Specification Number: Product Name: PAD-MOUNTED TRANSFORMERS SECTION PAD-MOUNTED TRANSFORMERS

Similar documents
This section applies to the design and installation of transformers.

TRANSFORMER DICTIONARY

Primary and Secondary Electrical Distribution Systems

2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV a. Section INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std.

S. C. Electric Cooperative s Specification for a Three-Phase, Padmounted URD Transformer (Revised 12/2014)

SECTION SUBSTATION TRANSFORMERS

Instructions for Secondary Unit Substation Transformers KVA, Three Phase

Medium Voltage Electrical Distribution

Submit shop drawings for equipment provided under this section Shop drawings shall indicate:

Multi-tap Transformers

Low Voltage Transformers Sealed, General Purpose, Dry Type

All work must conform to the National Electric Code, latest edition, and all other applicable codes and regulations.

Section 9: Power Distribution Equipment Bill Brown, P.E., Square D Engineering Services

ELECTRIC UTILITY SERVICE EQUIPMENT REQUIREMENTS COMMITTEE, EUSERC

Secondary Unit Substations

25-kV Apparatus Bushings B Series (bolt-in) for Elbow to Air-Insulated Service 200 Amp, 600 Amp and 1250 Amp

Specification Guide. for RVAC. Direct Replacement. AC Medium Voltage. Circuit Breakers

Digital Energy ITI. Instrument Transformer Basic Technical Information and Application

HPS Universal. Single and Three Phase Potted. Buck-Boost Transformers. Buck-Boost Applications & Standard Specification... 80

ELECTRIC METERING COMMERCIAL & INDUSTRIAL

SECTION POWER MONITOR FOR ELECTRICAL, STEAM CONDENSATE, AND WATER PART I - GENERAL

Customer Substation Manual 08/05/02

Fundamentals of Modern Electrical Substations Part 1: Mission of Electrical Substations and their Main Components

Step Voltage Regulators

BERTHOLD ELECTRIC GENERATOR CONNECTION CABINET

IRRIGATION PUMPING Table of Contents - Section 900

Sample - No Commercial Use

3. TYPES OF SERVICE AVAILABLE. 3.1 Scope

Diesel Engine Driven Generators Page 1 of 6

Distribution Voltage Regulators

Maintenance Report MEDIUM VOLTAGE POWER STATION 500SC / 630SC / 800SC / 900SC / SC / SC / 1250SC / 1600SC / 1800SC / 2000SC

Oil and Coolant Circulating Heating System. Model - OCSM

METER REQUIREMENTS GENERAL REQUIREMENTS SECTION D

Hyperlinks are Inactive

Lightning Arresters P KVA P KVA. Description & Installation

WINDING RESISTANCE TESTING

Unified requirements for systems with voltages above 1 kv up to 15 kv

SECTION ELECTRICAL ACCEPTANCE TESTS

SECTION DRY-TYPE TRANSFORMERS

Electrical Maintenance Workshop

Issued E.C.S. Section WTR00 INFORMATION SECTION Page 1 of 1

Distribution Dry Type Transformers

MEDIUM VOLTAGE CE-BF SWITCHBOARDS. UP TO 40.5 kv. CE - BF - C - en - REV

Chapter 9. Bonding and Grounding

Magnum Mobile Generator MMG55 Specifications

Distribution Transformers

understanding medium frequency induction melting furnace and its components

SUGGESTED SPECIFICATION for Series 185 Service Entrance Rated Automatic Transfer Switches

OPERATING AND MAINTENANCE MANUAL FOR COMMERCIAL ELECTRIC WATER HEATER ELECTRIC HEATER COMPANY BASE MODEL SE

SF 6 Gas Insulated Switchgear Type SDF for 170 kv

OUTDOOR DISCONNECTORS A division of ACTOM (Pty) Ltd

SALVAGING FLOOD DAMAGED ELECTRICAL EQUIPMENT

UNIVERSITY OF WASHINGTON Facilities Services Design Guide. Electrical. Switchboards. Basis of Design. Design Evaluation

Generator DoCKInG StatIonS

3) What is the difference between "Insulating", "Isolating", and "Shielded Winding" transformers?

