System range Power trunking up to 125A rated current on a 415Vmax 3-phase supply in a 5-pole configuration.

Similar documents
Trade of Electrician. Three-phase Distribution Boards And Socket Circuits

DOMESTIC ELECTRICAL INSTALLATION CERTIFICATE (Requirements for Electrical Installations BS 7671 IEE Wiring Regulations)

3.1.1 Full Type Tests & Routine Tests according to Clause 8 2 & Instructions For Installation, Operation & Maintenance

Operating Instructions

R.C.C.B. s two-pole LEXIC

ELECTRICAL INSTALLATION CONDITION REPORT (Requirements for Electrical Installations BS 7671 IEE Wiring Regulations)

Paper on Basbar Trunking System for Electrical Supply to Industrial & commercial Installation

12 SOLAR PHOTOVOLTAIC POWER SUPPLY SYSTEMS by John Ware. PV modules are current-limiting

MEDIUM VOLTAGE CE-BF SWITCHBOARDS. UP TO 40.5 kv. CE - BF - C - en - REV

ESP 120 M1, ESP 208 M1, ESP 240 M1, ESP 415 M1, ESP 277 M1, ESP 480 M1 and M1R variants. Installation instructions ESP M1/M1R mains protectors

SELECTION OF FINAL CIRCUIT PROTECTION

Type: DILM115(RAC240) Article No.: Sales text Contactor,55kW/400V,AC operated. Ordering information

ST Series POWER SUPPLIES USER INSTRUCTIONS

The complete range of consumer switchboards and switchgear

Positive-guided relay outputs: 3 safety contacts (N/O), instantaneous. 1 auxiliary contact (N/C), instantaneous

Distribution Boards & Consumer Units

8146/5 Series Breaker Panelboards

GE Power Controls. MiniFORM Switchboards

Outdoor 33.6W Dual Port Passive Power-over-Ethernet Midspan For External Security Cameras and Wireless Access Points

Emergency lighting units EM powerled

PROTECTION AGAINST ELECTRIC SHOCK by John Ware

EVC40 EMERGENCY VOICE COMMUNICATION SYSTEM

33.6W Power over Ethernet Waterproof Adapter PoE Plus Single Port Injector for Outdoor Application

Comparative study for cables and busbars

Electronic ballasts for fluorescent lamps Products for special applications. PC BASIC, 4 28 W Electronic ballast for system output < 25 W

Installation instructions for mains wire-in protectors ESP D1, D1R, D1/LCD and D1R/LCD variants

KAM A Lighting Busbar System KAP A Plug-in Busbar Distribution System

Unified requirements for systems with voltages above 1 kv up to 15 kv

IEC Connectors. Introduction

Technical data. RCBO s DS 261 / DS 271 Residual current operated circuit breakers with integral overcurrent protection

E-STOP relays, safety gate monitors

ASSEMBLED SOCKET-COMBINATIONS

CHAPTER 2 EXAMPLES AND TABLES

IEC >>> IEC GUIDE GLOBAL SPECIALIST IN ELECTRICAL AND DIGITAL BUILDING INFRASTRUCTURES

Building Regulations P.4. Socket Outlets P.6. Other Considerations P.10. Training Seminars P.24

INSTALLATION AND OPERATING INSTRUCTIONS For Model GL1 Gate Locks

Transformers from 25va to 500kva. Standard despatch in days not weeks

FL ballasts Electronic dimming. PCA T5 BASIC lp Y II, W BASIC T5

Electrical Practices for Construction Work

Product and functional description

LV MCC LOW VOLTAGE SWITCHGEAR MOTOR CONTROL CENTRE PRODUCT GUIDE

CONNECTOR AMPLIFIER FOR PROPORTIONAL VALVES (4-20 ma Input Version)

Screened cable and data cable segregation

Electronic overload relay EF65, EF96 and EF146

Current valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw

W DATA SHEET: RESIDUAL CURRENT CIRCUIT BREAKER A, SERIES BCF0 AND BCF6

Bulletin 150 SMC Flex Smart Motor Controller Specifications

Low voltage Direct Current Network. Compact NSX DC PV. Circuit breakers and switch disconnectors for solar application.

