The Different Types of AC Power Connectors in North America
|
|
|
- Barnaby Roberts
- 10 years ago
- Views:
Transcription
1 The Different Types of AC Power Connectors in North America White Paper 20 Revision 1 by James Spitaels > Executive summary A confusing array of AC power plugs and receptacles exist to deliver power to various electronic loads. This white paper describes the different types of connectors used to power computer equipment in North America. An illustration guide is provided at the end of the paper to help identify the various connectors by appearance and size. Contents Click on a section to jump to it Introduction 2 Connectors for multiple applications An international standard 2 North American standard AC connectors 2 4 Safety issues 5 Conclusion 7 Resources 8 Appendix 9 white papers are now part of the Schneider Electric white paper library produced by Schneider Electric s Data Center Science Center [email protected]
2 Introduction The connection of electronic equipment to the AC power supply is usually accomplished using detachable connectors. The alternative of "hard-wiring" equipment to the building wiring makes service and movement of equipment more costly and less convenient. Therefore, many types of connectors exist. As a result, much confusion is generated as to what the various connection types are, when they are used, and what they should look like. This white paper describes the different types of connectors used for powering computer equipment in North America, including internationally recognized connectors. A guide for identifying the connectors is provided as a reference (see Appendix) to help identify particular connectors by name, appearance, and size. Connectors for multiple applications Different styles of AC connectors exist in order to address different wiring systems and to ensure user safety. Within the North American NEMA standard alone, approximately 150 different styles of AC connectors are defined. Power distribution and utilization standards dictate that connectors have a specific number of pins. These recognized standards are listed in Table 1. AC power distribution system Single-phase without safety ground 2 Number of pins Application Lamps, double insulated appliances Single-phase with safety ground 3 Most business equipment Table 1 Applications and pin count for different wiring systems Three-phase without safety ground Single-phase center tapped without safety ground Three-phase with safety ground 4 Single-phase center tapped with safety ground Three-phase with neutral without safety ground Three-phase with neutral with safety ground 3 Uncommon; historical 3 Residential ovens and clothes dryers Three-phase business equipment and machines 4 Residential large appliances 4 Uncommon; historical 5 Three-phase equipment with unbalanced loads An international standard Standards for wall receptacles are often set by individual countries. The International Electrotechnical Commission, or IEC, has published international standards for AC interconnections between equipment. Two IEC standards are presented here: IEC and IEC When equipment uses connectors that comply with these standards, worldwide compatibility is achieved. Virtually all computer equipment is equipped with a detachable power cord. The end of the cord that plugs into the equipment is an IEC standard connector. The IEC C13 / 14 connector type is seen on almost all personal computers and monitors. It has a rating of 10 amps and the female connector end is noted as C13 while the male connector end is noted Schneider Electric Data Center Science Center White Paper 20 Rev 1 2
3 as C14. The IEC C19 / 20 connectors are rated for 16 amps and again have a female connector end (C19) and a male connector end (C20). C19 / 20 connectors are commonly used for devices such as some servers and UPS systems. IEC is an international standard for "plugs, socket-outlets and couplers for industrial purposes". It specifies general functional and safety requirements for any form of industrial high-current power connector. The IEC connectors are produced in many varieties and are designed so that a plug of one type can only be inserted into a socket of the same type. For each current rating (i.e. 16 A, 32 A, and 63 A), the plugs are a different diameter, the pins are a different size, and the separation between pins is varied. Different voltage and frequency combinations are distinguished by the location of the ground pin. Specifically, the ground pin can be in one of twelve locations spaced at 30 degree intervals around the circle on which all the pins lie (also referred to as clock positions). The ground pin has a larger diameter than the other pins, preventing the wrong type of plug from being inserted in a socket. Table 2 illustrates the two common IEC connectors used for computers and servers. The table also illustrates three variations of the IEC pin and sleeve connectors. These diagrams illustrate how the number of pins can vary. Figure 1 illustrates two examples of IEC connectors. The first illustration shows two phases, a neutral, and a ground. The second illustration depicts three-phases, and a ground. IEC connector type Diagram of connector type Comments IEC C13 / C14 C 13 is the female connector end and C14 is the male connector end Table 2 IEC international standard business equipment connectors IEC C19 / C20 IEC Phase + Earth C 19 is the female connector end and C20 is the male connector end Variations of different amperage (diameter of connector), voltage & frequency (grounding pin location and color coding) IEC Phase + Earth Variations of different amperage (diameter of connector), voltage & frequency (grounding pin location and color coding) IEC Phase + Earth + Neutral Variations of different amperage (diameter of connector), voltage & frequency (grounding pin location and color coding) Schneider Electric Data Center Science Center White Paper 20 Rev 1 3
