SION Vacuum Circuit-Breakers 3AE5 and 3AE1

Similar documents
3AH5 Vacuum Circuit-Breakers. Answers for energy. Medium-Voltage Equipment Selection and Ordering Data. Catalog HG

High Voltage Circuit Breakers 3AP Type 72.5 kv to 800 kv Answers for energy.

UniGear ZS1. Medium voltage, arc proof, air insulated switchgear for primary distribution

NATUS NES / NES-H Draw-out Type Medium Voltage Switchgear Systems. Safe energy distribution that meets the highest industrial requirements

High-Voltage Circuit-Breakers 3AP1/ kv up to 550 kv. Power Transmission and Distribution

METAL-CLAD AND METAL-ENCLOSED SWITCHGEAR 3.6KV~40.5KV. tgood.com. Energy. Fast.

2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV a. Section INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std.

High-Voltage Compact Switchgear 3AP1 DTC for 145 kv and 245 kv

SENTRON Switching and Protection Devices Air Circuit Breakers

The Intelligent AX1 Switchgear for Medium Voltage

MEDIUM VOLTAGE CE-BF SWITCHBOARDS. UP TO 40.5 kv. CE - BF - C - en - REV

Unified requirements for systems with voltages above 1 kv up to 15 kv

3TL Vacuum Contactors Selection and Ordering Data. Medium-Voltage Equipment Catalog HG

3.1.1 Full Type Tests & Routine Tests according to Clause 8 2 & Instructions For Installation, Operation & Maintenance

Our brand POWER DYNAMIC PASSION COMMITMENT CREATIVITY. A strong brand for strong products: 8PU Premium. MV Energy

The following components are common to most cubicles; this example is an ABB HK cubicle.

Siemens AG Power Transmission and Distribution Medium Voltage Division Mozartstr. 31c Erlangen Germany.

Dead Tank Circuit Breaker 72PM40-C Proven reliability through common platforms

Medium voltage indoor circuit breakers ANSI/IEC solutions

Electronic overload relay EF65, EF96 and EF146

UFES Active protection for switchgear

Electronic overload relay EF19 and EF45

e 2 ALPHA Medium Voltage Switchgear Data Sheet K EN

Voltage Rated operating voltage [kv] Rated power frequency withstand voltage [kv] Rated lightning impulse withstand voltage [kv]

7.2KV SL400 Withdrawable Vacuum Contactor-Fuse Combination Units

Type: DILM115(RAC240) Article No.: Sales text Contactor,55kW/400V,AC operated. Ordering information

Permissible ambient temperature Operation Storage, transport

Circuit Breakers. NRC Series. NRC Series

TRACTION NETWORK MONITORING AND PROTECTION SYSTEM SMTN-3 CITY ELECTRIC TRANSPORT RAILWAYS METRO INDUSTRY

Product and functional description

Medium Voltage Products. ZN1 12 kv arc-proof air-insulated switchgear for primary distribution

CAT ATC POWER BREAKER & POWER CASE SWITCH AUTOMATIC TRANSFER SWITCH

Electrical Shore Connections / Cold Ironing

SF 6 Gas Insulated Switchgear Type SDF for 170 kv

Medium Voltage Distribution FLUVAC. Vacuum Circuit Breaker Up to 24 kv 630 A 21 ka. Operation Maintenance Instructions.

Specification Guide. for RVAC. Direct Replacement. AC Medium Voltage. Circuit Breakers

R.C.C.B. s two-pole LEXIC

Bulletin 150 Smart Motor Controllers SMC-3 Smart Motor Controller

Masterclad Medium Voltage Passive Arc-Resistant Switchgear

Masterpact NW Circuit breakers and switch-disconnectors from 800 to 6300 A

MEDIUM VOLTAGE SWITCHGEAR CATALOGUE. Code: P2490_xx

Catalog. Arc Guard System TM TVOC-2

Low voltage Direct Current Network. Compact NSX DC PV. Circuit breakers and switch disconnectors for solar application.

ELEKTROTEHNI KO PODJETJE Leskoπkova cesta 12, 1000 Ljubljana, SLOVENIA

SURGE PROTECTIVE DEVICES

Low Voltage Products. Switches Automatic Transfer Switches

Electric Rotary Actuator - On/Off or programmable control actuator

Manual Motor Starter MS 116 up to 16 A Technical Data

Siemens Integrated Substation Condition Monitoring System. Circuit Breaker Monitoring

DATA CENTER UNIQUE CHARACTERISTICS AND THE ROLE OF MEDIUM VOLTAGE VACUUM CIRCUIT BREAKERS

Tmax MCCBs. Molded case circuit breakers. Tmax

SUBJECT: How to wire a motor starter Number: AN-MC-004 Date Issued: 2/08/2005 Revision: Original

Charge Controller CC611/CC612 Preliminary datasheet

MEDIUM AND HIGH VOLTAGE CAPACITORS, CAPACITOR BANKS AND SYSTEMS

Submit shop drawings for equipment provided under this section Shop drawings shall indicate:

Diesel Engine Driven Generators Page 1 of 6

Medium voltage VCP-W MR2 (integral racking)

Positive-guided relay outputs: 3 safety contacts (N/O), instantaneous. 1 auxiliary contact (N/C), instantaneous

PRODUCT GUIDE. SL Medium Voltage IEC Vacuum Contactors

T-05-S2. Rotary drive without spring return. Technical data sheet. Description. Technical data. Actuators

Safety technique. Emergency stop module BO 5988 safemaster

E-STOP relays, safety gate monitors

RM17TE V AC. Main. Product or component type. Product specific application. Relay monitored parameters 250 V DC 5 A DC

RM4TG20 three-phase network control relay RM4-T - range V

IZM ACB/Circuit-breakers. Robust safety. Extract from Main Catalogue HPL2010 IZM26 Circuit-breakers IN26 Switch-disconnectors

Circuit Breaker LTB D with Motor Drive. Motor Drive. ABB PP/H/HV - Page 1. Ed

01.4IB.51200B PowlVac-AR Arc Resistant Switchgear. 5kV & 15kV 1200A, 2000A, 3000A, & 4000A Forced Cooled. Powered by Safety

Data Sheet. Electro-mechanical counters Hengstler 800 series

OUTDOOR DISCONNECTORS A division of ACTOM (Pty) Ltd

Current and voltage measuring relays

VD4. Vacuum circuit-breaker

5SV Residual Current Protective Devices

Single-phase ( V) voltage monitoring: Undervoltage Overvoltage Window mode (overvoltage + undervoltage) Voltage fault memory selectable

Arc Terminator Active Arc-Resistant Switchgear

Product and Applications Description. Application Programs. Example of Operation. GAMMA instabus Technical Product-Information.

49 Series - Relay interface modules A. Features

Advantages of Fixed Circuit Breaker Switchgear

Emergency stop As an emergency switching off/emergency stop device. Standards According to IEC/EN , VDE 0113 Part 1

Type-Tested Power Distribution Board 8PT with Rear Busbars. sivacon

Electronic timer CT-AHD.12 OFF-delayed with 1 c/o (SPDT) contact

Vacuum Circuit Breaker Type VAD-3

Disconnectors and Earthing Switches 36 kv up to 800 kv

Medium Voltage Switchgear

MasterINTERFACE 39 Series - Relay interface modules

..OR How To Protect your 3-Phase Equipment Investment with 3-Phase Monitors from Time Mark...

ALTERNATIVE METHODS FOR INTERNAL ARC TESTS ON 12 KV AND 24 KV METAL-ENCLOSED SWITCHGEARS WITH COMPACT RMU

Secondary Unit Substations

Low Voltage Switchboards The Best Technical Solution for Your Ship

OVERCURRENT & EARTH FAULT RELAYS. To study the protection of equipment and system by relays in conjunction with switchgear.

Mini Motor Contactor J7KNA Main contactor Accessories Approved Standards Standard Guide No (US,C) Ordering Information tage Model Number Legend gear

Eaton Safety & Reliability Solutions in the Oil & Gas Industry Electrical

BETA Switching. Switching Devices. 5TT5 8 Insta contactors, AC technology. Overview

TWENTIES WORKSHOP, EWEA 2012 Unveiling the future energy system: full scale demonstrations to reach 2020 targets. 17th April 2012

Medium voltage products UniSec for Smart Grid Air-insulated medium-voltage secondary distribution switchgear

Bussmann. All-In-One Module. Bussmann Power Module Switch. How to configure Part Numbers: Step 1: Select Switch Amperage 1

Breaking and protection devices

Engineering Specification

Bulletin 150 SMC Flex Smart Motor Controller Specifications

New SACE Emax 2 for UL 1066 From Circuit Breaker to Power Manager

Siemens Fusesaver. Highest availability and cost savings for your MV distribution network.

Transcription:

www.siemens.com/sion SION Vacuum Circuit-Breakers AE5 and AE1 Medium-Voltage Equipment Catalog HG 11.0 01 Answers for infrastructure and cities.

SION Vacuum Circuit-Breakers AE5 and AE1 R-HG11-17.tif Siemens HG 11.0 01

SION Vacuum Circuit-Breakers AE5 and AE1 Contents SION Vacuum Circuit-Breakers AE5 and AE1 Medium-Voltage Equipment Catalog HG 11.0 01 Invalid: Catalog HG 11.0 011 Contents Description 5 General 6 Construction and mode of operation 8 Standards, maintenance-free design and interlocking 11 Ambient conditions, current carrying capacity and dielectric strength 1 Basic equipment, product range overview 1 Equipment Selection 15 Order number structure 16 Configuration example 17 Circuit-breaker and equipment package 18 Secondary equipment 1 Additional equipment 7 Accessories and spare parts 8 Technical Data 4 Electrical data, dimensions and weights 44 Dimension drawings 64 Operating times and internal times, short-circuit protection of motors 7 Consumption data of releases 7 Circuit diagrams 74 Annex 81 Inquiry form 8 Configuration instructions 8 Configuration aid Page Foldout page 1 4 The products and systems described in this catalog are manufactured and sold according to a certified management system (acc. to ISO 9001, ISO 14001 and BS OHSAS 18001). Siemens HG 11.0 01

SION Vacuum Circuit-Breakers AE5 and AE1 R-HG11-57.tif 4 Siemens HG 11.0 01

SION Vacuum Circuit-Breakers AE5 and AE1 Description Contents Contents Page Description 5 General 6 1 Industrial application: Refinery R-HG11-174.tif Construction and mode of operation Switching medium 8 Pole assemblies 8 Operating mechanism 8 Trip-free mechanism 8 Releases 9 Closing and anti-pumping 9 Closing spring charged indication 9 Circuit-breaker tripping signal 9 Interlocking 9 Low-voltage interface 9 Withdrawable module 10 Withdrawable module with make-proof earthing switch 10 Circuit-breaker on truck for retrofitting 8B switchgear 10 Standards 11 Maintenance-free design 11 Interlocking 11 Ambient and operating conditions Ambient conditions 1 Current carrying capacity 1 Dielectric strength 1 Basic equipment 1 Product range overview 1 Siemens HG 11.0 01 5

Description General SION Vacuum Circuit-Breakers AE5 and AE1 SION Vakuum Circuit-Breakers AE5 and AE1 from 7. kv to 4 kv The Modulars 1 SION vacuum circuit-breakers control all switching duties in medium-voltage distribution systems and are suitable for installation in all customary, new, air-insulated medium-voltage switchgear types as well as for retrofitting existing switchgear. They are applicable for operation of e.g. overhead lines, cables, transformers, capacitors and motors. The comprehensive installation accessories enable easy integration in the panel, and form maximally equipped as a withdrawable module with earthing switch almost the complete circuit-breaker compartment inside the switchgear. Our comprehensive circuit-breaker product range offers a wide selection for pole-center distances and widths across flats as well as various equipment options for voltage levels from 7. kv to 4 kv. The withdrawable part, contact arms, contacts and bushings enable easy integration in all customary mediumvoltage switchgear types. Identical dimensions and connection dimensions across several voltage levels reduce planning costs and the diversity of panel versions. High reliability and availability are just as much a matter of course as 10,000 maintenance-free operating cycles. SION vacuum circuit-breaker for fixed mounting SION vacuum circuit-breaker on withdrawable part The SION vacuum circuit-breaker can be adjusted to your requirements by means of various equipment options. This switching device can be mounted on a withdrawable part. Furthermore, mountable contact arms, contacts and bushings allow easy integration in your switchgear. R-HG11-7.tif The circuit-breaker mounted on a withdrawable part can be supplied both with and without contact arms and contacts. R-HG11-81.eps 6 Siemens HG 11.0 01

SION Vacuum Circuit-Breakers AE5 and AE1 Description General SION vacuum circuit-breaker on withdrawable part with contacts Withdrawable module with AE5 vacuum circuit-breaker 1 The SION vacuum circuit-breakers can be supplied with contact arms and contacts. Withdrawable module with earthing switch The withdrawable module contains all components required for the circuit-breaker compartment of a switchgear panel. It consists of the circuit-breaker mounted on a withdrawable part, with contact arms, fitted in a cartridge with side and rear walls. The withdrawable module is equipped with bushings, fixed contacts, shutters and the shutter mechanism. The side and rear walls form the tested connection compartment. Circuit-breaker on truck for retrofitting 8B swichgear (only for SION AE1 vacuum circuit-breaker) R-HG11-6.tif R-HG11-6.eps R-HG11-75.tif R-HG11-76.eps The withdrawable module is also available with earthing switch. It contains all components required for the circuitbreaker compartment of a switchgear panel. It consists of the circuit-breaker mounted on a withdrawable part, with contact arms, fitted in a cartridge with side and rear walls. The withdrawable module is equipped with bushings, fixed contacts, shutters and the shutter mechanism, as well as with a make-proof earthing switch. The side and rear walls form the tested connection compartment. Our retrofit solutions allow for considerable cost savings. With the consequent design of a simple plug & play principle, replacing the circuit-breaker requires extremely short operational interruptions. The retrofit solution for 8B switchgear is available up to 17.5 kv, 500 A and 1.5 ka; for 4 kv, up to 000 A and 5 ka. Other retrofit solutions are available on request. Siemens HG 11.0 01 7

Description Construction and mode of operation SION Vacuum Circuit-Breakers AE5 and AE1 Switching medium The vacuum switching technology, proven and fully developed for more than 0 years, serves as arc-quenching principle by using vacuum interrupters. AE1 AE5 1 Pole assemblies The pole assemblies consist of the vacuum interrupters and the pole shells. The vacuum interrupters are air-insulated and freely accessible. The pole assemblies are fixed on the mounting plate of the operating mechanism and supported by means of the pole shell (6). The vacuum interrupter (5) is mounted rigidly to the upper interrupter support. The lower part of the interrupter is guided in the lower interrupter support, allowing axial movement. The pole shell (6) absorbs the external forces resulting from switching operations and the contact pressure. HG11-501 eps Front view 1 Cover of low-voltage interface 1 HG11-88 eps Central control board 1 Operating mechanism The whole operating mechanism with motor (1), releases (11), indicators and actuating devices is mounted on the mechanism mounting plate (9). This compact design enables very fast operating times. The circuit-breaker operating mechanism is a stored-energy spring mechanism. The force is transmitted from the operating mechanism to the pole assemblies via operating levers. The closing spring (15) can be charged either electrically or manually, and latches automatically in when charging is complete. The closing spring (15) acts as a stored-energy mechanism. HG11-500a eps 4 5 6 7 8 Pole structure Separating shell to the operating mechanism 4 Upper connection 5 Vacuum interrupter 6 Pole shell 7 Lower connection 8 Insulator To close the breaker, the closing spring (15) can be unlatched either mechanically at the device (ON pushbutton), or electrically by remote control. The closing spring (15) charges the opening or contact-pressure springs (17) as the breaker closes. The now discharged closing spring (15) will be charged again automatically by the motor (1). In this way, the stored-energy mechanism stores the OPEN CLOSE OPEN operating sequence that is required for an auto-reclosing operation on the system side. All stored-energy mechanisms transmit the switching duties of synchronising, rapid load transfer, and auto-reclosing. Trip-free mechanism 10 11 HG11-50b eps 9 Operating mechanism AE1 without cover 9 Mechanism mounting plate 10 Auxiliary switch 11 1 st release 1 Terminal strip 1 Motor 14 Closing solenoid 15 Closing spring 16 Gear 17 Opening spring SION vacuum circuit-breakers have a trip-free mechanism. In the event of an opening coand being given after a closing operation has been initiated, the moving contacts return to the open position and remain there even if the closing coand is sustained. This means that the contacts of the vacuum circuit-breakers are momentarily in the closed position, which is permissible. For charging the closing spring (15), the motor (1) operates in short-time duty. Therefore the voltage and power consumption might differ from the data of the motor rating plate. 10 11 HG11-89a eps 9 1 1 14 15 16 17 Operating mechanism AE5 without cover 9 Mechanism mounting plate 10 Auxiliary switch 11 1 st release 1 Terminal strip 1 Motor 14 Closing solenoid 15 Closing spring 16 Gear 17 Opening spring 8 Siemens HG 11.0 01

SION Vacuum Circuit-Breakers AE5 and AE1 Description Construction and mode of operation Releases A release is a device which transfers electrical coands from an external source, such as a control room, to the latching mechanism of the vacuum circuit-breaker so that it can be opened or closed. The releases are designed for shorttime duty up to 1 minute and are reset internally. The various types of releases available are described in detail below: Closing solenoid The closing solenoid unlatches the charged closing spring of the vacuum circuit-breaker, closing it by electrical means. Shunt releases Shunt releases are used for automatic tripping of the circuitbreaker by suitable protection relays and for deliberate tripping by electrical means. They are intended for connection to an external power supply (DC or AC voltage). Current-transformer operated releases Current-transformer operated releases comprise a storedenergy mechanism, an unlatching mechanism, and an electromagnetic system. They are used when there is no external source of auxiliary power (e.g. a battery). Tripping is effected by means of a protection relay (e.g. overcurrent-time protection) acting on the current-transformer operated release. Undervoltage releases Undervoltage releases comprise a stored-energy mechanism, an unlatching mechanism and an electromagnetic system which is permanently connected to the secondary or auxiliary voltage while the circuit-breaker is closed. If the voltage falls below a predetermined value, unlatching of the release is enabled and the circuit-breaker is opened via the storedenergy mechanism. The maximum possible equipment are two releases according to page. The consumption data of the releases is listed on pages 70/71. Closing and anti-pumping In the standard version, the circuit-breakers can be remoteclosed electrically. In addition, they can be mechanically closed locally by direct unlatching of the closing spring. If constant electrical signals for CLOSE and OPEN coands are present at the circuit-breaker at the same time, the circuitbreaker will carry out an OPEN-CLOSE-OPEN or a CLOSE-OPEN operating sequence. A new CLOSE coand is given only following a short-time interruption of the closing signal. In this manner, continuous closing and opening (= pumping ) is prevented. Closing spring charged indication The circuit-breaker has a mechanically operated spring charged indication. The charging status of the closing spring can also be interrogated electrically by means of an integrated position switch. Circuit-breaker tripping signal During electrical opening, the NO contact S6 makes brief contact. This is often used to operate a hazard warning system which should respond to automatic tripping of the circuit-breaker. In case of local control, the NO contact S6 does not close. For the corresponding circuit diagrams, refer to page 58. Interlocking Mechanical interlocking At the interface of the mechanical interlocking of the circuitbreaker, sensors on the switchgear side can check the switch position and prevent the associated disconnector from being operated while the circuit-breaker is closed. The system also prevents the circuit-breaker from being closed while the associated disconnector is in a faulty position. Circuit-breakers mounted on withdrawable parts are mechanically interlocked, with the result that the handle for racking the withdrawable part can only be inserted in the OPEN position. The lock of the withdrawable part can only be released in the disconnected position by operating the pushing handles. If the circuit-breaker on the withdrawable part is in an intermediate position (neither in the service nor in the disconnected position), operation is not possible due to the mechanical interlocking. Electrical interlocking The auxiliary and signalling contacts which show the switch position of the circuit-breaker or the position of the withdrawable part can be integrated in the switchgear interlocking concept in order to exclude impermissible switching sequences. Low-voltage interface The removable cover of the SION AE1 and AE5 vacuum circuit-breakers enables easy access to the low-voltage interface. All possible customer-side control and signalling connections are concentrated here. 1 Siemens HG 11.0 01 9

Description Construction and mode of operation SION Vacuum Circuit-Breakers AE5 and AE1 Withdrawable module 1 The withdrawable module contains all necessary components for the circuit-breaker compartment of a switchgear panel. It consists of the circuit-breaker mounted on a withdrawable part, with contact arms, fitted in a cartridge with side and rear walls. The withdrawable module is equipped with bushings, fixed contacts, shutters and shutter mechanism. The side and rear walls form the tested connection compartment. Withdrawable module AE1 1 4 5 1 Fixed contact Bushing Shutter 4 Contact 5 Contact arm The vacuum circuit-breaker on the withdrawable part is racked into the cartridge with the associated handle by the rotary movement of the spindle. The shutter mechanism is controlled by lateral gates, and the shutters are opened for contacting. Signals for the service and disconnected positions are transmitted to the module connector at the low-voltage interface of the vacuum circuit-breaker via the position switches of the withdrawable part. HG11-815 eps Withdrawable module with make-proof earthing switch The make-proof earthing switch at the cartridge has a defined making capacity up to the values stated on the circuitbreaker rating plate. It features a compact design with spring-operated mechanism and a switching angle of 90, low torques for closing and opening, as well as low maintenance. Withdrawable module AE5 6 7 8 9 6 Cartridge 7 Low-voltage interface 8 Circuit-breaker 9 Withdrawable part The make-proof earthing switch has been tested in the withdrawable module and fulfills the relevant standards for the withdrawable module. HG11-840 eps Circuit-breaker on truck for retrofitting 8B swichgear (only for SION AE1 vacuum circuit-breaker) With our retrofit solution it is possible to replace only the components that have been stressed the most in long years of reliable operation, instead of the complete switchgear panel. As a rule, these are the circuit-breaker truck and the circuit-breaker itself. To do this, the new truck with the circuit-breaker including contact arms with contacts, secondary equipment, interlocking, wiring and low-voltage plug connector is adjusted at Siemens in such a way that replacement in the switchgear can take place based on a plug & play principle. Retrofit Solutions for other ratings or other switchgear types such as Reyrolle LMT are available on request. The switchgear documentation, e.g. circuit diagrams, must be provided by the customer. Special equipment like instrument transformers must be ordered separately. Dimension drawings for 8B retrofit are available on request. R-HG11-64.eps 10 Siemens HG 11.0 01

SION Vacuum Circuit-Breakers AE5 and AE1 Description Standards, maintenance-free design and interlocking Standards The circuit-breakers conform to the following standards: IEC 671-1 IEC 671-100 All circuit-breakers fulfil the endurance classes C, E and M according to IEC 671-100. The withdrawable modules have been tested according to IEC 671-00, 671-1 and 671-10 regarding Dielectric strength Temperature rise Switching capacity. Maintenance-free design The circuit-breakers are maintenance-free: Under normal ambient conditions according to IEC 671-1 Up to 10,000 operating cycles, no regreasing no readjusting The ratings are independent within their tolerances of the switching rate or standing times without switching. 1 Interlocking Vacuum circuit-breaker Disconnected position Racking Service position Switching state of vacuum circuit-breaker Interlocking of vacuum circuitbreaker against closing (optionally with key-operated interlock) Fixed-mounted OPEN Interlockable CLOSED Interlocking of withdrawable part in the switchgear panel (latching of locking handles) in disconnected position Interlocking of racking the withdrawable part (between disconnected, test and service position) Switching state of earthing switch Interlocking of earthing switch against closing Disconnecting on withdrawable part and in withdrawable module Disconnecting on withdrawable part, in withdrawable module and with earthing switch CLOSED Active OPEN OPEN Active Active CLOSED Active Active CLOSED Active OPEN OPEN OPEN OPEN Active Active OPEN Active CLOSED Active Active OPEN Active Earthing on withdrawable part, in withdrawable module and with earthing switch CLOSED or OPEN CLOSED or OPEN Active OPEN OPEN Siemens HG 11.0 01 11

Description Ambient conditions, current carrying capacity and dielectric strength SION Vacuum Circuit-Breakers AE5 and AE1 Ambient conditions 1 The circuit-breakers are designed for the normal operating conditions defined in IEC 671-100. Condensation can occasionally occur under the ambient conditions shown opposite. The circuit-breakers are suitable for use in the following climatic classes according to IEC 6071, Part -: Climatic ambient conditions: Class K4 1) Biological ambient conditions: Class B1 Mechanical ambient conditions: Class M Chemically-active substances: Class C Mechanically-active substances: Class S ) 1) Low temperature limit: 5 C (with order code A40 up to 5 C) ) Restriction: Clean insulation parts Current carrying capacity Rated normal current Altitude correction factor 400 A 000 600 00 1800 1400 1000 600 10 1.50 1.40 1.0 1.0 1.10 1.00 1000 0 1500 4 1 0 40 50 60 C 70 Ambient air temperature 5 HG11-516a_en eps HG11-517c_en eps 000 500 000 500 m 4000 Site altitude The rated normal currents specified in the diagram have been defined according to IEC 671-100 for an ambient air temperature of +40 C and apply to open switchgear. For enclosed switchgear the data of the switchgear manufacturer applies. At ambient air temperatures below +40 C, higher normal currents can be carried (see diagram): Characteristics curve 1 = Rated normal current 800 A Characteristics curve = Rated normal current 150 A Characteristics curve = Rated normal current 000 A Characteristics curve 4 = Rated normal current 500 A Characteristics curve 5 = Rated normal current 150 A Dielectric strength The dielectric strength of air insulation decreases with increasing altitude due to low air density. According to IEC 671-1, the values of the rated lightning impulse withstand voltage and the rated short-duration power-frequency specified in the chapter Technical Data apply to a site altitude of 1000 m above sea level. For an altitude above 1000 m, the insulation level must be corrected according to the opposite diagram. The characteristic shown applies to both rated withstand voltages. To select the devices, the following applies: U U 0 x K a U Rated under reference atmosphere U 0 Rated requested for the place of installation K a Altitude correction factor according to the opposite diagram Example For a requested rated lightning impulse of 75 kv at an altitude of 500 m, an insulation level of 90 kv under reference atmosphere is required as a minimum: 90 kv 75 kv x 1. 1 Siemens HG 11.0 01

