Installation Instructions DTS-HAZ DTS-HAZ-DC. for Use with Self-Regulating & Constant Wattage Heating Cables



Similar documents
Heat Tracing Sales Mt. Airy, Maryland Installation Instructions

DTS-HAZ DTS-HAZ-DC. Installation Instructions. for use with Self-Regulating, Constant Wattage & Mineral Insulated Electric Heating Cables

NELSON HEAT TRACING SYSTEMS

Self-Regulating Low Temperature Heating Cable

Thermwire. Selection Guide. Freeze Protection Heating Cable. Thermwire -Wrap. Pre-Assembled. Thermwire-Comp. Thermwire-Melt.

RayClic Connection System Installation Instructions

Installation Instructions. Industrial Heating Cable Products

Outdoor 33.6W Dual Port Passive Power-over-Ethernet Midspan For External Security Cameras and Wireless Access Points

ETC TWO STAGE ELECTRONIC TEMPERATURE CONTROL

33.6W Power over Ethernet Waterproof Adapter PoE Plus Single Port Injector for Outdoor Application

RayClic Connection System Installation Instructions

3. SEISCO PARTS & SERVICE REMOVAL AND REPAIR GUIDE

with MERCURY FREE 1 HP Relays ! WARNING Before using this product read and understand instructions.

BUILT-IN DISHWASHER INSTALLATION INSTRUCTIONS

Electric Heat Tracing INSTALLATION PROCEDURES

TABLE 1. Rugged cast aluminum alloy casing,celcon waterways with nichrome parts White (unless stainless steel housing)

READ THIS MANUAL BEFORE PROCEEDING WITH THE INSTALLATION. FAILURE TO FOLLOW THE INSTALLATION INSTRUCTIONS MAY VOID YOUR WARRANTY!

RAY-MAX Integrated Solar Power Strip

TECHNICAL DATA & SERVICE MANUAL SPLIT SYSTEM AIR CONDITIONER INDOOR UNIT: AW52AL AW64AL AW52AL AW64AL /05

REV. REL 1302 WEST BEARDSLEY AVENUE P.O. BOX 1127 ELKHART IN (574) FAX (574) ELKHART BRASS MFG. CO., INC.

Advantium 2 Plus Alarm

Service manual. Website: CAUTION - BEFORE SERVICING THE UNIT, READ THE SAFETY - PRECAUTIONS IN THIS MANUAL.

Contractors Guide Central Inverter System Installation

Oil and Coolant Circulating Heating System. Model - OCSM

Installation, Operation and MAINTENANCE INSTRUCTIONS. Industrial Heating Cable Products IMPORTANT GENERAL INSTRUCTIONS

Introduction. Safety Guidelines. Part Numbers. Operation and Maintenance Manual. Operation and Maintenance Manual

5800 Temperature Sensor Cable Assembly

OPERATING MANUAL CONTRACTOR STYLE AXIAL FANS

MCR1900 Media Converter 19-Slot Chassis

Reliance DuraStar ORDINARY LOCATION INSTALLATION, OPERATING & MAINTENANCE INSTRUCTIONS

LIEBERT VNSA Installation Sheet

ADDING AN ELECTRIC AUXILIARY FAN TO RADIATOR STACK ON 03 ALPINE COACH

SERVICE MANUAL RESIDENTIAL ELECTRIC AND LIGHT DUTY COMMERCIAL ELECTRIC WATER HEATERS. Troubleshooting Guide and Instructions for Service

EPSOLAR LS0512R / LS0524R. Solar Light Controller INSTRUCTION MANUAL. Please read this manual carefully before using the product!

Service Guide 12/27/03 TESTING, SERVICE & REPAIR GUIDE (For SH Space Heating Models & RA Water Heating Models)

KSR-SK-DB In-Line Splice Kit KSR Snow Melting Cable INSTALLATION PROCEDURES

INSTALLATION AND OPERATION INSTRUCTIONS - (LOW FLOW MODELS) (Before installation, compare electrical needed for the model of heater selected)

TABLE OF CONTENTS. I. TROUBLESHOOTING Section 1.01: Common Problems/Solutions... 2

TC-9102 Series Surface Mount Temperature Controllers

WIND ALARM. Wind Speed Alarm. Wind Speed. Set Point 2. Set Point 1 NEW BEDFORD, MA USA

