Rosemount 333 HART Tri-Loop

Similar documents
Rosemount 333 HART Tri-Loop

Rosemount 752 FOUNDATION fieldbus Remote Indicator

Rosemount 1199 Submersible Seal

Rosemount 1199 Submersible Seal

Rosemount 751 Field Signal Indicator

THE WORLD'S FIRST WIRELESS GUIDED WAVE RADAR

How To Connect An Hart Tri Loop To A Model 333 Hart To Analog Signal Converter

Reliable Pressure Measurement with Remote Diaphragm Seals in Cold Weather Applications

Import the Gateway Certificate to the Browser

Mobrey Ultrasonic. MSP900SH Level and MSP900FH Flow Transmitters. Product Data Sheet February 2015 IP2032, Rev BA

Replacing Displacers with Guided Wave Radar

Quick Start Guide , Rev DA March Rosemount 8714D (Calibration Standard) Magnetic Flowtube Simulator

Techniques for Interconnecting Smart Wireless Gateways to ProSoft RadioLinx Devices

Rosemount 5300 and 5400 Series Terminal Compartment Spare Part Instruction

Rosemount 708 Wireless Acoustic Transmitter

Analog signal converters CC-E I/I Current / current isolators

Model 3051 Pressure Transmitter with HART Protocol

Model: DC-A2IO Advanced HVAC Controller

DeltaV SISnet Repeater

Rosemount D Solids Scanners for Bulk Solids Inventory and Financial Reporting

S-series Mass Connection Solutions

LEVEL AND VOLUME MEASUREMENTS OF BULK SOLIDS

Rosemount 3095 MultiVariable Transmitter with MODBUS Protocol ProductDiscontinued

Differential Pressure Sensors for air and non-corrosive gases, with calibration certificate

Zlinx Wireless I/O. Peer-to-Peer and Modbus I/O B&B ELECTRONICS PRODUCT INFORMATION

Rosemount 248 Temperature Transmitter

3DLevelScanner II TECHNICAL DATA SHEET

Electronic Control Devices The European Product Catalogue 2007

Best Practices for Reducing Transmitter Life Cycle Costs

Isolating Barriers for our sensors A5S1 in Ex-areas Series D461

TM7BDM8B expansion block - TM7 - IP67-8 DI/DO - 24V DC A - M8 connector

Rosemount 248 Wireless Temperature Transmitter

HARDWARE MANUAL. Ixx24-A 1/20. Val Controls A/S Limfjordsvej 3 DK-6715 Esbjerg N Tel vc@valcontrols.com

Emerson Smart Wireless Gateway Solutions

38 Series - Relay interface modules A

Electro-Magnetic Flowmeters COPA-XT 2-Wire DT43

EMERSON S ROSEMOUNT PROJECT MANAGEMENT OFFICE. Delivering project success for your instrumentation

38 Series - Relay interface modules A

1.1 Fill fluids. Rosemount DP Level Fill Fluid Specifications July Technical Note , Rev DB

Digital input modules

80 Series - Modular timers 16 A. Features

Type: EASY719 DC RC Article No.: Ordering information Relay outputs Quantity 6 Power supply V DC 24 V DC. Description

Waveguide Access Point WGA631. Product Guide

Dynamic Pressure Charge Amplifier

CONTROLS DATA MANAGEMENT PROCESS AUTOMATION EUROCUBE. General purpose single phase thyristors and solid state relays Product data.

J TB/TW Temperature limiter, temperature monitor

Micro Motion Model 2200S Transmitters

Automation System TROVIS 6400 TROVIS 6493 Compact Controller

Electronic Control Devices The European Product Catalogue 2007

Certified according to DIN EN ISO 9001 Technical Datasheet KVO Series Vortex Flow Meter

Process modules Digital input PMI for 24 V DC inputs for 120 V AC inputs

MCR-VDC-UI-B-DC. Voltage Transducer for DC Voltages. INTERFACE Data Sheet _en_01. 1 Description

Brooks Models SLA5850, SLA5851, SLA5853 Mass Flow Controllers and Models SLA5860, SLA5861, SLA5863 Mass Flow Meters

3500/62 Process Variable Monitor

pole, 8 A Safety relay. Screw terminal. 35 mm rail (EN 60715) mounting. 2 CO (DPDT) 8/15 250/400 2, /0.65/0.

