Installation of over voltage protection in LV systems Denis Imširović, B.SC.E.E.

Similar documents
Lightning current simulation in the laboratory - parameters, procedures and test equipment -

SANS : 2008 CODE OF PRACTICE THE WIRING OF PREMISES Part 1 : Low Voltage Installation

SURGE PROTECTIVE DEVICES

CATALOGUE SURGE PROTECTION LOW VOLTAGE

This is a preview - click here to buy the full publication TECHNICAL REPORT

Power surges can also be generated by equipment in your facility such as:

AN Surging Ideas TVS Diode Application Note PROTECTION PRODUCTS. TRANSIENT IMMUNITY STANDARDS: IEC x

Bourns Resistive Products

Transient and Lightning Protection for the Water Industries

Main catalog. System pro M compact Surge and lightning protection solutions with QuickSafe technology

38 Series - Relay interface modules A

wietap wietap Overvoltage Protection Tensions running high

Type: EASY719 DC RC Article No.: Ordering information Relay outputs Quantity 6 Power supply V DC 24 V DC. Description

INTERNATIONAL STANDARD

THE LIGHTNING PROTECTION INTERNATIONAL STANDARD

POWER AND VOLTAGE RATING

Class I surge protection with sparkover gaps

38 Series - Relay interface modules A

The power of nature, the control of technology From ABB's experience, OVR PV: surge protection in photovoltaic plants

34 Series - Slim electromechanical PCB relays 6 A. Features SERIES 34.51

48 SERIES Relay interface modules 10 A

DS 600. A contact free flux gate based current measurement sensor 600A rms

pole, 8 A Safety relay. Screw terminal. 35 mm rail (EN 60715) mounting. 2 CO (DPDT) 8/15 250/400 2, /0.65/0.

Safety technique. Emergency stop module BO 5988 safemaster

Reyrolle Protection Devices. 7PG17 - XR Intertripping, Interposing, Supervision and Special Purpose Relays. Answers for energy

HOW TO SELECT VARISTORS

How to design SMPS to Pass Common Mode Lightning Surge Test

38 SERIES. Relay interface modules A. EMR Electromechanical Relays. Common features. SSR Solid State Relays. 6.

40 Series - Miniature PCB/Plug-in relays A. Features

Electronic timer CT-VBS OFF-delayed without auxiliary voltage, for DC contactors Data sheet

Product Safety Considerations for Insulation Coordination of Low- Voltage Equipment. Scott Aldous, Compliance Engineer

AN1826 APPLICATION NOTE TRANSIENT PROTECTION SOLUTIONS: Transil diode versus Varistor

Instrument Transformers Application Guide

1 pole, 16 A Screw terminal connection 35 mm rail (EN 60715) mounting. 2 pole, 8 A Screw terminal connection 35 mm rail (EN 60715) mounting

Protection ICs Insurance for Electronic Devices

Drive circuit basics + V. τ e. Industrial Circuits Application Note. Winding resistance and inductance

Surge protection for emergency alarm systems

RM17TE V AC. Main. Product or component type. Product specific application. Relay monitored parameters 250 V DC 5 A DC

IEC ESD Immunity and Transient Current Capability for the SP72X Series Protection Arrays

RM4TG20 three-phase network control relay RM4-T - range V

How To Make A Power Meter Safe

49 Series - Relay interface modules A. Features

0.8 U N /0.5 U N 0.8 U N /0.5 U N 0.8 U N /0.5 U N 0.2 U N /0.1 U N 0.2 U N /0.1 U N 0.2 U N /0.1 U N

IEC >>> IEC GUIDE GLOBAL SPECIALIST IN ELECTRICAL AND DIGITAL BUILDING INFRASTRUCTURES

The Importance of the X/R Ratio in Low-Voltage Short Circuit Studies

Surge Protection for Photovoltaic Systems

ALTERNATIVE METHODS FOR INTERNAL ARC TESTS ON 12 KV AND 24 KV METAL-ENCLOSED SWITCHGEARS WITH COMPACT RMU

Electrical safety requirements in DC distribution systems

Pulse Withstanding Thick Film Chip Resistor-SMDP Series. official distributor of

Three-phase monitoring relay CM-PFE

SUITABILITY OF DIFFERENT TEST VOLTAGES FOR ON-SITE TESTING OF XLPE CABLE SYSTEMS

Single-phase ( V) voltage monitoring: Undervoltage Overvoltage Window mode (overvoltage + undervoltage) Voltage fault memory selectable