Digital Energy ITI. Instrument Transformer Basic Technical Information and Application

Electronic overload relay EF19 and EF45

Fundamentals of Power

GUIDE TO THE AM2 EXAM

Power Supply Unit, Primary Switched, Narrow Design MINI-PS-12-24DC/24DC/1

Protection catalogue 15

A product made in Australia. Insulated Conductor Rail ACTIV-8 PLUS

OUTDOOR DISCONNECTORS A division of ACTOM (Pty) Ltd

SELECTION, APPLICATION AND MAINTENANCE

SOLAR PV STANDARD ELECTRICAL PLAN Microinverter Systems for Single Family Dwellings

Redundancy Module QUINT-DIODE/40

PNOZsigma - Base units

DSD 70 Dual Channel Hall Effect Speed Sensor for Railway Applications, compliant with EN 50155

REB 1 REB 3 REB 5 REB 6 REB 8 REB 10 REB 12 REB 16

ELEKTROTEHNI KO PODJETJE Leskoπkova cesta 12, 1000 Ljubljana, SLOVENIA

The Different Types of AC Power Connectors in North America

A B Brown. This sheet forms part of *Inspection Report Number/*Certificate Number NA/ * EC/ * PIR *Delete as applicable DB

MICROSENS. Central 48 V DC Power Supplies for PoE-Components. Description. Features

Distribution Boards. A perfect blend of aesthetics, functionality and safety

Masterseal Plus TM. ingress protected wiring devices. technical hotline +44 (0) IP66. Improved catch.

PPS-PPQ-BT-PIAS RESIN INSULATORS FOR OIL INSULATED ELECTRICAL MACHINES

Ferrostat Speed Sensor Series DSF Explosion Proof Versions EEx

ACS-30-EU-EMDR-10-MOD

Power Supplies 3. SDN-P DIN Rail Series

MK Electric Sentry Circuit Protection Solutions

STEP-PS/1AC/12DC/1.5. Extract from the online catalog. Order No.: DIN rail power supply unit 12 V DC/1.5 A, primary switched-mode, 1- phase

AUTOMATIC TRANSFER SWITCH. Changeover Type from 250A to 2500A

Safety automation solutions

RISH EM 3490 DS Dual Source Energy Meter RISH EM 3490 DS. Application : Product Features:

The Different Types of AC Power Connectors in North America

How can a charging station for electric vehicles be set up simply and safely?

Contact expansion modules

GRX-PWM Pulse Width Modulation Interface

TECHNICAL DATASHEET #TD1404AX PWM CONTROLLED SOLENOID DRIVER

2008 powertrack and floorboxes

RM17TE V AC. Main. Product or component type. Product specific application. Relay monitored parameters 250 V DC 5 A DC

Tape Wound, Split Core and Ebony Current Transformers

6.0 Electrical Installations

Mini Motor Contactor J7KNA Main contactor Accessories Approved Standards Standard Guide No (US,C) Ordering Information tage Model Number Legend gear

Contact expander modules

3-Component Measuring System

Distribution Dry Type Transformers

Medical Lighting. XL4 Patient Light

Our brand POWER DYNAMIC PASSION COMMITMENT CREATIVITY. A strong brand for strong products: 8PU Premium. MV Energy

Rated Lumen [lm] Nominal. Volts [V] [lm]

Securing your electrical installations Prisma,

TESTING AND COMMISSIONING PROCEDURE FOR ELECTRICAL INSTALLATION GOVERNMENT BUILDINGS THE HONG KONG SPECIAL ADMINISTRATIVE REGION

AF / AF09Z stack 3-pole Contactors AC / DC Operated - with Screw Terminals

Cable/Conduit Conversion

V94 BULK TAPE DEGAUSSER

Guide to Low Voltage Busbar Trunking Systems Verified to BS EN

MTE SERIES RLW. World REACTORS USER MANUAL PART NO. INSTR 030 REL MTE Corporation

Transcription:

System range System components and list numbers Assembly and mounting Circuit diagram Technical data Rated values Electrical properties Voltage drop Circuit protection IP rating Weights Terminal capacities end feeds Maintenance Special applications Functional earth (Clean earth) Flexible joint Drawings and dimensions System range Power trunking up to 125A rated current on a 415Vmax 3-phase supply in a 5-pole configuration. Single-pole tap-off units rated up to 32 A at 240Vmax 1-phase (SP&N+PE). Options: Outgoing circuit protective device MCB, RCD or RCBO; BS4343 industrial socket outlet +MCB; BS1363 twin 13A socket outlet. Triple-pole tap-off units rated up to 32 A at 415V 3-phase (TP&N+PE). Options: Outgoing circuit protective device MCB; BS4343 industrial socket-outlet +MCB. Page 1 of 10

