARDIZATION SECTOR OF ITU Technical Paper (13 December 2013) SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES

More information

JANUARY 2013 GUIDANCE NOTES ON HEATING, VENTILATION AND AIR- CONDITIONING (HVAC) SYSTEMS FOR MANUFACTURERS OF ORAL SOLID DOSAGE FORMS

JANUARY 2013 GUIDANCE NOTES ON HEATING, VENTILATION AND AIR- CONDITIONING (HVAC) SYSTEMS FOR MANUFACTURERS OF ORAL SOLID DOSAGE FORMS JANUARY 2013 GUIDANCE NOTES ON HEATING, VENTILATION AND AIR- CONDITIONING (HVAC) SYSTEMS FOR MANUFACTURERS OF ORAL SOLID DOSAGE FORMS Introduction Heating, Ventilation and Air-Conditioning (HVAC) plays

More information

Centre for Healthcare Related Infection Surveillance and Prevention & Tuberculosis Control

Centre for Healthcare Related Infection Surveillance and Prevention & Tuberculosis Control GUIDELINE Storage Design for Sterile and Non-Sterile Stock for New and Refurbished Healthcare Facilities TABLE OF CONTENTS GLOSSARY OF ACRONYMS, ABBREVIATIONS AND TERMS & DEFINITIONS... 2 1.0 INTRODUCTION...

More information

Commercial Coil Cleaning:

Commercial Coil Cleaning: 18 Commercial Coil Cleaning: by Barry Harris, PH.D., ASCS 1, Lindell F. Killian, ASCS 2, and Nicolaus P. Neumann, P.E. 3 A Case History Facility managers and HVAC engineering supervisors have limited budgets

More information

9.4 Air Conditioning, Heating, Cooling and Ventilating Systems

9.4 Air Conditioning, Heating, Cooling and Ventilating Systems 9.4 Air Conditioning, Heating, Cooling and Ventilating Systems 9.4.1 Control Building HVAC The Control Building (C/B) Heating, Ventilating and Air-Conditioning (HVAC) System is divided into two separate

More information

COMPARATIVE LIFE-CYCLE ANALYSIS OF ENERGY-EFFICIENCY MEASURES AT TVA S CHATTANOOGA OFFICE COMPLEX: PHASE II RESULTS & FINAL DESIGN

COMPARATIVE LIFE-CYCLE ANALYSIS OF ENERGY-EFFICIENCY MEASURES AT TVA S CHATTANOOGA OFFICE COMPLEX: PHASE II RESULTS & FINAL DESIGN COMPARATIVE LIFE-CYCLE ANALYSIS OF ENERGY-EFFICIENCY MEASURES AT TVA S CHATTANOOGA OFFICE COMPLEX: PHASE II RESULTS & FINAL DESIGN Umesh Atre Innovative Design Inc 850 W Morgan St Raleigh, NC 27603 umesh@innovativedesign.net

More information

Mold and Mildew Mold and mildew can be detected by sight, smell and touch.

Mold and Mildew Mold and mildew can be detected by sight, smell and touch. Mold and Mildew Mold and mildew can be detected by sight, smell and touch. Molds are usually black (not unlike the molds that grow in showers and between grout), green or tan in color, but can be in various

More information

Walkthrough Inspection Checklist

Walkthrough Inspection Checklist Walkthrough Inspection Checklist This checklist is to aid during an IAQ Walkthrough of the school. The checklist includes considerations both inside and outside the school building: Instructions: 1. Read

More information

SPECIAL ISSUE: NATIONAL SCIENCE FOUNDATION WORKSHOP

SPECIAL ISSUE: NATIONAL SCIENCE FOUNDATION WORKSHOP research journal 2013 / VOL 05.01 www.perkinswill.com SPECIAL ISSUE: NATIONAL SCIENCE FOUNDATION WORKSHOP ARCHITECTURE AND ENGINEERING OF SUSTAINABLE BUILDINGS Current Trends in Low-Energy HVAC Design

More information

Candidates Guide. for. Certified Ventilation Consultant (CVC)