Atlanta Chapter IEEE Industry Applications Society

CONSOLIDATED EDISON CO. OF NEW YORK, INC. 4 IRVING PLACE NEW YORK, NY DISTRIBUTION ENGINEERING DEPARTMENT SUBSTATION & EQUIPMENT SECTION

SECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM

Receiving, Installing, Operating and Maintaining Dry Type, VPI Sealed, Cast Coil and UNICLAD Transformers

3.1.1 Full Type Tests & Routine Tests according to Clause 8 2 & Instructions For Installation, Operation & Maintenance

ASCO SERIES 185 Power Transfer Switches

SECTION LOW VOLTAGE LIGHTING CONTROLS

AutoLink Three-Phase Sectionalizer Specifications. Scope. General. Applicable Standards. Operating principle

UNIVERSITY OF WASHINGTON Facilities Services Design Guide. Electrical. Metering and Monitoring. Basis of Design

PRE COMMISSIONING TESTS ON EQUIPMENT AT 33/11 KV SUB STATIONS

16300 MEDIUM VOLTAGE DISTRIBUTION

When power interruptions happen.

Multiple Meter Installation Amperes Per Position -Single Phase, Self-contained

Outdoor 33.6W Dual Port Passive Power-over-Ethernet Midspan For External Security Cameras and Wireless Access Points

Presentation of the France Transfo factories

Learning Module 13: Panelboards and Switchboards. 101 Basic Series

Power Plant Electrical Distribution Systems

Masterclad Medium Voltage Passive Arc-Resistant Switchgear

Fusible Disconnect Switch

SURGE PROTECTIVE DEVICES (SPDs) LOW VOLTAGE AC EXTERNAL SIDEMOUNT SURGE PROTECTION FOR ELECTRICAL DISTRIBUTION SYSTEMS SECTION 16671B SECTION 16671B

MEDIUM AND HIGH VOLTAGE CAPACITORS, CAPACITOR BANKS AND SYSTEMS

ABB ! CAUTION. Type COQ Negative Sequence Generator Relay. (50/60 Hertz) J. Instruction Leaflet

Explosion-Proof Electric Unit Heaters

HOUSTON COMMUNITY COLLEGE HCC ALIEF CAMPUS MAIN BUILDING, FIRST, SECOND & FOURTH FLOORS RENOVATION ISSUE DATE:

AMFA-27 AMFA-29. Operator s Manual & Installation Instructions. Rev. 2.5

SWITCHGEAR Section 16. SECTION INCLUDES This Section includes service and distribution switchboards rated 600 V and less.

Screw Plug Immersion Heaters

Services. Three Phase Service

Welcome to Linear Controls Quarterly Training

Transformer Design & Design Parameters

33.6W Power over Ethernet Waterproof Adapter PoE Plus Single Port Injector for Outdoor Application

Vertical Break Parallel (VBP) / Vertical Break Slant (VBS)

ELECTRIC HEATER COMPANY Operating and Maintenance Manual For Immersion Heating Elements

SUPPLEMENT TO SPECIFICATIONS FOR ELECTRICAL INSTALLATIONS

3.0 CHARACTERISTICS. AR Auxiliary Relay High Speed, High Threshold C

Electrical Code Regulation

Evaluating Water-Damaged Electrical Equipment

Electrical Grounding. Appendix C

MTE SERIES RLW. World REACTORS USER MANUAL PART NO. INSTR 030 REL MTE Corporation

600 Volt Class Transformers

Mini Power-Zone Unit Substation Product Description. Product Description. Features. Typical Applications

MCC Ratings. Voltage Rating

32:(5#5$7,1* 4833#USP283#+] 4;33#USP293#+] 3ULPH 113 kva, 90 kw 124 kva, 99 kw 6WDQGE\ 114 kva, 91 kw 125 kva, 100 kw

SECTION HEATING, VENTILATION AND AIR CONDITIONING EQUIPMENT

Applications. Remote Display Mounting Kits

Transcription:

