D7024 Fire Alarm Control Panels Software Version V2.06 Program Record Sheet Account Information: Account: Date: Name: Address: Panel Phone #: Contact Phone #: Contact Person: Comments: Panel Location: Notes: Program Time Default values are in bold. System Date and Time Auto Test 1) Test Time: 0200 (24-hour military format) 2) Test Frequency (Circle one): 1-6 hours 2-12 hours 3-24 hours 4-7 days 5-28 days 3) Daylight Savings Time: 1) DISABLE 2) ENABLE
Security User PINS Worksheet (User 0 to 69) User # 0 is the Programmer PIN. User # 1 is the panel default PIN. Authority Key: 0 = none; 1 = maximum; 2 = medium; 3 = minimum User # PIN Authority User Name User # PIN Authority User Name 0 9876 1 35 1 1234 2 36 2 0000 0 37 3 38 4 39 5 40 6 41 7 42 8 43 9 44 10 45 11 46 12 47 13 48 14 49 15 50 16 51 17 52 18 53 19 54 20 55 21 56 22 57 23 58 24 59 25 60 26 61 27 62 28 63 29 64 30 65 31 66 32 67 33 68 34 69 43706E Page 2 2005 Bosch
User PINS Worksheet (User 70 to 99) Authority Key: 0 = none; 1 = maximum; 2 = medium; 3 = minimum User # PIN Authority User Name User # 70 85 71 86 72 87 73 88 74 89 75 90 76 91 77 92 78 93 79 94 80 95 81 96 82 97 83 98 84 99 PIN Authority User Name Program System Default values are in Bold. Timers Smoke Reset 6 sec (1-16 seconds) AC Fail Delay 6 hours (1-24 hours, or wait for DC) Auto Silence 0 min (5-99 minutes) Display Rate 4=1 sec (1-16 ¼ seconds) AC Line Sync 1) 50Hz 2) 60Hz (circle one) Option Bus, # of Keypads 0 (1-4) PIN Required, Local 1) YES 0) NO (circle one) PIN Required, Remote 1) YES 0) NO (circle one) Remote Program 1) ENABLE 0) DISABLE (circle one) 2005 Bosch Page 3 43706E
Program Inputs Input Point Worksheet (Points 1 to 25) Some point types are not available with all control panels. Points 4-8 require a 4-Point Expander Module. Points 9-255 are available only with a Multiplex Expansion Module. See the Point Function Worksheet on Page 6 when filling in the Point Function column. Use the MUX Device Type Key when filling in the MUX Device Type column. Photocopy the blank table on Page 5 for Point Numbers 26-255. 0 No Device 2 Single Input 3 I/O Module 4 MUX Smoke 5 Smoke w/frz 6 Dual Input 7 Octal Input Mux Device Type Key Point Number Point Function (see p. 6) Alarm/ Trouble on Open Zone Verification Latching MUX Device Type Text (write in description) 1-16 1=alarm 1-50 0=no 0=no see key 2=trouble 1=yes 1=yes 1 1 2 1 0 1 2 2 2 2 0 1 3 3 2 3 0 1 4 4 2 4 0 0 5 5 2 5 0 1 6 6 2 6 0 1 7 7 2 7 0 1 8 8 2 8 0 1 9 10 2 9 0 1 0 10 10 2 9 0 1 0 11 10 2 9 0 1 0 12 10 2 9 0 1 0 13 10 2 9 0 1 0 14 10 2 9 0 1 0 15 10 2 9 0 1 0 16 10 2 9 0 1 0 17 10 2 9 0 1 0 18 10 2 9 0 1 0 19 10 2 9 0 1 0 20 10 2 10 0 1 0 21 10 2 10 0 1 0 22 10 2 10 0 1 0 23 10 2 10 0 1 0 24 10 2 10 0 1 0 25 10 2 10 0 1 0 43706E Page 4 2005 Bosch
Point Input Worksheet (Point to ) Photocopy this page for Point Numbers 26-255. See the Point Function Worksheet on Page 6 when filling in the Point Function column. Use the MUX Device Type Key when filling in the MUX Device Type column. Point Number Point Function (see p. 6) Alarm/ Trouble on Open Zone Verification Latching MUX Device Type Text (write in description) 1-16 1=alarm 1-50 0=no 0=no see key 2=trouble 1=yes 1=yes * zone default for points 20-39=10, 40-59=11, 60-79=12, etc. 2005 Bosch Page 5 43706E