4 Figure 1 Examples of EIC connectors: 2 phases + neutral +ground (left) and 3 phases + ground (right) North American standard AC connectors A wide variety of connectors support business computers and electronic equipment in North America. The typical 120 volt and 208 volt connectors for single-phase business equipment are illustrated in Table 3 and Table 4. The tables show that at several power ratings, the equipment manufacturers offer two different plug styles. One is called the "straight-blade" style and the other is called the "twist-lock" style. The 120 V 15 A NEMA 5-15 straight-blade style is far more common than the NEMA L5-15 twist lock style. However, at other ratings, straight-blade and twist-lock styles are both popular. Each connector has a voltage and current rating as shown. These ratings limit the amount of power which can be drawn by equipment using the connector. The limit set by Underwriters Laboratories (UL) is 80% of the connector rating. The volt-amp limits for each connector type are shown in the tables. For example, an equipment component that operates at 2600 VA, if rated for 120 volts, would require a 30 amp connector. If rated for 208 volts, the component would require a 20 amp connector. Abbreviations are used to describe characteristics of the plugs. P refers to the plug and R refers to the receptacle. In the tables, the plugs are illustrated but the receptacles are not. The receptacles are the same shape as the plugs except for the fact that they have holes where the plugs have prongs. One anomaly in the NEMA connector family organization is the receptacle for the 20 amp straight blade connectors, the NEMA 5-20R and 6-20R. In this case the receptacle is designed to accept either the 20 amp or the 15 amp plug by use of a special "T" shaped slot. This is permitted in the US since the National Electrical Code permits 15 amp outlets to be fed from a 20 amp circuit breaker. The Canadian electrical code does not permit this arrangement and therefore in Canada the 20 amp receptacles will only accept 20 amp plugs. This means that equipment with "T" slot receptacles cannot be sold in Canada. It is a common practice today to wire office buildings in the US with NEMA 5-20R "T" slot type receptacles. For this reason, the 20 amp NEMA 5-20P plug has become popular for use on small minicomputers which have an input power requirement between 1440 VA and 1920 VA. Schneider Electric Data Center Science Center White Paper 20 Rev 1 4
5 Size / type Straight-blade connector Twist-lock connector Comments 120 volt 15 amp 1440 VA equipment load Table 3 NEMA 5-15P NEMA L5-15P Common North American single-phase AC power connectors (120 V, 60 Hz) 120 volt 20 amp 1920 VA equipment load NEMA 5-20P NEMA L5-20P 120 volt 30 amp None 2880 VA equipment load NEMA L5-30P Safety issues A key reason why different styles of connectors exist within a country is to prevent misapplication by users. For this reason, receptacles are designed so that they will only accept appropriate connectors. Connectors are often manufactured differently for various utilization voltages in order to prevent equipment designed for one voltage to be inadvertently connected to another. Applying a voltage higher or lower than the voltage the equipment is designed for can be damaging to the equipment and may present a fire hazard. Connectors are also manufactured differently to accommodate utilization at several power levels even at the same utilization voltage. This is to prevent unknowing users from connecting equipment to a power distribution circuit which is not rated to handle the power requirement; thereby preventing overloading and overheating of building wiring. Schneider Electric Data Center Science Center White Paper 20 Rev 1 5
6 Table 4 Common North American single-phase AC power connectors ( V, 60 Hz) Size / type Straight-blade connector Twist-lock connector Comments 208 Volt 15 Amp 2496 VA equipment load NEMA 6-15P NEMA L6-15P 208 Volt 20 Amp 3328 VA equipment load NEMA 6-20P NEMA L6-20P 208 Volt 30 Amp None 4992 VA equipment load NEMA L6-30P 125 Volt 3-phase 30 Amp None 8640 VA equipment load NEMA L14-30P Schneider Electric Data Center Science Center White Paper 20 Rev 1 6
7 Conclusion Without the standardization of plugs and receptacles thousands of equipment manufacturers would be free to design and use any type of plug they desired. This would lead to large quantities of unique plugs, requiring other manufacturers to build and stock hundreds of backplates and adapters to allow a connection between the devices. The standards in place rate plug types for a maximum RMS voltage and maximum amperage. This paper provides guidelines for how common plugs and receptacles are configured and identified. About the author James Spitaels is a Consulting Engineer for Schneider Electric. He has Bachelors and Masters Degrees in Electrical Engineering from Worcester Polytechnic Institute. During his 16 years with the company he has developed UPSs, communications products, architectures and protocols, equipment enclosures, and power distribution products and has managed multiple product development teams. He holds four US Patents related to UPS and power systems. Schneider Electric Data Center Science Center White Paper 20 Rev 1 7
8 Resources Click on icon to link to resource White Paper Library whitepapers.apc.com TradeOff Tools tools.apc.com Contact us For feedback and comments about the content of this white paper: Data Center Science Center If you are a customer and have questions specific to your data center project: Contact your Schneider Electric representative Schneider Electric Data Center Science Center White Paper 20 Rev 1 8
