THE THERMO-FLOW PROCESSES PROCEEDING DURING THE TWO PHASE FLOW IN SUPERSONIC EJECTOR APPLIED IN LOW POWER SOLAR AIR CONDITIONING SYSTEMS

Similar documents
A comparison of heterogenous and homogenous models of two-phase transonic compressible

Thermal Analysis of Steam Ejector Using CFD

CFD Analysis of Supersonic Exhaust Diffuser System for Higher Altitude Simulation

Lecture 6 - Boundary Conditions. Applied Computational Fluid Dynamics

CFD SIMULATION OF SDHW STORAGE TANK WITH AND WITHOUT HEATER

ME6130 An introduction to CFD 1-1

Turbulence Modeling in CFD Simulation of Intake Manifold for a 4 Cylinder Engine

The Second Law of Thermodynamics

Keywords: CFD, heat turbomachinery, Compound Lean Nozzle, Controlled Flow Nozzle, efficiency.

OpenFOAM simulations of the Turbulent Flow in a Rod Bundle with Mixing Vanes

HEAT TRANSFER ANALYSIS IN A 3D SQUARE CHANNEL LAMINAR FLOW WITH USING BAFFLES 1 Vikram Bishnoi

How does solar air conditioning work?

AdSORPTION CHILLER NAK

INTRODUCTION TO FLUID MECHANICS

High Speed Aerodynamics Prof. K. P. Sinhamahapatra Department of Aerospace Engineering Indian Institute of Technology, Kharagpur

THE PSEUDO SINGLE ROW RADIATOR DESIGN

ME 239: Rocket Propulsion. Over- and Under-expanded Nozzles and Nozzle Configurations. J. M. Meyers, PhD

Environmental and Safety Impacts of HFC Emission Reduction Options for Air Conditioning and Heat Pump Systems

Testing methods applicable to refrigeration components and systems

Express Introductory Training in ANSYS Fluent Lecture 1 Introduction to the CFD Methodology

FUNDAMENTALS OF ENGINEERING THERMODYNAMICS

AUTOMOTIVE COMPUTATIONAL FLUID DYNAMICS SIMULATION OF A CAR USING ANSYS

The Second Law of Thermodynamics

Problem Statement In order to satisfy production and storage requirements, small and medium-scale industrial

Flow in data racks. 1 Aim/Motivation. 3 Data rack modification. 2 Current state. EPJ Web of Conferences 67, (2014)

Effect of Pressure Ratio on Film Cooling of Turbine Aerofoil Using CFD

Refrigeration and Airconditioning Prof. M. Ramgopal Department of Mechanical Engineering Indian Institute of Technology, Kharagpur

CO MPa (abs) 20 C

We will try to get familiar with a heat pump, and try to determine its performance coefficient under different circumstances.

Fluid Mechanics Prof. S. K. Som Department of Mechanical Engineering Indian Institute of Technology, Kharagpur

Differential Relations for Fluid Flow. Acceleration field of a fluid. The differential equation of mass conservation

Heat and cold storage with PCM

Research on the Air Conditioning Water Heater System

Customer Training Material. Lecture 2. Introduction to. Methodology ANSYS FLUENT. ANSYS, Inc. Proprietary 2010 ANSYS, Inc. All rights reserved.

THE CFD SIMULATION OF THE FLOW AROUND THE AIRCRAFT USING OPENFOAM AND ANSA

CFD analysis of external aerodynamic and entry into to the air conditioning system on the roof of a bus

Sheet 5:Chapter 5 5 1C Name four physical quantities that are conserved and two quantities that are not conserved during a process.