Candidates Guide. for. Certified Ventilation Consultant (CVC) Candidates Guide for Certified Ventilation Consultant (CVC) The Certified Ventilation Consultant (CVC) is an advanced, comprehensive certification targeted to highly qualified experts in the field of HVAC

More information

CE6500 Energy Recovery Ventilator

CE6500 Energy Recovery Ventilator ADVANCED COMMERCIAL Energy Recovery Ventilator PRODUCT SPECIFICATIONS & TECHNICAL DATA Features NOMINAL CAPACITY 5500-7000 CFM CASING Double-wall cabinet White exterior paint, -gauge galvanized steel -gauge

More information

Energy Efficiency in Industrial HVAC Systems

Energy Efficiency in Industrial HVAC Systems Energy Efficiency in Industrial HVAC Systems Heating, ventilation and air conditioning (HVAC) constitutes up to 35 percent of energy used in manufacturing facilities. This fact sheet is geared towards

More information

Ventilation Solutions Fresh Air Solutions for Ductless Heating & Cooling. fantech

Ventilation Solutions Fresh Air Solutions for Ductless Heating & Cooling. fantech Ventilation Solutions Fresh Air Solutions for Ductless Heating & Cooling 2 Ductless Ventilation & Fresh Air Solutions We can fill your home with healthy, fresh air Indoor Air Pollution is real, and it

More information

09/27/2006 Centers for Disease Control and Prevention Division of Tuberculosis Elimination

09/27/2006 Centers for Disease Control and Prevention Division of Tuberculosis Elimination Appendix B. Tuberculosis (TB) risk assessment worksheet This model worksheet should be considered for use in performing TB risk assessments for healthcare facilities and nontraditional facility-based settings.

More information

NEBB STANDARDS SECTION-8 AIR SYSTEM TAB PROCEDURES

NEBB STANDARDS SECTION-8 AIR SYSTEM TAB PROCEDURES NEBB STANDARDS SECTION-8 AIR SYSTEM TAB PROCEDURES 8.1 INTRODUCTION Testing, adjusting, and balancing of HVAC systems can best be accomplished by following a series of systematic procedures. The NEBB TAB

More information

HVAC Systems: Overview

HVAC Systems: Overview HVAC Systems: Overview Michael J. Brandemuehl, Ph.D, P.E. University of Colorado Boulder, CO, USA Overview System Description Secondary HVAC Systems Air distribution Room diffusers and air terminals Duct

More information

Corporate Medical Policy

Corporate Medical Policy File Name: anesthesia_services Origination: 8/2007 Last CAP Review: 1/2016 Next CAP Review: 1/2017 Last Review: 1/2016 Corporate Medical Policy Description of Procedure or Service There are three main

More information

Causes of High Relative Humidity Inside Air Conditioned Buildings. Roger G.Morse AIA, Paul Haas CSP, CIH Morse Zehnter Associates

Causes of High Relative Humidity Inside Air Conditioned Buildings. Roger G.Morse AIA, Paul Haas CSP, CIH Morse Zehnter Associates Causes of High Relative Humidity Inside Air Conditioned Buildings Roger G.Morse AIA, Paul Haas CSP, CIH Morse Zehnter Associates S. FLORIDA AVE. AMBIENT 91 F db / 78 F wb 16,000 HOURS ANNUALLY THAT wb

More information

Manual A - Minimising air pollution during building use

Manual A - Minimising air pollution during building use Par Hill Research Reducing air pollution from your building - a series of manuals for operators, designers & developers Manual A - Minimising air pollution during building use Factsheet A1 - Laws & Regulations

More information

PEOSH. Indoor Air Quality Training for Asthma-Friendly Schools Part I PEOSH Indoor Air Quality Standard Overview. Eric Weren, MSIH

PEOSH. Indoor Air Quality Training for Asthma-Friendly Schools Part I PEOSH Indoor Air Quality Standard Overview. Eric Weren, MSIH PEOSH Indoor Air Quality Training for Asthma-Friendly Schools Part I PEOSH Indoor Air Quality Standard Overview Eric Weren, MSIH Public Employees Occupational Safety and Health Unit IAQ Asthma-Friendly