9 Appendix The reference guide in this appendix can help to identify unknown connector types. Each diagram is illustrated in its actual size along with its name. Note Only male connectors are shown (with abbreviation P ), which are simply the plugs of the plug / receptacle set. Also note While the prong shapes and positions are standard, the actual shape of the insulated plug casings can vary greatly. For instance, rather than a circular shape, the NEMA 5-15 plugs often have a rounded triangular or rectangular shape. Figure a1 Quick reference guide NEMA 5-15P NEMA L5-15P NEMA 5-20P NEMA L5-20P NEMA 6-15P NEMA L5-30P NEMA L6-15P NEMA 6-20P NEMA L6-20P Schneider Electric Data Center Science Center White Paper 20 Rev 1 9
10 Figure a1 (cont.) Quick reference guide NEMA L6-30P NEMA L14-30R IEC C13/C14 IEC C19/C20 Schneider Electric Data Center Science Center White Paper 20 Rev 1 10
The Different Types of AC Power Connectors in North America
The Different Types of AC Power Connectors in North America White Paper #20 Executive Summary A confusing array of AC power plugs and receptacles exist to deliver power to various electronic loads. This
Dynamic Power Variations in Data Centers and Network Rooms
Dynamic Power Variations in Data Centers and Network Rooms White Paper 43 Revision 3 by James Spitaels > Executive summary The power requirement required by data centers and network rooms varies on a minute
Fundamentals of Power
Fundamentals of Power Fundamentals of Power 2008 American Power Conversion Corporation. All rights reserved. All trademarks provided are the property of their respective owners. Learning Objectives At
Efficiency and Other Benefits of 208 Volt Over 120 Volt Input for IT Equipment
Efficiency and Other Benefits of 208 Volt Over 120 Volt Input for IT Equipment By Neil Rasmussen White Paper #27 Revision 2 Executive Summary Decisions made regarding the distribution of 208V or 120V power
High-Efficiency AC Power Distribution for Data Centers
High-Efficiency AC Power Distribution for Data Centers White Paper 128 Revision 2 by Neil Rasmussen > Executive summary The use of 240 volt power distribution for data centers saves floor space, simplifies
Three-Phase Electric Power Distribution for Computer Data Centers
Three-hase Electric ower Distribution for Computer Data Centers WHITE AER E901 Geist January 008 Summary This paper will describe the characteristics of three-phase power and outline the advantages of
Increasing Data Center Efficiency by Using Improved High Density Power Distribution
Increasing Data Center Efficiency by Using Improved High Density Power Distribution By Neil Rasmussen White Paper #128 Executive Summary A new approach to power distribution for high density server installations
Trade of Electrician. Three-phase Distribution Boards And Socket Circuits
Trade of Electrician Standards Based Apprenticeship Three-phase Distribution Boards And Socket Circuits Phase 2 Module No. 2.3 Unit No. 2.3.2 COURSE NOTES Created by Charlie Walsh - Athlone TC Revision
Neutral Wire Facts and Mythology. White Paper #21
Neutral Wire Facts and Mythology White Paper #21 Executive Summary This Technical Note discusses many common misunderstandings about the function of the neutral wire and its relation to power problems.
CHAPTER 4 UTILITY SYSTEMS ELECTRICAL. Utility Systems Electrical. Main Panel
CHAPTER 4 UTILITY SYSTEMS ELECTRICAL Utility Systems Electrical The electrical supply to your home begins outside, where you will see either an overhead feed and piping down the side of your home or (if
Distributing Power to Blade Servers
Distributing Power to Blade Servers Ten steps to selecting the optimal power distribution design With the growth in blade servers with dual or triple power supplies, a single rack of equipment can easily
Power Distribution Systems for the Dell PowerEdge M1000e Modular Server Enclosure - Selection and Installation
One Dell Way Round Rock, Texas 78682 www.dell.com Dell Enterprise White Paper Power Distribution Systems for the Dell PowerEdge M1000e Modular Server Enclosure - Selection and Installation January, 2008
For Models #6-5001, #6-7501, #10-7501 & #10-12K1
EmerGen Switch Manual Transfer Switch Manufactured by CONNECTICUT ELECTRIC SWITCH MFG. CO. 1-800-730-2557 OWNER S MANUAL & INSTALLATION INSTRUCTIONS For Models #6-5001, #6-7501, #10-7501 & #10-12K1 PLEASE
DVI DA2 and DVI DA 4 User Guide
DVI DA2 and DVI DA 4 User Guide This guide describes the installation and operation of the Extron DVI DA2 and DVI DA4 Distribution Amplifiers. Unless stated otherwise, distribution amplifier or the unit
Instructions & Safety Information Models A220-20D and A220-20L Version 2
Quick 220 Voltage Converting Power Supply Instructions & Safety Information Models A220-20D and A220-20L Version 2 Quick 220 Systems LLC PO Box 47489 Phoenix, Arizona 85068-7489 800-347-0394 602-938-6057
Connection method for charging systems a key element for electric vehicles
Connection method for charging systems a key element for electric vehicles By Claude Ricaud and Philippe Vollet > Abstract At the heart of the energy and environmental challenges, the electric vehicle
Rack Power Distribution. Worldwide
Rack Distribution Worldwide Introduction APC TM by Schneider Electric TM offers a wide array of standardized Rack Distribution Units (PDUs) designed to increase manageability and efficiency in your data
Dynamic Power Variations in Data Centers and Network Rooms
Dynamic Power Variations in Data Centers and Network Rooms By Jim Spitaels White Paper #43 Revision 2 Executive Summary The power requirement required by data centers and network rooms varies on a minute
Extension Cord Safety Policy
NATIONAL HIGH MAGNETIC FIELD LABORATORY Operated by Florida State University, University of Florida, Los Alamos National Laboratory Florida State University, 1800 East Paul Dirac Drive, Tallahassee, Florida
NEWTECH PRO 1-2-3 KVA ONLINE UNINTERRUPTIBLE POWER SUPPLY USER MANUAL
NEWTECH PRO 1-2-3 KVA ONLINE UNINTERRUPTIBLE POWER SUPPLY USER MANUAL [email protected] / www.tuncmatik.com Table of Contents 1. Important Safety Warning 2 1-1. Transportation 2 1-2. Preparation 2 1-3.