SION Vacuum Circuit-Breakers AE5 and AE1 Description Basic equipment, product range overview Basic equipment Equipment Minimum equipment Alternative equipment Remarks Operating mechanism Electrical operating mechanism None Also for manual operation Closing Closing solenoid and None mechanical manual closing 1 st release Shunt release Undervoltage release, c.t.-operated release For SION AE5, only shunt releases are possible nd release Without Shunt release, undervoltage release, c.t.-operated release Varistor circuit Standard for SION AE1 Installed with 60 V DC f. SION AE5 None Combination of undervoltage releases or c.t.- operated releases is not possible. For SION AE5, the combination of undervoltage and c.t.-operated releases is not possible either For limiting switching overvoltages Auxiliary switch 6 NO + 6 NC 1 NO + 1 NC Plug connection 7-pole terminal strip f. SION AE1 0-pole plug connector f. SION AE5 4-pole plug, 64-pole plug 1 NO + 1 NC not available with 4-pole plug Anti-pumping Available None Circuit-breaker tripping Without Possible signal Operations counter Available None Position switches for withdrawable part 5 momentary-contact position switches per position None Mechanical interlocking Available for withdrawable module Mechanical interlocking for circuit-breaker Required for withdrawable module Installation accessories Fixed-mounted With withdrawable part, contact arms and contact, fixed contacts and bushings, complete withdrawable module with and without make-proof earthing switch 1 Product range overview: Circuit-breaker without installation accessories Rated voltage Rated shortcircuit breaking current Rated normal current Pole-center distance (in ) 150 160 10 75 Width across flats (in ) Type kv ka A 05 75 10 05 75 10 05 75 10 10 AE10 /AE50 7. 16 800/150 0 800/150 5 800/150 AE10 7. 5 000 1.5 800/150 1.5 000/500 40 150/000 40 500/150 AE11/AE51 1 16 800/150 0 800/150 5 800/150 AE11 1 5 000 1.5 800/150 1.5 000/500 40 150/000 40 500/150 AE1 17.5 1.5 800/150 16 800/150 5 800/150 5 000/500 1.5 800/150 1.5 000/500 40 150/000 40 500/150 AE1 4 1.5 800/150 16 800/150/000 0 800/150 0 000/500 5 800/150 5 000/500 Note: The circuit-breaker is available with various installation accessories: These versions can be configured from page 18. Siemens HG 11.0 01 1

SION Vacuum Circuit-Breakers AE5 and AE1 R-HG11-77.tif 14 Siemens HG 11.0 01

SION Vacuum Circuit-Breakers AE5 and AE1 Equipment Selection Contents Contents Page Equipment Selection 15 Order number structure 16 Configuration example 17 Circuit-breaker and equipment package Voltage level 7. kv 18 Voltage level 1 kv Voltage level 17.5 kv 7 AE5 vacuum circuit-breaker as fixed-mounted version R-HG11-78.tif Voltage level 4 kv 0 Secondary equipment Release combination 1 Operating voltage of the closing solenoid 1 Operating voltage of the 1 st release Operating voltage of the nd release Circuit-breaker installation accessories Operating voltage of the motor operating mechanism 4 Interlocking, auxiliary switch, circuit-breaker tripping signal and secondary connection 5 Languages of operating instructions and rating plate; AC frequency of operating voltages 6 Additional equipment 7 Accessories and spare parts Rating plate 8 Accessories catalog 8 R-HG11-176.eps AE1 vacuum circuit-breaker as fixed-mounted version Siemens HG 11.0 01 15

Equipment Selection Order number structure SION Vacuum Circuit-Breakers AE5 and AE1 Order number structure The circuit-breakers consist of a primary and a secondary part. The relevant data make up the 16-digit order number. The primary part covers the main electrical data of the circuit-breaker poles. The secondary part covers the auxiliary devices which are necessary for operating and controlling the vacuum circuit-breaker. Order codes Individual equipment versions, marked with 9 or Z in the 9 th to 16 th position, are explained more in detail by a -digit order code. Several order codes can be added to the order number in succession and in any sequence. Special versions («) In case of special versions, -Z is added to the order number and a descriptive order code follows. If several special versions are required, the suffix -Z is listed only once. If a requested special version is not in the catalog and can therefore not be ordered via order code, it has to be identified with Y 9 9 after consultation. The agreement hereto is made directly between your responsible sales partner and the order processing department at Siemens. a: alphabetical n: numerical Position: 1 4 5 6 7 8 9 10 11 1 1 14 15 16 Order codes Order No.: A E n n n n n a a n n n a a n «Primary part 1 st position Superior group Switching devices nd position Main group Circuit-breaker rd position Subgroup Circuit-breaker type series 4 th position Circuit-breaker version 5 th position Rated voltage from 7. kv to 4 kv 6 th position Pole-center distance / Width across flats 7 th position Rated short-circuit breaking current from16 ka to 40 ka 8 th position Rated normal current from 800 A to 150 A Secondary part 9 th to 16 th position Secondary equipment, operating mechanism, releases, operating voltages and further auxiliary equipment Order codes Groups of after the Order No. Format: a n a Special versions ( ) Initiated with -Z Groups of after the Order No. Format: a n n 16 Siemens HG 11.0 01

SION Vacuum Circuit-Breakers AE5 and AE1 Equipment Selection Configuration example Configuration example In order to simplify the selection of the correct order number for the requested circuit-breaker type, you will find two configuration examples below. Two complete circuit-breakers have been configured as an example. On the foldout page you can enter the Order No. determined for your circuit-breaker. Based on the Order No. you can request an offer from your Siemens partner. Configuration example 1: SION AE5 vacuum withdrawable module (vacuum circuit-breaker on withdrawable part in cartridge) Configuration example SION vacuum circuit-breaker A E 5 Rated voltage U r = 1 kv, 50 / 60 Hz Rated lightning impulse U p = 75 kv Rated short-circuit breaking current I SC = 5 ka Rated normal current I r = 150 A Pole-center distance = 150 Width across flats = 10 1 4 1 st shunt release (only one shunt release) A Operating voltage of the closing solenoid 48 V DC Position: 1 4 5 6 7 8 9 10 11 1 1 14 15 16 Order codes Order No.: A E 5 «Operating voltage of the 1 st release V DC 9 L 1 B Without nd release 0 Circuit-breaker on withdrawable part, with cartridge, contact arm, contact, fixed contacts, bushing, shutters, make-proof earthing switch 6 Operating voltage of the motor operating mechanism 0 V AC With mechanical interlocking, circuit-breaker tripping signal, auxiliary switch 1 NO + 1 NC and 64-pole plug Frequency of the operating voltage 50 Hz and DC, operating instructions and rating plate in english Hand crank C K N Z F 0 Example for Order No.: A E 5 1 4 A C 9 0 6 K N Z Order codes: L 1 B + F 0 Configuration example : SION vacuum circuit-breaker for 8B retrofit Position: 1 4 5 6 7 8 9 10 11 1 1 14 15 16 Order codes Order No.: A E 1 «Configuration example SION vacuum circuit-breaker A E 1 Rated voltage U r = 17.5 kv, 50 / 60 Hz Rated lightning impulse U p = 95 kv Rated short-circuit breaking current I SC = 5 ka Rated normal current I r = 150 A Pole-center distance = 10 Width across flats = 10 8 4 1 st shunt release (only one shunt release) A Operating voltage of the closing solenoid 48 V DC C Operating voltage of the 1 st release V DC 9 L 1 B Without nd release 0 8B retrofit: Circuit-breaker up to 17.5 kv, 5 ka, 150 A, contact arm type C 7 Z R 1 Operating voltage of the motor operating mechanism 0 V AC K With mechanical interlocking, circuit-breaker tripping signal, auxiliary switch 1 NO + 1 NC and 64-pole plug N Frequency of the operating voltage 50 Hz and DC, operating instructions and rating plate in english Hand crank Z F 0 Example for Order No.: A E 1 8 4 A C 9 0 7 K N Z Order codes: L 1 B + R 1 + F 0 Siemens HG 11.0 01 17

Equipment Selection Circuit-breaker and equipment package SION Vacuum Circuit-Breakers AE5 and AE1 7. kv Position: 1 4 5 6 7 8 9 1 1 th position Equipment package 14 16 Order codes Rated voltage for 50 / 60 Hz Rated lightning impulse Rated short-duration powerfrequency Rated short-circuit breaking current at 50 % DC component Rated short-circuit making current (at 50 / 60 Hz) Pole-center distance Order No.: A E 5 «Width across flats U r U p U d I SC I ma I r kv kv kv ka ka A Rated normal current See pages 1 and Circuit-breaker for fixed mounting, without circuit-breaker installation accessories Orderable versions 7. 60 0 16 40/4 10 10 800 A E 5 0 8 1 V V V V 10 150 A E 5 0 8 V V V V 75 800 A E 5 0 7 1 V V V V 75 150 A E 5 0 7 V V V V 05 800 A E 5 0 6 1 V V 05 150 A E 5 0 6 V V 160 10 800 A E 5 0 5 1 V V 10 150 A E 5 0 5 V V 75 800 A E 5 0 4 1 V V 75 150 A E 5 0 4 V V 05 800 A E 5 0 1 V V 05 150 A E 5 0 V V 150 10 800 A E 5 0 1 V V V V 10 150 A E 5 0 V V V V 75 800 A E 5 0 1 1 V V V V 75 150 A E 5 0 1 V V V V 05 800 A E 5 0 0 1 V V 05 150 A E 5 0 0 V V 7. 60 0 0 50/5 10 10 800 A E 5 0 8 1 V V V V 10 150 A E 5 0 8 V V V V 75 800 A E 5 0 7 1 V V V V 75 150 A E 5 0 7 V V V V 05 800 A E 5 0 6 1 V V 05 150 A E 5 0 6 V V 160 10 800 A E 5 0 5 1 V V 10 150 A E 5 0 5 V V 75 800 A E 5 0 4 1 V V 75 150 A E 5 0 4 V V 05 800 A E 5 0 1 V V 05 150 A E 5 0 V V 150 10 800 A E 5 0 1 V V V V 10 150 A E 5 0 V V V V 75 800 A E 5 0 1 1 V V V V 75 150 A E 5 0 1 V V V V 05 800 A E 5 0 0 1 V V 05 150 A E 5 0 0 V V Special version U d = kv Legend: V With contact system Without contact system On withdrawable part On withdrawable part with complete contact system * On withdrawable part with complete contact system and bushings * Withdrawable module without earthing switch Withdrawable module with earthing switch Retrofit See pages 4 to 6 See page 7 Z E 1 6 *) Can also be ordered without withdrawable part, see page, 1 th position 18 Siemens HG 11.0 01

SION Vacuum Circuit-Breakers AE5 and AE1 Equipment Selection Circuit-breaker and equipment package 7. kv Position: 1 4 5 6 7 8 9 1 1 th position Equipment package 14 16 Order codes Rated voltage for 50 / 60 Hz Rated lightning impulse Rated short-duration powerfrequency Rated short-circuit breaking current at 50 % DC component Rated short-circuit making current (at 50 / 60 Hz) Pole-center distance Order No.: A E 5 «Width across flats U r U p U d I sc I ma I r kv kv kv ka ka A Rated normal current See pages 1 and Circuit-breaker for fixed mounting, without circuit-breaker installation accessories Orderable versions 7. 60 0 5 6/65 10 10 800 A E 5 0 8 4 1 V V V V 10 150 A E 5 0 8 4 V V V V 75 800 A E 5 0 7 4 1 V V V V 75 150 A E 5 0 7 4 V V V V 05 800 A E 5 0 6 4 1 V V 05 150 A E 5 0 6 4 V V 160 10 800 A E 5 0 5 4 1 V V 10 150 A E 5 0 5 4 V V 75 800 A E 5 0 4 4 1 V V 75 150 A E 5 0 4 4 V V 05 800 A E 5 0 4 1 V V 05 150 A E 5 0 4 V V 150 10 800 A E 5 0 4 1 V V V V 10 150 A E 5 0 4 V V V V 75 800 A E 5 0 1 4 1 V V V V 75 150 A E 5 0 1 4 V V V V 05 800 A E 5 0 0 4 1 V V 05 150 A E 5 0 0 4 V V Special version U d = kv Legend: I sc = 6. ka V With contact system Without contact system On withdrawable part On withdrawable part with complete contact system * On withdrawable part with complete contact system and bushings * Withdrawable module without earthing switch Withdrawable module with earthing switch Retrofit See pages 4 to 6 See page 7 Z E 1 6 Z E 4 6 *) Can also be ordered without withdrawable part, see page, 1 th position Siemens HG 11.0 01 19

Equipment Selection Circuit-breaker and equipment package SION Vacuum Circuit-Breakers AE5 and AE1 7. kv Position: 1 4 5 6 7 8 9 1 1 th position Equipment package 14 16 Order codes Rated voltage for 50 / 60 Hz Rated lightning impulse Rated short-duration powerfrequency Rated short-circuit breaking current at 6 % DC component Rated short-circuit making current (at 50 / 60 Hz) Pole-center distance Order No.: A E 1 «Width across flats U r U p U d I SC I ma I r kv kv kv ka ka A Rated normal current See pages 1 and Circuit-breaker for fixed mounting, without circuit-breaker installation accessories Orderable versions 7. 60 0 16 40/4 10 10 800 A E 1 0 8 1 V V V V 10 150 A E 1 0 8 V V V V 75 800 A E 1 0 7 1 V V V V 75 150 A E 1 0 7 V V V V 05 800 A E 1 0 6 1 V V 05 150 A E 1 0 6 V V 160 10 800 A E 1 0 5 1 V V 10 150 A E 1 0 5 V V 75 800 A E 1 0 4 1 V V 75 150 A E 1 0 4 V V 05 800 A E 1 0 1 V V 05 150 A E 1 0 V V 150 10 800 A E 1 0 1 V V V V 10 150 A E 1 0 V V V V 75 800 A E 1 0 1 1 V V V V 75 150 A E 1 0 1 V V V V 05 800 A E 1 0 0 1 V V 05 150 A E 1 0 0 V V 7. 60 0 0 50/5 10 10 800 A E 1 0 8 1 V V V V 10 150 A E 1 0 8 V V V V 75 800 A E 1 0 7 1 V V V V 75 150 A E 1 0 7 V V V V 05 800 A E 1 0 6 1 V V 05 150 A E 1 0 6 V V 160 10 800 A E 1 0 5 1 V V 10 150 A E 1 0 5 V V 75 800 A E 1 0 4 1 V V 75 150 A E 1 0 4 V V 05 800 A E 1 0 1 V V 05 150 A E 1 0 V V 150 10 800 A E 1 0 1 V V V V 10 150 A E 1 0 V V V V 75 800 A E 1 0 1 1 V V V V 75 150 A E 1 0 1 V V V V 05 800 A E 1 0 0 1 V V 05 150 A E 1 0 0 V V Special version U d = kv Legend: V With contact system Without contact system On withdrawable part On withdrawable part with complete contact system * On withdrawable part with complete contact system and bushings * Withdrawable module without earthing switch Withdrawable module with earthing switch Retrofit See pages 4 to 6 See page 7 Z E 1 6 *) Can also be ordered without withdrawable part, see page, 1 th position 0 Siemens HG 11.0 01

SION Vacuum Circuit-Breakers AE5 and AE1 Equipment Selection Circuit-breaker and equipment package 7. kv Position: 1 4 5 6 7 8 9 1 1 th position Equipment package 14 16 Order codes Rated voltage for 50 / 60 Hz Rated lightning impulse Rated short-duration powerfrequency Rated short-circuit breaking current at 6 % DC component Rated short-circuit making current (at 50 / 60 Hz) Pole-center distance Order No.: A E 1 «Width across flats U r U p U d I SC I ma I r kv kv kv ka ka A Rated normal current See pages 1 and Circuit-breaker for fixed mounting, without circuit-breaker installation accessories Orderable versions 7. 60 0 5 6/65 10 10 800 A E 1 0 8 4 1 V V V V 10 150 A E 1 0 8 4 V V V V 10 000 A E 1 0 8 4 4 V V V V 75 800 A E 1 0 7 4 1 V V V V 75 150 A E 1 0 7 4 V V V V 05 800 A E 1 0 6 4 1 V V 05 150 A E 1 0 6 4 V V 160 10 800 A E 1 0 5 4 1 V V 10 150 A E 1 0 5 4 V V 75 800 A E 1 0 4 4 1 V V 75 150 A E 1 0 4 4 V V 05 800 A E 1 0 4 1 V V 05 150 A E 1 0 4 V V 150 10 800 A E 1 0 4 1 V V V V 10 150 A E 1 0 4 V V V V 75 800 A E 1 0 1 4 1 V V V V 75 150 A E 1 0 1 4 V V V V 05 800 A E 1 0 0 4 1 V V 05 150 A E 1 0 0 4 V V 7. 60 0 1.5 80/8 10 10 800 A E 1 0 8 5 1 V V V V 10 150 A E 1 0 8 5 V V V V 10 000 A E 1 0 8 5 4 V V V V 10 500 A E 1 0 8 5 6 V V V V 75 800 A E 1 0 7 5 1 V V V V 75 150 A E 1 0 7 5 V V V V 05 800 A E 1 0 6 5 1 V V 05 150 A E 1 0 6 5 V V 160 10 800 A E 1 0 5 5 1 V V 10 150 A E 1 0 5 5 V V 75 800 A E 1 0 4 5 1 V V 75 150 A E 1 0 4 5 V V 05 800 A E 1 0 5 1 V V 05 150 A E 1 0 5 V V 150 10 800 A E 1 0 5 1 V V V V 10 150 A E 1 0 5 V V V V 75 800 A E 1 0 1 5 1 V V V V 75 150 A E 1 0 1 5 V V V V 05 800 A E 1 0 0 5 1 V V 05 150 A E 1 0 0 5 V V 7. 60 0 40 100/104 10 10 150 A E 1 0 8 6 V V V V 10 000 A E 1 0 8 6 4 V V V V 10 500 A E 1 0 8 6 6 V V V V 10 150 A E 1 0 8 6 7 V V V V Special version U d = kv Legend: V With contact system Without contact system On withdrawable part On withdrawable part with complete contact system * On withdrawable part with complete contact system and bushings * Withdrawable module without earthing switch Withdrawable module with earthing switch Retrofit See pages 4 to 6 See page 7 Z E 1 6 *) Can also be ordered without withdrawable part, see page, 1 th position Siemens HG 11.0 01 1

Equipment Selection Circuit-breaker and equipment package SION Vacuum Circuit-Breakers AE5 and AE1 1 kv Position: 1 4 5 6 7 8 9 1 1 th position Equipment package 14 16 Order codes Rated voltage for 50 / 60 Hz Rated lightning impulse Rated short-duration powerfrequency Rated short-circuit breaking current at 50 % DC component Rated short-circuit making current (at 50 / 60 Hz) Pole-center distance Order No.: A E 5 «Width across flats U r U p U d I sc I ma I r kv kv kv ka ka A Rated normal current See pages 1 and Circuit-breaker for fixed mounting, without circuit-breaker installation accessories Orderable versions 1 75 8 16 40/4 10 10 800 A E 5 1 8 1 V V V V 10 150 A E 5 1 8 V V V V 75 800 A E 5 1 7 1 V V V V 75 150 A E 5 1 7 V V V V 05 800 A E 5 1 6 1 V V 05 150 A E 5 1 6 V V 160 10 800 A E 5 1 5 1 V V 10 150 A E 5 1 5 V V 75 800 A E 5 1 4 1 V V 75 150 A E 5 1 4 V V 05 800 A E 5 1 1 V V 05 150 A E 5 1 V V 150 10 800 A E 5 1 1 V V V V 10 150 A E 5 1 V V V V 75 800 A E 5 1 1 1 V V V V 75 150 A E 5 1 1 V V V V 05 800 A E 5 1 0 1 V V 05 150 A E 5 1 0 V V 1 75 8 0 50/5 10 10 800 A E 5 1 8 1 V V V V 10 150 A E 5 1 8 V V V V 75 800 A E 5 1 7 1 V V V V 75 150 A E 5 1 7 V V V V 05 800 A E 5 1 6 1 V V 05 150 A E 5 1 6 V V 160 10 800 A E 5 1 5 1 V V 10 150 A E 5 1 5 V V 75 800 A E 5 1 4 1 V V 75 150 A E 5 1 4 V V 05 800 A E 5 1 1 V V 05 150 A E 5 1 V V 150 10 800 A E 5 1 1 V V V V 10 150 A E 5 1 V V V V 75 800 A E 5 1 1 1 V V V V 75 150 A E 5 1 1 V V V V 05 800 A E 5 1 0 1 V V 05 150 A E 5 1 0 V V Special version U d = 4 kv U p = 95 kv On withdrawable part On withdrawable part with complete contact system * On withdrawable part with complete contact system and bushings * Withdrawable module without earthing switch Withdrawable module with earthing switch Retrofit See pages 4 to 6 See page 7 Z E 1 Z E 9 5 Legend: V With contact system Without contact system *) Can also be ordered without withdrawable part, see page, 1 th position Siemens HG 11.0 01

SION Vacuum Circuit-Breakers AE5 and AE1 Equipment Selection Circuit-breaker and equipment package 1 kv Position: 1 4 5 6 7 8 9 1 1 th position Equipment package 14 16 Order codes Rated voltage for 50 / 60 Hz Rated lightning impulse Rated short-duration powerfrequency Rated short-circuit breaking current at 50 % DC component Rated short-circuit making current (at 50 / 60 Hz) Pole-center distance Order No.: A E 5 «Width across flats U r U p U d I sc I ma I r kv kv kv ka ka A Rated normal current See pages 1 and Circuit-breaker for fixed mounting, without circuit-breaker installation accessories Orderable versions 1 75 8 5 6/65 10 10 800 A E 5 1 8 4 1 V V V V 10 150 A E 5 1 8 4 V V V V 75 800 A E 5 1 7 4 1 V V V V 75 150 A E 5 1 7 4 V V V V 05 800 A E 5 1 6 4 1 V V 05 150 A E 5 1 6 4 V V 160 10 800 A E 5 1 5 4 1 V V 10 150 A E 5 1 5 4 V V 75 800 A E 5 1 4 4 1 V V 75 150 A E 5 1 4 4 V V 05 800 A E 5 1 4 1 V V 05 150 A E 5 1 4 V V 150 10 800 A E 5 1 4 1 V V V V 10 150 A E 5 1 4 V V V V 75 800 A E 5 1 1 4 1 V V V V 75 150 A E 5 1 1 4 V V V V 05 800 A E 5 1 0 4 1 V V 05 150 A E 5 1 0 4 V V Special version U d = 4 kv I sc = 6. ka U p = 95 kv Circuit-breaker for installation in NXAIR World 1) On withdrawable part On withdrawable part with complete contact system * On withdrawable part with complete contact system and bushings * Withdrawable module without earthing switch Withdrawable module with earthing switch Retrofit See pages 4 to 6 See page 7 Z E 1 Z E 4 6 Z E 9 5 1 75 8 5 6/65 160 75 800 A E 5 5 5 4 1 Z W 6 Special version U d = 4 kv I sc = 6. ka U d = 95 kv 75 150 A E 5 5 5 4 Z W 6 Z E 1 Z E 4 6 Z E 9 5 1) W6 is absolutely necessary as order code *) Can also be ordered without withdrawable part, Legend: V With contact system Without contact system s Retrofit contact system see page, 1 th position Siemens HG 11.0 01

Equipment Selection Circuit-breaker and equipment package SION Vacuum Circuit-Breakers AE5 and AE1 1 kv Position: 1 4 5 6 7 8 9 1 1 th position Equipment package 14 16 Order codes Rated voltage for 50 / 60 Hz Rated lightning impulse Rated short-duration powerfrequency Rated short-circuit breaking current at 6 % DC component Rated short-circuit making current (at 50 / 60 Hz) Pole-center distance Order No.: A E 1 «Width across flats U r U p U d I SC I ma I r kv kv kv ka ka A Rated normal current See pages 1 and Circuit-breaker for fixed mounting, without circuit-breaker installation accessories Orderable versions 1 75 8 16 40/4 10 10 800 A E 1 1 8 1 V V V V 10 150 A E 1 1 8 V V V V 75 800 A E 1 1 7 1 V V V V 75 150 A E 1 1 7 V V V V 05 800 A E 1 1 6 1 V V 05 150 A E 1 1 6 V V 160 10 800 A E 1 1 5 1 V V 10 150 A E 1 1 5 V V 75 800 A E 1 1 4 1 V V 75 150 A E 1 1 4 V V 05 800 A E 1 1 1 V V 05 150 A E 1 1 V V 150 10 800 A E 1 1 1 V V V V 10 150 A E 1 1 V V V V 75 800 A E 1 1 1 1 V V V V 75 150 A E 1 1 1 V V V V 05 800 A E 1 1 0 1 V V 05 150 A E 1 1 0 V V 1 75 8 0 50/5 10 10 800 A E 1 1 8 1 V V V V 10 150 A E 1 1 8 V V V V 75 800 A E 1 1 7 1 V V V V 75 150 A E 1 1 7 V V V V 05 800 A E 1 1 6 1 V V 05 150 A E 1 1 6 V V 160 10 800 A E 1 1 5 1 V V 10 150 A E 1 1 5 V V 75 800 A E 1 1 4 1 V V 75 150 A E 1 1 4 V V 05 800 A E 1 1 1 V V 05 150 A E 1 1 V V 150 10 800 A E 1 1 1 V V V V 10 150 A E 1 1 V V V V 75 800 A E 1 1 1 1 V V V V 75 150 A E 1 1 1 V V V V 05 800 A E 1 1 0 1 V V 05 150 A E 1 1 0 V V Special version U d = 4 kv Legend: U p = 95 kv V With contact system Without contact system On withdrawable part On withdrawable part with complete contact system * On withdrawable part with complete contact system and bushings * Withdrawable module without earthing switch Withdrawable module with earthing switch Retrofit See pages 4 to 6 See page 7 Z E 1 Z E 9 5 *) Can also be ordered without withdrawable part, see page, 1 th position 4 Siemens HG 11.0 01

SION Vacuum Circuit-Breakers AE5 and AE1 Equipment Selection Circuit-breaker and equipment package 1 kv Position: 1 4 5 6 7 8 9 1 1 th position Equipment package 14 16 Order codes Rated voltage for 50 / 60 Hz Rated lightning impulse Rated short-duration powerfrequency Rated short-circuit breaking current at 6 % DC component Rated short-circuit making current (at 50 / 60 Hz) Pole-center distance Order No.: A E 1 «Width across flats U r U p U d I SC I ma I r kv kv kv ka ka A Rated normal current See pages 1 and Circuit-breaker for fixed mounting, without circuit-breaker installation accessories Orderable versions 1 75 8 5 6/65 10 10 800 A E 1 1 8 4 1 V V V V On withdrawable part On withdrawable part with complete contact system * On withdrawable part with complete contact system and bushings * 10 150 A E 1 1 8 4 V V V V s 10 000 A E 1 1 8 4 4 V V V V s 10 500 A E 1 1 8 4 6 V V V V s 75 800 A E 1 1 7 4 1 V V V V 75 150 A E 1 1 7 4 V V V V 05 800 A E 1 1 6 4 1 V V 05 150 A E 1 1 6 4 V V 160 10 800 A E 1 1 5 4 1 V V 10 150 A E 1 1 5 4 V V 75 800 A E 1 1 4 4 1 V V 75 150 A E 1 1 4 4 V V 05 800 A E 1 1 4 1 V V 05 150 A E 1 1 4 V V 150 10 800 A E 1 1 4 1 V V V V 10 150 A E 1 1 4 V V V V 75 800 A E 1 1 1 4 1 V V V V 75 150 A E 1 1 1 4 V V V V 05 800 A E 1 1 0 4 1 V V 05 150 A E 1 1 0 4 V V 1 75 8 1.5 80/8 10 10 800 A E 1 1 8 5 1 V V V V Special version U d = 4 kv Legend: U p = 95 kv V With contact system Without contact system s Retrofit contact system 10 150 A E 1 1 8 5 V V V V s 10 000 A E 1 1 8 5 4 V V V V s 10 500 A E 1 1 8 5 6 V V V V s 75 800 A E 1 1 7 5 1 V V V V 75 150 A E 1 1 7 5 V V V V 05 800 A E 1 1 6 5 1 V V 05 150 A E 1 1 6 5 V V 160 10 800 A E 1 1 5 5 1 V V 10 150 A E 1 1 5 5 V V 75 800 A E 1 1 4 5 1 V V 75 150 A E 1 1 4 5 V V 05 800 A E 1 1 5 1 V V 05 150 A E 1 1 5 V V 150 10 800 A E 1 1 5 1 V V V V 10 150 A E 1 1 5 V V V V 75 800 A E 1 1 1 5 1 V V V V 75 150 A E 1 1 1 5 V V V V 05 800 A E 1 1 0 5 1 V V 05 150 A E 1 1 0 5 V V Withdrawable module without earthing switch Withdrawable module with earthing switch Retrofit See pages 4 to 6 See page 7 Z E 1 Z E 9 5 *) Can also be ordered without withdrawable part, see page, 1 th position Siemens HG 11.0 01 5

