Engineering White Paper UTILIZING ECONOMIZERS EFFECTIVELY IN THE DATA CENTER



Similar documents
Economizer Fundamentals: Smart Approaches to Energy-Efficient Free-Cooling for Data Centers

Energy Efficient Cooling Solutions for Data Centers

Five Strategies for Cutting Data Center Energy Costs Through Enhanced Cooling Efficiency

Liebert : The Right Cooling For IT Environments. Precision Cooling For Business-Critical Continuity

Precision versus Comfort Cooling Choosing a Cooling System to Support Business-Critical IT Environments

Combining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency

Data Center Design Guide featuring Water-Side Economizer Solutions. with Dynamic Economizer Cooling

STULZ Water-Side Economizer Solutions

Defining Quality. Building Comfort. Precision. Air Conditioning

Maximize energy savings Increase life of cooling equipment More reliable for extreme cold weather conditions There are disadvantages

Data Center Precision Cooling: The Need For A Higher Level Of Service Expertise. A White Paper from the Experts in Business-Critical Continuity

Liebert EFC from 100 to 350 kw. The Highly Efficient Indirect Evaporative Freecooling Unit

CURBING THE COST OF DATA CENTER COOLING. Charles B. Kensky, PE, LEED AP BD+C, CEA Executive Vice President Bala Consulting Engineers

Free Cooling in Data Centers. John Speck, RCDD, DCDC JFC Solutions

How To Run A Data Center Efficiently

The Different Types of Air Conditioning Equipment for IT Environments

DATA CENTER COOLING INNOVATIVE COOLING TECHNOLOGIES FOR YOUR DATA CENTER

USE OF AIR SIDE ECONOMIZER FOR DATA CENTER THERMAL MANAGEMENT. A Thesis Presented to The Academic Faculty. Anubhav Kumar

IT White Paper MANAGING EXTREME HEAT: COOLING STRATEGIES FOR HIGH-DENSITY SYSTEMS

Liebert CW kW Chilled Water Cooled Precision Air Conditioning For Data Centers

HVAC Systems: Overview

Climate solutions. evaporative cooling, adiabatic humidification and programmable controllers. energy saving solutions for data centers. carel.

Energy Efficiency. Energy Efficient Home Cooling:

How to Save Over 60% on Cooling Energy Needed by a Data Center? The Roadmap from Traditional to Optimized Cooling

Moisture Control. It s The Dew Point. Stupid! Its not the humidity.

How and Why Mission- Critical Cooling Systems Differ From Common Air Conditioners

White Paper #10. Energy Efficiency in Computer Data Centers

New Deluxe Wall Mounted Heat Pump Series EXTERIOS

Protecting Our Information, Protecting Our Resources

State of the Art Energy Efficient Data Centre Air Conditioning

UNIVERSITY OF MISSOURI Heating Ventilating and Air-Conditioning (HVAC) March

Tech Byte 27: Small Computer Room and IT Closet Cooling

How To Save Energy On A Power Supply

Why Do I Need Precision Air Conditioning?

The High Performance Floormount Indoor Package Cooling Solution. Precision Cooling for Business-Critical Continuity

1932 Lexington Houston, Texas (713) Recommendations for installation of cooling systems

Example Retrocommissioning Measure: Opening Throttled Discharge Valves

Presentation Outline. Common Terms / Concepts HVAC Building Blocks. Links. Plant Level Building Blocks. Air Distribution Building Blocks

Bring the fresh in. Dedicated Outside Air Systems

APPLICATION GUIDE. Comparison of Latent Cooling Performance of Various HVAC systems in a Classroom Application

newsletter engineers energy-saving strategies for Water-Source Heat Pump Systems volume 36 2 providing insights for today s hvac system designer

Liebert CRV Row-Based Cooling Intelligent Precision Cooling For Data Center Equipment. Precision Cooling For Business-Critical Continuity

How To Design A Building In New Delhi

SmartDesign Intelligent, Integrated Infrastructure For The Data Center. Solutions For Business-Critical Continuity