Cisco Nexus 7000 Series Power Supply Modules
Cisco Nexus 7000 Series Power Supply Modules Product Overview The Cisco Nexus 7000 Series Power Supply Modules (Figures 1 and 2) deliver fault tolerance, high efficiency, load sharing, and hot-swappable
101 BASICS SERIES LEARNING MODULE 3: FUNDAMENTALS OF ELECTRICAL DISTRIBUTION. Cutler-Hammer
101 BASICS SERIES LEARNING MODULE 3: FUNDAMENTALS OF ELECTRICAL DISTRIBUTION Cutler-Hammer WELCOME Welcome to Module 3, Fundamentals of Electrical Distribution. If you have successfully completed Module
Online UPS. PowerWalker VFI 1000R/1U
Online UPS PowerWalker VFI 1000R/1U Manual Uninterruptible Power Supply System Table of Contents 1. Important Safety Warning... 1 1-1. Transportation... 1 1-2. Preparation... 1 1-3. Installation... 1 1-4.
QuickSpecs. HP 480/277 Volt Solutions. Overview
Overview As the quest for efficiency continues it becomes apparent that what worked in the past needs improvement. More and more data center managers are looking at alternate power plans to distribute
Electrical Connection. Provide Proper Electrical Supply. Electrical Requirements. Connecting using the supplied cord and plug
Electrical Connection When installed the range must be electrically grounded in accordance with local codes or; in the absence of local codes with the National Electrical Code ANSI/NFPA 70, latest edition.
Rack Power Distribution
The Rack PDU Selector is located at: www.apc.com/tools/selector/pdu Test drive a metered or switched Rack Power Distribution Rack PDU at testdrive.apc.com 132 Fairgrounds Road West Kingston, RI 02892 Phone:
Packet Power. Data Center Solutions. Packet Power for Data Centers. Benefits. Features. The Packet Power Solution. Data Center Monitoring Made Easy
Data Center Solutions Packet Power for Data Centers Packet Power provides the easiest, most cost-effective way to capture detailed power and temperature information for both single-site and large multi-facility
ZONIT POWER DISTRIBUTION SYSTEM ORDER CATALOG
ZONIT POWER DISTRIBUTION SYSTEM ORDER CATALOG Introduction The Zonit Data Center Power Distribution System (zpds ) offers an ultrareliable, turnkey power distribution system for modern high-availability
USER MANUAL CHARGING STATIONS FOR ELECTRIC VEHICLES
USER MANUAL CHARGING STATIONS FOR ELECTRIC VEHICLES 204.CAxxx 204.CBxxx 204.UBxxx 204.WBxxx MP36289 1 ZP90856-GB-6 INDICE 1 SYSTEM DESCRIPTION... 4 1.1 MODES OF OPERATION... 4 2 USER INTERFACE... 6 2.1
ELECTRICAL INSPECTION BULLETIN (Effective 2000-03-01)
ELECTRICAL INSPECTION BULLETIN (Effective 2000-03-01) Rule 28-900 Standby Generator Installations Due to the increasing number of standby generator installations being established to maintain continuity
QuickSpecs. HP Modular Power Distribution Units (Zero-U/1U Modular PDUs) Overview
Overview HP Modular PDUs have a unique modular architecture designed specifically for data center customers who want to maximize power distribution and space efficiencies in the rack. Modular PDUs consist
Electric Vehicle Charging Station Products EVoReel Charge Cable Management Solutions
Self-Retracts 30 ft. Charge Cable Length Electric Vehicle Charging Station Products EVoReel Charge Cable Management Solutions Safe, Convenient & Clean EV Charging The EVoReel cable management solutions
Product Guide AC Voltage Control Devices. Guide Guide. Popular Variable Transformers and AC Power Supplies. www.stacoenergy.com
Popular Variable Transformers and AC Power Supplies Product Guide AC Voltage Control Devices Guide Guide Your Tailored Power Solutions Provider TM Staco Energy Products Co. has been a leading manufacturer
Replacing an AC Power Cord in a Power Shelf
Replacing an AC Power Cord in a Power Shelf No system shutdown is required to replace one AC power cord in a power shelf. All components in the enclosure continue to receive power from the other power
IEC 309 INTERLOCKS NORTH AMERICAN
IEC 309 INTERLOCKS NORTH AMERICAN SWITCH VERSION with MCB (Circuit Breakers) 20, 30, 60 Amp NEMA 4X Watertight (IP67) Drawing A (See Drawing on Specification Page) 20, 30, 60 Amp Spashproof (IP44) Drawing
Power Commander Power Distribution Units from Wiremold/Legrand offer
Power Commander Power Distribution Units Rack Power Distribution Solutions for IT/Network Environments Power Commander Power Distribution Units from Wiremold/Legrand offer comprehensive power distribution