Automobile Air Conditioning Primer

Ravi Kumar Singh*, K. B. Sahu**, Thakur Debasis Mishra***

CFD Analysis of Swept and Leaned Transonic Compressor Rotor

Grant Agreement No SFERA. Solar Facilities for the European Research Area SEVENTH FRAMEWORK PROGRAMME. Capacities Specific Programme

Air-sourced 90 Hot Water Supplying Heat Pump "HEM-90A"

CFD Analysis of a butterfly valve in a compressible fluid

GT ANALYSIS OF A MICROGASTURBINE FED BY NATURAL GAS AND SYNTHESIS GAS: MGT TEST BENCH AND COMBUSTOR CFD ANALYSIS

HYBRID ROCKET TECHNOLOGY IN THE FRAME OF THE ITALIAN HYPROB PROGRAM

SIMULATION OF THERMODYNAMIC ANALYSIS OF CASCADE REFRIGERATION SYSTEM WITH ALTERNATIVE REFRIGERANTS

Routinely surveying tower overhead vacuum systems can

Analytical Study of Vapour Compression Refrigeration System Using Diffuser and Subcooling

Initial Experiments of a Novel Liquid Desiccant Dehumidifier for Industrial and Comfort Air Conditioning Systems

GEOMETRIC, THERMODYNAMIC AND CFD ANALYSES OF A REAL SCROLL EXPANDER FOR MICRO ORC APPLICATIONS

New absorption chillers for high efficient solar cooling systems

WASHING PROCESS OF CARGO TANKS ON TANKERS FOR TRANSPORTATION OF CRUDE OIL

A Demonstration Plant of a Liquid Desiccant Air Conditioning Unit for Drying Applications

CFD Grows Up! Martin W. Liddament Ventilation, Energy and Environmental Technology (VEETECH Ltd) What is Computational Fluid Dynamics?

Vicot Solar Air Conditioning. V i c o t A i r C o n d i t i o n i n g C o., l t d Tel: Fax:

CFD Analysis of a Centrifugal Pump with Supercritical Carbon Dioxide as a Working Fluid

INTERNATIONAL JOURNAL OF MECHANICAL ENGINEERING AND TECHNOLOGY (IJMET)

University Turbine Systems Research 2012 Fellowship Program Final Report. Prepared for: General Electric Company

HEAT TRANSFER ENHANCEMENT AND FRICTION FACTOR ANALYSIS IN TUBE USING CONICAL SPRING INSERT

How To Calculate The Performance Of A Refrigerator And Heat Pump

SWISSOLAR 2104 TASK 44 SOLAR AND HEAT PUMP SYSTEMS

Heat Pipe Selection Revision 12/04/2001

UNIT 2 REFRIGERATION CYCLE

PUTTING THE SPIN IN CFD

Dimensional analysis is a method for reducing the number and complexity of experimental variables that affect a given physical phenomena.

Building Energy Systems. - HVAC: Heating, Distribution -

REFRIGERATION (& HEAT PUMPS)

TEMA DESIGNATIONS OF HEAT EXCHANGERS REMOVABLE BUNDLE EXCHANGERS NON REMOVABLE BUNDLE EXCHANGERS SOURCE:

A car air-conditioning system based on an absorption refrigeration cycle using energy from exhaust gas of an internal combustion engine

AN EFFECT OF GRID QUALITY ON THE RESULTS OF NUMERICAL SIMULATIONS OF THE FLUID FLOW FIELD IN AN AGITATED VESSEL

Comparison of Heat Transfer between a Helical and Straight Tube Heat Exchanger

A Response Surface Model to Predict Flammable Gas Cloud Volume in Offshore Modules. Tatiele Dalfior Ferreira Sávio Souza Venâncio Vianna

Simulation to Analyze Two Models of Agitation System in Quench Process

Energy Efficient Data Center Design. Can Ozcan Ozen Engineering Emre Türköz Ozen Engineering

Condensers & Evaporator Chapter 5

ALONE. small scale solar cooling device Project No TREN FP7EN Project No TREN/FP7EN/ ALONE. small scale solar cooling device

Overview. Introduction Cooling Tower Basics Principles of Operation Types of Cooling Towers Common Applications Design Considerations

How To Power A Power Plant With Waste Heat

Low GWP Replacements for R404A in Commercial Refrigeration Applications

Performance Test of Solar Assisted Solid Desiccant Dryer

Graduate Certificate Program in Energy Conversion & Transport Offered by the Department of Mechanical and Aerospace Engineering

