ULTRASONIC NON-INVASIVE LEVEL SENSOR FOR REFRIGERANT RECEIVERS

Similar documents
Non-invasive CLAMP-ON ultrasonic flowmeter for liquids

How To Use A Ds340 (Dsp)

Easy drop down menu allows quick set up, the clear large display offers a choice of menus and the interface echo can be constantly seen if needed.

API Marine. BMS Presentation. Ballast Measurement Systems

Automation System TROVIS 6400 TROVIS 6493 Compact Controller

NC-12 Modbus Application

TMS TANK MANAGEMENT SYSTEM

ENAiKOON ultrasonic fuel-level sensor

12 Volt 30 Amp Digital Solar Charge Controller

O C M III. Open Channel Flow Monitor

HMI display Installation Guide

2.24. Pump Controller 704. Data Sheet

Radiant Temperature Sensor TY7321

REV. REL 1302 WEST BEARDSLEY AVENUE P.O. BOX 1127 ELKHART IN (574) FAX (574) ELKHART BRASS MFG. CO., INC.

Dupline Car Park System Type GP x 724-US 3-Colour Ultrasonic Sensor

ISO-9001:2000 certified. EE300 Series Electromechanical Inventory Level Measuring System. Aplus Finetek Sensor, Inc.

PIEZOMETER AIRFLOW MEASURING RING

Conlift1, Conlift2, Conlift2 ph+

CoolTop. A unique water cooled air-conditioning unit for server room cooling from the top AC-TOPx-CW-240/60

Chapter2. Installation

Various Technics of Liquids and Solids Level Measurements. (Part 3)

Duct Humidity Transmitter

Troubleshooting and Diagnostics

OZW30. Central Unit SYNERGYR

DREXELBROOK. USonic-R Series. Ultrasonic Level Measurement System. User Friendly

Continuous Monitoring of Flue and Combustible or Hazardous Gases and Vapors

FIRERAY 2000 Installation Guide

MAKING MODERN LIVING POSSIBLE. AK-SC255 On-Site Installation Guide DANFOSS ELECTRONIC CONTROLS & SENSORS

MTI10 Insertion and MTL10 In-line Thermal Mass Flowmeter and Temperature Transmitter

Short Form Catalogue. Alarm Systems. Reliable Supervision and Control

Sentinel LCT. Panametrics Ultrasonic Flowmeter for Liquid Custody Transfer Measurement. GE Measurement & Control Solutions. Benefits.

WEA-Base. User manual for load cell transmitters. UK WEA-Base User manual for load cell transmitters Version 3.2 UK

The Do s and Don ts of Pressure Transducers

Easily installed and simple to set up, Flow Pulse uses an acoustic technique never before seen in flow measurement to deliver reliable results across

OPL BASIC. Dosing System for Professional Laundry machines. Contents

Introduction. Refrigerant Leak Detecting System. Feature and Benefits

TAC I/NETTM MR-VAV-AX. Application Specific MicroRegulator TM

12 Volt 30 Amp Digital Solar Charge Controller Installation & Operation Manual

sip Sanyo Modbus Guide Technical Specification Pinouts, Cable Connections & Wiring Issue 2: February 2009 Synapsys Solutions Ltd, all rights reserved

PASSIVE INFRARED INTRUSION DETECTOR PASSIVE INFRAROOD DETECTOR DETECTEUR D INTRUSION PASSIF INFRAROUGE

Electronics Ltd. Presenting. Power, Intelligence... with a sense of feeling

Interface Level And Point Level Analyzers & Sensors

Electronic Control Devices The European Product Catalogue 2007

A Practical Overview of Level Measurement Technologies

SHARKY 775 COMPACT ENERGY METER ULTRASONIC

ETC TWO STAGE ELECTRONIC TEMPERATURE CONTROL

How To Use A Flowmeter

Instruction Sheet ACS-101. General Description. Specifications. Amplified Broadband UHF Combiner-Splitter. Overall. Antenna Splitter.

AMFA-27 AMFA-29. Operator s Manual & Installation Instructions. Rev. 2.5

FLR 1000 & 1000-BR Series Flow Sensors & Meters For Gases

32VFD Variable Frequency Drives for Centrifugal Chillers

WEB log. Device connection plans

Flow Measurement Options for Pipeline and Open Channel Flow

Evaluation copy. Blood Pressure. Project PROJECT DESIGN REQUIREMENTS

ENGINEERING COMPETENCY CLAIMS

Why a torque measuring system?