Manual for Fire Suppression & Methane Detection System

Series 510 Submersible Level Transmitters


OPL BASIC. Dosing System for Professional Laundry machines. Contents

Toroidal Conductivity Sensor

INSTALLATION AND OPERATING INSTRUCTIONS For Model GL1 Gate Locks

INSTALLATION & OPERATING INSTRUCTIONS

POWER LOCK KIT GENERAL INSTALLATION -J04427 REV Kit Number. Models. Additional Parts Required. Kit Contents

DTM04 TANK MONITOR DTM08 TANK MONITOR Dtm12 TANK MONITOR. Installation and Operation Manual

OWNER S MANUAL FORCE 10 MARINE COMPANY HAMILTON ROAD RICHMOND, BC CANADA V6V 1C9 TEL: (604) FAX: (604)

4 Installation Requirements

Contact Information: Electrical Connection Kit for CL Series Constant Wattage Temptrace for Low Temperature Maintenance.

Use & Care Manual. Electric Tankless Water Heaters. With Installation Instructions for the Installer AP15447 (10/10)

DIGITAL ALARM II FOR HOSPITALS AND LABORATORIES INSTALLATION AND OPERATING INSTRUCTIONS

Installation and Troubleshooting Instructions for Electric Tankless Residential Water Heaters.

8146/5 Series Breaker Panelboards

TWIN EAGLES ALL WEATHER ELECTRIC RADIANT HEATER

Quartzone Infrared Quartz Tube & Metal Sheathed Electric Heaters

Water Leak Detection System

SOLAR ELECTRIC MODULE ES-124 & ES-62T Owners Manual and Installation Guide

RI-215A Operator s Manual. Part Number: RK Revision 0 Released: 10/3/05

HMI display Installation Guide

RMM2 Heat-Tracing Remote Monitoring Module for the Raychem NGC Control System Installation Instructions

Installation Instructions

HM-W536 Install Guide

Chromalox. Installation, Operation. Portable Industrial Unit Blower Air Heater Type DRA RENEWAL PARTS IDENTIFICATION

OASIS-PLUS 120V READ ALL INSTRUCTIONS BEFORE OPERATING READ ALL INSTRUCTIONS BEFORE OPERATING OZONE IS A POWERFUL OXIDIZER AND MUST BE USED WITH CARE

Table of Contents. 1 - Specifications Installation Wiring User controls...7

I nstallation. M100Q Series Proportional Actuator with R81Q Controller Board for Thermistor Sensor Applications. Tools Needed.

SOLAR PV STANDARD ELECTRICAL PLAN Microinverter Systems for Single Family Dwellings

THERMONET UNDERFLOOR HEATING STANDARD THERMOSTAT KIT STOCK CODE 5260

Master Time Clock MTC-200 MTC-400 MTC-600. Users Manual

Elecraft K3 KPA3 Power Connector Replacement Revision A Review, April 16, 2012 Copyright 2012, Elecraft, Inc. All Rights Reserved

DIGITAL WARMING CABINETS

Powers Controls TH 192 HC Heating/Cooling Room Thermostat

Co-location Interconnect Power Panel (CIPP) Installation Guide

SELF-REGULATING PIPE TRACING HEATER CABLE

SCTK INSTALLATION PROCEDURES. Splice Connection Termination Kit. SCTK-1D for BSX, RSX, VSX SCTK-2D for KSX, HTSX SCTK-3D for HPT, FP

Roof Top Air Conditioner INSTALLATION AND OPERATING INSTRUCTIONS

! WARNING. Before using product, read and understand instructions.

CUSTOM AUXILIARY FORWARD LIGHTING KIT

Replacement parts. WM97+ gas-fired water boiler Boiler Manual. OBTAIN PARTS ONLY THROUGH WEIL-McLAIN THE BOILER CONTAINS CERAMIC FIBER MATERIALS

SERVICE MANUAL 12VDC WALL THERMOSTAT AIR CONDITIONING SYSTEMS ROOFTOP UNITS ONLY

INSTALLATION INSTRUCTIONS

About this Manual. Support for Your Product

DLP-PU/E Instruction Manual

BILLET HEADLAMP SHELL

Equipped with AEM Dryflow Filter No Oil Required! INSTALLATION INSTRUCTIONS PART NUMBER DS BMW 335i 3.0L

Installation Manual. 24 VDC Rooftop Air Conditioner

VX 2400 Dimmer User's Manual

Freeze Protection Thermostats MODELS SST 2. Installation and Operation Manual

Powers Controls Free Energy Band TH 193 HC Heating/Cooling Room Thermostat

INSTALLATION GUIDE. Card Reader & Controller with KIM Swipe Reader for Solitaire 850 / 950 / 850L Learnlok PK2930