Protect your home and family with Advanced Technology from Cutler-Hammer
Protect your home and family with Advanced Technology from Cutler-Hammer Residential Home Fire Statistics Annually - over 415,000 Residential Fires Annually - over 40,000 electrical fires over 350 deaths
VIEW. SLX300 SpeakerLinX IP Zone. Amplifier Installation and Setup Guide. AVoIP
VIEW SLX300 SpeakerLinX IP Zone Amplifier Installation and Setup Guide TM AVoIP ClearOne 5225 Wiley Post Way Suite 500 Salt Lake City, UT 84116 Telephone 1.800.283.5936 1.801.974.3760 Tech Sales 1.800.705.2103
Power and Cooling Guidelines for Deploying IT in Colocation Data Centers
Power and Cooling Guidelines for Deploying IT in Colocation Data Centers White Paper 173 Revision 0 by Paul Lin and Victor Avelar Executive summary Some prospective colocation data center tenants view
Guidance on Proper Use of EXTENSION CORDS, POWER STRIPS & SURGE PROTECTORS
Guidance on Proper Use of EXTENSION CORDS, POWER STRIPS & SURGE PROTECTORS The Language Used In This Document Does Not Create An Employment Contract Between The Employee And The Agency. This Document Does
Understanding Emergency Power Off (EPO)
Understanding Emergency Power Off (EPO) White Paper #22 Executive Summary Emergency Power Off (EPO) is the capability to power down a piece of electronic equipment or an entire installation from a single
GUIDE TO THE MAINTENANCE, INSPECTION AND TESTING OF PORTABLE EQUIPMENT (ELECTRICAL APPLIANCES AND TOOLS) IN THE WORKPLACE
GUIDE TO THE MAINTENANCE, INSPECTION AND TESTING OF PORTABLE EQUIPMENT (ELECTRICAL APPLIANCES AND TOOLS) IN THE WORKPLACE ET 215:2008 ELECTRO-TECHNICAL COUNCIL OF IRELAND 2008 Page 1 of 6 Published by
LT Charging Cart for Laptops
Built with Anthro-DNA LT Charging Cart for Laptops Owners Manual This unit has been tested to Underwriters Laboratories U.S. and Canadian (Bi-National) Standard for Safety of Informational Technology Equipment,
12-Volt 10-Amp Regulated Power Supply
22-506.fm Page 1 Friday, August 6, 1999 12:55 PM Cat. No. 22-506 OWNER S MANUAL Please read before using this equipment. 12-Volt 10-Amp Regulated Power Supply 22-506.fm Page 2 Friday, August 6, 1999 12:55
Refer installation of power supplies to qualified service personnel.
AC Power Supply For 5-Slot Housing and 9000 Series Access Carrier Installation Instructions Document Number 9000-A2-GN17-50 August 2000 Before You Begin Both the 5-slot housing and the 9000 Series Access
USER MANUAL Online UPS 1K/2K/3K
USER MANUAL EN Online UPS 1K/2K/3K Uninterruptible Power Supply System Table of Contents 1. Important Safety Warning 2 1.1. Transportation 2 1.2. Preparation 2 1.3. Installation 2 1.4. Operation 2 1.5.
Understanding Power Factor, Crest Factor, and Surge Factor. White Paper #17
Understanding Power Factor, Crest Factor, and Surge Factor White Paper #17 Executive Summary This paper explains the technical terms of Power Factor, Crest Factor, and Surge Factor. The use of these terms
Extollo Communications. Home Electrical Wiring and Cross Phase Coupling Overview
Extollo Communications Home Electrical Wiring and Cross Phase Coupling Overview Table of Contents Introduction... 3 Electrical Wiring in the Typical North American Home... 3 Figure 1. Transformer for a
BLACK BOX. T1/E1 Link Extenders OCTOBER 2007 MT195A-T1 MT196A-E1
BLACK BOX NETWORK SERVICES OCTOBER 2007 MT195A-T1 MT196A-E1 T1/E1 Link Extenders Important This is a Class A device and is intended for use in a light industrial environment. It is not intended nor approved
Square D Clipsal DIN-Rail Four-Channel Auxiliary Input Unit
Square D Clipsal DIN-Rail Four-Channel Auxiliary Input Unit SLCLE5504AUX for Use with Wired C-Bus Networks Instruction Bulletin Retain for future use. Square D Clipsal DIN-Rail Four-Channel Auxiliary Input
A Scalable, Reconfigurable, and Efficient Data Center Power Distribution Architecture
A Scalable, Reconfigurable, and Efficient Data Center Power Distribution Architecture White Paper 129 Revision 1 by Neil Rasmussen > Executive summary Significant improvements in efficiency, power density,
Directory chapter 04
M Directory chapter 04 D-Sub Mixed subminiature D connectors New Page D-Sub mixed connector system general information................... 04.02 Contact arrangements............................................