A Practical Guide to Dielectric Testing

Electrical safety and protection devices

How To Understand The Electrical Power Supply Of A Power Supply System

Lightning Arresters P KVA P KVA. Description & Installation

LOW VOLTAGE RING TYPE MEASURING CURRENT TRANSFORMERS

Coordination of Telecommunications Surge Protective Devices in Countries with Unstable AC Power

AN Surging Ideas TVS Diode Application Note PROTECTION PRODUCTS. Secondary Transient Protection for T1/E1 Line Cards

HERZ-Thermal Actuators

ISL Insulation monitoring devices Continuous monitoring of IT systems from photovoltaic to industrial applications.

Substation Grounding Study Specification

Guidance for upgrading to GB (IEC : 2005, MOD)

Circulating Current Relay. Type IRXm

ABB 1. Three-phase monitoring relay CM-PFS. Data sheet. Features. Approvals. Marks. Order data. Order data - Accessories. Application.

The complete range of consumer switchboards and switchgear

Relés e Contatores de Estado Sólido SIRIUS

Section B: Electricity

Telecommunication Line Protectors

A series of technology briefs spanning Tyco Electronics product portfolio

R.C.C.B. s two-pole LEXIC

Positive-guided relay outputs: 3 safety contacts (N/O), instantaneous. 1 auxiliary contact (N/C), instantaneous

Tamura Closed Loop Hall Effect Current Sensors

TYPE TEST CERTIFICATE OF SHORT-CIRCUIT PERFORMANCE. A three-phase outdoor oil-immersed distribution transformer

E-STOP relays, safety gate monitors

e 2 ALPHA Medium Voltage Switchgear Data Sheet K EN

SF 6 Gas Insulated Switchgear Type SDF for 170 kv

EVALUATION OF CURRENTS AND CHARGE IN SURGE PROTECTIVE DEVICES IN LOW-VOLTAGE DISTRIBUTION NETWORKS DUE TO DIRECT LIGHTNING STRIKES

Intersection Preassembled 19-inch Rack

3-Phase Energy meter with serial S-Bus interface

Power Supply, Primary Switch Mode, Narrow Design MINI-PS AC/2x15DC/1

Transformerless UPS systems and the 9900 By: John Steele, EIT Engineering Manager

Electronic timer CT-AHD.12 OFF-delayed with 1 c/o (SPDT) contact

Redline. Comfort functions. Surge Arresters. SurgeGuard. Functions. Applications. Standards. Features. Marking. plug-in

Fault location on power cables. Fault location on power cables

3) What is the difference between "Insulating", "Isolating", and "Shielded Winding" transformers?

RC NETWORKS SALES GUIDE

ELEMKO reserves the right to modify, add or remove any information included in this catalogue, if necessary. Every updated version of the catalogue

Power Resistor for Mounting onto a Heatsink Thick Film Technology

Thermistor motor protection relays CM-MSS.22 and CM-MSS.23

LUXEON LEDs. Circuit Design and Layout Practices to Minimize Electrical Stress. Introduction. Scope LED PORTFOLIO

DEHNshield Application-optimised multipole combined lightning current and surge arrester

GUIDE FOR TESTING POWER TRANSFORMERS

7. Reactive energy compensation

Thermistor motor protection

How To Build A Low Voltage Capacitor Lvcp

Part 1 System Modeling & Studies for Existing Systems

Exploring the Necessity of the Hot Hipot Test

However, industrial applications may utilize a relay, which short-circuits the ICL path after the inrush sequence.