Equipment Selection Circuit-breaker and equipment package SION Vacuum Circuit-Breakers AE5 and AE1 1 kv Position: 1 4 5 6 7 8 9 1 1 th position Equipment package 14 16 Order codes Rated voltage for 50 / 60 Hz Rated lightning impulse Rated short-duration powerfrequency Rated short-circuit breaking current at 6 % DC component Rated short-circuit making current (at 50 / 60 Hz) Pole-center distance Order No.: A E 1 «Width across flats U r U p U d I SC I ma I r kv kv kv ka ka A Rated normal current See pages 1 and Circuit-breaker for fixed mounting, without circuit-breaker installation accessories Orderable versions 1 75 8 40 100/104 10 10 150 A E 1 1 8 6 V V V V 10 000 A E 1 1 8 6 4 V V V V 10 500 A E 1 1 8 6 6 V V V V 10 150 A E 1 1 8 6 7 V V V V Circuit-breaker for installation in NXAIR World 1) Special version U d = 4 kv U p = 95 kv On withdrawable part On withdrawable part with complete contact system * On withdrawable part with complete contact system and bushings * Withdrawable module without earthing switch Withdrawable module with earthing switch Retrofit See pages 4 to 6 See page 7 Z E 1 Z E 9 5 1 75 8 5 6/65 160 75 800 A E 1 5 5 4 1 Z W 6 Special version U d = 4 kv U p = 95 kv 75 150 A E 1 5 5 4 Z W 6 1.5 80/81.9 160 75 800 A E 1 5 5 5 1 Z W 6 75 150 A E 1 5 5 5 Z W 6 10 75 150 A E 1 5 6 5 Z W 6 75 500 A E 1 5 6 5 6 Z W 6 40 100/104 10 75 150 A E 1 5 6 6 Z W 6 75 500 A E 1 5 6 6 6 Z W 6 75 150 A E 1 5 6 6 7 Z W 6 Z E 1 Z E 9 5 1) W6 is absolutely necessary as order code *) Can also be ordered without withdrawable part, Legend: V With contact system Without contact system see page, 1 th position 6 Siemens HG 11.0 01

SION Vacuum Circuit-Breakers AE5 and AE1 Equipment Selection Circuit-breaker and equipment package 17.5 kv Position: 1 4 5 6 7 8 9 1 1 th position Equipment package 14 16 Order codes Rated voltage for 50 / 60 Hz Rated lightning impulse Rated short-duration powerfrequency Rated short-circuit breaking current at 6 % DC component Rated short-circuit making current (at 50 / 60 Hz) Pole-center distance Order No.: A E 1 «Width across flats U r U p U d I SC I ma I r kv kv kv ka ka A Rated normal current See pages 1 and Circuit-breaker for fixed mounting, without circuit-breaker installation accessories Orderable versions 17.5 95 8 1.5 1/ 10 10 800 A E 1 8 1 1 V V V V 10 150 A E 1 8 1 V V V V 75 800 A E 1 7 1 1 V V V V 75 150 A E 1 7 1 V V V V 05 800 A E 1 6 1 1 V V 05 150 A E 1 6 1 V V 160 10 800 A E 1 5 1 1 V V 10 150 A E 1 5 1 V V 75 800 A E 1 4 1 1 V V 75 150 A E 1 4 1 V V 05 800 A E 1 1 1 V V 05 150 A E 1 1 V V 150 10 800 A E 1 1 1 V V V V 10 150 A E 1 1 V V V V 75 800 A E 1 1 1 1 V V V V 75 150 A E 1 1 1 V V V V 05 800 A E 1 0 1 1 V V 05 150 A E 1 0 1 V V 17.5 95 8 16 40/4 10 10 800 A E 1 8 1 V V V V 10 150 A E 1 8 V V V V 75 800 A E 1 7 1 V V V V 75 150 A E 1 7 V V V V 05 800 A E 1 6 1 V V 05 150 A E 1 6 V V 160 10 800 A E 1 5 1 V V 10 150 A E 1 5 V V 75 800 A E 1 4 1 V V 75 150 A E 1 4 V V 05 800 A E 1 1 V V 05 150 A E 1 V V 150 10 800 A E 1 1 V V V V 10 150 A E 1 V V V V 75 800 A E 1 1 1 V V V V 75 150 A E 1 1 V V V V 05 800 A E 1 0 1 V V 05 150 A E 1 0 V V 17.5 95 8 5 6/65 10 10 800 A E 1 8 4 1 V V V V Legend: V With contact system Without contact system s Retrofit contact system On withdrawable part On withdrawable part with complete contact system * On withdrawable part with complete contact system and bushings * 10 150 A E 1 8 4 V V V V s 10 000 A E 1 8 4 4 V V V V s 10 500 A E 1 8 4 6 V V V V s Withdrawable module without earthing switch Withdrawable module with earthing switch Retrofit See pages 4 to 6 See page 7 *) Can also be ordered without withdrawable part, see page, 1 th position Siemens HG 11.0 01 7

Equipment Selection Circuit-breaker and equipment package SION Vacuum Circuit-Breakers AE5 and AE1 17.5 kv Position: 1 4 5 6 7 8 9 1 1 th position Equipment package 14 16 Order codes Rated voltage for 50 / 60 Hz Rated lightning impulse Rated short-duration powerfrequency Rated short-circuit breaking current at 6 % DC component Rated short-circuit making current (at 50 / 60 Hz) Pole-center distance Order No.: A E 1 «Width across flats U r U p U d I SC I ma I r kv kv kv ka ka A Rated normal current See pages 1 and Circuit-breaker for fixed mounting, without circuit-breaker installation accessories Orderable versions 17.5 95 8 5 6/65 10 75 800 A E 1 7 4 1 V V V V 75 150 A E 1 7 4 V V V V 05 800 A E 1 6 4 1 V V 05 150 A E 1 6 4 V V 160 10 800 A E 1 5 4 1 V V 10 150 A E 1 5 4 V V 75 800 A E 1 4 4 1 V V 75 150 A E 1 4 4 V V 05 800 A E 1 4 1 V V 05 150 A E 1 4 V V 150 10 800 A E 1 4 1 V V V V 10 150 A E 1 4 V V V V 75 800 A E 1 1 4 1 V V V V 75 150 A E 1 1 4 V V V V 05 800 A E 1 0 4 1 V V 05 150 A E 1 0 4 V V 17.5 95 8 1.5 80/8 10 10 800 A E 1 8 5 1 V V V V On withdrawable part On withdrawable part with complete contact system * On withdrawable part with complete contact system and bushings * 10 150 A E 1 8 5 V V V V s 10 000 A E 1 8 5 4 V V V V 10 500 A E 1 8 5 6 V V V V s 75 800 A E 1 7 5 1 V V V V 75 150 A E 1 7 5 V V V V 05 800 A E 1 6 5 1 V V 05 150 A E 1 6 5 V V 160 10 800 A E 1 5 5 1 V V 10 150 A E 1 5 5 V V 75 800 A E 1 4 5 1 V V 75 150 A E 1 4 5 V V 05 800 A E 1 5 1 V V 05 150 A E 1 5 V V 150 10 800 A E 1 5 1 V V V V 10 150 A E 1 5 V V V V 75 800 A E 1 1 5 1 V V V V 75 150 A E 1 1 5 V V V V 05 800 A E 1 0 5 1 V V 05 150 A E 1 0 5 V V 17.5 95 8 40 100/104 10 10 150 A E 1 8 6 V V V V 10 000 A E 1 8 6 4 V V V V 10 500 A E 1 8 6 6 V V V V 10 150 A E 1 8 6 7 V V V V Legend: V With contact system Without contact system s Retrofit contact system Withdrawable module without earthing switch Withdrawable module with earthing switch Retrofit See pages 4 to 6 See page 7 *) Can also be ordered without withdrawable part, see page, 1 th position 8 Siemens HG 11.0 01

SION Vacuum Circuit-Breakers AE5 and AE1 Equipment Selection Circuit-breaker and equipment package 17.5 kv Position: 1 4 5 6 7 8 9 1 1 th position Equipment package 14 16 Order codes Rated voltage for 50 / 60 Hz Rated lightning impulse Rated short-duration powerfrequency Rated short-circuit breaking current at 6 % DC component Rated short-circuit making current (at 50 / 60 Hz) Pole-center distance Order No.: A E 1 «Width across flats U r U p U d I SC I ma I r kv kv kv ka ka A Rated normal current See pages 1 and Circuit-breaker for fixed mounting, without circuit-breaker installation accessories Orderable versions Circuit-breaker for installation in NXAIR World 1) Z W 6 17.5 95 8 5 6/65 160 75 800 A E 1 6 4 1 Z W 6 On withdrawable part On withdrawable part with complete contact system * On withdrawable part with complete contact system and bushings * 75 150 A E 1 6 4 Z W 6 1.5 80/81.9 160 75 800 A E 1 6 5 1 Z W 6 75 150 A E 1 6 5 Z W 6 10 75 150 A E 1 6 6 5 Z W 6 75 500 A E 1 6 6 5 6 Z W 6 40 100/104 10 75 150 A E 1 6 6 6 Z W 6 75 500 A E 1 6 6 6 6 Z W 6 75 150 A E 1 6 6 6 7 Z W 6 1) W6 is absolutely necessary as order code *) Can also be ordered without withdrawable part, Legend: Without contact system see page, 1 th position Withdrawable module without earthing switch Withdrawable module with earthing switch Retrofit See pages 4 to 6 See page 7 Siemens HG 11.0 01 9

Equipment Selection Circuit-breaker and equipment package SION Vacuum Circuit-Breakers AE5 and AE1 4 kv Position: 1 4 5 6 7 8 9 1 1 th position Equipment package 14 16 Order codes Rated voltage for 50 / 60 Hz Rated lightning impulse Rated short-duration powerfrequency Rated short-circuit breaking current at 6 % DC component Rated short-circuit making current (at 50 / 60 Hz) Pole-center distance Order No.: A E 1 «Width across flats U r U p U d I SC I ma I r kv kv kv ka ka A Rated normal current See pages 1 and Circuit-breaker for fixed mounting, without circuit-breaker installation accessories Orderable versions 4 15 50 1.5 1/ 10 10 800 A E 1 1 1 V V V V 10 150 A E 1 1 V V V V 4 15 50 16 40/4 10 10 800 A E 1 1 V V V V 10 150 A E 1 V V V V 10 000 A E 1 4 V V V V 75 10 800 A E 1 5 1 V V V V 10 150 A E 1 5 V V V V 10 000 A E 1 5 4 V V V V 4 15 50 0 50/5 10 10 800 A E 1 1 V V V V On withdrawable part On withdrawable part with complete contact system * On withdrawable part with complete contact system and bushings * 10 150 A E 1 V V V V s 10 000 A E 1 4 V V V V s 10 500 A E 1 6 V V V V 75 10 800 A E 1 5 1 V V V V 10 150 A E 1 5 V V V V 10 000 A E 1 5 4 V V V V 10 500 A E 1 5 6 V V V V 4 15 50 5 6/65 10 10 800 A E 1 4 1 V V V V Special version U d = 55 kv Special version U d = 65 kv 10 150 A E 1 4 V V V V s 10 000 A E 1 4 4 V V V V s 10 500 A E 1 4 6 V V V V 75 10 800 A E 1 5 4 1 V V V V 10 150 A E 1 5 4 V V V V 10 000 A E 1 5 4 4 V V V V 10 500 A E 1 5 4 6 V V V V Withdrawable module without earthing switch Withdrawable module with earthing switch Retrofit See pages 4 to 6 See page 7 Z E 5 5 Z E 6 5 1) ) Circuit-breaker for installation in NXAIR ) 4 15 50 5 6/65 10 0 150 A E 1 7 1 4 Z W 6 Special version U d = 55 kv 1) With special version E55 (selection is possible if 1 th position 0, 1,, and 5) ) With special version E65 (selection is possible if 1 th position 0 and 1) ) W6 is absolutely necessary as order code 75 0 000 A E 1 7 4 4 4 Z W 6 0 500 A E 1 7 4 4 6 Z W 6 Z E 5 5 *) Can also be ordered without withdrawable part, see page, 1 th position 1) Legend: V With contact system Without contact system s Retrofit contact system 0 Siemens HG 11.0 01

SION Vacuum Circuit-Breakers AE5 and AE1 Equipment Selection Secondary equipment 9 th position Release combination 1) Position: 1 4 5 6 7 8 9 10 11 1 1 14 15 16 Order codes Order No.: A E 1 «1 st shunt release nd shunt release Undervoltage release C.t.-operated release 0.5 A ) C.t.-operated release 1.0 A C.t.-operated release with tripping pulse 0.1 Ws (10 Ω) C.t.-operated release with tripping pulse 0.1 Ws (0 Ω) See page See page See page 4 See page 5 See page 6 See page 7 A B C D G H F E not for AE5 N not for AE5 P not for AE5 Q not for AE5 J not for AE5 1) Operating voltage is selected at positions 11 + 1 K not for AE5 L not for AE5 M not for AE5 ) Special version with c.t.-operated release 5 A: Can be ordered with order code A49 for all circuit-breakers (except retrofit) with c.t.-operated release 0.5 A (4 th column) (not for AE5) Z A 4 9 10 th position Operating voltage of the closing solenoid Standard voltages Special voltages 4 V DC B 48 V DC C 60 V DC D 110 V DC E 0 V DC F 100 V AC 50 / 60 Hz ) H 110 V AC 50 / 60 Hz ) J 0 V AC 50 / 60 Hz ) K ) The AC frequency 50 or 60 Hz is selected at the 16 th position of the order number together with the language (see page 6) 0 V DC M V DC N 10 V DC P 15 V DC Q 17 V DC R 40 V DC S 10 V AC 50 / 60 Hz ) U 15 V AC 50 / 60 Hz ) V 40 V AC 50 / 60 Hz ) W Siemens HG 11.0 01 1

Equipment Selection Secondary equipment SION Vacuum Circuit-Breakers AE5 and AE1 11 th position Operating voltage of the 1 st release Position: 1 4 5 6 7 8 9 10 11 1 1 14 15 16 Order codes Order No.: A E 1 «Standard voltages Special voltages See page 4 See page 5 See page 6 See page 7 C.t.-operated release 0 not for AE5 4 V DC 1 48 V DC 60 V DC 110 V DC 4 0 V DC 5 100 V AC 50 / 60 Hz 1) 6 110 V AC 50 / 60 Hz 1) 7 0 V AC 50 / 60 Hz 1) 8 0 V DC 9 L 1 A V DC 9 L 1 B 10 V DC 9 L 1 C 15 V DC 9 L 1 D 17 V DC 9 L 1 E 40 V DC 9 L 1 F 10 V AC 50 / 60 Hz 1) 9 L 1 K 15 V AC 50 / 60 Hz 1) 9 L 1 L 40 V AC 50 / 60 Hz 1) 9 L 1 M 1 th position Operating voltage of the nd release Standard voltages Special voltages without, or c.t.-operated release 0 4 V DC 1 48 V DC 60 V DC 110 V DC 4 0 V DC 5 100 V AC 50 / 60 Hz 1) 6 110 V AC 50 / 60 Hz 1) 7 0 V AC 50 / 60 Hz 1) 8 1) The AC frequency 50 or 60 Hz is selected at the 16 th position of the order number together with the language (see page 6) 0 V DC 9 M 1 A V DC 9 M 1 B 10 V DC 9 M 1 C 15 V DC 9 M 1 D 17 V DC 9 M 1 E 40 V DC 9 M 1 F 10 V AC 50 / 60 Hz 1) 9 M 1 K 15 V AC 50 / 60 Hz 1) 9 M 1 L 40 V AC 50 / 60 Hz 1) 9 M 1 M Siemens HG 11.0 01

SION Vacuum Circuit-Breakers AE5 and AE1 Equipment Selection Secondary equipment 1 th position Circuit-breaker installation accessories Position: 1 4 5 6 7 8 9 10 11 1 1 14 15 16 Order codes Order No.: A E 1 «Options See page 4 See page 5 See page 6 See page 7 Circuit-breaker for fixed mounting Without circuit-breaker installation accessories, circuit-breaker for fixed mounting Circuit-breaker prepared for separate mounting of withdrawable part Without withdrawable part, with contact arm, contact 1), wiring of withdrawable part (loose delivery) 0 Z M Without withdrawable part, with contact arm, contact 1), fixed contact, bushing, wiring of withdrawable part (loose delivery) Z M Circuit-breaker on withdrawable part On withdrawable part 1 On withdrawable part, with contact arm, contact 1) On withdrawable part, with contact arm, contact 1), fixed contact, bushing Withdrawable module Circuit-breaker on withdrawable part, with cartridge, contact arm, contact 1), fixed contacts, bushing, shutters Circuit-breaker on withdrawable part, with cartridge, contact arm, contact 1), fixed contacts, bushing, shutters, make-proof earthing switch Retrofit 8B Circuit-breaker on truck for retrofitting 8B switchgear, see next page 1) Special version: Contact with 1 contact fingers (only up to 150 A and 1.5 ka) can be ordered with order code Z-M1 5 6 7 not for AE5 R-HG11-79.tif R-HG11-75.tif R-HG11-76.tif R-HG11-6.eps Example: Circuit-breaker for fixed mounting Example: Circuit-breaker on drawout element with contact arms and contacts Example: Circuit-breaker with withdrawable module Example: Circuit-breaker with withdrawable module and earthing switch Siemens HG 11.0 01

Equipment Selection Secondary equipment SION Vacuum Circuit-Breakers AE5 and AE1 1 th position Position: Circuit-breaker installation accessories (continued) Order No.: 1 4 5 6 7 8 9 10 11 1 1 14 15 16 Order codes A E 1 «Options See page 5 See page 6 See page 7 Circuit-breaker on truck for retrofitting 8B switchgear Contact arm including contact Ratings of your 8B swichgear Type Thickness of fixed contact Lower insertion height A Fixed contact 10 665 B Fixed contact 15 665 C Fixed contact 10 598 D Fixed contact 15 598 Order number 7. 1 k V 1.5 5 ka 60 150 A Contact arm type A A E 1 1 8 4 7 Z R 1 7. 1 kv 1.5 5 ka 1600 A Contact arm type B A E 1 1 8 4 4 7 Z R 7. 1 kv 1.5 5 ka 000 A Contact arm type D A E 1 1 8 4 4 7 Z R 7. 1 kv 1.5 5 ka 500 A Contact arm type D A E 1 1 8 4 6 7 Z R 4 1 kv 9 (10 kv) 60 150 A Contact arm type A A E 1 1 8 5 7 Z R 5 7. 1 kv 1.5 ka 60 150 A Contact arm type D A E 1 1 8 5 7 Z R 6 1 kv 9 (10 kv) 1600 A Contact arm type B A E 1 1 8 5 4 7 Z R 7 7. 1 kv 1.5 ka 1600 500 A Contact arm type D A E 1 1 8 5 6 7 Z R 8 15 kv 1.5 5 ka 60 150 A Contact arm type A A E 1 8 4 7 Z R 9 17.5 kv 8 5 ka 60 150 A Contact arm type C A E 1 8 4 7 Z R 0 15 17.5 kv 0 5 ka 000 A Contact arm type D A E 1 8 4 4 7 Z R 1 15 kv 5 ka 500 A Contact arm type D A E 1 8 4 6 7 Z R 15 kv 1.5 ka 60 150 A Contact arm type D A E 1 8 5 7 Z R 15 kv 1.5 ka 1600 500 A Contact arm type D A E 1 8 5 6 7 Z R 4 4 kv 8 0 ka 60 150 A Contact arm type C A E 1 7 Z R 5 4 kv 1.5 ka 1600 A Contact arm type C A E 1 4 7 Z R 6 4 kv 1.5 ka 1600 A Contact arm type D A E 1 4 7 Z R 7 4 kv 0 ka 000 A Contact arm type D A E 1 4 7 Z R 8 4 kv 5 ka 150 A Contact arm type C A E 1 4 7 Z R 9 4 kv 5 ka 000 A Contact arm type D A E 1 4 4 7 Z R 4 0 14. position Operating voltage of the motor operating mechanism Standard voltages Special voltages 4 V DC B 48 V DC C 60 V DC D 110 V DC E 0 V DC F 100 V AC 50 / 60 Hz 1) H 110 V AC 50 / 60 Hz 1) J 0 V AC 50 / 60 Hz 1) K 1) The AC frequency 50 or 60 Hz is selected at the 16 th position of the order number together with the language (see page 6) 0 V DC M V DC N 10 V DC P 15 V DC Q 17 V DC R 40 V DC S 10 V AC 50 / 60 Hz 1) U 15 V AC 50 / 60 Hz 1) V 40 V AC 50 / 60 Hz 1) W S. page 5 S. page 6 S. page 7 4 Siemens HG 11.0 01

SION Vacuum Circuit-Breakers AE5 and AE1 Equipment Selection Secondary equipment 15 th position Interlocking, auxiliary switch, circuit-breaker tripping signal and secondary connection Auxiliary switch Secondary connection Position: 1 4 5 6 7 8 9 10 11 1 1 14 15 16 Order codes Order No.: A E 1 «Mechanical interlocking 6 NO + 6 NC 1 NO + 1 NC Circuit-breaker tripping signal 7-pole for AE1 0-pole for AE5 terminal strip 1) 4-pole plug 1) If 0 6 is selected at the 1 th position: Circuit-breaker / circuit-breaker withdrawable module p B 64-pole plug ) p D p F p H p K p M p R p Q A C p E p G J L N P Same as for N, but with 9 NO + 9 NC ) not for AE5 p U p See page 6 ) ) See page 7 if 0 is selected at the 1 th position If 7 is selected at the 1 th position: Retrofit circuit-breaker A B C D E F G Special versions H Auxiliary switch contacts 6 NO + 6 NC and pins of the 4-pole plug connector gold-plated (not for retrofit) Z A 0 Auxiliary switch contacts 1 NO + 1 NC and pins of the 64-pole plug connector gold-plated (not for retrofit) Z A 1 Key-operated interlock (lock at the circuit-breaker) Only for circuit-breakers with mechanical interlocking and without electrical closing lock-out (A47) (not for retrofit) 1) Electrical devices are wired to the lower part of a plug through the terminal strip. The free auxiliary switch connections are not wired. ) Electrical devices are wired to the lower part of a plug through the terminal strip. The auxiliary switches are wired to the lower part of the plug according to the circuit diagrams. ) Standard for NXAIR World. not for AE5 Z J 6 0 Siemens HG 11.0 01 5

Equipment Selection Secondary equipment SION Vacuum Circuit-Breakers AE5 and AE1 16 th position Languages of operating instructions and rating plate, as well as AC frequency of operating voltages 1) Position: 1 4 5 6 7 8 9 10 11 1 1 14 15 16 Order codes Order No.: A E 1 «Language selection Frequency selection German English French Spanish DC or AC 50 Hz 60 Hz See page 7 0 1 Special versions 4 5 6 7 Italian, DC or AC 50 Hz 9 R 1 F Russian, DC or AC 50 Hz 9 R 1 G Russian, 60 Hz 9 R 1 H Polish, DC or AC 50 Hz 9 R 1 K Other languages on request 1) AC voltage refers to the secondary side and not to the primary part of the circuit-breaker 6 Siemens HG 11.0 01

SION Vacuum Circuit-Breakers AE5 and AE1 Equipment Selection Additional equipment Additional equipment Position: Order No.: 1 4 5 6 7 8 9 10 11 1 1 14 15 16 Order codes A E 1 «Options Circuit-breaker 1 th pos. = 0, 1,, Withdrawable module 1 th position = 5, 6 Retrofit 1 th position = 7 AE1 AE5 Wiring cables, halogen-free Z A 1 0 Protection against condensed water, heating for 0 V AC, 50 W Z A 0 Silicone-free design Z A 1 Circuit-breaker for operation at ambient air temperatures down to 5 C Z A 4 0 Electrical closing lock-out Z A 4 7 C.t.-operated release 5 A Z A 4 9 Additional rating plate, loose delivery Z B 0 0 Without loose delivery Z B 4 Separating shell towards contact arm side (standard version) Z D 9 0 Separating shell towards contact arm side (short version, for 4 kv) Z D 9 1 Rated short-duration power-frequency kv (at 7. kv) Z E 1 6 Rated short-duration power-frequency 4 kv (at 1 kv) Z E 1 Rated short-circuit breaking current I sc = 6. ka Z E 4 6 Rated short-duration power-frequency 55 kv (at 4 kv) Z E 5 5 Rated short-duration power-frequency 65 kv (at 4 kv) 1) Z E 6 5 Routine test certificate (enclosed with delivery) Z F 0 Rated lightning impulse 95 kv (at 1 kv) Z E 9 5 Routine test certificate (with stamp and signature to orderer) Z F 1 Routine test certificate (to orderer) Z F Rated operating sequence O min CO min CO Z F 7 Rated operating sequence O 0. s CO 15 s CO Z F 8 Hand crank (for manual charging of the closing spring) (scope of supply: one hand crank per circuit-breaker) Z F 0 Hand crank, long (scope of supply: one hand crank per circuit-breaker) Z F 1 Handle for withdrawable part (for racking the circuitbreaker on the withdrawable part) (scope of supply: one handle per circuit-breaker). Only required when a withdrawable part is ordered Z F Handle for make-proof earthing switch (for operation of the earthing switch at the withdrawable module) (scope of supply: one handle per circuit-breaker). Only required when a withdrawable module with earthing switch is ordered Z F 4 Break time Y1 60 ms at rated voltage Z G Closing time T Close < 55 ms Z G Key-operated interlock (for circuit-breakers with mechanical interlocking and without A47) Z J 6 0 Contact with 1 contact fingers (up to 150 A and 1.5 ka) (selection via 1 th position / page 9) Z M 1 0,000 operating cycles for all circuit-breakers: 1 kv, 5 ka, 000 A and 1 kv, 1.5 ka and 17.5 kv, 1.5 ka Z M 0 Prepared for NXAIR World Z W 6 1) Only for 0 and 1 at the 1 th position Siemens HG 11.0 01 7