CURRENT TRANSFORMER MODEL 546 UL1015 #16 AWG LEAD WIRE, STANDARD LENGTH IS 24" 1 X
CURRENT TRANSFORMER MODEL 546 1.10" I.D. PAGE No 1-38 REV 15DEC00 TERMINAL OPTION LEAD WIRE OPTION 1.10 0 1.20 2.55 3.00 3.47 0.18 x 0.31 SLOT ( 2 PLACES) 8-32 BRASS STUD (2 PLACES) UL1015 #16 AWG LEAD
Precisely distribute, monitor, analyze and manage power distribution in your facility to maximize processing capacity and promote power efficiency.
SECTION FOUR Table of Contents Page 69-78 Enclosure Power Distribution Units (PDUs) 70 71 Single-Phase Basic/Smart PDUs 72 3-Phase Basic/Smart PDUs 73 Single- and 3-Phase Switched PDUs 74 PDU Accessories
Power Distribution Considerations for Data Center Racks
Power Distribution Considerations for Data Center Racks Power Distribution Considerations for Data Center Racks Table of Contents 3 Overview 4 At what voltage do you run all the IT equipment? 4 What electrical
5-Slot Housing and FrameSaver 9000 Series Access Carrier AC Power Supply Installation Instructions
TM 5-Slot Housing and FrameSaver 9000 Series Access Carrier AC Power Supply Installation Instructions Document Number 9000-A2-GN17-30 August 1998 Before You Begin Both the 5-slot housing and the FrameSaver
Electrical Resistance Resistance (R)
Electrical Resistance Resistance (R) Any device in a circuit which converts electrical energy into some other form impedes the current. The device which converts electrical energy to heat energy is termed
Common Electrical Hazards in the Workplace Including Arc Flash. Presented by Ken Cohen, PhD, PE & CIH (Ret.)
Common Electrical Hazards in the Workplace Including Arc Flash Presented by Ken Cohen, PhD, PE & CIH (Ret.) 1 What s New In February 1972, OSHA incorporated the 1971 edition of the National Fire Protection
Operation Manual. Trans-Flo
Operation Manual Trans-Flo The TRANS-FLO SYSTEM is a standard-output ballast that can be dimmed on most common theatrical SCR dimming systems. The modular design of the TRANS-FLO SYSTEM streamlines set
Emerson Network Power Rack PDU Systems
AC Power For Business-Critical Continuity Emerson Network Power Rack PDU Systems Product Selection Guide - North American Models TABLE OF CONTENTS 1.0 EMERSON NETWORK POWER RACK PDU SYSTEMS..............................1
READ THIS MANUAL BEFORE PROCEEDING WITH THE INSTALLATION. FAILURE TO FOLLOW THE INSTALLATION INSTRUCTIONS MAY VOID YOUR WARRANTY!
READ THIS MANUAL BEFORE PROCEEDING WITH THE INSTALLATION. FAILURE TO FOLLOW THE INSTALLATION INSTRUCTIONS MAY VOID YOUR WARRANTY! The main power to any existing system must be disconnected prior to the
Energy Communication Unit (ECU)
Altenergy Power System Energy Communication Unit (ECU) Installation and User Manual (For ECU-3 V3.8) ALTENERGY POWER SYSTEM INC. All rights reserved TABLE OF CONTENTS 1.0 Introduction... 2 2.0 Installation...
Packet Power. Data Center Solutions. Packet Power. Packet Power for Data Centers. Benefits. Features. The Packet Power Solution
Data Center Solutions for Data Centers provides the easiest, most cost-effective way to capture detailed power and temperature information for both single-site and large multi-facility operations. Gain
Eaton epdu Data Center Product Catalog
Power distribution solutions Eaton epdu Data Center Product Catalog Switch N to Eaton. 2 eaton corporation Enclosure Power Distribution Units Table of contents Product Line Overview... 4 Choosing epdu
USER MANUAL Online UPS 1K/2K/3K Rack
USER MANUAL EN Online UPS 1K/2K/3K Rack Uninterruptible Power Supply System Table of Contents 1. Important Safety Warning 2 1-1. Transportation 2 1-2. Preparation 2 1-3. Installation 2 1-4. Operation 2
APC Step-Down Transformer. User s Manual
APC Step-Down Transformer Models: AP9621, SURT005, SURT006, SUTF3, SYTF2, SYTF2J, SYTF3 and SYTF3J User s Manual English 990-7820D, July 2003 TABLE OF CONTENTS APC Contact Numbers and Support Visit the
Low Voltage Transformers Sealed, General Purpose, Dry Type
Low Voltage Transformers Sealed, General Purpose, Dry Type Catalog 7400CT9601R4/08 08 Class 7400 CONTENTS Description..............................................Page Introduction.................................................
