Alumni Roofing Co., Inc. Roof Assessment & Repair Proposal

Similar documents
HEB 38 BLANCO AND WEST AVENUE FLUID APPLIED EPDM RUBBER ROOF RECOVERY SYSTEM APPLICATION

Roof Restoration System. For building owners, property management firms and facility managers. seamless possibilities

Roof Repair Project Report. Fairbank Complex 40 Fairbank Road Sudbury, Massachusetts. February 14, RBA Project No

Preventing Ice Dams on Roofs

September 3, Ric Boyd, Public Works Director Ketchikan Gateway Borough 344 Front St. Ketchikan, AK 99901

FLAT ROOF REPAIR CUT COST WITHOUT CUTTING CORNERS

Thank You! Owner Aaron Perry! Clifty Drive! Madison IN 47250! (855) ! (812) !

Clear Fork Valley Local School District. Roofing Repairs Spring/Summer 2015

!!! !!!! !!! !!! !!! !!! !!!!!!!!! Table of Contents! Section 1: Most Common Types of Flat Roofing! Section 2: Better Understand Your Flat Roof!

Infrared Moisture Detection

How to repair your existing low slope flat roof.

Nondestructive Evaluation of. Outback Steakhouse/Bertucci s Building at Forest Drive, Annapolis, MD. Provided by: HurleyIR

Commercial Roof Management

MUNICIPALITY OF THAMES CENTRE COMMUNITY SERVICES AND DEVELOPMENT RECREATION

Aerial Infrared Roof Moisture Surveys

Get Rid of Roof Problems for Good. How spray foam roofing can protect your building and make you money

SELF-INSPECTION CHECKLIST Maintain Your Roof and Identify Potential Issues With Bloom s Comprehensive Self-Inspection Guide

Building Owners Guide to a Duro-Last System!

Bituminous Sheet Flat Roofs: Their repair and maintenance

Getting The Most Out of Your Roof Asset. Program #099 PM

ROOF INSPECTION & MAINTENANCE

RECOATING AND RENEWING SPF ROOFING SYSTEMS

Rooftop Matters Benchmark Report. Executive Summary

Roof Condition Analysis

Roof Condition Report. Academy International School 8550 Charity Drive. Colorado Springs, Colorado

Nondestructive Evaluation of USCG Hawkins Pt. Road Curtis Bay, MD Provided by: HurleyIR

NEOGARD. Preventive Maintenance Manual

The Perfect Fit For Metal Retrofit

TARRANT COUNTY DETAIL STANDARDS

Water Management & Damage Prevention:

DIY INSPECTION & MAINTENANCE

Safeguarding our clients interests. Active Roof Leaks

Inspecting to a higher standard.

T R A N S F E R A B L E F U L LY

Infrared Cameras Can Aid Building Inspectors in Detecting Roof Leaks, Water Damage, Mold and Other Moisture Related Problems

INDIAN HEAD ELEMENTARY SCHOOL

TITLE: MASONRY PARAPET WALLS AND FLAT ROOF REQUIREMENTS 11/1/09

Crescent Valley High School Roof Investigation

Reroof or Restore? The right decision can save weeks of time and thousands of dollars

Roof Inspection Report 3840 Greenway Circle, Lawrence Kansas, Sauer-Danfoss Building

Finegan Inspection Services, Inc.

Nondestructive Evaluation of. Lockheed Martin Building at Windsor BVLD, Windsor Mill, MD. Provided by: HurleyIR

Roof Inspection. Summary Report

The existing roof angle change terminations and flashings when sound and intact can be reused.

BUILT-UP ROOF COATING SMOOTH and GRANULE SURFACE SPECIFICATION

WET/DAMP BASEMENTS ANSWER: BASEMENT WALLS AND FLOORS CAN BECOME WET BY A LEAK, CAPILLARY SUCTION OR CONDENSATION.

ROOFS - Guidance for Repair, Maintenance and Replacement

Non Invasive Roof Leak Detection Using Infrared Thermography

first look at GigaCrete s revolutionary new New Construction GigaHouse GigaHouse Utilizing GigaPanel


Maintenance & Inspection Guide

Delaney-Vogel School

Roofing & Waterproofing Forensics for the 21 st Century. Peter Brooks, President

Total Home Inspection Checklist

Water Damage & Repair

Smooth cap sheet SQ $ Smooth cap sheet SQ $ Smooth cap sheet SQ $ Smooth cap sheet SQ $ 36.

INNOVATIVE. ADAPTABLE. ENERGY EFFICIENT.