Open Cycle Refrigeration System

1 DESCRIPTION OF THE APPLIANCE

P. A. Hilton Ltd REFRIGERATION & AIR CONDITIONING VAPOUR COMPRESSION HEAT PUMPS VENTILATION VOCATIONAL

A. Hyll and V. Horák * Department of Mechanical Engineering, Faculty of Military Technology, University of Defence, Brno, Czech Republic

Aerodynamic Department Institute of Aviation. Adam Dziubiński CFD group FLUENT

Understanding ejector systems necessary to troubleshoot vacuum distillation

Using CFD to improve the design of a circulating water channel

Chemistry 13: States of Matter

Use of OpenFoam in a CFD analysis of a finger type slug catcher. Dynaflow Conference 2011 January , Rotterdam, the Netherlands

Combination Ductless Heat Pump & Heat Pump Water Heater Lab and Field Tests

Variable Capacity Compressors, a new dimension for refrigeration engineers to explore

Development of Air-to-Water Heat Pump for Home Air conditioning/hot Water Supply Combination System with Chilled/Hot Water in European Markets

NUMERICAL ANALYSIS OF THE EFFECTS OF WIND ON BUILDING STRUCTURES

TWO-DIMENSIONAL FINITE ELEMENT ANALYSIS OF FORCED CONVECTION FLOW AND HEAT TRANSFER IN A LAMINAR CHANNEL FLOW

CHAPTER 7 THE SECOND LAW OF THERMODYNAMICS. Blank

Steady Heat Conduction

POSSIBILITY FOR MECHANICAL VAPOR RE-COMPRESSRION FOR STEAM BASED DRYING PROCESSES

EXPERIMENTAL RESEARCH ON FLOW IN A 5-STAGE HIGH PRESSURE ROTOR OF 1000 MW STEAM TURBINE

Increasing the evaporation temperature with the help of an internal heat exchanger

Transcription:

THE THERMO-FLOW PROCESSES PROCEEDING DURING THE TWO PHASE FLOW IN SUPERSONIC EJECTOR APPLIED IN LOW POWER SOLAR AIR CONDITIONING SYSTEMS S.Pietrowicz, J.Kasperski, Wroclaw University of Technology, Institute of Heat Engineering and Fluid Mechanics, Wybrzeze Wyspianskiego 27, Wroclaw 50 370, Poland Fax: +48 71 328 38 18 e-mail: slawomir.pietrowicz@pwr.wroc.pl, jacek.kasperski@pwr.wroc.pl ABSTRACT In the paper, the selected designing problems which can result from using the supersonic two-phase flow steam (R 718) ejector in low power refrigerating systems where the high heat source is solar energy have been presented. The numerical calculations were carried out using finite element method in ANSYS CFX software and the mesh was generated using ANSYS ICEM. In order to validate the numerical results a special set-up was designed and constructed. A series of experiments was carried out at the entrainment ratio in range from 0 to 0.3. During the experiments temperature and pressure of primary (motive), secondary (induced) and outlet stream were measured. The experimental results were validated with the numerical calculations. For boundary conditions and SST model of turbulence applied for calculations the numerical results showed a good agreement with the data obtained during experiments. 1. INTRODUCTION The solar collectors are the popular part of hot water installations. The increasing production of highly developed collectors created a possibility to use them in more advanced thermal systems like heat pumps or air conditioning systems. Both applications are widely described in literature on absorption and ejector systems. The authors selected water (R 718) as a refrigerant in the ejector appliance for the sake of the special thermodynamic properties. An essential issue of the ejector s refrigeration system and the solar collector cooperation (shown in Figure 1) is a correct match of a steam generator temperature level. Optimally selected temperature of a steam generator causes the maximization of the cooling effect of the solar air conditioner. The typical problem of the low power ejector is a nozzle geometry. For the low pressure of the primary stream essential outlet diameter value of the primary nozzle can exceed the diameter value of a mixing chamber. Such strona 1 / 11