Equipment Selection Accessories and spare parts SION Vacuum Circuit-Breakers AE5 and AE1 On request we will be pleased to send you a complete overview of the accessories and spare parts. Please take the following information into account for ordering. Note: For any query regarding spare parts, subsequent deliveries, etc., the following details are necessary: Type designation Serial no. Year of manufacture Rating plate HG11-518b_en eps Position: 1 9 Designation Description Feature Order No. Handles Hand crank for circuit-breaker AX15 0-B Long hand crank for circuit-breaker AX14 0-B Handle for withdrawable part AX14 0-C Handle for earthing switch (for modules up to 1.5 ka) AX14 0-D Handle for earthing switch (for 40 ka modules) AX14 0-D Lubricant 180 g of Klüber-Isoflex Topas L AX11 -H 1 kg of Klüber-Isoflex Topas L AX11 -E 1 kg of Molykote grease AX14 -L Operating solenoid Used as closing solenoid or 1 st shunt release For AE1 4 V DC AY15 10-5B For AE1 0/ V DC AY15 10-5M For AE1 48 V DC AY15 10-5C For AE1 60 V DC AY15 10-5D For AE1 100/14 V DC AY15 10-5E For AE1 15/144 V DC AY15 10-5N For AE1 0/50 V DC AY15 10-5F For AE1 100/15 V AC, 50/60 Hz AY15 10-5E For AE1 0/40 V AC, 50/60 Hz AY15 10-5F For AE5 4 V DC AY14 10-0B For AE5 0/ V DC AY14 10-0M For AE5 48 V DC AY14 10-0C For AE5 60 V DC AY14 10-0D For AE5 100/14 V DC AY14 10-0E For AE5 15/144 V DC AY14 10-0N For AE5 0/50 V DC AY14 10-0F For AE5 100/15 V AC, 50/60 Hz AY14 10-0E For AE5 0/40 V AC, 50/60 Hz AY14 10-0F nd shunt release For AE1 and AE5 4 V DC AX11 01-B For AE1 and AE5 48 60 V DC AX11 01-C For AE1 and AE5 110 17 V DC AX11 01-E For AE1 and AE5 0 40 V DC AX11 01-F For AE1 and AE5 100 15 V AC, 50 Hz AX11 01-G For AE1 and AE5 0 40 V AC, 50 Hz AX11 01-J For AE1 and AE5 100 15 V AC, 60 Hz AX11 01-G For AE1 and AE5 0 40 V AC, 60 Hz AX11 01-J Mounting parts For nd shunt release For AE1 AX14 11-A For AE5 AX14 11-5A 8 Siemens HG 11.0 01

SION Vacuum Circuit-Breakers AE5 and AE1 Equipment Selection Accessories and spare parts Position: 1 9 Designation Description Feature Order No. Current-transformer For rated normal current 0.5 A For AE1 and AE5 AX11 0-A operated release For rated normal current 1 A For AE1 and AE5 AX11 0-B For tripping pulsew0.1ws, 0 Ω for protection relay 7SJ45 For AE1 and AE5 AX11 04-B Mounting parts For current-transformer operated release For AE1 AX14 11-A For AE5 AX14 11-5A Undervoltage release For AE1 and AE5 4 V DC AX11 0-B For AE1 and AE5 0/ V DC AX11 0-L For AE1 and AE5 48 V DC AX11 0-C For AE1 and AE5 60 V DC AX11 0-D For AE1 and AE5 110 V DC AX11 0-E For AE1 and AE5 10/17 V DC AX11 0-N For AE1 and AE5 0 V DC AX11 0-F For AE1 and AE5 40 V DC AX11 0-P For AE1 and AE5 100 V AC, 50 Hz AX11 0-G For AE1 and AE5 110/15 V AC, 50 Hz AX11 0-H For AE1 and AE5 0 V AC, 50 Hz AX11 0-J For AE1 and AE5 40 V AC, 50 Hz AX11 0-M For AE1 and AE5 100 V AC, 60 Hz AX11 0-G For AE1 and AE5 110/15 V AC, 60 Hz AX11 0-H For AE1 and AE5 0 V AC, 60 Hz AX11 0-J For AE1 and AE5 40 V AC, 60 Hz AX11 0-M Mounting parts For undervoltage release For AE1 AX14 1-A For AE5 AX14 1-5A Drive motor For AE1 4/0/ V DC AY17 11-B For AE1 48 V DC AY17 11-C For AE1 60 V DC AY17 11-D For AE1 100/110/15 V DC/AC AY17 11-E For AE1 0 V DC/0 V AC AY17 11-F For AE5 4/0/ V DC AY17 11-0B For AE5 48 V DC AY17 11-0C For AE5 60 V DC AY17 11-0C For AE5 100/110/15 V DC/AC AY17 11-0E For AE5 0 V DC/0 V AC AY17 11-0F Auxiliary contactor Type RH11 For anti-pumping For AE1 4 V DC SWB: 55656 For AE1 0/ V DC SWB: 55658 For AE1 48 V DC SWB: 55659 For AE1 60 V DC SWB: 55660 For AE1 110 V DC SWB: 55661 For AE1 10/17 V DC SWB: 5566 For AE1 0 V DC SWB: 5566 For AE1 40/50 V DC SWB: 55665 For AE1 110 V AC, 50/60 HZ SWB: 55666 For AE1 10 V AC, 50/60 HZ SWB: 55667 For AE1 15 V AC, 50/60 HZ SWB: 55668 For AE1 0 V AC, 50/60 HZ SWB: 55669 For AE1 40 V AC, 50/60 HZ SWB: 55670 Electronic module For AE5 4 V 60 V AY14 0-0B 110 V 0 V AY14 0-0E Siemens HG 11.0 01 9

Equipment Selection Accessories and spare parts SION Vacuum Circuit-Breakers AE5 and AE1 Position: 1 9 Designation Description Feature Order No. Position switch Type SE4 without installation accessories Used for: Nos. SWB: 46677 Electrical anti-pumping (-S) 1 Electrical interlocking (-S1) 1 Motor control (-S1, -S) Closing spring charged (-S4) 1 Circuit-breaker tripping signal (-S6) Electrical closing lock-out (-S5) 1 Withdrawable part (-S1.0 to - S1.9) 10 Auxiliary switch (-S1) 6 NO + 6 NC SV9 7-AA0 1 NO + 1 NC SV9 74-AA0 Mechanical interlocking For AE1 AX14 0-A Key-operated interlocking For AE1 AX14 7-A Module connector State position indicator of withdrawable part For AE1 and AE5 AX14 60-A Accessories for (for conductor cross-section 1.5 ) plug connector Crimp pins (for lower part of plug) For AE1 and AE5 4-pole AX11 4-A For AE1 and AE5 64-pole AX11 4-4B Crimp sockets (for upper part of plug) For AE1 and AE5 64-pole AX11 4-4C Crimping pliers For AE1 and AE5 AX11 4-4D Disassembly tool For AE1 and AE5 AX11 4-4G Plug connector, complete For AE1 and AE5 4-pole AX11 4-7A For AE1 and AE5 64-pole AX11 4-6A Electrical For AE1 4 V DC AX14 05-B closing lock-out For AE1 0/ V DC AX14 05-K For AE1 48 V DC AX14 05-C For AE1 60 V DC AX14 05-D For AE1 100/17 V DC AX14 05-E For AE1 0/40 V DC AX14 05-F For AE1 100 V AC, 50/60 Hz AX14 05-G For AE1 100/15 V AC, 50/60 Hz AX14 05-H For AE1 0/40 V AC, 50/60 Hz AX14 05-J Mounting parts For electrical closing lock-out For AE1 AX14 15-A For AE1 AX14 16-A Bushing For AE1 and AE5 7. to 17.5 kv to 150 A AX14 51-A For AE1 and AE5 7. to 17.5 kv to 150 A AX14 51-B For AE1 and AE5 4 kv to 500 A AX14 51-B Separating shell towards contact arm Standard version, width across flats 10 For AE1 7. to 17.5 kv AX14 8-A side, for standard Standard version, width across flats 75 For AE1 7. to 17.5 kv AX14 8-C circuit-breakers only Standard version, width across flats 05 For AE1 7. to 17.5 kv AX14 8-D for additional screening Standard version, width across flats 10 For AE5 7. to 1 kv AX14 8-5A in case of narrow Standard version, width across flats 75 For AE5 7. to 1 kv AX14 8-5C installation conditions Standard version, width across flats 05 For AE5 7. to 1 kv AX14 8-5D Standard version, width across flats 10 For AE1 4 kv AX14 8-B Short version, width across flats 10 For AE1 4 kv AX14 8-B Gate for cartridge Short version AX14 5-B 40 Siemens HG 11.0 01

SION Vacuum Circuit-Breakers AE5 and AE1 Equipment Selection Accessories and spare parts Position: 1 9 Designation Description Feature Order No. Contact system For AE1 and AE5 7./1/4 kv, 800 up to 150 A AX14 4-A For AE1 and AE5 17.5 kv, 800 up to 150 A AX14 4-B For AE1 and AE5 7./1/4 kv, up to 150 A AX14 4-C For AE1 and AE5 17.5 kv, up to 150 A AX14 4-D Contact arm, complete For AE1 and AE5 7./1 kv, up to 1.5 ka, up to 150 A AX14 4-A with contact system For AE1 and AE5 7./1 kv, up to 1.5 ka, up to 500 A AX14 4-B For AE1 and AE5 17.5 kv, up to 1.5 ka, up to 150 A AX14 4-C For AE1 and AE5 17.5 kv, up to 1.5 ka, up to 500 A AX14 4-D For AE1 and AE5 4 kv, up to 5 ka, up to 150 A AX14 4-E For AE1 and AE5 4 kv, up to 5 ka, up to 500 A AX14 4-F For AE1 and AE5 7./1 kv, 40 ka, up to 150 A AX14 4-G For AE1 and AE5 7./1 kv, 40 ka, up to 150 A AX14 4-H For AE1 and AE5 17.5 kv, 40 ka, up to 150 A AX14 4-J For AE1 and AE5 17.5 kv, 40 ka, up to 150 A AX14 4-K Fixed contact For AE1 and AE5 7./1/17.5 kv, up to 1.5 ka, to 150 A AX14 44-A For AE1 and AE5 7./1/17.5 kv, up to 1.5 ka, to 500 A AX14 44-B For AE1 and AE5 7./1/17.5 kv, 40 ka, up to 150 A AX14 44-A For AE1 and AE5 4 kv, up to 5 ka, up to 500 A AX14 44-C Conductor bars For AE1 and AE5 (1 set each) for 150/10 pole-center distance, 75 width across flats 7./1/17.5 kv, up to 1.5 ka, to 150 A AX14 55-A earthing switch 150 pole-center distance, 10 width across flats 7./1/17.5 kv, up to 1.5 ka, to 150 A AX14 55-A connection 10 pole-center distance, 10 width across flats 7./1/17.5 kv, up to 1.5 ka, to 150 A AX14 55-B 10 pole-center distance, 10 width across flats 7./1/17.5 kv, up to 1.5 ka, to 500 A AX14 55-C 10 pole-center distance, 10 width across flats 7./1/17.5 kv, 40 ka, up to 150 A AX14 55-D 10 pole-center distance, 10 width across flats 4 kv, up to 5 ka, up to 150 A AX14 55-E 75 pole-center distance, 10 width across flats 4 kv, up to 5 ka, up to 150 A AX14 55-F 10 pole-center distance, 10 width across flats 4 kv, up to 5 ka, up to 500 A AX14 55-G 75 pole-center distance, 10 width across flats 4 kv, up to 5 ka, up to 500 A AX14 55-H Protection plate 150/160 pole-center distance For AE5 AX14 19-0A 10 pole-center distance For AE5 AX14 19-0B PG cable gland AX14 19-5A Siemens HG 11.0 01 41

Equipment Selection Accessories and spare parts SION Vacuum Circuit-Breakers AE5 and AE1 Position: 1 9 10 Designation Description Travel / feature Order No. Language code * Rated voltage for 50 / 60 Hz Rated short-circuit breaking current at 6 % DC component Pole-center distance Width across flats Rated normal current U r I SC I r kv ka A Withdrawable part 17.5 150 /160 0 (without cable harness) AX71 1-A 17.5 150 /160 0 (with cable harness) AX71 1-A 17.5 10 0 (without cable harness) AX71 1-B 17.5 10 0 (with cable harness) AX71 1-B 4 10 60 (without cable harness) AX71 1-C 4 10 60 (with cable harness) AX71 1-C 4 75 60 (without cable harness) AX71 1-D 4 75 60 (with cable harness) AX71 1-D 17.5 150 /160 180 (without cable harness) AX71 1-E 17.5 150 /160 180 (with cable harness) AX71 1-E 17.5 10 180 (without cable harness) AX71 1-F 17.5 10 180 (with cable harness) AX71 1-F Cartridge without earthing 17.5 1.5 150 75 150 AX71 11-5A switch 17.5 1.5 150 10 150 AX71 11-5B 17.5 1.5 10 75 150 AX71 11-5C 17.5 1.5 10 10 150 AX71 11-5D 17.5 1.5 10 10 > 150 AX71 11-5G 17.5 40 10 10 all I r AX71 11-5H 4 5 10 10 150 AX71 11-5E 4 5 75 10 150 AX71 11-5F 4 5 10 10 > 150 AX71 11-5J 4 5 75 10 > 150 AX71 11-5K Cartridge with earthing 17.5 1.5 150 75 150 with partition AX71 11-6A switch 17.5 1.5 150 10 150 with partition AX71 11-6B 17.5 1.5 10 75 150 without partition AX71 11-6C 17.5 1.5 10 10 150 without partition AX71 11-6D 17.5 1.5 10 10 > 150 without partition AX71 11-6G 17.5 40 10 10 all I r without partition AX71 11-6H 4 5 10 10 150 with partition AX71 11-6E 4 5 75 10 150 with partition AX71 11-6J 4 5 10 10 > 150 without partition AX71 11-6F 4 5 75 10 > 150 without partition AX71 11-6K *) The language of the rating plate is given in the table. The individual code has to be added to the order number. A German B English C French D Spanish E Italian F Russian G Portuguese H Polish Z Open with Z =... 4 Siemens HG 11.0 01

SION Vacuum Circuit-Breakers AE5 and AE1 Technical Data Contents Contents Page Technical Data 4 Electrical data, dimensions and weights Voltage level 7. kv 44 Operating cycle diagrams for 7. kv 50 Voltage level 1 kv 51 Operating cycle diagrams for 1 kv 57 Voltage level 17.5 kv 58 Operating cycle diagrams for 17.5 kv 61 Voltage level 4 kv 6 Operating cycle diagrams for 4 kv 6 Dimension drawings Voltage levels 7. to 4 kv 64 SION vacuum circuit-breaker on withdrawable part, with contacts R-HG11-80.tif Operating times and internal times 7 Short-circuit protection of motors 7 Consumption data of releases 7 Circuit diagrams Standard scheme for plug connector for AE1 74 Position switch for withdrawable part for AE1 74 Contact assignment for auxiliary switch for AE1 75 Additional equipment for AE1 75 Additional equipment: Releases for AE1 76 Standard scheme for plug connector for AE5 77 Position switch for withdrawable part for AE5 77 Contact assignment for auxiliary switch for AE5 78 Additional equipment for AE5 78 Additional equipment: Releases for AE5 79 R-HG11-75.tif SION vacuum circuit-breaker on withdrawable part, with contacts Siemens HG 11.0 01 4

Technical Data Electrical data, dimensions and weights for AE5 SION Vacuum Circuit-Breakers AE5 and AE1 7. kv 50 / 60 Hz Order No. Rated normal current Width across flats Pole-center distance Rated operating sequence: O min CO min CO O 0. s CO min CO O 0. s CO 15 s CO Rated duration of short-circuit Rated short-circuit breaking current DC component in % of the rated short-circuit breaking current Asyetrical breaking current Rated short-circuit making current (at 50 / 60 Hz) Rated lightning impulse Rated short-duration power-frequency Voltage drop U between connections (according to IEC 671-1 at DC 100 A) Minimum creepage distance, interrupter Minimum creepage distance, phase-to-earth Minimum clearance, phase-to-phase Minimum clearance, phase-to-earth Weight 1) (fixed-mounted circuit-breaker / withdrawable module) Detailed dimension drawing (has to be ordered) Operating cycle diagram no. (see page 50) I r t k I sc I ma U p U d A s ka % ka ka kv kv mv kg AE5 00-1... 800 05 150 16 50 17.9 40/4 60 0 9 45 9 19 49/ S_A7E_440010 1 AE5 00-... 150 05 150 16 50 17.9 40/4 60 0 9 45 9 19 49/ S_A7E_440010 1 AE5 00-1... 800 05 150 0 50.4 50/5 60 0 9 45 9 19 49/ S_A7E_440010 AE5 00-... 150 05 150 0 50.4 50/5 60 0 9 45 9 19 49/ S_A7E_440010 AE5 004-1... 800 05 150 5 50 8 6/65 60 0 9 45 9 19 49/ S_A7E_440010 a AE5 004-... 150 05 150 5 50 8 6/65 60 0 9 45 9 19 49/ S_A7E_440010 a AE5 01-1... 800 75 150 16 50 17.9 40/4 60 0 9 45 9 19 49/85 S_A7E_440011 1 AE5 01-... 150 75 150 16 50 17.9 40/4 60 0 9 45 9 19 49/85 S_A7E_440011 1 AE5 01-1... 800 75 150 0 50.4 50/5 60 0 9 45 9 19 49/85 S_A7E_440011 AE5 01-... 150 75 150 0 50.4 50/5 60 0 9 45 9 19 49/85 S_A7E_440011 AE5 014-1... 800 75 150 5 50 8 6/65 60 0 9 45 9 19 49/85 S_A7E_440011 a AE5 014-... 150 75 150 5 50 8 6/65 60 0 9 45 9 19 49/85 S_A7E_440011 a AE5 0-1... 800 10 150 16 50 17.9 40/4 60 0 9 45 9 19 49/85 S_A7E_44001 1 AE5 0-... 150 10 150 16 50 17.9 40/4 60 0 9 45 9 19 49/85 S_A7E_44001 1 AE5 0-1... 800 10 150 0 50.4 50/5 60 0 9 45 9 19 49/85 S_A7E_44001 AE5 0-... 150 10 150 0 50.4 50/5 60 0 9 45 9 19 49/85 S_A7E_44001 AE5 04-1... 800 10 150 5 50 8 6/65 60 0 9 45 9 19 49/85 S_A7E_44001 a AE5 04-... 150 10 150 5 50 8 6/65 60 0 9 45 9 19 49/85 S_A7E_44001 a Note: Dimension drawings from page 64 Possible with order suffix Z and order code F7 Standard information on rating plate Possible with order suffix Z and order code F8 1) The weight of the fixed-mounted circuit-breaker with withdrawable part increases by the values specified in the dimension drawing of the withdrawable part (page 68) 44 Siemens HG 11.0 01

SION Vacuum Circuit-Breakers AE5 and AE1 Technical Data Electrical data, dimensions and weights for AE5 7. kv 50 / 60 Hz Order No. Rated normal current Width across flats Pole-center distance Rated operating sequence: O min CO min CO O 0. s CO min CO O 0. s CO 15 s CO Rated duration of short-circuit Rated short-circuit breaking current DC component in % of the rated short-circuit breaking current Asyetrical breaking current Rated short-circuit making current (at 50 / 60 Hz) Rated lightning impulse Rated short-duration power-frequency Voltage drop U between connections (according to IEC 671-1 at DC 100 A) Minimum creepage distance, interrupter Minimum creepage distance, phase-to-earth Minimum clearance, phase-to-phase Minimum clearance, phase-to-earth Weight 1) (fixed-mounted circuit-breaker / withdrawable module) Detailed dimension drawing (has to be ordered) Operating cycle diagram no. (see page 50) I r t k I sc I ma U p U d A s ka % ka ka kv kv mv kg AE5 0-1... 800 05 160 16 50 17.9 40/4 60 0 9 45 9 19 49/ S_A7E_440016 1 AE5 0-... 150 05 160 16 50 17.9 40/4 60 0 9 45 9 19 49/ S_A7E_440016 1 AE5 0-1... 800 05 160 0 50.4 50/5 60 0 9 45 9 19 49/ S_A7E_440016 AE5 0-... 150 05 160 0 50.4 50/5 60 0 9 45 9 19 49/ S_A7E_440016 AE5 04-1... 800 05 160 5 50 8 6/65 60 0 9 45 9 19 49/ S_A7E_440016 a AE5 04-... 150 05 160 5 50 8 6/65 60 0 9 45 9 19 49/ S_A7E_440016 a AE5 04-1... 800 75 160 16 50 17.9 40/4 60 0 9 45 9 19 49/ S_A7E_440017 1 AE5 04-... 150 75 160 16 50 17.9 40/4 60 0 9 45 9 19 49/ S_A7E_440017 1 AE5 04-1... 800 75 160 0 50.4 50/5 60 0 9 45 9 19 49/ S_A7E_440017 AE5 04-... 150 75 160 0 50.4 50/5 60 0 9 45 9 19 49/ S_A7E_440017 AE5 044-1... 800 75 160 5 50 8 6/65 60 0 9 45 9 19 49/ S_A7E_440017 a AE5 044-... 150 75 160 5 50 8 6/65 60 0 9 45 9 19 49/ S_A7E_440017 a AE5 05-1... 800 10 160 16 50 17.9 40/4 60 0 9 45 9 19 49/ S_A7E_440018 1 AE5 05-... 150 10 160 16 50 17.9 40/4 60 0 9 45 9 19 49/ S_A7E_440018 1 AE5 05-1... 800 10 160 0 50.4 50/5 60 0 9 45 9 19 49/ S_A7E_440018 AE5 05-... 150 10 160 0 50.4 50/5 60 0 9 45 9 19 49/ S_A7E_440018 AE5 054-1... 800 10 160 5 50 8 6/65 60 0 9 45 9 19 49/ S_A7E_440018 a AE5 054-... 150 10 160 5 50 8 6/65 60 0 9 45 9 19 49/ S_A7E_440018 a AE5 06-1... 800 05 10 16 50 17.9 40/4 60 0 9 45 9 19 51.5/91.5 S_A7E_4400 1 AE5 06-... 150 05 10 16 50 17.9 40/4 60 0 9 45 9 19 51.5/91.5 S_A7E_4400 1 Possible with order suffix Z and order code F7 1) The weight of the fixed-mounted circuit-breaker with Standard information on rating plate withdrawable part increases by the values specified in the Possible with order suffix Z and order code F8 dimension drawing of the withdrawable part (page 68) Siemens HG 11.0 01 45

Technical Data Electrical data, dimensions and weights for AE5 SION Vacuum Circuit-Breakers AE5 and AE1 7. kv 50 / 60 Hz Order No. Rated normal current Width across flats Pole-center distance Rated operating sequence: O min CO min CO O 0. s CO min CO O 0. s CO 15 s CO Rated duration of short-circuit Rated short-circuit breaking current DC component in % of the rated short-circuit breaking current Asyetrical breaking current Rated short-circuit making current (at 50 / 60 Hz) Rated lightning impulse Rated short-duration power-frequency Voltage drop U between connections (according to IEC 671-1 at DC 100 A) Minimum creepage distance, interrupter Minimum creepage distance, phase-to-earth Minimum clearance, phase-to-phase Minimum clearance, phase-to-earth Weight 1) (fixed-mounted circuit-breaker / withdrawable module) Detailed dimension drawing (has to be ordered) Operating cycle diagram no. (see page 50) I r t k I sc I ma U p U d A s ka % ka ka kv kv mv kg AE5 06-1... 800 05 10 0 50.4 50/5 60 0 9 45 9 19 51.5/ S_A7E_4400 AE5 06-... 150 05 10 0 50.4 50/5 60 0 9 45 9 19 51.5/ S_A7E_4400 AE5 064-1... 800 05 10 5 50 8 6/65 60 0 9 45 9 19 51.5/ S_A7E_4400 a AE5 064-... 150 05 10 5 50 8 6/65 60 0 9 45 9 19 51.5/ S_A7E_4400 a AE5 07-1... 800 75 10 16 50 17.9 40/4 60 0 9 45 9 19 51.5/91.5 S_A7E_4400 1 AE5 07-... 150 75 10 16 50 17.9 40/4 60 0 9 45 9 19 51.5/91.5 S_A7E_4400 1 AE5 07-1... 800 75 10 0 50.4 50/5 60 0 9 45 9 19 51.5/91.5 S_A7E_4400 AE5 07-... 150 75 10 0 50.4 50/5 60 0 9 45 9 19 51.5/91.5 S_A7E_4400 AE5 074-1... 800 75 10 5 50 8 6/65 60 0 9 45 9 19 51.5/91.5 S_A7E_4400 a AE5 074-... 150 75 10 5 50 8 6/65 60 0 9 45 9 19 51.5/91.5 S_A7E_4400 a AE5 08-1... 800 10 10 16 50 17.9 40/4 60 0 9 45 9 19 51.5/91.5 S_A7E_44004 1 AE5 08-... 150 10 10 16 50 17.9 40/4 60 0 9 45 9 19 51.5/91.5 S_A7E_44004 1 AE5 08-1... 800 10 10 0 50.4 50/5 60 0 9 45 9 19 51.5/91.5 S_A7E_44004 AE5 08-... 150 10 10 0 50.4 50/5 60 0 9 45 9 19 51.5/91.5 S_A7E_44004 AE5 084-1... 800 10 10 5 50 8 6/65 60 0 9 45 9 19 51.5/91.5 S_A7E_44004 a AE5 084-... 150 10 10 5 50 8 6/65 60 0 9 45 9 19 51.5/91.5 S_A7E_44004 a Possible with order suffix Z and order code F7 1) The weight of the fixed-mounted circuit-breaker with Standard information on rating plate withdrawable part increases by the values specified in the Possible with order suffix Z and order code F8 dimension drawing of the withdrawable part (page 68) 46 Siemens HG 11.0 01

SION Vacuum Circuit-Breakers AE5 and AE1 Technical Data Electrical data, dimensions and weights for AE1 7. kv 50 / 60 Hz Order No. Rated normal current Width across flats Pole-center distance Rated operating sequence: O min CO min CO O 0. s CO min CO O 0. s CO 15 s CO Rated duration of short-circuit Rated short-circuit breaking current DC component in % of the rated short-circuit breaking current Asyetrical breaking current Rated short-circuit making current (at 50 / 60 Hz) Rated lightning impulse Rated short-duration power-frequency Voltage drop U between connections (according to IEC 671-1 at DC 100 A) Minimum creepage distance, interrupter Minimum creepage distance, phase-to-earth Minimum clearance, phase-to-phase Minimum clearance, phase-to-earth Weight 1) (fixed-mounted circuit-breaker / withdrawable module) Detailed dimension drawing (has to be ordered) Operating cycle diagram no. (see page 50) I r t k I SC I ma U p U d A s ka % ka ka kv kv mv kg AE1 00-1... 800 05 150 16 6 17.9 40/4 60 0.1 19 140 105 75 67/ S_A7E_440010 1 AE1 00-... 150 05 150 16 6 17.9 40/4 60 0.1 19 140 105 75 67/ S_A7E_440010 1 AE1 00-1... 800 05 150 0 6.4 50/5 60 0.1 19 140 105 75 67/ S_A7E_440010 AE1 00-... 150 05 150 0 6.4 50/5 60 0.1 19 140 105 75 67/ S_A7E_440010 AE1 004-1... 800 05 150 5 6 8 6/65 60 0.1 19 140 105 75 67/ S_A7E_440010 a AE1 004-... 150 05 150 5 6 8 6/65 60 0.1 19 140 105 75 67/ S_A7E_440010 a AE1 005-1... 800 05 150 1.5 6 5.4 80/8 60 0.1 19 140 105 75 80/ S_A7E_440010 4 AE1 005-... 150 05 150 1.5 6 5.4 80/8 60 0.1 19 140 105 75 80/ S_A7E_440010 4 AE1 01-1... 800 75 150 16 6 17.9 40/4 60 0.1 19 140 105 75 67/10 S_A7E_440011 1 AE1 01-... 150 75 150 16 6 17.9 40/4 60 0.1 19 140 105 75 67/10 S_A7E_440011 1 AE1 01-1... 800 75 150 0 6.4 50/5 60 0.1 19 140 105 75 67/10 S_A7E_440011 AE1 01-... 150 75 150 0 6.4 50/5 60 0.1 19 140 105 75 67/10 S_A7E_440011 AE1 014-1... 800 75 150 5 6 8 6/65 60 0.1 19 140 105 75 67/10 S_A7E_440011 a AE1 014-... 150 75 150 5 6 8 6/65 60 0.1 19 140 105 75 67/10 S_A7E_440011 a AE1 015-1... 800 75 150 1.5 6 5.4 80/8 60 0.1 19 140 105 75 80/10 S_A7E_440011 4 AE1 015-... 150 75 150 1.5 6 5.4 80/8 60 0.1 19 140 105 75 80/10 S_A7E_440011 4 AE1 0-1... 800 10 150 16 6 17.9 40/4 60 0.1 19 140 100 75 67/10 S_A7E_44001 1 AE1 0-... 150 10 150 16 6 17.9 40/4 60 0.1 19 140 100 75 67/10 S_A7E_44001 1 AE1 0-1... 800 10 150 0 6.4 50/5 60 0.1 19 140 100 75 67/10 S_A7E_44001 AE1 0-... 150 10 150 0 6.4 50/5 60 0.1 19 140 100 75 67/10 S_A7E_44001 AE1 04-1... 800 10 150 5 6 8 6/65 60 0.1 19 140 100 75 67/10 S_A7E_44001 a AE1 04-... 150 10 150 5 6 8 6/65 60 0.1 19 140 100 75 67/10 S_A7E_44001 a AE1 05-1... 800 10 150 1.5 6 5.4 80/8 60 0.1 19 140 100 75 80/10 S_A7E_44001 4 AE1 05-... 150 10 150 1.5 6 5.4 80/8 60 0.1 19 140 100 75 80/10 S_A7E_44001 4 Note: Dimension drawings from page 64 Possible with order suffix Z and order code F7 Standard information on rating plate Possible with order suffix Z and order code F8 1) The weight of the fixed-mounted circuit-breaker with withdrawable part increases by the values specified in the dimension drawing of the withdrawable part (page 69) Siemens HG 11.0 01 47