Server Technology, Inc.
Server Technology, Inc. Power Efficiency Gains by Deploying 415 VAC Power Distribution in North American Data Centers White Paper STI-100-008 2009-April-07 Headquarters Server Technology, Inc. 1040 Sandhill
How To Protect A Motor From Overcurrent
Phase ailure elays Type PS and PD Class 8430 Catalog 04 CONTENTS Description.....................................................Page Product Description and Definitions......................................
Electrical Grounding. Appendix C
Appendix C Electrical Grounding Low-Voltage Equipment Grounding The most frequently cited Office of Safety and Health Administration (OSHA) electrical violation is improper occupational grounding of equipment
Model Number Electrical Compatibility Module Connector Type. M250-60-2LL-S22 60 cell PV module MC-4 Type 2 Locking
TECHNICAL BRIEF M250 Microinverter System Installation Planning The M250 Microinverter The Enphase M250 Microinverter is a powerful and efficient grid-tied microinverter. It is compatible with most 60-cell
Energy Communication Unit (ECU)
Altenergy Power System Energy Communication Unit (ECU) Installation and User Manual (For ECU-3 V3.7) Version:3.0 ALTENERGY POWER SYSTEM INC. All rights reserved TABLE OF CONTENTS 1.0 Introduction... 2
Advantium 2 Plus Alarm
ADI 9510-B Advantium 2 Plus Alarm INSTALLATION AND OPERATING INSTRUCTIONS Carefully Read These Instructions Before Operating Carefully Read These Controls Corporation of America 1501 Harpers Road Virginia
Data Center Power Overload Protection: Circuit breakers and branch circuit protection for data centers
Data Center Power Overload Protection: Circuit breakers and branch circuit protection for data centers 2009, Raritan Inc. Introduction Over the past few years, average power consumption per server has
Industrial-Grade UPS System Heavy-duty power protection for harsh industrial environments
Industrial-Grade UPS System Heavy-duty power protection for harsh industrial environments Model #: SM2000RMX Heavy-duty, industrial-grade metal housings Shock and vibration rated to MIL-STD-810D 19 inch
ED1259R5 Updated April 2011 For latest specs visit www.legrand.us/wiremold
Rack Power Distribution Solutions for IT/Network Environments Wiremold Power Commander Power Distribution Units offer comprehensive power distribution solutions for IT environments from networking solutions
User Manual 1K/2K/3K Online UPS
User Manual 1K/2K/3K Online UPS Uninterruptible Power Supply System Table of Contents 1. Important Safety Warning... 1 1-1. Transportation... 1 1-2. Preparation... 1 1-3. Installation... 1 1-4. Operation...
LIEBERT VNSA Installation Sheet
LIEBERT VNSA Installation Sheet Description The Liebert vnsa network switch is designed for connecting multiple Ethernet-ready devices and comes in various models. The unit may have: A Liebert icom display
Electrical Plan Design
CHAPTER 1 Electrical Plan Design Chapter Outline Chapter Outline Introduction The Design Process Understanding the Project Scope Defining Parts of the Electrical Plan Determining Applicable Standards Creating
10000HXL31/15000HXL31/20000HXL31
Table of Contents www.eaton.com/dxups USER MANUAL ON LINE UPS 10000HXL31/15000HXL31/20000HXL31 Uninterruptible Power Supply Table of Contents 1. Brief introduction 1.1 System and model description---------------------------------------------------------------------1
Model #: SMART2200VS. 2200VA / 2.2kVA line interactive tower UPS. Maintains 120V nominal output over an input range of 79 to 147V
SmartPro VS Tower UPS System Intelligent, line-interactive power management system Model #: SMART2200VS 2200VA / 2.2kVA line interactive tower UPS Maintains 120V nominal output over an input range of 79
2XWSXWFKDQQHOV 3KDVH &+ CH 2 &+ CH 4 &+ CH 6 L1 X X L2 X X L3 X X
INSTALLATION INSTRUCTIONS ENGLISH Version 1 1 January 2004 EUROLIGHT LD6230 IMPORTANT SAFETY INSTRUCTIONS DETAILED SAFETY INSTRUCTIONS: 1) Read these instructions 2) Keep these instructions 3) Heed all
Server Technology Inc.