MIQ TM Mineral Insulated Heating Cable INSTALLATION PROCEDURES. (North America)

BLUE RIBBON CORP. BC001 Birdcage Installation Manual

GreenWay Solar LED Path and Trail Lighting System. Installation and Owner s Manual

DUAL SENSING DIGITAL THERMOSTAT PRODUCT INSTRUCTIONS. Construction Automotive Industry

Type FLX Freezer Floor Frost Heave Protection DESIGN GUIDE

Model 1756 Test Lead Kit

Transcription:

Installation Instructions DTS-HAZ DTS-HAZ-DC for Use with Self-Regulating & Constant Wattage Heating Cables PJ944-9 5625-81049 May 2013 1

2

DTS-HAZ Self-Regulating & Constant Wattage Heating Cables Junction Box RTD Compression Fitting O-Ring Protective Sleeve Locknut Silicone Termination Boot Pipe Sandoff RTV Self-Regulating & Constant Wattage Cable Grommets 9VDC Battery Connector Qty Description Qty Description 1 Junction Box 1 RTV 1 Line/Ambient Sensing RTD 1 O-Ring 1 Compression Fitting 1 Self-Regulating Cable Grommet 1 Locknut 1 1 Constant Wattage Cable Grommet 1 Silicone Termination Boot 1 9 VDC Battery Connector 1 Pipe Standoff 1 Protective Sleeve 3

General The DTS-HAZ is used for electrical termination of selfregulating and constant wattage cables. Each kit contains the terminations needed to make all electrical connections. The DTS-HAZ digital thermostat kit is a microprocessor based temperature control and power connection kit used for freeze protection or process temperature maintenance of pipes or tanks protected by heat tracing products. This thermostat can be used with Constant Wattage, Mineral Insulated or Self regulating heating cables in ordinary area or Div 2 hazardous area locations. Explanation of Symbols Used: Means WARNING. Means Earth (ground) terminal. A disconnect device and circuit breaker should be provided in the end installation. The installation and proximity for the disconnect device must satisfy the electrical Authority having jurisdiction for the installation. Branch circuit protection should be set for 40 amps or lower. HAZARD OF ELECTRIC SHOCK. Disconnect all power before starting. All installations must be effectively grounded in accordance with the National Electrical Code to eliminate shock hazard. In all cases where the symbol is used on the product, consult the documentation to find out the nature of the potential hazard and any actions to be taken. Turn off power before removing junction box cover at all times. Users should install adequate controls and safety devices with their electric heating equipment. Where the consequences of failure may be severe, back-up controls are essential. Although the safety of the installation is responsibility of the user, Chromalox will be glad to assist in making equipment recommendations. 4

Braid only cable instructions for SRL-C, SRF-C, SRM/E-C. CWM-C cable special instructions denoted by * Pipe Standoff 1. For each cable, push braiding back from the end of the cable. 11 inches from cable end create a bulge. At the bulge, separate the braid to make an opening. 2. While bending the heating cable, work the cable through the braid opening. Pull the braid tight 3. Insert cables and capillary tube though pipe standoff and grommet as shown. There should be 8 inches of cable past the grommets edge. Attach the pipe standoff to the pipe with a pipe strap (Chromalox type PS not included) as shown. Leave braid of the cable outside of pipe standoff and connect to ground (grounding clamp not included). Tape cable to pipe as shown. Small slice will need to be cut in grommet to allow the RTD wire to exit the pipe standoff out the bottom. For pipes smaller than 1-1/2 dia. a small pipe adapter (Chromalox model SPA not included) is required. Mounting Note: The Pipe Standoff is typically replaced by 1 NPT (straight) rigid conduit when the optional Wall Mounting Bracket is used. See Wall Mount Option. 4. Score the inner insulation 7 inches from the end. Lightly cut the inner jacket up the center to end of heating cable and remove the inner jacket from the cable. 5. Shave the core material from the outside of each bus wire. *Skip this step if using CWM-C constant wattage cable. 6. Starting at the end of the heating cable, using needle nose pliers or a knife pull each bus wire away from the core material. *Separate CWM-C leads and strip 1/4 from each leadwire. 5