combination of diameters can make it impossible to draw in the medium from the evaporator. Figure 1. The diagram of the devices and heat exchangers of the ejector unit and the occurring processes on lg p-h diagrams.it was shown that the low power ejector needs non-standard design procedures (Kasperski and Pietrowicz, 2006), e.g. modeling of processes using the finite element method.water as the ecological working medium has many advantages: high heat of evaporation, high specific heat, it is not chemically aggressive, not dangerous to people and its general availability and low price is conductive to use. However, there are also disadvantages such as: under atmospheric pressure of work, low volumetric capacity, freezing at minus Celsius degree, absorption of big amount of gases. In the last few years in the ejector refrigerating cycle the modern refrigerants from the fluorhydrocarbon groups are used with significant success. Their advantages are: high pressure of work, high refrigerating capacity, among drawbacks we can list: danger to people and high price. For ejector cycles important is that for water as the refrigerant the diameters of nozzles are bigger than 1 mm, when for the other refrigerants the diameters are smaller than 1 mm which makes the nozzles production technologically difficult or impossible. For that reason applying water in the systems of refrigerating capacities up to several kw is more favorable.figure 2. The design of internal device construction and an example of installation on the roof slope The analysis of technological possibilities of the solar collectors made by a cooperating producer allowed to develop the conception of a simple construction air conditioning unit which was based on water-ejector cycle, where steam was generated in a flat solar collector. The concept design of the solar air-conditioner unit is shown in Figure 2. The construction of the device was based on a flat heat exchanger. It was assumed that the device will have a simple, compact construction which does not need skilled assembly and special devices during installation. The installation in a skew hipped roof end should be similar to assembly of standard roof windows. The sprinkling evaporator of large volume with a filler was used in the refrigeration system, for the forced fluid flow circulation the low power consumption pump was installed. 2. EJECTOR SYSTEM A simple, classical ejector consists of three basic elements (Figure 3) primary nozzle called also motive nozzle, secondary (induced) nozzle, mixing chamber. Primary nozzle is convergent-divergent element in which the working fluid expands from the steam generator pressure to suction pressure and the velocity increases from zero to the values exceeding a few times Mach number. In the throat of primary nozzle the parameters reach the critical values. Then expanded motive stream draws from the space (2) working fluid called secondary stream at the value of pressure p 2 and temperature t 2. Both streams flow to mixing chamber. At the final stage of the process pressure in diffuser increases to p 3 and velocity decreases to w 3, which is much smaller strona 2 / 11

than the sonic speed. For this reason that part of ejector is called the subsonic diffuser.the parameter characterizing the quality of ejector is entrainment ratio ER the ratio between the amount of mass flow ratio of the induced stream and the amount of mass flow ratio of the motive stream. (1)Even for the best ejectors working in very beneficial system of cycle parameters the entrainment ratio does not exceed unit. Figure 3. The scheme of the supersonic small power ejector with the distribution of pressure and Mach number along symmetry axis of the device 3. NUMERICAL MODELING The physical processes occurring in the ejector can be described using the continuity, Navier Stokes and energy equations (Alexis and Rogdakis, 2003 and Bartosiewicz et al., 2005). The system of three equations was solved in commercial ANSYS CFX 11.0 software using the finite element method technique.the device which was subjected to the numerical analysis is shown in Figure 4a. The domain of calculations consisted of the parts described in section 2. Assuming that the flows occurring in the ejector are axisymmetric the numerical calculations were simplified to the ejector sector shown in Figure 4b. Figure 4. The main elements of the analyzed ejector; a) the physical model, b) the simplified numerical model with the applied boundary conditions strona 3 / 11