Specification Number: 26 12 00.10 Product Name: PAD-MOUNTED TRANSFORMERS SECTION 26 12 00.10 PAD-MOUNTED TRANSFORMERS Three-phase, pad-mounted transformers, for use on underground power distribution systems, meet modern design requirements for flexibility, and provide a visually pleasing installation. Construction allows installation in locations accessible to the general public without the need for protective fencing or vaults. These units are ideally suited for apartment buildings, schools, hospitals, shopping centers, commercial buildings, and industrial sites. Standard liquid-filled sizes range from 75-5,000 kva with primary ratings from 2,400 V to 46,000 V. For dry-type units, standard sizes range from 225-750 kva with primary rating from 2,400 V to 15,000 V. These designs meet all applicable industry standards of ANSI, NEMA, CSA, and IEEE. PART 1-GENERAL 1.01 SECTION INCLUDES A. Liquid-filled pad-mounted transformers. B. Dry-type pad-mounted transformers. 1.02 REFERENCES A. ANSI C37.47 - Specifications for Distribution Fuse Disconnecting Switches, Fuse Supports, and Current- Limiting Fuses. B. IEEE C57.12.00 - Standard General Requirements for Liquid-Immersed Distribution, Power, and Regulating Transformers. C. IEEE C57.12.01 - Standard General Requirements for Dry-Type Distribution and Power Transformers. D. IEEE C57.12.34 - Requirements for Pad-Mounted, Compartmental-Type, Self-Cooled, Three-Phase Distribution Transformers, 2,500 kva and Smaller: High Voltage, 34,500 GrdY/19,920 Volts and Below; Low Voltage, 480 Volts and Below. E. ANSI C57.12.28 - Switchgear and Transformers, Pad-Mounted Equipment - Enclosure Integrity. F. ANSI C57.12.50 - Requirements for Ventilated Dry-Type Distribution Transformers, 1-500 kva Single- Phase and 15-500 kva Three-Phase, with High Voltage 601-34,500 Volts, Low Voltage 120-600 Volts. G. IEEE C57.12.51 - Requirements for Ventilated Dry-Type Power Transformers, 501 kva and Larger Three- Phase, with High Voltage 601-34,500 Volts, Low Voltage 208Y/120-4,160 Volts. H. IEEE C57.12.90 - Standard Test Code for Liquid-Immersed Distribution Power, and Regulating Transformers and Guide for Short-Circuit Testing of Distribution and Power Transformers. I. IEEE C57.12.91 - Test Code for Dry-Type Distribution and PowerTransformers. J. IEEE C57.13 - Requirements for Instrument Transformers. K. ANSI/IEEE 386 - Separable Insulated Connector Systems for Power Distribution Systems above 600 V. L. ASTM D877 - Test Method for Dielectric Breakdown Voltage of Insulating Liquids Using Disk Electrodes. M. NEMA AB1 - Molded Case Circuit Breakers. N. CAN/CSA-C88-M90 - Electrical Power Systems and Equipment. 1.03 SUBMITTALS A. Submit shop drawings indicating outline dimensions, connection and support points, weight, specified ratings and materials. B. Submit product data indicating standard model design tests and options. C. Submit manufacturer's installation instructions. 1.04 OPERATION AND MAINTENANCE DATA A. Include procedures for [sampling and maintaining fluid,] cleaning and maintaining unit, and replacing components. 1.05 QUALITY ASSURANCE A. Manufacturer: Company specializing in distribution transformers with [three] [ ] years [documented] experience. 1.06 DELIVERY, STORAGE, AND HANDLING A. Protect dry-type transformers from moisture by using appropriate heaters as instructed by the manufacturer.