System components and list numbers Component Description Example of list number Straight lengths Feed units 40 125A 5-pole in 3 metre lengths with 8 tap-off outlets per length 1 and 2 metre lengths available on request Switched cable end-feed units up to 80A. Un-switched cable endfeed units at 100A and 125A. Polarity N, L1, L2, L3, E. Reverse cable end-feed units, rated as above. Polarity E, L3, L2, L1, N. Switched end-feeds at 100A and 125A available on request. Example: LP3100 3 = 3 metres 100 = 100A rated Example: LP80EFS 80 = 80A rated EF = end-feed S = switched Example: LP100REF 100 = 100A rated REF = reverse end-feed Intersection [cross] Centre-feed units, comprising an intersection (see below) an endfeed and an end-cap. May be used to feed in from the LH side or the RH side of the face. Allows a run to branch off left or right, or both. An end-cap is required if only one branch is used - to seal the unused branch. Angles A flat angle turns the face of the trunking laterally through 90 o. A right-hand angle turns the tapping face to the right as viewed from the normal direction of run. A left-hand angle turns the tapping face to the left as viewed from the normal direction of run. An edge angle turns the face of the trunking perpendicularly through 90 o either away from (AOE), or forward from the tapping face (AIE). Note: In all cases an 80A angle is used for all ratings up to 80A and a 125A angle is used for ratings of 100 and 125A. End cap Cover to seal the open end of a run. Fits all ratings. LP125EC Universal fixing Trunking fixing bracket for surface mounting. Fits all ratings. LPUFB bracket Universal code letters added to list numbers X added at the end of the list number of any of the trunking components signifies an IP54 protection rating T added after the numerals of the list number of any of the trunking components signifies tinned copper bars. Example: LP125CF 125 = 125A rated CF = centre-feed Example: LP125IS 125 = 125A rated IS = intersection Example: LP80AFRH 80 = 80A rated AFRH = angle flat right-hand Example: LP125AIE 125 = 125A rated AIE = angle inside edge Example: LP80EFSX As LP80EFS with degree of protection increased to IP54. Example: LP3100T 100A straight length with tinned copper bars Where the above letters are combined the sequence of use is T after the numerals with X at the end of the part number Example: LP80TEFSX Page 2 of 10

System components and list numbers [cont d.] Tap-off units This page - listed range Description Tap-off unit with 1-pole Type C MCB 10A, 16A or 32A, in moulded enclosure. Connected phase specified. Tap-off unit with 3-pole Type C MCB10A, 16A and 32A, in moulded enclosure Tap-off unit with twin 13A BS1363 socket outlet in moulded enclosure. Connected phase specified. Tap-off unit with 1-pole Type C MCB, 16A or 32A, with BS4343 socket outlet in moulded enclosure. Connected phase specified. Tap-off unit with 3-pole Type C MCB, 16A or 32A, with BS4343 socket outlet in moulded enclosure. Tap-off unit with 3-pole Type C MCB, 32A, in metal enclosure. Tap-off unit 3-pole fused, 30A, in moulded enclosure. Tap-off unit with double-pole 25A RCCB, IΔn = 30mA, in moulded enclosure. Connected phase specified. Tap-off unit with 1-pole 32A RCBO An RCBO is a combined circuit-breaker and RCD in the modular width of an MCB RC = residual current; B = breaker; O = overcurrent protection. Example of list number Example: LT116M/L1 1 = 1-pole 16 = 16A M = MCB L1 = connected L1 and N + E Example: LT316M 3 = 3-pole 16 = 16A M = MCB Example: LT113B/L2 1 = 1-pole 13B = 13A BS socket outlet L2 = connected L2 and N + E Example: LT116MC/L2 1 = 1-pole 16 = 16A rated M = MCB C= BS4343 socket-outlet L2 = connected L2 and N + E Example: LT316MC 3 = 3-pole 16 = 16A rated M = MCB C= BS4343 socket-outlet LT332MST ST = steel enclosure LT332F F = fused Example: LT125RCD/L3 1 = 1-phase (double-pole) 25 = 25A rated RCD = RCCB L3 = connected L3 and N + E Example: LT132MST/RCD 1 = 1-pole 32 = 32A rated M = MCB module ST = steel enc. RCD = RCBO L3 = connected L3and N + E MEMPOWER BUSBAR TRUNKING Page 3 of 10