Point Function Worksheet The default values are in Bold. 1 Fire 2 Waterflow 3 Supervisory 4 Monitor 5 Reset 6 Silence Function Configure Key Parameters Point Function Configure Local Only Silenceable Loop Response see key 0=no 0=no 1=fast 1=yes 1=yes 2=programmable 1 1-fire 0-no 0-no 1-fast 2 1-fire 0-no 0-no 1-fast 3 1-fire 0-no 0-no 1-fast 4 2-waterflow 0-no 0-no 2-16 sec. 5 1-fire 0-no 0-no 1-fast 6 1-fire 0-no 0-no 1-fast 7 1-fire 0-no 0-no 1-fast 8 1-fire 0-no 0-no 1-fast 9 1-fire 0-no 0-no 1-fast 10 1-fire 0-no 0-no 1-fast 11 3-super 0-no 0-no 1-fast 12 4-monitor 0-no 0-no 1-fast 13 1-fire 0-no 0-no 1-fast 14 1-fire 0-no 0-no 1-fast 15 1-fire 0-no 0-no 1-fast 16 1-fire 0-no 0-no 1-fast 43706E Page 6 2005 Bosch
Program s (NACs and Relays) Default values are in Bold. Configuration Zone A Parameters Zone B Zone C Onboard and Expansion NACs NAC 1 3 53 0 0 0 NAC 2 1 53 0 0 0 NAC 3- not supported 1 53 0 0 0 NAC 4- not supported 1 53 0 0 0 Remote NAC Module 1- requires a Remote NAC Power Supply 1 1 53 0 0 0 2 1 53 0 0 0 3 1 53 0 0 0 4 1 53 0 0 0 Remote NAC Module 2 requires a Remote NAC Power Supply 1 1 53 0 0 0 2 1 53 0 0 0 3 1 53 0 0 0 4 1 53 0 0 0 Local Relays Local Relay 1 63 0 0 0 Local Relay 2 62 0 0 0 Remote Relay Module 1- requires an Octal Relay Module Relay 1 63 0 0 0 Relay 2 62 0 0 0 Relay 3 61 0 0 0 Relay 4 60 0 0 0 Relay 5 58 0 0 0 Relay 6 57 0 0 0 Relay 7 56 0 0 0 Relay 8 53 0 0 0 Remote Relay Module 2 - requires an Octal Relay Module Relay 1 1 0 0 0 Relay 2 2 0 0 0 Relay 3 3 0 0 0 Relay 4 4 0 0 0 Relay 5 5 0 0 0 Relay 6 6 0 0 0 Relay 7 7 0 0 0 Relay 8 8 0 0 0 Zone D 1 Steady 2 Pulsing 3 Temporal 4 Wheelock (not available for RNACs) Configuration Key ( Pattern) 63 General Alarm (does not silence) 62 General trouble 61 General Waterflow 60 No AC 59 Alarm verification 58 General supervisory alarm (does not silence) 57 Communication trouble 56 (reserved) 55 (reserved) 54 Activates for ground start 53 General fire 52 General fire (does not silence) 51 (reserved) 1-50 User Assigned to Inputs Zone Key 2005 Bosch Page 7 43706E
Program s (Mux s) Multiplex outputs are not supported by all panels. Photocopy the blank table on Page 9 for Point Numbers 41 255. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 Device Address Zone A Parameters Zone B Zone C Zone D 63 General Alarm (does not silence) 62 General trouble 61 General Waterflow 60 No AC 59 Alarm verification 58 General supervisory alarm (does not silence) 57 Communication trouble 56 (reserved) 55 (reserved) 54 Activates for ground start 53 General fire 52 General fire (does not silence) 51 (reserved) 1-50 User Assigned to Inputs Zone Key For MUX relay outputs, be sure to carefully select an appropriate output zone, or 0, for each output zone entry. The defaults supplied by the panel assume that an input is installed at the address, and are not appropriate when output modules are installed instead. 43706E Page 8 2005 Bosch
MUX Worksheet (MUX to ) Photocopy this page for MUX outputs 41-255. Use the MUX Device Type Key when filling in the MUX Device Type column. Device Address Zone A Parameters Zone B Zone C Zone D 63 General Alarm (does not silence) 62 General trouble 61 General Waterflow 60 No AC 59 Alarm verification 58 General supervisory alarm (does not silence) 57 Communication trouble 56 (reserved) 55 (reserved) 54 Activates for ground start 53 General fire 52 General fire (does not silence) 51 (reserved) 1-50 User Assigned to Inputs Zone Key 2005 Bosch Page 9 43706E