ST Series POWER SUPPLIES USER INSTRUCTIONS

Wireless Data Logger Monitoring Systems

Application/Connection Examples

FIRE ALARM SYSTEM TECHNICAL SPECIFICATIONS Page 1 of 10

PD 100A. Printing data system

Drayton Digistat +2RF/+3RF

Solar Home System. User Manual. AEH-SHS01-10W2L Solar Home System 2 Lamps

PRODUCTIVITY THROUGH INNOVATION 600 CONTROL DIRECT DRIVE TECHNICAL/OPERATION MANUAL

SHARKY 775 COMPACT ENERGY METER ULTRASONIC

Contents. Document information

RISH EM 3490 DS Dual Source Energy Meter RISH EM 3490 DS. Application : Product Features:

Section TELEPHONE AUTOMATIC DIALER SYSTEM

Max primary circuit temperature 90ºC Max primary circuit temp. 90ºC Max secondary circuit temperature 45ºC Max secondary circuit temp.

PSDC PSDC 12V/8A/8x1A Power supply for up to 8 analog cameras PTC/TOPIC.

INTRODUCTION / TABLE OF CONTENTS

Commercial Refrigeration Temperature and Defrost Controls

TECHNICAL DATA & SERVICE MANUAL SPLIT SYSTEM AIR CONDITIONER INDOOR UNIT: AW52AL AW64AL AW52AL AW64AL /05

DS DRTE. AIR ROOM TEMPERATURE SENSOR with fan speed control switches

Series 510 Submersible Level Transmitters

PROFIBUS fault finding and health checking

SM6 Series Circuit Breaker Monitors CONSOLIDATED. Electronics, Inc. MONITORING THE FUTURE

Operating instructions IV / 2007

3DLevelScanner II TECHNICAL DATA SHEET

Single Channel Loop Detector

Instructions Manual. Electromagnetic sensor Series FLOMID FX. instrumentation for fluids. R-MI-FlomidFX Rev.: 0 English version

RI-215A Operator s Manual. Part Number: RK Revision 0 Released: 10/3/05

SYSTEM 4C. C R H Electronics Design

SELECTION, APPLICATION AND MAINTENANCE

FIREDEX Conventional Fire Panels

Tilt switches N3 / N4... MEMS technology, one or two axis. Use. Options. + long lifetime and highly reliability due to mechanism-free MEMS technology

Troubleshooting Salt Generators

Air conditioning, electrical testing

SLIM LINE FUME HOOD MONITOR

Silicon Pyranometer Smart Sensor (Part # S-LIB-M003)

Automatic Transfer Switch FT-10 Network Control Communications Module (CCM-T) Kit

Technical Data Sheet. 3DLevelScanner

EtherNet-RS232/485. London Electronics Limited. Ethernet to RS232 or RS485 data converter. Connection details and general information

PRODUCT PROFILE FEATURES

JNIOR. Overview. Get Connected. Get Results. JNIOR Model 310. JNIOR Model 312. JNIOR Model 314. JNIOR Model 410

Repeaters and Mimics Data Sheet

Oil and Coolant Circulating Heating System. Model - OCSM

SELECTION, APPLICATION & MAINTENANCE

Temperature & Humidity SMS Alert Controller

Instruction Manual. T3111 T3111L T3111P T3111Ex

Transcription:

ULTRASONIC NON-INVASIVE LEVEL SENSOR FOR REFRIGERANT RECEIVERS Feb-12 R5 1

Feb-12 R5 2

Table of Contents General Description... 4 Key Features for use... 4 Principle of Level Measurement... 5 Installation... 5 Signal Processor Unit... 5 Ultrasonic Sensor... 6 Electrical Supply and Cabling... 6 Board Terminations... 6 Sensor Positioning and Alignment... 6 Vessel Internal fittings and Restrictions... 8 Sloping Vessels and Angled Sensors... 8 Sensor Positioning and Final Alignment Checks... 9 Commissioning the System... 10 Interface Program and Display... 10 Low Refrigerant Levels... 11 Technical Specifications... 13 Signal Processor Unit... 13 Ultrasonic Sensor (standard type)... 13 Analogue Outputs... 13 Termination Diagram... 14 May 09 R4 3

ULTRASONIC NON-INVASIVE LEVEL SENSOR FOR REFRIGERANT RECEIVERS General Description The Engynius refrigerant level sensor is a highly versatile and non-invasive liquid level measurement method designed specifically for refrigeration installations. The system comprises an ultrasonic sensor and signal processor unit, which together provide a measurement of liquid height inside a pressure vessel, providing an ideal method of remote refrigerant trend analysis to end users. Key Features for use Ideal for retrofit applications but OEM installation also apply Non invasive installation with system under pressure Easy external fitting to receiver - no need to stop plant No refrigerant handling issues for installation electrical work only No refrigerant decanting required service or replacement No recalibration, non-drift, no moving parts, no leakage sources Sensor setup on-site to suit all vessel diameters or heights Suitable for any refrigerant type No unauthorized in-service adjustments possible due to software use controls No standpipe or isolation valves used that may be locked to give false levels System powered from a low voltage 24volt supply Standard 0-5 volt scalable analogue output. (options available to order) RS232 /485 communications port as standard. (other protocols to order) Use for remote refrigerant monitoring or local display as required Vertical vessel array options also available to order Feb-12 R5 4