Ordering Part Numbers: Universal Signal Converter: USC-CVB Universal Signal Converter with a 4-20mA input and +/- 10V output: USC-CVB225-B10V

2002 IS Catalog. Page

38 SERIES. Relay interface modules A. EMR Electromechanical Relays. Common features. SSR Solid State Relays. 6.

Technical Data Sheet. 3DLevelScanner

Power Supply Unit, Primary Switched, Narrow Design MINI-PS-12-24DC/24DC/1

Features. Picture. Specifications

80 Series - Modular timers 16 A. Features

How To Control A Power Supply With A Mini Transmitter And Switch (Power Supply)

1701/22 FieldMonitor Management Interface Module

SEZ220. Signal Converter. Synco 200. With preprogrammed standard applications Freely programmable Menu-driven operation. Use

Mobrey Hydrastep and Hydratect

Unidirectional Transmitter/ Receiver Units Introduction

Regards from the Team at Rheology Solutions.

Duct Humidity Transmitter

Rosemount 2088 Absolute and Gage Pressure Transmitter

Isolated AC Sine Wave Input 3B42 / 3B43 / 3B44 FEATURES APPLICATIONS PRODUCT OVERVIEW FUNCTIONAL BLOCK DIAGRAM

Telephone- and leased line modem for industrial applications TD-36

TX OPEN RS232/485 module

MINI MCR-SL-R-UI(-SP)

JNIOR. Overview. Get Connected. Get Results. JNIOR Model 310. JNIOR Model 312. JNIOR Model 314. JNIOR Model 410

93.68/ Time scale: from 0.1s to 6h Multi-function For use with (EMR) and (SSR) relays. Screw terminal and push-in terminal

QFP910. Water detector. Building Technologies. CE1N2732en. Synco living

Control Devices Catalogue. Control Devices. Preferred and Standard Products

S-series DeviceNet Interface Card

CQM1-SF200/CS1W-SF200

MLC TM Maximum Productivity and Versatility for Control without Compromise!

Input signal Maximum Range Accuracy. Thermocouple E -50 to 700 C (-58 to 1832 F) ±1 C

Series AMEPR30-AZ up to 2.5A AC-DC / DC-DC LED Driver / Converter

WD-AMX Water Detection Controllers

Contents. Document information

Level Instrumentation for the Refining Industry

Single-phase ( V) voltage monitoring: Undervoltage Overvoltage Window mode (overvoltage + undervoltage) Voltage fault memory selectable

Three-phase monitoring relay CM-PFE

MasterINTERFACE 39 Series - Relay interface modules

Voltage monitoring relays CM-ESS.M For single-phase AC/DC voltages

Current valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw

S-series DC to DC Power Supply

Analogue Input, 4-fold, MDRC AE/S 4.1, GH Q R0001

CompactLogix Power Supplies Specifications

FOSTCDR. Industrial Serial to Multimode Fiber Optic Converter PRODUCT INFORMATION B&B ELECTRONICS. Specifications Serial Technology

Temperature monitoring relays CM-TCS Monitoring relays for monitoring temperatures with a PT100 sensor (2- or 3-wire connection)

APT3200 SMART PRESSURE TRANSMITTER. Application Areas: For Gauge And Absolute Pressure Measurement

RHE12. Hazardous Area Coriolis Mass Flow Transmitter. Features. Applications. Benefits

Monitoring Water Quality For Today s Demanding World

DISCONTINUED PRODUCT. Infrastructure Management & Monitoring For Business-Critical Continuity. Liebert icom-do. User Manual

Transcription:

Product Data Sheet September 2014 00813-0100-4754, Rev GA Rosemount 333 HART Tri-Loop HART-to-Analog Signal Converter Convert a digital HART signal into three additional analog signals Easy to configure and install Accessory product for multivariable instruments Available as either High-alarm or Low-alarm device