Site Inspection Report

ABOVE ALL, IT S A ROOF SERVICED BY THE JAMES MYERS COMPANY

BLUESTAR INFRARED. Description: Thermal Properties Comparison. Project Location: Client: 759 South Federal Hwy 225 Bayshore Drive

Proven roofing SyStemS

Best Practices in Roof Design: Sustainable Energy Efficient Reroofing

Better Budgeting: Roof Management Plans Help Estimate Costs

BLACK JACK ALL WEATHER ROOF COATING

Commercial Roof Inspection Form

solutions & tips six Wise Energy Guide Building envelope solutions and simple tips AIR SEALING

CARLISLE OWNER S MANUAL

Exhibit 1. With 14 patents in coating technology, APOC is the industry leader in product development, performance and durability!

INFRARED DIAGNOSTIC REPORT ABLE INSPECTION COMPANY Post Office Box Houston, Texas (713)

NRDCA 400 GUIDELINE FOR FIELD APPLICATION of LIGHTWEIGHT INSULATING CONCRETE REROOFING/RECOVER SYSTEMS

Construction Coatings

ROOF CONDENSATION: A COSTLY PROBLEM

Maintenance & repair Solutions

THERMOTEK MODIFIED BITUMEN TORCH MEMBRANE OVER POLYSOCYANURATE SYSTEM DESCRIPTION TORCH SYSTEM OVER POLYISO (15,17,19 YR) TH/BS-TH/CS

Inspection Report. Dream Home Inspections Second Ave. Frisco CO (970)

Roofing Signs that Your Roof Needs Repair/Replacement

The Harold J. Becker Company, Inc.

metal Duil~ing manufacturers Association

North Fork Local School District 2014 Roof Inspection Report Version 1

Winterizing Your Building

Roofing Systems. New Applications / Re-Roofing / Maintenance

REQUEST FOR PROPOSALS

Roof Insulation Building. Energy. Environment friendly e-library

Re-Cover Board-3. Insulation for Above the Deck ROOF WALL SPECIALTY

foot skylight) is enough to knock a worker off their feet. A 10 mph wind gust on a 5 x 6 skylight develops a wind force of 270 lbs.

2011 Dodson Publications, Inc. Page 1 of 6 September 16, :19 AM

Home inspectors are not mold inspectors, however they do inspect for defects that

Asphalt Shingle Application Requirements

Warranty Information TABLE OF CONTENTS PROCEDURES FOR WARRANTY 2

CITY OF WHITE BEAR LAKE BUILDING INSPECTION DEPARTMENT 4701 Highway 61 White Bear Lake, MN Fax: Re-Roofing: Asphalt Shingles

Roofing Sustainability

SECTION MODIFIED BITUMINOUS MEMBRANE ROOFING. A. Vapor barrier (base ply); cover board at existing roof deck.

ITEM THERMOPLASTIC MEMBRANE ROOFING

Report for. Dick and Jane Homeowner Lovers Lane, Houston, Texas 77000

Roof. Walking on roofs

If you touch buildings, YOU can benefit from the Moisture Encounter Plus

SAVE ENERGY AT HOME INSULATE AND AIR SEAL

Peel & Seal Self-Stick Roofing Solutions

SECTION THERMOPLASTIC MEMBRANE ROOFING

STANDARD REQUIREMENTS FOR BONDING OR MECHANICAL ATTACHMENT OF INSULATION PANELS AND MECHANICAL ATTACHMENT OF ANCHOR AND/OR BASE SHEETS TO SUBSTRATES

Transcription:

P.O. Box 9084 2830 Lexington Ave. Lexington, Ohio 44904 (419) 884-9715 Phone (419) 884-9718 Fax Replacements / Repairs / Restoration Infrared Imaging Custom GPS & Internet Surveys Alumni Roofing Co., Inc. Roof Assessment & Repair Proposal

The existing roof is a Carlisle EPDM (rubber) roof that is fully adhered to 3 of PolyIsocyanurate insulation over metal decking. Alumni Roofing conducted a thermal scan of the roof to locate the leaks and quantify the wet insulation The roof appears to be about 13-14 years old and is overall in good condition An exhaust fan hood has blown across the roof and caused several tears in the membrane. These holes have caused the insulation in several areas to become saturated (approximately 2,500 sf) The field seams are starting to become loose and while not currently leaking will become an issue in the near future It is typical for EPDM roofs to shrink over time and cause bridging around penetrations and walls. This roof shows no signs of bridging The expansion joint between roofs B & E is in poor condition with several loose seams. Two 10 foot sections are currently leaking The metal siding around the second story in the back is in excellent condition With a few exceptions, the flashing around the penetrations is in good condition The roofs have adequate drainage with very little ponding water Downspouts and gutters are in good condition and will require only minor repair work With proper maintenance and annual inspections and repairs the roof system should last another 5-7 years