SAMPLE OF THE STUDY MATERIAL PART OF CHAPTER 3. Symmetrical Components & Faults Calculations

Transcription:

Installation of over voltage protection in LV systems Denis Imširović, B.SC.E.E. From old times the human beings have been fascinated by the lightning phenomenon, but unfortunately they were unable to explain it. Nowadays, in the era of computers and other sensitive devices it has become necessary to expand technical possibilities for successful or complete protection of vitally important services 1. Introduction Technology is entering into the future with big steps; therefore the devices are installed into the areas where can not be imagine a while ago. An enormous quantity of information is used over the world, which must be properly connected, reach faster transfers and use best possible protection. Now days especially in such an economically and technically developed world there is no possibility to refuse those demands. Over voltage protection must be considered, as hard cuirass which protects devices and people against strong outside influences, as stroke of lightning and prevent technological and economical damage. Over voltages are caused because of following: Atmospheric discharges resulting in direct strikes to structures or systems, or large induced voltages caused by those direct strikes Over-voltage cause by power switching transients Faults in power distribution systems such as line-to-ground contacts, or commingling of power and low voltage telecommunication lines Power regulation faults as can occur near large industrial consumers of power or near electrified rail systems The statistic of damages caused on electrical apparatus is demonstrated in below graph (Picture 1). The biggest share damage on electrical apparatus is caused because of over voltages and ranges between 27% and 35%. Picture 1: Ratio of different damage causes

2. Installation of over voltage protection Manufacturer can produce very quality product, but in case surge protection device is installed incorrectly into the system, there is no assurance for proper protection. Different type of surge protection devices are used according to the different network systems; therefore it is very important to ensure that surge protection device is correctly selected and coordinated with the type of power system in use and any over-current protection devices installed. To reach maximum level of protection, following points must be considered: proper selection of surge protection device according to the network system to create more levels of protection, consider the length of the ground conductors. define voltage protective level U p. 2.1. Different type of impulses and currents Before starting to write down on paper, define and even discuss about over voltage theme, defined supposition were needed. Simulation of short peak over voltages and atmospheric discharges demand precise definition of short current peaks and short voltage peaks. Standard IEC 61643 describe three types of impulses: energy current impulse 10/350, current impulse 8/20, voltage impulse 1,2/50. Energy current impulse 10/350, I imp Direct strikes can be simulated with energy current impulse 10/350. It is used to define Iimp current also, which can be according to IEC 61643 standard used, as energy current impulse for testing surge protection devices class I. According to standard the time 10µs is rise time of energy current impulse from 10% up to 90% of value, meanwhile 350µs is fall time from 90% to 50% of value. Standard allows 20% of deviation also. Current impulse 8/20, I n and I max Indirect strikes can be simulated with current impulse 8/20. It is used to define I n and I max. and both currents according to IEC 61643 standard can be used, as current impulse for testing surge protection devices class II. Maximum current, I max represent double value of nominal current, I n or according to different manufacturer technical data. According to standard the time 8µs is rise time of current impulse from 10% up to 90% of value, meanwhile 20µs is fall time from 90% to 50% of value. Standard allows 20% of deviation also. - 2 -

Voltage impulse 1,2/50, U oc Surge protection devices class III are tested according to the IEC 61643 standard with combine waves, voltage 1,2/50 and current wave 8/20. The combination wave is delivered by a generator that applies a 1,2/50 voltage impulse across an open circuit and an 8/20 current impulse into a short circuit. Voltage impulse is defined, as U oc and current at short circuit as I sc. Standard define time 1,2µs as rise time of voltage impulse from 30% up to 90% of value, meanwhile 50µs is fall time from 90% to 10% of value. Standard allows 20% of deviation also. Picture 2: difference between shape of waves 10/350 and 8/20 Picture 3: Wave 8/20 Above picture (picture 2) illustrate the difference between current impulses shape of waves 10/350 and 8/20. Square dimension under curve can be imagining, as energy of the strike. According to energy equation or Joule integral easy calculation can be done to proof that energy at direct strike is much higher. Calculation: I 2 x t (1) Direct strike; Indirect strike; I 2 x t = 25kA 2 x 350 x 10-6 s = I 2 x t = 5kA 2 x 20 x 10-6 s = = 218kJ = 500J 2.2. Determination of voltage protective level, Up Up, voltage protective level, which appears at surge protective device s terminals at presence of impulse with exact shape and amplitude. Main rule at surge protective device connection is to mount and connect it between phase and ground conductor (PE or PEN) or parallel to the protected element, as shown on below picture (picture 5). When atmospheric discharge or short peak voltage appears preliminary characteristics of installed varistor changes shape and arrestor goes to conducting stage. Reaction can be imagining, as closing switch and superfluous current flows into ground. Installed varistor is non-linear resistor and under normal condition it has very big resistance, at short peak voltage or atmospheric discharge the situation becomes inversely, it means low resistance and conducting stage all superfluous energy leads to the ground. - 3 -