Technical Data Electrical data, dimensions and weights for AE1 SION Vacuum Circuit-Breakers AE5 and AE1 7. kv 50 / 60 Hz Order No. Rated normal current Width across flats Pole-center distance Rated operating sequence: O min CO min CO O 0. s CO min CO O 0. s CO 15 s CO Rated duration of short-circuit Rated short-circuit breaking current DC component in % of the rated short-circuit breaking current Asyetrical breaking current Rated short-circuit making current (at 50 / 60 Hz) Rated lightning impulse Rated short-duration power-frequency Voltage drop U between connections (according to IEC 671-1 at DC 100 A) Minimum creepage distance, interrupter Minimum creepage distance, phase-to-earth Minimum clearance, phase-to-phase Minimum clearance, phase-to-earth Weight 1) (fixed-mounted circuit-breaker / withdrawable module) Detailed dimension drawing (has to be ordered) Operating cycle diagram no. (see page 50) I r t k I SC I ma U p U d A s ka % ka ka kv kv mv kg AE1 0-1... 800 05 160 16 6 17.9 40/4 60 0.1 19 140 115 75 67/ S_A7E_440016 1 AE1 0-... 150 05 160 16 6 17.9 40/4 60 0.1 19 140 115 75 67/ S_A7E_440016 1 AE1 0-1... 800 05 160 0 6.4 50/5 60 0.1 19 140 115 75 67/ S_A7E_440016 AE1 0-... 150 05 160 0 6.4 50/5 60 0.1 19 140 115 75 67/ S_A7E_440016 AE1 04-1... 800 05 160 5 6 8 6/65 60 0.1 19 140 115 75 67/ S_A7E_440016 a AE1 04-... 150 05 160 5 6 8 6/65 60 0.1 19 140 115 75 67/ S_A7E_440016 a AE1 05-1... 800 05 160 1.5 6 5.4 80/8 60 0.1 19 140 115 75 80/ S_A7E_440016 4 AE1 05-... 150 05 160 1.5 6 5.4 80/8 60 0.1 19 140 115 75 80/ S_A7E_440016 4 AE1 04-1... 800 75 160 16 6 17.9 40/4 60 0.1 19 140 115 75 67/ S_A7E_440017 1 AE1 04-... 150 75 160 16 6 17.9 40/4 60 0.1 19 140 115 75 67/ S_A7E_440017 1 AE1 04-1... 800 75 160 0 6.4 50/5 60 0.1 19 140 115 75 67/ S_A7E_440017 AE1 04-... 150 75 160 0 6.4 50/5 60 0.1 19 140 115 75 67/ S_A7E_440017 AE1 044-1... 800 75 160 5 6 8 6/65 60 0.1 19 140 115 75 67/ S_A7E_440017 a AE1 044-... 150 75 160 5 6 8 6/65 60 0.1 19 140 115 75 67/ S_A7E_440017 a AE1 045-1... 800 75 160 1.5 6 5.4 80/8 60 0.1 19 140 115 75 80/ S_A7E_440017 4 AE1 045-... 150 75 160 1.5 6 5.4 80/8 60 0.1 19 140 115 75 80/ S_A7E_440017 4 AE1 05-1... 800 10 160 16 6 17.9 40/4 60 0.1 19 140 110 75 67 S_A7E_440018 1 AE1 05-... 150 10 160 16 6 17.9 40/4 60 0.1 19 140 110 75 67 S_A7E_440018 1 AE1 05-1... 800 10 160 0 6.4 50/5 60 0.1 19 140 110 75 67 S_A7E_440018 AE1 05-... 150 10 160 0 6.4 50/5 60 0.1 19 140 110 75 67 S_A7E_440018 AE1 054-1... 800 10 160 5 6 8 6/65 60 0.1 19 140 110 75 67 S_A7E_440018 a AE1 054-... 150 10 160 5 6 8 6/65 60 0.1 19 140 110 75 67 S_A7E_440018 a AE1 055-1... 800 10 160 1.5 6 5.4 80/8 60 0.1 19 140 110 75 80 S_A7E_440018 4 AE1 055-... 150 10 160 1.5 6 5.4 80/8 60 0.1 19 140 110 75 80 S_A7E_440018 4 AE1 06-1... 800 05 10 16 6 17.9 40/4 60 0.1 19 140 165 75 67/ S_A7E_4400 1 AE1 06-... 150 05 10 16 6 17.9 40/4 60 0.1 19 140 165 75 67/ S_A7E_4400 1 Possible with order suffix Z and order code F7 Standard information on rating plate Possible with order suffix Z and order code F8 1) The weight of the fixed-mounted circuit-breaker with withdrawable part increases by the values specified in the dimension drawing of the withdrawable part (page 68) 48 Siemens HG 11.0 01

SION Vacuum Circuit-Breakers AE5 and AE1 Technical Data Electrical data, dimensions and weights for AE1 7. kv 50 / 60 Hz Order No. Rated normal current Width across flats Pole-center distance Rated operating sequence: O min CO min CO O 0. s CO min CO O 0. s CO 15 s CO Rated duration of short-circuit Rated short-circuit breaking current DC component in % of the rated short-circuit breaking current Asyetrical breaking current Rated short-circuit making current (at 50 / 60 Hz) Rated lightning impulse Rated short-duration power-frequency Voltage drop U between connections (according to IEC 671-1 at DC 100 A) Minimum creepage distance, interrupter Minimum creepage distance, phase-to-earth Minimum clearance, phase-to-phase Minimum clearance, phase-to-earth Weight 1) (fixed-mounted circuit-breaker / withdrawable module) Detailed dimension drawing (has to be ordered) Operating cycle diagram no. (see page 50) I r t k I SC I ma U p U d A s ka % ka ka kv kv mv kg AE1 06-1... 800 05 10 0 6.4 50/5 60 0.1 19 140 165 75 67/ S_A7E_4400 AE1 06-... 150 05 10 0 6.4 50/5 60 0.1 19 140 165 75 67/ S_A7E_4400 AE1 064-1... 800 05 10 5 6 8 6/65 60 0.1 19 140 165 75 67/ S_A7E_4400 a AE1 064-... 150 05 10 5 6 8 6/65 60 0.1 19 140 165 75 67/ S_A7E_4400 a AE1 065-1... 800 05 10 1.5 6 5.4 80/8 60 0.1 19 140 165 75 90/ S_A7E_4400 4 AE1 065-... 150 05 10 1.5 6 5.4 80/8 60 0.1 19 140 165 75 90/ S_A7E_4400 4 AE1 07-1... 800 75 10 16 6 17.9 40/4 60 0.1 19 140 165 75 67/10 S_A7E_4400 1 AE1 07-... 150 75 10 16 6 17.9 40/4 60 0.1 19 140 165 75 67/10 S_A7E_4400 1 AE1 07-1... 800 75 10 0 6.4 50/5 60 0.1 19 140 165 75 67/10 S_A7E_4400 AE1 07-... 150 75 10 0 6.4 50/5 60 0.1 19 140 165 75 67/10 S_A7E_4400 AE1 074-1... 800 75 10 5 6 8 6/65 60 0.1 19 140 165 75 67/10 S_A7E_4400 a AE1 074-... 150 75 10 5 6 8 6/65 60 0.1 19 140 165 75 67/10 S_A7E_4400 a AE1 075-1... 800 75 10 1.5 6 5.4 80/8 60 0.1 19 140 165 75 90/10 S_A7E_4400 4 AE1 075-... 150 75 10 1.5 6 5.4 80/8 60 0.1 19 140 165 75 90/10 S_A7E_4400 4 AE1 08-1... 800 10 10 16 6 17.9 40/4 60 0.1 19 140 160 75 67/10 S_A7E_44004 1 AE1 08-... 150 10 10 16 6 17.9 40/4 60 0.1 19 140 160 75 67/10 S_A7E_44004 1 AE1 08-1... 800 10 10 0 6.4 50/5 60 0.1 19 140 160 75 67/10 S_A7E_44004 AE1 08-... 150 10 10 0 6.4 50/5 60 0.1 19 140 160 75 67/10 S_A7E_44004 AE1 084-1... 800 10 10 5 6 8 6/65 60 0.1 19 140 160 75 67/10 S_A7E_44004 a AE1 084-... 150 10 10 5 6 8 6/65 60 0.1 19 140 160 75 67/10 S_A7E_44004 a AE1 084-4... 000 10 10 5 6 8 6/65 60 0 1.5 19 65 10 10 110/150 S_A7E_44008 AE1 085-1... 800 10 10 1.5 6 5.4 80/8 60 0.1 19 140 160 75 90/10 S_A7E_44004 4 AE1 085-... 150 10 10 1.5 6 5.4 80/8 60 0.1 19 140 160 75 90/10 S_A7E_44004 4 AE1 085-4... 000 10 10 1.5 6 5.4 80/8 60 0 1.5 19 65 10 10 110/150 S_A7E_44008 4 AE1 085-6... 500 10 10 1.5 6 5.4 80/8 60 0 1.5 19 65 10 10 110/150 S_A7E_44008 4 Possible with order suffix Z and order code F7 Standard information on rating plate Possible with order suffix Z and order code F8 1) The weight of the fixed-mounted circuit-breaker with withdrawable part increases by the values specified in the dimension drawing of the withdrawable part (page 68) Siemens HG 11.0 01 49

Technical Data Electrical data, dimensions and weights for AE1 SION Vacuum Circuit-Breakers AE5 and AE1 7. kv 50 / 60 Hz Order No. Rated normal current Width across flats Pole-center distance Rated operating sequence: O min CO min CO O 0. s CO min CO O 0. s CO 15 s CO Rated duration of short-circuit Rated short-circuit breaking current DC component in % of the rated short-circuit breaking current Asyetrical breaking current Rated short-circuit making current (at 50 / 60 Hz) Rated lightning impulse Rated short-duration power-frequency Voltage drop U between connections (according to IEC 671-1 at DC 100 A) Minimum creepage distance, interrupter Minimum creepage distance, phase-to-earth Minimum clearance, phase-to-phase Minimum clearance, phase-to-earth Weight 1) (fixed-mounted circuit-breaker / withdrawable module) Detailed dimension drawing (has to be ordered) Operating cycle diagram no. (see below) I r t k I SC I ma U p U d A s ka % ka ka kv kv mv kg AE1 086-... 150 10 10 40 6 44.9 100/104 60 0 1.7 145 155 169 140 10/160 S_A7E_440070 5 AE1 086-4... 000 10 10 40 6 44.9 100/104 60 0 1.0 145 49 149 140 160/10 S_A7E_440071 5 AE1 086-6... 500 10 10 40 6 44.9 100/104 60 0 1.0 145 49 149 140 160/10 S_A7E_440071 5 AE1 086-7... 150 10 10 40 6 44.9 100/104 60 0 1.0 145 49 149 140 160/10 S_A7E_440071 5 Possible with order suffix Z and order code F7 Standard information on rating plate Possible with order suffix Z and order code F8 1) The weight of the fixed-mounted circuit-breaker with withdrawable part increases by the values specified in the dimension drawing of the withdrawable part (page 68) Operating cycle diagrams for 7. kv Operating cycles No. 0 000 10 000 5 000 000 1 000 500 00 100 70 46 0 0 1 a 10 0.5 1 5 10 16 0 5 ka 50 Breaking current (r.m.s. value) HG11-540c_en eps The permissible number of electrical operating cycles is shown as a function of the breaking current (r.m.s. value). All SION vacuum circuit-breakers fulfil the endurance classes E, M and C according to IEC 671-100. The curve shape beyond the parameters defined in IEC 671-100 is based on average experience data. The number of operating cycles that can actually be reached can be different depending on the respective application. Operating cycles No. 0 000 10 000 5 000 000 1 000 500 00 100 80 50 0 4 5 10 0.5 1 5 10 ka 0 5 40 50 1.5 Breaking current (r.m.s. value) HG11-59c_en eps 50 Siemens HG 11.0 01

SION Vacuum Circuit-Breakers AE5 and AE1 Technical Data Electrical data, dimensions and weights for AE5 1 kv 50 / 60 Hz Order No. Rated normal current Width across flats Pole-center distance Rated operating sequence: O min CO min CO O 0. s CO min CO O 0. s CO 15 s CO Rated duration of short-circuit Rated short-circuit breaking current DC component in % of the rated short-circuit breaking current Asyetrical breaking current Rated short-circuit making current (at 50 / 60 Hz) Rated lightning impulse Rated short-duration power-frequency Voltage drop U between connections (according to IEC 671-1 at DC 100 A) Minimum creepage distance, interrupter Minimum creepage distance, phase-to-earth Minimum clearance, phase-to-phase Minimum clearance, phase-to-earth Weight 1) (fixed-mounted circuit-breaker / withdrawable module) Detailed dimension drawing (has to be ordered) Operating cycle diagram no. (see page 57) I r t k I sc I ma U p U d A s ka % ka ka kv kv mv kg AE5 10-1... 800 05 150 16 50 17.9 40/4 75 8 9 45 9 19 49/ S_A7E_440010 6 AE5 10-... 150 05 150 16 50 17.9 40/4 75 8 9 45 9 19 49/ S_A7E_440010 6 AE5 10-1... 800 05 150 0 50.4 50/5 75 8 9 45 9 19 49/ S_A7E_440010 7 AE5 10-... 150 05 150 0 50.4 50/5 75 8 9 45 9 19 49/ S_A7E_440010 7 AE5 104-1... 800 05 150 5 50 8 6/65 75 8 9 45 9 19 49/ S_A7E_440010 8a AE5 104-... 150 05 150 5 50 8 6/65 75 8 9 45 9 19 49/ S_A7E_440010 8a AE5 11-1... 800 75 150 16 50 17.9 40/4 75 8 9 45 9 19 49/85 S_A7E_440011 6 AE5 11-... 150 75 150 16 50 17.9 40/4 75 8 9 45 9 19 49/85 S_A7E_440011 6 AE5 11-1... 800 75 150 0 50.4 50/5 75 8 9 45 9 19 49/85 S_A7E_440011 7 AE5 11-... 150 75 150 0 50.4 50/5 75 8 9 45 9 19 49/85 S_A7E_440011 7 AE5 114-1... 800 75 150 5 50 8 6/65 75 8 9 45 9 19 49/85 S_A7E_440011 8a AE5 114-... 150 75 150 5 50 8 6/65 75 8 9 45 9 19 49/85 S_A7E_440011 8a AE5 1-1... 800 10 150 16 50 17.9 40/4 75 8 9 45 9 19 49/85 S_A7E_44001 6 AE5 1-... 150 10 150 16 50 17.9 40/4 75 8 9 45 9 19 49/85 S_A7E_44001 6 AE5 1-1... 800 10 150 0 50.4 50/5 75 8 9 45 9 19 49/85 S_A7E_44001 7 AE5 1-... 150 10 150 0 50.4 50/5 75 8 9 45 9 19 49/85 S_A7E_44001 7 AE5 14-1... 800 10 150 5 50 8 6/65 75 8 9 45 9 19 49/85 S_A7E_44001 8a AE5 14-... 150 10 150 5 50 8 6/65 75 8 9 45 9 19 49/85 S_A7E_44001 8a AE5 1-1... 800 05 160 16 50 17.9 40/4 75 8 9 45 9 19 49/ S_A7E_440016 6 AE5 1-... 150 05 160 16 50 17.9 40/4 75 8 9 45 9 19 49/ S_A7E_440016 6 Possible with order suffix Z and order code F7 Standard information on rating plate Possible with order suffix Z and order code F8 1) The weight of the fixed-mounted circuit-breaker with withdrawable part increases by the values specified in the dimension drawing of the withdrawable part (page 68) Siemens HG 11.0 01 51

Technical Data Electrical data, dimensions and weights for AE5 SION Vacuum Circuit-Breakers AE5 and AE1 1 kv 50 / 60 Hz Order No. Rated normal current Width across flats Pole-center distance Rated operating sequence: O min CO min CO O 0. s CO min CO O 0. s CO 15 s CO Rated duration of short-circuit Rated short-circuit breaking current DC component in % of the rated short-circuit breaking current Asyetrical breaking current Rated short-circuit making current (at 50 / 60 Hz) Rated lightning impulse Rated short-duration power-frequency Voltage drop U between connections (according to IEC 671-1 at DC 100 A) Minimum creepage distance, interrupter Minimum creepage distance, phase-to-earth Minimum clearance, phase-to-phase Minimum clearance, phase-to-earth Weight 1) (fixed-mounted circuit-breaker / withdrawable module) Detailed dimension drawing (has to be ordered) Operating cycle diagram no. (see page 57) I r t k I sc I ma U p U d A s ka % ka ka kv kv mv kg AE5 1-1... 800 05 160 0 50.4 50/5 75 8 9 45 9 19 49/ S_A7E_440016 7 AE5 1-... 150 05 160 0 50.4 50/5 75 8 9 45 9 19 49/ S_A7E_440016 7 AE5 14-1... 800 05 160 5 50 8 6/65 75 8 9 45 9 19 49/ S_A7E_440016 8a AE5 14-... 150 05 160 5 50 8 6/65 75 8 9 45 9 19 49/ S_A7E_440016 8a AE5 14-1... 800 75 160 16 50 17.9 40/4 75 8 9 45 9 19 49/ S_A7E_440017 6 AE5 14-... 150 75 160 16 50 17.9 40/4 75 8 9 45 9 19 49/ S_A7E_440017 6 AE5 14-1... 800 75 160 0 50.4 50/5 75 8 9 45 9 19 49/ S_A7E_440017 7 AE5 14-... 150 75 160 0 50.4 50/5 75 8 9 45 9 19 49/ S_A7E_440017 7 AE5 144-1... 800 75 160 5 50 8 6/65 75 8 9 45 9 19 49/ S_A7E_440017 8a AE5 144-... 150 75 160 5 50 8 6/65 75 8 9 45 9 19 49/ S_A7E_440017 8a AE5 15-1... 800 10 160 16 50 17.9 40/4 75 8 9 45 9 19 49/ S_A7E_440018 6 AE5 15-... 150 10 160 16 50 17.9 40/4 75 8 9 45 9 19 49/ S_A7E_440018 6 AE5 15-1... 800 10 160 0 50.4 50/5 75 8 9 45 9 19 49/ S_A7E_440018 7 AE5 15-... 150 10 160 0 50.4 50/5 75 8 9 45 9 19 49/ S_A7E_440018 7 AE5 154-1... 800 10 160 5 50 8 6/65 75 8 9 45 9 19 49/ S_A7E_440018 8a AE5 154-... 150 10 160 5 50 8 6/65 75 8 9 45 9 19 49/ S_A7E_440018 8a AE5 16-1... 800 05 10 16 50 17.9 40/4 75 8 9 45 9 19 51.5/ S_A7E_4400 6 AE5 16-... 150 05 10 16 50 17.9 40/4 75 8 9 45 9 19 51.5/ S_A7E_4400 6 AE5 16-1... 800 05 10 0 50.4 50/5 75 8 9 45 9 19 51.5/ S_A7E_4400 7 AE5 16-... 150 05 10 0 50.4 50/5 75 8 9 45 9 19 51.5/ S_A7E_4400 7 Possible with order suffix Z and order code F7 Standard information on rating plate Possible with order suffix Z and order code F8 1) The weight of the fixed-mounted circuit-breaker with withdrawable part increases by the values specified in the dimension drawing of the withdrawable part (page 68) 5 Siemens HG 11.0 01

SION Vacuum Circuit-Breakers AE5 and AE1 Technical Data Electrical data, dimensions and weights for AE5 1 kv 50 / 60 Hz Order No. Rated normal current Width across flats Pole-center distance Rated operating sequence: O min CO min CO O 0. s CO min CO O 0. s CO 15 s CO Rated duration of short-circuit Rated short-circuit breaking current DC component in % of the rated short-circuit breaking current Asyetrical breaking current Rated short-circuit making current (at 50 / 60 Hz) Rated lightning impulse Rated short-duration power-frequency Voltage drop U between connections (according to IEC 671-1 at DC 100 A) Minimum creepage distance, interrupter Minimum creepage distance, phase-to-earth Minimum clearance, phase-to-phase Minimum clearance, phase-to-earth Weight 1) (fixed-mounted circuit-breaker / withdrawable module) Detailed dimension drawing (has to be ordered) Operating cycle diagram no. (see page 57) I r t k I sc I ma U p U d A s ka % ka ka kv kv mv kg AE5 164-1... 800 05 10 5 50 8 6/65 75 8 9 45 9 19 49/ S_A7E_4400 8a AE5 164-... 150 05 10 5 50 8 6/65 75 8 9 45 9 19 49/ S_A7E_4400 8a AE5 17-1... 800 75 10 16 50 17.9 40/4 75 8 9 45 9 19 51.5/91.5 S_A7E_4400 6 AE5 17-... 150 75 10 16 50 17.9 40/4 75 8 9 45 9 19 51.5/91.5 S_A7E_4400 6 AE5 17-1... 800 75 10 0 50.4 50/5 75 8 9 45 9 19 51.5/91.5 S_A7E_4400 7 AE5 17-... 150 75 10 0 50.4 50/5 75 8 9 45 9 19 51.5/91.5 S_A7E_4400 7 AE5 174-1... 800 75 10 5 50 8 6/65 75 8 9 45 9 19 51.5/91.5 S_A7E_4400 8a AE5 174-... 150 75 10 5 50 8 6/65 75 8 9 45 9 19 51.5/91.5 S_A7E_4400 8a AE5 18-1... 800 10 10 16 50 17.9 40/4 75 8 9 45 9 19 51.5/91.5 S_A7E_44004 6 AE5 18-... 150 10 10 16 50 17.9 40/4 75 8 9 45 9 19 51.5/91.5 S_A7E_44004 6 AE5 18-1... 800 10 10 0 50.4 50/5 75 8 9 45 9 19 51.5/91.5 S_A7E_44004 7 AE5 18-... 150 10 10 0 50.4 50/5 75 8 9 45 9 19 51.5/91.5 S_A7E_44004 7 AE5 184-1... 800 10 10 5 50 8 6/65 75 8 9 45 9 19 51.5/91.5 S_A7E_44004 8a AE5 184-... 150 10 10 5 50 8 6/65 75 8 9 45 9 19 51.5/91.5 S_A7E_44004 8a AE5 554-1... 800 75 160 5 50 44.9 6/65 75 8 9 45 9 19 49/ S_A7E_44004 8a AE5 554-... 150 75 160 5 50 44.9 6/65 75 8 9 45 9 19 49/ S_A7E_44004 8a Possible with order suffix Z and order code F7 1) The weight of the fixed-mounted circuit-breaker with Standard information on rating plate withdrawable part increases by the values specified in the Possible with order suffix Z and order code F8 dimension drawing of the withdrawable part (page 68) Siemens HG 11.0 01 5

Technical Data Electrical data, dimensions and weights for AE1 SION Vacuum Circuit-Breakers AE5 and AE1 1 kv 50 / 60 Hz Order No. Rated normal current Width across flats Pole-center distance Rated operating sequence: O min CO min CO O 0. s CO min CO O 0. s CO 15 s CO Rated duration of short-circuit Rated short-circuit breaking current DC component in % of the rated short-circuit breaking current Asyetrical breaking current Rated short-circuit making current (at 50 / 60 Hz) Rated lightning impulse Rated short-duration power-frequency Voltage drop U between connections (according to IEC 671-1 at DC 100 A) Minimum creepage distance, interrupter Minimum creepage distance, phase-to-earth Minimum clearance, phase-to-phase Minimum clearance, phase-to-earth Weight 1) (fixed-mounted circuit-breaker / withdrawable module) Detailed dimension drawing (has to be ordered) Operating cycle diagram no. (see page 57) I r t k I SC I ma U p U d A s ka % ka ka kv kv mv kg AE1 10-1... 800 05 150 16 6 17.9 40/4 75 8.1 19 140 105 75 67/ S_A7E_440010 6 AE1 10-... 150 05 150 16 6 17.9 40/4 75 8.1 19 140 105 75 67/ S_A7E_440010 6 AE1 10-1... 800 05 150 0 6.4 50/5 75 8.1 19 140 105 75 67/ S_A7E_440010 7 AE1 10-... 150 05 150 0 6.4 50/5 75 8.1 19 140 105 75 67/ S_A7E_440010 7 AE1 104-1... 800 05 150 5 6 8 6/65 75 8.1 19 140 105 75 67/ S_A7E_440010 8a AE1 104-... 150 05 150 5 6 8 6/65 75 8.1 19 140 105 75 67/ S_A7E_440010 8a AE1 105-1... 800 05 150 1.5 6 5.4 80/8 75 8.1 19 140 105 75 80/ S_A7E_440010 9 AE1 105-... 150 05 150 1.5 6 5.4 80/8 75 8.1 19 140 105 75 80/ S_A7E_440010 9 AE1 11-1... 800 75 150 16 6 17.9 40/4 75 8.1 19 140 105 75 67/10 S_A7E_440011 6 AE1 11-... 150 75 150 16 6 17.9 40/4 75 8.1 19 140 105 75 67/10 S_A7E_440011 6 AE1 11-1... 800 75 150 0 6.4 50/5 75 8.1 19 140 105 75 67/10 S_A7E_440011 7 AE1 11-... 150 75 150 0 6.4 50/5 75 8.1 19 140 105 75 67/10 S_A7E_440011 7 AE1 114-1... 800 75 150 5 6 8 6/65 75 8.1 19 140 105 75 67/10 S_A7E_440011 8a AE1 114-... 150 75 150 5 6 8 6/65 75 8.1 19 140 105 75 67/10 S_A7E_440011 8a AE1 115-1... 800 75 150 1.5 6 5.4 80/8 75 8.1 19 140 105 75 80/10 S_A7E_440011 9 AE1 115-... 150 75 150 1.5 6 5.4 80/8 75 8.1 19 140 105 75 80/10 S_A7E_440011 9 AE1 1-1... 800 10 150 16 6 17.9 40/4 75 8.1 19 140 100 75 67/10 S_A7E_44001 6 AE1 1-... 150 10 150 16 6 17.9 40/4 75 8.1 19 140 100 75 67/10 S_A7E_44001 6 AE1 1-1... 800 10 150 0 6.4 50/5 75 8.1 19 140 100 75 67/10 S_A7E_44001 7 AE1 1-... 150 10 150 0 6.4 50/5 75 8.1 19 140 100 75 67/10 S_A7E_44001 7 AE1 14-1... 800 10 150 5 6 8 6/65 75 8.1 19 140 100 75 67/10 S_A7E_44001 8a AE1 14-... 150 10 150 5 6 8 6/65 75 8.1 19 140 100 75 67/10 S_A7E_44001 8a AE1 15-1... 800 10 150 1.5 6 5.4 80/8 75 8.1 19 140 100 75 80/10 S_A7E_44001 9 AE1 15-... 150 10 150 1.5 6 5.4 80/8 75 8.1 19 140 100 75 80/10 S_A7E_44001 9 AE1 1-1... 800 05 160 16 6 17.9 40/4 75 8.1 19 140 115 75 67/ S_A7E_440016 6 AE1 1-... 150 05 160 16 6 17.9 40/4 75 8.1 19 140 115 75 67/ S_A7E_440016 6 Possible with order suffix Z and order code F7 Standard information on rating plate Possible with order suffix Z and order code F8 Rated operating sequence possible up to I SC = 1.5 ka 1) The weight of the fixed-mounted circuit-breaker with withdrawable part increases by the values specified in the dimension drawing of the withdrawable part (page 68) 54 Siemens HG 11.0 01