More information

Mechanical Technical Assignment One ASHRAE Standard 62.1 and Standard 90.1 Evaluation

Mechanical Technical Assignment One ASHRAE Standard 62.1 and Standard 90.1 Evaluation Mechanical Technical Assignment One ASHRAE Standard 62.1 and Standard 90.1 Evaluation Prepared for: Dr. James D. Freihaut Department of Architectural Engineering The Pennsylvania State University Prepared

More information

Subpart 1. Installation. All plumbing systems must be. installed and tested according to this chapter and chapter 4715,

Subpart 1. Installation. All plumbing systems must be. installed and tested according to this chapter and chapter 4715, 4658.4500 PLUMBING SYSTEMS; NEW CONSTRUCTION. Subpart 1. Installation. All plumbing systems must be installed and tested according to this chapter and chapter 4715, the Minnesota Plumbing Code. Subp. 2.

More information

IEQ-15 Air Distribution System

IEQ-15 Air Distribution System AIM OF CREDIT To encourage and recognise the design and maintenance of air distribution systems that minimise the risk of particulate and microbial contamination to the internal air supply. CREDIT CRITERIA

More information

SECTION 5 HOSPITAL SERVICES. Free-Standing Ambulatory Surgical Center

SECTION 5 HOSPITAL SERVICES. Free-Standing Ambulatory Surgical Center SECTION 5 HOSPITAL SERVICES Table of Contents 1 GENERAL POLICY... 2 1-1 Clients Enrolled in a Managed Care Plan... 3 1-2 Clients NOT Enrolled in a Managed Care Plan (Fee-for-Service Clients)..................

More information

Heating Ventilation and Air Conditioning Diagnostics for Single Family Homes

Heating Ventilation and Air Conditioning Diagnostics for Single Family Homes Heating Ventilation and Air Conditioning Diagnostics for Single Family Homes Vincent Pedalino FSL Home Improvements Phoenix, AZ 1 HVAC Basics Ways to improve the performance of existing air conditioning

More information

Water should be removed as soon as possible once the safety of the structure has been verified.

Water should be removed as soon as possible once the safety of the structure has been verified. FACT SHEET Posted October 18 2005 Check List for Infection Control Concerns when Reopening Healthcare Facilities Closed due to Extensive Water and Wind Damage Prior to opening a healthcare facility that

More information

Risk Assessment: Biosafety Cabinet

Risk Assessment: Biosafety Cabinet Risk Assessment: Biosafety Cabinet Biosafety cabinets (BSCs) serve as primary containment devices for operations involving potential splashes, spills or aerosolization of hazardous biological materials.

More information

PERCENT OUTDOOR AIR (%OA) CALCULATION AND ITS USE

PERCENT OUTDOOR AIR (%OA) CALCULATION AND ITS USE PERCENT OUTDOOR AIR (%OA) CALCULATION AND ITS USE APPLICATION NOTE TI-138 TSI s IAQ-CALC TM Indoor Air Quality Meter and TH-CALC TM Thermohygrometer calculate Percent Outdoor Air (%OA). In order to take

More information

Remediation of Mold Contaminated Ductwork

Remediation of Mold Contaminated Ductwork Remediation of Mold Contaminated Ductwork Roger G. Morse AIA, Paul Haas CSP, CIH, Dean Zehnter, Andrea Grdina Morse Zehnter Associates The Problem Visible mold growth on interior of liner inside air handling

More information

Evaluate, Clean, and Tune Guidance

Evaluate, Clean, and Tune Guidance Evaluate, Clean, and Tune Guidance The Evaluate, Clean and Tune (ECT) process serves three essential purposes in the Weatherization Assistance Program (WAP). The first is to evaluate the existing system

More information

Procedures for the Effective Use of Biological Safety Cabinets

Procedures for the Effective Use of Biological Safety Cabinets Procedures for the Effective Use of Biological Safety Cabinets APPROVAL DATE BY BIOHAZARDS SUBCOMMITTEE: August 10, 2012 SUPERSEDES: March 1, 2012 This corporate guideline/procedure is intended as a minimum