Picture 4: Voltage level without arrester Picture 5: Voltage level with arrester The goal of over voltage protection is to reach lower value of voltage level, as dielectric withstand of protected equipment. According to the standard IEC 61643 devices are divided into four groups-categories. Dielectric withstand must be given by the each manufacturer. Dielectric withstand according to category Category Dielectric withstand (kv) I 6 II 4 III 2,5 IV 1,5 Table 1: Dielectric withstand according to the category 2.3. Proper length of ground conductors Main cause for irregular function of over voltage protection elements is un-considering the length of ground conductor PE, PEN. The length of the conductors influences additional inductive voltage drop as follows; a conductor length of 1m has an inductance of approximately 1μH, which at current steepness of 1kA/μs contributes approximately 1kV. Difference of voltage which appears because of additional conductor length must be considered with arresters Up voltage level, when reaching proper result. U=L x di/dt (2) U=5µH x 1kA/µs U=5kV Slika6: additional inductive voltage Therefore the surge protection devices must be installed with the sense of decreasing the length of connected conductors between phase and ground terminals. Example on next page (picture 8) demonstrate proper way of mounting and maximal conductor length. Cross-section of ground conductor must be considered, as following: - 4 -

class I: minimal 16mm 2, class II,III: minimal 6mm 2. Picture 7: Proper installation and maximum conductor length 2.4. Protecting zones and creating higher level of protection Protecting zones and cross points of protecting zones, where over voltage protection is installed are provided by the manufacturer. Protecting zones are divided into three levels. Places or connection points are: MB, SB in SA. Picture 8: Protecting levels At point MB (main distribution board) which is at crossing OB/1 and is subject to partial direct lightning strikes class I surge protection devices must be installed. Class I surge protection devices are those declared for current arrester pulses 10/350 μs. At point SB (sub distribution board) which is at crossing 1/2 and is subject to indirect lightning strikes class 2 surge protection devices must be installed. Class II surge protection devices are those declared for current arrester pulses 8/20 μs. At point SA (socket outlet) which is at crossing 2/3 and is subject to indirect lightning strikes, a class III surge protection devices must be installed. Class III surge protection devices are those declared for combined voltage pulses 1,2/50 and current pulses 8/20. Arresters class III are used, when very sensitive equipment is intended to protect, with dielectric withstand category IV and it is installed always behind arresters class I, II. When secondary or cascade level of protection is chosen, the manufacturer must provide table of Up values. Picture 9: Diagram of characteristic values Up (kv) in dependence of current (ka) - 5 -

2.5. Proper installation of protection according to the network systems For proper installation the over voltage arrester must be mounted into the system between phase (L) and ground conductor (PEN, PE). In TN-S and IT systems surge protection device must be installed between neutral N and ground conductor PE either. In TT systems special rule is valid; it means gas discharge tube must be installed between neutral N and ground PE conductor. Gas discharge tube is needed in case of phase-ground connection the high potential is transferred to the earth and housing of apparatus, which is not connected to the same potential level may present risk for human life. Gas discharge tube installation reaches galvanic separation between conductors and breaking of electrical circuit in first period. Picture 10: TNC-S system connection Picture 11: TNS system connection Picture 12: TT system connection Picture 13: IT system connection 3. CONCLUSION To reach maximum over voltage protection of equipment, at least above mentioned parameters must be considered. The theme over voltage protection is day by day closer to our lives, because of human nature, which is a cause, that short peaks voltages appears more and more into our homes. A fact is, that LV over voltage arresters represent big business potential, because some of countries put already a regulative that every new electro installation must include over voltage protection as well. - 6 -