Controller Automation, Model II+



Similar documents
GPD 506/P5 Start-up Procedure and Checklist

SMS Alarm Messenger. Setup Software Guide. SMSPro_Setup. Revision [Version 2.2]

NX Series Inverters. HVAC Pocket Programming Guide

MTS Power Products MIAMI FL ATS-22AG. Automatic Transfer Switch And Control PLC Operator s Manual

NOVA MULTI-MONITORING SOFTWARE. Instruction Manual

Programmer/Controller

AUTOMATIC TRANSFER SWITCH CONTROL UNIT OPERATOR S MANUAL

FLOW CALCULATOR INSTRUCTION MANUAL MESURES BAMOPHOX M1 02 E MES FLOW CALCULATOR /1

HCS-3300/3302/3304 USB Remote Programmable Laboratory Grade Switching Mode Power Supply

SMS GSM Alarm Messenger

Firmware version: 1.10 Issue: 7 AUTODIALER GD30.2. Instruction Manual

LiteKeeper 4 & 8 Programming Guide and User Manual

TMO2D with Fault Alarm and Event Log. Software Version 4B (or Earlier) Using the Fault Alarm

Chapter 9 N.C. C. N.O. Single-Pole Double-Throw

Contents. Introduction

FlexPak 3000 Digital DC Drive Software Reference Manual Version 4.3

DVR-4TL/8TL/16TL Setup Guide

ALARM ANNUNCIATOR ME INSTRUCTION MANUAL

NELSON VOLTAGE MONITOR INSTALLATION & PROGRAMMING MANUAL

Research RF Sputtering Packages

Electronic Control Devices The European Product Catalogue 2007

Temperature & Humidity SMS Alert Controller

TC 1818a. Operating Guide. Control Module SWM-015.5

T Sentry 4 Multi-Point Digital Alarm Instruction Manual

Contact Center CC-165 INSTALLATION & USER'S GUIDE

MANUAL FOR MODEL MP30 ELECTRIC MOTOR DRIVEN LIMITED SERVICE CONTROLLER

ALARMS-xx. Remote Alarm Unit Setup Guide RESET ALL

LEN s.r.l. Via S. Andrea di Rovereto 33 c.s CHIAVARI (GE) Tel Fax mailto: len@len.it url: http//

Applied Electronics. Commercial Dimming System UPDATE NOTICE

NL708 (XWA11V) Walk-In Temp / Door /Alarm / Light Module

TEMON 8-C. Doc. N MO-0370-ING TEMPERATURE MONITOR DEVICE TYPE TEMON 8-C OPERATION MANUAL. Microener - Copyright 2010 FW 2.2 Date Rev.

Variable Air Volume - VAV

TECHNICAL SERVICE DEPARTMENT Technical Service Bulletin Tankless Electric (RTE) Troubleshooting

T-100-R Installation Guide

DC1100 & 1400 Energy Controllers. Satchwell DC1100 & DC1400 for energy-efficient temperature control in smaller buildings.

NortechCommander Software Operating Manual MAN R6

HEAT HEAT COOL HEAT PUMP COOL

INSTALLER S & OWNER S MANUAL

ZC-24DO CANopen I/O Module: 24 Digital Outputs

BlueSolar Pro Remote Panel For BlueSolar PWM-Pro charge controllers 12/24V 5, 10, 20, 30A Article number SCC

STATUS POWER MONITOR ALARM SOS DISARM

MODEL 4400 TEMPERATURE CONTROL Royalton Rd. Cleveland, OH (440) (440)

Operational Overview and Controls Guide

Part Number Revision A, January Monitoring System Rack Configuration and Utilities Guide

S4000TH HART. HART Communication Manual

Technical Overview Add-on Sensors - Smoke Alarm. Get yours direct at:

VLT 6000 HVAC. Contents

Tutorial: Configuring GOOSE in MiCOM S1 Studio 1. Requirements

Configuring Alarms & Relays in the Enhanced Transformer Advantage

Owner s Guide Guide du propriétaire Guía para el usuario TH115-AF-GB-10. Programmable thermostat Thermostat programmable Termostato programable

EGCP-3 LS Revision L. Explanation of Software Changes Made for the EGCP-3 LS Control. Application Note 51294