ENERGY EFFICIENT HVAC DESIGN FOR WARM-HUMID CLIMATE CLIMATE

3/29/2012 INTRODUCTION HVAC BASICS

7 Best Practices for Increasing Efficiency, Availability and Capacity. XXXX XXXXXXXX Liebert North America

Liebert Hiross HPW The High Performance Wallmount Cooling Solutions for Telecom Mobile Remote Access Nodes

HVAC Simplified Approach Option

Analysis of data centre cooling energy efficiency

Total Heat Versus Sensible Heat Evaporator Selection Methods & Application

KU DESIGN GUIDELINES APPENDIX XVI RECOMMENDED BAS I/O CONTROL POINTS BY EQUIPMENT / SYSTEM

ENHANCED LABORATORY HVAC SYSTEM

> Executive summary. Explanation of Cooling and Air Conditioning Terminology for IT Professionals. White Paper 11 Revision 2. Contents.

Glossary of Heating, Ventilation and Air Conditioning Terms

THERMAL CLIMATE IN A DATA CENTER

Dehumidification Frequently Asked Questions

Rittal White Paper 507: Understanding Data Center Cooling Energy Usage & Reduction Methods By: Daniel Kennedy

Lesson 36 Selection Of Air Conditioning Systems

Impacts of Refrigerant Charge on Air Conditioner and Heat Pump Performance

White Paper. Data Center Containment Cooling Strategies. Abstract WHITE PAPER EC9001. Geist Updated August 2010

Guide to Minimizing Compressor-based Cooling in Data Centers

International Telecommunication Union SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES IN PUBLIC NETWORKS

It will be available soon as an 8.5 X 11 paperback. For easier navigation through the e book, use the table of contents.

Technical Note: Comparing R407C and R410A as Alternatives for R22. A Technical Note from the Experts in Business-Critical Continuity

APPLICATION GUIDE. Moisture Management in Waterborne Climate Systems

National Grid Your Partner in Energy Solutions

85 F 80 F 50% 75 F 70 F 73.0/ F 10% Figure 1

Measuring The Right Thing For Humidity Control It s the Dew Point Stupid!

AIR CONDITIONING EFFICIENCY F8 Energy eco-efficiency opportunities in Queensland Foundries

HVAC Basic Science - System Capacity

Dr. Michael K. West, PE 1 Dr. Richard S. Combes, PE 2 Advantek Consulting / Melbourne, Florida

Ten Steps to Increasing Data Center Efficiency and Availability through Infrastructure Monitoring

Liebert Deluxe System/3

Energy Efficiency in New and Existing Data Centers-Where the Opportunities May Lie

Creating Efficient HVAC Systems

Absolute and relative humidity Precise and comfort air-conditioning

HVAC Efficiency Definitions

Power Management Strategies for High-Density IT Facilities and Systems. A White Paper from the Experts in Business-Critical Continuity TM

Pool Dehumidification Basics

Rittal White Paper 508: Economized Data Center Cooling Defining Methods & Implementation Practices By: Daniel Kennedy

Liebert icom Thermal System Controls Greater Data Center Protection, Efficiency & Insight

Liebert CRV Row-Based Cooling Intelligent Precision Cooling For Data Center Equipment

STULZ Solutions and Services

CRITICAL COOLING FOR DATA CENTERS

How To Buy A Lennox Power System

Air Conditioning 101. STN Presentation AC101

Chapter 3.4: HVAC & Refrigeration System

Economizer Modes of Data Center Cooling Systems

Statement of Work. 3.0 Details of Service Pre Start-up Cooling Start-up Service. Installation Service. Table of Contents. 1.0 Executive Summary

How To Control Humidity With A Humidifier

Certified HVAC Audit Report Key Takeaways and Implications. Created for: Pets On the Go 445 Logging Road, Building 3 Yardley, PA-19034

Data Realty Colocation Data Center Ignition Park, South Bend, IN. Owner: Data Realty Engineer: ESD Architect: BSA LifeStructures

Air-Conditioning Buying Guide

Award-Winning Innovation in Data Center Cooling Design

SECTION 5 COMMERCIAL REFRIGERATION UNIT 22 CONDENSERS

Preliminary Final Proposal

Chilled Water HVAC Systems


Causes of High Relative Humidity Inside Air Conditioned Buildings. Roger G.Morse AIA, Paul Haas CSP, CIH Morse Zehnter Associates