System components and list numbers [cont d.] Component Description Example of list number Tap-off units Units available to special order Variations on listed tap-offs Tap-off unit 1-pole in metal enclosure with fuse unit mounted through lid. Connected phase specified. Tap-off unit 1-pole in metal enclosure with MCB mounted through lid. Connected phase specified. Alternative fuse ratings up to 32A Alternative MCB ratings up to 63A Alternative MCB Type to BSEN 60898 Type C characteristic MCBs are fitted unless otherwise specified suitable for most applications. If resistance to higher inrush currents is required then Type D is recommended. Example: LT132FST/BTL/L2 1 = 1-pole 32 = 32A rated F = fused ST = = steel enc. BTL = Through lid L2 = connected L2 and N + E Example: LT132MST/BTL/L2 1 = 1-pole 32 = 32A rated M = MCB ST = = steel enc. BTL = Through lid L2 = connected L2 and N + E Example: LT116M/D/L1 D signifies Type D MCB ---------------------------------------------------------------------------------------------------- Assembly and mounting Jointing 40A to 80A The two sections slot together as shown. The PE has a screw connector and as standard is bonded to the case. Screws secure the sections together mechanically. The line and neutral connections are made by screw-less spring contacts in the joint connector. The joint connector is plugged on to the bars and secured by a screw. Page 4 of 10

Assembly and mounting [cont d.] Jointing 100A and 125A The two sections slot together as shown. The PE and the line and neutral connections are made by a screw connector and screws secure the sections together mechanically. As standard the PE conductor is bonded to the case. The joint cover is fitted to provide protection against direct contact. End cap An end cap must be fitted to the open end of the trunking run as a barrier against direct contact. Mounting LP trunking is mounted using a universal fixing bracket LPUFB. The mounting position may be horizontal, flat or on edge, or vertical. LPUFB Side clips Fitting a tap-off unit (insulated enclosure) The wiring of the outgoing circuit should be carried out before fitting the unit to the trunking. The tap-off outlet is fitted with a spring-loaded shutter to prevent accidental contact with live parts when not in use. The shutter release peg engages first and the unit clips on to the trunking. Shutter release Page 5 of 10 LT113 shown

Assembly and mounting [cont d.] Fitting a tap-off unit (metal enclosure) The wiring of the outgoing circuit should be carried out before fitting the unit to the trunking. The tap-off outlet is fitted with a spring-loaded shutter to prevent accidental contact with live parts when not in use. The shutter release peg on the tap-off unit engages first and the unit clips on to the trunking. It is then secured by means of clamps at both ends. Clamp bars LT332MST shown --------------------------------------------------------------------------------------------------------------------- Circuit diagram N L1 L2 L3 PE case Tap-off units 1-ph 1-ph 1-ph 3-ph Figure 1. 5-pole trunking on a TP&N + PE supply. Single-phase tap-off units evenly distributed across the phases to minimise the current in the neutral. Supplied through a 3-phase and neutral linked switch. Page 6 of 10

Technical data 40A 63A 80A 100A 125A Standards BSEN60439-2, EN60439-2, IEC60439-2 Rated current 40A 63A 80A 100A 125A This is the maximum current per pole. Single-phase tap-off units must be evenly distributed across the poles so as not to exceed the current rating in one pole or the neutral. Rated insulation voltage (Ui) 500 V a.c. 500 V a.c. 500 V a.c. 500 V a.c. 500 V a.c. - This is a.c. voltage that the trunking system is designed for and provides a safety factor over the rated operational voltage. Rated operational voltage (Ue) 415 V a.c. 415 V a.c. 415 V a.c. 415 V a.c. 415 V a.c. - This is the maximum 3-phase voltage that trunking system is designed to operate at in service. Rated frequency 50Hz 50Hz 50Hz 50Hz 50Hz Phase resistance [mω/m] 0.96 0.96 0.96 0.48 0.48 - This is the resistance R 20 (at 20oC) of the conductor of each phase pole and the neutral and is used in the calculation of fault current, earth-loop impedance and voltage drop. For resistance at F/L temperature add 11%. Phase reactance [mω/m] 0.098 0.098 0.098 0.085 0.085 This is the inductive reactance X of each phase pole and the neutral and is used in the calculation of volt-drop and circuit impedance PE resistance [mω/m] 0.96 0.96 0.96 0.96 0.96 PE reactance [mω/m] 0.023 0.023 0.023 0.023 0.023 The PE resistance and reactance are used in the calculation of the fault level to earth. Volt-drop [V/A/100m] - Unity pf - 0.9 pf - 0.8 pf - 0.7 pf 0.166 0.157 0.143 0.128 0.166 0.157 0.143 0.128 0.166 0.157 0.143 0.128 0.083 0.077 0.070 0.062 0.083 0.077 0.070 0.062 This figure allows an estimate to be made of the voltage drop along a run. This is the phase-to-phase voltage drop per ampere of load, along a 100m run without tap-offs. When loaded with tap-off units evenly distributed along the run the figures are multiplied by 0.55. See example of application below. Note that it is advisable to check the actual voltage drop on the completed installation Overload current protection 40A 63A 80A 100A 125A Rated current of fuses or circuit-breaker Fault current (S/C) protection - Rated fused S/C current (I cf ) - Rated S/C current with CB 80kA * 80kA * 80kA * 80kA * 80kA * The rated fused S/C current I cf is the maximum fault level at the incomer to the trunking when protected by BS88 fuses of the rating quoted above for overload current protection. * The rated S/C current with circuit-breaker protection is dependent on the type of circuit breaker details of suitable devices on application. Degree of protection to BSEN60529 IP 4X as standard - IP4X code indicates protection against solid objects 1mm diameter and protection against access to hazardous parts even with a 1mm diameter wire. Weight of trunking [Kg/m] 1.7 1.7 1.7 2.9 2.9 Cable capacity feed units 25mm 2 35mm 2 35mm 2 70mm 2 70mm 2 Page 7 of 10