SCADA Controlled Multi-Step Automatic Controlled Capacitor Banks & Filter Banks

WD-AMX Water Detection Controllers

Daker DK 1, 2, 3 kva. Manuel d installation Installation manual. Part. LE05334AC-07/13-01 GF

Temperature & Humidity SMS Alert Controller

RAINCONTROL LCD Special

ETC TWO STAGE ELECTRONIC TEMPERATURE CONTROL

30RB/30RQ. Operation and maintenance instructions

Product Information Sheet UH36 Hi Pot Tester

Electronic Control Devices The European Product Catalogue 2007

AC-115 Compact Networked Single Door Controller. Installation and User Manual

Copyrights 2010 Victron Energy B.V. All Rights Reserved

OCTOPLUS WARNING AND MEASUREMENT CONTROL UNIT FOR TOXIC AND FLAMMABLE GASES

Multi-Range Programmable DC Power Supplies 9115 Series

Conventional Fire Detection and Extinguishant Control System Specification

Automatic Telephone Dialer TD-101(W)

Software Manual RS232 Laser Merge Module. Document # SU Rev A

Business/Home GSM Alarm System. Installation and User Manual

SFC-200 SERIES FIRE ALARM CONTROL PANELS. SFC-200 Series Fire Alarm Control Panels. Features. Description

Medical Vacuum Systems-PXMI

INSTALLATION MANUAL 3RP / 5RP 4-BUTTON SERIES VEHICLE SECURITY SYSTEMS

INSTRUCTION MANUAL for UNIBLITZ MODEL DM412 SHUTTER DRIVE MODULE

User Manual. Humidity-Temperature Chart Recorder. Model RH520

SECTION DETECTION AND ALARM

SECTION 13XXX CONTROL DESCRIPTION (DICP Models NC, 412, 622, 826, 1030)

MANUAL PC1000R

LINETRAXX VMD460-NA. Network and system protection (NS protection) for monitoring the power feed-in of power generation systems

K9 Heat Alarm Owners Manual HA-1520

Manual for Fire Suppression & Methane Detection System

Inwall 4 Input / 4 Output Module

MSL1000 Monitored Serial Link Interface Manual V1.01

Multi-Range Programmable DC Power Supplies 9115 Series

TURBOtech srl. SED-635 Digital Excitation System. Industrial Electronics Sector FEATURES

WinLIN Setup and Operation:

HP 5 Microprocessor Control for Mammoth Water Source Heat Pumps

D Issue D Original. Instruction Manual. Turbo Controller. TIC Turbo Controller 200W

MODEL 5010 DUAL CHANNEL SMOKE/FIRE DETECTION MODULE

T5000 T000 LCD Digital Fan Coil Thermostat

Input signal Maximum Range Accuracy. Thermocouple E -50 to 700 C (-58 to 1832 F) ±1 C

LOVELINK III- Process Monitoring, Logging, Graphing, & Configuration

Workshop 7 PC Software - Tracker

S100. GSM House Alarm System.

MAKING MODERN LIVING POSSIBLE. UniLynx Indoor User Manual. ULX 1800i ULX 3000i ULX 3600i ULX 5400i SOLAR INVERTERS

Preliminary. Dual-line FLOW rate/totalizers. Pr ovu Model PD6200 Analog Input. Pr ovu Model PD6300 Pulse Input. Analog Inputs.

KCU Communication. PC Software Installation and User s Guide For KCU-30 / KCU-40 / KCU-50 modules. System requirement: Windows XP or above

How to read this guide

RF Etch Monitor. Introduction

Memcom Emergency Telephone

22X DSP COLOR ZOOM CAMERA AUTO FOCUS ZOOM CAMERA

Operation Manual. Smart-UPS X Uninterruptible Power Supply

Transcription:

Controller Automation

Page 2 of 2

Automation with the RADAK II+ power controller II+ I/O Points: Inputs 5 Programmable Digital inputs 2 Dedicated digital inputs (Channel select and External SCR control select) SCR Control signal BNC Channel select input External SCR control select Relays (2A, 264Vac max.) Dedicated Alarm (SPDT) 2 Programmable (SPST) RS232 serial communications DB9 serial adapter Page 3 of 2