Transcription:

Engineering White Paper UTILIZING ECONOMIZERS EFFECTIVELY IN THE DATA CENTER

SUMMARY A proper balance of temperature and humidity control is essential for efficient data center operation, and integral to protecting the significant investment in computer and network technology in such facilities. However, increasing energy costs challenge engineers to find the most cost-effective ways to control temperature and humidity within acceptable ranges. The use of economizer systems is one method that has been adopted to lower energy usage, lessen wear and tear on precision air conditioning equipment and decrease operational costs. The two primary types of economizer systems are air-side economizers and fluid-based economizers. The stringent temperature and humidity requirements of data centers, coupled with the need for 24-hour cooling 365 days per year, typically make fluid-based economizers the system of choice for most data centers environments. Fluid-based economizers also provide effectiveness in a wider portion of the temperature/ humidity band required by today s data center computer systems, so they are more suited to a data center than dual-enthalpy control air-side economizer systems. Within the fluidbased economizer category, glycol-based systems operate effectively at the widest range of outdoor ambient temperatures. 1

What Are Economizer Systems and Why Are They Useful? Economizer systems use outside air, when it is cold enough, to help meet cooling requirements and provide so-called free cooling cycles for computer rooms and data centers. When an economizer system is operating, the use of an air conditioning system s compressor(s) and related electro-mechanical components is reduced or eliminated. In certain geographical locations, economizers can satisfy a large portion of data center cooling requirements. The use of economizer systems can have a significant impact on energy usage. A study on building control systems conducted by Battelle Laboratories and reported by the National Building Controls Information Program found that, on average, the normalized heating and cooling Energy Use Intensity (EUI) of buildings with economizers was approximately 13 percent lower than those without economizers. The use of economizers is also now required by some building codes. The energy code adopted by the City of Seattle in 2001 requires the application of economizer systems in computer rooms and data centers. The State of Massachusetts Energy Code for Commercial and High-Rise Residential New Construction, effective in 2001, requires, with some exceptions, air or water economizers for all cooling systems with a total cooling capacity of at least 65,000 btu per hour. Types of Economizers and How They Work There are two types of economizer systems, typically referred to as air-side and fluid-side economizers. An air-side economizer system serves as a control mechanism to regulate the use of outside air for cooling in a room or building. It utilizes a system of sensors, ducts and dampers to allow entry of the appropriate volume of outside air to satisfy cooling demands. The sensors measure the outside and inside air conditions. If outside conditions are suitable for the use of outside air for cooling, the economizer adjusts the dampers to introduce the outside air, making it the primary source of air for cooling the space. This reduces or eliminates the need for the air conditioning system s compressor(s), which results in a significant energy savings for cooling the space. Air-side economizers also include exhaust air dampers to prevent the facility from becoming over-pressurized when large amounts of outside air are introduced. A fluid-side economizer system (often called water-side) works in conjunction with a heat rejection loop consisting of either a cooling tower, evaporative cooler or drycooler to satisfy cooling requirements. A fluid-side economizer system is typically incorporated into a chilled water or glycolbased cooling system. For economizer operation, the fluid used in the cooling system passes through an additional coil to cool the room air, eliminating the need for compressor operation. 2