Program Accounts Default values are in Bold. Phone Numbers Worksheet Fill in the information on the lines provided. Phone Number 1: > Phone Number 2: > Computer Phone: Account Number 1: Account Number 2: Press See Action [TEST] 1 * Touch Tone * [TEST] 2 # Touch Tone # [TEST] 3 / 3 second delay [TEST] 4 > Wait for dial tone Special Phone Number Characters Phone 1 (Circle the desired setting) Format: (0) DISABLE (1) 3/1 (2) 4/2 (3) BFSK (4) SIA 110 (5) CONTACT ID (6) SIA 300 (7) Tone: (1) 19D, 14A, 10PS (2) 18D, 23A, 10PS (3) 19D, 14A, 20PS (4) 18D, 23A, 20PS (5) 19D, 14A, 40PS (6) 18D, 23A, 40PS Phone 2 (Circle the desired setting) Format: (0) DISABLE (1) 3/1 (2) 4/2 (3) BFSK (4) SIA 110 (5) CONTACT ID (6) SIA 300 (7) Tone: (1) 19D, 14A, 10PS (2) 18D, 23A, 10PS (3) 19D, 14A, 20PS (4) 18D, 23A, 20PS (5) 19D, 14A, 40PS (6) 18D, 23A, 40PS Phone Control Worksheet Circle the desired setting. Line 1 Line 2 Monitor Line: (1) YES (0) NO (1) YES (0) NO Dialing Type: (1) PULSE ONLY (2) TONE/PULSE (3) TONE ONLY (1) PULSE ONLY (2) TONE/PULSE (3) TONE ONLY Report Steering Worksheet Circle the desired setting. 1) Non-supervisory Alarm (1) Phone 1 (2) Phone 2 (3) Phones 1 and 2 (4) Phone 2 Backup 2) Supervisory Alarm (1) Phone 1 (2) Phone 2 (3) Phones 1 and 2 (4) Phone 2 Backup 3) Non-supervisory Restoral (1) Phone 1 (2) Phone 2 (3) Phones 1 and 2 (4) Phone 2 Backup 4) Supervisory Restoral (1) Phone 1 (2) Phone 2 (3) Phones 1 and 2 (4) Phone 2 Backup 5) Trouble (1) Phone 1 (2) Phone 2 (3) Phones 1 and 2 (4) Phone 2 Backup 6) Tests (1) Phone 1 (2) Phone 2 (3) Phones 1 and 2 (4) Phone 2 Backup 7) Silence (1) Phone 1 (2) Phone 2 (3) Phones 1 and 2 (4) Phone 2 Backup 8) Reset (1) Phone 1 (2) Phone 2 (3) Phones 1 and 2 (4) Phone 2 Backup 9) Fire Drill (1) Phone 1 (2) Phone 2 (3) Phones 1 and 2 (4) Phone 2 Backup Ring Count Ring Count Default : 00 Communicator Tries Communicator Tries Default : 10 Answering Machine Bypass 1) YES 2) NO 43706E Page 10 2005 Bosch
Program Formats Default values are in Bold. Data range is 0-9, A-F. 4/2 Point Reports Worksheet Fill in the desired setting in the User Setting column. Report Digit 1 Default Value Digit 1 User Setting Report Digit 2 Default Value User Setting Fire Alarm 0 Point 1 1 Fire Restore 3 Point 2 2 Waterflow 0 Point 3 3 Supervise 0 Point 4 4 Trouble 6 Point 5 5 Trouble Restl 3 Point 6 6 Disable B Point 7 7 Disable Restl 3 Point 8 8 Monitor 0 Point 9 9 Point 10 0 4/2 General Report Codes Worksheet Fill in the desired setting in the User Setting column. Data range is 00-FF. Report Digit 1 Default Value Digit 1 User Setting Report Digit 2 Default Value User Setting System in Test F1 AC Fail Restore EA System Test Rstl E1 Test Report EE Silence 9F Off Normal Test FD Fire Drill F2 Phone 1 Trbl FB Fire Drill Restl E2 Phone 1 Trbl Rstl EB Open Rst Report 9F Phone 2 Trbl FC Low Batt F9 Phone 2 Trbl Rstl EC Low Batt Restore E9 System Trbl FD AC Fail FA System Trbl Rstl ED 2005 Bosch Page 11 43706E
BFSK Reporting Codes Worksheet (for special reports) Fill in the desired setting in the User Setting column. Data range is 00-FF. BFSK Reporting Codes Default Value User Setting Off Normal Test Open/Reset Silence Fire Drill Fire Drill Restl SIA SIL Reporting Codes Worksheet Data range is 41-5A (hex). FD FD FD FD ED SIA SIL Reporting Codes Default Values User Setting Left Byte Right Byte 4B K 42 B Program Mux Mux Bus type (1) CLASS A (2) CLASS B Notes 2005 Bosch 130 Perinton Parkway, Fairport, NY 14450-9199 USA Customer Service: (800) 289-0096; Technical Support: (888) 886-6189 43706E 7/05 Program Record Sheet Software Version V2.06 Page 12 of 12