Configurations: Digital Input The digital inputs can be used to initiate various events in the temperature controller, such as starting and stopping programs, selecting a specific program to run, or selecting a different PID set to use. Each of the five digital inputs may be configured to activate one of the following events: Manual mode select Remote setpoint select Setpoint 2 select PID set 2 select Integral hold One shot self tune enable Adaptive tune enable Acknowledge alarms Select Full access level Keylock Run program Hold program Run program (closed) / Hold (open) Standby ALL control outputs turned OFF Simulate pressing of the up button Simulate pressing of the down button Simulate pressing of the cycle button Simulate pressing of the page button Skip to End of Current Segment, without changing the setpoint Program holdback enabled Setpoint Rate Limit Enable Program waits at the end of the current segment Program Run (closed) / Reset (open) Program Reset (closed) / Run (open) Reset program Process Value Select: Closed = PV / Open = PV2 Advance to End of Segment and to target Setpoint To use these capabilities, the temperature controller must be configured with the intended function of each input. Once configured, the digital inputs are activated by connecting their respective input lines to the digital I/O common lead. Relay The relay outputs can be used to signal various events in the temperature controller, such as temperature alarms, program end, sensor break, load failure, or programmed event. The RADAK II+ has one alarm relay and two programmable relays. Both the alarm relay and the programmable relays have the same functions, however, the alarm relay provides both a normally open (NO) and normally closed (NC) contact where the programmable relays have only one contact which can be configured as NO or NC. Page 4 of 2

Each of the three relays may be configured to signal any combination of the following events: Alarm active YES / no Alarm 2 active YES / no Alarm 3 active YES / no Alarm 4 active YES / no Controller in manual mode YES / no Sensor break YES / no Programmer event output ( to 8) active YES / no Load failure alarm YES / no Tuning in progress YES / no New Alarm has occurred YES / no End of setpoint rate limit, or end of program YES / no Voltage output open circuit, or ma output open circuit YES / no Process Value out of range YES / no To use these capabilities, the temperature controller must be configured with the intended function of each relay. Once configured, the relay will complete the circuit between the NO and common lead when any of the events it is assigned occurs. RS232 serial communications All parameters that can be accessed through the operator interface may also be accessed via RS232 serial communications. There are several methods available to perform the actual communications. Commands may be sent and received manually from any windows based terminal application. Communication can be performed through software written by the end user (see sample programs attached). Eurotherm itools software provides an extensive suite of applications for communicating with and operating the 244 controller, which is the heart of the RADAK II+. Example Control Schemes: Goal Condition the source to 4 C, deposit 2Å of material at Å/sec, ramp source back to ambient temperature. Equipment A vacuum chamber equipped with a RADAK furnace Suitable source shutter Crystal deposition rate monitor Deposition controller with input and output capabilities RADAK II+ power controller. Page 5 of 2

Assumptions All equipment is installed and operating properly. Both the RADAK II+ and the deposition controller have been calibrated and operating with appropriate PID s, tooling factors, etc. The crystal is positioned in the system such that deposition rate is monitored with the source shutter open or closed. The deposition controller is wired to control the source shutter The deposition controller is configured for shutter delay (controller establishes proper, stable rate prior to opening the shutter). As mentioned above, each digital input and each relay output must be configured with an associated event(s). See the RADAK II+ power controller manual for a detailed description of the event assignment procedure. Page 6 of 2

Item Alarm setpoint C Alarm relay close on: Alarm active Sensor break Programmable relay close on: Digital input Digital input 2 Digital input 3 Event output Reset Controller on Open Wait on close Standby on close RADAK II+ Configuration Description Indicates furnace hot. Prevent system vent with hot furnace Furnace over temp or temp. unknown. Reset power controller, return furnace control to power controller, and signal deposition controller to stop. Triggered by power controller program, signals the deposition controller that the furnace is at deposition temperature, and enables external furnace control. Resets power output to minimum and terminates program operation. Tied to event output, causes program operation to hold while deposition controller runs the deposition. Tied to deposition controller end of process, alarm, fault, etc. causes event output to clear, transferring control of the furnace back to the power controller resuming program operation for source shutdown. Page 7 of 2 Figure. System control wiring