While they operate in different ways, the ultimate goal of both air-side and fluid-side economizer systems is to provide free cooling to a room or facility, thus reducing the operating time of the air conditioning system s compressor(s). However, fundamental differences between the two types of economizers have a direct impact on the most appropriate economizer choice for a data center environment. Choosing the Right System for Data Center Applications Theoretically, if the outside temperature is cool enough, 100 percent outside air can be used to meet cooling demand. In this case, an air side economizer should be sufficient for the job. However, computer systems require special considerations. In most situations, a water or fluid-based economizer is the optimum choice for a data center. Year-Round 24x7 Cooling Unlike the seasonal and intermittent heating and cooling requirements of office buildings and similar facilities, the controlled environment of a data center requires continuous, year-round cooling. This makes it an ideal candidate for economizer systems during the fall, winter and spring months. Maintaining consistent, acceptable temperature levels can be done with either system, but humidity control becomes a significant challenge with the air-side system. Precision Humidification and Temperature Control A clean, filtered environment with precise control of humidity is mandatory in a data center. Ignoring the impact of humidity can result in serious short and long term problems, including damage to equipment and to the facility s infrastructure. In most cases, the optimal relative humidity (RH) range for a data center environment is 45- percent. Introducing outside air via an air-side economizer system in the cold winter months is fine from a temperature standpoint, but unless further treatment of the air is done, it can lower RH to unacceptable levels, causing electrostatic discharge that interferes with normal equipment operation. A humidifier can be used to compensate for this, but its operation offsets some of the energy savings provided by the economizer. Depending on the particular location of the data center, humidification costs could run into thousands of dollars per year to maintain a room condition of 72 F/% RH. Figure 1 shows the cost to humidify 1000 cfm of outside air in New York City based on a power cost of $0.10 per kwhr using a canister-type humidifier. Multiply these values by the thousands of CFM needed to cool a space (assuming that some mixing can be done when the air temperature gets below 55 F), and it is clear that the humidification costs are not trivial. 3

DB Temp < 24 25-29 30-34 35-39 - 44 45-49 - 54 55-59 - 64 < 64 Range (F) Moisture 49 46.9 42.7 38.5 34.3 28.7 21 12.6 2.8 to be Added* (grains/lb) Hours/Year in 387 344 512 739 791 733 7 722 776 5774 Temp Range Cost to $457 $386 $518 $667 $629 $483 $367 $205 $48 $3,761 Humidify* * Based on $0.10 per kwhr and room conditions of 72F/% RH Figure 1. Humidification Costs for 1000 CFM of Outside Air in New York City Free Cooling Circuit (Water Side Economizer) Operating Range Computer Room Application In contrast, fluid-side economizer systems use the cold outside air to cool the water/ glycol loop, which in turn provides fluid cold enough for the cooling coils in the air conditioning system. This keeps the outside air out of the space and eliminates the need to condition that air. DRY BULB TEMPERATURE (F) Figure 2. Free cooling circuit (water side economizer) operating range computer room applications. Wet Bulb (F) 80 80% 90 % % 20% 80 90 100.028.024.020.018.012.008.004 HUMIDITY RATIO (Lbv/Lba) Figure 2 shows the ambient temperature envelope of operation for this type of system, which has no restrictions for ambient temperatures under 65 degrees F because outside air is not introduced into the space. Enthalpy Control The advantages of fluid-based economizers in a data center environment are further demonstrated when comparing their use versus an air-side economizer with dual enthalpy controls. A system with dual enthalpy controls uses two sensors to compare inside and outside air temperature and humidity levels. Use of dual enthalpy economizer controls is similar in principle to a fluid-based economizer system because they both take advantage of cold outside conditions to cool indoor temperatures and reduce compressor use. However, while a dual enthalpy controlled system is suitable for a wide range of operating conditions in a general facility, it is only effective in a small band of the required temperature and humidity range for a data center environment. 4

Dual Enthalpy Controller Operating Range Comfort Cooling Application Wet Bulb (F) 80 80% 90 % %.028.024.020.018.012 HUMIDITY RATIO (Lbv/Lba) Figure 3 shows the effective operating range for optimizing energy in a comfort cooling environment using dual enthalpy controls. Figure 4 is the same analysis, but for a data center application. Bringing in air from outside the band in Figure 4 will require additional humidification as described earlier, plus even some dehumidification for a small period of time. 20%.008 The Liebert GLYCOOL System Figure 3. Dual enthalpy controller operating range comfort cooling application. Dual Enthalpy Controller Optimum Operating Range Computer Room Application DRY BULB TEMPERATURE (F) Wet Bulb (F) 80 DRY BULB TEMPERATURE (F) 80% 90 % % 20% 80 90 100 Figure 4. Dual enthalpy controller operating range computer room application. 80 90 100.028.024.020.018.012.008.004.004 HUMIDITY RATIO (Lbv/Lba) Liebert s GLYCOOL system is a fluid-based economizer that maximizes energy savings while providing the accuracy and reliability demanded by sensitive data center equipment and operations. The GLYCOOL system is part of a Liebert glycol-cooled Deluxe System/3. The system is self contained and includes controls to make an intelligent decision about cooling mode: Normal compressorized cooling, full free cooling or partial free cooling. At ambient temperatures above approximately 65 F, the unit functions as a normal glycol cooled dual compressor system, with the compressors providing the cooling. As the outdoor temperature drops, the temperature of the fluid in the heat rejection loop drops also. Once it is cold enough outside to supply some cooling, the control opens the modulating valve on the econ-o-coil circuit. The econ-o-coil then provides some free cooling, while the compressors provide the rest of the cooling to satisfy the load. Once the fluid temperature is cold enough, the econ-o-coil has enough capacity to eliminate the need for the compressors, so they shut off. 5