SION Vacuum Circuit-Breakers AE5 and AE1 Technical Data Electrical data, dimensions and weights for AE1 1 kv 50 / 60 Hz Order No. Rated normal current Width across flats Pole-center distance Rated operating sequence: O min CO min CO O 0. s CO min CO O 0. s CO 15 s CO Rated duration of short-circuit Rated short-circuit breaking current DC component in % of the rated short-circuit breaking current Asyetrical breaking current Rated short-circuit making current (at 50 / 60 Hz) Rated lightning impulse Rated short-duration power-frequency Voltage drop U between connections (according to IEC 671-1 at DC 100 A) Minimum creepage distance, interrupter Minimum creepage distance, phase-to-earth Minimum clearance, phase-to-phase Minimum clearance, phase-to-earth Weight 1) (fixed-mounted circuit-breaker / withdrawable module) Detailed dimension drawing (has to be ordered) Operating cycle diagram no. (see page 57) I r t k I SC I ma U p U d A s ka % ka ka kv kv mv kg AE1 1-1... 800 05 160 0 6.4 50/5 75 8.1 19 140 115 75 67/ S_A7E_440016 7 AE1 1-... 150 05 160 0 6.4 50/5 75 8.1 19 140 115 75 67/ S_A7E_440016 7 AE1 14-1... 800 05 160 5 6 8 6/65 75 8.1 19 140 115 75 67/ S_A7E_440016 8a AE1 14-... 150 05 160 5 6 8 6/65 75 8.1 19 140 115 75 67/ S_A7E_440016 8a AE1 15-1... 800 05 160 1.5 6 5.4 80/8 75 8.1 19 140 115 75 80/ S_A7E_440016 9 AE1 15-... 150 05 160 1.5 6 5.4 80/8 75 8.1 19 140 115 75 80/ S_A7E_440016 9 AE1 14-1... 800 75 160 16 6 17.9 40/4 75 8.1 19 140 115 75 67/ S_A7E_440017 6 AE1 14-... 150 75 160 16 6 17.9 40/4 75 8.1 19 140 115 75 67/ S_A7E_440017 6 AE1 14-1... 800 75 160 0 6.4 50/5 75 8.1 19 140 115 75 67/ S_A7E_440017 7 AE1 14-... 150 75 160 0 6.4 50/5 75 8.1 19 140 115 75 67/ S_A7E_440017 7 AE1 144-1... 800 75 160 5 6 8 6/65 75 8.1 19 140 115 75 67/ S_A7E_440017 8a AE1 144-... 150 75 160 5 6 8 6/65 75 8.1 19 140 115 75 67/ S_A7E_440017 8a AE1 145-1... 800 75 160 1.5 6 5.4 80/8 75 8.1 19 140 115 75 80/ S_A7E_440017 9 AE1 145-... 150 75 160 1.5 6 5.4 80/8 75 8.1 19 140 115 75 80/ S_A7E_440017 9 AE1 15-1... 800 10 160 16 6 17.9 40/4 75 8.1 19 140 110 75 67/ S_A7E_440018 6 AE1 15-... 150 10 160 16 6 17.9 40/4 75 8.1 19 140 110 75 67/ S_A7E_440018 6 AE1 15-1... 800 10 160 0 6.4 50/5 75 8.1 19 140 110 75 67/ S_A7E_440018 7 AE1 15-... 150 10 160 0 6.4 50/5 75 8.1 19 140 110 75 67/ S_A7E_440018 7 AE1 154-1... 800 10 160 5 6 8 6/65 75 8.1 19 140 110 75 67/ S_A7E_440018 8a AE1 154-... 150 10 160 5 6 8 6/65 75 8.1 19 140 110 75 67/ S_A7E_440018 8a AE1 155-1... 800 10 160 1.5 6 5.4 80/8 75 8.1 19 140 110 75 80/ S_A7E_440018 9 AE1 155-... 150 10 160 1.5 6 5.4 80/8 75 8.1 19 140 110 75 80/ S_A7E_440018 9 AE1 16-1... 800 05 10 16 6 17.9 40/4 75 8.1 19 140 165 75 67/ S_A7E_4400 6 AE1 16-... 150 05 10 16 6 17.9 40/4 75 8.1 19 140 165 75 67/ S_A7E_4400 6 AE1 16-1... 800 05 10 0 6.4 50/5 75 8.1 19 140 165 75 67/ S_A7E_4400 7 AE1 16-... 150 05 10 0 6.4 50/5 75 8.1 19 140 165 75 67/ S_A7E_4400 7 Possible with order suffix Z and order code F7 Standard information on rating plate Possible with order suffix Z and order code F8 Rated operating sequence possible up to I SC = 1.5 ka 1) The weight of the fixed-mounted circuit-breaker with withdrawable part increases by the values specified in the dimension drawing of the withdrawable part (page 68) Siemens HG 11.0 01 55

Technical Data Electrical data, dimensions and weights for AE1 SION Vacuum Circuit-Breakers AE5 and AE1 1 kv 50 / 60 Hz Order No. Rated normal current Width across flats Pole-center distance Rated operating sequence: O min CO min CO O 0. s CO min CO O 0. s CO 15 s CO Rated duration of short-circuit Rated short-circuit breaking current DC component in % of the rated short-circuit breaking current Asyetrical breaking current Rated short-circuit making current (at 50 / 60 Hz) Rated lightning impulse Rated short-duration power-frequency Voltage drop U between connections (according to IEC 671-1 at DC 100 A) Minimum creepage distance, interrupter Minimum creepage distance, phase-to-earth Minimum clearance, phase-to-phase Minimum clearance, phase-to-earth Weight 1) (fixed-mounted circuit-breaker / withdrawable module) Detailed dimension drawing (has to be ordered) Operating cycle diagram no. (see page 57) I r t k I SC I ma U p U d A s ka % ka ka kv kv mv kg AE1 164-1... 800 05 10 5 6 8 6/65 75 8.1 19 140 165 75 67/ S_A7E_4400 8a AE1 164-... 150 05 10 5 6 8 6/65 75 8.1 19 140 165 75 67/ S_A7E_4400 8a AE1 165-1... 800 05 10 1.5 6 5.4 80/8 75 8.1 19 140 165 75 90/ S_A7E_4400 9 AE1 165-... 150 05 10 1.5 6 5.4 80/8 75 8.1 19 140 165 75 90/ S_A7E_4400 9 AE1 17-1... 800 75 10 16 6 17.9 40/4 75 8.1 19 140 165 75 67/10 S_A7E_4400 6 AE1 17-... 150 75 10 16 6 17.9 40/4 75 8.1 19 140 165 75 67/10 S_A7E_4400 6 AE1 17-1... 800 75 10 0 6.4 50/5 75 8.1 19 140 165 75 67/10 S_A7E_4400 7 AE1 17-... 150 75 10 0 6.4 50/5 75 8.1 19 140 165 75 67/10 S_A7E_4400 7 AE1 174-1... 800 75 10 5 6 8 6/65 75 8.1 19 140 165 75 67/10 S_A7E_4400 8a AE1 174-... 150 75 10 5 6 8 6/65 75 8.1 19 140 165 75 67/10 S_A7E_4400 8a AE1 175-1... 800 75 10 1.5 6 5.4 80/8 75 8.1 19 140 165 75 90/10 S_A7E_4400 9 AE1 175-... 150 75 10 1.5 6 5.4 80/8 75 8.1 19 140 165 75 90/10 S_A7E_4400 9 AE1 18-1... 800 10 10 16 6 17.9 40/4 75 8.1 19 140 160 75 67/10 S_A7E_44004 6 AE1 18-... 150 10 10 16 6 17.9 40/4 75 8.1 19 140 160 75 67/10 S_A7E_44004 6 AE1 18-1... 800 10 10 0 6.4 50/5 75 8.1 19 140 160 75 67/10 S_A7E_44004 7 AE1 18-... 150 10 10 0 6.4 50/5 75 8.1 19 140 160 75 67/10 S_A7E_44004 7 AE1 184-1... 800 10 10 5 6 8 6/65 75 8.1 19 140 160 75 67/10 S_A7E_44004 8a AE1 184-... 150 10 10 5 6 8 6/65 75 8.1 19 140 160 75 67/10 S_A7E_44004 8a AE1 184-4... 000 10 10 5 6 8 6/65 75 8 1.5 19 65 10 10 110/150 S_A7E_44008 8 AE1 184-6... 500 10 10 5 6 8 6/65 75 8 1.5 19 65 10 10 110/150 S_A7E_44008 8 AE1 185-1... 800 10 10 1.5 6 5.4 80/8 75 8.1 19 140 160 75 90/10 S_A7E_44004 9 AE1 185-... 150 10 10 1.5 6 5.4 80/8 75 8.1 19 140 160 75 90/10 S_A7E_44004 9 AE1 185-4... 000 10 10 1.5 6 5.4 80/8 75 8 1.5 19 65 10 10 110/150 S_A7E_44008 9 AE1 185-6... 500 10 10 1.5 6 5.4 80/8 75 8 1.5 19 65 10 10 110/150 S_A7E_44008 9 AE1 186-... 150 10 10 40 6 44.9 100/104 75 8 1.7 145 155 169 140 10/160 S_A7E_440070 10 AE1 186-4... 000 10 10 40 6 44.9 100/104 75 8 1.0 145 49 149 140 160/10 S_A7E_440071 10 Possible with order suffix Z and order code F7 Standard information on rating plate Possible with order suffix Z and order code F8 Rated operating sequence possible up to I SC = 1.5 ka 1) The weight of the fixed-mounted circuit-breaker with withdrawable part increases by the values specified in the dimension drawing of the withdrawable part (page 68) 56 Siemens HG 11.0 01

SION Vacuum Circuit-Breakers AE5 and AE1 Technical Data Electrical data, dimensions and weights for AE1 1 kv 50 / 60 Hz Order No. Rated normal current Width across flats Pole-center distance Rated operating sequence: O min CO min CO O 0. s CO min CO O 0. s CO 15 s CO Rated duration of short-circuit Rated short-circuit breaking current DC component in % of the rated short-circuit breaking current Asyetrical breaking current Rated short-circuit making current (at 50 / 60 Hz) Rated lightning impulse Rated short-duration power-frequency Voltage drop U between connections (according to IEC 671-1 at DC 100 A) Minimum creepage distance, interrupter Minimum creepage distance, phase-to-earth Minimum clearance, phase-to-phase Minimum clearance, phase-to-earth Weight 1) (fixed-mounted circuit-breaker / withdrawable module) Detailed dimension drawing (has to be ordered) Operating cycle diagram no. (see below) I r t k I SC I ma U p U d A s ka % ka ka kv kv mv kg AE1 186-6... 500 10 10 40 6 44.9 100/104 75 8 1.0 145 49 149 140 160/10 S_A7E_440071 10 AE1 186-7... 150 10 10 40 6 44.9 100/104 75 8 1.0 145 49 149 140 160/10 S_A7E_440071 10 AE1 554-1... 800 75 160 5 6 44.9 6/65 75 8.1 19 140 115 75 67/ 8a AE1 554-... 150 75 160 5 6 44.9 6/65 75 8.1 19 140 115 75 67/ 8a AE1 555-1... 800 75 160 1.5 6 44.9 80/8 75 8.1 19 140 115 75 80/ 9 AE1 555-... 150 75 160 1.5 6 44.9 80/8 75 8.1 19 140 115 75 80/ 9 AE1 565-... 150 75 10 1.5 6 44.9 80/8 75 8.1 19 140 165 75 90/ 9 AE1 565-6... 500 75 10 1.5 6 44.9 80/8 75 8 9 AE1 566-... 150 75 10 40 6 44.9 100/104 75 8 1.7 145 155 169 140 10/ 10 AE1 566-6... 500 75 10 40 6 44.9 100/104 75 8 1.0 145 49 149 140 160/ 10 AE1 566-7... 150 75 10 40 6 44.9 100/104 75 8 1.0 145 49 149 140 160/ 10 Possible with order suffix Z and order code F7 Standard information on rating plate Possible with order suffix Z and order code F8 1) The weight of the fixed-mounted circuit-breaker with withdrawable part increases by the values specified in the dimension drawing of the withdrawable part (page 68) Operating cycle diagrams for 1 kv Operating cycles No. 0 000 10 000 5 000 000 1 000 500 00 100 70 46 0 0 6 8a 7 10 0.5 1 5 10 16 0 5 ka 50 Breaking current (r.m.s. value) HG11-75b_en eps The permissible number of electrical operating cycles is shown as a function of the breaking current (r.m.s. value). All SION vacuum circuit-breakers fulfil the endurance classes E, M and C according to IEC 671-100. The curve shape beyond the parameters defined in IEC 671-100 is based on average experience data. The number of operating cycles that can actually be reached can be different depending on the respective application. Operating cycles No. 0 000 10 000 5 000 000 1 000 500 00 100 80 50 0 9 8 10 10 0.5 1 5 10 ka 0 5 40 50 1.5 Breaking current (r.m.s. value) HG11-74a_en eps Siemens HG 11.0 01 57

Technical Data Electrical data, dimensions and weights for AE1 SION Vacuum Circuit-Breakers AE5 and AE1 17.5 kv 50 / 60 Hz Order No. Rated normal current Width across flats Pole-center distance Rated operating sequence: O min CO min CO O 0. s CO min CO O 0. s CO 15 s CO Rated duration of short-circuit Rated short-circuit breaking current DC component in % of the rated short-circuit breaking current Asyetrical breaking current Rated short-circuit making current (at 50 / 60 Hz) Rated lightning impulse Rated short-duration power-frequency Voltage drop U between connections (according to IEC 671-1 at DC 100 A) Minimum creepage distance, interrupter Minimum creepage distance, phase-to-earth Minimum clearance, phase-to-phase Minimum clearance, phase-to-earth Weight 1) (fixed-mounted circuit-breaker / withdrawable module) Detailed dimension drawing (has to be ordered) Operating cycle diagram no. (see page 61) I r t k I SC I ma U p U d A s ka % ka ka kv kv mv kg AE1 01-1... 800 05 150 1.5 6 14.9 1/ 95 8.1 19 75 7 150 80/ S_A7E_44001 11 AE1 01-... 150 05 150 1.5 6 14.9 1/ 95 8.1 19 75 7 150 80/ S_A7E_44001 11 AE1 0-1... 800 05 150 16 6 17.9 40/4 95 8.1 19 75 7 150 80/ S_A7E_44001 1 AE1 0-... 150 05 150 16 6 17.9 40/4 95 8.1 19 75 7 150 80/ S_A7E_44001 1 AE1 04-1... 800 05 150 5 6 8 6/65 95 8.1 19 75 7 150 80/ S_A7E_44001 1 AE1 04-... 150 05 150 5 6 8 6/65 95 8.1 19 75 7 150 80/ S_A7E_44001 1 AE1 05-1... 800 05 150 1.5 6 5.4 80/8 95 8.1 19 75 7 150 80/ S_A7E_44001 14 AE1 05-... 150 05 150 1.5 6 5.4 80/8 95 8.1 19 75 7 150 80/ S_A7E_44001 14 AE1 11-1... 800 75 150 1.5 6 14.9 1/ 95 8.1 19 75 14 150 80/10 S_A7E_440014 11 AE1 11-... 150 75 150 1.5 6 14.9 1/ 95 8.1 19 75 14 150 80/10 S_A7E_440014 11 AE1 1-1... 800 75 150 16 6 17.9 40/4 95 8.1 19 75 14 150 80/10 S_A7E_440014 1 AE1 1-... 150 75 150 16 6 17.9 40/4 95 8.1 19 75 14 150 80/10 S_A7E_440014 1 AE1 14-1... 800 75 150 5 6 8 6/65 95 8.1 19 75 14 150 80/10 S_A7E_440014 1 AE1 14-... 150 75 150 5 6 8 6/65 95 8.1 19 75 14 150 80/10 S_A7E_440014 1 AE1 15-1... 800 75 150 1.5 6 5.4 80/8 95 8.1 19 75 14 150 80/10 S_A7E_440014 14 AE1 15-... 150 75 150 1.5 6 5.4 80/8 95 8.1 19 75 14 150 80/10 S_A7E_440014 14 AE1 1-1... 800 10 150 1.5 6 14.9 1/ 95 8.1 19 75 190 150 80/10 S_A7E_440015 11 AE1 1-... 150 10 150 1.5 6 14.9 1/ 95 8.1 19 75 190 150 80/10 S_A7E_440015 11 AE1-1... 800 10 150 16 6 17.9 40/4 95 8.1 19 75 190 150 80/10 S_A7E_440015 1 AE1 -... 150 10 150 16 6 17.9 40/4 95 8.1 19 75 190 150 80/10 S_A7E_440015 1 AE1 4-1... 800 10 150 5 6 8 6/65 95 8.1 19 75 190 150 80/10 S_A7E_440015 1 AE1 4-... 150 10 150 5 6 8 6/65 95 8.1 19 75 190 150 80/10 S_A7E_440015 1 AE1 5-1... 800 10 150 1.5 6 5.4 80/8 95 8.1 19 75 190 150 80/10 S_A7E_440015 14 AE1 5-... 150 10 150 1.5 6 5.4 80/8 95 8.1 19 75 190 150 80/10 S_A7E_440015 14 AE1 1-1... 800 05 160 1.5 6 14.9 1/ 95 8.1 19 75 47 150 80/ S_A7E_440019 11 AE1 1-... 150 05 160 1.5 6 14.9 1/ 95 8.1 19 75 47 150 80/ S_A7E_440019 11 Possible with order suffix Z and order code F7 Standard information on rating plate Possible with order suffix Z and order code F8 Rated operating sequence possible up to I SC = 1.5 ka 1) The weight of the fixed-mounted circuit-breaker with withdrawable part increases by the values specified in the dimension drawing of the withdrawable part (page 68) 58 Siemens HG 11.0 01

SION Vacuum Circuit-Breakers AE5 and AE1 Technical Data Electrical data, dimensions and weights for AE1 17.5 kv 50 / 60 Hz Order No. Rated normal current Width across flats Pole-center distance Rated operating sequence: O min CO min CO O 0. s CO min CO O 0. s CO 15 s CO Rated duration of short-circuit Rated short-circuit breaking current DC component in % of the rated short-circuit breaking current Asyetrical breaking current Rated short-circuit making current (at 50 / 60 Hz) Rated lightning impulse Rated short-duration power-frequency Voltage drop U between connections (according to IEC 671-1 at DC 100 A) Minimum creepage distance, interrupter Minimum creepage distance, phase-to-earth Minimum clearance, phase-to-phase Minimum clearance, phase-to-earth Weight 1) (fixed-mounted circuit-breaker / withdrawable module) Detailed dimension drawing (has to be ordered) Operating cycle diagram no. (see page 61) I r t k I SC I ma U p U d A s ka % ka ka kv kv mv kg AE1-1... 800 05 160 16 6 17.9 40/4 95 8.1 19 75 47 150 80/ S_A7E_440019 1 AE1 -... 150 05 160 16 6 17.9 40/4 95 8.1 19 75 47 150 80/ S_A7E_440019 1 AE1 4-1... 800 05 160 5 6 8 6/65 95 8.1 19 75 47 150 80/ S_A7E_440019 1 AE1 4-... 150 05 160 5 6 8 6/65 95 8.1 19 75 47 150 80/ S_A7E_440019 1 AE1 5-1... 800 05 160 1.5 6 5.4 80/8 95 8.1 19 75 47 150 80/ S_A7E_440019 14 AE1 5-... 150 05 160 1.5 6 5.4 80/8 95 8.1 19 75 47 150 80/ S_A7E_440019 14 AE1 41-1... 800 75 160 1.5 6 14.9 1/ 95 8.1 19 75 4 150 80/ S_A7E_44000 11 AE1 41-... 150 75 160 1.5 6 14.9 1/ 95 8.1 19 75 4 150 80/ S_A7E_44000 11 AE1 4-1... 800 75 160 16 6 17.9 40/4 95 8.1 19 75 4 150 80/ S_A7E_44000 1 AE1 4-... 150 75 160 16 6 17.9 40/4 95 8.1 19 75 4 150 80/ S_A7E_44000 1 AE1 44-1... 800 75 160 5 6 8 6/65 95 8.1 19 75 4 150 80/ S_A7E_44000 1 AE1 44-... 150 75 160 5 6 8 6/65 95 8.1 19 75 4 150 80/ S_A7E_44000 1 AE1 45-1... 800 75 160 1.5 6 5.4 80/8 95 8.1 19 75 4 150 80/ S_A7E_44000 14 AE1 45-... 150 75 160 1.5 6 5.4 80/8 95 8.1 19 75 4 150 80/ S_A7E_44000 14 AE1 51-1... 800 10 160 1.5 6 14.9 1/ 95 8.1 19 75 00 150 80/ S_A7E_44001 11 AE1 51-... 150 10 160 1.5 6 14.9 1/ 95 8.1 19 75 00 150 80/ S_A7E_44001 11 AE1 5-1... 800 10 160 16 6 17.9 40/4 95 8.1 19 75 00 150 80/ S_A7E_44001 1 AE1 5-... 150 10 160 16 6 17.9 40/4 95 8.1 19 75 00 150 80/ S_A7E_44001 1 AE1 54-1... 800 10 160 5 6 8 6/65 95 8.1 19 75 00 150 80/ S_A7E_44001 1 AE1 54-... 150 10 160 5 6 8 6/65 95 8.1 19 75 00 150 80/ S_A7E_44001 1 AE1 55-1... 800 10 160 1.5 6 5.4 80/8 95 8.1 19 75 00 150 80/ S_A7E_44001 14 AE1 55-... 150 10 160 1.5 6 5.4 80/8 95 8.1 19 75 00 150 80/ S_A7E_44001 14 AE1 61-1... 800 05 10 1.5 6 14.9 1/ 95 8.1 19 75 165 150 90/ S_A7E_44005 11 AE1 61-... 150 05 10 1.5 6 14.9 1/ 95 8.1 19 75 165 150 90/ S_A7E_44005 11 AE1 6-1... 800 05 10 16 6 17.9 40/4 95 8.1 19 75 165 150 90/ S_A7E_44005 1 AE1 6-... 150 05 10 16 6 17.9 40/4 95 8.1 19 75 165 150 90/ S_A7E_44005 1 Possible with order suffix Z and order code F7 Standard information on rating plate Possible with order suffix Z and order code F8 1) The weight of the fixed-mounted circuit-breaker with withdrawable part increases by the values specified in the dimension drawing of the withdrawable part (page 68) Siemens HG 11.0 01 59

Technical Data Electrical data, dimensions and weights AE1 SION Vacuum Circuit-Breakers AE5 and AE1 17.5 kv 50 / 60 Hz Order No. Rated normal current Width across flats Pole-center distance Rated operating sequence: O min CO min CO O 0. s CO min CO O 0. s CO 15 s CO Rated duration of short-circuit Rated short-circuit breaking current DC component in % of the rated short-circuit breaking current Asyetrical breaking current Rated short-circuit making current (at 50 / 60 Hz) Rated lightning impulse Rated short-duration power-frequency Voltage drop U between connections (according to IEC 671-1 at DC 100 A) Minimum creepage distance, interrupter Minimum creepage distance, phase-to-earth Minimum clearance, phase-to-phase Minimum clearance, phase-to-earth Weight 1) (fixed-mounted circuit-breaker / withdrawable module) Detailed dimension drawing (has to be ordered) Operating cycle diagram no. (see page 61) I r t k I SC I ma U p U d A s ka % ka ka kv kv mv kg AE1 64-1... 800 05 10 5 6 8 6/65 95 8.1 19 75 165 150 90/ S_A7E_44005 1 AE1 64-... 150 05 10 5 6 8 6/65 95 8.1 19 75 165 150 90/ S_A7E_44005 1 AE1 65-1... 800 05 10 1.5 6 5.4 80/8 95 8.1 19 75 165 150 90/ S_A7E_44005 14 AE1 65-... 150 05 10 1.5 6 5.4 80/8 95 8.1 19 75 165 150 90/ S_A7E_44005 14 AE1 71-1... 800 75 10 1.5 6 14.9 1/ 95 8.1 19 75 165 150 90/10 S_A7E_44006 11 AE1 71-... 150 75 10 1.5 6 14.9 1/ 95 8.1 19 75 165 150 90/10 S_A7E_44006 11 AE1 7-1... 800 75 10 16 6 17.9 40/4 95 8.1 19 75 165 150 90/10 S_A7E_44006 1 AE1 7-... 150 75 10 16 6 17.9 40/4 95 8.1 19 75 165 150 90/10 S_A7E_44006 1 AE1 74-1... 800 75 10 5 6 8 6/65 95 8.1 19 75 165 150 90/10 S_A7E_44006 1 AE1 74-... 150 75 10 5 6 8 6/65 95 8.1 19 75 165 150 90/10 S_A7E_44006 1 AE1 75-1... 800 75 10 1.5 6 5.4 80/8 95 8.1 19 75 165 150 90/10 S_A7E_44006 14 AE1 75-... 150 75 10 1.5 6 5.4 80/8 95 8.1 19 75 165 150 90/10 S_A7E_44006 14 AE1 81-1... 800 10 10 1.5 6 14.9 1/ 95 8.1 19 75 160 150 90/10 S_A7E_44007 11 AE1 81-... 150 10 10 1.5 6 14.9 1/ 95 8.1 19 75 160 150 90/10 S_A7E_44007 11 AE1 8-1... 800 10 10 16 6 17.9 40/4 95 8.1 19 75 160 150 90/10 S_A7E_44007 1 AE1 8-... 150 10 10 16 6 17.9 40/4 95 8.1 19 75 160 150 90/10 S_A7E_44007 1 AE1 84-1... 800 10 10 5 6 8 6/65 95 8.1 19 75 160 150 90/10 S_A7E_44007 1 AE1 84-... 150 10 10 5 6 8 6/65 95 8.1 19 75 160 150 90/10 S_A7E_44007 1 AE1 84-4... 000 10 10 5 6 8 6/65 95 8 1.5 19 65 10 10 110/150 S_A7E_44009 1 AE1 84-6... 500 10 10 5 6 8 6/65 95 8 1.5 19 65 10 10 110/150 S_A7E_44009 1 AE1 85-1... 800 10 10 1.5 6 5.4 80/8 95 8.1 19 75 160 150 90/10 S_A7E_44007 14 AE1 85-... 150 10 10 1.5 6 5.4 80/8 95 8.1 19 75 160 150 90/10 S_A7E_44007 14 AE1 85-4... 000 10 10 1.5 6 5.4 80/8 95 8 1.5 19 65 10 10 110/150 S_A7E_44009 14 AE1 85-6... 500 10 10 1.5 6 5.4 80/8 95 8 1.5 19 65 10 10 110/150 S_A7E_44009 14 AE1 86-... 150 10 10 40 6 44.9 100/104 95 8 1.7 145 49 169 140 10/160 S_A7E_440070 15 AE1 86-4... 000 10 10 40 6 44.9 100/104 95 8 1.0 145 49 149 140 160/10 S_A7E_440071 15 Possible with order suffix Z and order code F7 Standard information on rating plate Possible with order suffix Z and order code F8 1) The weight of the fixed-mounted circuit-breaker with withdrawable part increases by the values specified in the dimension drawing of the withdrawable part (page 68) 60 Siemens HG 11.0 01