RADAK II+ Power Controller Alarm NO NC C Deposition Controller Input Stop Input Reset on SCR Select Event NO C NO C In Progress Input Start Input 2 Wait NC Input 3 Standby C Shutdown Page 8 of 2

Deposition sequence. Operator initiates process by pressing the Run/Hold button on the power controller front panel 2. Power controller program segment one raises source temperature to 4 C over 2 minutes. 3. Power controller program segment two maintains the source at 4 C for 2 minutes to condition source. 4. Power controller program segment three dwells at 4 C and activates output event. 5. event signals the deposition controller to start the deposition and places the power controller in a wait state holding the program in the segment three dwell. 6. The deposition controller enters its in progress state, closing the in progress output relay. 7. With the in progress relay (NO), output event relay (NO), and alarm relay (NC) contacts closed, the SCR select relay is energized transferring furnace control to the deposition controller. 8. The deposition controller enters the shutter delay state, adjusting furnace power as required to stabilize rate at Å/sec. 9. The deposition controller enters the deposit state and opens the shutter, varying furnace power as necessary to maintain deposition rate at Å/sec. At 2Å, the deposition controller enters the end of process state, closes the source shutter and opens the normally closed shutdown relay.. With the shutdown relay s (NC) contact open, the power controllers input 3 is activated causing a standby event. 2. The standby event clears all digital outputs (except alarms) on the power controller. Clearing the event output de energizes the SCR relay, transferring furnace control back to the power controller. Clearing the event output also releases the controller from its wait state resuming program operation. Page 9 of 2

3. The power controller reduces the furnace temperature setpoint to over 2 minutes. 4. Deposition is complete. Program 2 3 4 4 Furnace Temperatur 25 C RADAK Power Controller II+ Alarm Input Input 2 Input 3 Input Input Deposition Controller Input Sequence Step,2 3 4 5 6 7 8,9 2 3 Page of 2

Other automation options Use the II+ controllers logic input as a vacuum interlock. Logic A will be configured for standby (StbY). In standby mode, all controller outputs (power) are turned off, and the temperature setpoint display will alternate between the set temperature and StbY. To configure the logic input, place the controller in configuration mode (see the explanation in the manual). Use the advance button to select the logic A menu (LA). Use the scroll button to advance to the function (Func) screen (Figure 2). Use the up/down buttons to select reset (res). Use the advance button to return to the top menu and advance to the exit screen. Use the arrows to select yes then advance to reboot the controller. Figure 2 Menu structure to access the logic function in config mode. Controller wiring. Logic A input is accessed through I/O cable 4 wire (red). Logic A common is on cable 4, wire (black). Closing the circuit between these two wires will place the controller in standby mode holding program execution and turning all power output off. Program execution/power output will resume once the circuit is opened. Page of 2

A few other thoughts: You may want to disable the manual feature. In this controller, manual means manually overriding the pid and setting the power output. Despite the warning in the instruction manual, we ve had more than one customer place the unit in manual mode and, thinking they were setting temperature, get very frustrated that they could not raise the temperature setpoint above. Having inadvertently set the power output to %, the furnace temperature quickly rises above C. There is a decent section in the manual on disabling this feature. Remote trim. As an alternative to driving the scr directly via the bnc connector on the rear panel, remote trim may be used. With remote trim, your external voltage signal is used to vary the controller temperature setpoint by a preset range. This allows the rate controller to produce an error signal but leaves actual temperature control to the controllers pid. The downside of this method is that you need to have a good idea of the range to be set for the trim. It takes a little experimenting to determine the proper range for the trim. If the range is something that will be changed often, it is possible to promote these setpoints to the operator screen so you don t have to go into configuration every time. If you re interested, contact us and we ll help you set it up. Eurotherms auto tune feature is a good starting point for calibration but can produce some prohibitively long time constants for operation at lower temperatures ( 3 C). Integral and derivative times in the hundreds of seconds may produce a smooth ramp rate but it s a long wait. The controller has a feature called gain scheduling which allows two pid s to be used depending on the temperature of the furnace. The controllers are shipped with gain scheduling enabled and set for 5 C. If you don t already have itools from Eurotherm, it can be quite useful http://www.eurotherm3.com/itools/itdnlds.htm. Page 2 of 2