Roof A Overall picture Branches should be trimmed Drains need cleaned

Roof B Overall picture Curled patch that should be repaired Typical field seam that is loose, but not leaking Curled patch

Roof B Roof B has approximately 10-12 holes Typical loose but not leaking field seam throughout the entire roof system

Roof B Vent hood blew across the roof and caused most of the holes Existing Roof Roof C Overall picture Typical loose, but not leaking field seam

Roof E Wall flashing should be repaired Missing drain cover Hole in wall flashing should be repaired

Roof F Overall picture Expansion joint needs repaired The culprit

Thermal Roof Analysis Alumni Roofing performed a thermal scan of the roof to determine the location and extent of moisture in the roof system. Normally there is little or no water within a flat roof assembly. When a leak develops, water enters the roof system and, depending on the type of insulation system, is either absorbed by the insulation or runs to the cracks between the nonabsorbent insulation. When water enters the roof assembly it is present for a long time, sometimes the life of the roof. Thermal capacitance is the physical property of a material s ability to store heat. The materials in roof assemblies have relatively low thermal capacitance, especially when compared to water. Water requires a lot of energy to raise its temperature and likewise must release a lot of energy to cool. The physics used for thermal roof inspections is based on dry roof insulation heating up and cooling down faster than wet roof insulation. A thermal inspection goes beyond simply finding a leak by locating the extent of the moisture invasion of the insulation. To do this we require solar heating of a sunny day. Then at night, after the sun goes down and the roof surface begins to cool, the dry roof insulation cools faster than wet roof insulation. This temperature difference can be detected by the IR-InSight Thermal Imaging camera. Thermal Scan Results Alumni scanned the roof and found six areas where the insulation was wet. Most of the wet areas were caused by small holes in the rubber caused when a vent hood blew across the roof. The holes have been present for some time and around each hole the area of wet insulation is from 50 to over 300 square feet. The expansion joint between Roofs B & F is leaking. All other leaks were caused by nickel / dime sized holes in the membrane. The field seams while showing their age are not leaking. No leaks were found around the drains or any other penetrations (vents / hatch, etc.) All the wet locations were marked with paint on the roof. IR Insight XS

The pictures below show the wet areas. For the color pictures, blue indicates a cool section; the presence of heat is indicated in increasing order from green to red to white. Color enhanced Roof A No moisture was detected in Roof A Gray scale of the same photo Roof B Significant moisture was found around one vent Two pin-hole leaks on Roof B

Roof B Expansion Joint between Roofs B & F More around the expansion joint Two Leaks on Roof F

Wet Areas Roof B Wet Areas Roof F

Recommendations It is our recommendation that the wet insulation be replaced prior to making any repairs. If the holes are patched without replacing the insulation, over time as the insulation dries it collapses and causes the insulation screws to poke through the rubber under snow loads. Also, the metal decking can begin to rust. The field seams are starting to lift / curl, and should have cover tape installed. In the winter water and ice will continue to cause the seams to lift We would recommend in 2-3 years that the owners consider the use of a restoration coating for this roof that will extend its life by 10 years at approximately half the cost of a replacement. We have successfully restored many EPDM roofs with the use of an elastomeric coating. For tax purposes, restorations can be deducted in one year versus a multi-year amortization that may be required for a new roof. Based on today s prices a replacement of this roof (46,000 sf) would be approximaely $160,000. Our suggesttion would be to remove the rubber and install a new TPO roof over the existing insulation.

Proposed Scope Of Work All Rubber Roofs Apply 6 cover tape over all field seams (approximately 6,000 linear feet) Apply cover tape over any curled patches Clean drains on Roof A Trim Branches on Roof A Remove rubber over any wet areas and replace with new insulation. Fully adhere new Carlisle rubber over the new insulation and seam to the existing membrane. This represents approximately 2,500 square feet Repair any holes in the wall flashing (especially Roof E) Repair a broken downspout along the back of the building Repair the entire expansion joint between Roofs B & F with new rubber Alumni will return this fall to perform a second thermal image of the roof system to insure no leaks or wet insulation Alumni will return up to 3 additional times over the next year to make any additional leak repairs at no additional cost.