Principle of Level Measurement The unique non-intrusive method of level sensing makes the Engynius system ideal in situations where no existing access points or level connections to the receiver are available on the vessel. An ultrasonic transmit-receive sensor, normally mounted on the underside of the vessel as shown above emits a series of ultrasonic pulses up through the receiver liquid contents. The time taken for an echo to be received from the liquid surface is measured electronically by the signal processing unit. This time is directly proportional to the distance to the refrigerant liquid surface. Software enhancement and development over several years through on-site trials and testing has resulted in a system which detects and responds only to reliable echo signals from the liquid surface and provides this information continuously as an analogue of vessel fill height relative to the full span setting. The signal processor unit houses a microprocessor control circuit board which is the heart of the level sensing system. It generates, transmits, receives, and interprets the ultrasonic signals; then conditions and filters the received echoes to a determined liquid surface height, this is reported as a user scalable analogue voltage output, or alternatively an RS232 or RS485 single point serial link (jumper selectable) is also supplied as standard with Modbus RTU or ASCII protocol. Installation Signal Processor Unit The signal processor unit is normally fed from the refrigeration system control panel to derive the low voltage supply, and the analogue output returned to panel using a multi-core cable. The processor unit s IP56 enclosure can be externally mounted in a sheltered location if necessary to best suit receiver vessel location. Feb-12 R5 5

Ultrasonic Sensor The ultrasonic sensor is connected to the processor electronics by a single pair cable. Cable length should be kept as short as possible to reduce the possibility of electrical interference, and should not exceed 50metres. The standard sensor cable length is supplied as a 1 metre flying lead. Electrical Supply and Cabling The system requires a 24vAC or DC supply, from a sub-fused power source. One side of the supply must be grounded at the supply end. Low voltage cabling for power supply and analogue output between signal processor unit and the refrigeration system control panel would typically be made using 22 AWG (0.65mm) 5 core cabling. Follow good practice to segregate the signal and low voltage power supply cable runs from heavy duty mains cables wherever possible especially over long common runs to limit any risk of signal disruptions. Board Terminations All cable connection to be made in accordance with the termination diagram as shown (page 14) Sensor Positioning and Alignment Bad Position To ensure optimum performance of the sensing system to track the liquid level movements inside the vessel, it is essential that the ultrasonic sensor is installed in the most suitable location on an individual vessel. Ultrasonic sensor should be positioned to the underside of vessel so that the ultrasonic beam is perpendicular to the liquid surface formed in vessel. Good Position Some vessels and plant are not always installed perfectly level, or have only very limited clear space below vessel for sensor location; both situations which may require special attention to sensor design and arrangement. Feb-12 R5 6

A maximum sensor misalignment angle of 3 from horizontal liquid surface in vessel has been found to the practical limit to ensure satisfactory vertical ultrasonic beam projection and system operation. However this limit is also subject to the distance over which the sensor beam has to transmit and the conditions at the liquid measurement surface during operation. If the operating angle misalignment is greater than this then a special angled sensor or perhaps a vertical sensor array solution will be required. This will be determined based on an initial site surveys carried out by Engynius. Vertical receivers with poor access to underside of vessel especially may need this type of array solution. The sensor should not be placed below fill points (condenser returns), liquid outlets or where obstructions such as dip tubes or other level measurement (float type) devices may be directly in the sensors line of fire. Drain Fill Fill Bad Position Bad Position Bad Position Drain Best Position Sensors placed near or over welds and irregularities on the receiver vessel wall should be avoided. Such may prevent the sensor being located flat and true to the underside surface of the receiver. Sensor should not be located too close to the dished end knuckle radius of a horizontal vessel; make sure sensor is located on the straight section only. Feb-12 R5 7

Vessel Internal fittings and Restrictions To avoid detecting false echoes from any internal vessel or fitment, the sensor must be carefully positioned, after carefully testing the echo responses. Especially important when placed near to a drain or fill points, where refrigerant flow rate may interfere with reading stability. Internal Vessel Drain Fill Point Fill Sensor Position Sensor Position, on right of Dish Weld Sloping Vessels and Angled Sensors There are certain refrigeration system with a purposely sloped receiver such as shown below, and will require a special angled sensor to present the ultrasonic beam at the correct angle to the liquid level surface within vessel. (See sketch below) Angled sensors are a special build that must be specially matched to the slope angle of the vessel. Fill Angled Sensor Drain If final alignment is too poor after installation then the sensor will not react reliably and will exhibit typical signs of a misaligned sensor with signal loss at liquid level extremes. Feb-12 R5 8