Rosemount 333 September 2014 HART Tri-Loop HART-to-Analog Signal Converter Convert a digital HART signal into three analog signals Convert a multivariable digital HART signal into independent 4-20 ma analog process variables using the Rosemount 333 HART Tri-Loop. Apply in control or monitoring applications to obtain up to three additional analog outputs without additional process penetrations. Accessory product for multivariable instruments For use with the Rosemount 3051S MultiVariable, 3051S Advanced HART Diagnostics, and 3144P products. When used with the 3051S MultiVariable Transmitter, the 333 HART Tri-Loop allows possible outputs of Differential, Absolute or Gage pressure, Process Temperature, Mass or Volumetric Flow, Energy Flow, Totalized Flow, and Sensor Module Temperature. When used with the 3051S Advanced HART Diagnostics, possible outputs include Pressure, Sensor Module Temperature, Scaled Variable, Standard Deviation, and Mean. When used with the Rosemount 3144P, possible outputs include Sensor 1, Sensor 2, Differential and Transmitter Terminal Temperature. Easy to configure and install The 333 HART Tri-Loop is easy to configure and maintain using the 475 Field Communicator. AMS Device Manager provides easy PC-based user configuration. Installation is quick and easy with three DIN rail mount options and electrically isolated analog output channels for flexible grounding. Available as either high-alarm or low-alarm device Tri-Loop alarm channels are factory configured. All channels alarm if the attached device indicates a sensor failure or transmitter malfunction. Figure 1. Example Tri-Loop Installation with Rosemount 3051S MultiVariable Transmitter HAZARDOUS AREA DIN Rail Mounted HART Tri-Loop Each Tri-Loop Channel receives Ch. 3 power from Control Room Ch. 2 Ch. 1 Burst Input to Tri-Loop Channel 1 must be powered for the Tri-Loop to operate Rosemount 3051S MultiVariable Transmitter RL 250 Ω HART Burst Command 3/ Analog Output Intrinsically Safe Barrier Device receives power from Control Room for Primary Variable Loop Control Room NON HAZARDOUS AREA Contents Ordering Information... 3 Specifications...3 2 Dimensional Drawings...5

September 2014 Rosemount 333 Ordering Information Specification and selection of product materials, options, or components must be made by the purchaser of the equipment. See page 4 for more information on Material Selection. Table 1. Rosemount 333 HART Tri-Loop The Standard offering represents the most common options. The starred options ( ) should be selected for best delivery. The Expanded offering is subject to additional delivery lead time. Model Product description 333 HART Tri-Loop Alarm option U High Alarm D Low Alarm Configuration option C2 Custom Configuration (Configuration Data Sheet must be completed) Typical model number: 333 U Specifications Functional specifications Service Accessory product for use with the 3051S MultiVariable Transmitter, 3051S Advanced HART Diagnostics Transmitter, 3144P Temperature Transmitter, or any other HART device with a burst mode output. Output One, two, or three 4 20 ma user-selectable output signals. Device 3051S MultiVariable 3051S 3144P Power supply External power supply required for each channel. Each channel operates on terminal voltage of 11 42.4 Vdc. Note Channel 1 must be powered for Tri-Loop operation. Output options DP, AP, GP, PT, Mass or Volumetric, Energy Flow, Totalized Flow, and Sensor Module Temperature. Pressure, Sensor Module Temperature, Scaled Variable, Standard Deviation, and Mean. Sensor 1, Sensor 2, Differential Temperature, or Transmitter Terminal Temperature. Load limitations Loop resistance is determined by the voltage level of the external power supply, as described below: Max. Loop Resistance = Power Supply Voltage-11.0 0.022 Load (Ohms) 1400 1200 1000 800 600 400 200 Turn-on time Analog signals will be within specifications five seconds after power is applied to Tri-Loop. Installation locations Approved for FM ordinary locations, approved for CSA ordinary locations. Temperature limits Ambient 50 to 104 F (10 to 40 C) Storage 40 to 158 F ( 40 to 70 C) Operating Region 0 10 20 30 40 42.4 Power Supply Voltage, Vdc 3