Typically, a closed-circuit drycooler lowers the glycol temperature to the required 45 F needed to get full capacity from the econ-o-coil. Closed circuit evap coolers can also be used to take advantage of low wet bulb temperatures in very dry climates. By controlling the fluid temperature off of the ambient wet bulb temperature, significant free cooling can be obtained in cities such as Phoenix. Figure 5 compares power consumption of three glycol-cooled environmental systems and one glycol-cooled free cooling system (GLYCOOL) in their ranges of outdoor ambient temperature operation. Power consumption varies with outdoor temperature due to changes in system operating head pressure, system cooling capacity and amount of compressor operation required. Actual energy usage varies based on the hours of operation at each ambient range. The GLYCOOL fluid-based economizer system enables free cooling that significantly lowers power consumption at outdoor temperatures below 35 F, and relatively lower power consumption as temperatures approach 65 F. The Liebert equipment is also designed to operate as efficiently as possible even at high outdoor temperatures because it utilizes semi-hermetic compressor systems and A-frame coils. Adding cylinder unloaders to the compressors provides even more efficient operation, especially if the system is not fully loaded. 100% 90% 80% % of Full Compressor KW % % % % 30% 20% Single Compressor 100% load Single Compressor % loaded 100% load % loaded w/unloaders 100% loaded w/unloaders % loaded w/unloaders & Free Cooling % loaded 10% 0% 30 80 90 100 Ambient Temp (F) Figure 5. Compressor power consumption for 15-ton system 6

Precision air conditioners with dual compressors and unloaders operate 25 to 30 percent more efficiently than single compressor, non-unloading systems, while providing N+1 redundancy and capacity for future expansion. The GLYCOOL system uses dual compressors and unloading features to take full advantage of part load operation and lower outdoor ambient temperatures. Because start-up of each compressor is with the unloader valve activated, initial current surge and wear on the compressor is reduced. Conclusion The nature of today s computer and communications systems requires a more complex and thoughtful approach to environmental control planning for data centers than ever before. In most situations, air-side economizer systems do not meet the stringent temperature and humidity control requirements necessary for these mission-critical facilities. Glycol-based fluid economizer systems are the most appropriate choice to help reduce data center cooling costs, decrease energy usage and provide efficient, economical heat dissipation in a wide range of outdoor temperature and humidity conditions. LIEBERT CORPORATION 10 DEARBORN DrIVE P.O. BOX 29186 COLUMBUS, OHIO 43229 800.877.9222 (U.S. & CANADA ONLY) 614.888.0246 (OUTSIDE U.S.) FAX: 614.841.22 www.liebert.com While every precaution has been taken to ensure accuracy and completeness in this literature, Liebert Corporation assumes no responsibility, and disclaims all liability for damages resulting from use of this information or for any errors or omissions 2003 Liebert Corporation. All rights reserved throughout the world. Specifications subject to change without notice. Trademarks or registered trademarks are property of their respective owners. Liebert and the Liebert logo are registered trademarks of the Liebert Corporation Keeping Business in Business is a registered trademark of the Liebert Corporation. The Emerson logo is a trademark and service mark of the Emerson Electric Co. Printed in U.S.A. 1003. 7