The analyzed domain of calculations was meshed using the 4986 elements: 245 elements of wedge type and 4741 elements of hexahedra type. The mesh was generated in ANSYS ICEM 11.0 software. Additionally, in the places where the high pressure and temperature gradients were expected - very near the walls and in the outlet surrounding of the primary nozzle - the mesh was thickened. The details of the structured mesh were shown in Figure 5. Figure 5. The details of the mesh applied in numerical calculations; a) the motive nozzle with the part of the induced nozzle, b) the middle part of the ejector the mixing region of the two streams, c) the outlet of the ejector In the numerical domain the following boundary conditions were assumed (Figure 4b):- the main inlet is the inlet type condition at given saturated temperature of steam and the value of mass flow rate;- the side inlet is the inlet type condition at given saturated temperature of steam and the value of mass flow rate; - the outlet is the outlet type condition at given average absolute pressure; - at the walls of ejector - the adiabatic wall without slip type strona 4 / 11

condition; - at the side-surfaces in respect of axisymmetric form of the fluid fow the symmetry type of conditions were applied. The working medium was the steam (R718), whose properties were calculated on the basis of the model of steam called IAPWS-IF97 (Wagner and Kruse, 1998) proposed in ANSYS CFX 11.0 software. It was assumed that the steam supplied to primary and secondary nozzle was saturated and the quality of steam equaled x = 1.Very important for the flow processes is using the correct turbulence model. Comparing the numerical results with the experimental data Bartosiewicz et al. (2005) proved that one of the best models of turbulence is the model called SST - the shear stress transport. 4. EXPERIMENTAL SET-UP In order to validate the results obtained from the numerical calculations the special set-up was designed and constructed. The set-up was dedicated to research the two-phase thermal flow in the steam ejector. The scheme of set-up is shown in Figure 6. Instead of the solar collector the electrical steam generator with the heater regulated by the autotransformer (maximum of power 900 watts) was used. The steam was produced at saturated conditions. Another very similar, regulated heater was installed in a pump circulation of an evaporator (2). The maximum power was lower than that in the steam generator and reached 300 W. Instead of the air cooling evaporator the water cooling system (3) was used. This strona 5 / 11

solution is more independent of temporary ambient temperature in laboratory. During the experiment temperature and pressure of the inlet steam and the outlet steam were measured. The suction pressure of the secondary stream very near the outlet of the primary stream was gauged. Temperature of the liquid in the evaporator cycle was measured on the section before the circulation pump. The volumetric method was applied to determine the values of the steam mass flow rate. For this purpose the level indicators were placed near the steam generator, evaporator and condenser. During volumetric measurements lower line of the liquid was separated by the valves from the steam generator, evaporator and condenser. The pump supplying the steam generator was switched off during the experiment. Figure 6. Experimental set-up of the two-phase refrigeration ejector system In the set-up there were installed: the primary nozzle of the ejector (made of brass, Figure 7 d) with the 10 cone and the critical diameter 1.8 mm, the secondary nozzle (Figure 7 b) with the diameter of the mixing chamber 6.1 mm and the transparent plastics, which will be necessary for the visualization research. The parts of the set-up with the assembled ejector, the mixing chamber and the details of the motive nozzle are shown in Figure 7. strona 6 / 11

Figure 7. The set-up: a) the general view, b) the details of the assembled ejector, c) the mixing chamber d) the primary nozzle The design criteria of the ejector were decided as follows: pressure of the primary steam (47,4 kpa) corresponding to the boiling temperature +80 C, temperature of condensation +35 C, temperature of evaporation +15 C. The research of the ejector consisted of the measurement series at constant power of the steam generator and at different power of the evaporator ranging from 0 to 150 W. On the basis of changes in the level indicator the entrainment ratios were determined. At the same time of the experiment the following parameters were monitored: pressure and temperature in the steam generator, condenser and evaporator. 5. NUMERICAL RESULTS AND THEIR VALIDATION The numerical calculations were carried out for the designing criteria of the ejector at the entrainment ratio in the range from 0 to 0.3. After a series of calculations the three-dimensional distribution of several parameters was obtained. The examples of numerical calculations of Mach number, quality and streamline of steam at the different entrainment ratios are shown in Figure 8. strona 7 / 11