SION Vacuum Circuit-Breakers AE5 and AE1 Technical Data Electrical data, dimensions and weights AE1 17.5 kv 50 / 60 Hz Order No. Rated normal current Width across flats Pole-center distance Rated operating sequence: O min CO min CO O 0. s CO min CO O 0. s CO 15 s CO Rated duration of short-circuit Rated short-circuit breaking current DC component in % of the rated short-circuit breaking current Asyetrical breaking current Rated short-circuit making current (at 50 / 60 Hz) Rated lightning impulse Rated short-duration power-frequency Voltage drop U between connections (according to IEC 671-1 at DC 100 A) Minimum creepage distance, interrupter Minimum creepage distance, phase-to-earth Minimum clearance, phase-to-phase Minimum clearance, phase-to-earth Weight 1) (fixed-mounted circuit-breaker / withdrawable module) Detailed dimension drawing (has to be ordered) Operating cycle diagram no. (see below) I r t k I SC I ma U p U d A s ka % ka ka kv kv mv kg AE1 86-6... 500 10 10 40 6 44.9 100/104 95 8 1.0 145 49 149 140 160/10 S_A7E_440071 15 AE1 86-7... 150 10 10 40 6 44.9 100/104 95 8 1.0 145 49 149 140 160/10 S_A7E_440071 15 AE1 64-1... 800 75 160 5 6 44.9 6/65 95 8.1 19 75 4 150 80/ 1 AE1 64-... 150 75 160 5 6 44.9 6/65 95 8.1 19 75 4 150 80/ 1 AE1 65-1... 800 75 160 1.5 6 44.9 80/8 95 8.1 19 75 4 150 80/ 14 AE1 65-... 150 75 160 1.5 6 44.9 80/8 95 8.1 19 75 4 150 80/ 14 AE1 665-... 150 75 10 1.5 6 44.9 80/8 95 8.1 19 75 165 150 90/ 14 AE1 665-6... 500 75 10 1.5 6 44.9 80/8 95 8 14 AE1 666-... 150 75 10 40 6 44.9 100/104 95 8 1.7 145 49 169 140 10/ 15 AE1 666-6... 500 75 10 40 6 44.9 100/104 95 8 1.0 145 49 149 140 160/ 15 AE1 666-7... 150 75 10 40 6 44.9 100/104 95 8 1.0 145 49 149 140 160/ 15 Possible with order suffix Z and order code F7 Standard information on rating plate Possible with order suffix Z and order code F8 1) The weight of the fixed-mounted circuit-breaker with withdrawable part increases by the values specified in the dimension drawing of the withdrawable part (page 68) Operating cycle diagrams for 17.5 kv Operating cycles No. 0 000 10 000 5 000 000 1 000 500 180 00 100 80 50 0 1 1 15 10 0.5 1 5 ka 10 16 0 5 40 50 Breaking current (r.m.s. value) HG11-57b_en eps The permissible number of electrical operating cycles is shown as a function of the breaking current (r.m.s. value). All SION vacuum circuit-breakers fulfil the endurance classes E, M and C according to IEC 671-100. The curve shape beyond the parameters defined in IEC 671-100 is based on average experience data. The number of operating cycles that can actually be reached can be different depending on the respective application. Operating cycles No. 0 000 10 000 5 000 000 1 000 500 50 00 100 50 0 11 14 10 0.5 1 5 ka 101.5 0 1.5 50 Breaking current (r.m.s. value) HG11-541a_en eps Siemens HG 11.0 01 61

Technical Data Electrical data, dimensions and weights AE1 SION Vacuum Circuit-Breakers AE5 and AE1 4 kv 50 / 60 Hz Order No. Rated normal current Width across flats Pole-center distance Rated operating sequence: O min CO min CO O 0. s CO min CO O 0. s CO 15 s CO Rated duration of short-circuit Rated short-circuit breaking current DC component in % of the rated short-circuit breaking current Asyetrical breaking current Rated short-circuit making current (at 50 / 60 Hz) Rated lightning impulse Rated short-duration power-frequency Voltage drop U between connections (according to IEC 671-1 at DC 100 A) Minimum creepage distance, interrupter Minimum creepage distance, phase-to-earth Minimum clearance, phase-to-phase Minimum clearance, phase-to-earth Weight 1) (fixed-mounted circuit-breaker / withdrawable module) Detailed dimension drawing (has to be ordered) Operating cycle diagram no. (see page 6) I r t k I SC I ma U p U d A s ka % ka ka kv kv mv kg AE1 1-1... 800 10 10 1.5 6 14.9 1/ 15 50.6 00 50 00 10 10/160 S_A7E_440050 16 AE1 1-... 150 10 10 1.5 6 14.9 1/ 15 50.6 00 50 00 10 10/160 S_A7E_440050 16 AE1-1... 800 10 10 16 6 17.9 40/4 15 50.6 00 50 00 10 10/160 S_A7E_440050 17 AE1 -... 150 10 10 16 6 17.9 40/4 15 50.6 00 50 00 10 10/160 S_A7E_440050 17 AE1-4... 000 10 10 16 6 17.9 40/4 15 50.0 00 40 00 05 140/180 S_A7E_440051 17 AE1-1... 800 10 10 0 6.4 50/5 15 50.6 00 50 00 10 10/160 S_A7E_440050 18 AE1 -... 150 10 10 0 6.4 50/5 15 50.6 00 50 00 10 10/160 S_A7E_440050 18 AE1-4... 000 10 10 0 6.4 50/5 15 50.0 00 40 00 05 140/180 S_A7E_440051 18 AE1-6... 500 10 10 0 6.4 50/5 15 50.0 00 40 00 05 140/180 S_A7E_440051 18 AE1 4-1... 800 10 10 5 6 8 6/65 15 50.6 00 50 00 10 10/160 S_A7E_440050 19 AE1 4-... 150 10 10 5 6 8 6/65 15 50.6 00 50 00 10 10/160 S_A7E_440050 19 AE1 4-4... 000 10 10 5 6 8 6/65 15 50.0 00 40 00 05 140/180 S_A7E_440051 19 AE1 4-6... 500 10 10 5 6 8 6/65 15 50.0 00 40 00 05 140/180 S_A7E_440051 19 AE1 5-1... 800 10 75 16 6 17.9 40/4 15 50.6 00 50 65 10 10/180 S_A7E_44005 17 AE1 5-... 150 10 75 16 6 17.9 40/4 15 50.6 00 50 65 10 10/180 S_A7E_44005 17 AE1 5-4... 000 10 75 16 6 17.9 40/4 15 50.0 00 40 65 05 150/00 S_A7E_44005 17 AE1 5-1... 800 10 75 0 6.4 50/5 15 50.6 00 50 65 10 10/180 S_A7E_44005 18 AE1 5-... 150 10 75 0 6.4 50/5 15 50.6 00 50 65 10 10/180 S_A7E_44005 18 AE1 5-4... 000 10 75 0 6.4 50/5 15 50.0 00 40 65 05 150/00 S_A7E_44005 18 AE1 5-6... 500 10 75 0 6.4 50/5 15 50.0 00 40 65 05 150/00 S_A7E_44005 18 Possible with order suffix Z and order code F7 Standard information on rating plate Possible with order suffix Z and order code F8 1) The weight of the fixed-mounted circuit-breaker with withdrawable part increases by the values specified in the dimension drawing of the withdrawable part (page 68) 6 Siemens HG 11.0 01

SION Vacuum Circuit-Breakers AE5 and AE1 Technical Data Electrical data, dimensions and weights AE1 4 kv 50 / 60 Hz Order No. Rated normal current Width across flats Pole-center distance Rated operating sequence: O min CO min CO O 0. s CO min CO O 0. s CO 15 s CO Rated duration of short-circuit Rated short-circuit breaking current DC component in % of the rated short-circuit breaking current Asyetrical breaking current Rated short-circuit making current (at 50 / 60 Hz) Rated lightning impulse Rated short-duration power-frequency Voltage drop U between connections (according to IEC 671-1 at DC 100 A) Minimum creepage distance. interrupter Minimum creepage distance, phase-to-earth Minimum clearance, phase-to-phase Minimum clearance, phase-to-earth Weight 1) (fixed-mounted circuit-breaker / withdrawable module) Detailed dimension drawing (has to be ordered) Operating cycle diagram no. (see below) I r t k I SC I ma U p U d A s ka % ka ka kv kv mv kg AE1 54-1... 800 10 75 5 6 8 6/65 15 50.6 00 50 65 10 10/180 S_A7E_44005 19 AE1 54-... 150 10 75 5 6 8 6/65 15 50.6 00 50 65 10 10/180 S_A7E_44005 19 AE1 54-4... 000 10 75 5 6 8 6/65 15 50.0 00 40 65 05 150/00 S_A7E_44005 19 AE1 54-6... 500 10 75 5 6 8 6/65 15 50.0 00 40 65 05 150/00 S_A7E_44005 19 AE1 714-... 150 0 10 5 6 8 6/65 15 50.6 00 50 00 10 10/ 19 AE1 744-4... 000 0 75 5 6 8 6/65 15 50.0 00 40 00 05 150/ 19 AE1 744-6... 500 0 75 5 6 44.9 6/65 15 50.0 00 40 00 05 150/ 19 AE1 74-4... 000 0 10 5 6 44.9 6/65 15 50 19 AE1 74-6... 500 0 10 5 6 44.9 6/65 15 50 19 AE1 754-6... 500 0 75 5 6 44.9 6/65 15 50.0 00 40 00 05 150/ 19 Possible with order suffix Z and order code F7 Standard information on rating plate Possible with order suffix Z and order code F8 1) The weight of the fixed-mounted circuit-breaker with withdrawable part increases by the values specified in the dimension drawing of the withdrawable part (page 68) Operating cycle diagrams for 4 kv Operating cycles No. 0 000 10 000 5 000 000 1 000 500 00 150 100 50 0 16 18 10 0.5 1 5 10 1.5 0 ka 50 Breaking current (r.m.s. value) HG11-58b_en eps The permissible number of electrical operating cycles is shown as a function of the breaking current (r.m.s. value). All SION vacuum circuit-breakers fulfil the endurance classes E, M and C according to IEC 671-100. The curve shape beyond the parameters defined in IEC 671-100 is based on average experience data. The number of operating cycles that can actually be reached can be different depending on the respective application. Operating cycles No. 0 000 10 000 5 000 000 1 000 500 00 100 90 0 50 0 17 10 0.5 1 5 10 16 5 ka 50 Breaking current (r.m.s. value) 19 HG11-54a_en eps Siemens HG 11.0 01 6

i Technical Data Dimensions drawings for voltage levels 7. kv to 1 kv for AE5 SION Vacuum Circuit-Breakers AE5 and AE1 Dimension drawings for 7. to 1 kv Vacuum circuit-breaker without contact arm l q n a c a m d e b HG11-84 eps o g f p Voltage level 7. kv 1 kv Pole-center distance a Width across flats b c d e f g 150 05 445 540 17.5 80 9 500.5 71 540 105 8 88 169 150 75 445 540 17.5 80 9 500.5 71 540 105 8 88 169 150 10 445 540 7.5 80 9 500.5 71 540 105 8 88 169 160 05 465 540 17.5 80 9 500.5 71 540 105 8 88 169 160 75 465 540 17.5 80 9 500.5 71 540 105 8 88 169 160 10 465 540 7.5 80 9 500.5 71 540 105 8 88 169 10 05 565 540 17.5 80 9 500.5 71 540 105 8 88 169 10 75 565 540 17.5 80 9 500.5 71 540 105 8 88 169 10 10 565 540 7.5 80 9 500.5 71 540 105 8 88 169 150 05 445 540 17.5 80 9 500.5 71 540 105 8 88 169 150 75 445 540 17.5 80 9 500.5 71 540 105 8 88 169 150 10 445 540 7.5 80 9 500.5 71 540 105 8 88 169 160 05 465 540 17.5 80 9 500.5 71 540 105 8 88 169 160 75 465 540 17.5 80 9 500.5 71 540 105 8 88 169 160 10 465 540 7.5 80 9 500.5 71 540 105 8 88 169 10 05 565 540 17.5 80 9 500.5 71 540 105 8 88 169 10 75 565 540 17.5 80 9 500.5 71 540 105 8 88 169 10 10 565 540 7.5 80 9 500.5 71 540 105 8 88 169 i l m n o p q Note: Small deviations of the dimensions are permissible 64 Siemens HG 11.0 01

i SION Vacuum Circuit-Breakers AE5 and AE1 Technical Data Dimensions drawings for voltage levels 7. kv to 4 kv for AE1 Dimension drawings for 7. to 4 kv Vacuum circuit-breaker without contact arm l q n a c a m HG11-81a eps d e b o g f p Voltage level 7. kv 1 kv 17.5 kv 4 kv Pole-center distance a Width across flats b c d e f 150 05 445 540 5) 17.5 80 00 6) 5 7) 71 540 105 0 79 165 150 75 445 540 5) 17.5 80 00 6) 5 7) 71 540 105 0 79 165 150 10 445 540 5) 7.5 80 00 6) 5 7) 71 540 105 0 79 165 160 05 465 540 5) 17.5 80 00 6) 5 7) 71 540 105 0 79 165 160 75 465 540 5) 17.5 80 00 6) 5 7) 71 540 105 0 79 165 160 10 465 540 5) 7.5 80 00 6) 5 7) 71 540 105 0 79 165 10 05 565 540 5) 17.5 80 00 6) 5 7) 71 540 105 0 79 165 10 75 565 540 5) 17.5 80 00 6) 5 7) 71 540 105 0 79 165 10 10 565 540 5) 7.5 80 1) 00 ) 6) 5 ) 7) 71 4) 540 105 0 8) 79 165 150 05 445 540 5) 17.5 80 00 6) 5 7) 71 540 105 0 79 165 150 75 445 540 5) 17.5 80 00 6) 5 7) 71 540 105 0 79 165 150 10 445 540 5) 7.5 80 00 6) 5 7) 71 540 105 0 79 165 160 05 465 540 5) 17.5 80 00 6) 5 7) 71 540 105 0 79 165 160 75 465 540 5) 17.5 80 00 6) 5 7) 71 540 105 0 79 165 160 10 465 540 5) 7.5 80 00 6) 5 7) 71 540 105 0 79 165 10 05 565 540 5) 17.5 80 00 6) 5 7) 71 540 105 0 79 165 10 75 565 540 5) 17.5 80 00 6) 5 7) 71 540 105 0 79 165 10 10 565 540 5) 7.5 80 1) 00 ) 6) 5 ) 7) 71 4) 540 105 0 8) 79 165 150 05 445 56 17.5 80 10 517.5 71 540 105 0 79 165 150 75 445 56 17.5 80 10 517.5 71 540 105 0 79 165 150 10 445 56 7.5 80 10 517.5 71 540 105 0 79 165 160 05 465 56 17.5 80 10 517.5 71 540 105 0 79 165 160 75 465 56 17.5 80 10 517.5 71 540 105 0 79 165 160 10 465 56 7.5 80 10 517.5 71 540 105 0 79 165 10 05 565 56 17.5 80 10 517.5 71 540 105 0 79 165 10 75 565 56 17.5 80 10 517.5 71 540 105 0 79 165 10 10 565 56 7.5 80 1) 10 ) 517.5 ) 71 4) 540 105 0 8) 79 165 10 10 570 79 8 469 60 79 41 540 105 58 79 165 75 10 700 79 8 469 60 79 41 540 105 58 79 165 g i l m n o p q Note: Dimension drawings for 8B retrofit (1 th position = 7) are available on request. Note: Small deviations of the dimensions are permissible 1) At I sc = 40 ka --> 450 ) At I sc = 40 ka --> 50 ) At I sc = 40 ka --> 610 4) At I sc = 40 ka --> 40 5) At I r >150 A or at I sc = 1.5 ka --> 56 6) At I r >150 A or at I sc = 1.5 ka --> 10 7) At I r >150 A or at I sc = 1.5 ka --> 518 8) At I sc = 40 ka --> 50 Siemens HG 11.0 01 65

i Technical Data Dimensions drawings for voltage levels 7. kv to 1 kv for AE5 SION Vacuum Circuit-Breakers AE5 and AE1 Dimension drawings for 7. to 1 kv Vacuum circuit-breaker with contact arm k l q n a c a m d e b HG11-85 eps o g f p Voltage level 7. kv 1 kv Pole-center distance a Width across flats b c d e f g 150 05 445 540 17.5 80 9 500.5 74 71 540 105 8 88 169 150 75 445 540 17.5 80 9 500.5 74 71 540 105 8 88 169 150 10 445 540 7.5 80 9 500.5 74 71 540 105 8 88 169 160 05 465 540 17.5 80 9 500.5 74 71 540 105 8 88 169 160 75 465 540 17.5 80 9 500.5 74 71 540 105 8 88 169 160 10 465 540 7.5 80 9 500.5 74 71 540 105 8 88 169 10 05 565 540 17.5 80 9 500.5 74 71 540 105 8 88 169 10 75 565 540 17.5 80 9 500.5 74 71 540 105 8 88 169 10 10 565 540 7.5 80 9 500.5 74 71 540 105 8 88 169 150 05 445 540 17.5 80 9 500.5 74 71 540 105 8 88 169 150 75 445 540 17.5 80 9 500.5 74 71 540 105 8 88 169 150 10 445 540 7.5 80 9 500.5 74 71 540 105 8 88 169 160 05 465 540 17.5 80 9 500.5 74 71 540 105 8 88 169 160 75 465 540 17.5 80 9 500.5 74 71 540 105 8 88 169 160 10 465 540 7.5 80 9 500.5 74 71 540 105 8 88 169 10 05 565 540 17.5 80 9 500.5 74 71 540 105 8 88 169 10 75 565 540 17.5 80 9 500.5 74 71 540 105 8 88 169 10 10 565 540 7.5 80 9 500.5 74 71 540 105 8 88 169 i k l m n o p q Note: Small deviations of the dimensions are permissible 66 Siemens HG 11.0 01

i SION Vacuum Circuit-Breakers AE5 and AE1 Technical Data Dimensions drawings for voltage levels 7. kv to 4 kv for AE1 Dimension drawings for 7. to 4 kv Vacuum circuit-breaker with contact arm k l q n a c a m d e b HG11-81a eps o g f p Voltage level 7. kv 1 kv 17.5 kv 4 kv Pole-center distance a Width across flats b c d e f g 150 05 445 540 5) 17.5 80 00 6) 5 7) 74 71 540 105 0 79 165 150 75 445 540 5) 17.5 80 00 6) 5 7) 74 71 540 105 0 79 165 150 10 445 540 5) 7.5 80 00 6) 5 7) 74 71 540 105 0 79 165 160 05 465 540 5) 17.5 80 00 6) 5 7) 74 71 540 105 0 79 165 160 75 465 540 5) 17.5 80 00 6) 5 7) 74 71 540 105 0 79 165 160 10 465 540 5) 7.5 80 00 6) 5 7) 74 71 540 105 0 79 165 10 05 565 540 5) 17.5 80 00 6) 5 7) 74 71 540 105 0 79 165 10 75 565 540 5) 17.5 80 00 6) 5 7) 74 71 540 105 0 79 165 10 10 565 540 5) 7.5 80 1) 00 ) 6) 5 ) 7) 74 71 4) 540 105 0 8) 79 165 150 05 445 540 5) 17.5 80 00 6) 5 7) 74 71 540 105 0 79 165 150 75 445 540 5) 17.5 80 00 6) 5 7) 74 71 540 105 0 79 165 150 10 445 540 5) 7.5 80 00 6) 5 7) 74 71 540 105 0 79 165 160 05 465 540 5) 17.5 80 00 6) 5 7) 74 71 540 105 0 79 165 160 75 465 540 5) 17.5 80 00 6) 5 7) 74 71 540 105 0 79 165 160 10 465 540 5) 7.5 80 00 6) 5 7) 74 71 540 105 0 79 165 10 05 565 540 5) 17.5 80 00 6) 5 7) 74 71 540 105 0 79 165 10 75 565 540 5) 17.5 80 00 6) 5 7) 74 71 540 105 0 79 165 10 10 565 540 5) 7.5 80 1) 00 ) 6) 5 ) 7) 74 71 4) 540 105 0 8) 79 165 150 05 445 56 17.5 80 10 517.5 74 71 540 105 0 79 165 150 75 445 56 17.5 80 10 517.5 74 71 540 105 0 79 165 150 10 445 56 7.5 80 10 517.5 74 71 540 105 0 79 165 160 05 465 56 17.5 80 10 517.5 74 71 540 105 0 79 165 160 75 465 56 17.5 80 10 517.5 74 71 540 105 0 79 165 160 10 465 56 7.5 80 10 517.5 74 71 540 105 0 79 165 10 05 565 56 17.5 80 10 517.5 74 71 540 105 0 79 165 10 75 565 56 17.5 80 10 517.5 74 71 540 105 0 79 165 10 10 565 56 7.5 80 1) 10 ) 517.5 ) 74 71 4) 540 105 0 8) 79 165 10 10 570 79 8 469 60 79 4 41 540 105 58 79 165 75 10 700 79 8 469 60 79 4 41 540 105 58 79 165 i k l m n o p q Note: Small deviations of the dimensions are permissible 1) At I sc = 40 ka --> 450 ) At I sc = 40 ka --> 50 ) At I sc = 40 ka --> 610 4) At I sc = 40 ka --> 40 5) At I r >150 A or at I sc = 1.5 ka --> 56 6) At I r >150 A or at I sc = 1.5 ka --> 10 7) At I r >150 A or at I sc = 1.5 ka --> 518 8) At I sc = 40 ka --> 50 Siemens HG 11.0 01 67

Technical Data Dimensions drawings for voltage levels 7. kv to 4 kv for AE5 SION Vacuum Circuit-Breakers AE5 and AE1 Dimension drawings for 7. to 1 kv Cartridge without earthing switch i k l q a c a d HG11-86 eps m n e f b f h g Voltage level 7. kv 1 kv Pole-center distance a Width across flats b c d e f g 150 75 594 147 850 66.5 710 6 4 476 71 540 105 169 150 10 594 147 905 86.5 710 6 4 476 71 540 105 169 10 75 794 187 850 66.5 710 6 4 476 71 540 105 169 10 10 794 187 905 86.5 710 6 4 476 71 540 105 169 150 75 594 147 850 66.5 710 6 4 476 71 540 105 169 150 10 594 147 905 86.5 710 6 4 476 71 540 105 169 10 75 794 187 850 66.5 710 6 4 476 71 540 105 169 10 10 794 187 905 86.5 710 6 4 476 71 540 105 169 h i k l m n q Note: Small deviations of the dimensions are permissible Withdrawable part d c a HG11-590a eps b e Voltage level 7. kv 1 kv 17.5 kv 4 kv Pole-center distance a b c d e f Weight 150 59 44 500 470 107 4 approx. 15 kg 160 59 44 500 470 107 4 approx. 15 kg 10 679 44 650 60 107 4 approx. 0 kg 150 59 44 500 470 107 4 approx. 15 kg 160 59 44 500 470 107 4 approx. 15 kg 10 679 44 650 60 107 4 approx. 0 kg 150 59 44 500 470 107 4 approx. 15 kg 160 59 44 500 470 107 4 approx. 15 kg 10 679 44 650 60 107 4 approx. 0 kg 10 679 44 650 60 107 4 approx. 0 kg 75 879 44 850 80 107 4 approx. 5 kg 68 Siemens HG 11.0 01

SION Vacuum Circuit-Breakers AE5 and AE1 Technical Data Dimensions drawings for voltage levels 7. kv to 4 kv for AE1 Dimension drawings for 7. to 4 kv Cartridge without earthing switch i k l q a c a d m n HG11-78b eps e f b f h g Voltage level 7. kv 1 kv 17.5 kv 4 kv Pole-center distance a Width across flats b c d e f g h 150 75 594 147 850 66.5 710 6 4 476 71 540 105 165 150 10 594 147 905 66.5 710 6 4 476 71 540 105 165 10 75 794 187 850 86.5 710 6 4 476 71 540 105 165 10 10 794 187 905 86.5 710 1) 6 4 74 476 ) 71 ) 540 105 165 150 75 594 147 850 66.5 710 6 4 476 71 540 105 165 150 10 594 147 905 66.5 710 6 4 476 71 540 105 165 10 75 794 187 850 86.5 710 6 4 476 71 540 105 165 10 10 794 187 905 86.5 710 1) 6 4 74 476 ) 71 ) 540 105 165 150 75 594 147 850 66.5 710 6 4 476 71 540 105 165 150 10 594 147 905 66.5 710 6 4 476 71 540 105 165 10 75 794 187 850 86.5 710 6 4 476 71 540 105 165 10 10 794 187 905 86.5 710 1) 6 4 74 476 ) 71 ) 540 105 165 10 10 794 187 1040.5 810 74 57 41 540 105 165 75 10 994 1040.5 810 74 57 41 540 105 165 h i i k l m n q h/i = up to I r = 150 A h /i = up to I r = 000 A, 500 A and 150 A Note: Small deviations of the dimensions are permissible Withdrawable part d c a HG11-590a eps b e Voltage level 7. kv 1 kv 17.5 kv 4 kv Pole-center distance a b c 1) At I sc = 40 ka --> 760 ) At I sc = 40 ka --> 56 ) At I sc = 40 ka --> 40 d e f Weight 150 59 44 500 470 107 4 approx. 15 kg 160 59 44 500 470 107 4 approx. 15 kg 10 679 44 650 60 107 4 approx. 0 kg 150 59 44 500 470 107 4 approx. 15 kg 160 59 44 500 470 107 4 approx. 15 kg 10 679 44 650 60 107 4 approx. 0 kg 150 59 44 500 470 107 4 approx. 15 kg 160 59 44 500 470 107 4 approx. 15 kg 10 679 44 650 60 107 4 approx. 0 kg 10 679 44 650 60 107 4 approx. 0 kg 75 879 44 850 80 107 4 approx. 5 kg Siemens HG 11.0 01 69