Sensor Positioning and Final Alignment Checks This simple assembly procedure should be carried out for horizontal vessels: Carry out surface preparation, and cleaning of vessel at proposed sensor location, apply non setting Kilo-Poise acoustic coupling grease to prepared surface of vessel. Mount the sensor into the special spirit level based alignment tool (where access allows) and carefully locate the sensor in the preferred position under the receiver. Place sensor webbing attachment strap around the vessel shell diameter and tighten loosely. Hold the sensor firmly in the selected position with the alignment tool (where possible), ensuring sensor face is on a truly horizontal plane. Fully tighten webbing strap to prevent any further movement. Recheck alignment remains undisturbed. Make off wiring connections to sensor, output cable and power supply to signal processor unit as per above. Verify operation that the sensor is reading correctly and viable with the commissioning process detailed below. Seal sensor strap location to vessel shell with the tamper evident adhesive labeling over strap location. Feb-12 R5 9

Commissioning the System Interface Program and Display Commissioning and adjustments to the settings of the system can only be carried out using dedicated controlled access software via a direct serial connection at site. This software is not readily available to the site service engineers to prevent unwanted changes to the refrigerant level reading output once installed. On initial installation the system, signal type and settings are tailored to the exact vessel size, construction characteristics and refrigerant type using the interface software package. Once correctly installed there is no need for adjustment or recalibration of the system. No user serviceable parts are installed on the signal processor units on this basis; again to prevent changes without the appropriate interface software after initial commissioning. Commissioning of system is via a laptop computer with user interface display as pictured below. This details the system status in a simple readout with a recorded liquid refrigerant height in vessel (mm). Communication settings and current status are clearly shown and easily changed where needed. The signal processor unit has the simple commissioning inputs of refrigerant type (or acoustic velocity for other fluids) plus the span height (mm) representing the full scale of the vessel diameter or a vertical vessel height. After the minimal manual setting inputs commissioning follows an auto-calibration process, and these values are stored in nonvolatile memory once the Install button is clicked. Feb-12 R5 10

A short data log file of the initial 5 minute operating period recorded levels and signal quality along with system serial number, is made available at the end of commissioning process for installation record purposes. The set up software also features advance diagnostic and level analysis tools to visualize the echo patterns recorded from the vessel in an oscilloscope type output to aid in troubleshooting any difficult sensor locations. Low Refrigerant Levels When level sensing system commissioning is required on equipment with little or no detectable refrigerant level in system receiver, it may be necessary to briefly pump down system during set up process. This would carried out by briefly closing the liquid receiver outlet valve during plant operation to allow sufficient liquid level to build up in the receiver to enable the sensing software to clearly recognize a liquid level surface inside the vessel. The sensing system set up and configuration can then be completed as above, and the equipment returned to normal operation by opening the liquid valve again to full refrigerant flow. The level sensing system will retain all settings as commissioned and provide accurate level readings, even though level may initially drop back to zero on a completely empty system Feb-12 R5 11

receiver; correct readings will still be output when refrigerant level cycles to normal again during operation. When there is insufficient refrigerant to form a detectable level even during pump down, then the system refrigerant operating level must be corrected by the users refrigeration service contractor before level system commissioning can be completed Feb-12 R5 12

Technical Specifications Signal Processor Unit Enclosure rating: Supply: Power Consumption: Ambient Temperature Range: Maximum distance from vessel sensor: IP56 24 volt (AC or DC) 50mA -10 to +40 C 50 metre Ultrasonic Sensor (standard type) Housing construction: Operating Temperature Range: Dimensions: Range: Cable length: Ertacetal in Tufnol housing -20 to +125 C continuous 30mm dia. x 25 mm high 25 mm to 1000 mm (liquid depth) 1 metre flying lead Analogue Outputs Standard unit: 0 5 volt DC RS 232 / RS 485 Modbus ASCII or RTU (install options) Optional output: Accuracy: 4-20mA (on special order) Better than 1% of full scale Feb-12 R5 13

Termination Diagram Feb-12 R5 14

Feb-12 R5 15

CONTACT INFORMATION: Call: +44 (0) 1604 726274 Email: info@engynius.co.uk Engynius Limited 3 Fortune Close, Riverside Business Park, Northampton NN3 9HZ United Kingdom Feb-12 R5 16