Compression Fitting Grommet 7. Remove the exposed core material and cut 1/4 off the end of each bus wire. *Skip this step if using CWM-C constant wattage cable. 8. Liberally apply RTV over the exposed matrix and leads. Push the rubber boot over the heating cable. Trim lead ends as needed. *Boot is not needed when using CWM-C constant wattage cable. 9. Slide compression fitting over cable. Grommet should be placed inside pipe standoff. Termination boot should be spaced 1/2 from sealing grommet. Tighten compression fitting until it bottoms out against pipe standoff. 10. Assemble junction box to compression fitting as shown. Tighten locknut until the junction box bottoms out against the lip of the compression fitting. 11. Attach 3/4 conduit hub. Please see the electric diagrams below for proper wiring for your application. Attach junction box cover to seal enclosure. Note: The conduit hub shall be listed for Class 1, Div. 2; Class II Div. 1 & 2, Class III, Div. 1 & 2, and 4X rated by a nationally recognized testing laboratory. 6

Up to 277 VAC may be present at these terminals. Use 14 AWG copper wire or better. To Grounding Hub Alarm Contacts L or L1 N or L2 G + - White Red COM Red Up to 277 VAC may be present at these terminals. Use 10 AWG copper wire or better. Grounding braid shall be secured to UL listed grounding hub. 3 Wire RTD Be sure to install this device vertically as pictured. This controller utilizes a heat sink which is designed to cool the unit during operation. Under no circumstance should air flow around the controller be compromised in any way. Failure to do so may result in the overheating of the controller, product failure, product temperatures which exceed the Hazardous Area maximum temperature limit and even fire. The maximum allowable length of the RTD wire is 50ft. (15m) in order to remain UL/cUL compliant. Enclosure lid must be properly sealed prior to operating. Each of the four (4) screws are to be evenly tightened by hand with appropriate screw driver ONLY until snug. It is recommended that the lid be secured with a torque of 12-15 inch-lbs per screw. Overtightening or uneven tightening may cause the lid to break which would void all environmental and hazardous location approvals. Due to an electrical shock hazard, do not operate thermostat if lid is cracked, broken or uneven with enclosure. 7

Overjacketed cable instructions for SRL-CR, SRL-CT, SRF-CR, SRM/E-CT. CWM-CT cable instructions denoted by * Pipe Standoff 1. Insert heating cable and capillary tube through pipe standoff and grommet as shown. 8 inches of cable should extend past the grommet. Attach the pipe standoff to the pipe with a pipe strap (Chromalox type PS not included) as shown. Attach extra cable to pipe as appropriate. Small slice will need to be cut in grommet to allow the RTD wire to exit the pipe standoff out the bottom. For pipes smaller than 1-1/2 diameter optional small pipe adapter (Chromalox model SPA not included) is required. Mounting Note: The Pipe Standoff is typically replaced by 1 NPT (straight) rigid conduit when the optional Wall Mounting Bracket is used. See Wall Mount Option. 2. Score the outer insulation 7 inches from the end of the cable. Lightly cut the outer jacket up the center to the end of heating cable and remove the outer jacket from the cable. WARNING: DO NOT CUT METAL BRAID. 3. Move braid back toward the overjacket, creating a bulge. At the bulge, separate the braid to make an opening. 4. While bending the heating cable, work the cable through the braid opening. Pull the braid tight. 5. Score the inner insulation 6 inches from the end. Lightly cut the inner jacket up the center to end of heating cable and remove the inner jacket from the cable. 6. Shave the core material from the outside of each bus wire. *Skip this step if using CWM-C constant wattage cable. 8

7. Starting at the end of the heating cable, using needle nose pliers or a knife pull each bus wire away from the core material. *Separate CWM-C leads and strip 1/4 from each leadwire. 8. Remove the exposed core material and cut 1/4 of the end of each bus wire. *Skip this step if using CWM-C constant wattage cable. 9. Liberally apply RTV over the exposed matrix and leads. Push the rubber boot over the heating cable. Trim lead ends as needed. *Boot is not needed when using CWMC constant wattage cable. Compression Fitting Grommet 10. Slide compression fitting over cable. Grommet should be placed inside pipe standoff. Termination boot should be spaced 1/2 from sealing grommet. Tighten compression fitting until it bottoms out against pipe standoff. 11. Assemble junction box to compression fitting as shown. Tighten locknut until the junction box bottoms out against the lip of the compression fitting. 9