Technical Data Dimensions drawings for voltage levels 7. kv to 17.5 kv for AE5 SION Vacuum Circuit-Breakers AE5 and AE1 Dimension drawings for 7. to 4 kv Cartridge with earthing switch i k l q a c a d p o HG11-87 eps v m n w e f b h t u r g s Voltage level 7. kv 1 kv Pole-center distance a Width across flats b c d e f 150 75 594 147 850 66.5 710 6 4 476 71 540 105 150 10 594 147 905 86.5 710 6 4 476 71 540 105 10 75 794 187 850 66.5 710 6 4 476 71 540 105 10 10 794 187 905 86.5 710 6 4 476 71 540 105 150 75 594 147 850 66.5 710 6 4 476 71 540 105 150 10 594 147 905 86.5 710 6 4 476 71 540 105 10 75 794 187 850 66.5 710 6 4 476 71 540 105 10 10 794 187 905 86.5 710 6 4 476 71 540 105 g h i k l m n Voltage level 7. kv 1 kv o p q r s t u v w 59 87 169 80 64 114 1 575 5 6 87 169 80 64 114 1 575 5 59 87 169 80 65 114 14 - - 59 87 169 80 65 114 14 - - 59 87 169 80 64 114 1 575 5 6 87 169 80 64 114 1 575 5 59 87 169 80 65 114 14 - - 59 87 169 80 65 114 14 - - Note: Small deviations of the dimensions are permissible 70 Siemens HG 11.0 01

SION Vacuum Circuit-Breakers AE5 and AE1 Technical Data Dimensions drawings for voltage levels 7. kv to 17.5 kv for AE1 Dimension drawings for 7. to 4 kv Cartridge with earthing switch Voltage level 7. kv 1 kv 17.5 kv 4 kv Pole-center distance a Width across flats b c d e f g 150 75 594 147 850 66.5 710 6 4 476 71 540 105 150 10 594 147 905 86.5 710 6 4 476 71 540 105 10 75 794 187 850 66.5 710 6 4 476 71 540 105 10 10 794 187 905 86.5 710 1) 6 4 74 476 ) 71 ) 540 105 150 75 594 147 850 66.5 710 6 4 476 71 540 105 150 10 594 147 905 86.5 710 6 4 476 71 540 105 10 75 794 187 850 66.5 710 6 4 476 71 540 105 10 10 794 187 905 86.5 710 1) 6 4 74 476 ) 71 ) 540 105 150 75 594 147 850 66.5 710 6 4 476 71 540 105 150 10 594 147 905 86.5 710 6 4 476 71 540 105 10 75 794 187 850 66.5 710 6 4 476 71 540 105 10 10 794 187 905 86.5 710 1) 6 4 74 476 ) 71 ) 540 105 10 10 794 187 1040.5 810 74 57 41 540 105 75 10 994 1040.5 810 74 57 41 540 105 h h i i k l m n Voltage level 7. kv 1 kv 17.5 kv 4 kv o p q r s t u v w 59 87 165 80 64 114 1 575 5 59 87 165 80 64 114 1 575 5 59 87 165 80 65 114 14 59 87 165 80 65 114 14 59 87 165 80 64 114 1 575 5 59 87 165 80 64 114 1 575 5 59 87 165 80 65 114 14 59 87 165 80 65 114 14 59 87 165 80 64 114 1 575 5 59 87 165 80 64 114 1 575 5 59 87 165 80 65 114 14 59 87 165 80 65 114 14 59 87 165 90 64 14 14 575 10 59 87 165 90 65 14 14 h/i = up to I r = 150 A h /i = up to I r = 000 A, 500 A and 150 A Note: Small deviations of the dimensions are permissible 1) At I sc = 40 ka --> 760 ) At I sc = 40 ka --> 56 ) At I sc = 40 ka --> 40 Siemens HG 11.0 01 71

Technical Data SION Vacuum Circuit-Breakers AE5 and AE1 Operating times and internal times, short-circuit protection of motors, consumption data of releases Operating times and internal times for AE5 Operating times at rated voltage of the secondary circuit Equipment of circuit-breaker Operating time of the circuit-breaker Closing time < 60 ms Opening time 1 st shunt release < 60 ms nd release < 45 ms Arcing time < 15 ms Break time 1 st shunt release < 75 ms nd release < 60 ms Dead time 00 ms CLOSE / OPEN contact time 1 st shunt release < 75 ms nd release < 60 ms Minimum coand duration Closing solenoid 45 ms 1 st shunt release 40 ms nd release 0 ms Pulse time for circuit-breaker tripping signal 1 st shunt release > 10 ms nd release > 6 ms Charging time for electrical operation < 10 s Synchronism error between the poles ms Short-circuit protection of motors (fuse protection of drive motors) for AE5 Rated voltage of the motor Operating voltage Power consumption of the motor Smallest possible rated current 1) of the m.c.b. (miniature circuit-breaker) with C-characteristic V max. V min. V W A 4 DC 6 0 150 W 6 48 DC 5 41 170 W 4 60 DC 66 51 170 W 4 110 DC 11 9 10 W 0 DC 4 187 115 W 1.6 110 AC 11 9 00 V A 0 AC 44 187 00 V A 1.6 1) The current inrush in the drive motor can be neglected due to its very short presence. Consumption data of releases for AE5 Release Power consumption Tripping ranges DC approx. W Operation at Tripping voltage Tripping voltage or tripping current AC 50 / 60 Hz approx. VA at DC at AC 50 / 60 Hz Closing solenoid AY14 10 00 00 85 to 110 % U 85 to 110 % U 1 st shunt release (without energy store) AY14 10 nd shunt release (with energy store) AX11 01 00 00 70 to 110 % U 85 to 110 % U 70 50 70 to 110 % U 85 to 110 % U Undervoltage release AX11 0 0 0 5 to 0 % U 5 to 0 % U Current-transformer operated release AX11 0 (rated normal current 0.5 A or 1 A) Current-transformer operated release AX11 04 (tripping pulse 0.1 Ws) 10 ) 90 to 110 % I a ) Consumption at pickup current (90 % of the rated normal current) and open armature. 7 Siemens HG 11.0 01

SION Vacuum Circuit-Breakers AE5 and AE1 Technical Data Operating times and internal times, short-circuit protection of motors, consumption data of releases Operating times and internal times for AE1 Operating times at rated voltage of the secondary circuit Equipment of circuit-breaker Operating time of the circuit-breaker Closing time < 60 ms Opening time 1 st shunt release < 60 ms nd release < 45 ms Arcing time < 15 ms Break time 1 st shunt release < 75 ms nd release < 60 ms Dead time 00 ms CLOSE / OPEN contact time 1 st shunt release < 75 ms nd release < 60 ms Minimum coand duration Closing solenoid 45 ms 1 st shunt release 40 ms nd release 0 ms Pulse time for circuit-breaker tripping signal 1 st shunt release > 10 ms nd release > 6 ms Charging time for electrical operation < 10 s Synchronism error between the poles ms Short-circuit protection of motors (fuse protection of drive motors) for AE1 Rated voltage of the motor Operating voltage Power consumption of the motor Smallest possible rated current 1) of the m.c.b. (miniature circuit-breaker) with C-characteristic V max. V min. V W A 4 DC 6 0 400 8 48 DC 5 41 400 6 60 DC 66 51 400 4 110 DC 11 9 400 0 DC 4 187 400 1.6 110 AC 11 9 400 0 AC 44 187 400 1.6 1) The current inrush in the drive motor can be neglected due to its very short presence. Consumption data of releases for AE1 Release Power consumption Tripping ranges DC approx. W Operation at Tripping voltage Tripping voltage or tripping current AC 50 / 60 Hz approx. VA at DC at AC 50 / 60 Hz Closing solenoid AY15 10 140 140 85 to 110 % U 85 to 110 % U 1 st shunt release (without energy store) AY15 10 nd shunt release (with energy store) AX11 01 140 140 70 to 110 % U 85 to 110 % U 70 50 70 to 110 % U 85 to 110 % U Undervoltage release AX11 0 0 0 5 to 0 % U 5 to 0 % U Current-transformer operated release AX11 0 (rated normal current 0.5 A or 1 A) Current-transformer operated release AX11 04 (tripping pulse 0.1 Ws) 10 ) 90 to 110 % I a ) Consumption at pickup current (90 % of the rated normal current) and open armature. Siemens HG 11.0 01 7

Technical Data Circuit diagrams for AE1 SION Vacuum Circuit-Breakers AE5 and AE1 Standard scheme for plug connector 1st shunt release nd shunt release 1st c.t.-operated release 1st c.t.-operated release 5A Low energy c.t.-operated release Undervoltage release Electrical closing lock-out DC -Q0 -X0 C C -Q0 -X0 A D -Q0 -X0 A4 -Q0 -X0 A4 -Q0 -X0 A4 -Q0 -X0 C5 ) D5 -Q0 -X0 A5 -Q0 -S1 -Q0 -S1 -Q0 -S1 4 4 4 1 L N -V4.1 44 4 + A1 -Q0 -Y1 A 1) ) U A1 -Q0 -Y A 1) ) U A1 -Q0 -Y4 A 1) ) U A1 -Q0 -Y4.1 A 1) ) U A1 -Q0 -Y6 A 1) ) U D1 -Q0 -Y7 D 1) ) U -Q0 -F1 E1 E -Q0 -X0 D S_A7E_449_800_001 -Q0 -X0 B S_A7E_449_801_001 -Q0 -X0 B4 S_A7E_449_804_001 -Q0 -X0 B4 -Q0 -X0 B4 S_A7E_449_804_004 S_A7E_449_80_001 Order Zusatz code A49 A49 1 -Q0 -R1 -Q0 -X0 B5 S_A7E_449_806_001 -Q0 -X0 B1 HG11-84 eps S_A7E_449_800_001 Zusatz Order code A49 A49 Position switch for withdrawable part -Q0 -X01 1 5 7 -Q0 -X0 1 5 7 Q1 Withdrawable part -S1.0 1 -S1.1 14 1 -S1. 14 1 -S1. 14 1 -S1.4 14 1 14 -S1.5 1 -S1.6 14 1 -S1.7 14 1 -S1.8 14 1 -S1.9 14 1 14 HG11-847 eps -Q0 -X01 4 6 8 -Q0 -X0 4 6 8 S_A7E_449_8085_001 -Q0 -X0 A14 A15 A16 B14 B15 B16 C1 C4 -Q0 -X0 C15 C16 D1 D1 D14 D15 C1 C14 -Q0 -X01 1 4 5 6 7 8 -Q0 -X0 1 4 5 6 7 8 HG11-848 eps S_A7E_449_8085_00 Legend see page 76 74 Siemens HG 11.0 01

SION Vacuum Circuit-Breakers AE5 and AE1 Technical Data Circuit diagrams for AE1 Contact assignment for auxiliary switch Auxiliary switch 6NO/6NC Open Open Open Closed Open Closed Open Closed Open Closed Closed Closed Closed Open Closed Open Closed Open Closed Open Closed Open Closed Open Closed -Q0 -X0 C7 A8 C8 C8 A10 C10 A11 C11 A1 C1 A1 11 1 1 1 41 4 51 5 61 6 -Q8 -S1 1 14 4 4 4 44 5 54 6 64 1) 1) 1) 1) 1) 1) 1) 1) 1) 1) 1) 1) HG11-849 eps (-Y9) (-Y1) (-Y) (-Y7) S_A7E_449_8066_001 -Q0 -S1 11 1 1 14 1 4 1 4 41 4 4 44 51 5 5 54 61 6 6 64 71 7 7 74 81 8 8 84 91 9 9 101 10 111 11 11 1 94 10 104 11 114 1 14 1) ) ) ) ) ) ) ) ) ) ) -Q0 -X0 D7 B8 D8 D9 B9 C9 B10 D10 B11 D11 B1 D1 B1 HG11-846 eps Additional equipment Motor charging Closing and anti-pumping with mechanical interlocking and closing lock-out S_A7E_449_806_001 Hilfsschalter Auxiliary switch 1S/1Ö 1NO/1NC -Q0 -X0 A1 -Q0 -X0 A ) -Q0 -S1 1 A1 1) -Q0 -M1 M 1= U D -Q0 -S1 11 1 -Q0 -S 1 -Q0 -K1 1 1 14 -Q0 -K1 1 1) ) A1 -Q0 -Y9 A U -Q0 -K1 -Q0 -S5 1 14 -Q0 -S 1 -Q0 -S1 1 14 -Q0 -X0 ) D16 HG11-841 eps -Q0 -X0 B HG11-84 eps S_A7E_449_8001_001 S_A7E_449_8011_504 Legend see page 76 Siemens HG 11.0 01 75

Technical Data Circuit diagrams for AE1 SION Vacuum Circuit-Breakers AE5 and AE1 Additional equipment: Releases Signal: Spring charged Circuit breaker tipping signal Heating -Q0 -X0 A6 C6 -Q0 -X0 A7 -Q0 -X0 A7 -Q0 -S4 1 14 1 -Q0 -S6 1 -Q0 -R01 1 -Q0 -X0 B6 D6 HG11-844 eps -Q0 -X0 B7 -Q0 -X0 B7 HG11-845 eps S_A7E_449_04_001 S_A7E_449_804_001 S_A7E_449_8050_001 Zusatz Order code A0 A0 Legend (for pages 74 to 76) K1 Contactor (anti-pumping) M1 Motor operating mechanism Q0 Circuit-breaker wiring Q1 Wiring of withdrawable part R1 Resistance S1 Auxiliary switch S Position switch (anti-pumping) S4 Position switch (for closing spring charged) S5 Electrical closing lock-out S6 Circuit-breaker tripping signal S1 Mechanical interlocking S1 Position switches S (to de-energise the motor operating mechanism after charging) X0 X1 Y1 Y Y4 Plug connector, 4-pole or 64-pole Terminal strip, 7-pole 1 st shunt release nd shunt release Current-transformer operated release (rated normal current 0.5 A or 1 A) Y6 Y7 Y9 Current-transformer operated release (tripping pulse W 0.1 Ws) Undervoltage release Closing solenoid Abbreviations: NC = Normally closed NO = Normally open The circuit diagrams shown here are examples from the manifold possibilities of circuit-breaker wiring. 76 Siemens HG 11.0 01

SION Vacuum Circuit-Breakers AE5 and AE1 Technical Data Circuit diagrams for AE5 Standard scheme for plug connector 1st shunt release nd shunt release 1st c.t.-operated release 1st c.t.-operated release 5A Undervoltage release -Q0 -X1.1 4 -Q0 -X0 C -Q0 -X1.5.1 4 -Q0 -X1.5. -Q0 -X1.1 5 -Q0 -X0 D -Q0 -X1.1 5 -Q0 -X1.1 5 -Q0 -X1.1 7 -X1.1 5 -Q0 -S1 -Q0 -S1 4 4 44 A1 -Q0 -Y7 A 1) U -Q0 -S 4 A1 -Q0 -Y1 A 1) U A1 -Q0 -Y A 1) U -Q0 -Y4 A1 A -Q0 -Y6 A1 A -Q0 -X1.5. 4 -Q0 -X1.5.1 -Q0 -X1.1 -Q0 -X1.1 6 -Q0 -X1.1 6 -Q0 -X1.1 6 -Q0 -X1.1 6 HG11-855 eps S_A7E_449_4100_001 S_A7E_449_4100_010 S_A7E_449_4100_00 Part Teil des of basic Grundleitungssatzes wiring S_A7E_449_41099_010 S_A7E_449_4101_001 S_A7E_449_4104_001 S_A7E_449_410_001 S_A7E_449_4106_001 Position switch for withdrawable part Q1 -Q0 -X01 Withdrawable part -S1.0 1 1 -S1.1 14 1 -S1. 14 5 1 -S1. 14 7 1 -S1.4 14 -Q0 -X0 1 -S1.5 14 1 1 -S1.6 14 1 -S1.7 14 5 1 -S1.8 14 7 1 -S1.9 14 1 14 HG11-858 eps -Q0 -X01 4 6 8 -Q0 -X0 4 6 8 S_A7E_449_41085_001 -Q0 -X0 A14 A15 A16 B14 B15 B16 C1 C4 -Q0 -X0 C15 C16 D1 D1 D14 D15 C1 C14 -Q0 -X01 1 4 5 6 7 8 -Q0 -X0 1 4 5 6 7 8 HG11-859 eps S_A7E_449_41085_00 Legend see page 79 Siemens HG 11.0 01 77

Technical Data Circuit diagrams for AE5 SION Vacuum Circuit-Breakers AE5 and AE1 Contact assignment for auxiliary switch Auxiliary switch 6NO/6NC -Q0 -X0 C7 A8 C8 C8 A10 C10 A11 C11 A1 C1 A1 Open Closed Open Closed Open Closed Open Closed Open Closed Open Closed (-Y9) (-Y1) (-Y) (-Y7) 11 1 1 1 41 4 51 5 61 6 -Q8 -S1 1 14 4 4 4 44 5 54 6 64 1) 1) 1) 1) 1) 1) 1) 1) 1) 1) 1) 1) HG11-860 eps 11 1 1 1 41 4 51 5 61 6 71 7 81 8 91 9 101 10 111 11 11 1 -Q0 -S1 1 14 4 4 4 44 5 54 6 64 7 74 8 84 9 94 10 104 11 114 1 14 1) ) ) 1) ) 4) ) ) ) ) ) S_A7E_449_41066_401 -Q0 -X0 D7 B8 D8 D9 B9 C9 B10 D10 B11 D11 B1 D1 B1 HG11-857 eps S_A7E_449_4106_001 Additional equipment Closing and anti-pumping device -Q0 -X1. 7 Closing and anti-pumping device -Q0 -X1.5. 8 Closing and anti-pumping device 4 V - V 100 V - 17 V -Q0 -X1. Closing and anti-pumping device 48 V - 60 V 0 V - 40 V -Q0 -X1. 4 Closing and anti-pumping device 4 V - V 100 V - 17 V -Q0 -X1. Closing and anti-pumping device 48 V - 60 V 0 V - 40 V -Q0 -X1. 4 Closing and anti-pumping device -Q0 -X1. 8 -Q0 -X1.5.1 Motor charging 1 -Q0 -S 1 -Q0 -S -Q0 -S 11 1 1 A1 -Q0 -Y9 A -Q0 -S1 14 1 1) U -Q0 -M1 A1 M 1= D 1) U 14 -Q0 -X1. 6 -Q0 -X1. 5 -Q0 -X1.5. 7 -Q0 -X1.5. 7 -Q0 -X1.5. 9 -Q0 -X1.5. 9 -Q0 -X1.5.1 7 -Q0 -X1.5.1 9 HG11-85 eps -Q0 -X1.5.1 HG11-851 eps S_A7E_449_4101_001 S_A7E_449_4101_00 S_A7E_449_4101_00 S_A7E_449_4101_004 S_A7E_449_4101_005 S_A7E_449_4101_006 S_A7E_449_4101_010 Part Teil des of basic Grundleitungssatzes wiring S_A7E_449_41099_010 S_A7E_449_41001_010 Part Teil des of basic Grundleitungssatzes wiring S_A7E_449_41099_010 Legend see page 79 78 Siemens HG 11.0 01

SION Vacuum Circuit-Breakers AE5 and AE1 Technical Data Circuit diagrams for AE5 Additional equipment: Releases Motor charging Signal: Spring charged Circuit breaker tipping signal -Q0 -X1.1 1 -Q0 -X1.5. -Q0 -X1.1 -Q0 -X1. 1 0 8 -Q0 -X1. 1 -Q0 -X1. -Q0 -X1.5.1 5 -Q0 -X1. 8 -Q0 -S1 1 -Q0 -S4 1 14 1 -Q0 -S6 1 -R01 1 -Q0 -X1.5. 1 -Q0 -X1.1 HG11-850 eps -Q0 -X1.1 9-Q0 -X1.1 10 -Q0 -X1.5. 5 -Q0 -X1.5. 6 -Q0 -X1.5.1 6 -Q0 -X1. 9 HG11-856 eps S_A7E_449_41001_001 Closing and antipumping device -Q0 -K1 -Q0 -X0 -Q0 -X1.1 -Q0 -X1.1 1 1 A1 (-M1) D16 (-M1) D (-Y1) 4 4 C (-Y1) 5 5 6 6 7 7 8 8 C6 (-S4) 9 9 B6 (-S4) 10 10 D6 (-S4) -Q0 -X1. -Q0 -X1.4 1 1 A7 (-S6) B7 (-S6) (100-17 V) (100-17 V) 4 (0-40 V) 4 (0-40 V) B (-Y9) 5 5 A (-Y9) 6 6 7 7 8 8 (-R01) 9 9 (-R01 ) 10 10 S_A7E_449_4104_001 -Q0 -K1 -Q0 -X1.1 1 4 5 6 7 8 9 10 Closing and antipumping device -X1. 1 4 5 6 7 8 9 10 -Q0 -X1. 1 -Q0 -X1.4 (4 - V) 4 (48-60 V) 5 6 7 8 9 10 10 S_A7E_449_4104_001 1 (4 - V) 4 (48-60 V) 5 6 7 8 9 -Q0 -X0 A1 D16 D C C6 B6 D6 A7 B7 B A (-R01) (-R01 ) (-M1) (-M1) (-Y1) (-Y1) (-S4) (-S4) (-S4) (-S6) (-S6) (-Y9) (-Y9) S_A7E_449_4104_010 Part Teil des of basic Grundleitungssatzes wiring S_A7E_449_41099_010 S_A7E_449_41050_001 Order Zusatzcode A0 HG11-85 eps HG11-854 eps S_A7E_449_4101_051 S_A7E_449_4101_05 Legend (for pages 77 to 79) K1 Contactor (anti-pumping) M1 Motor operating mechanism Q0 Circuit-breaker wiring Q1 Wiring of withdrawable part R1 Resistance S1 Auxiliary switch S Position switch (anti-pumping) S4 Position switch (for closing spring charged) S5 Electrical closing lock-out S6 Circuit-breaker tripping signal S1 Mechanical interlocking S1 Position switches S (to de-energise the motor operating mechanism after charging) X0 X1 Y1 Y Y4 Plug connector, 4-pole or 64-pole Terminal strip, 7-pole 1 st shunt release nd shunt release Current-transformer operated release (rated normal current 0.5 A or 1 A) Y6 Y7 Y9 Current-transformer operated release (tripping pulse W 0.1 Ws) Undervoltage release Closing solenoid Abbreviations: NC = Normally closed NO = Normally open The circuit diagrams shown here are examples from the manifold possibilities of circuit-breaker wiring. Siemens HG 11.0 01 79

SION Vacuum Circuit-Breakers AE5 and AE1 R-HG11-181.tif 80 Siemens HG 11.0 01

SION Vacuum Circuit-Breakers AE5 and AE1 Annex Contents Contents Page Annex 81 Inquiry form 8 Configuration instructions 8 Configuration aid Foldout page Switchgear Factory in Berlin, Germany R-HG11-180.eps 4 Siemens HG 11.0 01 81

Annex Inquiry form SION Vacuum Circuit-Breakers AE5 and AE1 Please copy, fill in and return to your Siemens partner or you can use our prompted online configurator under www.siemens.com/sion 4 Inquiry concerning SION vacuum circuit-breaker from 7. to 4 kv Please Submit an offer Call us Visit us Your address Company Dept. Name Street Postal code / city Country Phone Fax E-mail Siemens AG Dept. Technical data Other values Rated voltage 7. kv 1 kv 17.5 kv 4 kv kv Rated lightning impulse 60 kv 75 kv 95 kv 15 kv kv Rated short-duration 0 kv 8 kv 8 kv power-frequency 4 kv 50 kv 55 kv kv Rated short-circuit 1.5 ka 16 ka 0 ka breaking current 5 ka 1.5 ka 40 ka ka Rated normal current 800 A 150 A 000 A 500 A 150 A A Pole-center distance 150 160 10 75 Width across flats 05 75 10 Secondary equipment For possible combinations see pages 1 to 6 Circuit-breaker equipment Fixed Withdrawable part, contact arms mounting Withdrawable part, contact arms, bushings Withdrawable module with earthing switch Withdrawable module without earthing switch Retrofit Motor operating mechanism V DC V AC, Hz Closing solenoid V DC V AC, Hz 1 st shunt release V DC V AC, Hz nd shunt release V DC V AC, Hz Current-transformer operated release Undervoltage release V DC V AC, Hz Auxiliary switch 6 NO + 6 NC 1 NO + 1 NC Low-voltage connection 0- or 7-pole 4-pole 64-pole terminal strip plug plug Mechanical interlocking Circuit-breaker tripping signal Electrical closing lock-out Operating instructions German English French Spanish Name Application and other requirements Street Postal code / city Country Fax Please check off Please fill in 8 Siemens HG 11.0 01

You prefer to configure your SION vacuum circuit-breaker on your own? Please follow the steps for configuration and enter the order number in the configuration aid. Alternatively you can also use our prompted online configurator under www.siemens.com/sion. Instruction for configuration of the SION vacuum circuit-breaker 1 st step: Definition of the circuit-breaker and equipment package (see pages 18 to 0) Please specify the following ratings: Rated voltage (U r ) Rated lightning impulse (U p ) Rated short-duration power-frequency (U d ) Rated short-circuit breaking current (I SC ) Rated normal current (I r ) Pole-center distance Width across flats Possible options: U r : 7. kv to 4 kv U p : 60 kv to 15 kv U d : 0 kv, 8 kv, kv, 4 kv, 55 kv, 65 kv I SC : 16 ka to 40 ka I r : 800 A and 150 A 150 to 75 05 to 10 These ratings define the positions 5 to 8 of the order number. nd step: Definition of the secondary equipment (see pages 1 to 6) Please specify the following equipment features: Release combination (position 9) Closing solenoid (position 10) Operating voltage of the releases (positions 11 / 1) Installation accessories (position 1) Motor operating mechanism (position 14) Number of auxiliary contacts (position 15) Design of the secondary connection (position 15) Mechanical interlocking, circuit-breaker tripping signal (position 15) Language of the documentation (position 16) Frequency of the operating voltage of the secondary equipment at AC (position 16) Possible options: Shunt release, current-transformer operated release and undervoltage release Operating voltages from 4 V DC to 40 V AC Operating voltages from 4 V DC to 40 V AC Fixed mounting, with withdrawable part, with contact, fixed contact, bushing, cartridge, with / without earthing switch, retrofit 8B Operating voltages from 4 V DC to 40 V AC 6 NO + 6 NC, 1 NO + 1 NC 0- or 7-pole terminal strip, 4-pole plug connector 64-pole plug connector With or without English, German, French, Spanish, Russian, further languages on request DC or AC 50 Hz; 60 Hz These equipment features define the positions 9 to 16 of the order number. rd step: Do you have any further requirements concerning the equipment? (Please refer to page 7) Should you still need more options than the possible special equipment like halogen-free and flame-retardant or silicone-free design, condensation protection or an additional rating plate, etc., please contact your responsible sales partner. Siemens HG 11.0 01 8

For configuration of your SION vacuum circuit-breaker 1 4 5 6 7 8 9 10 11 1 1 14 15 16 A E Z See page 18 to page 0 See page 1 See page 1 See page See page See pages +4 See page 4 See page 5 See page 6 See page 7 A E + + + + + + + + A E + + + + + + + + A E + + + + + + + + A E + + + + + + + + A E + + + + + + + + A E + + + + + + + + A E + + + + + + + + A E + + + + + + + +