PART 2 PRODUCT 2.01 MANUFACTURERS A. Square D Company [no equal] [or approved equal] 2.02 LIQUID-FILLED PAD-MOUNTED TRANSFORMERS A. The transformer(s) shall be compartment type, self-cooled, for mounting on a pad and shall comply with the latest applicable standards. B. The average temperature rise of the windings, measured by the resistance method, shall be [55 C] [65 C] [55/65] when the transformer is operated at rated kva output in a 40 C ambient. The transformer shall be capable of being operated at rated load in a 30 C average, 40 C maximum ambient, as defined by IEEE C57.12.00 without loss of service life expectancy. C. Coolant and insulating fluid shall be [inhibited mineral oil.] [less flammable seed-oil based fluid]. D. The high and low voltage compartments shall be located side by side, separated by a steel barrier. When facing the transformer, the low voltage compartments shall be on the right. Terminal compartments shall be full height, air-filled, with individual doors. The high voltage door fastenings shall not be accessible until the low voltage door has been opened. E. The following accessories shall be provided as standard on all transformers: 1. Nameplate in low voltage compartment, 1inch upper filter press and filling plug, [1 inch drain plug] [1 inch drain valve with sampling device]. 2. Drain plug provided on 75-500 kva. Drain valve provided on units rated 750 kva and above. 3. (Lightning arrester mounting provisions in live front units only.) Tap changer, for de-energized operation only, which is externally operable and padlockable. The front of both compartments shall be removable to allow the transformer to be rolled or skidded into position over conduit stubs. ANSI tank grounding provisions shall be furnished in both compartments. F. The transformer(s) shall be rated [ ] kva self cooled (OA). Primary voltage [delta] [wye]. Secondary voltage [delta] [wye], [3-wire] [4-wire], 60 Hz with two 2-1/2% full capacity above normal and two 2-1/2% below normal taps. Impedance shall be [ %] [manufacturer's standard impedance], ±7-1/2%. Basic impulse level of the primary winding shall be [kv] [as specified in ANSI C57.12.00 for comparable kv class]. G. The transformer shall be of sealed-tank construction of sufficient strength to withstand a pressure of 7 psi without permanent distortion. The cover shall be welded and the fastenings tamper-resistant. The transformer shall remain effectively sealed for a top oil temperature range of -5 C to 105 C. When required, cooling panels will be provided on the back and sides of the tank. Lifting eyes and jacking pads will be provided. H. Coils shall be wound with [copper] [aluminum] conductors. I. The core shall be manufactured using high grade, grain-oriented silicon steel laminations carefully annealed after fabrication to restore high magnetic permeability. Magnetic flux is to be kept well below the saturation point. J. The high voltage terminations and equipment shall be [live front] [dead front]. K. Live front bushings shall be porcelain with [clamp-type connector] [blade terminals incorporating a 2-hole drilling pattern]. Bushings shall be externally clamped and front removable. L. Dead front bushings shall be either universal wells or one-piece integrated for use with separable connectors. Bushings shall be externally clamped and front removable. M. The low voltage bushings shall be molded epoxy, and provided with blade-type spade terminals with NEMA standard hole spacing arranged for vertical take-off. The low voltage neutral shall be an insulated bushing, grounded to the tank by a removable ground strap. N. Wye-wye transformers shall have the high and low voltage neutrals internally tied, with a removable strap. O. Provide a load break, gang operated, liquid immersed switch that is externally operable from the high voltage compartment through the use of a distribution hot-stick. P. Switch to be [2-position "OFF-ON" type for use on a radial feed-system] [3-position for use on an alternate feed system with feed-from-the-left, feed-from-the-right, or off] [4-position "sectionalizing" type for use on an extended radial or loop-feed system with feed-from-the-left, feed-from-the-right, isolated-from-either-side, or through-feed to both sides] [2-position switches to be used as "sectionalizing" switches on extended radial or loop-feed systems with feed-from-the-left, feed-from-the-right, isolated-from-either-side, or through-feed-toboth-sides]. Q. Liquid-immersed switch to be rated at: [200 A] [300 A] [600 A].

R. Select one of the following options for fusible protection: 1. Provide internal liquid immersed cartridge fuses sized at [ amperes] [approximately three times the fullload primary current]. 2. Provide Bay-O-Net(r) liquid immersed fuses that are externally replaceable with a hot-stick without opening the transformer tank. 3. Provide Bay-O-Net liquid immersed fuses in series with oil immersed current-limiting fuses. Bay-O-Net fuses are to be externally replaceable with a hot-stick without opening the transformer tank. 4. Provide Bay-O-Net liquid immersed current limiting fuses that are externally replaceable with a hot-stick without opening the transformer tank. 5. Provide dry-well canister mounted current limiting fuses that are externally replaceable with a distribution hot-stick without opening the transformer tank. 6. Provide McGraw-Edison type NX Arc Strangler(r) fuses or switchblades in series with NX fuses mounted for cold-sequence connection of incoming radial feed line. S. Surge Protection - Provide three kv distribution class lightning arresters for surge protection. Arresters are to be mounted in the high voltage compartment. T. Additional Accessories 1. 1 inch drain valve with sampling device, 75-500 kva only. Standard on units above 500 kva. 2. Dial type thermometer. 3. Magnetic liquid-level gauge. 4. Pressure vacuum gauge. 5. Pressure relief valve. 6. Automatic pressure relief device (self-resealing with indicator). 7. Mounting provisions for low voltage current transformers and potential transformers. 8. Busway opening into the low voltage compartment to accommodate Square D I-LINE(r) Busway. 9. Molded case circuit breaker in the low voltage compartment rated amperes - 2000 amperes maximum rating. 10. Sudden pressure relay. 11. Key interlock to primary or secondary compartment door. 12. KWH meter socket with hinge cover externally mounted on the side of the low voltage compartment. 13. Bushing well inserts 14. Feed-thru inserts. 15. MOVE elbow arresters. 16. Pentahead bolts for compartment doors. U. Testing - Tests shall be conducted in accordance with the provisions of IEEE C57.12.90 and shall include, as a minimum, the following tests: 1. Ratio 2. Polarity 3. Phase Rotation 4. No-Load Loss 5. Excitation Current 6. Impedance Voltage 7. Load Loss 8. Applied Potential 9. Induced Potential 10. QA Impulse Test 2.03 VPI DRY-TYPE PAD-MOUNTED TRANSFORMERS A. The transformer(s) shall be compartment type, self-cooled, for mounting on a pad and shall comply with the latest applicable standards. B. The coils and all clamping structure and buswork shall be assembled on the core, and then dried at atmospheric pressure in an oven through which hot air is continuously circulated. The totally assembled core and coil assembly shall be vacuum pressure impregnated in polyester varnish. The total VPI process shall apply a one (1) cycle polyester protective shield of varnish the coils and a protective shield to the bus, core and support structure. The varnish shall be cured on the core and coil assembly following an established temperature vs. time baking cycle in a hot air circulating oven. The VPI process shall effectively impregnate the entire core and coil assembly, which results in a unit, which is virtually impermeable to moisture, dust, salt air and other industrial contaminants. The coils shall be wound with [aluminum] [copper] conductors.