Technical data [cont d.] Voltage drop Examples: Case 1.. 100A LP trunking run total length 50 metres. 20 tap-off units evenly distributed along the run. Tap-off ratings the same and similarly loaded, drawing a total load of 87 A at 0.9 power-factor. Volt-drop at the far end of the run = 0.077 x 87 x 50/100 x 0.55 = 1.84 volts ph to ph. Case 2. Supply 40m 10m 100A LP trunking run total length 50 metres. 7 tap-off units evenly distributed over the last 10 metres. Tap-off ratings the same and similarly loaded, drawing a total load of 87 A at 0.9 power-factor. Volt-drop at the far end of the run = (0.077 x 87 x 40/100) + (0.077 x 87 x 10/100 x 0.55 = 3.04 volts ph to ph. Note that the volt-drop figure for the trunking has to be added to the volt-drop of the circuit from the supply source to the trunking feeder, to obtain the overall volt-drop according to the Wiring Regulations. Neutral current The neutral conductor within the busbar trunking is of the same capacity as the phase conductors (100% neutral). Particular care needs to be taken to ensure that the neutral current is not excessive. Conditions under which this can arise include the following: - Unbalanced load the connections to single-phase tap-off units on a 3-phase system must be alternated across the phases along the run to balance the load. Harmonic currents Electronic equipment and luminaires with electronic control gear generate harmonics in the supply current. Certain harmonic currents accumulate in the neutral of the supply, even when the load is balanced across the phases. Usually this is not a problem with a 100% neutral but in the case of total loads near to the full rating of the trunking this should be checked. Either consult the manufacturer of the equipment and, if necessary, size the trunking according to the neutral current. or split the load over two or more circuits. Page 8 of 10

Maintenance procedure 1. A check should be made annually to ensure the security of mountings and the fixing of covers. 2. It is recommended that condition monitoring is carried out annually e.g. by thermal imaging. This would require a temperature profile being established under normal running conditions for comparison with the subsequent check results. 3. Subject to satisfactory results of monitoring, no routine examination of the electrical joints is necessary; however it is recommended that that the integrity of each joint, where accessible, is checked at not more than5 year intervals by the use of thermalimaging. 4. Circuit protective devices in tap-off units should be maintained in accordance with the instructions for each device. Special applications Functional earth- also referred to as noiseless earth or clean earth. In certain applications it is desirable to have an earth conductor that is not used as the protective earth (PE) for the system. This is to enhance the electromagnetic compatibility (EMC) function of the system, for example with supplies to buildings with a high concentration of data processing equipment. Using a separate earth conductor for connecting functional parts of equipment minimizes the risk of spurious signals or unwanted levels of voltage that might be present in the PE. LP trunking can be factory-built with a clean earth by isolating the earth terminals in the end feed and at each joint, from the case. A protective earth (PE) terminal is available at the end-feed in addition to a clean earth terminal. This protective earth terminal serves to bond the trunking case. In this case the tap-off units must be of the metal enclosed pattern in order to provide a PE connection to the outgoing circuit in addition to the clean earth connection. Flexible joint A flexible connector can be supplied, for ratings 40A 80A, to allow a change of direction in the trunking run of up to 90 degrees Part No. LP80FB. Page 9 of 10

Drawings and dimensions LP125AEF 85 300 60 300 115 115 115 150 115 LP80EF 300 60 300 115 100-125A end-feeds 115 LP125AEFS 40 80A end-feeds LP80EFS Angle outside edge A = 65mm Angle inside edge A = 75mm Angle-flat left hand BS fused tap-off unit Metal-clad tap-off unit Intersection Page 10 of 10