Rosemount 333 September 2014 Humidity limits 0 95% non-condensing relative humidity Failure mode alarm If Tri-Loop diagnostics detect a Tri-Loop failure or the transmitter indicates a transmitter malfunction, the analog signal for all channels will be driven either below 3.75 ma or above 21.75 ma to alert the user. The high or low alarm signal is determined by the Tri-Loop Model Number, see Alarm configuration on page 4. Performance specifications (Performance specifications are for the HART Tri-Loop only.) Reference accuracy ±0.045% of span Ambient temperature effect per 50 F (28 C) ±0.15% of span Stability ±0.1% of span for 12 months Analog output update Tri-Loop responds to every HART burst update (typical transmitter burst update rate: 0.3 to 0.5 s.) Tri-Loop Response Time (after each burst update) Channel 1:120 ms; Channel 2:220 ms; Channel 3:320 ms Total Response Time Typical response time from sensor change to transmitter to Tri-Loop analog update: 0.7 to 1.0 seconds. Electromagnetic Compatibility (EMC) Meets all relevant requirements of EN 61326-1:2006 ESD tested to 4 kv contact and 4 kv air EM field immunity from 80 MHz to 1 GHz tested to 3 V/m Limits of performance criterion A defined as < ± 0.1% of span Physical specifications Material selection Emerson provides a variety of Rosemount products with various product options and configurations including materials of construction that can be expected to perform well in a wide range of applications. The Rosemount product information presented is intended as a guide for the purchaser to make an appropriate selection for the application. It is the purchaser s sole responsibility to make a careful analysis of all process parameters (such as all chemical components, temperature, pressure, flow rate, abrasives, contaminants, etc.), when specifying product materials, options, and components for the particular application. is not in a position to evaluate or guarantee the compatibility of the process fluid or other process parameters with the product options, configuration, or materials of construction selected. Electrical connections Screw clamps. Accepts 24 12 AWG solid or stranded wire. Dimensions 1.57 x 3.11 3.36 in. (40 79 85,5 mm) DIN rail mounting options Asymmetrical 32 mm G rail, symmetrical 35 x 7.5 mm top hat rail, or symmetrical 35 x 15 mm top hat rail (see Tri-Loop Dimensions on page 5). Weight 0.27 lb (0,12 kg) Alarm configuration Tri-Loops are configured with all channels to alarm in the same direction. Alarm direction is configured at the factory, and cannot be changed in the field. In addition, all channels alarm if the attached device indicates a sensor failure or transmitter malfunction. Tri-Loops are ordered according to the desired alarm direction. Standard configuration Unless otherwise specified with a C2 option, Tri-Loop is shipped as described in Table 2. Tri-Loop label Each Tri-Loop is labeled with serial number, part number, and factory configuration. Custom configuration If a Tri-Loop is ordered with a C2 option for custom configuration, the assigned variable, variable range, variable units, and channel status are assigned for all three channels. 333 HART Tri-Loop configuration The 333 HART Tri-Loop can be fully configured using the 475 Field Communicator. AMS Device Manager software provides a PC-based user configuration. 4

September 2014 Rosemount 333 Table 2. Standard Configuration Tri-Loop channel Assigned variable Variable range Variable units Channel status Channel 1 Second 0 250 inh 2 O at 68 F Disabled Channel 2 Third 0 800 psi Disabled Channel 3 Fourth 4 0 to 400 Degree F Disabled Figure 2. DIN Rail Mounting Options SYMMETRICAL 35 X 7.5 MM TOP HAT RAIL SYMMETRICAL 35 X 15 MM TOP HAT RAIL ASYMMETRICAL 32 MM G RAIL Dimensional Drawings Tri-Loop Dimensions 1.57 (40) 3.11 (79) 3.36 (86) Dimensions are in inches (millimeters). 5

Rosemount 333 00813-0100-4754, Rev GA Product Data Sheet September 2014 Rosemount Inc. 8200 Market Boulevard Chanhassen, MN 55317 USA T (U.S.) 1-800-999-9307 T (International) (952) 906-8888 F (952) 906-8889 Blegistrasse 23 P.O. Box 1046 CH 6341 Baar Switzerland T +41 (0) 41 768 6111 F +41 (0) 41 768 6300 Blegistrasse 23 P.O. Box 1046 CH 6341 Baar Switzerland T +41 (0) 41 768 6111 F +41 (0) 41 768 6300 Asia Pacific Pte Ltd 1 Pandan Crescent Signapore 128461 T +65 6777 8211 F +65 6777 0947 Service Support Hotline: +65 6770 8711 Email: Enquiries@AP.EmersonProcess.com Latin America 1300 Concord Terrace, Suite 400 Sunrise Florida 33323 USA T + 1 954 846 5030 Blegistrasse 23 P.O. Box 1046 CH 6341 Baar Switzerland T +41 (0) 41 768 6111 F +41 (0) 41 768 6300 Standard Terms and Conditions of Sale can be found at \terms_of_sale The Emerson logo is a trade mark and service mark of Emerson Electric Co. AMS, MultiVariable, Tri-Loop, Rosemount, and the Rosemount logotype are registered trademarks of Rosemount Inc. HART is a registered trademark of the HART Communication Foundation. All other marks are the property of their respective owners. 2014 Rosemount Inc. All rights reserved.