More information

DUCT CLEANLINESS FOR NEW CONSTRUCTION GUIDELINES

DUCT CLEANLINESS FOR NEW CONSTRUCTION GUIDELINES DUCT CLEANLINESS FOR NEW CONSTRUCTION GUIDELINES Sheet Metal and Air Conditioning Contractors National Association, Inc. 4201 Lafayette Center Drive Chantilly, VA 20151-1209 DUCT CLEANLINESS FOR NEW CONSTRUCTION

More information

NORSOK STANDARD H-001 Rev. 4, Nov. 2001. Heating, ventilation and air-conditioning

NORSOK STANDARD H-001 Rev. 4, Nov. 2001. Heating, ventilation and air-conditioning NORSOK STANDARD H-001 Rev. 4, Nov. 2001 Heating, ventilation and air-conditioning This NORSOK standard is developed by NTS with broad industry participation. Please note that whilst every effort has been

More information

Terms of Reference Air Handling Unit (HVAC System) Cleaning

Terms of Reference Air Handling Unit (HVAC System) Cleaning Terms of Reference Air Handling Unit (HVAC System) Cleaning Introduction General cleaning of the air handling units is currently undertaken by the Mechanical Division staff composing of 3 personnel. Cleaning

More information

RKE. Heat recovery unit. heat recovery unit RKE. from 200 to 6800 m 3 /h. General features

RKE. Heat recovery unit. heat recovery unit RKE. from 200 to 6800 m 3 /h. General features RKE Heat recovery unit from 200 to 6800 m 3 /h General features RKE heat recovery units are suitable for residential and commercial applications and offer a real energy saving in forced ventilation plants,

More information

USP <797> Cleanroom Design and Environmental Monitoring. Andrew King, USP <797> Specialist CETA Member RCCP-SC

USP <797> Cleanroom Design and Environmental Monitoring. Andrew King, USP <797> Specialist CETA Member RCCP-SC USP Cleanroom Design and Environmental Monitoring Andrew King, USP Specialist CETA Member RCCP-SC Objectives The objectives of this presentation: To summarize basic cleanroom concepts and how

More information

Lesson 36 Selection Of Air Conditioning Systems

Lesson 36 Selection Of Air Conditioning Systems Lesson 36 Selection Of Air Conditioning Systems Version 1 ME, IIT Kharagpur 1 The specific objectives of this chapter are to: 1. Introduction to thermal distribution systems and their functions (Section

More information

DUFFERIN-PEEL CATHOLIC DISTRICT SCHOOL BOARD

DUFFERIN-PEEL CATHOLIC DISTRICT SCHOOL BOARD DUFFERIN-PEEL CATHOLIC DISTRICT SCHOOL BOARD JOB DESCRIPTION POSITION TITLE: Air Conditioning Mechanic DEPARTMENT: Plant TITLE OF IMMEDIATE SUPERVISOR: Supervisor, Maintenance Services Position Summary

More information

(Rev. 37, Issued: 10-17-08; Effective/Implementation Date: 10-17-08) 482.51 Condition of Participation: Surgical Services

(Rev. 37, Issued: 10-17-08; Effective/Implementation Date: 10-17-08) 482.51 Condition of Participation: Surgical Services Interpretive Guidelines 482.45(b)(1) (3) If you have questions concerning the facility membership in the Organ Procurement and Transplantation Network; you may verify the membership by contacting the CMS

More information

Bring the fresh in. Dedicated Outside Air Systems

Bring the fresh in. Dedicated Outside Air Systems Bring the fresh in. Dedicated Outside Air Systems The inside story on outside air. On average, we breathe in 3,400 gallons of air each day. Ambient indoor air pollution is a major problem, affecting health

More information

Environment of Care Utility Systems Management Plan 2014 Updated 4.18.2014

Environment of Care Utility Systems Management Plan 2014 Updated 4.18.2014 Environment of Care Utility Systems Management Plan 2014 Updated 4.18.2014 PURPOSE The objectives of the Utility Systems Management plan is to establish, maintain, and continually provide a reliable utility

More information