C. All transformers shall have a maximum temperature rise of [150 C] [115 C] [80 C] above a 40 C maximum ambient. D. Primary taps shall be full capacity, with a minimum of two 2-1/2% above and below rated voltage. E. kva sizes, voltages, and taps shall be as shown on the electrical plans or on the transformer schedule. F. The basic impulse levels (BIL) shall be a minimum of [60 kv for the 15 kv class] [optional 95 kv BIL available] [30 kv for the 5 kv class] [20 kv for the 2.5 kv class] [10 kv for the 1.2 kv class]. Primary and secondary BIL shall be kv and kv respectively. G. The coils shall be wound with [aluminum] [copper] conductors. H. The core shall be constructed of high grade, grain oriented, non-aging silicon steel with high magnetic permeability and low hysteresis and eddy current losses. Magnetic flux densities are to be kept well below the saturation point. I. The manufacturer shall install rubber vibration isolation pads between the core and coil and the enclosure base. The core shall be visibly grounded to the ground bus or ground pad by means of a flexible grounding conductor sized in accordance with applicable NEC standards. J. Dry-type transformers shall be mounted in a heavy gauge sheet steel enclosure consisting of three isolated sections, high voltage compartment, low voltage compartment, and transformer compartment on a common base to form an integral load center. The enclosure is to be of NEMA Type 3R rated rain-resistant construction. Indoor enclosures with weather shields are not acceptable. K. The secondary termination section shall contain spade type terminals with standard NEMA type hole patterns. (Available options include main breaker and I-LINE(r) panelboard with or without main breaker.) L. The primary termination section shall contain spade type terminals with standard NEMA type hole patterns. (Available options include hook-stick operated and individual-pole load break fused disconnects with current limiting fuses.) M. The enclosure base is to be constructed of structural steel members to permit rolling or skidding in any direction. The base shall also be provided with lifting devices and jacking pads designed to be flush with the enclosure. N. Access to the transformer section is to be through a removable panel equipped with padlock hasps to prevent entry by unauthorized personnel when padlocks are installed. Entrance to the high voltage compartment shall not be possible until the low voltage compartment door is open and interlocking screws are released. The low voltage compartment shall have 3-point latching and padlocking provisions. O. Any parts of the enclosure that do not have padlocking provisions shall be secured with either tamperresistant hardware or carriage bolts with nuts inside the enclosure to prevent removal by unauthorized personnel. P. Metal-oxide, gapless-type distribution class lightning arresters shall be installed by the manufacturer on the high voltage side of the transformer to provide additional protection against high voltage lightning or switching surges. Q. Transformers are to be manufactured and tested in accordance with ANSI/IEEE standards C57.12.01, C57.12.91, C57.12.50, and C57.12.51, and shall include, as a minimum, the following tests: 1. Ratio 2. Polarity 3. Phase Rotation 4. No Load Loss 5. Excitation Current 6. Impedance Voltage 7. Load Loss 8. Applied Potential 9. Induced Potential 10. QA Impulse Test PART 3 EXECUTION 3.01 EXAMINATION A. Verify that pads are ready to receive work. B. Verify field measurements are as [shown on drawings.] [instructed by manufacturer.] C. Verify that required utilities are available, in proper location and ready for use. D. Beginning of installation means installer accepts conditions. 3.02 INSTALLATION A. Install in accordance with manufacturer s instructions. B. Install safety labels to NEMA 260.

3.03 FIELD QUALITY CONTROL A. Test dielectric liquid to ASTM D877, using 25,000 volts minimum breakdown voltage, after installation and before energization from system. B. Test transformer to IEEE C57.12.90. C. Test transformer to IEEE C57.12.91. 3.04 ADJUSTING A. Adjust primary taps so that secondary voltage is within [2] [ ] % of rated voltage.