Fgure 8. The numerical results of selected parameters at the entrainment ratio ER = 0.00, 0.10, 0.20, 0.30: a) Mach number, b) quality, c) streamline Additionally, in Figure 9 it is shown how the pressure (9a), Mach number (9b) and quality of steam (9c) at the different entrainment ratios along the symmetry axis of the ejector were changing.figure 9. The selected values along the symmetry axis of the ejector a) Mach number, b) pressure from the primary nozzle outlet c) quality of steam One of the parameters very useful for validation of the numerical results (correctness of the applied boundary conditions and the turbulence model) was the secondary (induced) pressure. Its value is a function of entrainment ratio and indirectly the pressure occurring after the primary nozzle outlet. This pressure depends on the applied boundary conditions and the turbulence model. In Table 1 there were shown the selected values obtained from a series of experiments, additionally the numerical values of induced pressure were inserted and errors/measurements were compared. Table 1. The comparison of the experimental data with the numerical results. Pos.set-up experiment numerical modeling Comparison steam generator Evaporatorcondenser entrainment evaporator ratio Evaporator p 1 t 1 p 2 t 2" p 3 t 3" p nm kpa C kpa C kpa C [-] kpa kpa % 1 47,4 80 0,95 6,2 5,7 35,20 0,963 0,013 1,4 strona 8 / 11

2 0,9 5,4 0 0,963 0,063 7 3 1,65 14,5 0,15 1,623 0,027 1,6 4 1,35 11,4 0,1 1,367 0,017 1,3 5 1,45 12,5 0,1 1,367 0,083 5,7 6 2,45 20,7 0,3 2,603 0,153 6,2 7 2,4 20,4 0,3 2,603 0,203 8,5 8 2,8 22,9 0,3 2,603 0,197 7 9 1,8 15,8 0,2 1,914 0,114 6,3 10 1,9 16,7 0,2 1,914 0,014 0,7 11 2 17,5 0,2 1,914 0,086 4,3 12 1,25 10,3 0,05 1,147 0,103 8,2 The induced pressure values in the suction space were obtained during the experiment and as the results of numerical calculations shown in Figure 10. Figure 10. The induced pressure as the function of entrainment ratios, the comparison of the numerical results (in blue) with experimental data (in red) 6. CONCLUSION strona 9 / 11

In this paper the concept of the solar air conditioned ejector device was presented. The special set-up was designed and constructed for observation and measurement of the two-phase flow physical processes in the ejector cycle with water as the a refrigerant. The temperature levels of the air conditioner in particular heat exchangers were assumed to be +80/+35/+15 C. A series of measurements was carried out.for the values obtained from the experiment the numerical analysis of the thermal flow processes occurring in the ejector was performed.on the basis of numerical calculations there were indicated mutual relations of several important use parameters of the model ejector. The numerical results proved a good agreement with the experimental data. The comparison of measurement values of induced pressure with numerical results showed that for the tested range of entrainment ratio the error contained in limits 0.7 8.7 %.Presented method can be helpful in numerical matching of ejector geometry without necessity of constructing the prototypes. The authors proved that it is possible to perform numerical modification of the ejector geometry or working conditions, especially in case of the work conditions difficult to obtain in laboratory. Acknowledgements This work is supported by Polish Ministry of Science and Higher Education within the research grant No. 3 T10B 046 29 REFERENCES strona 10 / 11

1. Alexis G.K., Rogdakis E.D., 2003, A verification study of steam-ejector refrigeration model, Applied Thermal Engineering 23; 2. Wagner W., Kruse A., 1998,The Industrial Standard IAPWS-IF97, Properties of Water and Steam, Springer, Berlin; 3. Bartosiewicz Y., Aidoun Z., Desevaux P., Mercadier Y., 2005, Numerical and experimental investigations on supersonic ejectors, International Journal of Heat and Fluid Flow 26, 56-70; 4. Kasperski J., Pietrowicz S. 2006, Modeling of energetic optimal working point of an ejector air conditioner combined with a flat solar collector, Archives of Thermodynamics 27: 111-122, Warsaw. strona 11 / 11