Server Technology Inc. Alternating Phase Power Distribution at the Data Center Rack PDU White Paper STI-100-012 2013-April-18 By Steve Hammond, Product Manager, Server Technology Headquarters Server Technology,
SmartOnline 200-240V 6kVA 4.2kW On-Line Double-Conversion UPS, Extended Run, SNMP, Webcard, 6U Rack/Tower, DB9 Serial, Hardwire
SmartOnline 200-240V 6kVA 4.2kW On-Line Double-Conversion UPS, Extended Run, SNMP, Webcard, 6U Rack/Tower, DB9 Serial, Hardwire MODEL NUMBER: SU6000RT3UHV Highlights 6000VA / 6kVA / 4200W on-line double-conversion
AMPSEAL* Automotive Plug Connector and Header Assembly
AMPSEAL* Automotive Plug Connector and Header Assembly Application Specification 24 SEP 97 Rev E All dimensions are given in millimeters unless otherwise specified. All dimensional tolerances are +0.2
LTR Series Uninterruptible Power Systems 700 VA - 2.1 KVA. General Specification
08/17/12 Rev2 LTR Series General Specification 700 VA to 2.1 KVA 1.0 General LTR Series Uninterruptible Power Systems 700 VA - 2.1 KVA General Specification This specification describes the features and
HPS Universal. Single and Three Phase Potted. Buck-Boost Transformers. Buck-Boost Applications & Standard Specification... 80
Buck-Boost Transformers Single and Three Phase Potted Buck-Boost Transformers Buck-Boost Applications & Standard Specification... 80 Selecting Buck-Boost Transformers... 81 Single Phase Selection Tables...
Enphase Microinverters and Ungrounded Renewable Energy Systems: Canadian Electrical Code Compliance
WHITE PAPER Enphase Microinverters and Ungrounded Renewable Energy Systems: Canadian Electrical Code Compliance Overview Enphase has developed a new microinverter family that includes the M250 and new
St Peter s College ELECTRICAL SAFETY. B. University Safety Office Policy Statement S4/10, Working safely with Electricity.
St Peter s College ELECTRICAL SAFETY References: A. Peninsula Business Services Guidance Note 4-1, Electrical Safety. B. University Safety Office Policy Statement S4/10, Working safely with Electricity.
GENERAL ELECTRICAL REQUIREMENTS
GENERAL ELECTRICAL REQUIREMENTS RECEPTACLE SPACING Within 6-feet of the edge of any door HABITABLE Not more than 12-feet apart along wall ROOMS: At all wall spaces 24 or more wide Within 24 of edge of
EVlink Electric Vehicle Charging Solutions Powering the Future of Sustainable Mobility
EVlink Electric Vehicle Charging Solutions Powering the Future of Sustainable Mobility Catalog 2800CT1001 2014 Class 2800 CONTENTS Description............................................ Page 2 Outdoor
USER GUIDE TURBOCORD TM PORTABLE CHARGER 120V/240V: DUAL VOLTAGE. AeroVironment EV Solutions
USER GUIDE TURBOCORD TM PORTABLE CHARGER 120V/240V: DUAL VOLTAGE AeroVironment EV Solutions 2013 AeroVironment, Inc. All rights reserved. AeroVironment, EV Solutions, and the AeroVironment logo are trademarks
HP UPS R1500 Generation 3
HP UPS R1500 Generation 3 Installation Instructions Part Number 650952-001 NOTE: The rating label on the device provides the class (A or B) of the equipment. Class B devices have a Federal Communications
Vilter motor starter solutions The NEW industry standard in motor starter packages
Vilter motor starter solutions The NEW industry standard in motor starter packages Electrical safety by design Built to Underwriters Laboratory (UL) 508A UL Standard for Safety for Industrial Control Panels.
SmartOnline 200-240V 5kVA 4.5kW On-Line Double-Conversion UPS, Extended Run, SNMP, Webcard, 4U Rack/Tower, USB, DB9 Serial
SmartOnline 200-240V 5kVA 4.5kW On-Line Double-Conversion UPS, Extended Run, SNMP, Webcard, 4U Rack/Tower, USB, DB9 Serial MODEL NUMBER: SU5000RT4UHV Description Tripp Lite SU5000RT4UHV 5000VA / 5kVA /
ICON Server box installation manual Rev. 1.1
ICON Server box installation manual Rev. 1.1 Contents 1.0 About this manual... 3 2.0 Intended use... 3 2.1 European WEEE directive... 3 3.0 Installation and service instructions... 4 Server box overview...
Electrical Wiring Methods, Components and Equipment for General Use. Approved for Public Release; Further Dissemination Unlimited
Electrical Wiring Methods, Components and Equipment for General Use Approved for Public Release; Further Dissemination Unlimited At the completion of this unit you shall be able to: 1. Utilize section
October Safety Subject
October Safety Subject Electrical Hazards All electrical equipment should be kept in good repair. Replace defective equipment or have it repaired by a qualified person. Watch for wiring on appliances that
CTO Configuration Guide. Eaton Ferrups Ferrups 60Hz RM Series
CTO Configuration Guide Eaton Ferrups Ferrups 60Hz RM Series FER5GDE July,, 203 Table of Contents Ferrups CTO Worksheet..2 Ferrups 60Hz Rackmount Series Quick Reference Sheet.. 3 Ferrups CTO Details FES.4kVA...4k-