Up to 277 VAC may be present at these terminals. Use 14 AWG copper wire or better. Alarm Contacts L or L1 N or L2 G + - White Red COM Red Up to 277 VAC may be present at these terminals. Use 10 AWG copper wire or better. Grounding braid shall have the included protective sleeve slid over it once inside the enclosure. Then, insert grounding braid into grounding terminal. 3 Wire RTD 12. Attach 3/4 conduit hub. Please see the electric diagrams below for proper wiring for your application. Attach junction box cover to seal enclosure. For over-jacketed cable with internally grounded braid: Grounding braid shall have the included protective sleeve slid over it once inside the enclosure. Then, insert grounding braid into grounding terminal. Note: The conduit hub shall be listed for Class 1, Div. 2; Class II Div. 1 & 2, Class III, Div. 1 & 2, and 4X rated by a nationally recognized testing laboratory. The maximum allowable length of the RTD wire is 50ft. (15m) in order to remain UL/cUL compliant. Enclosure lid must be properly sealed prior to operating. Each of the four (4) screws are to be evenly tightened by hand with appropriate screw driver ONLY until snug. It is recommended that the lid be secured with a torque of 12-15 inch-lbs per screw. Overtightening or uneven tightening may cause the lid to break which would void all environmental and hazardous location approvals. Due to an electrical shock hazard, do not operate thermostat if lid is cracked, broken or uneven with enclosure. Be sure to install this device vertically as pictured. This controller utilizes a heat sink which is designed to cool the unit during operation. Under no circumstance should air flow around the controller be compromised in any way. Failure to do so may result in the overheating of the controller, product failure, product temperatures which exceed the Hazardous Area maximum temperature limit and even fire. 10

Optional Wall Mount Kit The DTS-HAZ may be mounted on vertical surfaces. To maintain UL/cUL and Class 1, Division 2 compliance, the user must use the optional Wall Mounting Bracket Kit (MP-2 DTS-HAZ Mounting Plate Kit, part number 5120-13015). Considerations: 1. The kit comes complete with two stainless steel mounting brackets and the necessary hardware to mount the brackets to the DTS-HAZ. 2. Should the owner use other means to mount the DTS to a vertical surface, a minimum of 3 inches or 76 mm must be maintained from the rear of the DTS-HAZ to the mounting surface. This is necessary to provide adequate airflow across the heat sink at the rear of the DTS. 3. When installing the DTS on a vertical surface, the Pipe Standoff is not used and is typically replaced by rigid 1 NPT conduit. The conduit shall terminate into the Compression Fitting. Ordering Information: Wall Mount Kit PCN (Part Number): 318043 3.000 [76.20mm] RECOMMENDED - WALL MOUNT LAYOUT MAXIMUM #10 STUD.657 [16.69mm] 7.750 [196.85mm].875 [22.23mm] Ø.218 [Ø5.54mm] 4.500 [114.30mm] Bracket Material: 16 ga Stainless Steel 0.059 " (1.5mm) nominal Ø.390 [Ø9.91mm].875 [22.23mm] 11

Start-Up For up to 30 amp loads, use minimum 10 AWG wiring or better for 120/277 VAC power input. Connecting power to the unit. 1. Powering up with 120/277 VAC: To power up the unit apply 120/277 VAC to the terminal block according to the schematic below: Connections for Power, Cable, Alarm and Sensor AC Power, Earth & Heating Cable Terminal Blocks Ground L or L1 IN (AC High) Cable OUT Cable OUT N or L2 IN (AC Low) Terminal Blocks For: Alarm RTD ~ AC Com RTD - RTD + I Alarm + Contact DC 2. Programming with 9VDC battery: The DTS-HAZ may be programmed with a 9VDC battery should standard service line voltage be unavailable. Note: Powering unit with 9VDC should only be used for programming purposes and not operation of the unit. 3. Programming and alarm overview Digital Thermostat must have the following components set to correctly control the temperature: a. Setpoint targeted temperature value that controller will aim to reach b. Hi Temperature Threshold max. temperature value. After reaching this threshold controller will set Alarm condition. c. Lo Temperature Threshold min. temperature value. After reaching this threshold controller will set Alarm condition. d. Deadband The allowable temperature differential between the Set Point and the Sensed Temperature during normal operation. The Deadband is centered on the Setpoint. The Deadband has a range of 2 to 10 deg. in 2 degree increments. The Load is removed once the temperature is 1/2 way between the Setpoint and the upper limit of the Deadband. e. Units selection between degrees Fahrenheit or Celsius. f. Soft Start Function The soft start may be enabled or disabled. When enabled, the Soft start algorithm initiates at power on & whenever low end of dead band is realized. When initiated, 0% - 100% Power is achieved over 167 seconds. g. Alarm The alarm on the DTS-HAZ functions only with AC voltage. The alarm on the DTS-HAZ-DC functions only with DC voltage. The FACTORY DEFAULT SETTING IS NORMALLY CLOSED. You may toggle this setting to Normally Open via the control push buttons. Connecting RTD Wire 1. Connect RTD wire according to the schematic: + - White Red 3 Wire RTD COM Red 12

Programming To To Program the the Digital Thermostat follow follow the the instructions below: below: Press Parameter Display Action MODE Set Point Press UP or Down to adjust the Set Point Temperature UP DOWN MODE High Temp Press UP or Down to adjust the High Temperature Alarm UP DOWN MODE Low Temp Press UP or Down to adjust the Low Temperature Alarm UP DOWN MODE Dead Band Press UP or Down to adjust the Dead Band From 2 to 100 UP DOWN MODE Temp. Units Press UP or Down to toggle between temp units: F or C UP DOWN MODE Soft Start Press UP or Down to enable or disable the Soft Start Function UP DOWN MODE Alarm State Press UP or Down to toggle Alarm State to be Normally Open or Normally Closed UP DOWN 13

Troubleshooting Alarm Type: Display Solution: Sensor Open Sens err Check if your sensor is correctly connected to the unit Sensor Shorted Sens err Check if your sensor is correctly connected to the unit Lo Temperature Hi Temperature Blinking between sensed temperature and LotP Blinking between sensed temperature and HitP Sensed temperature is below Lo Temp. Threshold. Alarm will be cleared automatically when sens temp > lo threshold + 5 deg Sensed temperature is above HI Temp. Threshold. Alarm will be cleared automatically when sens temp < hi threshold - 5 deg EPR EEprom memory error Press UP & DOWN keys for 2 seconds. Unit will be loaded with default settings ERR1 Program memory error Program memory corrupt. Solution: Reprogram the unit. Consult Factory. Product Maintenance & Care The following inspections should occur upon receipt of product and at least once every year. a. Wiring Inspect wiring for wear, fraying and evidence of overheating. Repair minor defects with a high quality grade of electrical tape or replace if needed. b. Hardware & Connectors Inspect for loose electrical and mechanical connections. Tighten or replace all loose or missing hardware. c. Cleaning This product does not require cleaning. However, the heat sink fins on back must routinely be inspected for any debris. Remove any debris with a stiff brush or other careful means. Take care not to break any fins. Should any of the fins break, the unit should be replaced. EXPLOSION HAZARD. Substitution of any component may impair suitability for Class 1, Div. 2. Equipment Ratings: Voltage Rating: 100-277 VAC, 50/60 Hz Current Rating: 30 amps Ambient Temperature Rating: -40 F to +104 F Alarm Rating: DTS-Haz: 12-277 Vac and 1.8 Amps RMS DTS-Haz-DC: 0-42 Vdc and 1.8 Amps RMS VA rating on electronics: 4.0 Watts The electronics are protected by a 0.5 Amp 350 VAC 2AG fuse Maximum RTD output 1.25 volts, 7 milliamps Settings: Setpoint: Alarms: -80 F to 1100 F (-62 C to 593 C) High temp to 1150 F (621 C) Low temp to -80 F (-62 C) Deadband: 2 F (or C) to 100 F (or C) +/- 1 to 50 around the setpoint Alarm Function: Mode Default Optional Normal Operation Closed Open Alarm Condition Open Closed Power Off Open Open Agency Approvals: UL/cUL - Ordinary area, File number E336917 UL/cUL - Hazardous area (C1D2, Groups A, B, C & D) File number E347725 CE Field Wiring Considerations: Torque values for field wiring terminals...11-15 in-lbs (1.2-1.7 n-m) Wire gauge range...6-18 ga Stripped insertion length... 1/2 (12mm) Replacement Parts Fuse Specifications... 0.5A, 350V, 2 AG Dimensions... 14.18 mm (L) x 4.5 mm (W) Material... Glass Vendor & Model...Littlefuse, Model 209.500 Replacing Fuse: Hazard of electric shock. Turn off power before removing junction box cover. 1. Remove Cover. 2. Carefully remove display board from 4 nylon posts. 3. Fuse is in upper left corner of bottom board. 4. Carefully remove the bad fuse and replace with new fuse. 14

15

Limited Warranty: Please refer to the Chromalox limited warranty applicable to this product at http://www.chromalox.com/customer-service/policies/termsofsale.aspx. 2013 Chromalox, Inc. 1347 HEIL QUAKER BLVD., 16 LAVERGNE, TN 37086 Phone: (615) 793-3900 www.chromalox.com